1 Delta Ia-Ies DX-2300LN-W
1 Delta Ia-Ies DX-2300LN-W
Asia
Delta Electronics (Jiangsu) Ltd.
Wujiang Plant 3
1688 Jiangxing East Road,
Wujiang Economic Development Zone
Wujiang City, Jiang Su Province, P.R.C. 215200
TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290
                                                                                                       User Manual
Plot No 43 Sector 35, HSIIDC
Gurgaon, PIN 122001, Haryana, India
TEL : 91-124-4874900 / FAX : 91-124-4874945
Americas
Delta Products Corporation (USA)
Raleigh Office
Europe
Delta Electronics (Netherlands) B.V.
Eindhoven Office
De Witbogt 20, 5652 AG Eindhoven, The Netherlands
TEL : +31 (0)40-8003800 / FAX : +31 (0)40-8003898
                                                                                       DX-020BC20-02
2020-05-14
*We reserve the right to change the information in this manual without prior notice.
                                                                                                       www.deltaww.com
         DX-2300 Series
 Industrial Ethernet Cloud Router
           User Manual
                             Revision History
Version                                      Revision                                         Date
  1st     The first version was published.                                                  2016/3/21
          1. Add new functions featuring Auto Detect/ Target Address in section 3.2.1.
          2. Add a new function featuring PHY Auto Reset in section 3.2.2.
          3. Add a new function featuring Storm Filtering in section 3.2.3.
          4. Add a new function featuring Remote Access Port in section 3.2.1.
          5. Chapter 3: Add new function featuring Set Local PC Time in Section3.4.2.
          6. Chapter 3: Update information concerning Transparent mode/ Slave mode/
              Master mode/ Serial Server-TCP Server/ Serial Server-TCP Client/ Serial
              Server-UDP Client/ RS485 mode in Section3.4.3.
          7. Chapter 3: Add new function featuring MC master mode in section 3.4.3.
          8. Chapter 3: Update information concerning Transparent mode/ Slave mode/
  2nd                                                                                       2020/5/14
              Master mode/ Serial Server-TCP Server/ Serial Server-TCP Client/ Serial
              Server-UDP Client/ RS485 mode in Section 3.4.4.
          9. Chapter 3: Add new function of Siemens TCP in section 3.4.6.
          10. Chapter 3: Update information concerning functions of Diagnosing Method/
               Host Name/IP Address in section 3.4.14.
          11. Chapter 3: Add new function of Trouble shooting in section3.4.15.
          12. Chapter 3: Add new function of Add/ Export Configure List/ Import Configure
               List/ Register Type/ Register Start Address in section 3.4.18.
          13. Chapter 4: Update information concerning functions of PPI and add new
               function of Auto Baudrate. In section 4.2.2.
        DX-2300 Series Industrial Ethernet Cloud
                 Router User Manual
                                          Table of Contents
Chapter 1 Introduction
Chapter 3 Functions
                                                                                                                           1
   3.2.3     Storm Filtering .................................................................................... 3-11
   3.2.4     Static Routing Rules ............................................................................. 3-11
   3.2.5     Dynamic DNS...................................................................................... 3-13
Chapter 4 DIACom
                                                                                                                        2
    4.1.2       DIACom Installation............................................................. 4-3
    4.1.3       DIACloud Account Registration .............................................. 4-3
    4.1.4       Bind DIACloud Account ........................................................ 4-5
Chapter 5 DIACloud
                                                                                                         3
                                                                                                           1
Chapter 1               Production Introduction
Table of Contents
 1.1   Product Overview ....................................................................................... 1-3
   1.1.1    Network Design ..................................................................................... 1-3
   1.1.2    Features ............................................................................................... 1-4
   1.1.3    Front Panel Ports and LEDs ..................................................................... 1-5
   1.1.4    Bottom Panel ........................................................................................ 1-5
   1.1.5    Dimension ............................................................................................ 1-6
                                                                                                                   1-1
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
please refer to the model name DX-2300LN-CN on the Delta website, or contact our branch offices or distributors.
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation.
This equipment generates radio frequency signal and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of
---Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
     CE Declaration of Conformity
     In accordance with the Directives 2004/108/EC*, 2014/30/EU, 2006/95/EC* and 2014/35/EU. The test record, data
evaluation and DX-2300 Series configurations represented herein are true and accurate under the standards herein
specified.
damages, DELTA is not liable to any user or anyone else for: (a) any loss of use, data, reputation, goodwill, credit,
opportunity, economy or profits, whether or not foreseeable; (b) any special, incidental, indirect, consequential, or punitive
damages whatsoever; (c) any losses or damages based on any theory of liability, including breach of contract or warranty,
negligence or other tortious action; (d) any losses or damages resulting from use or unable to use the systems or devices
to which the Software or Services are incorporated or co-operated; and (e) any losses or damages arising from any other
     1-2
                                                                                   Ch ap te r 1 Pro duc t In tr oduc tio n
RS485 serial interface, and thus can satisfy the user’s various different application demands.
The product supports DIACloud platform services, and by this platform, convenient and efficient point-to-point connection
with the router, safe and reliable data transmission, remote device management and configuration, remote firmware
upgrading, remote maintenance and other functions can be realized, so as to save the cost of device operation and
The product can be widely used in the fields requiring mobile network interconnection, such as industrial automation,
smart home, intelligent building, smart power grids, video surveillance, intelligent self-service and intelligent
transportation.
point-to-point connection through DIACloud platform. In addition to safe and reliable data transmission, it can save the
The maintenance personnel can realize remote maintenance and management of the device through DIACloud platform
whenever and wherever possible, which can ensure safe and reliable data transmission, and also can save operation and
                                                                                                                         1-3
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
_1
1.1.2 Features
          Device support various connection method in WAN port, such as the static IP, DHCP client.
          Provide dual serial port (RS232 & RS485) and LAN port connectivity.
 Build in Watch-Dog.
          DIACloud platform services that can realize safe point-to-point data transmission, remote device configuration and
           management, firmware upgrading, and support batch configuration and upgrading of multiple devices
     1-4
                                                                                Ch ap te r 1 Pro duc t In tr oduc tio n
SD Card Slot
                WAN Port
                                                                                             Reset Button
                                                                                             RS232 Port
                LAN Port
RS485 Port
                                                                                                Grounding
                                                                                                 Screw
Power Port
Notice
        This router’s reset button is on the front panel. By pressing the Reset button, users can reset the
        router or reset the router to factory default settings. See the instruction below:
             Reset the Router: With the router powered on, press the Reset button and release the button
              right away.
                                                                                                                   1-5
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                   Reset to Factory Defaults: With the router powered on, press and hold the Reset button for
                    3~6 seconds and then release the button.
_1
                         Reset can only be done when the device is running properly.
                         With the router powered on, press and hold the Reset button until all the LEDs go out
                          (Except the Power LED). Then release the button and wait the router to reboot to its
                          factory default settings.
1.1.5 Dimension
Unit = mm
     1-6
                                                                               Ch ap te r 1 Pro duc t In tr oduc tio n
Notice
 Verify that nothing is missing from the DX-2300LN-WW package by using the check list above. If any item
    is found missing or damaged, please contact your local sales representative for support.
                                                                                                                  1-7
                                                                                                                             2
Chapter 2                         User Interface
Table of Contents
2.1       Web-based GUI Configuration ..................................................................................... 2-2
  2.1.1         System Connection ............................................................................................... 2-2
  2.1.2         Default IP Address/Account/Password ...................................................................... 2-2
  2.1.3         Local Network Setups ............................................................................................ 2-2
  2.1.4         Logging in ............................................................................................................ 2-4
                                                                                                                                      2-1
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
1. Open Network Connections by clicking the Start button , and then clicking Control Panel.
                3.    Right-click the connection that you want to change, and then click Properties.      If you're prompted for
                      an administrator password or confirmation, type the password or provide confirmation.
                4.    Click the Networking tab. Under This connection uses the following items, click either Internet Protocol
                      Version 4 (TCP/IPv4) or Internet Protocol Version 6 (TCP/IPv6), and then click Properties.
                5.     Click Obtain DNS server address automatically and then click OK to get a DNS server address
                automatically using DHCP.
     2-2
                                                                Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
    Since the router’s default IP address is 192.168.5.5 and the subnet mask is 255.255.255.0, the computer’s IP
    address can be set between 192.168.5.1 to 192.168.5.254 except 192.168.5.5. However, you’ll need to make sure
    there are no IP conflicts.
                                                                                                                   2-3
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
            Here, we set the address to 192.168.5.10 and the default gateway to 192.168.5.5. For DNS, the usable DNS
            address can be selected or the address can also be set to 192.168.5.5.
2_
     2.1.4        Logging in
     1.    Open your Internet Explorer browser and input LAN IP address (Default is 192.168.5.5) in the search bar and then
           press Enter.
     2.     You’ll be prompted with the log-in page. Input the user name and the password (Default is admin/admin) and then
            press Enter to log in to the setup page.
     3.     After login, you can see the main selection area on the left hand side and the upper area of the page. The detailed
            settings can be seen on the right hand side of the page.
     2-4
                                                                   Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
2.2         DIADevice
DIADevice is a tool for quickly configuring network devices. Users simply connect the DX device to the PC through the
network cable. This tool can be used to quickly and easily configure the network setting of the device and complete the
device binding DIACloud cloud account.
The DIADevice software is included in the latest DIACom software package. From the official website or sales staff to
obtain DIACom packag. The following example uses DX-2300 to show you how to configure your device with DIADevice.
                                                                                                                        2-5
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2_
     3.    After DIACom detects the device, it will automatically go to the login page, and the user needs to enter login
           password on the login page.
     4.    After passing the authentication, the device information page is displayed, including the basic device information
           (Device Name, S / N, firmware, LAN IP address), network status, WAN information, and cloud service information
     2-6
                                                                    Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
                                                                                                                 2-7
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2. The default is DHCP. If you can not connect to the Internet using auto-setup, please use manual settings.
2_
     3.    Please confirm the network environment and then decide whether to enable HTTP Proxy. If you need to set up HTTP
           PROXY, contact your IT staff.
     2-8
                                                                    Cha p ter 2 In tr oduc tio n to Use r In ter face
4. After the device successfully connected to the Internet, the connection would be successful.
2_
                                                                                                                 2-9
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2. Enter the DIAcloud account number and password, and click Next.
2_
     2-10
                                                                     Cha p ter 2 In tr oduc tio n to Use r In ter face
4. If your device is successfully bound to the cloud, the following screen will appear
2_
       Notice
     If the device has been bound to the cloud account, you need to switch to another cloud
      account binding, you only need to repeat 1-3 steps and then enter the new cloud account
      you need to bind
                                                                                                                 2-11
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2_
     2-12
                                                                    Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
     Cloud account is an important credential of DX router ownership. When the router is bound with a DIACloud account,
     only the account or the sub-account authorized by the account can access the device remotely. All data uploaded by
     the router belongs to this account, which can only be accessed by this account or sub-accounts authorized by this
     account. If you don't already have a cloud account, follow these steps to register:
                                                                                                                  2-13
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
 Fill in account info and select “I Agree”, click “CREATE AN ACCOUNT” button.
2_
              Login your mailbox. Open the activation email sent from [email protected] and complete
               DIACloud account activation operation.
2. Config DX Router
          Here shows how to config the DX router, make it as the modbus master to collect the data from Delta PLC via
          RS-485.
 Connect DX router to local PC via cable, login the config GUI, See section 2.1 for more details.
              DX-2300 is a wire router. You can go to “Network”-“WAN Configurations” to set up the parameters for internet
               connection.
     2-14
                                                             Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
After configuration, you can go to” Status”-“network status” to confirm the connection is ready.
   Go to “System”-“RS485” and enter RS-485 setting page, set the working mode as “Master mode”. Detail
    configuration is as follows::
                                                                                                          2-15
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2_
              Go to “System”-“Register Management” and enter register setting page, set up the data upload rules. Detail
               configuration is as follows:
              Go to “Cloud Service”-“Cloud configurations”and enter account setting page, binding the device with DIACloud
               account. Detail configuration is as follows:
     2-16
                                                          Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
Click the "verify" button to verify the user name/password, it will show below page after verification is pass.
Users can use the default parameters. Click the "bind" button to bind the device to this account.
After binding successful, you can log in the device configuration page again and check the binding information.
                                                                                                             2-17
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
 Click “Devices” from the menu, find the device and click the to view the details.
               Select “Registers” and a register list will be displayed, values shown behind register addresses are collected
                data.
2_
     2-18
                                                                   Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
If you’ve already had a DIACloud account, skip this step. To register a new account, please refer to section 2.3.1.
2. Config DX Router
Here show how to config the DX router and perform remote debug Delta PLC via RS-485.
 Connect DX router to local PC via cable, login the config GUI, See section 2.1 for details
          DX-2300 is a wire router. You can go to” Network”-“WAN Configurations” to set up the parameter for internet
          connection. After configuration, you can go to” Status”-“network status” to confirm the connection is ready.
         Go to ”System”-“RS485” to enter RS-485 setting page, set up it’s working mode to “Transparent mode”,
          configuring as follows:
                                                                                                                     2-19
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2_
              Go to “Cloud Service”-“Cloud configurations” to enter account setting page, binding the device with DIACloud
               account, please refert to section 2.3.1 for more details.
3. DIACom Tool
              Obtain the DIACom firmware package from the official website or from our sales representative. Administrator
               privileges are required to run and install the package. After install successfully, run this programe and login
               with DIACloud account.
              Select the tunnel group which router belongs to. Set up local IP address same segment with DX route. And
               click “Create Tunnel” button.
     2-20
                                                           Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
   After the tunnel has been created, click    button of the DX router, goto create virtual com page. If “Create”
    button is not available, please check the RS-485 wrok mode in DX router config page.
                                                                                                             2-21
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2_
              After the virtual serial port is created, open the corresponding debugging tool WPLSoft of Delta PLC, you can
               remotely download the program to the PLC, which connect to DX router through RS-485.
     2-22
Cha p ter 2 In tr oduc tio n to Use r In ter face
2_
                                            2-23
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
MEMO
2_
     2-24
                                                                                                                3
Chapter 3                    Functions
Table of Contents
 3.1      Status ........................................................................................................ 3-3
    3.1.1       Device Information ................................................................................ 3-3
    3.1.2       Network Status ..................................................................................... 3-4
    3.1.3       Routing Table........................................................................................ 3-5
    3.1.4       Local Log .............................................................................................. 3-5
    3.1.5       Traffic Statistics .................................................................................... 3-6
    3.1.6       Cloud Status ......................................................................................... 3-6
    3.1.7       Connected Device .................................................................................. 3-6
 3.2      Network ..................................................................................................... 3-7
    3.2.1       WAN Configurations ............................................................................... 3-7
    3.2.2       LAN Configurations ................................................................................ 3-9
    3.2.3       Storm Filtering .................................................................................... 3-11
    3.2.4       Static Routing Rules ............................................................................. 3-11
    3.2.5       Dynamic DNS...................................................................................... 3-13
 3.3    Firewall .................................................................................................... 3-14
   3.3.1    Firewall Settings .................................................................................. 3-14
    3.3.2       DMZ Settings ...................................................................................... 3-17
    3.3.3       Port Forward ....................................................................................... 3-17
                                                                                                                        3-1
D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
3-2
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
3.1         Status
You can view summary or detailed information on the Device Information, Network Status, Routing Table, Local Log,
Traffic Statistics, Cloud Status, and Connected Device.
3_
 Hardware Version
Item Description
 Software Version
Item Description
                                                                                                             3-3
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Current Version Version number of the software currently used on the router
Upgrade Date Upgrade time of the software currently used on the router
Item Description
     Internet Information includes the MAC Address, IP Address, Gateway Address, Primary DNS, Network Mask, WAN
     Connection Mode, and Secondary DNS.
     LAN Status includes the Device Name, IP Address, DHCP Server, MAC Address and Network Mask. When the DHCP
     server is enabled, you can see more information, including the address lease time, start address and end address.
     3-4
                                                                        Cha p ter 3 In tr od ucti on to F unc tio ns
                                                                                                                   3-5
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
_3
     3-6
                                                                    Cha p ter 3 In tr od ucti on to F unc tio ns
3.2         Network
You can set up networks, including the WAN Configurations, LAN Configurations, Storm Filtering, Static Routing Rules
and Dynamic DNS.
3_
                               Description                                             Default
 WAN Connection Mode
 Your device can connect to the internet via the WAN port with a Dynamic IP
 or Static IP.
  Static IP: Manually set up the IP address.                                           DHCP
  Dynamic IP: DHCP (Dynamic Host Configuration Protocol) server on
      the network will assign an IP address to the DX router automatically.
 IP Allocation Method
The IP Allocation Method is the same as the WAN Connection Mode that DHCP
                                                                                                                  3-7
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                      Description                                          Default
      you have set. You can apply to different option by modifying the WAN
      Connection Mode.
       Dynamic: DHCP (Dynamic Host Configuration Protocol) server on the
          network will assign an IP address to the DX router automatically.
       Manual: Manually set up the IP address (Static).
      IP Address
      Set up an IP address for your device to connect to the internet via the WAN
                                                                                           0.0.0.0
      port. It’s configurable when the mode is set to Static.
      Network Mask
      Set up the WAN network mask. It’s configurable when the mode is set to
_3    Static.
                                                                                           0.0.0.0
      Gateway Address
      Set up the gateway address. It’s configurable when the mode is set to
                                                                                           0.0.0.0
      Static.
      MTU
      Maximum Transmission Unit is the largest packet that can be transmitted
                                                                                            1500
      over packet based networks.
      Retrieve DNS Address By
      The Retrieve DNS Address Method is the same as the WAN Connection
      Mode that you have set. You can apply to different option by modifying the
      WAN Connection Mode.
      DNS address can be retrieved by DHCP setup or manually set.                           DHCP
       Dynamic: DHCP (Dynamic Host Configuration Protocol) server on the
          network will assign an DNS address to the DX router automatically.
       Manual: Manually set up the IP address (Static).
      Primary DNS
      Set up the primary DNS. It’s configurable when the mode is set to Static.            0.0.0.0
      Secondary DNS
      Set up the secondary DNS. It’s configurable when the mode is set to Static.          0.0.0.0
      Auto Detect
      With two ways to detect the network connection automatically, users can
      choose between “PING” and “Cloud Service” or choose “Disable” to shut             Cloud Service
      down this function.
      Target Address
     Set the IP/domain of the server that program will do a ping testing.           www.DIACloudSolutions.
                                                                                            com
     3-8
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
3_
                                Description                                           Default
 Device Name
 Set up a device name for your router. The name shall be composed of letters,     DX2300 + “_” +
 numbers and underline, starting with a letter or number. The maximum string    “the last four digits
 length is 32 bytes.                                                              of Mac address”
 IP Address
 Set up an IP address for your device.                                             192.168.5.5
 Network Mask
 Set up the LAN network mask.                                                     255.255.255.0
 DHCP Server
 If DX router uses DHCP to assign IP addresses automatically on your
 network. You can specify the IP address range and lease time for the clients
                                                                                      Enable
 on your network. Once the DX router have bound the DIACloud and enabled
 the DIACloud DHCP the DHCP in DX router will be disabled automatically.
 Address Lease Time
 To set up the address lease time so that a client doesn't hold an IP address
                                                                                     One day
 indefinitely. It allows for a mechanism to gracefully reuse DHCP addresses.
                                                                                                                  3-9
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                       Description                                           Default
      Options here are 1 to 3 days.
      First IP Address
      To increase the number of addresses available to clients, you can change
                                                                                          192.168.5.100
      the Start Address.
     Last IP Address
      To increase the number of addresses available to clients, you can change
                                                                                          192.168.5.200
      the End Address.
     STP
      STP is a network protocol that builds a logical loop-free topology for Ethernet
_3    networks. The basic function of STP is to prevent bridge loops and
                                                                                              Disable
      the broadcast radiation that results from them. If this STP is enabled, the
      traffic usage will increase about 15Mbit in 24 hours.
      PHY Auto Reset
     Activate DIACloud DHCP after the account is bound. To determine whether
     LAN needs to be reset if DIACloud is manually reboot or reconnected due to
     unstable network.
           Enable: Allow LAN to be reset which would cause a short period of                 Disable
            disconnection between devices and DX LAN ports
Notice:
                         8.    Connect your PC to LAN2 to ping LAN1 to see if the IP address of the LAN1
                               cannot communicate for a short time.
     3-10
                                                                       Cha p ter 3 In tr od ucti on to F unc tio ns
3_
                                  Description                                            Default
 Broadcast Packet Filtering
 Enable or disable storm filtering function for broadcast packets. Condition to
                                                                                        Disabled
 determine: Destination: FF:FF:FF:FF:FF:FF, protocols: DHCP、ARP、UDP...
 Period
Set the time period of storm filtering with options: 800ms, 400ms, 200ms and
                                                                                         800ms
100ms.
 Allowed Packet Number
Set the allowed packet number to process in a time period. Options are 8, 16,
32, 64 and 256.                                                                             8
                                                                                                                     3-11
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
After clicking the “Add A Rule”, you will see the following page.
_3
                                         Description                                    Default
      Rule Name
      Set up a name for your rule. The name shall be composed of letters,
      numbers and underline, starting with a letter or number. The maximum string        N/A
      length is 32 bytes.
      Network Interface
      For a specific network destination address, select the network interface of the
                                                                                        WAN
      router for sending data package. Options are LAN and WAN.
      Enabled
      Activate the static routing functionality.                                         Yes
      Destination IP
     Set up a Destination IP address for your device.                                    N/A
      Network Mask
      Set up the subnet mask corresponding to the destination network segment. If
      the final destination of the routing is a single host, please type in              N/A
      255.255.255.255.
      Gateway Address
      Set up the next-hop routing address.                                               N/A
     3-12
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
                                 Description                                         Default
 Metric
 Set up the hops. The number of hops that are passed for reaching the
 destination address. One hop indicates passing one router passed. The                 2
 range is 2~15.
3_
                                 Description                                        Default
 Dynamic DNS
 Dynamic Host Configuration Protocol allows you to obtain an IP address
                                                                                    Disable
 automatically from your router. You can enable or disable this functionality.
 Service Provider
 Select the dynamic domain service provider.
                                                                                 www.DynDns.org
 Options are www.DynDNS.org and www.NOIP.com
 Domain
 The domain applied for to the corresponding dynamic domain service
                                                                                      N/A
 provider.
 User Name
The name of the user registered at the corresponding dynamic domain service
provider.                                                                             N/A
                                                                                                             3-13
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                          Description                                        Default
      Password
     The corresponding password to the registered user.                                        N/A
      Refreshing Interval
      Set up the time for the router to update its public network IP from the dynamic
                                                                                              86400
      domain service provider. The value range is 120~86400 sec.
     3.3          Firewall
     You can set up firewall configurations, including the Firewall Settings, DMZ Settings, Port Forward, Port Trigger, URL
_3   Filter, MAC Filter, and IP Filter.
     2.     Users can also set up configuration via web browser by accessing the public IP address obtained from WAN port
            with port 80 or 502.
     3-14
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
3_
Description                                                                          Default
Firewall
The SPI Firewall keeps track of the state of network connections travelling
across it, protecting your Internet connection against Internet threats              Enable
and Denial of Service (DoS).
WAN Ping
It creates a filter that your router not to respond to Ping command and
prevents other users on the internet from pinging your pc and gaining your IP     Not responded
address.
LAN SSH
Set up whether to allow LAN end to connect with the router via SSH.                  Enable
WAN SSH
Set up whether to allow WAN end to connect with the router via SSH.                  Disable
Notice:
                                                                                                             3-15
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                       1.    Access the DX configuration page with public IP address and port 80 on a remote
                             computer.
2. Login DX webpage.
                       8.    Open the web browser on a remote PC and access the IP address (http://123.123.123.1:80)
                             to enter DX configuration webpage.
            Example    9.    Use MODBUS TCP Client tool to connect with MODBUS TCP Server on DX devices and
                             obtain MODBUS data
     3-16
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
Figure
3_
                                 Description                                           Default
 DMZ Server
 Demilitarized zone (DMZ) is a special segment of the local network reserved
 for servers accessible from the Internet, adding an additional layer of               Disable
 security.
 DMZ Host IP Address
1. Click the “Add A Portforward Rule” to add port forwarding entries to the router.
                                                                                                                3-17
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
2. After clicking the “Add A Portforward Rule”, you will see the following page.
_3
                                              Description                                            Default
        Network Services
        Select the common network services. Refer to the following common service list for
                                                                                                    Customized
        optional values.
        Service Name
        Set up the service name for port forwarding. The name is composed of letters,
        numbers and underline, starting with a letter or number. The maximum string length is          N/A
        32 bytes.
        Protocol
        Public Port
        Set up the public port for port forwarding. The port range is 1~65534. A Public port
                                                                                                    Single Port
        should be less than or equal to the server port.
        Server Port
        Set up the server port for port forwarding. The port range is 1~65534. A server port
        should be greater than or equal to the public port.
        When the public port is set to a Single Port, the server port can only be set to a Single
        Port. When the public port is set to a Port Range, the server port can be set to a          Single Port
        Single Port or a Port Range. And when the public port is set to a single port, all the
        port will be forwarded to ONE single port.
        Examples of different port forwarding settings:
     3-18
                                                                  Cha p ter 3 In tr od ucti on to F unc tio ns
                                      Description                                        Default
1:1
N:1
                                                                                                                 3_
N:N
Server IP Address
Set up the server IP address that applies to the port mapping rule. 192.168.1.*
FTP TCP 20 21
HTTP TCP 80 80
Telnet TCP 23 23
                                                                                                         3-19
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     Port triggering is port forwarding with an on/off switch for the ports that have been forwarded. Have data flown out of a
     trigger port or not by enabling or disabling this functionality. Set up the time for the Port Trigger Timeout and click
     “Save” to save the setting.
1. Click the “Add A Trigger Rule” to add port trigger entries to the router.
_3
2. After clicking the “Add A Trigger Rule”, you will see the following page.
                                         Description                                           Default
      Service Name
      Set up the service name for port triggering. The name is composed of letters,
      numbers and underline, starting with a letter or number. The maximum string               N/A
      length is 32 bytes.
      Service User
      Select the service user to apply the port triggering rule.                             Any Address
     3-20
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
                                    Description                                         Default
 Service Type
Triggering Port
 Inbound Connection
 Protocol Role
Set up the protocol type for the inbound connection.                                  TCP/UDP
 Begin port
                                                                                                                            3_
 Set up the starting port for the inbound connection. The port range is 1~65534.         N/A
End Port
Set up the ending port for the inbound connection. The port range is 1~65534. N/A
Status
URL Filter is used to block particular website from the local network. Select Enable/Disable to activate/deactivate this
functionality. Click the “Add An URL Address” to block the URL.
After clicking the “Add An URL Address”, you will see the following page.
                                                                                                                     3-21
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                        Description                                         Default
      URL Address
      Manually input the URL address that you’d like to block, for example
                                                                                              N/A
      www.baidu.com.
      LAN IP Address
      Set up the LAN IP address that you’d like to block. Options are “Any Address”,
                                                                                         Any Address
      “Single Address” and “Address Range”.
      Status
     MAC Filter is used to block particular MAC address from the local network. Select Enable/Disable to activate/deactivate
     this functionality. Click the “Add A MAC Address” to block the MAC Address.
After clicking the “Add A MAC Address”, you will see the following page.
                                        Description                                         Default
      MAC Address
      Manually input the MAC address that you’d like to block.                                N/A
      Device Name
      Set up the device name corresponding to the set MAC address.                            N/A
      Status
     3-22
                                                                        Cha p ter 3 In tr od ucti on to F unc tio ns
3.3.7        IP Filter
This page is used for setting up the IP Filter, including configuring the Source IP, Source Port, Destination IP, Destination
Port, Protocol and Status.
IP Filter is used to block particular IP address from the local network. Select Enable/Disable to activate/deactivate this
functionality. Click the “Add An IP Address” to block the IP Address.
After clicking the “Add An IP Address”, you will see the following page.
                                                                                                                                3_
                                    Description                                            Default
 Source IP
 Set up the source IP.                                                                  Any Address
 Source Port
 Set up the source port where the datagram came from.                                      Any port
 Destination IP
 Set up the destination IP.                                                              Any Address
 Destination Port
 Set up the destination port where the datagram is going to.                               Any port
 Protocol
 Set up the protocol type for the IP Filter.                                              TCP/UDP
 Status
                                                                                                                       3-23
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     3.4         System
     You can set up the system configurations, including the User Management, Time Zone Configurations, RS232, RS485,
     Modbus TCP, Log Settings, Firmware Upgrade, Backup & Restore, Scheduled Jobs, Network Diagnosis, System Reboot,
     Event Management, and Register Management.
_3
Description Default
Old Password
New Password
      Input the new password you’d like to use. The password length should be 5-12
      digits and is composed of lowercase letters, uppercase letters (case sensitive),    N/A
      numerals 0-9 and underline.
Confirm Password
Again input the password you’d like to use to double confirm there is no typo. A/A
Session Timeout
      Session timeout is an expired time limit for a logged in user which as been
                                                                                           30
      inactive for a period of time. Setting range is from 10 to 1440 minutes
     3-24
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
3_
Description Default
Configure time and date settings to be synchronized with the connected PC. N/A
Select the operating time zone of your device: GMT-12:00 - GMT+13:00. GMT+08:00
Example: Sync time between the device and the connected PC.
                    1.    Enter DX webpage.
                    2.    Go to “SYSTEM -> Time Zone Settings”
Instruction
                    3.    Click “Set Local PC Time”
                    4.    After a confirmation message prompted, click yes and reboot the device to
                          complete synchronization.
Figure
                                                                                                                    3-25
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     3.4.3          RS232
     RS-232 supports 7 working modes: Transparent mode, Slave mode, Master mode, Serial Server-TCP Server, Serial
     Server-TCP Client, Serial Server-UDP Client and MC master mode.
     This section provides information of specific RS232 port parameters under different working modes. The basic
     parameters are presented in the table below.
Description Default
Working Mode
Select the working mode for the current active serial port. Close
      Baud Rate
_3
      Set up the baud rate for the serial port. Options are 2400, 4800, 9600, 19200,
                                                                                             9600
      38400, 57600 and 115200.
Data Bits
      Set up the data bits for the serial port. Options are 7 and 8. It must be set to 8
                                                                                               8
      when communication mode is Modbus RTU.
Stop Bits
Set up the stop bits for the serial port. Options are 1 and 2. 1
Parity Bits
Set up the parity bits for the serial port. Options are None, Odd and Even. None
Flow Control
Set up the flow control. Options are None, XON, XOFF, RTS, and CTS. None
 Transparent mode
     When RS-232 is under transparent mode, users can debug devices and upload/ download data remotely by creating
     virtual serial ports via DIACom.
     3-26
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
 Slave mode
This mode is for the master device to perform the read/ write tasks on the open register of DX router to achieve
bidirectional data transmission.
3_
Description Default
Slave ID
Mode
 Set up the communication mode for the device. Device support Modbus RTU
                                                                                      Modbus RTU
 and Modbus ASCII
Timeout
 Set up the timeout timer from 200ms to 5000ms. If the set value is out of range,
                                                                                          200ms
 it will be automatically changed to its maximum or minimum value.
                                                                                                                   3-27
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
 Master mode
          In this mode, it is allowable for DX router to perform the read/ write tasks on the open register of the slave device via
          RS-232 to achieve bidirectional data transmission.
_3
Description Default
Slave ID
Mode
      Set the communication mode for the device. Device support Modbus RTU and
                                                                                              Modbus RTU
      Modbus ASCII.
Timeout
      Set the timeout timer from 200ms to 5000ms. If the set value is out of range, it
                                                                                                 200ms
      will be automatically changed to its maximum or minimum value.
Scan Interval
Set the time for scan interval, ranging from 50ms to 60000ms. 30000ms
     3-28
                                                                        Cha p ter 3 In tr od ucti on to F unc tio ns
Description Default
Add Mappings
Delete all the existing mapping under the master mode of RS-232. N/A
Export all the mapping and save as a file in the local PC.                                N/A
                                                                                                                       3_
 Import Configure List
Notice:
Read/Write
Slave ID
Controller
                                                                                                               3-29
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Description Default
Address Type
     In master mode, the address type would changes with different options of
     controller type:
           Delta PLC: address types would be D/M/S/X/Y, which D is a word type and
            M/S/X/Y are of bit type.
      Set up the slave starting address for read/write the registers in a PLC.
            Delta PLC: Enter the internal D register number. If you need to read / write
              D0, please enter 0 here.                                                       N/A
            Other: Enter the Hexadecimal or Decimal actual address. For example:
              Holding Register: 400100, take 0100 (decimal) that is 64 (hex).
Bit
      For the X/Y type of Delta AH/AS series, the address input format is 0.0~X.15.
      Enter the values before decimal point in the input field of Slave Starting             N/A
      Address; values after decimal point should be entered in the input field of Bit.
      Set up the device starting address (decimal, word-type input range is from
      $2048 to $4095; bit-type input range is from M0 to M511). Must start at the            N/A
      beginning of a Device Starting Address with a “$” or “M”.
Length (1-123)
     Set the length which is the number of continuous addresses followed by the
     starting address which will be read or write, ranging from 1 to 123.                    N/A
Operation
Edit
     3-30
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
In this working mode, DX series routers working as TCP servers receive data packets from clients, then send to RS-232
after parsing.
3_
Description Default
 Setting how long TCP activity keep idle, then the TCP connection will be drop.
                                                                                         7
 Input range is from 0 to 99 minutes. 0 means will never drop it.
Listening Port
Packing Length
 Setting the length of packet, packet will be transmitted when the size reaches
 the values. Input range is from 0 to 1024 byte. 0 means will transmit at once           0
 when received the data.
Force Transmit
 Setting how long the program waiting, then transmit the packet. Input range is
                                                                                         0
 from 0 to 65535 millisecond. 0 means will never force to transmit.
                                                                                                                3-31
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Under this mode, DX routers will be clients of device servers to send data with a TCP connection.
_3
Description Default
-1~99:Shut off when the duration of idle state reaches the setting value.
     3-32
                                                                       Cha p ter 3 In tr od ucti on to F unc tio ns
Description Default
Packing Length
 Setting the length of packet, packet will be transmitted when the size reaches
 the values. Input range is from 0 to 1024 byte. 0 means will transmit at once             0
 when received the data.
Force Transmit
 Configure the length of time awaiting to transmit a data packet forcibly, ranging
 0~65535ms. When reaches the setting of time duration or the length of                                                3_
                                                                                           0
 accumulated data, the data would be transmitted immediately. If set as 0, no
 data packet would be sent.
Under this mode, DX routers will be clients of device servers to send data with a UDP connection.
                                                                                                              3-33
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Description Default
      Packing Length
_3    Setting the length of packet, packet will be transmitted when the size reaches
      the values. Input range is from 0 to 1024 byte. 0 means will transmit at once           0
      when received the data.
Force Transmit
      Set the length of time awaiting to transmit a data packet forcibly, ranging
      0~65535ms. When reaches the setting of time duration or the length of
                                                                                              0
      accumulated data, the data would be transmitted immediately. If set as 0, no
      data packet would be sent.
 MC master mode
     When RS232 is in MC master mode, DX series routers can perform the read/ write tasks on the slave device of Mitsubishi
     PLC FX series via RS232 to achieve bidirectional data transmission.
     3-34
                                                                       Cha p ter 3 In tr od ucti on to F unc tio ns
                                     Description                                       Default
 Slave ID
 Set up the MODBUS ID for DX router. Invalid in MC Master mode.                           0
 Mode
It’s fixed to “MC ASCII” in MC master mode.                                           MC ASCII
 Timeout
 Set the timeout timer from 200ms to 5000ms according to the actual situation. If
 the set value is out of range, it will be automatically changed to its maximum or     200ms
 minimum value.
                                                                                                                      3_
 Scan Interval
 Set up the time for scan interval, ranging from 50ms to 60000ms.                     30000ms
 Add Mappings
 Click the button to add mappings. After creating a mapping between IP
 addresses of slave device and DX router under the user’s configuration, the             N/A
 system will collect data from the slave device.
 Delete All Mappings
Delete all the existing mapping under the master mode of RS-232.                         N/A
Notice:
 Read/Write
 Set up the access permissions for the mapped register address;
  Read-only: The device regular read data from appointed registers in the
       slave, but will not update the data to the slave
  Write-only: The device updates the data to the slave when the registers           Read/Write
       values were changed, but will not read the data from the slave
  Read/write: The device regular read data from appointed registers in the
       slave, will update the data to the slave when the registers values are
       changed.
 Slave ID
It’s fixed to 0 in MC master mode.                                                        0
                                                                                                              3-35
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                         Description                                           Default
      Controller
                                                                                             MITSUBISHI
      It’s fixed to “MITSUBISHI PLC” in MC master mode.
                                                                                                PLC
      Address Type
     Address types would be D/M/S/X/Y, which D is a word type and M/S/X/Y are bit
     types.                                                                                      D
     3.4.4         RS485
     RS-485 supports 6 working modes: Transparent mode, Slave mode, Master mode, Serial Server-TCP Server, Serial
     Server-TCP Client and Serial Server-UDP Client. This section provides information of specific RS-485 port parameters
     under different working modes. The basic parameters are presented in the table below.
Description Default
Working Mode
Select the working mode for the current active serial port. Close
Baud Rate
      Set up the baud rate for the serial port. Options are 2400, 4800, 9600, 19200,
                                                                                                9600
      38400, 57600 and 115200.
Data Bits
     Set port data bits as 7 or 8. When operating in Modbus RTU mode, the value can
     only be set as 8.                                                                           8
Stop Bits
Set up the stop bits for the serial port. Options are 1 and 2. 1
     3-36
                                                                       Cha p ter 3 In tr od ucti on to F unc tio ns
Description Default
Parity Bits
Set up the parity bits for the serial port. Options are None, Odd and Even. None
 Transparent mode
When RS-485 is under transparent mode, users can debug devices and upload/ download data remotely by creating
virtual serial ports via DIACom.
3_
 Slave mode
This mode is for the master device to perform the read/ write tasks on the open register of DX routers to achieve
bidirectional data transmission.
                                                                                                                    3-37
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Description Default
Slave ID
Mode
      Set up the communication mode for the device. Device support Modbus RTU
                                                                                             Modbus RTU
      and Modbus ASCII
Timeout
      Set up the timeout timer from 200ms to 5000ms. If the set value is out of range,
                                                                                                200ms
      it will be automatically changed to its maximum or minimum value.
_3
         Master mode
     In this mode, it is allowable for DX router to perform the read/ write tasks on the slave device via an RS-485 connection to
     achieve bidirectional data transmission.
     3-38
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
                                   Description                                        Default
 Slave ID
 Set up the MODBUS ID for DX router. Invalid in Master mode.                             1
 Mode
 Set up the communication mode for the device. Device support Modbus RTU
                                                                                    Modbus RTU
 and Modbus ASCII.
 Timeout
 Set up the timeout timer from 200ms to 5000ms. If the set value is out of range,
                                                                                      200ms
 it will be automatically changed to its maximum or minimum value.
 Scan Interval
 Set up the time for scan interval, ranging from 50ms to 60000ms.                    30000ms
                                                                                                                     3_
 Add Mappings
 Click the button to add mappings. After creating a mapping between IP
 addresses of slave device and DX router under the user’s configuration, the            N/A
 system will collect data from the slave device.
 Delete All Mappings
Delete all the existing mapping under the master mode of RS-485.                        N/A
Notice:
 Read/Write
 Set up the access permissions for the mapped register address;
  Read-only: The device regular read data from appointed registers in the
       slave, but will not update the data to the slave
  Write-only: The device updates the data to the slave when the registers          Read/Write
       values were changed, but will not read the data from the slave
  Read/write: The device regular read data from appointed registers in the
       slave, will update the data to the slave when the registers values are
       changed.
 Slave ID
 Set up the corresponding slave communication port. The value is between 1
                                                                                         1
 and 247.
                                                                                                             3-39
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                         Description                                          Default
      Controller
      In master mode, device types options are:
       Delta PLC: Use this option for Delta DVP / AH / AS series PLCs
                                                                                           Delta DVP PLC
       Other: Use this option for non-Delta PLCs. HEX means hexadecimal
           address; DEC means decimal address.
      Address Type
     In master mode, the address type would changes with different options of
     controller type.:
           Delta PLC: address types would be D/M/S/X/Y, which D is a word type and
            M/S/X/Y are of bit type.
_3
           Other: Address type is 0x/1x/3x/4x/Swap
     3-40
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
In this working mode, DX series routers working as TCP servers receive data packets from clients, then send to RS-485
after parsing.
3_
                                         Description                                    Default
 TCP Alive Check Time
Configure the duration of the idle state before disconnect TCP automatically.
Selectable values: 0~99
 -0:Never shut off TCP connection due to idle state.                                       7
Listening Port
                                                                                                                3-41
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Under this mode, DX routers will be clients of device servers to send data with a TCP connection.
_3
                                       Description                                           Default
      TCP Alive Check Time
     Configure the duration of the idle state before disconnect TCP automatically.
     Selectable values: 0~99
      -0:Never shut off TCP connection due to idle state.                                       7
     3-42
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
                                    Description                                         Default
to be connected at the same time.
 Packing Length
Set the length of the accumulated data for packets sending, ranging 0~1024
bytes. Set as 0 for real-time data transmission.                                           0
 Force Transmit
Set the length of time awaiting to transmit a data packet, ranging 0~65535 ms.
When reaches the setting of time duration or the length of accumulated data, the           0                        3_
data would be transmitted immediately. If set as 0, no data packet would be sent.
Under this mode, DX routers will be clients of device servers to send data with a UDP connection.
                                                                                                            3-43
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                         Description                                      Default
      Destination IP address and Port
     Set the destination IP addresses and ports. (Default:6001~6004, configurable) IP
     addresses and ports cannot be duplicated with a maximum of 4 servers allowed
     to be connected under UDP at the same time. Each server can support up to 99        6001~6004
     addresses, counting from the starting address.
      Force Transmit
     Set the length of time awaiting to transmit a data packet, ranging 0~65535 ms.
     When reaches the setting of time duration or the length of accumulated data, the        0
     data would be transmitted immediately. If set as 0, no data packet would be sent.
     3-44
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
3_
                                   Description                                        Default
 Working Mode
     Modbus TCP Server: Only Modbus TCP server works. And supports up
       to 32 Client to connect.
     Modbus TCP Server+Client: Modbus TCP server + Modbus TCP client               Modbus TCP
       work at the same time. MODBUS TCP Client supports to connect to 32             Server
       different servers at most.
 Server IP
 Set up the IP address of a PLC in the Modbus TCP Client mode                           N/A
 Server Port
 Set up the server port of a PLC in the Modbus TCP Client mode                          502
 Response Timeout
 Set up the timeout timer from 50ms to 10000ms. If the set value is out of range,
 it will be automatically changed to its maximum or minimum value. The default          300
 is 300ms.
 Scan Interval
 Set up the time for scan interval, ranging from 50ms to 60000ms; the default is
                                                                                      30000
 3000ms.
 Add Mappings
 Click the button to add mappings. After creating a mapping between IP
 addresses of slave device and DX router under the user’s configuration, the            N/A
 system will collect data from the slave device.
 Delete All Mappings
Delete all the existing mapping of the device.                                          N/A
                                                                                                             3-45
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                        Description                                       Default
      Export Configure List
     Export all the mapping and save as a file in the local PC.                            N/A
Notice:
      Read/Write
      Set up the access permissions for the mapped register address;
       Read-only: The device regular read data from appointed registers in the
            slave, but will not update the data to the slave
           Write-only: The device updates the data to the slave when the registers     Read/Write
             values were changed, but will not read the data from the slave
           Read/write: The device regular read data from appointed registers in the
             slave, will update the data to the slave when the registers values are
             changed.
      Slave ID
      Set up the corresponding slave communication port. The value is between 1
                                                                                            1
      and 247.
      Controller
      In master mode, device types options are:
       Delta PLC: Use this option for Delta DVP / AH / AS series PLCs
                                                                                       Delta DVP PLC
       Other: Use this option for non-Delta PLCs. HEX means hexadecimal
           address; DEC means decimal address.
      Address Type
     In master mode, the address type would changes with different options of
     controller type.:
         Delta PLC: address types would be D/M/S/X/Y, which D is a word type and
          M/S/X/Y are of bit type.
         Other: Address type is 0x/1x/3x/4x/Swap
                                                                                            D
          a)     0x: Coils(Modbus function code: 01/05), read-write.
     3-46
                                                                        Cha p ter 3 In tr od ucti on to F unc tio ns
                                    Description                                         Default
       e)   Swap: If using “double words” to read/write “holding registers”, before
            reading or writing, the values in Hi Word and Low Word will be
 Length (1-123)
Set the number of the continuous address followed by the starting address which
will be read or write. Input range is from 1 to 123.                                      N/A
 Operation
 Click the +/- button to add mapping or delete mapping.                                   N/A
 Edit
 Click an item of register mapping forms that can be edited.                              N/A
                                                                                                               3-47
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
_3
                                       Description                                     Default
      Add Server
     Choose the target Siemens TCP server for connection to the routers with 32
     servers supported at most.                                                          NA
      Controller
     Set the model type of the Siemens devices for communication.                      S7-300
      Server IP
     Set the IP address of the Siemens devices for communication.                       N/A
      Local TSAP
     Set up the address of local TSAP with Siemens ISO-on-TCP only when
     controller’s model “S7-200 ISO TCP” or “S7-1200/1500 ISO TCP” is used.             N/A
      Remote TSAP
     Set up the address of remote TSAP with Siemens ISO-on-TCP only when
     controller’s model “S7-200 ISO TCP” or “S7-1200/1500 ISO TCP” is used.             N/A
      Response Timeout
     Users can change the time-out value according to the actual situation with the
     acceptable time range from 50ms to 10000ms. If specified but the input value is    300
     out of the range, it will be set to the value of the min or max attribute.
      Scan Interval
      Set up the time for scan interval, ranging from 50ms to 60000ms.                 30000
     3-48
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
                                   Description                                       Default
 Add Mappings
Click the button to add mappings. After creating a mapping between IP addresses
of slave device and DX router under the user’s configuration, the system will          N/A
collect data from the slave device.
Notice:
 Read/Write
 Set up the access permissions for the mapped register address;
  Read-only: The device regular read data from appointed registers in the
       slave, but will not update the data to the slave
  Write-only: The device updates the data to the slave when the registers         Read/Write
       values were changed, but will not read the data from the slave
  Read/write: The device regular read data from appointed registers in the
       slave, will update the data to the slave when the registers values are
       changed.
 Data Type
Set the type for collected data:
  BIT: Bit type
  WORD: Word type                                                                   WORD
  WORD(SWAP) : Double words type.
 Address Type
    If controller’s model type is “S7-200 ISO TCP”, address type can be set as
     V/M/Q/I; combined with data types:
     -Bit type:VB/MB/QB/IB
     -Word type:VW/MW/QW/IW                                                            DB
     -DWord type:VD/MD/QD/ID
    If controller’s model type is “S7-300” or “S7-1200/1500 ISO TCP”, address
     type can be set as DB/M/Q/I; combined with data types:
                                                                                                            3-49
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                        Description                                        Default
            -Bit type: DBn_DBX/MB/QB/IB
            -Word type: DBn_DBW/MW/QW/IW
            -DWord type: DBn_DBD/MD/QD/ID
      DB Number
     Set the DB number for the starting address of Siemens slave’s register operated
     in read/ write tasks. Not configurable when controller’s model type is “S7-200 ISO     N/A
     TCP”.
      Bit
      The address input format is 0.0~X.7. Enter the values before decimal point in
      the input field of Slave Offset Address, while values after decimal point should       NA
      be entered in the input field of Bit.
      Device Starting Address
      Set the starting address of the corresponding register. Word-type input range is
      from $2048 to $4095. Bit type range is M0~M511. The beginning of a Device             N/A
      Starting Address must starts with a “$” or “M”.
      Length
     Set the number of the continuous address followed by the starting address which
     will be read or write. Input range is from 1 to 123.                                   N/A
      Operation
      Click the +/- button to add mapping or delete mapping.                                N/A
      Edit
      Click an item of register mapping forms that can be edited.                           N/A
     3-50
                                                                        Cha p ter 3 In tr od ucti on to F unc tio ns
3_
Description Default
Log to Console
Set up the remote log server port, ranging from 1 to 65534. 514
      Notice
     Remote log service is used for qualified engineers to check the device remotely
      when errors occurred. With this service, there is no need to log in to the device,
      device logs can be exported to the remote log server. The server should support
      the syslog protocol. When this functionality is enabled, it will take up some
      resources. Do not enable this functionality disabled, unless it’s necessary.
                                                                                                               3-51
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                        Description                                       Default
_3    Select Firmware
Upgrade
      Click “Upgrade” to upgrade firmware. The device will reboot after the upgrade is
                                                                                           N/A
      done.
Description Default
Backup
Restore
      Click “Browse” to select the backup file and then click “Restore” to restore the
      configurations. The device configuration will be restored to the previous version    N/A
      and the device will reboot after the restoring is done.
     3-52
                                                                       Cha p ter 3 In tr od ucti on to F unc tio ns
Description Default
3_
Description Default
Job Name
 Set up a name for your scheduled job. The name shall be composed of letters,
 numbers and underline, starting with a letter or number. The maximum string              N/A
 length is 32 bytes.
Enable
Recurring Job
                                                                                                                      3-53
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Description Default
      The scheduled job can be done Once, Every day, Every week, or Every month.            Once
      And the specific time can be further defined.                                         01:00
Date
Job Type
     3-54
                                                                         Cha p ter 3 In tr od ucti on to F unc tio ns
3_
                             Description                                              Default
 Diagnosing Method
Selections are “Ping Test”, “Route Trace” and “Cloud Service
Diagnose”.                                                                           Ping Test
                                                                                                                        3-55
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     troubleshoot remotely. If the problem persists, the time interval for the device to upload the logs is 1, 2, 4, 5, 16, and 24
     and then the time interval is fixed to every 24 hours.
_3
            Notice
           It is suggested to disable this function. However you should enable this function, if
            the engineer analyzed and advised you to, when some issues occur.
      Communication Verification: when the slave (such as PLC) is connected with a router via MODBUS TCP or
         MODBUS RTU, the router checks whether the tunnel is a reliable connection-critical lock or not.
     Communication verification expression between PLC and the router can be set here. The expression is the numeric
     expression in C, complying with the standard C programming syntax. The expression can be a single variable, a constant,
     or a single variable equation. The name of the variable is limited to “A", and the expression should be something like this
     (A+100)*45.
     3-56
                                                                     Cha p ter 3 In tr od ucti on to F unc tio ns
3_
 Alarm Event: Click “Add” to set a new alarm event, input the Alarm Name, Description, Alarm Criteria, Event Interval,
   Repeat Times, Alarm Content and Target Receiver. Click “Details” to modify the existing alarm. Click “Delete” to
   delete the existing alarm. Click “Copy” to duplicate the alarm.
                                                                                                                  3-57
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
_3
                                        Description                                        Default
      Alarm Name
      Input an alarm name. The name shall be composed of numbers, English
                                                                                            N/A
      letters, uppercase and lowercase. The maximum string length is 32 bytes.
      Alarm Description
      The alarm description shall be composed of numbers, English letters,
                                                                                            N/A
      uppercase and lowercase. The maximum string length is 50 bytes.
      Alarm Criteria
      The format of alarm variable is {$number 0-4095}, the alarm criteria can be a
      single alarm variable, or a formula of one or several alarm criteria. For example,    N/A
      the formula can be: {$2003}+{$2004}*100/2-1.
      Event Interval
      The time interval of alarm sending                                                     0
      Repeat Times
      The repeated times of alarm sending                                                    0
      Alarm Content
      Set up the information shown on the alarm contents. The content of the alarm
      will be sent to the target when alarm criteria are met. The information order can     N/A
      be self-defined.
     3-58
                                                                         Cha p ter 3 In tr od ucti on to F unc tio ns
                                    Description                                              Default
    Time: the time when the alarm occurred
    Date: the date when the alarm occurred
    Name: the name of the occurred alarm
    Description: the description of the occurred alarm
 For example: Register $2048 represents electrical voltage, the value of
 register $2048 is 10, and the alarm content is set as: {Date} {Time} Voltage =
 {$2048}, then the query content received by users will be: 2016/06/01
 10:00:00(currently time) Voltage = 10. The maximum content length is 95
 characters.
 Target Receiver
 Set up the recipient. User can maintain the list by 【Control List Of Event
 Management】in Privilege Management function. System only response the                         N/A
                                                                                                                                3_
 query from receiver list.
      Notice
     {} is a special system symbol, which is used to reference system variables or system registers,
      like ${Time}, ${Date} or ${Number 0 - 4095}. Please use it with caution.
The address segment 2048~4095 can be self-defined. The Start address, Length, Uploaded to Cloud or not and keep
history or not can be set up.
                                                                                                                         3-59
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
                                         Description                                            Default
      Export Configure List
      Export the configure list to the file and save to local PC                                 N/A
      Import Configure List
     Import configure list from the local PC.
_3    Set up the register data type, options are “Word” and “Bit”.                               Word
      Register Start Address
      Set Register Start Address applicable for rules. Word-type addresses start with
      “$”, configurable from $2048~$4095. Bit-type addresses start with “M”,                     N/A
      configurable from M0~M511.
      Length
      Set the number of the effective register address followed by the start address.
      Input value as 1 indicates one register. Word-type effective range:1-2048.                 N/A
      Bit-type effective range: 1-512.
      Uploaded To Cloud
是否将这些寄存器的值上传到云端,可选项:“是”和“否”,默认选项“是”。 Yes
            Notice
           When the values in the register changes, the results will be uploaded to cloud.
1. Login with your DIACloud account then click the “Verify” button to authenticate with DIACloud server.
     3-60
                                                                       Cha p ter 3 In tr od ucti on to F unc tio ns
2.   After authentication successfully, the cloud configurations will show up then the user can modify the secure tunnel
     and device name.
                                                                                                                            3_
4.   Click the "Bind" button, the DX router will bind with DIACloud server and establishe a secure tunnel between the
     DIACloud server and the DX router. Meanwhile a new IP will assign to DX router from DIACloud server (assign from
     the cloud DHCP server or a user specified).
                                                                                                                     3-61
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     5.   Your browser will access to the DX router with new IP address automatically if DIACloud account binds with
          DIACloud server successfully. Please make sure a PC and DX router are in the same subnet; otherwise PC will not
          be able to access to the DX router.
_3
     6.   If the network is in the poor condition, The binding proccess could be successfully but the Service Status is shown
          “Disable”.
     7.   In this situation, the browser will access to 192.168.1.1 and the service status will be “Disable”. You can re-enable the
          service status to rebuild the secure tunnel again in cloud configurations.
     3-62
                                                                      Cha p ter 3 In tr od ucti on to F unc tio ns
8.   When the service status is shown “Enable”, that means the DIACloud service is actived on DX-2300LN-WW. The
     user also can get the related information in cloud platform.
3_
9. Click the “Unbind” button, DX-2300LN-WW will remove the registered account in DIACloud.
Description Default
User Name
Password
Verify
Secure Tunnel
 Select the device under the account to join in a certain secure tunnel network
 group. For secure tunnel related settings, go to                                     Default
 http://www.DIACloudSolutions.com/
Device Name
                                                                                                             3-63
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
Description Default
Network protocol
      Set the network protocol of the security tunnel.Options are TCP and UDP.
           UDP: UDP has a faster data transfer speed. If the network is not lost
            packet, please use this option
           TCP: When the network packet loss is serious, it is recommended to                 UDP
            select TCP. After binding the cloud account, you can still change this
            option, but you must disable the cloud service before changing. When the
            agent is turned on, the user can only select TCP.
      Cloud IP Rang
_3
      Display the Cloud IP Range. The Cloud IP Range is depended on the secure
      tunnel setting. For the secure tunnel setting, please refer to 5.2.5 Tunnel              N/A
      Network.
Cloud Netmask
      Display the Cloud Netmask. The Cloud Netmask is depended on the secure
      tunnel setting. For the secure tunnel setting, please refer to 5.2.5 Tunnel              N/A
      Network.
Device IP
      User can assign a IP address for this device, the IP should be in the same
                                                                                               N/A
      subnet with Cloud IP.
            Notice
           Users can log-in to http://www.DIACloudSolutions.com/ and register for a
            DIACloud account.
           In rare case, you can’t access the web because the computer did not refresh the
            IP and DNS after the activation, please re-plug the cable to resolve the issue.
     3-64
                                                                  Cha p ter 3 In tr od ucti on to F unc tio ns
3_
                                    Description                                     Default
HTTP Proxy
Proxy Addr
Proxy Port
Proxy Username
Proxy Password
                                                                                                              3-65
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
_3
Description Default
      Set the security tunnel, whether to allow multicast transmission of the nature of
      the packet.                                                                          Yes
      Options: Allowed, not allowed
      Set up the specified MAC device will be allow or forbid to transmit the data in
      the secure tunnel. Options as below:
           Disable: Disable this function.
           Black List: If the network device's MAC address is blacklisted, these         Disable
            devices will NOT be able to transmit packets to the secure tunnel
           White List: If the network device's MAC address is blacklisted, these
            devices will be able to transmit packets to the secure tunnel.
Add
     3-66
                                                                         Cha p ter 3 In tr od ucti on to F unc tio ns
3_
Description Default
                                                                                                                3-67
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
The SD Card quick configurations will triggers by the following file is created in the SD card after the DX-2300LN reboots:
         The device configuration files ‘backup.cfg’. (Please refer 3.4.8 Backup & Restore)
_3       The cloud configuration file ‘Provision.bin’ (Please refer to the following steps).
3. Click to select the Network which you’d like to use and then click the to see and check the details.
     Power off the device and then insert the SD card into the device (SD card slot below the SIM card slot, on the right side of
     the device). Turn on the device and it will automatically bind. Check the SD card status indicator to see if the binding is
     successful.
     The following beep codes are for SD Card Quick Configurations, its definition that the various combinations of the
     configuration file exist on SD card. (× – fail, √ - success or not this operation)
1 long × √ √
1 long, 1 short √ × √
     3-68
                                                                          Cha p ter 3 In tr od ucti on to F unc tio ns
1 long, 2 short × × √
1 long, 3 short √ √ ×
1 long, 4 short × √ ×
1 long, 5 short √ × ×
1 long, 6 short × × ×
None √ √ √ 3_
       Notice
      Name rule for BIN file: Provision.bin
      Please do not create the two different upgrade-package file in SD Card. In order to
       avoid the upgrading process fails.
                                                                                                                 3-69
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
MEMO
_3
     3-70
                                                                                                            4
Chapter 4                    DIACom
Table of Contents
 4.1     Introduction to DIACom ............................................................................. 4-2
   4.1.1         Select a Suitable Firmware Version .......................................................... 4-2
   4.1.2         DIACom Installation ............................................................................... 4-3
   4.1.3         DIACloud Account Registration ................................................................ 4-3
   4.1.4         Bind DIACloud Account ........................................................................... 4-5
 4.2     DIACom Operation ..................................................................................... 4-6
   4.2.1         Setup a Secure Tunnel ........................................................................... 4-6
   4.2.2         Create a Virtual Serial-Port ................................................................... 4-10
   4.2.3         Remote Control and Monitoring via DIACom ............................................ 4-12
       4.2.3.1      Via a LAN Port ................................................................................. 4-12
       4.2.3.2      Via a RS232/RS485 Port ................................................................... 4-12
   4.2.4         Automation Startup ............................................................................. 4-14
                                                                                                                     4-1
     DX-2300 Series Industrial Ethernet Cloud Router
_4
           Notice
          DIACloud provides you with cloud services, including the connected device
           management, secure tunnel network creation, data upload/download, and
           directional transmission.
          If you need to configure or monitor your controller, you will need to install
           programmable logic controller software, for example WPLSoft/ISPSoft for Delta
           PLC.
Corresponding Table:
           Notice
     If the device firmware is lower than 1.3.3.0, please use DIACom 1.2.8.0 or lower.
     4-2
                                                Cha p ter 4 In tr od ucti on to D IACo m
     Notice
DIACom supports Windows XP, Windows 7 (32-bit and 64-bit) and Windows 8 (32-bit and 64-bit).
2.   Open the DIACloud web page (http://www.DIACloudSolutions.com). The system will redirect
     you to the registration page:
4_
Notice
Click at the upper right corner to change the interface language to English.
3.   Input your email address, password and other relevant information on the registration page.
     Select “I Agree” and click “CREATE AN ACCOUNT”.
                                                                                             4-3
     DX-2300 Series Industrial Ethernet Cloud Router
_4
     5.    You will find an activation email sent from [email protected] in your email box.
           Open the email, click “here” link in the email and complete DIACloud account activation
           operation. And you will be redirected to the DIACloud login page. Input your account and
           password to log in to the DIACloud.
     4-4
                                                Cha p ter 4 In tr od ucti on to D IACo m
4_
1.   Local Network Setups: Please refer to Chapter 2.1 to 2.1.3 Web-based GUI Configuration for
     more information.
2. Bind DIACloud Account: Please refer to Chapter 3.5 Cloud Service for more information.
           Notice
          Secure Tunnel: Secure tunnel is a virtual network. Users can set up several
           groups of secure tunnel for easier device management.
          Device Name: the serial number + “_” + “Mac address” of the device is the device
           name by default.
                When selecting “Yes”: The system will assign an IP address for the device
                 according to the Secure Tunnel settings and the availability of the IP
                 addresses. Take note of the assigned IP address, it will be used when
                 logging to the DIACloud.
                 The IP address of the DX-2300 Series and the WAN of your connected PC
                 should be in different network segments.
                                                                                              4-5
     DX-2300 Series Industrial Ethernet Cloud Router
_4
                  Http proxy: Please fill in the proxy server address, port, username and password if
                   the LAN needs to set the proxy to access the Internet. Click “Save” button to enable
                   the config.
                  Diagnose: The user can click the Diagnostic button to test the current internet settings,
                   whether to connect to the DIACloud server
     4-6
                                                   Cha p ter 4 In tr od ucti on to D IACo m
             Notice
          DIACom will automatically determine whether the port agent needs to enable.
          Make sure that the external network port 80 and port 443 are opened and can                    4_
            access any network domains and IP addresses
3.   After the login is successful, the software displays the security tunnel page. The security
     tunnel list is displayed on the left side of the page, and the network information of the security
     tunnel and the device list are displayed on the right. Users can choose to use DHCP or
     manually set the cloud IP address
           DHCP: Obtain an IP address from Cloud automatically when Cloud DHCP function is
            available.
           Static: Manually set the IP address, the IP should be in the same subnet with DX
            device
                                                                                                   4-7
           DX-2300 Series Industrial Ethernet Cloud Router
           Notice
     If it is found that the static IP address is configured from DIACom, the IP address of the local IP
     address in the bottom right corner will be different from the original setting. Please change according
     to the following settings.
     1.   Go to Network and Sharing Center and click on the DIACom Ethernet Adapter for your network
          connection.
     3.   Click the Networking tab. Under This connection uses the following items, click either Internet
          Protocol Version 4 (TCP/IPv4)。
_4
     4.   Go to Network and Sharing Center and click on the DIACom Ethernet Adapter for your network
          connection.
           4-8
                                                       Cha p ter 4 In tr od ucti on to D IACo m
6.   Click the Networking tab. Under This connection uses the following items, click either Internet
     Protocol Version 4 (TCP/IPv4)
4_
7.   Set the IP address of the local computer manually. However, you’ll need to make sure there are
     no IP conflicts.
      4.   After the configuration is complete, click the Create Tunnel button to establish a connection
           with the specified tunnel.
      5.   The following information is displayed: tunnel connection status, local delay to the DIACloud
           cloud server, and the IP address used by the local virtual network adapter.
                                                                                                       4-9
     DX-2300 Series Industrial Ethernet Cloud Router
     6.   After successful connection with the cloud, the local computer will be able to use debugging
          tools or monitoring software to debug, monitor, and program the remote network interface
          devices. In addition, you can remotely configure the router's router page (click the device in
          the device list Of the IP address) of the router for remote configuration.
             Notice
       You can create different groups of secure tunnels, divide different devices into
            groups according to their needs, and implement group management devices
       To avoid the virtual network card IP network segment and the local computer
            network card of the actual network to avoid the same network conflict
       After the secure tunnel is successfully connected, you must first disconnect the
            current connection to select another security tunnel,
     1.   Click the icon      at the back of the corresponding remote device to enter the Create Virtual
          Serial Interface
     2    Click on the “Create” button to create a virtual COM port on the local PC, related to
     the RS-232 or RS-485 port on the remote devices. If the RS-232 or RS-485 port is not
     working with transparent mode, the corresponding “Create” button would be
     unavailable.
                 Notice
            Support RS-232 and RS-485 working with transparent mode at the same time.
     4-10
                                                 Cha p ter 4 In tr od ucti on to D IACo m
4_
3    After create successfully, the local PC can perform commissioning, programming and
monitoring to the remote devices with debugging tools or monitoring software.
                                   Description                                       Default
 PPI
 Specially optimize uploading and downloading action PPI for Siemens S7-200
 series.
       Notice
                                                                                    Unchecked
 Please leave unchecked for devices not included in Siemens S7-200 series to
 avoid failed upload/ download error.
Auto Baudrate
       Notice
 We suggest to turn off this function if you’re using Gitzo’s or Mitsubishi’s PLC
 devices.
                                                                                          4-11
     DX-2300 Series Industrial Ethernet Cloud Router
                 Notice
                If the device's RS-232 / RS-485 is not operating in Transparent mode, the
                 corresponding button is grayed out.
_4
     4.2.3        Remote Control and Monitoring via DIACom
     4.2.3.1      Via a LAN Port
     If your router is connected to remote devices via a LAN port, you can use the
     configuring/monitoring software on your local computer to configure and monitor after opening a
     virtual tunnel. Some program would require the IP addresses of your remote device. Simply input
     the required information in the configuring/monitoring software and then you can configure and
     monitor the connected device remotely.
     After opening a virtual tunnel, you will need to follow the setups below before using WPLSoft or
     other configuring/monitoring software on your local computer to configure and monitor the
     connected device remotely.
     1.   Click IP address in the DIACom device list or open a browser and input the IP address of the
          router which is connected to your remote device on the search bar and then log in.
     2.   Go to the System setup page, select the setup option RS232 or RS485 and input the required
          information to set up. Make sure the parameters are consistent with your remote device.
 Parameters of COM (Baud Rate, Data Bits, Stop Bits, Parity Bits, Flow Control)
     3.   Go back to the DIACom and click          to create a virtual tunnel. Once the creation is done,
          the virtual serial-port number will show up on the same page. Users can use it to configure
          and monitor the connected device remotely. Click “Delete” to delete the virtual serial-port.
     4-12
                                              Cha p ter 4 In tr od ucti on to D IACo m
4_
     Notice
    If the PLC is Siemens S7-200, you can select the “PPI” in the DIACom to support PPI
    protocol.
4. Open the WPLSoft to check if the COM parameters are consistent with the settings on your
    router. When these parameters are consistent, you can use the WPLSoft to configure/monitor
    your device remotely.
                                                                                          4-13
     DX-2300 Series Industrial Ethernet Cloud Router
1. Login to DIACom.
2. Click on the icon button in the upper right corner of the windows, and select "Settings".
     3.   Boot automatically log in the required configuration is as follows. Users can set according to
          your needs. If you only need DIACom to connect the security tunnel automatically, the device
          list, RS-485 and RS-232 do not need to be set.
_4
4. Check " Start DIACom on windows logon ", and click "OK" button to save the settings.
            Notice
           Login must be checked "remember password", otherwise DIACom can not be activated
            automatically
     4-14
                                                                                                               5
Chapter 5                  DIACloud
Table of Contents
5.1   Introduction to DIACloud .............................................................................. 5-2
                                                                                                                      5-1
     DX-2300 Series Industrial Ethernet Cloud Router
_5
     2.    Input your email address, password and other relevant information on the registration page. Select “I Agree” and
           click “CREATE AN ACCOUNT”. Please insure your region information is correct, otherwise it may cause problems
           in payment when you extend your service.
                              Notice
                      Click         at the upper right corner to change the interface language to English or
                      Chinese.
     5-2
                                                                       CH5 In trod uc ti on to IOT D IACl ou d
5_
3.   After clicking “CREATE AN ACCOUNT”, a congratulation page will be prompted and an activation email will be sent
     to the email address you have used as your DIACloud account.
4.   You will find an activation email sent from [email protected] in your email box. Open the email,
     click the link in the email and complete DIACloud account activation operation. And you will be redirected to the
     DIACloud login page. Input your account and password to log in to the DIACloud.
                                                                                                                     5-3
     DX-2300 Series Industrial Ethernet Cloud Router
_5
     5.    Open the DIACloud web page (http://www.DIACloudSolutions.com). Log in using your account that you have
           registered.
     5.2.2       Home
     The Home Page will show up after login.
     5-4
                                                                              CH5 In trod uc ti on to IOT D IACl ou d
Item Description
Menu User can switch to corresponding function through menu on the left.
Secure Tunnel is Usable It will show the number of Secure Tunnel groups under the account.
                                Show the service package you selected, users can add package to shopping cart
                                through Devices function and Profile function.
 Electric Invoice
 Paper Invoice
                                                                                                                 5-5
     DX-2300 Series Industrial Ethernet Cloud Router
3. Click , we accept PayPal payments and process credit cards on your order forms.
_5
     5.2.3           Devices
     It will switch to page of device list after clicking “Devices” in navigation bar.
     5-6
                                                                          CH5 In trod uc ti on to IOT D IACl ou d
Item Description
You can filter the device base on you input the key word of the device name.
                             Filter base on tunnel group, show all devices or only show the devices under user
                             specified tunnel group.
                             Show the list of device.The information includes device’s name, device’s SN,
       Devices List          device’s type, storage usage, data usage and the time of binding device.
                              Green represents that the device is online
                              Gray represents the device is offline.
                                    : Represents that all device is displayed currently, and you can switch to
                                   on-line device list after clicking this icon.
                                     : Represents that on-line device is displayed currently, and you can switch
                                   to list of on-line device after clicking this icon.
Refresh pages
 : It will show relevant position information of the device after you click “ ” , which is shown as follows: 5_
It will show the device name and SN of the device after clicking position icon in the map. When a large number of devices
bound to the user’s account, it will switch to other corresponding devices when user clicks blue arrows at the edge of the
map.
        : More detail information about the device will be shown after clicking        under the “Operation” on the right
    side of the device list:
                                                                                                                         5-7
     DX-2300 Series Industrial Ethernet Cloud Router
1. OVERVIEW: The page will show the basic information of the device and the latest alarm message.
_5
Item Description
                                       It represents that device is online if background color is blue, and device is offline if
                                       shows gray.
                                                                 : Show device names; it can switch device after clicking
           Operation zone of device
                                             the drop down arrow.
     5-8
                                                                         CH5 In trod uc ti on to IOT D IACl ou d
                                   Modbus TCP: work modes of Modbus TCP, including Modbus TCP Server,
                                      Modbus TCP Client and Closed
                                   RSSI: it means signal strength of device which contains 5 bars; the larger the
                                      number of green bars is, the stronger the signal strength is;
                             The latest five Alarm of the current device. “      ” represents the state that the email
                             has been sent;
     Latest Alarms
                                   Green represents that the email has been sent successfully
                                   Red represents failure of sending.
2. REGISTER: The page will show and manage register value that uploaded from DX devices.
5_
Item Description
The filtering function displays a list of keywords that match specific registers.
                                  Click     and add the corresponding register and register value, then click “SAVE”
                                  button. DIACloud server will send the corresponding data to the device.
                                  “<” Pervious page,“>” Next page,“1/205” show the current page of register table
                                  and the total amount of register table page.
                                                                                                                         5-9
     DX-2300 Series Industrial Ethernet Cloud Router
Register Table Show the register table, displaying a maximum of 10 registers per page.
                                            Show the register name, when you do not configure an alias in the register, the
                Register Name
                                            register number is displayed.
Register Value Show the current register value and data transfer time.
                                            You can view the current register of historical data or delete the current register; it
                                            can also be configuring registers.
                                            P.S. If this register is not set to remeber history (device configuration page), the
                                            menu does not appear [History] after clicking       icon.
_5
Item Description
     5-10
                                                                           CH5 In trod uc ti on to IOT D IACl ou d
Item Description
Date Start Set the Start Date and query the historical data for a specific time.
    Date End                             Set the End Date and query the historical data for a specific time.
                                                                                                                          5_
    Register Value History Diagram       The latest trend chart of value of register;
Time Axis Users can change time scope of historical data by sliding “ ”.
                                                                                                                 5 - 11
     DX-2300 Series Industrial Ethernet Cloud Router
Item Description
Length
Alias Name Users can set the display name of the register in "Alias Name"
                      function(val) is used for converting register values and similar to the grammar
     function(val)
                      of function-supported JavaScript.
Input the code: return val+“m/s” in function (val){…} as the following picture and save the configuration.
     5-12
                                                                         CH5 In trod uc ti on to IOT D IACl ou d
    Example 2: If you want to convert the register value to the text such as the register value of 1 showing the text as
     ‘NO’; register value of 2 showing the text as ‘OFF’
Input the code in function (val) {…} as the following picture and Click “Save” botton.
5_
3.   SERVICES: This page shows the Device Data Usage, Device Storage Usage and Account Storage Usage for
     users.
                                                                                                                     5-13
     DX-2300 Series Industrial Ethernet Cloud Router
Item Description
 Device Data Usage: Show device traffic usage till now and total capacity.
                                              : User can purchase more traffic package for this accoount if need.
                                   After successful payment, the moment is ready for use.
                                  Device Storage Usage: Show device storage usage till now and total
                                   capacity.
                                  Account Storage Usage:
                                   1.    Account storage is the total amount of traffic showing additional
                                         purchases.
     Storage
                                   2.    Account storage can be shared with all devices under your account.
_5                                 3.    Before the device storage is exhausted strorage space, the account
                                         storage will not be used.
                                              : User can purchase more traffic package for this accoount if need.
                                   After successful payment, the moment is ready for use.
        After Click the           in Data field, it will show the traffic package select page. User can add a package to cart or
         checkout directly.
 After Click the , it will show the Data Usage History in past 12 months.
     5-14
                                                                        CH5 In trod uc ti on to IOT D IACl ou d
    After Click the         in Storage field, it will show the storage package select page. User can add a package to cart
     or checkout directly.
5_
4. MORE: This page will show the Serial Number, Software Version, Hardware Version, and IMEI for users.
                                                                                                                     5-15
     DX-2300 Series Industrial Ethernet Cloud Router
Item Description
     5.2.4          Alarm
     Click the Alarm in the left menu. The warning information in the latest 7 days will be shown in this page. The warning
     information includes name and serial number of device, content of warning, status of email that is being sent (green“    ”
     represents that the email has been sent successfully, and red represents fail.), time of warning and content record of
     warning.
_5
     5-16
                                                                         CH5 In trod uc ti on to IOT D IACl ou d
5_
Users can manager the tunnel network in this page. Interface is shown as follows:
tem Description
Tunnel network List List all tunnel network under this account.
                                                                                                           5-17
     DX-2300 Series Industrial Ethernet Cloud Router
Item Description
     5-18
                                                                     CH5 In trod uc ti on to IOT D IACl ou d
Item Description
Sub Users List Show the list of all sub users in main account.
                                                                                                       5-19
     DX-2300 Series Industrial Ethernet Cloud Router
Item Description
               : User can add sub users after clicking the “+” on the page, and.the following interface will be shown after
            clicking the “+” in the page:
_5
     2.     The system will send an activation email which is attached with random login password to email box of sub user.
            The account status is “Un-activated” now.
     3.     Go to the mailbox, click the hyperlink to complete account activation operation, then sub user can login DIACloud
            with new account.
4. The page will link to the following page after clicking the activation link in the email:
     5-20
                                                                          CH5 In trod uc ti on to IOT D IACl ou d
                                                                                                                                5_
5.    When user login to DIACloud with main account and the sub user that we created has been activated.
5.2.7          Logs
This page will show the web operation information of some users. It includes: login IP, setup of register, API interface call
of DIACloud and other information.
                                                                                                                        5-21
     DX-2300 Series Industrial Ethernet Cloud Router
     5.2.8          Orders
     In this page, users can check all orders. Continue to pay for the unpaid orders or cancel the unpaid orders.
_5 Item Description
 Order detail
 Payment Method: Currently, we only support PayPal payment for the world wide user.
     5-22
                                                                        CH5 In trod uc ti on to IOT D IACl ou d
5.2.9          Profile
In this page, QR Code of user, Package info, password management and other information will be shown.
Item Description
QR Code You can get the part information of user by using DIACloud APP and scanning QR Code.
Packeage info  Users can purchase more traffic/storage package for this account if need
                                                                                                                 5-23
     DX-2300 Series Industrial Ethernet Cloud Router
MEMO
_5
     5-24
                                                                                                            6
Chapter 6               DIACloud APP
Table of Contents
 6.1   Introduction to DIACloud APP .................................................................... 6-2
                                                                                                                   6-1
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     6-2
                              Ch ap ter 6 In trod uc ti on to D IAC lou d APP
Item Description
Auto Login Save the password and login the APP automatically
                                                                                 6-3
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     Device tab and alarm tab will be shown in the APP. In the device tab, the device information will
     be shown, including the value of registers of the remote device. And the value of the register can
     be changed in the APP as well. In the alarm tab, users can read the alarm messages.
_6
              Item                                      Description
     6-4
                                         Ch ap ter 6 In trod uc ti on to D IAC lou d APP
Item Description
                                                                                    6-5
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
     In the register page, the user can browse the collected data. The register data can be refreshed
     by the pull-down screen. When the number of registers is large, you can pull up the screen to
     display more data.
_6
            Item                                        Description
     6-6
                                         Ch ap ter 6 In trod uc ti on to D IAC lou d APP
Click “ok” button, the register value will be pushed to the device.
     Alarm tab will be shown by clicking icon    , the alarm messages in Red are unread
      messages. Digit in parentheses is the number of alarm messages.
                                                                                                   6_
     Pull down the APP to refresh the alarm list.
                                                                                             6-7
     D X-2 300 Se ri es Ind ustr ia l Ethe rne t C lo ud Ro u ter
MEMO
_6
6-8