Page 1(9)
E75000375-100
TEST REPORT OF CURRENT TRANSFORMERS
Test Object ABB Order
IMB 72 E75000375-100
Serial no. Quantity
8876620 - 8876621 - 8876622 3
Standard Test completed
IEC 61869-2 / IEEE C57.13 2017-11-21
Customer Customer reference
PH JC Electrofields Power Sy PO: 2028
Tested by
Daniel Fridh
Test witnessed by
We hereby certify that these transformers have passed all routine tests in accordance
with the standard referred to above and with the terms of the contract.
ABB AB
High Voltage Products
Instrument Transformers
Quality Assurance
Lars Karlén
ABB
ABB ABB AB Made in Sweden
Current transformer Type IMB 72 Production year yyyy
Serial number 1HSE nnnnnnn Standard IEC 61869-2 / IEEE C57.13
Insulation level 140 / 325 kV Frequency 60 Hz
Max continuous primary current 600 A Temperature range -25 – +40 ºC
Highest voltage for equipment 72.5 kV Total mass 210 kg
1HSE 68504-3
Serial number 1HSE nnnnnnn Terminal Ratio (A) Ratings Rct
X,Y 1-2 250/5 C100
Insulation oil (IEC 61039: L-NTIO-296) 26 kg X,Y 1-3 500/5 C100
Ith 31.5 / 1 kA/s Z 1-2 250/5 25VA 0.2S
Idyn 80 kA Z 1-3 500/5 25VA 0.2S
H1 H2 DDF terminal
in secondary box
X1 X2 X3 must be earthed
Y1 Y2 Y3 when in service
Z1 Z2 Z3
1HSE 68504-4
Serial number 1HSE nnnnnnn = 1HSE 8876620 - 8876621 - 8876622
Production year yyyy = Actual year for production
Prepared Responsible department Title
Isabella Eriksson 2017-09-08 PPHC/IM Rating plate
Approved Take over department Language
Björn Sjöström 2017-09-08 en
Revision Order No. Sheet
- E75000375-100 1
Document No. Last
ABB AB 1HSE 22030-RSG 1
We reserve all rights in this document and in the information contained This document is issued by means of a computerized system. The digitally stored
herein. Reproduction, use or disclosure to third parties without express original is electronically approved. The approved document has a date entered in
authority is strictly forbidden. © ABB Power Technologies AB (SE) the ‘Approved’-field. A manual signature is not required.
Page 3(9)
E75000375-100
PRESSURE AND TIGHTNESS TEST
After oil impregnation the transformer withstood an internal oil overpressure without leakage.
POWER - FREQUENCY WITHSTAND TEST AND PARTIAL DISCHARGE MEASUREMENT
Temperature: 21 C
Insulation between DDF terminal and earth withstood a test voltage of 3 kV rms
for 60 seconds. Frequency: 50 Hz
Insulation between each secondary winding and earth withstood a test voltage of 3 kV rms
for 60 seconds. Frequency: 50 Hz
Insulation on primary winding withstood 140 kV for 60 seconds. Frequency: 50 Hz
The partial discharge voltage is reached while decreasing the voltage after the power frequency
withstand test.
Serial no. Partial discharge levels for tested primary voltages
72,5 kV 50,2 kV
[pC] [pC]
8876620 <5 <5
8876621 <5 <5
8876622 <5 <5
CAPACITANCE MEASUREMENT
Temperature: 21 C, Frequency: 50 Hz
Serial no. Capacitance C1
(Top to earth)
[pF]
8876620 927
8876621 842
8876622 943
ABB
Page 4(9)
E75000375-100
MEASUREMENT OF DIELECTRIC DISSIPATION FACTOR
Temperature: 21 C, Frequency: 50 Hz
Serial no. Dissipation factor (tan ) for tested primary voltages
50,2 kV 10 kV
[%] [%]
8876620 0,25 0,25
8876621 0,24 0,24
8876622 0,25 0,25
SECONDARY RESISTANCE MEASUREMENT
Temperature: 20 C
Serial no. Resistance on secondary windings
Term. [m] Term. [m] Term. [m] Term. [m]
8876620 X1-X2 119 X1-X3 236 Y1-Y2 117 Y1-Y3 232
Z1-Z2 176 Z1-Z3 270
8876621 X1-X2 120 X1-X3 241 Y1-Y2 118 Y1-Y3 235
Z1-Z2 178 Z1-Z3 268
8876622 X1-X2 114 X1-X3 230 Y1-Y2 113 Y1-Y3 228
Z1-Z2 172 Z1-Z3 265
INTER – TURN OVERVOLTAGE TEST
Frequency: 60 Hz
At rated primary current (or rated extended primary current when applicable)
applied for 60 s. max. 6000 V peak secondary.
Serial no. Current on primary winding.
Voltage on secondary winding
Terminal [A] [Vpeak] Terminal [A] [Vpeak]
8876620 X1-X3 600 900 Y1-Y3 600 900
Z1-Z3 600 700
8876621 X1-X3 600 900 Y1-Y3 600 900
Z1-Z3 600 700
8876622 X1-X3 600 900 Y1-Y3 600 900
Z1-Z3 600 700
VERIFICATION OF TERMINAL MARKINGS AND TURNS RATIO CHECK
Marking of terminals, polarity and turns ratio is checked on all windings.
When no determination of errors is carried out the turns ratio is checked at 100% of rated current
with the secondary windings unloaded.
ABB
Page 5(9)
E75000375-100
DETERMINATION OF ERRORS
The tests are performed in accordance to the standard and classes referred to in page 1 and 2.
Temperature: 20 C, Frequency: 60 Hz, Rating factor: 1,2
Serial no. Ratio Sec. Primary Burden Ratio Phase
terminal current error error
[A] [VA] [P.F] [%] [min]
8876620 50 X1-X2 250 1 1 -0,06 2,4
50 X1-X2 250 25 0,5 -0,26 -1,5
100 X1-X3 500 1 1 -0,02 1,1
100 X1-X3 500 25 0,5 -0,08 0,1
50 Y1-Y2 250 1 1 -0,06 2,2
50 Y1-Y2 250 25 0,5 -0,25 -1,7
100 Y1-Y3 500 1 1 -0,02 0,9
100 Y1-Y3 500 25 0,5 -0,08 -0,3
50 Z1-Z2 300 6,25 0,8 0,16 0,8
50 Z1-Z2 300 25 0,8 0,12 0,6
50 Z1-Z2 50 25 0,8 0,08 2,7
50 Z1-Z2 2,5 25 0,8 0,07 5,3
100 Z1-Z3 600 6,25 0,8 0,18 -0,1
100 Z1-Z3 600 25 0,8 0,17 0,0
100 Z1-Z3 100 25 0,8 0,16 0,5
100 Z1-Z3 5 25 0,8 0,16 1,1
ABB
Page 6(9)
E75000375-100
Serial no. Ratio Sec. Primary Burden Ratio Phase
terminal current error error
[A] [VA] [P.F] [%] [min]
8876621 50 X1-X2 250 1 1 -0,07 2,4
50 X1-X2 250 25 0,5 -0,26 -1,5
100 X1-X3 500 1 1 -0,02 1,0
100 X1-X3 500 25 0,5 -0,08 -0,2
50 Y1-Y2 250 1 1 -0,06 2,3
50 Y1-Y2 250 25 0,5 -0,26 -1,7
100 Y1-Y3 500 1 1 -0,02 1,0
100 Y1-Y3 500 25 0,5 -0,08 -0,3
50 Z1-Z2 300 6,25 0,8 0,14 0,2
50 Z1-Z2 300 25 0,8 0,09 -0,7
50 Z1-Z2 50 25 0,8 -0,01 0,5
50 Z1-Z2 2,5 25 0,8 -0,08 13,6
100 Z1-Z3 600 6,25 0,8 0,18 0,2
100 Z1-Z3 600 25 0,8 0,16 0,0
100 Z1-Z3 100 25 0,8 0,13 0,5
100 Z1-Z3 5 25 0,8 0,12 3,9
8876622 50 X1-X2 250 1 1 -0,06 2,4
50 X1-X2 250 25 0,5 -0,26 -1,7
100 X1-X3 500 1 1 -0,02 1,0
100 X1-X3 500 25 0,5 -0,08 -0,2
50 Y1-Y2 250 1 1 -0,06 2,3
50 Y1-Y2 250 25 0,5 -0,26 -1,7
100 Y1-Y3 500 1 1 -0,02 1,0
100 Y1-Y3 500 25 0,5 -0,08 -0,3
50 Z1-Z2 300 6,25 0,8 0,15 1,0
50 Z1-Z2 250 6,25 0,8 0,15 1,1
50 Z1-Z2 50 6,25 0,8 0,15 2,2
50 Z1-Z2 12,5 6,25 0,8 0,15 2,4
50 Z1-Z2 2,5 6,25 0,8 0,15 2,3
50 Z1-Z2 300 25 0,8 0,11 0,6
50 Z1-Z2 250 25 0,8 0,10 0,7
50 Z1-Z2 50 25 0,8 0,07 3,4
50 Z1-Z2 12,5 25 0,8 0,07 5,2
50 Z1-Z2 2,5 25 0,8 0,06 5,8
100 Z1-Z3 600 6,25 0,8 0,18 0,2
100 Z1-Z3 500 6,25 0,8 0,18 0,2
100 Z1-Z3 100 6,25 0,8 0,18 0,3
100 Z1-Z3 25 6,25 0,8 0,18 0,4
100 Z1-Z3 5 6,25 0,8 0,18 0,3
100 Z1-Z3 600 25 0,8 0,16 0,1
100 Z1-Z3 500 25 0,8 0,16 0,2
100 Z1-Z3 100 25 0,8 0,16 0,9
100 Z1-Z3 25 25 0,8 0,16 1,2
100 Z1-Z3 5 25 0,8 0,16 1,4
ABB
Page 7(9)
E75000375-100
VERIFICATION OF SECONDARY LIMITING E.M.F.
Secondary limiting e.m.f. is verified at a exciting current corresponding to rated value of
composite error in percent of rated secondary current multiplied with rated accuracy limit
factor or instrument security factor.
Frequency: 60 Hz
Serial no. Terminal Verification of sec.
limiting e.m.f.
[A] [V]
8876618 X1-X2 10 133
Y1-Y2 10 134
8876619 X1-X2 10 134
Y1-Y2 10 133
8876620 X1-X2 10 134
Y1-Y2 10 134
8876621 X1-X2 10 133
Y1-Y2 10 133
8876622 X1-X2 10 134
X1-X3 10 269
Y1-Y2 10 133
Y1-Y3 10 268
8876623 X1-X2 10 134
Y1-Y2 10 133
ABB
Page 8(9)
E75000375-100
SECONDARY MAGNETIZING CURRENT
Frequency: 60 Hz
Serial no. 8876622
Winding X1-X3
[V] [mA]
266,5 3703,5
255,7 358,05
243,1 101,79 10 2
195,3 51,42
178,2 47,02
155 42,24
U [V]
131 37,72
89,6 29,76
53,1 21,34
23,4 12,15
13,5 8,16 10 1
5,9 4,54
101 102 103
I [mA]
Serial no. 8876622
Winding Y1-Y3
[V] [mA]
265,4 4211,51
255,5 441,93
235,8 84,66 10 2
214,5 59,73
185,4 49,38
157,8 43,23
U [V]
131,1 37,97
93 30,42
52,5 21,07
22,8 11,77
14,5 8,51
7,8 5,39 10 1
101 102 103
I [mA]
ABB
Page 9(9)
E75000375-100
Serial no. 8876622
Winding Z1-Z3
[V] [mA] 8*10 1
69,6 3349,04 6*10 1
68,4 224,37 4*10 1
63,8 31,18
51,8 10,3
44,2 6,67 2*10 1
38,2 5,32
31,2 4,36
U [V] 10 1
21,8 3,19 8*10 0
13,2 2,26 6*10 0
6,8 1,51
3,5 1,05 4*10 0
1,9 0,75
2*10 0
100 101 102 103
I [mA]
ABB