Instrumentation-Cables Updated
Instrumentation-Cables Updated
1
Offshore Instrumentation Cables
Halogen-free, fire-resistant, flame retardant, mud-resistant cable for use on board ships, offshore units and fixed
installations for instrumentation, communication, control and alarm systems. For emergency and critical systems
requiring fire resistance.
Application Standards applied
Fixed installation for instrumentation, communication, control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX (Zone 0, 1 & 2) and safe areas,
emergency and critical systems where requirement for fire IEC 60228 class 2 - Conductor
resistance exists. IEC 60092-360 - Insulation
BFOU(i) M 250V for installation in areas exposed to MUD and IEC 60092-360 - Sheath
drilling/cleaning fluids. Meets the Oil & Mud resistance IEC 60332-1-2 - Flame Retardant
requirement in NEK TS 606:2016. IEC 60332-3-22 - Flame Retardant
IEC 60331-1, -2, -21 - Fire Resistant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated conductors
Lay up / Shielding Individually shielded pairs/triples/quads are laid up in concentric
layers and wrapped with a PETP tape.
Inner covering F Flame retardant and halogen-free extruded compound
Tape over inner covering PET tape
Armour/screen O Tinned annealed copper wire braid
Tape over armour/screen PET tape
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> BFOU(I) M
250V S3/S7/S103 16 PAIR 0,75 mm2 FLEX - FLAME IEC 60092-376
IEC 60331-1*) or IEC 60331-2*)
IEC 60331-21**) IEC 60332-3-22 Production no. <Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm
**) IEC 60331-21 also at enhanced temperature 1000°C for 180 minutes
2
Offshore Instrumentation Cables
1 2 0.75 1.1 0.6 1.1 7.5 ± 0.5 0.2 4.5 1.1 10.5 ±0.8 198 65 8000073 8002608
1 4 0.75 1.1 0.6 1.1 8.5 ± 0.5 0.2 4.5 1.2 11.5 ± 0.8 240 78 on request on request
2 2 0.75 1.1 0.6 1.1 10.5 ±0.8 0.3 10.2 1.3 14.5 ± 0.8 348 141 8000149 8001300
4 2 0.75 1.1 0.6 1.1 12.5 ±0.8 0.3 11.9 1.4 16 ± 0.8 470 201 8001713 8001531
8 2 0.75 1.1 0.6 1.1 17 ± 0.8 0.3 15.3 1.6 21 ± 1 749 321 8000327 8001304
12 2 0.75 1.1 0.6 1.1 19.5 ±0.8 0.3 17.8 1.7 24 ± 1 976 432 8000015 8000019
16 2 0.75 1.1 0.6 1.5 23 ± 1 0.3 20.4 1.8 27 ± 1 1274 546 8000031 8001753
24 2 0.75 1.1 0.6 1.5 27.5 ± 1 0.4 31.7 2.1 33 ± 1.5 1840 832 8001297 8000121
1 3 0.75 1.1 0.6 1.1 8 ± 0.5 0.2 4.5 1.1 11 ± 0.8 213 71 8000092 8001751
2 3 0.75 1.1 0.6 1.1 12 ± 0.8 0.3 10.2 1.4 15.5 ± 0.8 395 154 on request 8030341
4 3 0.75 1.1 0.6 1.1 14 ± 0.8 0.3 11.9 1.4 17.5 ± 0.8 544 226 8001797 8001754
8 3 0.75 1.1 0.6 1.1 18.5 ±0.8 0.3 17.8 1.7 23 ± 1 947 396 8001915 8001794
12 3 0.75 1.1 0.6 1.1 22 ± 1 0.3 20.4 1.8 26.5 ± 1 1206 533 on request 8001530
16 3 0.75 1.1 0.6 1.5 25.5 ± 1 0.3 22.9 1.9 30 ± 1.5 1588 670 8029469 on request
24 3 0.75 1.1 0.6 1.5 31 ± 1.5 0.4 36.2 2.2 36.5 ± 1.5 2290 1024 on request on request
1 2 1.5 1.55 0.7 1.1 9 ± 0.5 0.2 4.5 1.2 12 ± 0.8 246 81 8000081 8002525
2 2 1.5 1.55 0.7 1.1 13 ± 0.8 0.3 11.9 1.4 16.5 ± 0.8 448 190 8002526 8000168
4 2 1.5 1.55 0.7 1.1 15 ± 0.8 0.3 13.6 1.5 19 ± 0.8 631 282 8002018 8000288
8 2 1.5 1.55 0.7 1.1 20.5 ± 1 0.3 17.8 1.7 25 ± 1 1034 475 8000341 8000344
12 2 1.5 1.55 0.7 1.1 24.5 ± 1 0.3 20.4 1.9 29 ± 1 1380 654 8000024 8001292
16 2 1.5 1.55 0.7 1.5 28 ± 1 0.3 22.9 2 33 ± 1.5 1821 833 8039011 8001834
24 2 1.5 1.55 0.7 1.5 34.5 ±1.5 0.4 40.7 2.3 40 ± 2 2683 1306 8063771 8000126
32 2 1.5 1.55 0.7 1.5 38 ± 1.5 0.4 45.2 2.5 44 ± 2 3313 1654 on request on request
1 3 1.5 1.55 0.7 1.1 9.5 ± 0.5 0.2 5.3 1.2 12.5 ± 0.8 280 101 8000099 8001295
2 3 1.5 1.55 0.7 1.1 14 ± 0.8 0.3 11.9 1.5 18 ± 0.8 525 217 on request 8003592
4 3 1.5 1.55 0.7 1.1 16.5 ±0.8 0.3 15.3 1.6 20.5 ± 1 770 351 8000297 8002409
8 3 1.5 1.55 0.7 1.1 22.5 ± 1 0.3 20.4 1.8 27 ± 1 1314 604 8001964 8001306
12 3 1.5 1.55 0.7 1.1 27 ± 1 0.3 22.9 2 31.5 ± 1.5 1747 839 8000029 8003334
16 3 1.5 1.55 0.9 1.5 34 ± 1.5 0.4 36.2 2.2 39.5 ± 1.5 2663 1168 8029470 on request
24 3 1.5 1.55 0.9 1.5 42 ± 2 0.4 45.2 2.5 48 ± 2 3713 1668 on request 8000129
1 2 2.5 1.9 0.7 1.1 9.5 ± 0.5 0.2 5.3 1.2 12.5 ± 0.8 286 106 on request 8001349
2 2 2.5 1.9 0.7 1.1 14 ± 0.8 0.3 11.9 1.5 18 ± 0.8 519 226 on request 8052977
4 2 2.5 1.9 0.7 1.1 16.5 ± 0.3 15.3 1.6 20.5 ± 1 761 368 on request on request
0.8
8 2 2.5 1.9 0.7 1.1 22.5 ± 1 0.3 20.4 1.8 27 ± 1 1269 639 on request on request
12 2 2.5 1.9 0.7 1.5 27.5 ± 1 0.3 22.9 2 32.5 ± 1.5 1806 889 on request 8002042
16 2 2.5 1.9 0.9 1.5 35 ± 1.5 0.4 36.2 2.2 40 ± 2 2603 1240 on request on request
1 3 2.5 1.9 0.7 1.1 10 ± 0.8 0.2 6.0 1.2 13 ± 0.8 329 133 on request 8042205
2 3 2.5 1.9 0.7 1.1 15.5 ±0.8 0.3 13.6 1.5 19.5 ± 0.8 621 282 on request on request
4 3 2.5 1.9 0.7 1.1 18.5 ±0.8 0.3 15.3 1.6 22.5 ± 1 920 456 on request on request
8 3 2.5 1.9 0.7 1.3 25 ± 1 0.3 22.9 2 29.5 ± 1 1648 824 on request on request
16 3 2.5 1.9 0.9 1.5 38 ± 1.5 0.40 40.7 2.4 43.5 ± 2 3319 1612 on request on request
3
Offshore Instrumentation Cables
Installation recommendations
Minimum Bending Radius Minimum Bending Radius Maximum Tensile Load Minimum Installation
during Installation Fixed Installed During Installation Temperature
50 N x total
8xD 6xD cross section (mm²) of -20°C
conductors
4
Offshore Instrumentation Cables
Construction
5
Offshore Instrumentation Cables
6
Offshore Instrumentation Cables
Halogen-free, fire-resistant, flame retardant, mud-resistant cable for use on board ships, offshore units and fixed
installations for instrumentation, communication, control and alarm systems. For emergency and critical systems
requiring fire resistance.
Application Standards applied
Fixed installation for instrumentation, communication, control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX (Zone 0, 1 & 2) and safe areas,
emergency and critical systems where requirement for fire IEC 60228 class 2 - Conductor
resistance exists. IEC 60092-360 - Insulation
BFOU(i) M 250V for installation in areas exposed to MUD and IEC 60092-360 - Sheath
drilling/cleaning fluids. Meets the Oil & Mud resistance IEC 60332-1-2 - Flame Retardant
requirement in NEK TS 606:2016. IEC 60332-3-22 - Flame Retardant
IEC 60331-1, -2, -21 - Fire Resistant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated conductors
Inner covering F Flame retardant and halogen-free extruded compound
Tape over inner covering PET tape
Armour/screen O Tinned annealed copper wire braid
Tape over armour/screen PET tape
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> BFOU(C) M
250V S4/S8/S104 4 PAIR 0,75 mm2 FLEX - FLAME IEC 60092-376
IEC 60331-1*) or IEC 60331-2*) IEC 60331-21**) IEC 60332-3-22
Production no. <Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm
**) IEC 60331-21 also at enhanced temperature 1000°C for 180 minutes
7
Offshore Instrumentation Cables
2 2 0.75 1.1 0.6 1.1 10.5 ±0.8 0.3 8.5 1.3 14 ± 0.8 323 120 8002509 8000153
4 2 0.75 1.1 0.6 1.1 12 ± 0.8 0.3 10.2 1.4 16 ± 0.8 424 162 8002185 8000278
8 2 0.75 1.1 0.6 1.1 16 ± 0.8 0.3 13.6 1.5 20 ± 1 656 248 8000326 8000332
12 2 0.75 1.1 0.6 1.1 18.5 ±0.8 0.3 15.3 1.6 22.5 ± 1 828 321 8052970 8000018
16 2 0.75 1.1 0.6 1.5 21 ± 1 0.3 17.8 1.7 25 ± 1 1068 393 8038840 8001755
24 2 0.75 1.1 0.6 1.5 27.5 ± 1 0.3 22.9 2 30 ± 1.5 1469 546 on request 8000120
2 3 0.75 1.1 0.6 1.1 12 ± 0.8 0.3 10.2 1.3 15.5 ± 0.8 391 150 on request 8002523
4 3 0.75 1.1 0.6 1.1 14 ± 0.8 0.3 11.9 1.4 17.5 ± 0.8 521 204 on request 8000294
8 3 0.75 1.1 0.6 1.1 19 ± 0.8 0.3 15.3 1.6 23 ± 1 856 316 on request 8001756
12 3 0.75 1.1 0.6 1.1 21.5 ± 1 0.3 17.8 1.8 26 ± 1 1080 420 on request on request
16 3 0.75 1.1 0.6 1.5 24 ± 1 0.3 20.4 1.9 28.5 ± 1 1404 521 on request on request
24 3 0.75 1.1 0.6 1.5 29 ± 1 0.4 36.2 2.1 34.5 ± 1.5 2019 830 on request on request
2 2 1.5 1.55 0.7 1.1 12.5 ±0.8 0.3 10.2 1.4 16.5 ± 0.8 420 166 8000162 8009346
4 2 1.5 1.55 0.7 1.1 14.5 ±0.8 0.3 11.9 1.4 18.5 ± 0.8 562 222 8058145 8000286
8 2 1.5 1.55 0.7 1.1 20 ± 1 0.3 17.8 1.7 24 ± 1 937 398 8000339 8000343
12 2 1.5 1.55 0.7 1.1 23 ± 1 0.3 20.4 1.8 27 ± 1 1203 528 on request on request
16 2 1.5 1.55 0.7 1.5 25.5 ± 1 0.3 22.9 1.9 30 ± 1.5 1559 656 on request 8000044
24 2 1.5 1.55 0.7 1.5 31 ± 1.5 0.4 36.2 2.2 36.5 ± 1.5 2253 995 8000125 on request
2 3 1.5 1.55 0.7 1.1 14.5 ±0.8 0.3 11.9 1.4 18 ± 0.8 509 197 on request on request
4 3 1.5 1.55 0.7 1.1 16.5 ±0.8 0.3 13.6 1.5 20.5 ± 1 715 289 on request 8001752
8 3 1.5 1.55 0.7 1.1 22.5 ± 1 0.3 20.4 1.8 27 ± 1 1231 528 on request 8000352
12 3 1.5 1.55 0.7 1.1 26.5 ± 1 0.3 22.9 1.9 31 ± 1.5 1580 711 on request 8087252
16 3 1.5 1.55 0.7 1.5 29.5 ± 1 0.4 36.2 2.1 34.5 ± 1.5 2192 996 8000049 8000050
24 3 1.5 1.55 0.7 1.5 36 ± 1.5 0.4 40.7 2.4 41.5 ± 2 2988 1357 on request on request
2 2 2.5 1.9 0.7 1.1 14 ± 0.8 0.3 11.9 1.4 17.5 ± 0.8 493 214 on request 8069857
4 2 2.5 1.9 0.7 1.1 16 ± 0.8 0.3 13.6 1.5 20 ± 1 688 301 on request on request
8 2 2.5 1.9 0.7 1.1 21.5 ± 1 0.3 17.8 1.8 26 ± 1 1125 520 on request on request
12 2 2.5 1.9 0.7 1.5 26 ± 1 0.3 22.9 1.9 30.5 ± 1.5 1594 739 on request 8050517
16 2 2.5 1.9 0.9 1.5 31.5 ±1.5 0.4 31.7 2.1 36.5 ± 1.5 2240 998 on request 8062712
24 2 2.5 1.9 0.9 1.5 38 ± 1.5 0.4 40.7 2.4 43.5 ± 2 3117 1414 on request on request
4 3 2.5 1.9 0.7 1.1 18.5 ±0.8 0.3 15.3 1.6 22.5 ± 1 881 415 on request on request
8 3 2.5 1.9 0.7 1.1 25.5 ± 1 0.3 20.4 1.9 30 ± 1.5 1523 713 on request on request
12 3 2.5 1.9 0.7 1.5 30 ± 1.5 0.4 31.7 2.1 35 ± 1.5 2200 1083 on request on request
16 3 2.5 1.9 0.9 1.5 35.5 ±1.5 0.4 36.2 2.3 41.5 ± 2 3012 1374 on request on request
8
Offshore Instrumentation Cables
Installation recommendations
Minimum Bending Radius Minimum Bending Radius Maximum Tensile Load Minimum Installation
during Installation Fixed Installed During Installation Temperature
50 N x total
8xD 6xD cross section (mm²) of -20°C
conductors
9
Offshore Instrumentation Cables
Halogen-free, fire-resistant, flame retardant, mud-resistant cable for use on board ships, offshore units and fixed
installations for instrumentation, communication, control and alarm systems. For emergency and critical systems
requiring fire resistance.
Application Standards applied
Fixed installation for instrumentation, communication, control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX (Zone 0, 1 & 2) and safe areas,
emergency and critical systems where requirement for fire IEC 60228 class 2 - Conductor
resistance exists. IEC 60092-360 - Insulation
RFOU(i) M 250V for installation in areas exposed to MUD and IEC 60092-360 - Sheath
drilling/cleaning fluids. Meets the Oil & Mud resistance IEC 60332-1-2 - Flame Retardant
requirement in NEK TS 606:2016. IEC 60332-3-22 - Flame Retardant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated conductors
Lay up / Shielding Individually shielded pairs/triples/quads are laid up in concentric
layers and wrapped with a PETP tape.
Inner covering F Flame retardant and halogen-free extruded compound
Tape over inner covering PET tape
Armour/screen O Tinned annealed copper wire braid
Tape over armour/screen PET tape
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> RFOU(i) M
250V S1/S5/S101 4 PAIR 0,75 mm2 IEC 60092-376 IEC 60332-3-22
Production no.<Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm
**) IEC 60331-21 also at enhanced temperature 1000°C for 180 minutes
10
Offshore Instrumentation Cables
1 2 0.75 1.1 0.6 1.1 6.5 ± 0.5 0.2 3.8 1.1 9.5 ± 0.5 176 58 8000074 8000077
2 2 0.75 1.1 0.6 1.1 9.5 ± 0.5 0.2 5.3 1.2 12.5 ± 0.8 262 95 8001774 8000157
4 2 0.75 1.1 0.6 1.1 11 ± 0.8 0.3 10.2 1.3 14.5 ± 0.8 408 185 8000277 8000281
8 2 0.75 1.1 0.6 1.1 14.5±0.8 0.3 13.6 1.5 18.5 ±0.8 653 304 8001476 8000334
12 2 0.75 1.1 0.6 1.1 17 ± 0.8 0.3 15.3 1.6 21 ± 1 841 407 8001671 8002320
16 2 0.75 1.1 0.6 1.5 19.5 ±0.8 0.3 17.8 1.7 24 ± 1 1107 518 8000034 on request
24 2 0.75 1.1 0.6 1.5 24 ± 1 0.3 20.4 1.9 28.5 ± 1 1502 716 8001487 8001547
1 3 0.75 1.1 0.6 1.1 7 ± 0.5 0.2 3.8 1.1 10 ± 0.8 188 64 on request 8000095
2 3 0.75 1.1 0.6 1.1 10.5 ± 0.3 8.5 1.3 14 ± 0.8 346 142 on request on request
0.8
4 3 0.75 1.1 0.6 1.1 12 ± 0.8 0.3 10.2 1.4 16 ± 0.8 479 212 8000293 on request
8 3 0.75 1.1 0.6 1.1 16 ± 0.8 0.3 15.3 1.6 20 ± 1 777 371 on request on request
16 3 0.75 1.1 0.6 1.5 22 ± 1 0.3 20.4 1.8 26.5 ± 1 1365 644 on request 8000047
24 3 0.75 1.1 0.6 1.5 27 ± 1 0.3 25.4 2 32 ± 1.5 1899 917 on request on request
1 2 1.5 1.55 0.7 1.1 8 ± 0.5 0.2 4.5 1.1 11 ± 0.8 225 81 on request 8001560
2 2 1.5 1.55 0.7 1.1 11.5 ± 0.3 10.2 1.3 15 ± 0.8 399 174 on request 8000170
0.8
4 2 1.5 1.55 0.7 1.1 13.5 ±0.8 0.3 11.9 1.4 17.5 ± 0.8 563 265 on request 8000292
8 2 1.5 1.55 0.7 1.1 18.5 ±0.8 0.3 15.3 1.6 22.5 ± 1 920 451 on request 8000347
12 2 1.5 1.55 0.7 1.1 21.5 ± 1 0.3 17.8 1.8 26 ± 1 1239 631 8000025 8001353
16 2 1.5 1.55 0.7 1.5 25 ± 1 0.3 20.4 1.9 29.5 ± 1 1634 803 8033109 on request
24 2 1.5 1.55 0.7 1.5 30.5±1.5 0.4 36.2 2.2 36 ± 1.5 2422 1262 8003023 on request
1 3 1.5 1.55 0.7 1.1 8.5 ± 0.5 0.2 4.5 1.2 11.5 ± 0.8 254 94 on request 8002515
2 3 1.5 1.55 0.7 1.1 13 ± 0.8 0.3 11.9 1.4 16.5 ± 0.8 479 215 on request on request
4 3 1.5 1.55 0.7 1.1 15 ± 0.8 0.3 13.6 1.5 19 ± 0.8 691 332 on request on request
8 3 1.5 1.55 0.7 1.1 20 ± 1 0.3 17.8 1.7 24 ± 1 1139 578 on request on request
24 3 1.5 1.55 0.7 1.5 34 ± 1.5 0.4 40.7 2.3 39.5 ± 1.5 3033 1613 on request on request
1 2 2.5 1.9 0.7 1.1 8.5 ± 0.5 0.2 4.5 1.2 12 ± 0.8 263 99 on request on request
2 2 2.5 1.9 0.7 1.1 12.5 ±0.8 0.3 11.9 1.4 16.5 ± 0.8 479 225 on request on request
4 2 2.5 1.9 0.7 1.1 15 ± 0.8 0.3 13.6 1.5 19 ± 1 693 351 on request on request
1 3 2.5 1.9 0.7 1.1 9.5 ± 0.5 0.2 5.3 1.2 12.5 ± 0.8 304 126 on request on request
11
Offshore Instrumentation Cables
Installation recommendations
Minimum Bending Radius Minimum Bending Radius Maximum Tensile Load Minimum Installation
during Installation Fixed Installed During Installation Temperature
50 N x total
8xD 6xD cross section (mm²) of -20°C
conductors
12
Offshore Instrumentation Cables
Halogen-free, flame retardant and mud-resistant cable for use on board ships, offshore units and fixed installations
for instrumentation, communication, and control and alarm systems.
Application Standards applied
Fixed installation for instrumentation, communication, Control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX (Zone 0, 1 & 2)- and safe areas. IEC 60228 class 2 - Conductor
RFOU(c) M 250V for installation in areas exposed to MUD and IEC 60092-360 - Insulation
IEC 60092-360 - Sheath
drilling/cleaning fluids. Meets the Oil & Mud resistance IEC 60332-1-2 - Flame Retardant
requirement in NEK TS 606:2016. IEC 60332-3-22 - Flame Retardant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated conductors
Inner covering F Flame retardant and halogen-free extruded compound
Tape over inner covering PET tape
Armour/screen O Tinned annealed copper wire braid
Tape over armour/screen PET tape
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> RFOU(c) M
250V S2/S6/S102 8 PAIR 0,75 mm2 IEC 60092-376 IEC 60332-3-22
Production no.<Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
13
Offshore Instrumentation Cables
2 2 0.75 1.1 0.6 1.1 9.5 ± 0.5 0.2 5.3 1.2 12.5 ± 0.8 258 89 8000150 8000155
4 2 0.75 1.1 0.6 1.1 11 ± 0.8 0.3 10.2 1.3 14.5 ± 0.8 382 161 8000275 8029964
8 2 0.75 1.1 0.6 1.1 14.5 ±0.8 0.3 11.9 1.4 18 ± 0.8 566 230 8000329 8029975
12 2 0.75 1.1 0.6 1.1 16.5 ±0.8 0.3 13.6 1.5 20.5 ± 1 712 299 on request on request
16 2 0.75 1.1 0.6 1.5 18.5 ±0.8 0.3 15.3 1.6 22.5 ± 1 911 366 8000033 8000037
24 2 0.75 1.1 0.6 1.5 22.5 ± 1 0.3 20.4 1.8 27 ± 1 1247 518 8023352 on request
2 3 0.75 1.1 0.6 1.1 10.5 ± 0.3 8.5 1.3 14 ± 0.8 335 132 on request 8000171
0.8
4 3 0.75 1.1 0.6 1.1 12 ± 0.8 0.3 10.2 1.3 15.5 ± 0.8 446 188 on request on request
8 3 0.75 1.1 0.6 1.1 16 ± 0.8 0.3 13.6 1.5 20 ± 1 698 298 8000350 on request
2 2 1.5 1.55 0.7 1.1 11.5 ±0.8 0.3 10.2 1.3 15 ± 0.8 389 164 on request 8000169
4 2 1.5 1.55 0.7 1.1 13.5 ±0.8 0.3 11.9 1.4 17 ± 0.8 524 233 8079985 8000291
8 2 1.5 1.55 0.7 1.1 18 ± 0.8 0.3 15.3 1.6 22 ± 1 834 372 8000342 8000346
12 2 1.5 1.55 0.7 1.1 21 ± 1 0.3 17.8 1.7 25 ± 1 1080 502 on request on request
16 2 1.5 1.55 0.7 1.5 23.5 ± 1 0.3 20.4 1.8 28 ± 1 1400 630 on request 8000046
24 2 1.5 1.55 0.7 1.5 28 ± 1 0.3 25.4 2.1 33 ± 1.5 1928 887 on request on request
2 3 1.5 1.55 0.7 1.1 12.5 ± 0.3 10.2 1.4 16.5 ± 0.8 453 191 on request on request
0.8
on request on request
2 2 2.5 1.9 0.7 1.1 12.5 ± 0.3 10.2 1.4 16.5 ± 0.8 452 198 on request on request
0.8
4 2 2.5 1.9 0.7 1.1 15 ± 0.8 0.3 11.9 1.4 18.5 ± 0.8 623 284 on request on request
8 2 2.5 1.9 0.7 1.1 20 ± 1 0.3 17.8 1.7 24.5 ± 1 1061 521 on request on request
12 2 2.5 1.9 0.7 1.5 24 ± 1 0.3 20.4 1.8 28.5 ± 1.5 1459 713 on request on request
Installation recommendations
Minimum Bending Radius Minimum Bending Radius Maximum Tensile Load Minimum Installation
during Installation Fixed Installed During Installation Temperature
50 N x total
8xD 6xD cross section (mm²) of -20°C
conductors
14
Offshore Instrumentation Cables
Halogen-free, fire-resistant, flame retardant, mud-resistant cable for use on board ships, offshore units and fixed
installations for instrumentation, communication, control and alarm systems. For emergency and critical systems
requiring fire resistance.
Application Standards applied
Fixed installation for instrumentation, communication, control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX-(Zone 2) and safe areas, IEC 60228 class 2 - Conductor
emergency and critical systems where requirement for fire IEC 60092-360 - Insulation
IEC 60092-360 - Sheath
resistance exists. IEC 60332-1-2 - Flame Retardant
BU(i) M 250V meets the Oil & Mud resistance requirements in IEC 60332-3-22 - Flame Retardant
IEC 60331-1, -2, -21 - Fire Resistant
NEK TS 606:2016. IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated conductors
Lay up / Shielding Individually shielded pairs/triples/quads are laid up in concentric
layers and wrapped with a PETP tape.
Inner covering No inner covering. (Additional tapes may be applied)
Armour/screen No armour
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> BU(i)
M 250V S13/S107 8 PAIR 0,75 mm2 FLEX - FLAME IEC
60092-376 IEC 60331-1*) or IEC 60331-2*) IEC 60331-21**)
IEC 60332-3-22 Production no. <Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm
**) IEC 60331-21 also at enhanced temperature 1000°C for 180 minutes
15
Offshore Instrumentation Cables
1 2 1.5 1.55 0.7 1.1 8.5 ± 0.5 127 38 1 2 1.5 1.55 8001960
2 2 1.5 1.55 0.7 1.3 13 ± 0.8 230 75 2 2 1.5 1.55 on request
4 2 1.5 1.55 0.7 1.4 15.5 ±0.8 376 150 4 2 1.5 1.55 on request
1 2 2.5 1.9 0.7 1.1 9.5 ± 0.5 154 55 1 2 2.5 1.9 8000084
4 2 2.5 1.9 0.7 1.4 17 ± 0.8 473 220 4 2 2.5 1.9 on request
16 2 2.5 1.9 0.7 2.0 31.5 ±1.5 1704 887 16 2 2.5 1.9 on request
Installation recommendations
Overall diameter Minimum Bending Minimum Bending Maximum Tensile Minimum Installation
of cable (D) Radius during Radius Fixed Load During Temperature
Installation Installed Installation
≤25 mm 50 N x total
8xD 4xD cross section (mm²) of -20°C
>25 mm 6xD conductors
16
Offshore Instrumentation Cables
Halogen-free, fire-resistant, flame retardant, mud-resistant cable for use on board ships, offshore units and fixed
installations for instrumentation, communication, control and alarm systems. For emergency and critical systems
requiring fire resistance.
Application Standards applied
Fixed installation for instrumentation, communication, control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX-(Zone 2) and safe areas, IEC 60228 class 2 - Conductor
emergency and critical systems where requirement for fire IEC 60092-360 - Insulation
IEC 60092-360 - Sheath
resistance exists. IEC 60332-1-2 - Flame Retardant
BU(c) M 250V meets the Oil & Mud resistance requirements in IEC 60332-3-22 - Flame Retardant
IEC 60331-1, -2, -21 - Fire Resistant
NEK TS 606:2016 IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated conductors
Lay up / Shielding Individually shielded pairs/triples/quads are laid up in concentric
layers and wrapped with a PETP tape.
Inner covering No inner covering. (Additional tapes may be applied)
Armour/screen No armour
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> BU(c) M 250V
S14/S108
8 PAIR 0,75 mm2 FLEX - FLAME IEC 60092-376 IEC 60331-1*) or
IEC 60331-2*)
IEC 60331-21**) IEC 60332-3-22 Production no. <Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm
**) IEC 60331-21 also at enhanced temperature 1000°C for 180 minutes
17
Offshore Instrumentation Cables
No of
Number Cross Conducto Thicknes Weight Copper Ordering info Ordering info
cores Insulation Diameter
of section r s Outer of Cable content Blue outer Grey outer
in Thicknes outer sheath,
element core, Diameter, Sheath, Approx. Approx. sheath sheath
elemen s, mm mm
s mm² mm mm (Kg/Km) (kg/km)
t
Installation recommendations
Overall diameter Minimum Bending Minimum Bending Maximum Tensile Minimum Installation
of cable (D) Radius during Radius Fixed Load During Temperature
Installation Installed Installation
≤25 mm 50 N x total
8xD 4xD cross section (mm²) of -20°C
>25 mm 6xD conductors
18
Offshore Instrumentation Cables
Halogen-free, flame retardant and mud-resistant cable for use on board ships, offshore units and fixed installations
for instrumentation, communication, and control and alarm systems.
Application Standards applied
Fixed installation for instrumentation, communication, Control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX- (Zone 2) and safe areas. IEC 60228 class 2 - Conductor
RU(i) M 250V meets the Oil & Mud resistance requirement in IEC 60092-360 - Insulation
IEC 60092-360 - Sheath
NEK TS 606:2016. IEC 60332-1-2 - Flame Retardant
IEC 60332-3-22 - Flame Retardant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together. Pairs/Triples are screened by
Pair / Triple / Quad twisting copper backed polyester tape with tinned copper drain wire. Each
pair/triple is wrapped with polyester tape to prevent electrical contact
with adjacent pairs/triples. Pairs/triples are identified by numbered tape
or by numbers printed directly on the insulated
conductors
Lay up / Shielding Individually shielded pairs/triples/quads are laid up in concentric
layers and wrapped with a PETP tape.
Inner covering No inner covering. (Additional tapes may be applied)
Armour/screen No armour
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> RU(I) M
250V S11/S105 2 pair 0,75 mm2 IEC 60092-376 IEC 60332-
3-22 Production no. <Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
19
Offshore Instrumentation Cables
No of
Number Cross Conducto Thicknes Weight Copper Ordering info Ordering info
cores Insulation Diameter
of section r s Outer of Cable content Blue outer Grey outer
in Thicknes outer sheath,
element core, Diameter, Sheath, Approx. Approx. sheath sheath
elemen s, mm mm
s mm² mm mm (Kg/Km) (kg/km)
t
Installation recommendations
Overall diameter Minimum Bending Minimum Bending Maximum Tensile Minimum Installation
of cable (D) Radius during Radius Fixed Load During Temperature
Installation Installed Installation
≤25 mm 50 N x total
8xD 4xD cross section (mm²) of -20°C
>25 mm 6xD conductors
20
Offshore Instrumentation Cables
Halogen-free, flame retardant and mud-resistant cable for use on board ships, offshore units and fixed installations
for instrumentation, communication, and control and alarm systems.
Application Standards applied
Fixed installation for instrumentation, communication, Control
IEC 60092-376 (2003-05) - Design
and alarm systems in both EX- (Zone 2) and safe areas. IEC 60228 class 2 - Conductor
RU(C) M 250V meets the Oil & Mud resistance requirement in IEC 60092-360 - Insulation
IEC 60092-360 - Sheath
NEK TS 606:2016. IEC 60332-1-2 - Flame Retardant
IEC 60332-3-22 - Flame Retardant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
Construction
Code
letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R EP-rubber, IEC 60092-360 (EPR)
Color coded cores twisted together and wrapped with polyester tape.
Pair / Triple / Quad twisting Pairs/Triples are laid up collectively and screened by copper backed
polyester tape with tinned copper drain wire.Pairs/triples are identified
by numbered tape or by numbers printed directly on the insulated
conductors
Inner covering No inner covering. (Additional tapes may be applied)
Armour/screen No armour
Outer sheath U Flame retardant, halogen-free thermoset compound, SHF2 (IEC
60092-360)
Marking text (example) "meter" "year/week" DRAKA 01 Part no. <SAP code> RU(c) M
250V S12/S106 2 pair 0,75 mm2 IEC 60092-376 IEC 60332-
3-22 Production no. <Prod.ordre no.>
Manufacturing unit DRAKA 01 = Prysmian Group Norge AS
Outer sheath color Grey or Blue
21
Offshore Instrumentation Cables
Installation recommendations
Overall diameter Minimum Bending Minimum Bending Maximum Tensile Minimum Installation
of cable (D) Radius during Radius Fixed Load During Temperature
Installation Installed Installation
≤25 mm 50 N x total
8xD 4xD cross section (mm²) of -20°C
>25 mm 6xD conductors
22