Client                                                      Telangana State Power Generation Corporation limited
Project                                                     5x800MW Yadadri TPS, Nalgonda
          Cotractor/Vendor                                            BHEL , PEM
          Drawing No.                                                 PE-DC-417-510-E044-R0
          Title                                                       RELAY SETTING CALCULATIONS
                                                                      FOR TRANSFORMER PROTECTION
Sl. No.                    TCE/TSGENCO Comments                                                BHEL Reply
          Submit the revised relay settings calculation document by   Pls. note 2 Runs of 2.5 sqmm Cu Cable has been evisaged
          considering the CT Secondary cable size 4.0Sq.mm            instead of 4 sq.mm size for 3 Core cable accordingly the
  1       (instead of 2.5Sq.mm) as per the approved CT & VT sizing    calculation for relay setting is furnished. Kindly furnish
          document (PE-DC-417-510-E43-R06).                           your kind approval on the same.
          87OH( Overhang) Protections settings not furnished.         Noted and incorporated in the revised document.
  2
         TITLE :                                     DOCUMENT NO.
             RELAY SETTING CALCULATIONS              PE-DC-417-510-E044
                         FOR STRP                    REV NO. : 01 DATE : 30.11.2022
                 5 X 800 MW YADADRI TPS
STATION TRANSFORMER PARAMETERS
RATING                                       :   135/ 67.5/ 67.5 MVA
IMPEDANCE, ZHV-LV1 (AT 135 MVA BASE)         :   31% + 7.5% TOL. AT PRINCIPAL TAP
ZHV-LV2 (AT 135 MVA BASE)                    :   31% + 7.5% TOL. AT PRINCIPAL TAP
VOLTAGE RATIO                                :   400/11.5/11.5 kV
RATED HV SIDE CURRENT                        :   195 A
ZLV1-LV2                                     :   57.5%
VECTOR GROUP                                 :   YNyn0yn0
RELAY DETAILS:-
ST DIFF (87ST), HV (51NSTHV)
BACK UP E/F& OVERFLUXING(99ST) (STR4) :              MICOM P643
ST LV1 / LV2 (51NSTHV/LV1/LV2)
BACK UP E/F (STR5/STR6)                  :           MICOM P14N/ GE
ST REF (64R ST-LV1/LV2) (STR2/STR1)      :           GE P14D
ST HV O/C(50/51 ST), REF(64RSTHV) (STR3) :           GE P14D
LINE DIFF (87OHV)                        :           MICOM P14N/ GE
                                                                              Document No:           PE-
                                     5x800 MW YADADRI TPS
                                                                              DC-417-510-E044
                                   RELAY SETTING CALCULATIONS                 Revison:                     1
                                  FOR TRANSFORMER PROTECTION
                                                                              Date:      11/30/22
TRANFORMER DIFFERENTIAL PROTECTION (87ST):                                                   Home
Relay type:                                P643
CT Details       CT primary :              250        A
(TRF HV side):   CT secondary :             1         A
CT Details       CT primary :              4000       A
(TRF LV side):   CT secondary :              1        A
TRF Impedance (HV-LV1)                       31       %         TRF Impedance (HV-LV1)          31
Impedance Tolerance                          7.5      %
Transformer through fault current     =1/(0.31x0.925)
                                            3.51      In
Recommended setting:
Is1:                                        0.2       In
Is2:                                         1        In
k1:                                         30        %
k2:                                         80        %
Is-HS1:                                     4.5       In
Is-HS2:                                      8        In
2nd Harmonic setting, Ih(2)%>:              10        %
5th Harmonic setting, Ih(5)%>:              20        %
Zero seq filt HV:                         Enabled
Zero seq filt LV:                         Enabled
Zero seq filt TV:                        DISABLED
                                                                                             Document No:              PE-
                                       5x800 MW YADADRI TPS
                                                                                             DC-417-510-E044
                                  RELAY SETTING CALCULATIONS                                  Revison:                   1
                                 FOR TRANSFORMER PROTECTION
                                                                                                Date:     11/30/22
TRANSFORMER HV RESTRICTED EARTH FAULT PROTECTION (64RT-HV):                                                     Home
Relay type:                                       P14N
TRF Rating:                                       135           MVA
TRF HV Side Voltage:                              400           kV
TRF LV Side Voltage:                              11.5          kV
TRF Impedance:                                     31           %
Tolerance inTRF Impedance:                        7.5           %
CT Details:
             Phase CT details:
             CT primary :                         250           A
             CT secondary :                        1            A
             Neutral CT Details:
             CT primary :                         250           A
             CT secondary :                        1            A
CT Resistance, Rct:                               0.8           Ohm
Maximum fault current (LV side):           =(135x1000) / (1.732x11.5x0.31x0.925)
                                               23636.58       A
Fault current reffered to HV side:         23636.58x11.5/400
                                                679.55        A
Corresponding CT secondary
                                           = 679.552 x (1/250)
current (If):
                                     If=          2.72          A
Voltage across the relay under
                                           = If (Rct + 2RL)     V
through fault condition
Cable size used for CT connection:                 2.5          sq. mm.     No. of runs:          2
Resistance of cable:                              8.89          Ohms/kM
Length of Connecting cable:                        25           Meters
Lead Resistance, RL:                        = (8.89/2 x0.025)
                                                 0.1111         Ohms
Voltage across the relay under
                                           =2.72 x (0.8 + 2x 0.111125)
through fault condition, Vf:
                                                  2.78          V
Recommended Setting:
Current Setting:                                   10           %
                                                  0.10          A
Value of stabilising resistor:                 = 2.78/0.1
                                                   28           Ohm
Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
                                                                                              Document No:             PE-
                                       5x800 MW YADADRI TPS
                                                                                              DC-417-510-E044
                                   RELAY SETTING CALCULATIONS                                  Revison:                      1
                                  FOR TRANSFORMER PROTECTION
                                                                                                 Date:     11/30/22
TRANSFORMER RESTRICTED EARTH FAULT PROTECTION (64RUT-LV1):                                                      Home
Relay type:                                    P14D
TRF Rating:                                    135           MVA
TRF LV Side Voltage:                           11.5          kV
TRF Impedance:                                  31           %
Tolerance inTRF Impedance:                     7.5           %
CT Details:
             Phase CT details:
             CT primary :                      4000          A
             CT secondary :                      1           A
             Neutral CT Details:
             CT primary :                      4000          A
             CT secondary :                      1           A
CT Resistance, Rct:                             10           Ohm
Maximum fault current :                 =(135x1000) / (1.732x11.5x0.31x0.925)
                                            23636.58       A
Corresponding CT secondary current
                                    = 23636.58 x (1/4000)
(If):
                                If=       5.91         A
Voltage across the relay under
                                        = If (Rct + 2RL)     V
through fault condition
Cable size used for CT connection:              2.5          sq. mm.         No. of runs:           2
Resistance of cable:                           8.89          Ohms/kM
Length of Connecting cable:                     25           Meters
Lead Resistance, RL:                     = (8.89/2 x0.025)
                                              0.1111         Ohms
Voltage across the relay under
                                        =5.91 x (10 + 2x 0.111125)
through fault condition, Vf:
                                               60.41         V
Recommended Setting:
Current Setting:                                 3           %
                                               0.03          A
Value of stabilising resistor:             = 60.41/0.03
                                               2068          Ohm
Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
                                                                                              Document No:             PE-
                                      5x800 MW YADADRI TPS
                                                                                              DC-417-510-E044
                                  RELAY SETTING CALCULATIONS                                   Revison:                 1
                                 FOR TRANSFORMER PROTECTION
                                                                                                 Date:     11/30/22
TRANSFORMER RESTRICTED EARTH FAULT PROTECTION (64RUT-LV2):                                                      Home
Relay type:                                   P14D
TRF Rating:                                    135          MVA
TRF LV Side Voltage:                           11.5         kV
TRF Impedance:                                  31          %
Tolerance inTRF Impedance:                      7.5         %
CT Details:
             Phase CT details:
             CT primary :                      4000         A
             CT secondary :                      1          A
             Neutral CT Details:
             CT primary :                      4000         A
             CT secondary :                      1          A
CT Resistance, Rct:                             10          Ohm
Maximum fault current :                =(135x1000) / (1.732x11.5x0.31x0.925)
                                           23636.58       A
Corresponding CT secondary current
                                    = 23636.58 x (1/4000)
(If):
                                If=       5.91         A
Voltage across the relay under
                                       = If (Rct + 2RL)     V
through fault condition
Cable size used for CT connection:             2.5          sq. mm.          No. of runs:          2
Resistance of cable:                          8.89          Ohms/kM
Length of Connecting cable:                    25           Meters
Lead Resistance, RL:                    = (8.89/2 x0.025)
                                             0.1111         Ohms
Voltage across the relay under
                                       =5.91 x (10 + 2x 0.111125)
through fault condition, Vf:
                                              60.41         V
Recommended Setting:
Current Setting:                                3           %
                                              0.03          A
Value of stabilising resistor:            = 60.41/0.03
                                              2068          Ohm
Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
                                  5x800 MW YADADRI TPS
                                                                                         !"# $ 
                                      
                                                                                         %& ' &&
                                                                                        DC-417-510-E044
                                  () *$%(%(*$                                              010
                                 +$ +%*$                                         11/30/22
                                                                                                     
                                                                                                     07/25/22
dZE^&KZDZ,s<hWZd,&h>dWZKdd/KE;ϱϭEdͲ,sͿ͗                                                 ,ŽŵĞ
ZĞůĂLJƚLJƉĞ͗                                    Wϲϰϯ
dĞƚĂŝůƐ͗   dƉƌŝŵĂƌLJ͗                      ϮϱϬ       
              dƐĞĐŽŶĚĂƌLJ͗                     ϭ        
ZĞĐŽŵŵĞŶĚĞĚƐĞƚƚŝŶŐ͗
ƵƌƌĞŶƚ^ĞƚƚŝŶŐ͗                                Ϭ͘ϯ       /Ŷ
dŝŵĞĞůĂLJ͗                                     ϭ͘ϱ       ƐĞĐΎ
Ύ͗dŚĞĂďŽǀĞƚŝŵĞƐĞƚƚŝŶŐƐŚĂůůďĞĐŽŽƌĚŝŶĂƚĞĚĂƚƐŝƚĞǁŝƚŚůŝŶĞƐŝĚĞƉƌŽƚĞĐƚŝŽŶ͘
EŽƚĞĨŽƌƐŝƚĞ͗^d,sďĂĐŬƵƉŶĞƵƚƌĂůĞĂƌƚŚĨĂƵůƚƌĞůĂLJ;ϱϭEdͲ,sͿĐĂŶŵĂůŽƉĞƌĂƚĞĚƵĞƚŽŝŶƌƵƐŚĐƵƌƌĞŶƚƐŽĨ^dƐ͘dŚĞ
ƉƌŽƚĞĐƚŝŽŶŶĞĞĚƐƚŽďĞďůŽĐŬĞĚďLJϮŶĚŚĂƌŵŽŶŝĐƐŝŐŶĂůŐĞŶĞƌĂƚĞĚŝŶϴϳ^dƌĞůĂLJ;ƚŽďůŽĐŬĚŝĨĨĞƌĞŶƚŝĂůƉƌŽƚĞĐƚŝŽŶĚƵĞ
ƚŽŝŶƌƵƐŚͿ͘ϮŶĚ,ĂƌŵŽŶŝĐƐŝŐŶĂůĨƌŽŵϴϳ^dƚŽďĞƵƐĞĚĂŶĚĐŽƌƌĞƐƉŽŶĚŝŶŐůŽŐŝĐƚŽďĞƉƌĞƉĂƌĞĚŝŶƚŚĞƌĞůĂLJĚƵƌŝŶŐ
ĐŽŵŵŝƐƐŝŽŶŝŶŐ͘
          ϱϭE^dͲ,s
                                                                               Θ
                                                                   EKd
          ϮŶĚ,Ăƌŵ͘ůŬ^ŝŐŶĂů
                                                                                      Document No:            PE-
                                   5x800 MW YADADRI TPS
                                                                                      DC-417-510-E044
                                RELAY SETTING CALCULATIONS                            Revison:                 1
                               FOR TRANSFORMER PROTECTION
                                                                                      Date:        11/30/22
TRANSFORMER LV BACK UP EARTH FAULT PROTECTION (51NT-LV1):                                             Home
Relay type:                                  P14N
CT Details:   CT primary :                   300       A
              CT secondary :                  1        A
Recommended setting:
Current Setting:                              0.3      In A
Time Delay:                                   1.1      sec*
*: The above time setting shall be coordinated with corresponding MV switchgear incomer at site.
                                                                                      Document No:            PE-
                                   5x800 MW YADADRI TPS
                                                                                      DC-417-510-E044
                                RELAY SETTING CALCULATIONS                            Revison:                 1
                               FOR TRANSFORMER PROTECTION
                                                                                      Date:        11/30/22
TRANSFORMER LV BACK UP EARTH FAULT PROTECTION (51NT-LV2):                                             Home
Relay type:                                  P14N
CT Details:   CT primary :                   300       A
              CT secondary :                  1        A
Recommended setting:
Current Setting:                              0.3      In A
Time Delay:                                   1.1      sec*
*: The above time setting shall be coordinated with corresponding MV switchgear incomer at site.
                                                                                            Document No:          PE-
                                         5x800 MW YADADRI TPS
                                                                                            DC-417-510-E044
                                      RELAY SETTING CALCULATIONS                            Revison:                1
                                     FOR TRANSFORMER PROTECTION
                                                                                            Date:      11/30/22
TRF HV IDMT OVERCURRENT PROTECTION (51TRF):
Tranformer rating:                       135                      MVA                                      Home
HV Winding Voltage                       400                      kV
LV Winding Voltage                      11.5                      kV
Relay type:                             P14D
ZHV-LV1:                                 31                       %
CT Details:      CT primary :            500                      A
                 CT secondary :           1                       A
TRF HV side current :                        =(135x1000)/( 1.732 x 400)
                                                   195         A
Corresponding CT secondary current (Is): =194.9 x (1/500)
                                       Is=        0.390        A
Largest motor on the swgr bus:                     BFP
Load details on station bus during starting of largest motor are tabulated below:
   Load type               MVA                    Cos ø             Sin ø           MW       MVAR
Base Load                    33                    0.85             0.53            28.05    17.49
Largest motor              73.29                   0.2              0.98            14.66    71.82
                                                                         Total      42.71    89.31
Total MVA load on transformer during starting of largest motor:
                                        = Sqrt[(42.71)^2 + (89.31)^2]          MVA
                                                 99         MVA
Corresponding HV side current:          99/(sqrt(3)x400)
                                               142.9        A
Correspondiong CT sec current:          142.9 x 1/500
                                               0.286        A
IDMT Pickup Current:                             0.4        In
Through fault current on the LV side:        23636.58       A
Through fault current on the LV side
                                             23636.58 x 11.5/400
reflected on HV side through trf, (Is)
                                                   679.55         A
Time delay to coordinate with LV side
                                                      1           sec
relay setting:
IEC Very Inverse Characteristic on the
                                             TMS(K)= (t [(I/Is) -1 ]) / 13.5
relay:
TMS:                                         {(1)x[679.55/(0.4x500)-1]}/13.5
                                         =          0.178
Recommended setting:
IDMT Over Current Setting(51):                      0.4                   In
TMS                                                0.178
Curve Type:                                   IEC Very Inverse
                                                                                               Document No:                PE-
                                          5x800 MW YADADRI TPS
                                                                                               DC-417-510-E044
                                       RELAY SETTING CALCULATIONS                              Revison:                      1
                                      FOR TRANSFORMER PROTECTION
                                                                                               Date:       11/30/22
TRF HV INSTANTANEOUS OVERCURRENT PROTECTION (50TRF):
Tranformer rating:                      135         MVA                                                          Home
HV Winding Voltage                      400         kV
LV Winding Voltage                      11.5        kV
Relay type:                            P14D
ZHV-LV1:                                 31         %
CT Details:      CT primary :           500         A
                 CT secondary :           1         A
                                        7.5
TRF HV side current :             =(135x1000)/( 1.732 x 400)
                                        195         A
Corresponding CT secondary current (Is): =194.9 x (1/500)
                                        Is=      0.390        A
Through fault current on the LV side:          23636.58       A
Through fault current on the LV side
                                              679.551675      A
reflected on HV side through trf.:
Transformer Inrush current (Iinrush)
                                                1558.9        A
(Assumed 8 times the FLC):
Through fault current reflected on HV on
                                                  1.36        A
CT secondary:
Transformer Inrush current on CT
                                                  3.12        A
secondary (Iinrush sec):
Calculated Current setting:                       3.12
      (Higher of 1.1 times through fault current(HV) on sec of CT or Transformer Inrush current (8 xI flc) on sec of CT)
Recommended setting:
Def. time Over Current Setting(50):              3.15                In
Time                                             0.00               sec
Curve Type:                                    Definate
                                                                                      Document No:             PE-
                                   5x800 MW YADADRI TPS
                                                                                      DC-417-510-E044
                               RELAY SETTING CALCULATIONS                             Revison:                     1
                              FOR TRANSFORMER PROTECTION
                                                                                      Date:        11/30/22
TRANSFORMER OVER FLUXING PROTECTION (99T)                                                              Home
Transformer Overfluxing withstand capability is tabulated below (Derived from Over Fluxing curves obtained
from Tranformer manufacturer:
                                                                                                    Bottom
                                                                                           Relay OverFluxing
   S.No.        Transformer Overfluxing capability
                                                                                            Characteristics
                  Value(pu)            Time(sec)                                                     Time(sec)
     1              1.05                 99999                                           Alarm
     2              1.10                  420                                            IDMT          220.5
     3              1.15                  132                                            IDMT          55.13
     4              1.20                  90                                            Definite        15
     5              1.25                  60
     6              1.30                  36                                            Definite         5
     7              1.35                  20
     8              1.40                   5                                            Definite         2
IDMT characteristics can be provided upto 1.2 pu of Over fluxing. Beyond 1.2 pu, definite time settings could be
provided.
Rated Freq:                               50          Hz
Rated Voltage:                           400          kV
PT Primary:                          400 / sqrt(3)    kV
PT Secondary:                        110 / sqrt(3)    V
Recommended setting:
Alarm stage
Alarm setting:                            1.05          pu
                                          2.31          V/Hz
Alarm delay:                               10           sec
Trip stage
V/Hz>1 Trip setting-1:                     1.05           pu
                                                        2
IDMT Equation:                   [(V/F) / (Vn/ Fn) - 1 ]
V/Hz> 1 Trip Set:                          2.31           V/Hz
V/Hz> 1Trip TMS:                           0.5
V/Hz>2 Trip setting-2:                    1.4           pu
                                          3.08          V/Hz
Trip delay-2:                              2            sec
V/Hz>3 Trip setting-3:                    1.2           pu
                                          2.64          V/Hz
Trip delay-3:                              15           s
V/Hz>4 Trip setting-4:                    1.4           pu
                                          2.42          V/Hz
Trip delay-4:                              0            sec
                                                                                                                                    Document No:            PE-
                                                                       5x800 MW YADADRI TPS
                                                                                                                                    DC-417-510-E044
                                                                   RELAY SETTING CALCULATIONS                                       Revison:                 1
                                                                  FOR TRANSFORMER PROTECTION
                                                                                                                                    Date:       11/30/22
                                                                                                                                                     Home
                                                                                                                                                     Top
                                                                           Setting
                        Settings
                                                                          Settings
V/f Alm Status                                                             Enabled
V/f Alarm Set                                                         2.31 V/Hz (1.05 pu)
V/f Alarm Delay                                                                10 s
V/Hz>1 Status                                                              Enabled
V/Hz>1 Trip Func                                                               IDMT
V/Hz>1 Trip Set                                                       2.31 V/Hz (1.05 pu)
V/Hz>1 Trip TMS                                                                0.5 s
V/Hz>2 Status                                                              Enabled
V/Hz>2 Trip Set                                                       3.08 V/Hz (1.4 pu)
V/Hz>2 Delay                                                                   2s
V/Hz>3 Status                                                              Enabled
V/Hz>3 Trip Set                                                       2.64 V/Hz (1.2 pu)
V/Hz>3 Delay                                                                   15 s
V/Hz>4 Status                                                              Enabled
V/Hz>4 Trip Set                                                       2.42 V/Hz (1.1 pu)
V/Hz>4 Delay                                                                   0s
                                                      1.45
                                                      1.40                                             Transformer Overfluxing capability
           (V/F) / (Vn/ Fn)------------------------
                                                      1.35                                             Relay OverFluxing Characteristics
                                                      1.30                                             Relay Alarm
                                                      1.25
                                                      1.20
                                                      1.15
                                                      1.10
                                                      1.05
                                                      1.00
                                                             0   50      100           150         200          250      300        350        400
                                                                                       Time(Sec)---------------------
The three definite time stages and one IDMT stage are combined to create a combined multi-stage V/Hz trip operating
characteristic using PSL as indicated in relay manual (Figure 40 and Figure 41. page 290 Technical manual no. P64x/EN M/A32)
and shown below:(To be implememted at site)
                                                                                   Document No:          PE-
                                                 5x800 MW YADADRI TPS
                                                                                   DC-417-510-E044
                                            RELAY SETTING CALCULATIONS             Revison:                    1
                                           FOR TRANSFORMER PROTECTION
                                                                                   Date:      11/30/22
OVERHANG DIFFERENTIAL PROTECTION (87OHV):                                                         Home
System Paramet
1. Relay Type Used                                         P14N
2. Type of Impedance                             High
3. Voltage Rating in kV                                              400    A
4. Through Fault Current If in kA                                     63    kA
5. Bus Side CT Ratio -primary                                       2000    A
6. Bus Side CT Ratio -secondary                                        1    A
7. Tie Side CT Ratio -primary                                       2000    A
8. Tie Side CT Ratio -secondary                                        1    A
9. ST Bushing CT Ratio -primary                                     2000
10. ST Bushing CT Ratio -secondary                                     1
11. CT secondary resistance Rct                  10 Ohms                    In
12. Lead Length                                  200 m
 13. Resistance considered for 4.0sqmm CT
lead                                             5.81 Ohms/ kM
 Calculations
 14. Resistance considered for single run of 4
sqmm                                             = 5.81
15. Lead Resistance Rl                           =0.200 x 5.81 Ohms
                                                                    1.162   ohm
                                                 63000/ 2000 (10 + 2 x
                                                                            V
16. Vs = If (Rct + 2 Rl)                         1.162)
                                                                     2.55   V
17. Rstab = Vs / Is                              = 2.55V / 30mA             ohm
                                                                       85   Ohms
Settings Adopted
18 Relay Pickup Is                               30 mA
19 Rstab                                         85 ohm