0% found this document useful (0 votes)
37 views12 pages

Liebert Exm2 BR en GL

The Vertiv™ Liebert® EXM2 is a highly efficient UPS system designed for critical applications, offering power capacities from 100 to 250 kW with efficiencies up to 98.8% in Dynamic Online mode. It features advanced technology for optimal performance, including compatibility with lithium-ion batteries, and is designed for high ambient temperatures and diverse application scenarios. Vertiv provides extensive support and services globally, ensuring reliability and efficiency for data centers and industrial facilities.

Uploaded by

Emon Sharma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views12 pages

Liebert Exm2 BR en GL

The Vertiv™ Liebert® EXM2 is a highly efficient UPS system designed for critical applications, offering power capacities from 100 to 250 kW with efficiencies up to 98.8% in Dynamic Online mode. It features advanced technology for optimal performance, including compatibility with lithium-ion batteries, and is designed for high ambient temperatures and diverse application scenarios. Vertiv provides extensive support and services globally, ensuring reliability and efficiency for data centers and industrial facilities.

Uploaded by

Emon Sharma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Vertiv™ Liebert® EXM2

100 to 250 kW
Highly Reliable and Efficient
UPS designed to provide
industry-leading performance
Vertiv™ Liebert® EXM2 | 100 to 250 kW

About Vertiv

Vertiv brings together hardware, software, analytics and ongoing services to ensure its
customers’ vital applications run continuously, perform optimally and grow with their
business needs. Vertiv solves the most important challenges faced by today’s data centers,
communication networks and commercial and industrial facilities with a portfolio of
power, cooling, and IT infrastructure solutions and services that extends from the cloud
to the edge of the network. Headquartered in Columbus, Ohio, USA, Vertiv employs
around 20,000 people and does business in more than 130 countries. For more
information, and for the latest news and content from Vertiv, visit Vertiv.com.

Vertiv.com

OUR PURPOSE Global Presence


We believe there is a better way to meet the world’s accelerating demand
Manuf. and Assembly Locations 24
for data - one driven by passion and innovation.
Service Centers 220+
Service Field Engineers 3,500+
Technical Support/Response 220+
Customer Experience Centers/Labs 19

Americas Europe, Middle East and Africa Asia Pacific and India
Manuf. and Assembly Locations 10 Manuf. and Assembly Locations 10 Manuf. and Assembly Locations 4
Service Centers 80+ Service Centers 65+ Service Centers 75+
Service Field Engineers 1,600+ Service Field Engineers 650+ Service Field Engineers 1,250+
Technical Support/Response 90+ Technical Support/Response 100+ Technical Support/Response 30+
Customer Experience Centers/Labs 5 Customer Experience Centers/Labs 5 Customer Experience Centers/Labs 9

2
Liebert® EXM2, The Next Generation Mid-size UPS for
Mission-critical Applications

Liebert® EXM2
At Vertiv we believe that being mindful of
product design, development, use, and
disposal are important to the longevity
of our industry.

Checkout these environmentally


conscious features of the Liebert® EXM2:
y Saves cost with up to 98.8%
efficient in Dynamic Online mode
compared to average industry
standard of 96.5% efficiency

y Up to 97% efficient when using Vertiv™ Liebert® EXM2 drives Its extraordinary Double
double conversion mode its evolution from the flagship conversion efficiency up to 97%
Liebert® EXM/Liebert® NXC ensures remarkable operational
y Can sustain high ambient
temperature up to 50 °C which has been widely recognized cost savings. Our proven Dynamic
as proven and highly stable online mode delivers efficiency up
performing UPS in its range to 98.8% whilst compensates the
and has been supporting over load THDi, PF, main sags and
Highlights thousands of critical sites across swells, ensuring fast transfer output
the globe. Backed by dedicated performance. On top of this, Liebert
y Power Capacity: 100, 120, 160, research of Vertiv experts, EXM2 adopts to a range of
200 and 250 kVA/kW Liebert EXM2 is poised to lead in infrastructure conditions including
y Three modes of operation to
the industry with technologically Lithium-ion battery compatibility
boost TCO and performance advancements implanting all the and supports for the leading
next-gen attributes. Machine power factor needs of modern
y Maximum efficiency in the learning based- Three modes of server loads.Seamlessly operates
Mid-size range: Up to 98.8% in
Dynamic online mode and Up to
energy operation ensures the up to 40 oC and can tolerate high
97% in Double conversion mode best energy credentials and ambient temperature up to 50 oC
assures maximum availability. with auto-derating.
y Diverse application scenarios:
In-Row, Room and
Against-the-wall

y Flexible battery configuration: Healthcare Railway/Metro Enterprises Light Industries


Lithium-Ion Batteries
compatibility & adapts to
two wire connection

y Symmetrical Power Factor


(0.5 leading to 0.5 lagging)

y Scalable in parallel up to 1.5 MW

• Health • Communication • Critical


y High ambient temperature • Datacenter
Diagnostic System Process
up to 50 °C with auto-derating • CPSS
Equipments • Automatic Fare Equipments
above 40 °C • Work stations
• Datacenter Collection • Datacenter
y Reliability boosters: Robust air • CPSS • CPSS • CPSS
channels, PCBs embedded with • Operational • Work stations
conformal coating Control Center

y Seismic complaint
(with optional kit)

3
Vertiv™ Liebert® EXM2 | 100 to 250 kW

Flexible And Optimized Design

Aesthetic Design Adapts Well Into Your Infrastructural Needs


y Ideal for In-the-Row server
rack applications

y Suitable to be installed against


the wall using optional top fan kit

y Suitable to be installed adjacent


to the wall

y Compact and lightweight


footprint saves significant
white floor space

1 Bypass Section
1 2
2 Power Section

3 Integrated 2
Surge Protection 6

6
4 Switch Assembly
3 3

5 Cable Termination
Section (Bottom 4 4
as standard)

6 Top cable
Termination panel 5
(Optional)
5

100-160 kVA 200-250 kVA

4
Highly Efficient and Lowest TCO

Liebert® EXM2 delivers an The efficiency and electricity cost The Dynamic online mode ensures
outstanding Double conversion savings of Liebert EXM2 can be Class 1* output performance under
efficiency of up to 97%, which attributed to: most stringent conditions:
further increases up to 98.8% y Network fault
y Latest generation IGBT
with the Dynamic online mode, (voltage variation, high/ low
consequently reducing operating y Adoption of a three-level impedance mains failures)
costs and energy dissipation (kW) T-type converter topology
to a minimum. This significantly y Load fault (short circuit downstream
minimizes the consumption of y DC controlled fan speed of the UPS)
the cooling system, providing an y Type of load connected
y Intelligent paralleling mode
overall TCO reduction and rapid (PDU transformer)
payback time. y Advanced digital technology
The unit discriminates between various
Furthermore, the Liebert EXM2 and fast transfer
interferences and responds rapidly,
can optimize efficiency at partial The seamless activation of Liebert meanwhile also ensures compatibility
load thereby attaining additional EXM2’s functioning modes ensures with downstream equipment (such as
cost savings through the intelligent the highest level of efficiency Transformers, STS, mechanical loads, etc).
paralleling feature. without compromising power
quality and availability.

Manual Bypass Manual Bypass Manual Bypass

Static Bypass Static Bypass Static Bypass


Rectifier Inverter Rectifier Inverter Rectifier Inverter

Batteries Batteries Batteries

Maximum Power Control (VFI) Maximum Energy Saving (VFD) Dynamic Online, High Efficiency &
Power Conditioning (VI)
Provides the highest level of power Detects when conditioning is not
conditioning and protects the load from required and allows the energy flow to Compensates the load THDi, PF, main
all electrical network disturbances. pass through the bypass line. sags and swells, ensuring fast transfer
output performance.

Dynamic online mode: No more availability trade off with efficiency TYPICAL FUNCTIONING MODES OF A UPS
SYSTEM
DOUBLE CONVERSION ECO MODE
Dynamic online mode is the latest output voltage within the IEC 62040 MODE (VFI) (VFD)
high efficiency mode of operation Class 1* specification, thus offering Maximum Availability with Can’t ensure perfect power
Class 1* UPS quality
offered by Vertiv, developed for the same level of availability typically
those that do not want to trade achieved in a double conversion Highest level of efficiency
up to 97%
Above 99.2% Efficiency

off any level of availability for operating mode.


incremental gains in efficiency. Dynamic online mode is therefore
Dynamic online mode enables able to combine the superior
NEW CONTROL MODE
operating efficiency up to 98.8% availability of a Double conversion DYNAMIC ONLINE MODE
without sacrificing availability. operating mode with the excellent (VI with VFI support)

In fact, while in this mode, the energy cost savings of a high Maximum Availability with
Class 1* UPS

inverter can instantaneously efficiency mode for a reduced


assume the load and maintain the total cost of ownership. Up to 98.8% Efficiency

* Conditions apply

5
Vertiv™ Liebert® EXM2 | 100 to 250 kW

Robust & Proven Design

Innovative Internal Air Channel Tolerates Higher Scalable up to 1.5 MW


Ambient Temperatures
Designed in such a way that 6 units of intelligent paralleling
internal hot air drives directly Internal components and circuitry helps to achieve maximum
towards heat sink without of Liebert EXM2 are designed to capacity up to 1.5 MW. Comes
distressing the PCB's and other seamlessly operate up to 40 °C with Integrated Parallel and LBS
internal sensitive circuits, without any capacity impact and communication ports, and allow
improving the service life of further can sustain high ambient single touch to initiate inverter
components and UPS reliability. temperature up to 50 °C with ON/OFF for all parallel connected
auto-derating. UPS system.
Conformal Coating
Integrated Backfeed Protection Symmetrical Power Factor
Applied as standard feature for all
Compatibility
PCBs in Liebert® EXM2. Its primary Backfeed protection prevents any
purpose is to protect electronics potential risk from electric shock Liebert EXM2 is fully adapted to
from environmental elements on the UPS mains and bypass meet diverse system requirements
and corrosion. The coating acts input AC terminals in the event of in terms of power capacity and
as both a protective shield and a failure of the rectifier and bypass redundancy allowing different
insulative material for a PCB. static switch SCR. The control system designs.
circuit includes output dry
Higher Short Circuit y Output Power Factor up to 1
contacts that activates an internal
Handling Capacity
isolating device (optional) upon y No power derating from
During the short circuit, load will backfeed detection. 0.5 lagging to 0.5 leading
be transferred via bypass to clear
higher short circuit currents. y Optimum space/power ratio
Fuse is considered optionally to
clear short circuit capacity of
up to 65 kA.

Intelligent Paralleling

15%

Six units at 15% load each =


96% efficiency

30%
Liebert® EXM2 Intelligent
Paralleling: three units at 30%
load each = 96.8% efficiency

6
User Interface and Advanced Diagnostic

Liebert® EXM2 makes your


mission critical space a peaceful
place through its advanced
diagnostic capability, measuring
and logging, enhanced event
analysis as well as an intelligent
colored multi-language touch
screen display.
Liebert EXM2 advanced DSP
control platform together with
the patented Vector Control
technology enables increased
performance of three-level power
converters and real time control
of output power quality,
guaranteeing continuous
operation and premium
protection for your business.

Bypass Input Battery


Voltage and frequency Status/values including
measurements. temperature, cell voltage, capacity
run time and testing.
Mains Input
Vertiv™ LIFE™ Services
Current, voltage and frequency
values of the three input phases. Status of Vertiv LIFE Services
connections and calls.
Warning/fault
Tools
Alerts of anomalies on bypass,
rectifier, inverter, booster/charger, LCD settings and language selection.
battery and load.
Output
Events log
Voltage, current, frequency, and
Date and time of important UPS battery measurements.
events, alarms and other warnings.
Measurements
Voltage, current and frequency
values of each internal
functional block.

7
Vertiv™ Liebert® EXM2 | 100 to 250 kW

Lithium-ion Battery Compatibility

The Liebert® EXM2 is powered with most powerful & intelligent battery charger that enables to integrate
seamlessly with any Lithium-ion chemistry batteries.

Considering the benefits lithium-ion batteries provides


over traditional battery deployments. Not only do users
enjoy the longer life, more cycles and fewer replacements,
they also benefit from the compact, smaller size and lower
weight. Plus, the higher operating temperature and lower
maintenance add to the savings.
All these advantages directly impact IT facilities to
drive an impressive total cost of ownership experience.

Vertiv leverages its DNA in critical systems to deliver a


lithium-ion battery system that is integrated seamlessly
into the power chain.
Our capabilities and processes come together to
Vertiv™ HPL lithium-ion cabinet battery with Liebert® EXM2 UPS
ensure the UPS, batteries, monitoring, management,
service and support offerings are orchestrated for
Reduce Battery Replacement Cycles delivering on our customer expectations.
VRLA 3-5 years

LIB 10-15 years

VRLA = valve regulated lead-acid


LIB= data center lithium-ion

Fewer Facility Disruptions


Lower Total Cost of Ownership

Benefits of Lithium-ion Batteries

Longer life Weighs less More cycles

VRLA LIB VRLA LIB LEAD ACID LIB

Saves space Saves cooling cost Battery Management System

VRLA LIB VRLA LIB EXTERNAL BUILT-IN LIB


LEAD ACID

8
Flexible Monitoring & Management Options

Hardware Connectivity User configurable


Input and Output contacts
Liebert® EXM2 allows for the
monitoring and control of y Monitoring external breakers
networked UPS through different y Monitorning "on generator"
protocol options: signal
y Permissive signal for SKRU
The integration of UPS with y Trip external breakers
Building Monitoring and
Automation Systems via MODBUS
RTU, MODBUS/TCP Protocols and
environment sensors.
The integration with synoptic
panels via a dry contact board.

IS-UNITY-DP CARD IS-UNITY-LIFE CARD IS-RELAY CARD

y Supports two simultaneous y SNMP y Dry contact alarm notification


third party protocols (SNMP, y Email & SMS notifications
Modbus TCP or RTU (485), (through LIFE Server)
BACNet IP or MSTP (485)
y Vertiv™ LIFE™ services
y WEB browser
y Email
notifications
y SMS text messages
y SN series sensor support
y Vertiv™ LIFE™ services

Designed for Easy Service and Maintenance

Designed for ease of service

Liebert® EXM2 is designed to allow access to


cable terminal blocks, switches and all the
replaceable components including power &
bypass power modules and communications
from the front side for both installation and
maintenance purposes.

Modular Design and Construction

Common building blocks sub-assembly for an


easy on-site replacement and reduced MTTR.

9
Vertiv™ Liebert® EXM2 | 100 to 250 kW

VERTIV™ LIFE™ Services Remote Diagnostic and Preventive Monitoring

Vertiv's service program is First Time Fix Rate Fast Incident Response
designed to ensure that your
critical power protection system Pro-active monitoring and data Vertiv LIFE Services allow for
is maintained in an optimum state measuring ensure that when our immediate definition of the best
of readiness at all times. customer engineers are dispatched course of action, as a result of the
on-site, they arrive prepared for regular communication between
The Vertiv™ LIFE™ Services first time resolution. your Liebert® EXM2 system and
remote diagnostic and preventive our Vertiv LIFE Service centers.
Proactive Analysis
monitoring service provides early
Reporting
warning of UPS conditions and out From Vertiv LIFE Service centers,
of tolerances. This allows effective our experts proactively analyze the You will receive a comprehensive
proactive maintenance, fast data and trends of your equipment, report detailing the working order
incident response and remote to recommend actions to ensure of your equipment and its
troubleshooting, giving customers their best performance. operational performance.
complete security and peace of
mind. With Vertiv LIFE Services Minimized Total Cost of
you will benefit from: Ownership of Your Equipment
Uptime Assurance The continuous monitoring of all
relevant parameters in turn
Constant monitoring of UPS maximizes unit performance,
parameters, thus maximizing the reduces on-site maintenance and
system’s availability. extends the life of your equipment.

10
Technical Specifications
Nominal Ratings (kVA/kW) 100 kVA 120 kVA 160 kVA 200 kVA 250 kVA

Input
Nominal input voltage (V) 380 / 400 / 415 (three-phase and sharing neutral with the bypass input)
Input voltage range without
228 to 478
battery discharge (V)*
Nominal input frequency (Hz) 50 / 60
Input frequency range (Hz) 40 to 70
Upper limit: +10, +15, or +20, default: +15
Bypass voltage tolerance (%)
Lower limit: -10, -20, -30, -40, default: -20
Bypass frequency tolerance (%) ±10
Input power factor (kW/kVA) 0.99
Input THDi* <3% (full load), 4% (half load)

Battery
Battery bus voltage (VDC) 360 to 528 , 2 Wire
Battery charger max. (A) 30 45 45 60 75

Output
380 / 400 / 415
Nominal output voltage (V)
(three-phase and sharing neutral with the bypass input)
Nominal output frequency (Hz) 50 / 60
Nominal active power (kW) 100 120 160 200 250
THDv with 100% linear load (%) 1
Inverter overload capacity <105 % for Continuous; <110% for 60min; <125 % 10 min; <150 % for 1 min; >150 % for 200ms

Efficiency
Double conversion mode Up to 97%
Dynamic online mode Up to 98.8%
Eco mode Up to 99.2%

Dimensions and weight1


Dimensions (W x D x H), mm 600 x 850 x 1600 600 x 850 x 2000
Shipping dimensions (W x D x H), mm 800 x 1000 x 1800 800 x 1000 x 2180
Weight, kg 315 350 350 412 447
Shipping weight, kg 345 380 380 443 478

General
Noise at 1 m dBA 60 62
Altitude 1500 m no derating, 1500 to 3000 m derate power by 1 % per each 100 m increase
Protection level IP20, IP21, IP31 optional
General and safety requirements for UPS IEC 62040-1
EMC requirements for UPS IEC 62040-2
UPS classification according to VFI-SS-111
IEC EN 62040-3
Central Power Supply Systems (CPSS)
EN 50171
applications*
Rail applications* EN 50121-1; EN 50121-5

* Conditions apply
1. Without side cabinet and top fan subassembly

11
Vertiv.com | Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2023 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While
every precaution has been taken to ensure accuracy and completeness herein, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to
change without notice.

MKA4L0UKEXM2-R4-06/2023 UPS-EXM2-BR-V1-0321-EN

You might also like