0% found this document useful (0 votes)
28 views16 pages

Sl. No. TCE/TSGENCO Comments BHEL Reply

The document presents relay setting calculations for transformer protection at the 5x800MW Yadadri TPS project, detailing parameters for various protection relays and their recommended settings. It includes comments from Telangana State Power Generation Corporation and responses from BHEL regarding adjustments in cable sizes and protection settings. The calculations cover transformer differential protection, restricted earth fault protection, and backup earth fault protection, with specific settings and configurations outlined for each relay type.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views16 pages

Sl. No. TCE/TSGENCO Comments BHEL Reply

The document presents relay setting calculations for transformer protection at the 5x800MW Yadadri TPS project, detailing parameters for various protection relays and their recommended settings. It includes comments from Telangana State Power Generation Corporation and responses from BHEL regarding adjustments in cable sizes and protection settings. The calculations cover transformer differential protection, restricted earth fault protection, and backup earth fault protection, with specific settings and configurations outlined for each relay type.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Client Telangana State Power Generation Corporation limited

Project 5x800MW Yadadri TPS, Nalgonda


Cotractor/Vendor BHEL , PEM
Drawing No. PE-DC-417-510-E044-R0
Title RELAY SETTING CALCULATIONS
FOR TRANSFORMER PROTECTION

Sl. No. TCE/TSGENCO Comments BHEL Reply


Submit the revised relay settings calculation document by Pls. note 2 Runs of 2.5 sqmm Cu Cable has been evisaged
considering the CT Secondary cable size 4.0Sq.mm instead of 4 sq.mm size for 3 Core cable accordingly the
1 (instead of 2.5Sq.mm) as per the approved CT & VT sizing calculation for relay setting is furnished. Kindly furnish
document (PE-DC-417-510-E43-R06). your kind approval on the same.

87OH( Overhang) Protections settings not furnished. Noted and incorporated in the revised document.
2
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-417-510-E044
FOR STRP REV NO. : 01 DATE : 30.11.2022
5 X 800 MW YADADRI TPS

STATION TRANSFORMER PARAMETERS

RATING : 135/ 67.5/ 67.5 MVA


IMPEDANCE, ZHV-LV1 (AT 135 MVA BASE) : 31% + 7.5% TOL. AT PRINCIPAL TAP
ZHV-LV2 (AT 135 MVA BASE) : 31% + 7.5% TOL. AT PRINCIPAL TAP
VOLTAGE RATIO : 400/11.5/11.5 kV

RATED HV SIDE CURRENT : 195 A


ZLV1-LV2 : 57.5%

VECTOR GROUP : YNyn0yn0

RELAY DETAILS:-

ST DIFF (87ST), HV (51NSTHV)


BACK UP E/F& OVERFLUXING(99ST) (STR4) : MICOM P643

ST LV1 / LV2 (51NSTHV/LV1/LV2)


BACK UP E/F (STR5/STR6) : MICOM P14N/ GE

ST REF (64R ST-LV1/LV2) (STR2/STR1) : GE P14D

ST HV O/C(50/51 ST), REF(64RSTHV) (STR3) : GE P14D

LINE DIFF (87OHV) : MICOM P14N/ GE


Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANFORMER DIFFERENTIAL PROTECTION (87ST): Home

Relay type: P643

CT Details CT primary : 250 A


(TRF HV side): CT secondary : 1 A

CT Details CT primary : 4000 A


(TRF LV side): CT secondary : 1 A

TRF Impedance (HV-LV1) 31 % TRF Impedance (HV-LV1) 31


Impedance Tolerance 7.5 %
Transformer through fault current =1/(0.31x0.925)
3.51 In

Recommended setting:
Is1: 0.2 In
Is2: 1 In
k1: 30 %
k2: 80 %
Is-HS1: 4.5 In
Is-HS2: 8 In
2nd Harmonic setting, Ih(2)%>: 10 %
5th Harmonic setting, Ih(5)%>: 20 %
Zero seq filt HV: Enabled
Zero seq filt LV: Enabled
Zero seq filt TV: DISABLED
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANSFORMER HV RESTRICTED EARTH FAULT PROTECTION (64RT-HV): Home

Relay type: P14N

TRF Rating: 135 MVA


TRF HV Side Voltage: 400 kV
TRF LV Side Voltage: 11.5 kV
TRF Impedance: 31 %
Tolerance inTRF Impedance: 7.5 %
CT Details:
Phase CT details:
CT primary : 250 A
CT secondary : 1 A
Neutral CT Details:
CT primary : 250 A
CT secondary : 1 A
CT Resistance, Rct: 0.8 Ohm

Maximum fault current (LV side): =(135x1000) / (1.732x11.5x0.31x0.925)


23636.58 A
Fault current reffered to HV side: 23636.58x11.5/400
679.55 A
Corresponding CT secondary
= 679.552 x (1/250)
current (If):
If= 2.72 A

Voltage across the relay under


= If (Rct + 2RL) V
through fault condition
Cable size used for CT connection: 2.5 sq. mm. No. of runs: 2
Resistance of cable: 8.89 Ohms/kM
Length of Connecting cable: 25 Meters
Lead Resistance, RL: = (8.89/2 x0.025)
0.1111 Ohms

Voltage across the relay under


=2.72 x (0.8 + 2x 0.111125)
through fault condition, Vf:

2.78 V
Recommended Setting:
Current Setting: 10 %
0.10 A
Value of stabilising resistor: = 2.78/0.1
28 Ohm
Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANSFORMER RESTRICTED EARTH FAULT PROTECTION (64RUT-LV1): Home

Relay type: P14D

TRF Rating: 135 MVA


TRF LV Side Voltage: 11.5 kV
TRF Impedance: 31 %
Tolerance inTRF Impedance: 7.5 %
CT Details:
Phase CT details:
CT primary : 4000 A
CT secondary : 1 A
Neutral CT Details:
CT primary : 4000 A
CT secondary : 1 A
CT Resistance, Rct: 10 Ohm

Maximum fault current : =(135x1000) / (1.732x11.5x0.31x0.925)


23636.58 A
Corresponding CT secondary current
= 23636.58 x (1/4000)
(If):
If= 5.91 A

Voltage across the relay under


= If (Rct + 2RL) V
through fault condition
Cable size used for CT connection: 2.5 sq. mm. No. of runs: 2
Resistance of cable: 8.89 Ohms/kM
Length of Connecting cable: 25 Meters
Lead Resistance, RL: = (8.89/2 x0.025)
0.1111 Ohms

Voltage across the relay under


=5.91 x (10 + 2x 0.111125)
through fault condition, Vf:

60.41 V
Recommended Setting:
Current Setting: 3 %
0.03 A
Value of stabilising resistor: = 60.41/0.03
2068 Ohm
Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANSFORMER RESTRICTED EARTH FAULT PROTECTION (64RUT-LV2): Home

Relay type: P14D

TRF Rating: 135 MVA


TRF LV Side Voltage: 11.5 kV
TRF Impedance: 31 %
Tolerance inTRF Impedance: 7.5 %
CT Details:
Phase CT details:
CT primary : 4000 A
CT secondary : 1 A
Neutral CT Details:
CT primary : 4000 A
CT secondary : 1 A
CT Resistance, Rct: 10 Ohm

Maximum fault current : =(135x1000) / (1.732x11.5x0.31x0.925)


23636.58 A
Corresponding CT secondary current
= 23636.58 x (1/4000)
(If):
If= 5.91 A

Voltage across the relay under


= If (Rct + 2RL) V
through fault condition
Cable size used for CT connection: 2.5 sq. mm. No. of runs: 2
Resistance of cable: 8.89 Ohms/kM
Length of Connecting cable: 25 Meters
Lead Resistance, RL: = (8.89/2 x0.025)
0.1111 Ohms

Voltage across the relay under


=5.91 x (10 + 2x 0.111125)
through fault condition, Vf:

60.41 V
Recommended Setting:
Current Setting: 3 %
0.03 A
Value of stabilising resistor: = 60.41/0.03
2068 Ohm
Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
5x800 MW YADADRI TPS
!"# $ 
 
%& ' &&
DC-417-510-E044
() *$%(%(*$  010
+$ +%*$ 11/30/22
  
07/25/22

dZE^&KZDZ,s<hWZd,&h>dWZKdd/KE;ϱϭEdͲ,sͿ͗ ,ŽŵĞ

ZĞůĂLJƚLJƉĞ͗ Wϲϰϯ

dĞƚĂŝůƐ͗ dƉƌŝŵĂƌLJ͗ ϮϱϬ 


dƐĞĐŽŶĚĂƌLJ͗ ϭ 

ZĞĐŽŵŵĞŶĚĞĚƐĞƚƚŝŶŐ͗
ƵƌƌĞŶƚ^ĞƚƚŝŶŐ͗ Ϭ͘ϯ /Ŷ
dŝŵĞĞůĂLJ͗ ϭ͘ϱ ƐĞĐΎ

Ύ͗dŚĞĂďŽǀĞƚŝŵĞƐĞƚƚŝŶŐƐŚĂůůďĞĐŽŽƌĚŝŶĂƚĞĚĂƚƐŝƚĞǁŝƚŚůŝŶĞƐŝĚĞƉƌŽƚĞĐƚŝŽŶ͘

EŽƚĞĨŽƌƐŝƚĞ͗^d,sďĂĐŬƵƉŶĞƵƚƌĂůĞĂƌƚŚĨĂƵůƚƌĞůĂLJ;ϱϭEdͲ,sͿĐĂŶŵĂůŽƉĞƌĂƚĞĚƵĞƚŽŝŶƌƵƐŚĐƵƌƌĞŶƚƐŽĨ^dƐ͘dŚĞ
ƉƌŽƚĞĐƚŝŽŶŶĞĞĚƐƚŽďĞďůŽĐŬĞĚďLJϮŶĚŚĂƌŵŽŶŝĐƐŝŐŶĂůŐĞŶĞƌĂƚĞĚŝŶϴϳ^dƌĞůĂLJ;ƚŽďůŽĐŬĚŝĨĨĞƌĞŶƚŝĂůƉƌŽƚĞĐƚŝŽŶĚƵĞ
ƚŽŝŶƌƵƐŚͿ͘ϮŶĚ,ĂƌŵŽŶŝĐƐŝŐŶĂůĨƌŽŵϴϳ^dƚŽďĞƵƐĞĚĂŶĚĐŽƌƌĞƐƉŽŶĚŝŶŐůŽŐŝĐƚŽďĞƉƌĞƉĂƌĞĚŝŶƚŚĞƌĞůĂLJĚƵƌŝŶŐ
ĐŽŵŵŝƐƐŝŽŶŝŶŐ͘

ϱϭE^dͲ,s
Θ
EKd
ϮŶĚ,Ăƌŵ͘ůŬ^ŝŐŶĂů
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANSFORMER LV BACK UP EARTH FAULT PROTECTION (51NT-LV1): Home

Relay type: P14N

CT Details: CT primary : 300 A


CT secondary : 1 A

Recommended setting:
Current Setting: 0.3 In A
Time Delay: 1.1 sec*

*: The above time setting shall be coordinated with corresponding MV switchgear incomer at site.
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANSFORMER LV BACK UP EARTH FAULT PROTECTION (51NT-LV2): Home

Relay type: P14N

CT Details: CT primary : 300 A


CT secondary : 1 A

Recommended setting:
Current Setting: 0.3 In A
Time Delay: 1.1 sec*

*: The above time setting shall be coordinated with corresponding MV switchgear incomer at site.
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22
TRF HV IDMT OVERCURRENT PROTECTION (51TRF):
Tranformer rating: 135 MVA Home
HV Winding Voltage 400 kV
LV Winding Voltage 11.5 kV
Relay type: P14D
ZHV-LV1: 31 %
CT Details: CT primary : 500 A
CT secondary : 1 A

TRF HV side current : =(135x1000)/( 1.732 x 400)


195 A
Corresponding CT secondary current (Is): =194.9 x (1/500)

Is= 0.390 A
Largest motor on the swgr bus: BFP
Load details on station bus during starting of largest motor are tabulated below:
Load type MVA Cos ø Sin ø MW MVAR
Base Load 33 0.85 0.53 28.05 17.49
Largest motor 73.29 0.2 0.98 14.66 71.82
Total 42.71 89.31

Total MVA load on transformer during starting of largest motor:


= Sqrt[(42.71)^2 + (89.31)^2] MVA
99 MVA
Corresponding HV side current: 99/(sqrt(3)x400)
142.9 A
Correspondiong CT sec current: 142.9 x 1/500
0.286 A
IDMT Pickup Current: 0.4 In
Through fault current on the LV side: 23636.58 A
Through fault current on the LV side
23636.58 x 11.5/400
reflected on HV side through trf, (Is)

679.55 A
Time delay to coordinate with LV side
1 sec
relay setting:
IEC Very Inverse Characteristic on the
TMS(K)= (t [(I/Is) -1 ]) / 13.5
relay:
TMS: {(1)x[679.55/(0.4x500)-1]}/13.5
= 0.178
Recommended setting:
IDMT Over Current Setting(51): 0.4 In
TMS 0.178
Curve Type: IEC Very Inverse
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22
TRF HV INSTANTANEOUS OVERCURRENT PROTECTION (50TRF):
Tranformer rating: 135 MVA Home
HV Winding Voltage 400 kV
LV Winding Voltage 11.5 kV
Relay type: P14D
ZHV-LV1: 31 %
CT Details: CT primary : 500 A
CT secondary : 1 A
7.5
TRF HV side current : =(135x1000)/( 1.732 x 400)
195 A
Corresponding CT secondary current (Is): =194.9 x (1/500)

Is= 0.390 A

Through fault current on the LV side: 23636.58 A

Through fault current on the LV side


679.551675 A
reflected on HV side through trf.:

Transformer Inrush current (Iinrush)


1558.9 A
(Assumed 8 times the FLC):

Through fault current reflected on HV on


1.36 A
CT secondary:

Transformer Inrush current on CT


3.12 A
secondary (Iinrush sec):

Calculated Current setting: 3.12


(Higher of 1.1 times through fault current(HV) on sec of CT or Transformer Inrush current (8 xI flc) on sec of CT)

Recommended setting:
Def. time Over Current Setting(50): 3.15 In
Time 0.00 sec
Curve Type: Definate
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

TRANSFORMER OVER FLUXING PROTECTION (99T) Home

Transformer Overfluxing withstand capability is tabulated below (Derived from Over Fluxing curves obtained
from Tranformer manufacturer:
Bottom
Relay OverFluxing
S.No. Transformer Overfluxing capability
Characteristics
Value(pu) Time(sec) Time(sec)
1 1.05 99999 Alarm
2 1.10 420 IDMT 220.5
3 1.15 132 IDMT 55.13
4 1.20 90 Definite 15
5 1.25 60
6 1.30 36 Definite 5
7 1.35 20
8 1.40 5 Definite 2

IDMT characteristics can be provided upto 1.2 pu of Over fluxing. Beyond 1.2 pu, definite time settings could be
provided.
Rated Freq: 50 Hz
Rated Voltage: 400 kV
PT Primary: 400 / sqrt(3) kV
PT Secondary: 110 / sqrt(3) V

Recommended setting:
Alarm stage
Alarm setting: 1.05 pu
2.31 V/Hz
Alarm delay: 10 sec

Trip stage
V/Hz>1 Trip setting-1: 1.05 pu
2
IDMT Equation: [(V/F) / (Vn/ Fn) - 1 ]
V/Hz> 1 Trip Set: 2.31 V/Hz
V/Hz> 1Trip TMS: 0.5

V/Hz>2 Trip setting-2: 1.4 pu


3.08 V/Hz
Trip delay-2: 2 sec

V/Hz>3 Trip setting-3: 1.2 pu


2.64 V/Hz
Trip delay-3: 15 s

V/Hz>4 Trip setting-4: 1.4 pu


2.42 V/Hz
Trip delay-4: 0 sec
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

Home

Top

Setting
Settings
Settings
V/f Alm Status Enabled
V/f Alarm Set 2.31 V/Hz (1.05 pu)
V/f Alarm Delay 10 s
V/Hz>1 Status Enabled
V/Hz>1 Trip Func IDMT
V/Hz>1 Trip Set 2.31 V/Hz (1.05 pu)
V/Hz>1 Trip TMS 0.5 s
V/Hz>2 Status Enabled
V/Hz>2 Trip Set 3.08 V/Hz (1.4 pu)
V/Hz>2 Delay 2s
V/Hz>3 Status Enabled
V/Hz>3 Trip Set 2.64 V/Hz (1.2 pu)
V/Hz>3 Delay 15 s
V/Hz>4 Status Enabled
V/Hz>4 Trip Set 2.42 V/Hz (1.1 pu)
V/Hz>4 Delay 0s

1.45
1.40 Transformer Overfluxing capability
(V/F) / (Vn/ Fn)------------------------

1.35 Relay OverFluxing Characteristics

1.30 Relay Alarm

1.25
1.20
1.15
1.10
1.05
1.00
0 50 100 150 200 250 300 350 400
Time(Sec)---------------------
The three definite time stages and one IDMT stage are combined to create a combined multi-stage V/Hz trip operating
characteristic using PSL as indicated in relay manual (Figure 40 and Figure 41. page 290 Technical manual no. P64x/EN M/A32)
and shown below:(To be implememted at site)
Document No: PE-
5x800 MW YADADRI TPS
DC-417-510-E044
RELAY SETTING CALCULATIONS Revison: 1
FOR TRANSFORMER PROTECTION
Date: 11/30/22

OVERHANG DIFFERENTIAL PROTECTION (87OHV): Home

System Paramet
1. Relay Type Used P14N
2. Type of Impedance High
3. Voltage Rating in kV 400 A
4. Through Fault Current If in kA 63 kA
5. Bus Side CT Ratio -primary 2000 A
6. Bus Side CT Ratio -secondary 1 A
7. Tie Side CT Ratio -primary 2000 A
8. Tie Side CT Ratio -secondary 1 A
9. ST Bushing CT Ratio -primary 2000
10. ST Bushing CT Ratio -secondary 1
11. CT secondary resistance Rct 10 Ohms In
12. Lead Length 200 m
13. Resistance considered for 4.0sqmm CT
lead 5.81 Ohms/ kM
Calculations
14. Resistance considered for single run of 4
sqmm = 5.81

15. Lead Resistance Rl =0.200 x 5.81 Ohms


1.162 ohm
63000/ 2000 (10 + 2 x
V
16. Vs = If (Rct + 2 Rl) 1.162)
2.55 V
17. Rstab = Vs / Is = 2.55V / 30mA ohm
85 Ohms
Settings Adopted
18 Relay Pickup Is 30 mA
19 Rstab 85 ohm