Dsmc0006 en Medc Bg2 Callpoint - PDF 1
Dsmc0006 en Medc Bg2 Callpoint - PDF 1
BG2 range
manual call point
Ex de, Ex ia, weatherproof
Overview Features
This manual fire alarm call point has • Zone 0, Zone 1 and Zone 2 use • Corrosion resistant red painted
been designed for use in flammable GRP
atmospheres and harsh • Ex de, Ex ia or weatherproof
• Retained stainless steel cover
environmental conditions. • ATEX approved - Ex II 1GD (Ex ia) screws
The GRP enclosure is suitable for - Ex II 2GD (Ex de) • Optional lift flap
use offshore or onshore where
lightweight combined with a high • IP66 and IP67 • Key operated test facility
level of corrosion resistance is • Certified temperature from -40°C • Lightweight and robust
required. to +70°C*
*Model dependent
Eaton
Unit B, Sutton Parkway
Oddicroft Lane
Sutton in Ashfield
United Kingdom © 2019 Eaton
NG17 5FB All Rights Reserved
Printed in UK Eaton is a registered trademark.
T: +44 (0) 1623 444 400 Publication
www.crouse-hinds.com/hac No.DSMC0006/B All other trademarks are property
[email protected] May 2019 of their respective owners.
All specifications, dimensions, weights and tolerances are nominal (typical) and Eaton reserve the right to vary all data without prior notice.
No liability is accepted for any consequence of use.
Certifications General arrangement drawing (all dimensions in mm)
ATEX Ex de Cert. no. BAS02ATEX2105X. ATEX Approved Ex II 2GD
Certified to: EN60079-0, EN60079-1, EN60079-7, EN60079-18, EN60079-31
Ex db eb IIC T6 Gb, Ex tb IIIC T85°C Db (switch only)
Ex db eb mb IIC T4 Gb, Ex tb IIIC T135°C Db (with resistors & diodes)
ATEX Ex ia Cert no. Baseefa 03ATEX0084X. ATEX Approved Ex II 1 GD
Certified to: EN60079-0, EN60079-11
Ex ia IIC T4 Ga, Ex ia IIIC T135°C Da
Specifications
Material Anti static UV resistant glass reinforced polyester
Finish Painted red
Certified temp -40°C to +70°C
Voltage Up to 250Vac. Up to 50Vdc (model dependent)
Weight 1.2Kg
Ingress protection IP66 and IP67
Cable entries 2 x M20 bottom
Terminals 6 x 2.5 mm²
Resistors values Ex de - 100Ω minimum, 39 KΩ maximum
Ex ia - 470Ω minimum
Switch ratings Switch only 30Vdc 5A (resistive) or 3A (inductive)
30-50Vdc 1A (resistive or inductive)
250Vac 5A (resistive or inductive)
Resistor(s) 24Vdc 0.05A
Ordering requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box
The Eaton BG range of manual alarm call point caters for numerous
options such as variety of colours, LED indication, earth continuity,
double switch, etc. See separate catalogue sheet for details
DSMC0006/B 05/19
DO NOT SCALE
2. CERTIFICATION:
BG2E:
ATEX: Baseefa02ATEX2105X
STANDARD: Ex de IIC T6 Gb (-40 $ C to +70 $ C)
Ex tb IIIC T85 $ C Db IP66/67 (-40 $ C to +70)
BG2W: INDUSTRIAL
FIXING CENTRES
Cooper MEDC Ltd, Unit B, Sutton Parkway,
Oddicroft Lane, Sutton-in-Ashfield, DESIGNERS & MANUFACTURERS
OF ELECTRICAL & ELECTRONIC
Nottinghamshire, NG17 5FB, U.K.
FIXING HOLES: n 6.0 (4 POSITIONS) EQUIPMENT & SYSTEMS FOR
Tel:+ 44 (0) 1623 444400 HAZARDOUS AREAS
web: www.coopermedc.com
D.COATES 03-04-14
EITHER WHOLLY OR PARTLY. CUSTOMER GA
APPROVED BY: DATE:
REMOVE ALL BURRS
ALL RIGHTS IN RESPECT OF
AND SHARP CORNERS P.FISHWICK 03-04-14
PATENTS, DESIGNS AND
DRG No.
A4
SCALE: SIZE: ISSUE
MACHINE
SYMBOLS THUS COPYRIGHT ARE RESERVED 480-366 B
DO NOT SCALE
CURRENT
PRODUCTION COPY
See Schedule
SGS Baseefa Customer Reference No. 0676 Project File No. 21/0385
This document is issued by the Company subject to its General Conditions for Certification Services accessible at http://www.sgs.com/en/Terms-and-
Conditions.aspx and the Supplementary Terms and Conditions accessible at http://www.sgs.com/SGSBaseefa/Terms-and-Conditions.aspx. Attention is
drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information contained
herein reflects the Company’s findings at the time of its intervention only and within the limits of Client’s instructions, if any. It does not necessarily indicate
that the equipment may be used in particular industries or circumstances. The Company’s sole responsibility is to its Client and this document does not
exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents. This document cannot be reproduced
except in full, schedule included, without prior written approval of the Company. Any unauthorized alteration, forgery or falsification of the content or
appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law.
13 Schedule
14 Certificate Number BAS21UKEX0544X
15 Description of Product
The BGE, BG2E and PBE models are non-metallic enclosure, containing separately certified rail or direct mount terminals and
optionally fitted separately certified encapsulated resistors and diode assemblies. (See Table 4 below.)
Models BGE and BG2E utilise a top shell with an external recess, which houses an emergency break glass pane, in which the
release actuator is housed. Optionally, a separately certified LED indicator assembly may be fitted.
Model PBE utilise a top shell with a mounted push-button momentary-release or latching actuator; optionally, a separately
certified LED indicator assembly may be fitted.
All models provide an ingress protection levels of IP66 and IP67 and internal and optional external earthing facilities. Refer to
certificate annex for electrical supply ratings and list of permitted separately certified devices.
Table 1
Maximum Electrical Supply Ratings
Units fitted with up to 2 micro switches
Voltage d.c. Resistive load Amps Inductive load Amps
30 5 3
50 1 1
75 0.75 0.75
125 0.5 0.03
250 0.25 0.03
Voltage a.c. Resistive load Amps Inductive load Amps
125 5 5
250 5 5
Table 2
Units fitted with the encapsulated resistors/LED
Maximum Electrical Supply Ratings based on devices fitted.
LED: 24VDC 30 mA
Resistor/Diode: 1.2W max per resistor or diode fitted.
Voltage Current
6 VDC 200 mA
24 VDC 50mA
48 VDC 25mA
60 VDC 20mA
80 VDC 15mA
Table 3
Minimum Resistor
Values
R1Min R2Min
A 100 Ω 180 Ω
B 250 Ω 47 Ω
Table 4
ASSOCIATED CERTIFIED ELECTRICAL COMPONENTS
The following certified components may be incorporated into the equipment
Certificate No. IECEx/ATEX Description Manufacturer Type Designation
BAS01ATEX2358U Micro Switch SAIA-Burgess E1V3CS/XXXX
Baseefa13ATEX0067U Encapsulated LED and Eaton MEDC Encapsulated
Resistor Units Resistor/Diode assembly
TUV 18 ATEX 8221U Terminal Weidmuller AKZ 4
AKZ 2.5
TUV 18 ATEX 8209U Terminal Weidmuller BK 6/E
The terminals as listed in Table 4 above, are reviewed against the latest requirements of EN IEC 60079-0:2018 and EN 60079-
7:2015 and are considered suitable for the assembly.
In addition the AKZ 4 AKZ 2.5 and BK 6/E terminals show compliance with EN IEC 60079-7:2015+A1:2018
All models are permitted to be fitted with type BK6/E terminal strip as detailed in Table 4.
16 Report Number
SGS Baseefa Certification Report 21(C)0385
Digitally signed by
RAFAEL DE OLIVEIRA
Rafael Parada PARADA:32218566877
Program Owner Date: 2025.04.30 17:33:56
-03'00'
Página/Page: 1 / 9
Certificado de conformidade válido somente acompanhado das páginas de 1 a 9 © 2023 UL LLC. All rights reserved.
Certificate of Conformity valid only if accompanied from pages 1 to 9 Form-ULID-017660 – Rev. 3.0
Certificado de Conformidade
Certificate of Conformity
Certificado/Certificate: UL-BR 15.0936X / 00
Emissão/Issue Revisão/Review: 06 Validade/Expiration
26 de abril de 2016 25 de abril de 2028
April 26, 2016 April 25, 2028
Modelo de certificação/ 5
Certification model
Os modelos BGE, BG2E e PBE são invólucros não metálicos, contendo terminais de montagem direta em trilho ou BK6
separadamente certificados e opcionalmente instalados com resistores e conjuntos de diodos encapsulados certificados
separadamente.
Os modelos BGE e BG2E utilizam um invólucro com um recesso externo, que abriga uma janela de vidro de ruptura de
emergência, na qual o atuador está alojado. Opcionalmente, pode ser montado com um conjunto de LED indicador
certificado separadamente.
O Modelo PBE utiliza um invólucro montado com um botão de pressão de liberação momentânea ou trava de atuação.
Opcionalmente, pode ser montado com um conjunto de LED indicador certificado separadamente.
Todos os modelos possuem grau de proteção IP66 e IP67 e são fornecidos com terminais de aterramento interno e
externo.
Consulte o item “CARACTERÍSTICAS ELÉTRICAS” a seguir para determinação dos valores da alimentação de energia
elétrica e para a lista de dispositivos certificados separadamente permitidos.
The BGE, BG2E and PBE models are non-metallic enclosure, containing separately certified rail or BK6 direct mount terminals and optionally fitted
separately certified encapsulated resistors and diode assemblies.
Models BGE and BG2E utilize a top shell with an external recess, which houses an emergency break glass pane, in which the actuator is housed.
Optionally, a separately certified LED indicator assembly may be fitted.
Model PBE utilize a top shell with a mounted push-button momentary-release or latching actuator; optionally, a separately certified LED indicator assembly
may be fitted.
All models provide an ingress protection levels of IP66 and IP67 and internal and external earthing facilities.
Refer to ELECTRICAL CHARACTERISTICS for electrical supply ratings and list of permitted separately certified devices.
MARCAÇÃO Ex / Ex MARKING:
Modelos BGE, BG2E e PBE fornecidos com LEDs:
Ex db eb mb IIC T6 Gb
Ex tb IIIC T85°C Db IP66
Tamb = -35°C a +70°C
Modelos BGE, BG2E e PBE fornecidos somente com interruptores (sem LEDs ou Resistores):
Ex db eb IIC T6 Gb
Ex tb IIIC T85°C Db IP66
Tamb = -40°C a +70°C
BGE, BG2E and PBE models fitted with LEDs and Resistors:
Ex db eb mb IIC T4 Gb
Ex tb IIIC T135°C Db IP66/IP67
Tamb = -35°C to +70°C
BGE, BG2E and PBE models fitted only with Switches (no LEDs or Resistors):
Ex db eb IIC T6 Gb
Ex tb IIIC T85°C Db IP66/IP67
Tamb = -40°C to +70°C
Tabela 1 / Table 1
Valores Máximos da Alimentação Elétrica
Maximum Electrical Supply Ratings
Corrente / Current
Tensão / Voltage
Carga Resistiva / Resistive Load Carga Indutiva / Inductive Load
(Vcc/dc)
(A) (A)
30 5,00 3,00
50 1,00 1,00
75 0,75 0,75
125 0,50 0,03
250 0,25 0,03
Tensão/ Voltage Carga Resistiva / Resistive Load Carga Indutiva / Inductive Load
(Vca/ac) (A) (A)
125 5,00 5,00
250 5,00 5,00
Tabela 2 / Table 2
Unidades fornecidas com resistores/LED encapsulados
Units fitted with encapsulated resistors/LED
Valores Máximos da Alimentação Elétrica com base nos dispositivos instalados.
LED: 24 VCC 30 mA
LED: 24VDC 30 mA
Tabela 3 / Table 3
COMPONENTES ELÉTRICOS CERTIFICADOS ASSOCIADOS
ASSOCIATED CERTIFIED ELECTRICAL COMPONENTS
O invólucro pode ser fornecido como uma moldagem pigmentada preta sem tratamento de superfície adicional ou pode ser fornecido
revestido externamente com uma tinta epóxi pigmentada ou acrílica.
Os terminais listados na Tabela 3 acima são analisados de acordo com os requisitos mais recentes da IEC 60079-0: 2017 Edição 7 e
IEC 60079-7: 2015 Edição 5 e considerados adequados para a montagem.
Além disso, os terminais AKZ 4 AKZ 2.5 e BK 6 / E mostram conformidade com IEC 60079-7: 2017 Edição 5.1
O invólucro pode ser fornecido como o molde pigmentado preto sem tratamento de superfície adicional ou pode ser fornecido revestido
externamente com um sistema de tinta epóxi ou acrílica pigmentada.
The enclosure may be supplied as the black pigmented moulding without additional surface treatment or may be supplied coated externally with a
pigmented epoxy or acrylic paint system.
The terminals as listed in Table 3 above, are reviewed against the latest requirements of IEC 60079-0:2017 Edition 7 and IEC 60079-7:2015 Edition 5
and considered suitable for the assembly.
In addition the AKZ 4 AKZ 2.5 and BK 6/E terminals show compliance with IEC 60079-7:2017 Edition 5.1
The enclosure may be supplied as the black pigmented molding without additional surface treatment or may be supplied coated externally with a
pigmented epoxy or acrylic paint system.
a) Para versões equipadas com até dois micro-interruptores somente - os valores máximos para cada interruptor instalado são os
especificados na Tabela 1.
b) Para versões equipadas com invólucro encapsulado - os valores máximos do sistema são detalhados na Tabela 2; consulte a Tabela
4 para obter valores de resistência alternativos.
a) For versions which are equipped with up to two micro switches only – the maximum values for each switch fitted are as specified in Table 1.
b) For versions which are equipped with encapsulated housing – the maximum system values are detailed in Table 2; refer to Table 4 for alternative
resistor values.
Tabela 4 / Table 4
Valores Mínimos dos Resistores
Minimum Resistor Values
R1Min R2Min
A 100 Ω 180 Ω
B 250 Ω 47 Ω
1. As unidades devem ser incorporadas em sistemas que limitem os valores elétricos de alimentação – ver tabelas sob
“CARACTERÍSTICAS ELÉTRICAS”.
2. As terminações de cabos entre as partes fixas e móveis dos invólucros devem ser alojadas, durante a montagem, de forma que
os condutores e seus reforços não fiquem presos na face de conexão entre os invólucros.
3. Os prensa-cabos instalados nos modelos BGE, BG2E e PBE devem ser fornecidos com anéis de vedação para manter a
classificação IP66 do invólucro.
4. As unidades LED encapsuladas e as unidades resistor/diodo encapsuladas devem ser protegidas por um fusível adequado para
corrente de curto-circuito de, no mínimo, 1500 A.
1. The units must be incorporated in systems which limit the electrical supply ratings - see Tables under “ELECTRICAL CHARACTERISTICS”.
2. The wiring loom between the fixed and detachable enclosure shell must be located, during assembly, such that the conductors and the restraint
loop are not trapped in the sealing face between the shells.
3. The cable glands installed on the BGE, BG2E and PBE models are to be provided with sealing washers to maintain the IP66 rating of the enclosure.
4. The encapsulated LED and an encapsulated resistor/diode units shall be protected by a fuse rated for a prospective short circuit current of at least
1500A.
Nenhum / None
Observações/Observations:
1. A validade deste Certificado de Conformidade está atrelada à realização das avaliações de manutenção e tratamento
de possíveis não conformidades de acordo com as orientações da UL do Brasil Certificações previstas no RAC
específico. Para verificação da condição atualizada de regularidade deste Certificado de Conformidade deve ser
consultado o banco de dados de produtos e serviços certificados do Inmetro.
The validity of this Certificate of Conformity is linked to the performance of maintenance assessments and treatment of possible non-
conformities in accordance with the guidelines of UL do Brasil Certifications provided for in the specific Conformity Assessment
Regulation. To check the updated condition of regularity of this Certificate of Conformity, the Inmetro database of certified products
and services must be consulted.
2. Este certificado aplica-se aos equipamentos (produtos) idênticos ao protótipo avaliado e certificado, manufaturados
na(s) unidade(s) fabril(is) mencionada (s) acima.
This certificate applies to the products that are identical to the prototype investigated, certified and manufactured at the production
site mentioned in this certificate.
3. Qualquer alteração no produto, incluindo a marcação, invalidará o presente certificado, salvo se o solicitante informar
por escrito à UL do Brasil Certificações sobre esta modificação, a qual procederá à avaliação e decidirá quanto à
continuidade da validade do certificado.
Any non-authorized changes performed in the product, including marking, will invalidate this certificate. UL do Brasil Certificações
must be notified about any desired change. This notification will be analyzed by UL do Brasil Certificações that will decide about
certificate force.
5. Somente as unidades comercializadas durante a vigência deste certificado estarão cobertas por esta certificação.
Only the products placed into the market during the validity of this certificate will be covered by this certification.
7. As atividades de instalação, inspeção, manutenção, reparo, revisão e recuperação dos equipamentos são de
responsabilidade dos usuários e devem ser executadas de acordo com os requisitos das normas técnicas vigentes e
com as recomendações do fabricante.
The installation, inspection, maintenance, repair, review and rebuild equipment activities are responsibility of the end user and must
be performed in accordance with the requirements of the standards and manufacturer's recommendation.
Government of India
Ministry of Commerce & Industry
Petroleum & Explosives Safety Organisation (PESO)
5th Floor, A-Block, CGO Complex, Seminary Hills,
Nagpur - 440006
E-mail : [email protected]
Phone/Fax No : 0712 -2510248, Fax-2510577
Sub : Approval of Flame Proof, Encapsulated, Increased Safety Type Electrical Equipment under Petroleum Rules
2002- Regarding.
Sir(s),
Please refer to your letter No. OIN1177171 dated 10/10/2022 on the subject.
The following Ex electrical equipment(s) manufactured by you according to IEC 60079-0 : 2017, IEC 60079-1
: 2014-06, IEC 60079-7 : 2017, IS/IEC 60079-18 : 2014, standards and covered under SGS Baseefa
Limited Test reports mentioned below is/are approved for use in Zone 2 of Gas IIC hazardous areas
coming under the the Petroleum Rules, 2002 administered by this Organization.
2)The equipment shall be used only with approved type of accessories and associated apparatus.
3)Each equipment shall be marked either by raised lettering cast integrally or by plate attached permanently to the
main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the SGS Baseefa Limited applicable to the equipment.
(d) Equipment reference number of this letter by which use of apparatus is approved.
(e) Protection level.
4) A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing
referred to in the SGS Baseefa Limited Test report and is identical with the one tested and certified at SGS
Baseefa Limited shall be furnished with each equipment.
5) The customer shall be supplied with a copy of this letter, an extract of the conditions and maintenence
schedule, if any, recommended by SGS Baseefa Limited in their test reports and copy of instructions booklet
detailing operation & maintenance of the equipment so as to maintain its Flame Proof characterestics.
6) The After sales service and maintanance of subject equipment shall be looked after by your representative MTL
Instruments Private Limited, 3, Old Mahabalipuram Road, Sholinganallur, Chennai 600119
This approval also covers the permissible variations as approved under the SGS Baseefa Limited test reports
referred above. This approval is liable to be cancelled if any of the conditions of the approval is violated or not
complied with . The approval may also be amended or withdrawn at any time, if considered necessary in the interest
of safety.
The field performance report from actual users/your customers of the subject equipment may please be
collected and furnished to this office for verification and record on annual basis.
The Approval is Valid upto 31/12/2026
Yours faithfully,
(A.B. Tamgadge)
Dy. Chief Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to :
1. Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
2. MTL Instruments Private Limited,3, Old Mahabalipuram Road, Sholinganallur, Chennai 600119
for Chief Controller of Explosives
Nagpur
(For more information regarding status,fees and other details please visit our website http://peso.gov.in)
This is System Generated document. Signature is not required.
Disclaimer : This page gives the latest action taken by this organization on your application. This page is
made available for the information of concerned applicant/licensee only. All efforts have been made to secure
this information. However, PESO will not be responsible for any misuse of the information by unauthorized
persons including the hackers.
Print Back
Government of India
Ministry of Commerce & Industry
Petroleum & Explosives Safety Organisation (PESO)
5th Floor, A-Block, CGO Complex, Seminary Hills,
Nagpur - 440006
E-mail : [email protected]
Phone/Fax No : 0712 -2510248, Fax-2510577
Sub : Approval of Flame Proof, Encapsulated, Increased Safety Type Electrical Equipment under Petroleum Rules
2002- Regarding.
Sir(s),
Please refer to your letter No. OIN1177171 dated 10/10/2022 on the subject.
The following Ex electrical equipment(s) manufactured by you according to IEC 60079-0 : 2017, IEC 60079-1
: 2014-06, IEC 60079-7 : 2017, IS/IEC 60079-18 : 2014, standards and covered under SGS Baseefa
Limited Test reports mentioned below is/are approved for use in Zone 2 of Gas IIC hazardous areas
coming under the the Petroleum Rules, 2002 administered by this Organization.
2)The equipment shall be used only with approved type of accessories and associated apparatus.
3)Each equipment shall be marked either by raised lettering cast integrally or by plate attached permanently to the
main structure to indicate conspicuously:-
(a) Name of the manufacturer
(b) Name and number by which the equipment is identified.
(c) Number & date of the test report of the SGS Baseefa Limited applicable to the equipment.
(d) Equipment reference number of this letter by which use of apparatus is approved.
(e) Protection level.
4) A certificate to the effect that the equipment has been manufactured strictly in accordance with the drawing
referred to in the SGS Baseefa Limited Test report and is identical with the one tested and certified at SGS
Baseefa Limited shall be furnished with each equipment.
5) The customer shall be supplied with a copy of this letter, an extract of the conditions and maintenence
schedule, if any, recommended by SGS Baseefa Limited in their test reports and copy of instructions booklet
detailing operation & maintenance of the equipment so as to maintain its Flame Proof characterestics.
6) The After sales service and maintanance of subject equipment shall be looked after by your representative MTL
Instruments Private Limited, 3, Old Mahabalipuram Road, Sholinganallur, Chennai 600119
This approval also covers the permissible variations as approved under the SGS Baseefa Limited test reports
referred above. This approval is liable to be cancelled if any of the conditions of the approval is violated or not
complied with . The approval may also be amended or withdrawn at any time, if considered necessary in the interest
of safety.
The field performance report from actual users/your customers of the subject equipment may please be
collected and furnished to this office for verification and record on annual basis.
The Approval is Valid upto 31/12/2026
Yours faithfully,
(A.B. Tamgadge)
Dy. Chief Controller of Explosives
For Chief Controller of Explosives
Nagpur
Copy to :
1. Jt. Chief Controller of Explosives, South Circle Office, CHENNAI
2. MTL Instruments Private Limited,3, Old Mahabalipuram Road, Sholinganallur, Chennai 600119
for Chief Controller of Explosives
Nagpur
(For more information regarding status,fees and other details please visit our website http://peso.gov.in)
This is System Generated document. Signature is not required.
Disclaimer : This page gives the latest action taken by this organization on your application. This page is
made available for the information of concerned applicant/licensee only. All efforts have been made to secure
this information. However, PESO will not be responsible for any misuse of the information by unauthorized
persons including the hackers.
Certificate Num ber
Baseefa03ATEX0084X Issued 14 Septem ber 2016
Issue 6 Page 1 of 3
3.1 In accordance with Article 41 of Directive 20 14/34/EU , EC-Type Examination Certificates referring to 94/9/EC that were in
existence prior to the date of application of2014/34/EU (20 April 2016) may be referenced as if they were issued in accordance
with Directive 20 l4/34/EU. Supplementary Certificates to such EC-Type Examination Certificates, and new issues of such
certificates, may continue to bear the original certificate number issued prior to 20 April 2016.
7 This re-issued certificate extends EC Type Examination Certificate No. Baseefa03ATEX0084X to apply to product designed
and constructed in accord ance with the specification set out in the Schedule of the said certificate but having an y variations
specified in the Schedule attached to this certificate and the documents therein referred to.
8 SOS Baseefa, Notified Body number 1180, in accordance with Article 17 of Directive 20 14/34/EU of the European Parliament
and of the Council, dated 26 February 2014 , certifies that this product has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of products intended for use in potentially explosive atmospheres
given in Annex II to the Directive.
The examination and test results are recorded in confidenti al Report No. See Certificate History
9 Compliance with the Essential Health and Safety Requirements has been assured by compliance with:
10 If the sign "X" is placed after the certificate number, it indicates that the product is subject to the Specific Conditions of Use
specified in the schedule to this certificate.
11 This EU - TYP E EXAMINATION CERTIFICATE relates only to the design and construction of the specified product.
Further requirements of the Directive appl y to the manufacturing process and suppl y of this product. These are not covered by
this certi ficate.
® II 1 GD Ex ia II C T4 Ga
Ex ia IIIC T 135°C Da
SOS Baseefa Customer Reference No. 0676 Project File No. 16/0088
This document is issued by the Company subject to its General Conditions for Certification Services accessible at http ://www.sgs .com/enrrerms-and-
Conditions.aspx and the Supplementary Terms and Conditions accessible at http ://www .sgs .com/SGSBaseefafferms-and-Conditions.aspx Attention is drawn to
the limitation of liability , indemnification and jurisdiction issues defined therein . Any holder of this document is advised that information contained herein
reflects the Company's findings at the time of its intervention only and within the limits of Client's instructions, if any. It does not necessarily indicate that the
equipment may be used in particular industries or circum stanc es. The Company' s sole responsibility is to its Client and this document does not exonerate
parties to a tran saction from exercising all their right s and obli gations under the transaction documents. This document cannot be reproduced except in full,
schedule included , without prior written approval of the Company. Any unauth or ized alteration, forgery or falsific ation of the content or appearance of this
docum ent is unlawful and offe nders may be prosecuted to the fullest extent of the law.
13 Sc ed ule
14 Certificate Number Baseefa03ATEX0084X - Issue 6
The unit comprises of a polyester enclosure with an optional epoxy or acrylic paint finish, terminal block and a push button
switch under a flap or a break glass switch unit. Different versions contain resistors and / or zener diodes. These
components may optionally be mounted on an encapsulated PCB. An optional end-o f-line resistor may be added.
External connections are made at the terminals via gland entries at the bottom of the unit.
Vi 30V C o
I1 147mA I-I o
p I. 0.8W
28V o
93mA o
0.65W
20 Certificate History
Certificate No. Date Comments
The release of the prime certificate. The associated test and
assessment against the requirements of EN 50014: 1997 + Amd 1 &
Baseefa03ATEX0084X 27 February 2003 2, EN 50020: 2002 , EN 50284: 1999 & EN 50281- 1-1: 1998 is
documented in Test Report No. 02(C)0186. Project File No.
02/0186.
To permit modifications to introduce the BGI break glass call point.
Baseefa03ATEX0084X/l 28 April 2003
Project File No. 03/0236.
Baseefa03ATEX0084X/2 24 April 2007 To permit the use of epoxy or acrylic paint processes. Project File
No. 07/0181.
Baseefa03ATEX0084X/3 4 January 2008 To permit the use of an alternative enclosure material. Project File
No. 07/0852.
To permit minor drawing changes and to confirm that the original
Baseefa03ATEX0084X/4 2 September 2010 special condition of safe use stated at 17.3 (UV exposure) no longer
applies. Project File No.1 0/0075 .
To confirm that the equipment meets the requirements of IEC
60079-0:2011/EN 60079-0:201 2 & EN 60079-11 :2012, including
Baseefa03ATEX0084X/5 3 September 2012
revision of the marking. Report No . GB/BAS /ExTRI2.0220/00.
Project File No . 12/0715.
This issue of the certificate incorporates previousl y issued primary
& supplementary certificates into one certificate, perm its minor
mechanical changes and confirms the current design meets the
Baseefa03ATEX0084X requirements of EN 60079-0:2012+All :2013. Report No .
14 September 2016
Issue 6 GB/BAS/ExTRI6.0249/00. Project File No. 16/0088. A lso to
permit existing information (for example on Schedule Drawings) to
be replaced by the revised certificate holders name. No other
changes may be made to the certified design
For drawings applicable to each issue, see original of that issue.
Certificate Number
Issued 1 November 2021
Baseefa03ATEX0084X
Page 1 of 3
Issue 7
SGS Fimko Oy Customer Reference No. 0676 Project File No. 21/0385
This document is issued by the Company subject to their General Conditions for Certification Services accessible at http://www.sgs.com/en/Terms-and-
Conditions.aspx . Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is
advised that information contained herein reflects the Company’s findings at the time of their intervention only and within the limits of Client’s instructions,
if any. It does not necessarily indicate that the equipment may be used in particular industries or circumstances. The Company’s sole responsibility is to
its Client and this document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents.
This document cannot be reproduced except in full, schedule included, without prior written approval of the Company. Any unauthorized alteration, forgery
or falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law .
SGS Fimko Oy
Takomotie 8
FI-00380 Helsinki, Finland
Telephone +358 (0)9 696 361
e-mail [email protected]
web site www.sgs.fi Tuomas Hänninen
Business ID 0978538-5 Member of the SGS Group (SGA SA) SGS Fimko Oy
BAS-CERT-081 SGS Baseefa Limited is an associate of SGS Fimko OY Issue 3
Certificate Number
Issued 1 November 2021
Baseefa03ATEX0084X
Page 2 of 3
Issue 7
13 Schedule
14 Certificate Number Baseefa03ATEX0084X – Issue 7
15 Description of Product
The Manual Call Point Type PBI / BGI is designed to initiate an electrical signal when the alarm switch is operated. Alternative
versions can provide local LED indication.
The unit comprises of a polyester enclosure with an optional epoxy or acrylic paint finish, terminal block and a push button
switch under a flap or a break glass switch unit. Different versions contain resistors and / or zener diodes. These components
may optionally be mounted on an encapsulated PCB. An optional end-of-line resistor may be added.
External connections are made at the terminals via gland entries at the bottom of the unit.
Input Parameters
Group IIC (Ex ia IIC T4 Ga)
Ui = 30V Ci = 0
Ii = 147mA Li = 0
Pi = 0.8W
Ui = 28V Ci = 0
Ii = 93mA Li = 0
Pi = 0.65W
16 Report Number
See Certificate History
All drawings are common to, and held with, IECEx BAS 12.0093X.
20 Certificate History
Certificate No. Date Comments
The release of the prime certificate. The associated test and
assessment against the requirements of EN 50014: 1997 + Amd 1 &
Baseefa03ATEX0084X 27 February 2003
2, EN 50020: 2002, EN 50284: 1999 & EN 50281-1-1: 1998 is
documented in Test Report No. 02(C)0186. Project File No. 02/0186.
To permit modifications to introduce the BGI break glass call point.
Baseefa03ATEX0084X/1 28 April 2003
Project File No. 03/0236.
Baseefa03ATEX0084X/2 24 April 2007 To permit the use of epoxy or acrylic paint processes. Project File
No. 07/0181.
Baseefa03ATEX0084X/3 4 January 2008 To permit the use of an alternative enclosure material. Project File
No. 07/0852.
To permit minor drawing changes and to confirm that the original
Baseefa03ATEX0084X/4 2 September 2010 special condition of safe use stated at 17.3 (UV exposure) no longer
applies. Project File No. 10/0075.
To confirm that the equipment meets the requirements of IEC 60079-
0:2011/EN 60079-0:2012 & EN 60079-11:2012, including revision
Baseefa03ATEX0084X/5 3 September 2012
of the marking. Report No. GB/BAS/ExTR12.0220/00. Project File
No. 12/0715.
This issue of the certificate incorporates previously issued primary
& supplementary certificates into one certificate, permits minor
mechanical changes and confirms the current design meets the
Baseefa03ATEX0084X
14 September 2016 requirements of EN 60079-0:2012+A11:2013. Report No.
Issue 6 GB/BAS/ExTR16.0249/00. Project File No. 16/0088. Also to
permit existing information (for example on Schedule Drawings) to
be replaced by the revised certificate holders name. No other
changes may be made to the certified design
Baseefa03ATEX0084X
1 November 2021 To assess the product against the requirements of EN IEC 60079-0:
Issue 7 2018. SGS Baseefa Certification Report 21(C)0385/01
For drawings applicable to each issue, see original of that issue.