Belimo 22PDP-58.. Datasheet En-Us

The document provides a technical data sheet for the 22PDP-58 differential pressure sensor designed for HVAC systems, suitable for water and water-glycol mixtures. It includes specifications such as measuring ranges, output signals, electrical data, and safety information. The sensor features a NEMA 4X/IP65 rated enclosure, an LCD display, and requires manual zero-point calibration every 12 months.

Uploaded by

Rodrigo Carrasco
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views4 pages

Belimo 22PDP-58.. Datasheet En-Us

The document provides a technical data sheet for the 22PDP-58 differential pressure sensor designed for HVAC systems, suitable for water and water-glycol mixtures. It includes specifications such as measuring ranges, output signals, electrical data, and safety information. The sensor features a NEMA 4X/IP65 rated enclosure, an LCD display, and requires manual zero-point calibration every 12 months.

Uploaded by

Rodrigo Carrasco
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Technical data sheet 22PDP-58..

Differential pressure sensor Water

Active sensor (4...20 mA / 0...5 V / 0...10 V) for


differential pressure measurement in HVAC
systems. The sensor is suitable for water and
water-glycol mixtures. NEMA 4X / IP65 rated
enclosure and with LCD display.

Type Overview

Measuring Output signal


Overpressure
Type range pressure active Overpressure Burst pressure
note
[psi] pressure
22PDP-585 0...100 4...20 mA, 200 psi Single-sided 2000 psi
0...5 V, 0...10 V
22PDP-588 0...250 4...20 mA, 500 psi Single-sided 5000 psi
0...5 V, 0...10 V

Technical data

Electrical Data Nominal voltage AC/DC 24 V


Nominal voltage range AC 21.6...26.4 V / DC 21.6...26.4 V
Power consumption AC 3.1 VA
Power consumption DC 1.4 W
Electrical connection Pluggable spring loaded terminal block max.
2.5 mm²
Cable entry Cable gland with strain relief ø6...8 mm

Functional Data Application water


Water-glycol mixture
Multirange 4 measuring ranges selectable
Voltage output 1 x 0...5 V, 0...10 V, min. resistance 10 kΩ
Current output 1x 4...20 mA, max. resistance 500 Ω
Output signal active note 0...5/10 V or 4...20 mA output, selectable with
switch
Mechanical connection pressure connector: G 1/4"
Display LCD, 16 x 38 mm
Response time <0.5 s

Measuring Data Measured values Differential pressure


Measuring range pressure settings Type Ranges [psi]
22PDP-585 0...100 (factory setting),
0...10, 0...20, 0...50
22PDP-588 0...250 (factory setting),
0...25, 0...50, 0...125
Accuracy pressure ±1% FS (Full scale) @ 72°F [22°C]
±0.03% FS (Full scale) per K and pressure
transmitter
Accuracy pressure ±1% FS (Full scale) @ 72°F [22°C] ±0.03% FS (Full
scale) per K and pressure transmitter
Long-term stability ±0.25% FS p.a. and per pressure transmitter

Materials Cable gland PA6, black

www.belimo.com 22PDP-58.. • en-us • 2023-03-13 • Subject to change 1/4


Technical data sheet 22PDP-58..

Materials Housing Cover: PC, transparent


Bottom: PC, orange
Cable: PVC, grey
Seal: NBR
Fluid wetted parts Stainless steel 17-4 PH

Safety Data Protection class IEC/EN III, Safety Extra-Low Voltage (SELV)
Degree of protection IEC/EN IP65
Degree of protection NEMA/UL NEMA 4X
Enclosure UL Enclosure Type 4X
EU Conformity CE Marking
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-6
Quality Standard ISO 9001
UL Approval cULus acc. to UL60730-1/-2-6, CAN/CSA
E60730-1/-2
Type of action Type 1
Rated impulse voltage supply 0.8 kV
Installation method Independently mounted control
Pollution degree 4
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature 0...50°C [32...122°F]
Fluid temperature -40...220°F [-40...105°C]
At a fluid temperature of < 2°C [< 36°F], frost
protection must be guaranteed

Safety Notes

This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application. Unauthorized
modifications are prohibited. The product must not be used in relation with any equipment that
in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
Only authorized specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.

Remarks

Manual zero-point calibration In normal operation zero-point calibration should be executed every 12 months.
A sensor zeroing can be initiated by pressing and holding the internal ZERO switch for at least 3
seconds. If both pressure ports are close to zero pressure, the device will calibrate with a new
zero point. The zeroing can also be initiated by pressing the optionally connected remote
switch, and thus by holding the ZERO terminal low for 3 seconds.
Please make sure on the system side that the same pressure conditions exist at both remote
sensors as precondition of a correct zeroing.

www.belimo.com 22PDP-58.. • en-us • 2023-03-13 • Subject to change 2/4


Technical data sheet 22PDP-58..
Indicators and Operation

Indicators The display has 2 lines with 8 characters each.


The software version, model pressure range and output signal type are displayed during
booting.
The display is menu-guided and used for programming during installation as well as for display
of pressure read from sensors.
The menu allows to set parameters such as output signal, pressure range, pressure scale,
pressure port, damping and backlight.
For a convenient reading of the display, an upright wall mounting of the sensor housing with
the display at the top, electrical connections on the right and at the bottom is recommended.

1 Start and programming

Line 1: Parameter
Line 2: Value

2 Operation

Line 1: Differential pressure value


Line 2: Differential pressure unit

Parts included

Parts included Description Type


Mounting plate L housing A-22D-A10
Cable Gland with strain relief ø6...8 mm
Dowels
Screws

Accessories

Optional accessories Description Type


3-valve manifold with bracket EXT-GS-3WM
Reduction adapter, G 1/4" (internal thread) to G 1/2" (external thread) A-22WP-A02
Connection adapter flex conduit, M20x1.5, for cable gland 1 x 6 mm, A-22G-A01.1
Multipack 10 pcs.

Wiring Diagram

Notes The external switch at terminal ZERO is optional. It can be used in case remote zeroing is
required. Otherwise, ZERO terminal can be left open. Zeroing can be initialized by pressing the
internal ZERO key in this case.
See also details under chapter manual zero-point calibration.

www.belimo.com 22PDP-58.. • en-us • 2023-03-13 • Subject to change 3/4


Technical data sheet 22PDP-58..
Dimensions

Further documentation

• Installation instructions
• Operating instructions

www.belimo.com 22PDP-58.. • en-us • 2023-03-13 • Subject to change 4/4