Civil & Electrical 299059350 Finishing 88486265 Plumbing 10795935 Fire 7631442
Civil & Electrical 299059350 Finishing 88486265 Plumbing 10795935 Fire 7631442
1.02 In all kinds of soil. (Basement 1 and 2) Cu.m 7925 200 1585000
Back filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc.
in layers not exceeding 20cm in depth consolidating each deposited layer by ramming ( by
1.03 Mechanical compactor )and watering including rehandling of the earth from stacks within the Cu.m 1450 150 217500
battery limits. (Backfilling shall be paid upto the vertical outer edge of lean concrete and retaining
wall only) -All kinds of soils.
Disposal of surplus excavated earth away from site by means of mechanical transport, including
1.04 loading, unloading etc., complete for 10km leads as per the direction of Engg-in-charge. Cu.m 7500 150 1125000
Providing & filling sand for foundation pits and wherever specified including filling in 150mm
1.05 layers and compacting/ saturating to the required levels, including all leads and lifts and Cu.m 395 2000 790000
as per the instructions of Engineer in Charge
Provoding Anti Termite treatment comprising of providing & injecting chemical emulsion for
preconstructional Anti termite treatment with Chloropyrifos emulsifiable concentrate (20%
1.06 concentration) diluted to a water based emulsion of 1% Chloropyrifos as per CPWD / IS Sq.m 1150 250 287500
specifications in foundation trenches, upper floors, junction of floors & walls, external perimeter
of building & backfilling. Plinth area only shall be measured & paid for.
2.00 CEMENT CONCRETE: PLAIN 0
Providing & laying plain cement concrete of required grade consolidated & curing complete
2.01 including the cost of form work, if any, in foundations & plinth at all level. Cu.m 2000 4500 9000000
4.01 Raft, Footing, R/Wall, Column, S/case, Beam, Slab, Liftwall, Road & Ramp etc. Cu.m 18940 7000 132580000
5.00 SHUTTERING 0
Centering and shuttering (as per IS:4990) by providing & using approved shuttering for
unexposed concrete work (plain and rein-forced) in locations called for including making ,
strutting, propping, bracing with steel props, bolting, wedging, casing, striking, removal etc.
complete Allow for forming grooves, drips throats, chamfers, cut-outs, openings, recesses etc.
where called for and for coating with approved mineral shuttering oil ( REEBOL of FOSROC / 0
equivalent ) to prevent adhesion. This item is for all floor levels & all heights. The contractor will
use approved supporting system viz. Doka formwork system/ Cup lock system & no wooden
ballies etc. are allowed .
5.01 Raft, Footing, R/Wall, Column, S/case, Beam, Slab, Liftwall,& Ramp etc. Sq.m 48250 500 24125000
6.00 Reinforcement
Sl. No. Description Units Qty Rate Amount
Providing and fixing, Storing, Stacking and placing of MS/ HYSD bar Reinforcement for R.C.C in
situ and precast work including straightening, cutting, bending, placing in position, binding,
providing and tying with 20 G annealed wire all complete as per drawings, specifications and as
directed by the Engineer-in-Charge.(Rate shall include cost of binding wire, cover blocks, etc. )
(Steel will be supplied free of cost by owner) The rate to include for making of proper base for tor
steel stacking (with brick layer) , unloading with crane if required and shifting of stacks of tor
steel to facilitate the site progress works. The rate also to include as directed stacking of Tor
steel scrap, Steel stack binders and regular collection of steel scrap from site to scrap stacking
designated area on site.
6.01 Thermo-mechanically treated bars (Fe500) M.T. 1500 55000 82500000
7.00 MASONRY 0
Providing and laying 230mm thick brick work using bricks of class designation 75 in Basement/
Super structure in cement mortar 1:6 ( 1 cement : 6 coarse sand ) including, curing, joints
7.01 finished flush/raked to 12 mm depth, etc.complete as directed, cleaning and soaking the bricks cum 1500 5500 8250000
at least for 6 hours before use, curing for 7 days etc. complete at all heights/depth and for all
leads.
Providing and laying common burnt clay bricks115 mm thk confirming to IS 12894 - 2002 of
class designation 100 in half brick walls in Basement/superstructure in cement mortar 1:6 (1
cement : 6 coarse sand) including joints finished flush/raked to 6 mm depth as work proceeds
7.02 excluding mild steel reinforcement (2 Nos of 6mm dia ) at every fourth course, cleaning and sqm 2000 700 1400000
soaking the bricks at least for 6 hours before use, curing for 7 days etc. complete at all heights /
depth and for all leads.(All Internal walls). Including all scaffolding, staging, raking out joints,
curing etc. complete and as directed.
8.00 PLASTER 0
Providing & laying 12 mm thick plaster, on internal walls, in cement mortar 1:3:3 (1 cement: 3
8.01 Sqm 4995 250 1248750
coarse sand : 3 fine sand) at all levels including staging and currying, complete.
Providing & laying 6 mm thick plaster, on Ceiling, in cement mortar 1:1:2 (1 cement: 1 coarse
8.02 Sqm 2000 230 460000
sand : 2 fine sand) at all levels including staging and currying, complete.
Providing & laying two layer 20mm thick Plaster, on external surfaces, first layer with 12 mm
thickness in cement mortar 1:3:2 (1 cement: 3 coarse sand:2 fine sand),second layer with 8 mm
8.03 thickness in cement mortar 1:2:2 (1 cement: 2 coarse sand:2 fine sand), at all levels including all Sqm 25500 500 12750000
staging, currying & mixing waterproofing compound in proportion recommended by the
manufacturer. Water proofing compound paid separately.
9.00 Electrical Work 0
9.01 Providing and fixing Conducting, M.S. Box, Wiring, Switch Socket, as per approved make Sqft. 233000 75 17475000
10.00 Railing Work 0
10.01 Providing and fixing M.S. Railing, Balcony, S/case, Chajja etc. as per approved design Kg. 40000 90 3600000
TOTAL 299059350
FINISHING WORK
Sl. No. Description Unit Qty. Rate Amount
Interior Work
1 Supply and Fixing of Door frame with door shutter (as per approved ma Each 300.00 40,000.00 12,000,000
2 Supply and Fixing of Wooden Counter. (as per approved make) Sqft 1,550.00 1,250.00 1,937,500
3 Supply and Fixing of Wooden Rack. (All Class Rooms) Sqft 2,670.00 1,250.00 3,337,500
Supply and Fixing of grid false ceiling in rooms.
4 (Armstrong make grid ceiling in Rooms) Sqft 48,252.00 120.00 5,790,240
Stone Work -
Total 88,486,265
PLUMBING WORK
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
A) SANITARY FIXTURES & FITTINGS:
i) Note : The sanitaryware and CP fittings may change as per internal layout and architect consent. Out of
Roca/Kohler / Duravit ; we have selected kohler models for tentative estimate.
1.0 Providing and Fixing of vitreous china single trap syphonic pattern having back inlet, supporting chair wall
hung water closet withflush valve and CP brass flush bend (European type) Wall Hung water closet with
seat and lid, with C.P. brass hinges and rubber buffers, adapter, rubber joints fixed to W.C., C.P. brass
screwed washers including cutting and making good the walls and floors wherever required and HDPE wc
pan connector including jointing with white cement coomplete in all respects. (Make - Roca Model
Victoria Cat. No.: Rs346303460 and Seat cover RE80P397461)
-
a) 160 mm dia POLO KAL NG RM 160 1,500 240,000
b) 110 mm dia POLO KAL NG RM 405 1,200 486,000
-
2.0 Providing and laying cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm
and down gauge) 75 mm in bed and all round PP soil and waste pipe. -
a) 160 mm dia POLO KAL NG RM 1 700 700
b) 110 mm dia POLO KAL NG RM 100 600 60,000
-
3.0 Providing and fixing sound insulated POLO KAL NG piping system as per ON EN 1451-Part 1-6 & EN 12056
Part 1-5 with 3 layer pipe made of PP-C + PP-MV + PP-C in Blue Ral 5014 (halogen and calcium free) colour,
push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 21 dBA at
a flow rate of 4 l/s and having pipe ring stiffness as per 1S0/DIS 9969 and tightness as per EN 1277/B and C
and DIN 19560, with all necessary fittings in blue colour, fitted with factory fitted lip ring (Make:
POLOPLAST, Germany). ( For Indirect waste/ Wash Basin/Urinal/Sink/Floor Drain )
-
a) 40 mm dia POLO KAL NG RM 105 500 52,500
b) 50 mm dia POLO KAL NG RM 85 400 34,000
-
4.0 Providing and fixing PP 110mm P Trap with minimum 50mm water seal with rubber seal on inlet to push fit
hopper for indirect waste connections . (Make - POLOPLAST/REHAU / HULIOT ) Each 2 2,500 5,000
-
5.0 Providing, fixing, testing and commissioning of pipe inlet fittings fabricated with Polyproplene Pipe with
maximum 3 inlets 40, 50 & 75 mm OD size Polyproplene pipe, fixed to 'P' traps including Dripseal/Pipe
seal/solvent /rubber ring joint complete .(Make - POLOPLAST/REHAU / HULIOT )
-
a 160 mm dia RM 130 1,800 234,000
b 110 mm dia RM 10 1,500 15,000
-
11.0 Providing and fixing C.I. Grating (medium duty) at outlet point of rain water outlet in rain water khurra.
-
a 250 x 250 mm Nos. 4 800 3,200
-
BASEMENT DRAINAGE INSTALLATION -
-
11 Providing and fixing G.I. Pipes complete (IS:1239 C class) with G.I. Fittings e.g. elbows, tees, reducers,
unions, plugs etc.and clamps and jointing with holdite or teflon tape including chase cutting and making
good the walls etc. wherever requird for waste connection from W.B. , A.S.P., Sump Rising main etc.
Complete.
-
a 80 mm nominal bore Rm 60 1,200 72,000
-
12 Painting G.I. pipes and fittings with paint of any colour such as chocolate, grey or buff etc. over a coat of
primer (of approval quality) -
a 80 mm nominal bore Rm 60 100 6,000
-
13.00 Providing & fixing dual plate spring actuated non return valve conforming to IS 5312 with C.I. body
complete with bolts, nuts, washers & inserted rubber gasket etc. as required complete as per direction of
Engineer incharge.
-
a 80 nominal bore Each 4 500 2,000
-
14.00 Providing and fixing water type cast iron butterfly valves tested to 15kg/sqcm pressure including flanges.
-
a 80 nominal bore Each 4 6,000 24,000
-
15.00 Providing & fixing pressure gauges of not less than 100mm dia dial of pressure range 0-15 kg/cmsq
complete with shut off valve duly calibrated before installation. It shall be provided on suction & discharge
of pumps complete as per direction of Engineer incharge.
Each 4 500 2,000
-
16.00 Providing & fixing of F.R.P. Grating (Heavy Duty) for channel drains including all accessoreis complete
capable to bear 10.0 T Load. (Make - Prolong/Thermodrain / Pooja) -
a 488 wide x 40mm thk. - Drain Cover Mtr 200 1,500 300,000
-
F.R.P. MH Cover with frame 600 mm dia dimensions for basement sump. ( capable to bear 10.0 T Load ).
(Make - Prolong/Thermodrain/Pooja) Each 2 2,000 4,000
C) WATER SUPPLY SYSTEM : -
-
INTERNAL PIPING -
-
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
1 Providing and fixing of Polyethylene Raised Temperature (PE-RT) Piping system with D-2388 material as
per PN-16 in accordance with ISO 10508,PERT Grade-2 for Hot and Cold water application with
corresponding hot fusion welded PERT fittings in PN-16 like Tee's, Elbows, Sockets, Reducers, Unions, brass
adaptors (both male female) etc. conforming to ISO 10508 standards. Further all termination points
should be brass fittings only for connection with faucets. Installation guidelines should be strictly followed
as per the company's technical literature. Further the system should bear a maximum pressure of 16 Bar at
20 Degree centigrade and a pressure of 5 Bar at 95 degree centigrade.
-
a 16mm PERT Rm 505 400 202,000
b 20mm PERT Rm 110 400 44,000
c 25mm PERT Rm 200 450 90,000
d 32mm PERT Rm 125 500 62,500
e 40mm PERT Rm 80 500 40,000
f 50mm PERT Rm 40 550 22,000
-
2 Providing & Laying G.I pipes (Heavy class) (Tertiary Treatment Equipment piping) of approved make
conforming to IS:1239-1982 complete with GI fittings such as tees, crosses, plugs, sockets, elbows,
reducers, unions, glanges, sleeves pieces, check nuts. (For Roof level and Riser)
-
a 65 mm dia RM 20 1,166 23,320
b 80 mm dia RM 90 1,458 131,220
c 100 mm dia RM 35 2,092 73,220
-
3 Providing, fixing, testing and commissioning of full way level operated forged brass ball valve of brass body
with forged brass hard chrome plated steel ball tested to a pressure not lass than 15 kg/sq.cm with
threaded/flanged complete with nuts, bolts, gaskets, washers etc. as required complete as per direction of
Engineer incharge.
-
a 15 mm NB Each 8 400 3,200
b 20 mm NB Each 60 800 48,000
c 25 mm NB Each 18 1,100 19,800
d 32 mm NB Each 8 1,400 11,200
e 40 mm NB Each 6 1,700 10,200
f 50 mm NB Each 4 2,000 8,000
-
4 Providing and fixing hand lever operated cast iron butterfly valves. Operating pressure not lass than 16
kg/sq.cm with threaded/flanged complete with nuts, bolts, gaskets, washers etc. as required complete as
per direction of Engineer incharge.
-
a 65 mm NB Each 2 5,000 10,000
b 80 mm NB Each 8 6,000 48,000
b 100 mm NB Each 2 7,000 14,000
-
5.0 Providing & fixing dual plate spring actuated non return valve (pressur of 15 cm/sq.cm) conforming to IS
5312 with C.I. body complete with bolts, nuts, washers & inserted rubber gasket etc. as required complete
as per direction of Engineer incharge.
-
a 80 mm NB Each 2 500 1,000
b 100 mm NB Each 1 800 800
-
6 Providing and fixing brass auto air vent valve PN 10 rating of GIA complete suitable for domestic cold water
supply riser. -
a 15 mm dia nominal bore Each 4 1,200 4,800
-
7 Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked,
with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow
pipes but without fittings and the base support for tank.
per litre 35,000 8 280,000
-
8 Providing, fixing, testing and commissioning of motorised butterfly valve of 50mm dia for filling of
overhead water tank complete with high and low level control switches to control tanks. The level
controllers shall be installed in overhead tanks. The level switch will close the valve when water level is
high in overhead tank and open the valve when overhead water tank level is low. The system should be
complete in all respects with accessories 220 V AC / 2 V DC, IP67 electrical water level control unit, copper
control wiring in whether proof casing etc. (Make: Zooloto/Audco/Advance/AIP)
-
a 20mm PERT mtr 10 400 4,000
b 50mm PERT mtr 200 550 110,000
-
14 Providing and filling sand of grading zone V or coarse grade alround the PE-RT pipes in external work.
-
a 20mm PERT mtr 10 100 1,000
b 50mm PERT mtr 200 150 30,000
-
15 Providing & Laying G.I pipes (Heavy class) (Tertiary Treatment Equipment piping) of approved make
conforming to IS:1239-1982 complete with GI fittings such as tees, crosses, plugs, sockets, elbows,
reducers, unions, glanges, sleeves pieces, check nuts. (For Bore well to tank and Municipal line to tank)
-
a 80 mm dia RM 50 1,500 75,000
b 100 mm dia RM 25 200 5,000
-
16 Providing & Fixing of washing hydrant / Garden hydrant outlet consisting 1 No. 20mm dia. ball valve &
brass nozzle for connecting rubber hose including pipes, fittings and accesssories complete.
Nos 4 5,000 20,000
-
17.00 Constructing masonry Chamber 60x45x50 cm,inside with 75 class designation brick work in cement mortar
1:5 (1 cement:5 fine sand) for water meter complete with C.I. Doble flap surface box 400x200x200mm
(inside) with locking arrangement and RCC top slab 1:2:4 mix (1 cement : 2 corase sand: 4 graded stonr
aggregate 20mm nominal size) necessary excavation foundation concret 1:5:10 (1 cement:5 fine sand : 10
graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortor 1:3 (1 cement : 3
coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design.
-
a With F.P.S. bricks Each 2 5,000 10,000
-
18 Providing & Fixing of water meter conforming to IS and tested by Municipal Board complete -
a 50 mm dia nominal bore Each 1 8,000 8,000
-
19 Sterilization of all cold water supply lines as per specifcation with chlorine dosing. Item 1 20,000 20,000
-
20 Making 80mm Diam. water connection with local authority including approvals / liasioning, excavtion &
back filling, cutting and making good of existing Authority supply line etc. complete (Fees Payment by
Client)
Item 2 25,000 50,000
-
21 Solar Water Heaters -
Supply, erection, testing & commissioning of solar water heating system with following details : -
System temperature output : 60 degree C (during clear sunny days) -
System type : Thermo syphon -
System : Non Pressurised -
Application : Bathing / Washing / Cooking -
Type of Solar Collectors : Copper tube Flat Plate Collectors as per BIS with following specifications -
-
Size of Collector : 2080 x 1070 x 100 mm -
Number of Collector : To suit system requirement. -
Absorber area : 2 sq M -
Type : Cu - Cu -
Weight : 46 Kg (Dry) -
Absorber Coating : Selective - NALSUN -
Absorbivity : > 0.95 -
Emissivity : < 0.2 -
Frame Material : 16 SWG extruded Aluminium -
Glazing : Toughened Glass -
Glass beeding : EPDM -
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
Finish : Painted by approved shade -
electrical element -
Hardware : SS 304 -
Insulation : PUF -
Collector Stand : 35x35x3 mm MS angle -
Hot Water Tank : Cylindrical - vertical / horizontal, Stainless steel 304 grade with 100 mm thick Rock Wool
insulation including 22 SWG aluminium cladding.
-
The entire system should be complete with internal piping in SS(304) with 50 mm rock wool insulation of
density 48 kg/m3 with 26 SWG Al cladding, necessary isolation valves, Y type CI strainer, hardwares,
temperature gauge of range 0 - 120oC, water meter, MS angle iron structure of min thickness 3 mm duly
painted etc as required to complete the system in all respects.
-
The entire system should be approved by BIS as per IS : 12933 and as per local regulations. -
System Capacity : 500 liters ( storage tank of 500 litres ) per day (LPD) having 5.0 collectors. Item 1 80,000 80,000
D EXTERNAL DRAINAGE INSTALLATION -
-
1 Supplying, laying, jointing, testing and commissioning of uPVC Foamcore pipes conforming to IS 16098 -
Part-1 with SN4 rubber ring/Solvent cement joints including all necessary fittings for underground
drainage on compacted filled soil below ground level. (Make - ASHIRWAD / FINOLEX )
-
a 160 mm diameter Rm 45 1,800 81,000
b 250 mm diameter Rm 45 2,500 112,500
-
2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm
nominal size) alround uPVC pipes including bed concrete as per standard design.
-
a 250 mm diameter Rm 80 500 40,000
-
3 Providing and fixing square-mouth S.W. gully trap grade ‘A" complete with C.I. Grating, brick masonry
chamber with bricks of class designation 75 in cement mortar 1:5 (1 cement : 5 coarse sand) inside plaster
above trap 12 mm thick m cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of
neat cement outside plaster 12 mm thick in cement mortar 1:3 (1cement :3 coarse sand) 10 cm thick
foundation concrete 1:5:10 mix (1cement :5 coarse sad : 10 graded stone aggregate 40 mm nominal size)
space between chamber, and trap filled-with cement concrete 1:2:4 (1cement :2 coarse sand :4graded
stone aggregate 20 mm nominal size) and water tight C.I. cover with frame of 300 x 300 mm size (inside)
the weight of cover to be not less than 4.50 kg frame to be not less than 2.70 kg as per standard design.
-
a 180x150mm size P type With FPS bricks Each 1 8,000 8,000
-
4 Construction brick masonry manhole with 75 class designation bricks in cement mortar 1:4 (1 cement : 4
coarse sand) RCC top slab with 1:2:4 mix (1 cement : 2 coarse sand 4 graded stone aggregate 20mm
nominal size) foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm
nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished
with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement
complete as per standard design.
-
a Inside size 120 X 90 cm. and 90 cm. deep including CI cover with frame (medium duty) 500 mm internal
diameter, total weight of cover and frame to be not less than 116 kg (wt of cover 58 kg and wt. of frame 58
kg.)
-
With FPS bricks Each 4 9,000 36,000
-
6 Extra for depth for manhole with F.P.S. bricks -
a size 1.2m X 90 cm m 2 3,000 6,000
-
7 Providing and fixing of orange colour safety rest of minimum 6 mm thick plastic encapsulated as per
IS:10910 on 12 mm dia steel bar conforming to IS: 1786 having minimum cross section as 23 mm x 25 mm
and over all minimum length 263 mm width as 165 mm with minimum 112 mm space between protruded
legs having 2 mm as per standard drawing and suitable to withstand the bend test and chemical resistance
test as per specifications and having manufacturer's permanent identification mark to be visible even after
fixing, including fixing in manholes with 30 x 20 x 15 cm cement concrete block 1:3:6 ( 1 cement : 3 coarse
sand : 6 graded stone aggregate 20 mm nominal size ) complete as per design.
-
a All kinds of soil -
b Pipes, cables etc exceeding 80 mm dia but not exceeding 300 mm dia RM 80 100 8,000
-
9 Making 260mm Diam. Sewage connection with existing sewage line Item 1 10,000 10,000
-
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
10.0 Construction brick masonry grease trap of 1.2 m x 0.6m x 0.6 m having 230mm thick brick wall upto
900mm and 345mm thick above 900mm with 1:2:4 mix (1 cement : 2 coarse sand 4 graded stone
aggregate 20mm nominal size), 100 mm thick RCC top slab with 1:2:4 mix (1 cement : 2 coarse sand 4
graded stone aggregate 20mm nominal size), 100mm thick P.C.C. 1:4:8 mix (1 cement : 4 coarse sand : 8
graded stone aggregate 40 mm nominal size), Inside plastering 12 mm thick with cement mortar 1:3 (1
cement : 3 coarse sand) finished with floating coat of neat cement on all inside surface, 3 Nos. 750x750 SS
perforated tray and 90 Kg M.S. cover with frame complete as per standard design.
-
a 160 mm diameter Rm 24 1,800 43,200
b 250 mm diameter Rm 105 2,500 262,500
c 315 mm diameter Rm 5 3,000 15,000
-
2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm
nominal size) haunching bed concrete for uPVC pipes as per standard design. -
a 160 mm diameter Rm 24 500 12,000
b 250 mm diameter Rm 105 500 52,500
c 315 mm diameter Rm 5 800 4,000
-
3 Constructing brick masonry road gully chamber with bricks of class designation 75 in cement mortar 1:5 (1
cement : 5 fine sand) including FRP perforated grating (capable to bear 60.0 T Load.) with frame complete
as per standard design:
-
With FPS bricks -
Internal size 600x600x1000mm average depth Each 13 9,000 117,000
-
4 Extra for depth for manhole with F.P.S. bricks -
a size 60X 60 cm m 2 2,000 4,000
-
5 Constructing masonry Chamber 90x60x50 cm,inside with 75 class designation brick work in cement mortar
1:5 (1 cement:5 fine sand) for water meter complete with C.I. Doble flap surface box 400x200x200mm
(inside) with locking arrangement and RCC top slab 1:2:4 mix (1 cement : 2 corase sand: 4 graded stonr
aggregate 20mm nominal size) necessary excavation foundation concret 1:5:10 (1 cement:5 fine sand : 10
graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortor 1:3 (1 cement : 3
coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design.
-
a With F.P.S. bricks Each 1 10,000 10,000
-
6.0 Excavating trenches of required width for pipe, cables etc including excavation for sockets & dressing of
sides, ramming of bottoms, depth upto 1.5m including getting out the excavated soil & then returning the
soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by
ramming, watering etc and disposing of surplus excavated soil as directed, within lead of 50m.
-
All kinds of soil -
a Pipes, cables etc exceeding 80 mm dia but not exceeding 300 mm dia RM 134 150 20,100
-
7 Providing and constructing Rain water Harvesting Pit of 4000 dia. x 3000 mm size depth (internal) in overall
size with inlet & outlet connection with Upto 1500mm from ground level Ist class brick 230 mm thick in
cement mortar 1:4 (1 cement: 4 coarse sand) inside and outside 12 mm thick plaster with cement mortar
1:3 (1 cement : 3 coarse sand) with a floating coat of neat cement on inside surface, After 1500mm depth
500 mm thicksand bed; then 500mm thick gravel and 500mm thick boulders. FRP for 20T Load, cover 560
mm including necessary excavation backing filling, disposal of surplus earth, Providing and fixing of poly
propelene coated rungs @ 300 mm c/c complete as per standard design.
-
a Constructing Rain Water Harvesting Pits. Item 1 80,000 80,000
b 350mm diameter boring with 150mm dia, upvc slotted pipes located centrally in 350mm diameter bore
filled with boulder. Meter 40 1,000 40,000
-
8.0 Providing and fixing 210mm dia. uPVC pipes (6 Kg/sqcm) including all fittings, excavation and back filling
for connecting over flow from rain water harvesting pits to external network. Rm 20 1,800 36,000
-
9.0 Providing and constructing masonry desilting chamber of size 150x120x150 cms inside with 75 class
designation brick work 230mm thick in cement mortar 1:5 (1cement:5 fine sand), F.R.P. cover with Frame
heavy duty 560mm dia and 200 mm thick R.C.C. top slab 1:2:4 mix(1 Cement : 2 coarse sand : 4 graded
stone aggregate 20mm nominal size), foundation concrete 1:5:10 mix (1 cement : 5 fine sand : 10 graded
stone aggregate 40mm nominal size) below masonry walls with 75mm projection at either side including
excavation, back filling, compaction and disposal of surplus earth upto a lead of 50 Metre., poly propelene
coated rungs @ 300 mm c/c .
Each 1 15,000 15,000
-
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
10.00 Making Storm connection with municipal line including approvals/ liasioning, excavtion & back filling, Item
cutting and making good of existing municiapl line & approval from Pollution Control Board etc. complete
(Payment by Client)
1 25,000 25,000
-
TOTAL OF EXTERNAL STORM WATER DRAINAGE CARRIED OVER TO SUMMARY -
-
F WATER SUPPLY, DRAINAGE PUMPS AND WATER TREATMENT PLANT -
-
1 Raw Water Treatment Feed Pump set Set 1 25,000 25,000
Providing, fixing, commissioing and testing package vertical raw water pumps, comprising of 2.0 nos.
Electrical Driven inline pumping sets each of 1.5 LPS to a head to 35 meter (1 working + 1 stand by) with all
accessories, Pumps shall be with C.I. Base, S.S 304, impeller, shaft, mechanical seal, S.S. Shaft directly
coupled to motor suitable for operation on 400/440 volts, 3 phase 2900 RPM. TEFC electronic motor
mounted on a common channel baseplate 150mm dia pressure gauge, GM isolation cock and cement
concrete foundation with plaster with dunlop cushy foot mountings with all accessories such as NRVs,
valves, pressure guage bourden type, common suction and delivery header, bellows on sucton and
delivery side complete in all repsects.
-
Pumps shall be suitable for 415 ± 10% volts 3 phase 50 Hz A.C supply & shall be having the following
requirement complete with foundation and associated civil works. -
Suction & Delivery Header - SS 304 -
Control Valve On suction and Delivery - Ball Valve Only (No Butterfly Valve Accepted). -
Flow Prevention - Only Check Valve -
Suction & delivery header including all pipes, suction & delivery sides valves, NRV, Pressure gauges &
accessories complete. -
Flow Rate : 1.5 LPS -
Head : 35 M -
Min. Motor HP : 1.5 H.P. (Each) -
. -
2 Treated Water Supply Pumps Set 1 25,000 25,000
-
Providing, fixing, commissioing and testing package vertical treated water transfer pumps, comprising of
2.0 nos. Electrical Driven inline pumping sets each of 2.0 LPS to a head to 70.0 meter (1 working + 1 stand
by) with all accessories, Pumps shall be with C.I. Base, S.S 304, impeller, shaft, mechanical seal, S.S. Shaft
directly coupled to motor suitable for operation on 400/440 volts, 3 phase 2900 RPM. TEFC electronic
motor mounted on a common channel baseplate 150mm dia pressure gauge, GM isolation cock and
cement concrete foundation with plaster with dunlop cushy foot mountings with all accessories such as
NRVs, valves, pressure guage bourden type, common suction and delivery header, bellows on sucton and
delivery side complete in all repsects.
-
Pumps shall be suitable for 415 ± 10% volts 3 phase 50 Hz A.C supply & shall be having the following
requirement complete with foundation and associated civil works. -
Suction & Delivery Header - SS 304 -
Control Valve On suction and Delivery - Ball Valve Only (No Butterfly Valve Accepted). -
Flow Prevention - Only Check Valve -
Suction & delivery header including all pipes, suction & delivery sides valves, NRV, Pressure gauges &
accessories complete. -
Flow Rate : 2.0 LPS -
Head : 70 M -
Min. Motor HP : 4.0 H.P. (Each) -
-
4 Sump Pumps -
Supply & Installation, testing and commissioning of centrifugal non clogging submersible sump pumps for
plant room drainage. Pump capable capable of handling 25 mm dia soft solids. Motor suitable for 415 +
10% volts, 3 phase, 50 Hz AC Power supply. Pumps shall be suitable for automatic/manual operation
(Overall depth of sump – 1.5 M). Submersible sump pump shall be provided with dry running protection.
Inclusive of supporting arrangement for stationary type.
-
Two nos. of pump installed in one sump pit 1 working & 1 standby with automatic/manual opration as
requireds. -
-
a Waste Water Drainage Sump Pump - Pump room Each 2 25,000 50,000
Flow rate : 4.0 LPS -
Head : 22.5 Mtrs. -
Min. Motor HP : 2.0 (Each) -
-
b Waste Water Drainage Sump Pump - Basement Each 2 25,000 50,000
Flow rate : 4.0 LPS -
Head : 22.5 Mtrs. -
Min. Motor HP : 2.0 (Each) -
-
WATER TREATMENT PLANT -
-
6 Supply & installation, testing & commissioning of sand filter having FRP pressure vessel suitable for test
pressure of 7 Kg. / cm2 including valves for back-wash arrangement complete with initial charge of media
to remove the total suspended particles from the water.
Each 1 10,000 10,000
Capacity : 1.5 LPS -
Working Pressure : (5 ± 2.5)MWC -
-
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
7 Supplying, storing, handling, installation, testing & commissioning of Activated Carbon Filter having FRP
pressure vessel suitable for test pressure of 7 Kg./cm2 including valves for back-wash arrangement
complete with initial charge of media to remove the total suspended particles from the water.
-
a INCOMER -
100 A TP MCCB with heavy duty solid neutral link with (0-100A) ammeter with 3 CT and selector switch, (0
- 500 V) voltmeter with selector switch, phase indication light with protection fuse. - 01 Set
-
-
b OUTGOINGS -
-
For 2.0 x 1.5 HP Filter Feed Pumps -
12 A TP MCB with 10 A DOL starter, overload relay, 96 mm (0-25A) ammeter with single CT, start / stop
push buttons, on / off / trip indication lights with protection fuse, single phase preventer. - 01 set.
-
-
For 2.0 x 4.0 HP Water Tranesfer Pumpset -
25 A TP MCB with 12 A DOL starter, overload relay, 96 mm (0-40A) ammeter with single CT, start / stop
push buttons, on / off / trip indication lights with protection fuse, single phase preventer. - 01 set.
-
-
For 2 x 2.2 HP Waste Water Transfer Pumps - only feeder to sub panels. -
12 A TP MCB with 10 A DOL starter, overload relay, 96 mm (0-25A) ammeter with single CT, start / stop
push buttons, on / off / trip indication lights with protection fuse, single phase preventer. - 01 set.
-
-
For 4 x 2.2 HP Waste Water Transfer Pumps - only feeder to sub panels. - For Basement -
25 A TP MCB with Isolator - 2 sets -
-
2 SUB - PANELS FOR 1.0 NOS 2.2 HP WASTE WATER SUMP PUMPS. Item 1 60,000 60,000
Supply, installation, testing and commissioning of Cubical type sectionalised floor standing switch board of
31 MVA fault capacity at 415 V complete with 3.5 strip, 40 A capacity Aluminium Bus - Bar Electrolytic
grade, cable alley, switchgears of following capacity & as per specifications.
-
-
a INCOMER -
40 A TP MCB with (0-40A) ammeter with 3 CT and selector switch, (0 - 500 V) voltmeter with selector
switch, phase indication light with protection fuse. - 06 Set -
-
b OUTGOINGS -
32A TP MCB, 32 A DOL starter, overload relay, start / stop push buttons, phase indication lights with
protection fuse, on / off / trip indication lights with protection fuse, including single phase preventer. -
06SET
-
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
-
NOTE : -
i) All the drainage pumps shall be work cyclic process i.e. in first operation duty pump work on duty and
stand by pump duty pump work on stand by and stand by pump work as duty pump. -
-
ii) The drainage Stand by pumps automatically work as drainage assist pump for Duty pump when level of
water rises in drainage sump pumps i.e. Both pumps can work at a time & operation shall be controlled
with the help of level controllers and float switches.
-
-
POWER & CONTROL CABLING -
-
Supply, laying, testing and commissioning of power and control cabling, as per Standard specification
3 including end termination as required. -
-
Power cabling (XLPE) insulated and PVC sheathed, armoured, Aluminium Conductor of 1.1 KV grade on
a existing cable trays). -
3C x 10 Sq. mm RMT 65 300 19,500
3C x 6 Sq. mm RMT 115 200 23,000
-
Control Cabling (PVC insulated and PVC sheathed, armoured, Copper Conductor of 1.1 KV grade on
4 existing cable trays). -
a 5C x 1.5 Sq. mm RMT 180 400 72,000
-
5 Earthing Strip / Wires. -
-
a Providing and fixing 25 x 5 mm copper strip in 40 mm RMT 45 1,100 49,500
Providing and fixing 25 x 5 mm copper strip on surface or in recess for connections etc. as required.
b RMT 55 1,100 60,500
c Providing and fixing 4.0 mm dia. Copper wire on surface or in recess for loop earthing as required. RMT 75 120 9,000
-
d Supply & laying of rubber mat of size 1000 mm & 12 mm thick. RMT 10 1,300 13,000
-
6 Supply and installation of ladder type 16G ms cadmium plated 'U' shaped channel 40mm x 20mm cable
tray of following sizes: -
a 150 mm wide RMT 25 900 22,500
b 300 mm wide RMT 30 950 28,500
H SBR Based Sewage Treatment Plant -
Supplying, installation, testing & commissioning of Sewage Treatment Plant for the following duty:
-
-
Nature of waste water - Sewage -
-
Daily average flow - 20 cum/day -
-
Influent Characteristics -
pH - 8 -
BOD5 - 250- 300 mg/liter -
S. Solids - 250 mg/liter -
COD - 400-600 mg/liter -
Oil & Grease ` - <50 mg/liter -
-
Effluent discharge standard : -
pH - 6.5-8.0 -
BOD5 - Less than 10 mg/liter & < 5 after GRA-UOT -
S. Solids - Less than 10 mg/liter -
COD - Less than 50 mg/liter -
Oil & Grease - < 5 mg/lt -
-
Reuse of STP treated water after treatment. Horticulture, Landscaping, irrigation, flushing etc.
-
-
NOTE -
(1) All Civil works finished with water proofing, plaster, snowcem, structure duly tested for leak-proofing,
plant room flooring etc and related S.S/MS/CI works such as supply and fixing of handrails, manholes,
gratings, grills, doors, vents, footrests etc shall be in the scope of the STP Client. Supply and fixing of
puddle flanges will in the scope of Civil Contractor/ Client. -
-
(2) Contractor shall ensure submission of detailed GA drawings (Plan & Section), P & I diagram, schematic
diagram for the above mentioned components and additional components such as inserts, puddle flanges,
vent pipes etc. if so required for the complete automatic working of the STP and have it approved by the
Owner / Consultants. -
-
Part (A) -
STP -
1 Supply, installation, testing & commissioning of Screens
2 Nos.Mild Steel Suitable Sized Manually operated Bar Screen made of MS in RCC screen channel as per
Nos 2 500,000.00
following specifications 1,000,000
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
Cleaning :- Manual Screen -
MOC :- Complete in MS -
-
2 Supply, installation, testing & commissioning of Raw sewage Transfer pumps with suitable solid handling
capacity with CI casing & CI impeller complete with all accessories, motor of required capacity. The pumps
Nos 2 20,000.00
shall be complete with Delivery header with, pressure gauge on delivery line with isolation level controller
(with wiring) to control the level of Sump automatically. Pumps shall have following duty: 40,000
Pumps = 02 Nos.(1w + 1s) -
Flow rate (each) = 1.6 m³/hr -
Head = 8-10 m -
Make = Crompton/WILO/Eqv. -
-
3 Providing and fixing all interconnecting exposed plant piping of required MOC as MS/GI/PVC/CPVC/UPVC
Lot 1 50,000.00
and isolation control valves for making the piping arrangement complete within the battery limits. 50,000
-
4 Supply, installation, testing & commissioning of SBR Based Biological system comprising of the following
Lot 1 50,000.00
equipments: 50,000
-
Air Blowers For SBR tanks -
Capacity : 20-30 m3/hr @ 5000-5500 mmwg -
Type Twin Lobe -
Qty -2 Nos. (1 w+1s) -
-
Fine Bubble Diffusers -
Qty: 1 Lot -
-
Decanter system -
Qty -1 Nos. -
Type : Moving/Floating Type Decanter, motor driven with a Moving Arm for decantation of supernatant
-
Weir loading rate shall be around 2 m3/min/m -
Length of the arm shall be derived by taking moving angle around 55-60® -
MOC : SS-304 -
Make: PS Aqua Pvt. Ltd./Grannus Water Pvt. Ltd. -
-
Pipes and fittings for Air piping and Air Grid -
Qty-1 Lot -
-
Level transmitter/controller and accessories -
Qty-1 Lot -
-
PLC for SBR system -
Qty -1 Set -
Make: PS Aqua Pvt. Ltd. -
-
5 Supplying, installing, testing, commissioning of Centrifugal Horizontal Filter Feed pumps Complete in CI
body& CI impeller with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line.
Isolation valve, strainer at suction. The pump shall be suitable for 415±10% volts 3 phase AC supply . Nos. 2 60,000 120,000
Pumps = 02 Nos.(1w + 1s) -
Flow rate (each) = 1 m³/hr -
Head = 25 - 30 m -
Make - Kirloskar/Eqv -
-
6 Supply, installation, testing & commissioning of Sludge transfer pumps for sludge Feeding to filter press
complete with all the accessories, motor of required capacity. The pumps shall be complete with Base
frame, Delivery header with pressure gauge on delivery line . Nos 2 60,000 120,000
Pumps = 02 Nos.(1w + 1s) -
Flow rate (each) = 0.5 m³/hr -
Head = 8-10 m -
Make - Kirloskar/Eqv -
-
7 Supply, installation, testing & commissioning of Sludge feed pumps for sludge Feeding to sludge bag
system complete with all the accessories, motor of required capacity. The pumps shall be complete with
Base frame, Delivery header with pressure gauge on delivery line . Nos 2 60,000 120,000
Pumps = 02 Nos.(1w + 1s) -
Flow rate (each) = 0.5-1 m³/hr -
Head = 8-10 m -
Make - Kirloskar/Eqv -
-
8 Supplying, Installation, testing and commissioning of Chemical dosing system compromising of Sintex Tank
with inlet/ outlet connection, piping and valves alongwith metering pump for dosing. Set 1 70,000 70,000
-
9 Supplying, installing, testing, commissioning of Sludge Bag system of suitable size for the dewatering of
sludge generated per day. Set 1 70,000 70,000
S. NO DESCRIPTION UNIT QTY RATE (Rs.) AMOUNT(Rs.)
Mode of operation: Manual -
-
10 Supplying, installation, testing & commissioning of FRP vessel filter with frontal piping and Valves with all
the required accessories. Filter shall include media, standard fittings like pressure gauges, sampling cock,
rinse drain. -
-
Multigrade Sand Filter No. 1 15,000 15,000
Dia : 300 mm -
HOS: 1300-1500 mm -
Filter media: Fine and coarse sand, pebbles and gravels -
Make: PS AQUA Pvt. Ltd./Eqv. -
-
Activated Carbon Filter No. 1 15,000 15,000
Dia : 300 mm -
HOS: 1300-1500 mm -
Filter media: Activated Carbon, fine and coarse sand, pebbles and gravels -
Make: PS AQUA Pvt. Ltd./Eqv. -
-
Flushing/Soft Water Supply Pumps -
-
11 Providing, fixing, commissioing and testing package vertical Flushing/Soft water transfer pumps,
comprising of 2.0 nos. Electrical Driven inline pumping sets each of 2.0 LPS to a head to 70.0 meter (1
working + 1 stand by) with all accessories, Pumps shall be with C.I. Base, S.S 304, impeller, shaft,
mechanical seal, S.S. Shaft directly coupled to motor suitable for operation on 400/440 volts, 3 phase 2900
RPM. TEFC electronic motor mounted on a common channel baseplate 150mm dia pressure gauge, GM
isolation cock and cement concrete foundation with plaster with dunlop cushy foot mountings with all
accessories such as NRVs, valves, pressure guage bourden type, common suction and delivery header,
bellows on sucton and delivery side complete in all repsects.
Total 10,795,935.00
FIRE FIGHTING WORK
S.NO. DESCRIPTION UNIT TOTAL QTY. RATE (Rs.) AMOUNT (Rs.)
S I FIRE FIGHTING PLANT ROOM EQUIPMENTS
1 Supply, installation, testing and commissioning of fire authority approved fire fighting pumps,
electrically driven generally as specified and shown in equipment schedule complete with:
a Fire Hydrant Main Fire Pump
Supply, installation, testing and commissioning of fire authority approved horizontal single stage, single
outlet pumping set with bronze impeller, C.I. body and connected by a flexible coupling to a totally
enclosed fan cooled induction motor mounted on a common structural base plate with RCC base and
with all pump accessories, including pressure switch, pressure gauge ( both with cut off ball valves )
complete as per specifications. Motor to be suitable for 415 volts, 3 phase, 50 cycles A.C. supply
(specifications as per fire fighting requirements and on the pattern of TAC or local authority approval) as
per instruction and specifications.
-
a 250 nominal bore Each 0 - -
b 200 nominal bore Each 1 11,270 11,270
c 150 nominal bore Each 12 9,085 109,020
d 100 nominal bore Each 2 6,670 13,340
e 80 nominal bore Each 2 5,635 11,270
S.NO. DESCRIPTION UNIT TOTAL QTY. RATE (Rs.) AMOUNT (Rs.)
9 Providing, Installation, Testing and Commissioning of wafer type spring loaded dual plate non return -
valve as per PN-1.6 API 594 with IS:1865 Ductile Iron Body, Nitrile seat, ASTM A351 CF8 SS Disc, Shaft,
Spring and stop rod AISI SS304 SS and Tested as per API 598 Class 150 along with rubber gasket, GI bolts,
nuts, washers etc. as required. (MAKE - ZOLOTO/
NEU-G/LEADER/SANT)
-
a 200 nominal bore Each 1 15,525 15,525
b 150 nominal bore Each 6 9,775 58,650
c 100 nominal bore Each 1 7,820 7,820
d 80 nominal bore Each 1 6,095 6,095
10 Supplying, Installation, Testing and Commissioning of CI body flanged (both ends) type serviceable -
suction / Y strainer with (stainless steel / brass mesh) conforming to relevant IS specifications amended
upto date complete including providing and fixing nuts, bolts, washers, gaskets etc. complete as
required. (MAKE - ZOLOTO/ NEU-G/LEADER/SANT)
-
a Size 150mm Each 2 28,750 57,500
11.00 Supply, installation, testing and commissioning C.I. flanged double air valves size 25mm with 25mm SS 17,250
isolation valve etc. all complete. (MAKE - ZOLOTO/ NEU-G/LEADER/SANT) Each 2 34,500
12.00 Providing, fixing, testing and commissioning of full way level operated forged brass ball valve of brass -
body with forged brass hard chrome plated steel ball tested to a pressure not lass than 15 kg/sq.cm with
threaded/flanged complete with nuts, bolts, gaskets, washers etc. as required complete as per direction
of Engineer incharge. (MAKE - ZOLOTO/ NEU-G/LEADER/SANT)
-
a 25 mm NB Each 2 1,208 2,415
b 50 mm NB Each 2 2,530 5,060
13 Supply, fabrication & laying heavy grade IS marked “C” class heavy duty MS pipe piping complete with -
all fittings, pipe supports, clamps etc. as approved with weleded jointing for external hydrant system.
Thes pipes shall be provided with 4.0mm thick weather proof treatment like covering with pypkote
complete. (MAKE - Jindal Hissar / Tata /Prakash Surya )
-
a 150 nominal bore M 175 2,110 369,294
b 100 nominal bore M 10 1,225 12,248
14 Excavation upto hard murram as per general profiles and back filling in all kind of soil Cum 9 173 1,553
15 Making 1:2:4 cement concrete supports and thrust blocks generally as per required and approved. 5,750
Cum 1 5,750
16.00 Providing, fixing, jointing and testing of (Class-C/Heavy duty) MS Pipe IS:1239 / 3589 marked, with -
accessories like tees, elbows, flanged joints, reducers, compressed asbestos gaskets, nuts and bolts
including using modular pipe support. complete as required for delivery/suction manifold relating to
the pumps including painting of two coats of Red Oxide including all civil breakages and making good
the same. The rate includes the cost of installing DI threaded fittings UL listed & FM approved for pipe
sizes upto 50mm dia and grooved fittings UL listed & FM approved listed for jointing pipe sizes above
50mm dia. No welding is to be done anywhere in the fire fighting system. All work is to be carried out as
per the specifications
-
The support channel should be made up of cold rolled steel of quality DX51 or greater. The Support -
channel should be pre-galvanised with minimum GSM of 275 and should have universal mounting slot
on the front of the rail for accurate positioning of fasteners and system compatible round and long holes
on back of the rail the pipe. -
The pipe clamps should be split type with EPDM inner rubber lining, FM/UL approved. - -
Threaded rod should be of 4.8 stregth class and necessary accessories should be of 8.8 strength class. -
-
Make for MS Pipe: Jindal (Hisar), Prakash Surya, Tata Metallics, - -
DI Threaded Fittings for pipe size upto 50mm dia: (Make - NEW, Victaulic, Tyco) - -
Grooved Fittings for pipe sizes above 50mm dia: (Make - NEW, Victaulic, Tyco) - -
a 250 mm nominal bore (Class C) Rm 25 4,025 100,625
b 200 mm nominal bore (Class C) Rm 35 3,278 114,713
c 150 mm nominal bore (Class C) Rm 210 2,110 443,153
d 100 mm nominal bore (Class C) Rm 10 1,225 12,248
e 80 mm nominal bore (Class C) Rm 10 943 9,430
f 65 mm nominal bore (Class C) Rm 10 719 7,188
g 25 mm nominal bore (Class C) Rm 20 426 8,510
17 Supply, installation, testing and commissioning ss orifice plates in pipelines to reduce pressure from 8 1,035
kg. to 3.5kg/ sq.cm. (MAKE - NEWAGE MUMBAI/ MINIMAX /LIFE GUARD) Each 20 20,700
18.00 Preparation of working drawing, getting approval from statutory/ local fire authority at all stage of work 172,500
including inspection of authorities, obtaining licences from authorities including incidental changes etc.
complete in all respect.
Job 1 172,500
S.NO. DESCRIPTION UNIT TOTAL QTY. RATE (Rs.) AMOUNT (Rs.)
19.00 Supply and fixing 4 way fire brigade connection of cast iron body with 4 Nos Gun metal Male 10,350
instantaneous inlet couplings complete with cap and chain as required for 150mm dia MS pipe
connection, conforming to IS 904 as required.
Each 2 20,700
20.00 Supply and fixing 2 way fire brigade connection of cast iron body with 2 Nos Gun metal Male 7,475
instantaneous inlet couplings complete with cap and chain as required for 100mm dia MS pipe
connection, conforming to IS 904 as
Each 1 7,475
S III SPRINKLER SYSTEM -
21 Supply, installation, testing and commissioning of 150 mm dia Installation Control Valve inclusive of 2 40,825
nos 150 mm dia Butterfly Valve, trainer, Alarm Valve with Water Motor Gong, Pressure Gauges, Test
Lines with Ball Valves with necessary GI (H) piping with threaded fittings of required sizes complete.
Set 1 40,825
22 Supply, installation, testing and commissioning of 150 mm dia Zonal Control Valve inclusive of 1 nos 150 25,300
mm dia butterfly valve, 150mm diam. non return valve, Flow Switch, water pressure gauges & 25 mm
dia. Auxillary Drain valve with sight glass with necessary GI (H) piping with threaded fittings of required
sizes complete.
Set 11 278,300
23 Supply, installation, testing and commissioning of 100 mm dia Zonal Control Valve inclusive of 1 nos 100 -
mm dia butterfly valve, 100mm diam. non return valve, Flow Switch, water pressure gauges & 25 mm
dia. Auxillary Drain valve with sight glass with necessary GI (H) piping with threaded fittings of required
sizes complete.
Set 0 -
24 Providing and fixing 100 mm dia Pressure Gauges on Sprinkler Headers including Ball Valves. Each 1 1,265 1,265
25 Providing and fixing 15 mm dia gunmetal quick response sprinkler head with quartz bulb and set to -
operate at specified temperature. Sprinkler head shall carry UL-FM approval (Make : Tyco / Viking /
Newage Mumbai).
-
Temperature of operation 68 deg.C. - -
a Pendent/Upright type Sprinkler Each 930 362 336,893
b Side wall type Each 65 339 22,051
26 Providing and fixing 25 mm dia, UL-FM approval flexible stainless steel (SS 304) pipe for making final -
connection of sprinkler head with sprinkler system piping network including 2 nos. 25mm diameter G.I.
connector, G.I. Nipple, Reducer, elbow and threaded jointing complete as per detail. (Make
Tyco/Newage Mumbai/VIKING )
-
a 1200mm long Each 2 2,933 5,865
27 Providing, fixing, jointing and testing of (Class-C/Heavy duty) MS Pipe IS:1239 / 3589 marked, with -
accessories like tees, elbows, flanged joints, reducers, compressed asbestos gaskets, nuts and bolts
including using modular pipe support. complete as required for delivery/suction manifold relating to
the pumps including painting of two coats of Red Oxide including all civil breakages and making good
the same. The rate includes the cost of installing DI threaded fittings UL listed & FM approved for pipe
sizes upto 50mm dia and grooved fittings UL listed & FM approved listed for jointing pipe sizes above
50mm dia. No welding is to be done anywhere in the fire fighting system. All work is to be carried out as
per the specifications
-
The support channel should be made up of cold rolled steel of quality DX51 or greater. The Support -
channel should be pre-galvanised with minimum GSM of 275 and should have universal mounting slot
on the front of the rail for accurate positioning of fasteners and system compatible round and long holes
on back of the rail the pipe. -
The pipe clamps should be split type with EPDM inner rubber lining, FM/UL approved. - -
Threaded rod should be of 4.8 stregth class and necessary accessories should be of 8.8 strength class. -
-
Make for MS Pipe: Jindal (Hisar), Prakash Surya, Tata Metallics, - -
DI Threaded Fittings for pipe size upto 50mm dia: (Make - NEW, Victaulic, Tyco) - -
Grooved Fittings for pipe sizes above 50mm dia: (Make - NEW, Victaulic, Tyco) - -
a 150 mm nominal bore Rm 120 2,110 253,230
b 100 mm nominal bore Rm 165 1,225 202,084
c 80 mm nominal bore Rm 280 943 264,040
d 65 mm nominal bore Rm 230 719 165,313
e 50 mm nominal bore Rm 310 685 212,474
f 40 mm nominal bore Rm 290 253 73,370
g 32 mm nominal bore Rm 95 523 49,709
h 25 mm nominal bore Rm 1975 426 840,363
28 Providing and fixing blank flange with butterflu valve for tested pressure of 16 kg/sq.cm. of the following -
size including providing necessary union/flange. -
a 100 mm dia No 8 7,820 62,560
S IV PORTABLE FIRE EXTINGUISHERS & EXIT SIGNAGES - -
S.NO. DESCRIPTION UNIT TOTAL QTY. RATE (Rs.) AMOUNT (Rs.)
32 Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylindrical body, -
internal discharge tube, discharge nozzle, suspension bracket, conforming to IS 2878, finished
externally with red enamel paint and fixed to wall with brackets complete with internal charges. (MAKE
- MINIMAX/ KANEX/CEASEFIR)
-
a Capacity 4.5 kg Each 6 5,779 34,673
33 Providing & Fixing of stored pressure Fire Extinguisher ABC powder type (Mono Ammonium Phosphate -
Powder) Magnetic Pressure Gauge having the facility to check at site, Discharge Time less than 9 Secs,
Controllable discharge mechanism, Range minimum 4 Meters, applicable on Class A,B,C and electrically
started Fire, A Rating- 21A, B Rating 55B as per BS EN-3 BIS 15683 marked, Can Construction : Deep
drawn & CO2 Mig welded, Valve Construction : Forging & Machining, Internal Coating of Can : Epoxy
Powder coating, External Coating ofCan : Epoxy Polyster Powder coating, Sheet metal thickness :
1.60MM, Helium LeakDetection Tested, Warranty. (MAKE - MINIMAX/ KANEX/CEASEFIRE)
-
a 6 kg Mono ammonium phosphate (ABC) type cartridge operated extinguishers Each 31 3,680 114,080
b 2 kg Mono ammonium phosphate (ABC) type cartridge operated extinguishers Each 2 1,058 2,116
34 Providing and fixing Fire buckets round bottom type enamel painted, white inside & Red out side and 6,325
Letter "FIRE" in black out side and handle with mounting bracket. Nos 4 25,300
35 Providing and fixing Fire bucket stand fabricated by MS angles to install 2 Nos. of buckets. Nos 4 6,325 25,300
36 Providing and fixing mechanical foam type Trolley Mounted Fire Extinguisher of bearing to 74,750
IS:10568/IS13385/IS13386 with dis (MAKE - MINIMAX/ KANEX/CEASEFIRE) Nos. 1 74,750
a Capacity 50 Lit. - -
37 Providing and fixing Carbon Dioxide Type Trolley Mounted Fire Extinguisher of as per IS: 2878 with -
discharge time of 10 to 20 sec/15 to 36sec/20 to 60sec respectively. (MAKE - MINIMAX/
KANEX/CEASEFIRE)
-
a 22.5 Kg. CO2 Fire Extinguisher (trolley mounted) Nos. 1 80,500 80,500
S. V ELECTRICAL WORKS FOR FIRE INSTALLATION WORKS -
38 CUBICAL FIRE PANEL BOARD -
Fabricating, supplying, testing and commissioning of electrical control panel of cubicle construction,
floor mounted type, fabricated out of 2mm thick crca sheet, compartmentallised and hinged lockable
doors, dust and vermin proof, powder coated approved shade after 7 tank treatment process, cable
alley interconnection, having switchgears and accessories mounting and internal wiring, earth terminals,
numbering etc., complete in all respects, suitable for operation on 415V, 3 phase 50 Hz., AC supplywith
enclosure protection class IP-42as required.
No. 1 297,000 297,000
COMMON PANEL IN FIRE PUMP HOUSE. -
INCOMER -
400 Amps. TP & N SFU with HRC fuses. -
Voltmeter (0-500 Volts) with selector switch. -
Ameter (0- 400 Amps.) with selector switch & CT's etc. -
A) Set of 3 phase indicating lamp. -
Set of Each bus bar 100 Amps. -
OUTGOING. -
B) Main fire pump and Sprinkler pump -
100 Amps. TP& N SFU with HRC fuses with suitable HP fully automatic star/delta starter with over load
protection, current sensing type single phase preventor complete with all acessories and internal wiring
required for automatic operation, selector switch for local / remote, auto/ manual OFF operation.
-
Jockey pump -
40 Amps. TP& N SFU with HRC fuses with suitable HP fully automatic star / delta starter with over load
protection, current sensing type single phase preventor complete with all accessories and internal
wiring required for automatic operation, selector switch for local / remote, auto / manual / OFF
operation.
-
Diesel Engine Control -
Control for Diesel Engine comprising:- -
Auto / Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons,
start / stop in manual mode. -
Indication lamp for High / Low Lub. Oil pressure, High Water Temp. and Engine ON indication. -
Battery charger suitable for 12V / 24 V DC with boost and tickle selector switch, 0-30 V DC volt meter, 0-
20A DC Ammeter. -
All standard relays and acessories for automatic operation of diesel engine. -
DIESEL ENGINE CONTROL -
(i) Control for Diesel Engine comprising:- -
(ii) Auto / Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons,
start / stop in manual mode. -
S.NO. DESCRIPTION UNIT TOTAL QTY. RATE (Rs.) AMOUNT (Rs.)
Indication lamp for High / Low Lub. Oil pressure, High Water Temp. and Engine ON indication. -
Battery charger suitable for 12 V / 24 V DC with boost and tickle selector switch, 0-15 V / 0-30 V DC volt
meter, 0-20A DC Ammeter. -
MAIN FIRE PUMP CONTROL -
275 Amps. TP&N SFU with HRC fuses -
Voltmeter (0-500 Volts) with selector switch. -
Ammeter (0-300 Amps.) with selector switch, CTs etc. -
Set of 3 phase indication lamp. -
Suitable HP fully automatic Star / Delta Starter with over load protection, current sensing type single
phase preventor complete with all acessories and internal wiring required for automatic operation.
-
Selector switch for local / remote, auto / manual / off operation. -
SYSTEM CONTROLLER -
Designing, Supply, Installation, Testing and Commissioning of system controller to control operation of
Main Electric Fire Pump, Diesel Pump, Pressurisation Pump, Terrace Pump in sequence as per
specification consisting of relays, timets, sensors, annunciation window for fault indication, complete as
per specification.
-
-
POWER & CONTROL CABLING -
-
Supply, laying, testing and commissioning of power and control cabling, as per Standard specification
including end termination as required. -
Power cabling (XLPE) insulated and PVC sheathed, armoured, Aluminium Conductor of 1.1 KV grade on
37 existing cable trays). -
a 3C x 70 Sq. mm RMT 60 817 49,020
b 3C x 6 Sq. mm RMT 25 171 4,275
Control Cabling (PVC insulated and PVC sheathed, armoured, Copper Conductor of 1.1 KV grade on
38 existing cable trays). -
a 5C x 1.5 Sq. mm RMT 75 386 28,950
39 Earthing Strip / Wires. -
a Providing and fixing 25 x 5 mm copper strip in 40 mm RMT 30 1,263 37,890
Providing and fixing 25 x 5 mm copper strip on surface or in recess for connections etc. as required.
b RMT 20 1,188 23,760
Providing and fixing 4.0 mm dia. Copper wire on surface or in recess for loop earthing as required.
c RMT 30 116 3,480
40 Supply & laying of rubber mat of size 1000 mm & 12 mm thick. RMT 15 2,673 40,095
41 Supply and installation of ladder type 16G ms cadmium plated 'U' shaped channel 40mm x 20mm
cable tray of following sizes: -
a 150 mm wide RMT 15 966 14,490
c 300 mm wide RMT 30 1,263 37,890
Total 7,631,442