Three-phase C&I Hybrid Inverter
X3-ULTRA
15kW / 19.9kW / 20kW
25kW / 30kW
Smart Management Assured Reliability
Single unit UPS-level switchover time <10ms IP66 Ingress protection
Built-in shadow tracking Type II SPD on AC&DC side
Smart loads management(e.g. heat pump, smart EV charger) Optional AFCI protection
Loads respond time within 0.3 s
VPP ready with a variety of compatibility
(OpenADR, IEEE2030.5, FCAS, API)*
High Performance Flexible Adaptability
200% PV oversizing and up to 110% AC output Max. 10pcs parallel for on-grid and off-grid
200% EPS overload for 10s Microgrid and generator function for versatile operations
Max. 60A charging / discharging current Max. 36A PV input per MPPT, optimized for high-power
Low start-up voltage for more power generation solar panel
* Feature to be upgraded in the future
Efficiency Curve Circuit Diagram
DC Switch
98 EPS L1
PV1+ MPPT 1 EPS L2
97 EPS L3
PV1- EPS N
96 PV EMI Inverter INV EMI
800V PV2+ MPPT 2 DC Bus Circuit
Max. Efficiency (%)
Filter Filter
PV2- DC/AC
95 Grid L1
700V Grid L2
PV3+
94 MPPT 3 Grid L3
650V PV3- Grid N
93 600V
92 500V DC SPD
91 400V BAT1+ BAT 1 BAT 1
BAT1- EMI
Circuit
90 320V Filter
89 BAT 2 BAT 2
BAT2+
0% 20% 40% 60% 80% 100% EMI
BAT2- Filter Circuit AC SPD
Load (%)
solaxpower www.solaxpower.com [email protected] +86 571-56260008
*V2.2 Information may be subject to modify without notice. 650.00038.00
X3-ULT-15K X3-ULT-15KP X3-ULT-19.9K X3-ULT-20K X3-ULT-20KP X3-ULT-25K X3-ULT-30K
PV INPUT
Max. recommended PV array power 30 kWp 40 kWp 50 kWp 60 kWp
Max. PV input voltage 1000 V
Rated PV input voltage 600 V
Operation voltage range 120 ~ 950 V
MPPT voltage range 160 ~ 950 V
Start-up voltage 200 V
No. of MPP trackers / strings per MPP tracker 2 / (2 / 2) 3 / (2 / 2 / 2) 2 / (2 / 2) 3 / (2 / 2 / 2)
Max. input current per MPPT 36 A / 36 A 36 A / 36 A / 36 A 36 A / 36 A 36 A / 36 A / 36 A
Max. input short circuit current per MPPT 45 A / 45 A 45 A / 45 A / 45 A 45 A / 45 A 45 A / 45 A / 45 A
AC INPUT & OUTPUT (ON-GRID)
Rated output power 25000 W 30000 W (AS4777 29999 W,
15000 W (AS4777 14999 W) 19999 W 20000 W 20000 W (VDE4105 24900 W) VDE4105 29900 W)
Rated output current 21.8 A 29.0 A 29.0 A 29.0 A 36.3. A 43.5 A
Max. output apparent power 27500 VA 30000 VA (AS4777 29999 VA,
16500 VA (AS4777 14999 VA) 19999 VA 22000 VA 22000 VA (VDE4105 24900 VA) VDE4105 29900 VA)
Max. output continuous current 39.9 A 43.5 A
24.0 A (AS4777 21.8 A) 29.0 A 31.9 A 31.9 A (VDE4105 36.3 A)
Rated AC voltage 3 / N / PE, 220 / 380 V
3 / N / PE, 230 / 400 V
Max. AC input apparent power 15000 VA 19999 VA 20000 VA 20000 VA 25000 VA 30000 VA
Max. AC input current 21.8 A 29.0 A 29.0 A 29.0 A 36.3 A 43.5 A
Rated AC frequency 50 Hz / 60 Hz
Adjustable power factor range ~ 1 (0.8 lagging to 0.8 leading)
THDi (rated power) < 3%
BATTERY
Battery type Lithium
Battery voltage range 120 ~ 800 V
Max. charge / discharge current 60 A (30 A × 2)
EPS (OFF-GRID) OUTPUT (WITH BATTERY)
Rated EPS output voltage, frequency 230 V / 400 V, 50 Hz / 60 Hz
Rated EPS output power 15000VA 19999 VA 20000 VA 25000 VA 30000 VA
Peak EPS output power 2 times of rated power, 10 s
Switchover time < 10 ms
EFFICIENCY
Max. efficiency 98.0%
European efficiency 97.7%
ENVIRONMENT LIMIT
Ingress protection IP66
Operation temperature range -35 ~ 60°C ( > 45°C derating)
Max. operation altitude 3000 m
Relative humidity 0 ~ 100% RH (condensing)
Overvoltage category Mains: III, Battery: II, PV: II
GENERAL
Dimensions (W × H × D) 696 × 526 × 240 mm
Net weight 47 kg
Cooling concept Smart air cooling
Communication interfaces Meter (RS-485), DI x 2, DO x 1, Modbus
Power consumption (night) <5W
Topology Non-isolated
Certifications VDE4105, G99, AS4777, EN50549, CEI 0-21, IEC61727, PEA/MEA, NRS-097-2-1, RD1699, TOR
PROTECTION
Over / under voltage protection, DC reverse-polarity protection, Residual current detection, Over temperature protection,
Protections
DC isolation protection, Grid monitoring, DC injection monitoring, Back feed current monitoring
Active anti-islanding method Frequency shift
Surge protection DC: Type II, AC: Type II
Arc-fault circuit interrupter (AFCI) Optional
The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter
Input voltage exceeding the MPPT voltage range may triggers inverter protection
Compatible with a minimum of 3 units of HS Series batteries, but if the total voltage of the 3 batteries is less than 127V and there is no PV input, the system will not able to startup
When the voltage is below 180V, the inverter will limit the battery current to less than 20A