0% found this document useful (0 votes)
429 views32 pages

Fleck Model 7000 Service Manual

The document is a service manual for the Model 7000 water conditioner. It provides instructions for installation, start up procedures, control operation and settings. Key sections include filling out the job specification sheet, valve programming instructions, installation checklist, valve installation steps, control panel functions and settings, regeneration cycle diagrams, and troubleshooting guides. The manual aims to guide service technicians in properly servicing and maintaining the Model 7000 water conditioner.

Uploaded by

jsbatch
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
429 views32 pages

Fleck Model 7000 Service Manual

The document is a service manual for the Model 7000 water conditioner. It provides instructions for installation, start up procedures, control operation and settings. Key sections include filling out the job specification sheet, valve programming instructions, installation checklist, valve installation steps, control panel functions and settings, regeneration cycle diagrams, and troubleshooting guides. The manual aims to guide service technicians in properly servicing and maintaining the Model 7000 water conditioner.

Uploaded by

jsbatch
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Model 7000 Service Manual

IMPORTANT: Fill in pertinent information on page 3 for future reference.

Model 7000
Table of Contents
Job Specifications Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Valve Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Residential Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Valve Installation and Start-up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7000 Control Operation and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Water Conditioner Flow Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 In Service Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Backwash Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Brine Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Slow Rinse Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Rapid Rinse Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Brine Tank Refill Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Power Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Power Head Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Valve Assembly Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Bypass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 2310 Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Removing Gear Box Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Inserting Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Connecting Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Meter Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Injector Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

IMPORTANT: The information, specifications and illustrations in this manual are based on the latest information available at the time of printing. The manufacturer reserves the right to make changes at any time without notice.

Model 7000
Job Specifications Sheet
Job Number ___________________________________________ Model Number _________________________________________ Serial Number _________________________________________ Water Test ____________________________________________ Capacity Of Unit ________________________ Max. _____________ Per Regeneration Brine Tank Size _____________________________________ Salt Setting Per Regeneration ____________________________________

Valve Programming
Treated Water Capacity _____________________________________ (Gallons / Liters) Regeneration Day Override ____________________________________ (Max. Days between Regen.) Regeneration Time _____________________________________ (A.M.) (P.M.) Type of Timer _____________________________________ (with meter) (without meter)

Notes

Model 7000
Water Softener Control Valve
Water Pressure
A minimum of 25 psi inlet water pressure is required for regeneration valve to operate effectively.

Electrical Facilities
An uninterrupted alternating current (A/C) supply is required. Make sure: Voltage supply is compatible with unit before installation. Current supply is always hot and cannot be turned off with another switch.

Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Replace piping that has heavy lime and/or iron build-up. If piping is clogged with iron, install a separate iron filter unit ahead of the water softener.

Location of Softener and Drain


Locate the softener close to a clean working drain and connect according to local plumbing codes.

Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one.

CAUTION
Minimum water pressure 20 psig. Maximum water pressure 125 psig. Minimum water temperature 34 F. Maximum water temperature 110 F. Ambient temperature 34 to 122 F (1 to 50 C) Disconnect all power sources before servicing. Always operate with cover in place.

NOTE: This product should be installed by qualified personnel. Comply with all plumbing codes when installing this product. Comply with all electrical codes when installing this product.

WARNING
The controller MUST be depressurized before removing any quick connection clips for servicing. The connector should be pushed toward the control while removing clips.

Model 7000
Valve Installation and Start-up Procedures
Installation Instructions 1. Place the softener tank where you want to install the unit.

NOTE: Be sure the tank is level and on a firm, clean base.


2. Perform all plumbing according to local plumbing codes. 3. Cut the 1.05" (32mm) distributor tube flush with the top of the tank (A). Deburr the outside of the tube (B) after cutting. Lubricate the o-ring (C) with non-petroleum based oil. 4. Lubricate the distributor 0-ring seal and tank 0-ring seal. Use only non-aerosol silicone lubricant. 5. Load media and place the control valve on the tank. 6. All soldering MUST be done on any connections requiring soldering prior to connecting the main control valve. The main control valve will by damaged if it is connected at the time of soldering. 7. Apply Teflon tape to all threaded fittings. 8. On units with a bypass, place in Bypass position. Turn on the main water supply. Open a cold soft water tap nearby and let water run a few minutes or until the system is free of foreign material (usually solder) resulting from the installation. Close the water tap when water runs clean. 9. Make plumbing connections to valve. 10. Plug the valve into an approved power source.

NOTE: Make all electrical connections according to codes.


11. Place the bypass In Service position. Cycle the valve to the Backwash position, and let the water flow slowly into the mineral tank until the air is purged from the unit. 12. Add water to the brine tank until the top of the air check is covered. Manually step the valve to the Brine Draw Position, and allow the valve to draw water from the brine tank until it stops.

NOTE: The air check will check at approximately the midpoint of the screened intake area.
13. Manually step the valve to the Brine Refill Position, and allow the valve to return to In Service automatically. 14. With the valve In Service, check that there is at least 1" of water above the grid in the brine tank, if used. 15. Fill the brine tank with salt. 16. Allow the control to run automatically. Setup is now complete.

Model 7000
7000 Control Operation and Settings
Display
Program Indicator Programming Mode Active, Light On In Service Indicator Valve In Service, Light On Manual Regeneration Qued, Flashing Light Flow Indicator Water Flow, Light Flashing

P.M. Indicator/Valve Moving Light Flashing P.M., Light On A.M., Light Off Display Screen Time of Day alternates with Process Display (for example, Volume Remaining, Time Remaining, programming information), Error Codes Set Down Button Adjust Values Down Set Up Button Adjust Values Up Extra Cycle Button User-Initiated and Program Step Advance Regeneration
Figure 1 : Control Panel and Display

Time Clock Regeneration Valves


In normal operation the Time of Day Display may be viewed at all times. The control operates for a preset number of days between Regeneration cycles. When the number of days since the last Regeneration reaches the preset number of days, a Regeneration cycle initiates at the preset Regeneration Time. NOTE: Program the number of days between Regeneration cycles and the Regeneration time using the 7000 Control Start-Up Procedures, page 8.

Flow Meter Equipped Valves General


Flow meter equipped valves calculate the volume of water that the system can treat between Regeneration cycles based on the system capacity which is preset by the system manufacturer in a Master Programming Mode and the feed water hardness which is programmed in the Start-Up procedure safety factor (Master Mode only). The remaining system capacity displays in gallons or liters. The display has a range of 0 to 9999 (gallons or liters). If the remaining capacity exceeds 9999 liters when in the Metric Mode, then the display changes to millions of liters and a letter t is displayed as the first digit. The display then has a range of t1.0 (1,000,000) to t1.9 (1,900,000).

Flow Meter Equipped Valves Immediate Regeneration Mode


The Time Of Day display alternates with the Volume Remaining display in gallons or liters. The Meter dot flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from a maximum value to zero and initiates a Regeneration cycle.

Model 7000
Flow Meter Equipped Valves Delayed Regeneration Mode
In Normal operation the Time Of Day display alternates with the Volume Remaining display. The flow dot flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from a maximum value to zero. If the reserve is reached, a Regeneration queues. The display shows all dashes if the entire volume is depleted before the scheduled Regeneration time. At the preset Regeneration Time, a Regeneration cycle initiates.

Control Operation During Regeneration


In Regeneration the display shows the Regeneration status two ways: When the valve advances to the next position, the display flashes the number of that next position followed by three dashes. Once the valve reaches a position the display shows that position and number of minutes left in that Regeneration step. NOTE: If the step time exceeds 100, the leading digit flashes. Once all Regeneration steps are complete, the valve returns to In Service and resumes normal operation. NOTE: Pressing the Extra Cycle Button during a Regeneration cycle immediately advances the valve to the next cycle step position and resumes normal step timing.

Control Operation During Programming


The control enters Program Mode with the valve In Service. While in Program Mode the control continues to operate normally, monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently. There is no need for battery backup power.

Control Operation During a Power Failure


During a power failure all control displays and programming are stored for use upon power re-application. An inaccurate or flashing Time of Day display indicates that a power outage has occurred. During power failure the control: Is fully inoperative and any calls for Regeneration are delayed. Upon power re-application, resumes normal operation from the point that it was interrupted. Does not monitor the volume of water used during a power outage. In Delay Regeneration types, the reserve capacity is set to 1/3 the capacity.

Manually Initiating a Regeneration


A Regeneration cycle may be initiated manually (referred to as an Extra Regeneration Cycle). There are two options when starting an Extra Regeneration Cycle: Press and release the Extra Cycle Button: Flow Meter - Immediate Regeneration controls immediately go into a Regeneration cycle. For Time Clock and Flow Meter - Delayed Regeneration controls, the In Service dot begins to flash immediately and a Regeneration occurs at the pre-programmed Regeneration time.

Figure 2 : Manually Initiated Regeneration

Press and hold the Extra Cycle Button for five (5) seconds: For Time Clock and Flow Meter - Delayed Regeneration controls, the control immediately begins the Regeneration cycle.

Model 7000
7000 Control Start-Up Procedures
Set Time of Day
Press the Set Up and Set Down buttons to set time of day. Metric = 24 hour clock US = 12 hour clock with PM indicator light

Figure 3 : Set Time of Day

Enter Control Programming Mode


Press and hold both the Set Up and Set Down buttons for five (5) seconds to enter Programming Mode. When the program mode is entered, the program dot turns on.

Figure 4 : Enter Control Programming Mode

CAUTION
Do not set the time of day to 12:01 PM when entering the Start-Up programming mode. Doing so causes the control to enter the Master Programming Mode and alter the factory settings, resulting in a system malfunction. The 7000 controller performs four (4) basic types of Regeneration systems. The type of system is selected by the system manufacturer and set in the Master Programming Mode. Basic systems are: Time Clock The control operates for a preset number of days between Regeneration cycles. On the day that a Regeneration cycle is required the system regenerates at the preset Regeneration Time. Meter Immediate The control regenerates immediately when the remaining capacity (volume of water that can be treated before a Regeneration is required) drops to zero (0). Meter Delayed The control regenerates on the day that the remaining capacity drops to less than the reserve volume. Regeneration starts at the preset Regeneration Time.

Model 7000
Programming a Meter Delayed Regenerated System
1. Feed water hardness (Display Code H).

NOTE: The feed water hardness setting only displays when the system is set to operate as a Meter Immediate or Meter Delayed system type.
Press the Set Up or Set Down buttons to set the amount of feed water hardness in grains/gallon (U.S.) or degrees (metric). The system automatically calculates treated water capacity based on the feed water hardness and the system capacity preset in the Master Programming mode. "Calc" is displayed during calculations.

Example:
Range: 4 199 U.S. and metric

To program 9 grains / gallon (U.S.) or 9 degrees (metric) [ H - 9] Press the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button once to advance to the next step.

Figure 5 : Feed Water Hardness

2. Regeneration Time (No display Code)

NOTE: The Regeneration Time setting does not display in Meter Immediate Regeneration Mode since the system regenerates immediately when the available capacity reaches zero (0).
Identify the Regeneration Time display by observing a non-flashing colon between two sets of numbers. Set the desired time of day for Regeneration to occur.

Example:
2 o'clock A.M. regeneration time: [ 2:00 ] (P.M. Indicator Dot Off) Press the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button to exit the programming mode or press and hold the Set Up and Set Down buttons simultaneously for five (5) seconds to enter the Extended Setup Programming Mode.

Figure 6 : Regeneration Time

Model 7000
3. EXTENDED Programming Mode Regeneration Cycle Step Programming (Display Code 1 to 6) Use this feature to program the Regeneration Cycle step times. The Regeneration Cycle Step being programmed appears in the first digit of the display. Each display is used to set the duration time in minutes of that specific step in the regeneration cycle.

Example:
Cycle Step 1 2 3 4 5 6 dF 10 = Backwash 60 = Brine Draw 5 = 2nd Backwash 10 = Rapid Rinse 12 = Refill dFFF 12 = Refill 60 = Brine Making 10 = Backwash 60 = Brine Draw 5 = 2nd Backwash 10 = Rapid Rinse FLtr 10 = Backwash 10 = Rapid Rinse

Use the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button to advance to the extended diagnostics.

Figure 7 : Extended Programming Mode

4. Extended Diagnostics Mode (Viewable Only) (Dy xx) Display Code xx = days since last Regeneration Press the Extra Cycle button once to advance to the next diagnostics. (xxxx) No Display code xxxx = volume used since the last Regeneration. (yyyy) No Display code yyyy Reserve Volume. Press the Extra Cycle button once to Exit Extended Setup Programming Mode. Control Programming Complete

Figure 8 : Extended Diagnostics Mode

10

Model 7000
Programming a Meter Immediate Regenerated System
1. Feed water hardness (Display Code H). The feed water hardness setting displays only if the system is set to operate as a Meter Immediate or Meter Delayed system type. Press the Set Up and Set Down buttons to set the amount of feed water hardness (grains/gallon or degrees). The system automatically calculates treated water capacity based on the feed water hardness and the system capacity preset in the Master Programming mode.

Example:
Range: 4 199 US and Metric

To program 9 grains / gallon (US) or 9 degrees (Metric) [H 9] Press the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button once to Exit Setup Programming Mode or press and hold the Up and Down buttons simultaneously for five (5) seconds to enter the Extended Setup Programming Mode.

Figure 9 : Feed Water Hardness

2. EXTENDED Programming Mode Regeneration Cycle Step Programming (Display Code 1 6) This Program Step is used to program the Regeneration Cycle step times. The Regeneration Cycle Step being programmed is displayed in the first digit of the display. Each display is used to set the duration time in minutes of that specific step in the Regeneration cycle.

Example: Cycle Step


1 2 3 4 5 6

dF 10 = Backwash 60 = Brine Draw 5 = 2nd Backwash 10 = Rapid Rinse 12 = Refill

dFFF 12 = Refill 60 = Brine Making 10 = Backwash 60 = Brine Draw 5 = 2nd Backwash 10 = Rapid Rinse

FLtr 10 = Backwash 10 = Rapid Rinse

Figure 10 : Extended Programming Mode

11

Model 7000
3. Extended Diagnostics Mode (Viewable Only) (Dy xx) Display Code xx = days since last Regeneration Press the Extra Cycle button once to advance to the next diagnostics. (xxxx) No Display code xxxx = the volume used since the last Regeneration Press the Extra Cycle button once to Exit Extended Setup Programming Mode. Control Programming Complete

Figure 11 : Extended Diagnostics Mode

Programming a Time Clock Regenerated System


1. Regeneration Time (No Display Code) The Regeneration Time display can be identified by observing a non-flashing colon between two sets of numbers. Set the desired time of day that you want Regeneration to occur.

Example:
2 o'clock A.M. regeneration time: [ 2:00 ] (P.M. Indicator Dot Off) Use the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button to proceed to the next step.

Figure 12 : Regeneration Time

2. Regeneration Day (Display code A) Use this display to set the number of days between Regeneration cycles. This setting is identified by observing the letter "A" in the first digit. In the Time Clock regeneration mode, the system regenerates at the time set in Step 1 on the programmed number of days.

Example:
Regeneration every 7 days [A -- 7] Use the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button once to Exit Setup Programming Mode or press and hold the Set Up and Set Down buttons simultaneously for five (5) seconds to enter the extended setup programming mode.

Figure 13 : Regeneration Day

12

Model 7000
3. Extended Programming Mode Regeneration Cycle Step Programming (Display Code 1 6) This Program Step is used to program the Regeneration Cycle step times. The Regeneration Cycle Step being programmed is displayed in the first digit of the display. Each display is used to set the duration time in minutes of that specific step in the Regeneration cycle.

Example: Cycle Step


1 2 3 4 5 6

dF 10 = Backwash 60 = Brine Draw 5 = 2nd Backwash 10 = Rapid Rinse 12 = Refill

dFFF 12 = Refill 60 = Brine Making 10 = Backwash 60 = Brine Draw 5 = 2nd Backwash 10 = Rapid Rinse

FLtr 10 = Backwash 10 = Rapid Rinse

Use the Set Up and Set Down buttons to adjust this value. Press the Extra Cycle button once to proceed to the diagnostics.

Figure 14 : Extended Programming Mode

4. Extended Diagnostics Mode (Viewable Only) (Dy xx) Display Code xx = days since last Regeneration Press the Extra Cycle button once to advance to the next diagnostics. Press the Extra Cycle button once to Exit Extended Setup Programming Mode. Control Programming Complete

Figure 15 : Extended Diagnostics Mode

13

Model 7000
Water Conditioner Flow Diagrams
In Service Position

40988A

Figure 16 : In Service Position

Backwash Position

1st Backwash Cycle

40988B

2nd Backwash Cycle

40988C

Figure 17 : Backwash Position

14

Model 7000
Water Conditioner Flow Diagrams
Brine Position

40988D

Figure 18 : Brine Position

Slow Rinse Position

40988E

Figure 19 : Slow Rinse Position

15

Model 7000
Water Conditioner Flow Diagrams
Rapid Rinse Position

40988F

Figure 20 : Rapid Rinse Position

Brine Tank Refill Position

40988G

Figure 21 : Brine Tank Refill Position

16

Model 7000
Notes:

17

Model 7000
Power Head

Figure 22 : Power Head

18

Model 7000
Power Head Parts List
Item Number
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

No. Reqd
1 1 1 1 1 1 1 1 1 1 3 1 3 1 2 1 1 1

Part Number
40968 10218 40978 61460 40702 40703 40704 40977 40979 61430 19367 13602 40980 40967 15727 11805 40981 19791-01 41122

Description
motor optional auxiliary switch plate, upper support circuit board shaft, encoder gear, main drive cam, brine, down flow cam, aux. switch/filter plate, lower support cover asm screw, thumb screw, 6-32x.312" backplate screw, 1/4-20x1.0" screw, 10-24x1/2" screw, 4-40x5/8" transformer, US 24V, 9.6VA meter cable assembly, turbine o-ring

19

Model 7000
Valve Assembly

Figure 23 : Valve Assembly

20

Model 7000
Valve Assembly Parts List
Item Number
1 2

No. Reqd
1 1

Part Number
61050 61452-10 61453-10 61452-20 40576 61438 60016-01 40577 61XXX

Description
valve body assembly piston assembly, 7000 softener, D/F 35 GPM piston assembly, 7000 softener, D/F 28 GPM piston assembly, 7000, filter clip, H, plastic seal and spacer kit brine valve, 7000 turbine meter assembly injector assemblies Part Number 61454-000 61454-00 61454-0 61454-1 61454-2 61454-3 61454-4 61454-5 cap, injector BLFC assemblies Part Number 61450-12 61450-25 61450-50 61450-100 61451-12 61451-25 61451-50 61451-100 DLFC assemblies Part Number 61455-17 61455-20 61455-24 61455-30 61455-35 61455-40 61455-45 61455-50 61455-60 61455-70 o-ring, -021 o-ring, 014 clip, brine retaining clip, drain retaining screen, injector o-ring, -220 collector, top, 1"x.011, gray kit, 1.05" dist. adapter DLFC kits Part Number 61456-8.0 61456-9.0 61456-10 61456-12 61456-15 61456-20 61456-25 61456-30 stuffer tool assembly

3 4 5 6 7

3 1 1 1 1

Injector Number #000 #00 #0 #1 #2 #3 #4 #5

8 9

1 1

40556 61XXX

BLFC Size 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 1/2" DLFC Size 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

GPM 0.125 0.25 0.50 1.0 0.125 0.25 0.50 1.0 GPM 1.7 2.0 2.4 3.0 3.5 4.0 4.5 5.0 6.0 7.0

10

61XXX

11 12 13 14 15 16 17 18 23

1 2 1 1 1 1 1 1 1

13303-01 13302-01 40946 40945 40950 40951 18280 61419 61xxx

DLFC Size 1" 1" 1" 1" 1" 1" 1" 1"

GPM 8.0 9.0 10.0 12.0 15.0 20.0 25.0 30.0

Not Shown
12763-10

21

Model 7000
Bypass Assembly

41118

Figure 24B

41147

Figure 24 : 7000 Bypass Assembly

IMPORTANT To bypass the valve, turn bypass knob on both sides of the valve to bypass position. (See Figure 24 B.) When returning to service, put the inlet into service before the outlet.

Item Number
1 2

No. Reqd
1 1

Part Number
40569 40563 40563-10 40565 40565-10 40953 40576 40951

Description
7000 bypass assembly connector, 1" NPT connector, 1" BSP connector, 1-1/4" NPT connector, 1-1/4" BSP connector, 1-1/4" sweat, copper clip, H, plastic o-ring

3 4 5

1 2 1

Not Shown
1 61462

7000 valve bypass service kit (includes all internal parts for 7000 bypass assembly bypass body not included)

22

Model 7000
2310 Safety Brine Valve

Figure 25 : 2310 Safety Brine Valve

Item Number
1 2 3

No. Reqd
1 1 1

Part Number
60014 60068 60026-30 60002

Description
2310 safety brine valve 2310 float assembly float assembly red/white (float fill) #500 air check

23

Model 7000
Troubleshooting
Error Codes
NOTE: Error Codes appear on the In Service display.
There are three possible error codes.: Error Code ( Err 0 ) ( Err 1 ) Probable Cause Drive motor is stalled Drive motor is running continuously Recover and Resetting Unplug the unit from the power source. When power is restored to the unit, the Err _ display code clears. If the condition causing the error has not been resolved the Err _ code reappears in the four digit display. Do not attempt to troubleshoot this problem any further. Contact the installer for service. Regeneration must occur for the unit to recover, the display to clear and the valve to function normally. Contact the installer for service.

( Err 2 )

There have been more than 99 days since the last Regeneration

WARNING
The controller MUST be depressurized before removing any quick connection clips for servicing. The connector should be pushed toward the control while removing clips.

General Troubleshooting
PROBLEM
1. Softener fails to regenerate.

CAUSE
A. Electrical service to unit has been interrupted. B. Timer is defective.

CORRECTION
A. Assure permanent electrical service (check fuse, plug, pull chain or switch). B. Replace timer. A. Close bypass valve. B. Add Salt to brine tank and maintain salt level above water level. C. Clean injector screen. D. Check brine tank fill time and clean brine line flow control if plugged. E. Repeated flushing of the hot water tank is required. F. Make sure distributor tube is not cracked. Check O-Ring and tube pilot. B. Replace seals and spacers and/or piston.

2. Hard water.

A. Bypass valve is open. B. No salt in brine tank.

C. Injector screen plugged.


D. Insufficient water flowing into brine tank. E. Hot water tank hardness. F. Leak at distributor tube.

G. Internal valve leak.

24

Model 7000
3. Unit used too much salt. A. Improper salt setting. B. Excessive water in brine tank. 4. Loss of water pressure. A. Iron buildup in line to water conditioner. B. Iron buildup in water conditioner. A. Check salt usage and salt setting. B. See Problem No. 7. A. Clean line to water conditioner. B. Clean control and add mineral cleaner to mineral bed. Increase frequency of regeneration and/or backwash time. C. Remove pistons and clean control.

C. Inlet of control plugged due to foreign material broken loose from pipe by recent work done on plumbing system. 5. Loss of mineral through drain line. A. Air in water system.

A. Assure that well system has proper air eliminator control. Check for dry well condition. B. Check to ensure drain line flow control is sized properly for your mineral tank. A. Check backwash, brine draw and brine tank fill. Increase frequency of regeneration. A. Check flow control. B. Clean injector and screen. C. Replace timer. D. Replace brine valve seat and clean valve. E. Clean brine line flow control. F. Check power source.

B. Drain line flow control too large.

6. Iron in treated water.

A. Fouled mineral bed.

7. Excessive water in brine tank.

A. Plugged drain line flow control. B. Plugged injector system. C. Timer not cycling. D. Foreign material in brine valve. E. Foreign material in brine line flow control. F. Power loss during brine fill.

25

Model 7000
Removing Gear Box Assembly

Tabs

41033

40988G

Figure 26 : Removing the Gear Box Assembly

1. Unplug the power source. 2. With 3/8" nut driver, turn the cycle cam counter-clockwise to the position shown in Figure 26 above. 3. Slightly pull the two tabs outward and push the gearbox slightly upward to remove. 4. When returning valve to service after powerhead dissassembly, manually step valve through regeneration using the extra cycle button until valve is in service.

26

Model 7000
Inserting Circuit Board

Figure 27 : Aligning Circuit Board Notches

1. To insert the circuit board, align the notches on the left side of the board with the flexible finger on the power head. Apply pressure to the left while rotating the board back.

Figure 28 : Snapping Circuit Board Into Place

2. When all the way down, snap the circuit board into place under the notches on the right.

27

Model 7000
Connecting Circuit Board

41033-2 DF254-0 41033-2 DF254-0

Figure 29 : Connecting the Circuit Board

After the circuit board is installed: 1. Connect the motor wires (A) to the motor connector (A1) on board. 2. Connect the transformer cable (B) to the transformer connector (B1) on board. 3. Connect the meter cable (C) to the meter cable connector (C1) on board. 4. Connect the valve end to the opening on the valve body. 5. Thread meter cable (D1) and power wire (D2) along path shown in Figure 29 .

28

Model 7000
Dimensions

Figure 30 : Dimensions

29

Model 7000
Meter Flow Data
7000
7000 Valve
50 45 40 35 Softener Valve 35 GPM w/ Meter and 32mm Distributor Pilot CV=9.2 Filter Valve w/ 32mm Distributor Pilot CV=8.9 Softener Valve 28 GPM w/ Meter and 1 in. Distributor Pilot CV=7.2

Service Flow (GPM)

30 25 20 15 10 5 0 0 5 10 15 20

25
41140-02

30

TR18753 softener TR18688 Filter

Pressure Drop (PSID)

Figure 31 : 7000 Flow Data

30

Model 7000
Injector Flow Data
7000
j
Injector #000
0.7 0.6
3/8" Brine System

Injector #00
0.7 0.6 3/8" Brine System

Injector Flow (GPM)

0.5 0.4 0.3 0.2 0.1 0.0 0 20 40 60 80 100 120 Total Rinse Draw

Injector Flow (GPM)

0.5 0.4 0.3 0.2 0.1 0 0 20

Total Rinse

Draw

40

60 Pressure (PSI)

80

100

120

TR18755

Pressure (PSI)

TR18755

Injector #0
1.6 1.4 3/8" Brine System
1.6 1.4

Injector #1
3/8" Brine System

Injector Flow (GPM)

Injector Flow (GPM)

1.2 1 0.8 0.6 0.4 0.2 0 0


TR18755

1.2 1 0.8 0.6 0.4 0.2 0

Total Rinse

Total Rinse Draw

Draw

20

40

60

80

100

120

0
TR18755

20

40

60

80

100

120

Pressure (PSI)

Pressure (PSI)

Injector #2
2.5 3/8" Brine System
2.5 3/8" Brine System

Injector #3

Injector Flow (GPM)

Injector Flow (GPM)

Total
1.5

1.5

Total Rinse

Rinse

Draw
0.5

Draw

0.5

0 0
TR18755

20

40

60

80

100

120

0
TR18755

20

40

60

80

100

120

Pressure (PSI)

Pressure (PSI)

Injector #4
3 2.5

Injector #5
B A
4 3.5

B A Total C Rinse

Injector Flow (GPM)

C Rinse

Injector Flow (GPM)

Total

3 2.5 2 1.5 1 0.5 0

1.5 1 0.5 0 0
TR18755

Draw E D

Draw

E D

20

40

60

80

100

120

0
TR18755

20

40

60

80

100

120

Pressure (PSI)

Pressure (PSI)

A) Total Flow, 3/8" Brine System C) Rinse B) Total Flow, 1/2" Brine Line D) Brine Draw, 3/8" Brine System E) Brine Draw, 1/2" Brine Line Note: All data taken with 2310 Safety Brine Valve and 500 Air Check

Figure 32 : 7000 Injectors

31

P/N 41028

Rev. D

11/03

You might also like