GTYQ-CX1200
Series Fixed Gas Detector
Operation Manual
Hanwei Electronics Group Corporation
Ver. No.: HW25051601WY
Thank you for purchasing our products. When you are
ready to use this product, please be sure to read the
instruction carefully and follow the relevant operation
steps provided, so that you can fully enjoy the service
provided by our company, and avoid damage to the
machine or other accidents caused by incorrect
operation. If the user does not follow this manual to
install or repair the replacement parts, the resulting
liability of our company is not responsible.
Hanwei Electronics is solely responsible for the
edition and amendment of this manual, and try to
ensure that the content of the manual is correct. At
the same time, the company reserves the right to
improve the product and modify the manual without
prior notice. The pictures in this manual are only for
function description. If it does not match the actual
product, please refer to the actual product.
Please keep this manual properly so that you can
refer to it and get help whenever you need it in the
future.
Copyright Statement
The copyright of this operation manual is owned by
Hanwei Electronics Group Corporation. Without
written permission, copy, calibration, or store in
database or retrieval system of this operation manual
is not allowed, including diffuse it through electronic,
copy, record, or other means.
User service guide
⚫ When receiving the device, please check whether
the accessories and inspection report certificate
are complete. If there is any missing, please
contact the vendor or manufacturer immediately.
⚫ Within 12 months after the product is sold, under
the normal operation by following the
requirements of storage, transportation and
operating, if the product quality is below the
technical index, the user can get free services
and repairs through the warranty card.
⚫ If you have any query or dissatisfaction about our
product and service, including product
technology, quality, installation & maintenance,
service attitude and charging rates, please
contact the vendor or manufacturer in time. Your
suggestion will be well treated immediately.
Safety Information
Before using the product, please read the following
safety information, and follow the related operation
requirements strictly.
⚫ Please don’t use the gas detector which is
broken. Please check whether there is crack in
the housing or there is short of accessories about
the gas detector. If the gas detector has already
broken or short of accessories, please contact
the vendor or manufacturer.
⚫ The device is calibrated well before leaving the
factory. In order to ensure the detection accuracy
and reliability, we suggest the user make re-
calibration before using on site.
⚫ In order to ensure the user’s safety and the
detector can work normally, please make Bump
Test (put the device in the target gas of a high
concentration than high alarm) before normal
operation. If the device testing result is not within
the required range, please make calibration in
time.
⚫ If the detector is exposed to high concentration of
mixed gas or high humidity and high temperature
environment for a long time, it may cause
pollution or sensitivity reduction of the sensor. In
this case, the detector needs to be calibrated
frequently to ensure reliable operation and
correct indication.
⚫ Disconnect power supply before opening. Be
sure not to open the housing or change sensor
where dangerous gas may be present.
⚫ This gas detector must be installed strictly in
accordance with the operation manual and
following the national and local electrical
installation requirements. Otherwise it may lead
to unpredictable and serious consequences.
⚫ The inside of the sensor may contain corrosive
electrolyte, so please treat it carefully. If there is
leakage, the sensor must be immediately
transferred and treated appropriately. Please
avoid the electrolyte to touch the skin, clothes, or
other instrument circuit, to avoid personal injury
or damage to the equipment.
⚫ The detector must be safely grounded to prevent
RF interference.
⚫ It is forbidden to block or obscure the detection
part during the use of the detector, otherwise it
will lead to failure of the detector.
⚫ When the flammable gas sensor is affected by
poisonous gas or other inhibitors (such as
silicone, sulfur, lead, or halogenated
hydrocarbons, etc.), the sensitivity will be
reduced.
⚫ Spraying or painting of the detector is not
allowed. If the coating has been sprayed,
attention must be paid to ensure that the coating
is not deposited at the entrance of the sensor.
Otherwise, it will hinder the flow and diffusion of
the measured gas and affect the test accuracy.
⚫ In the maintenance process, it is strongly
recommended to use original accessories of
Hanwei company, so as not to damage the
equipment or reduce the performance of the
equipment. Unauthorized replacement of parts
may compromise the internal security of the
detector.
⚫ Do not replace the sensor in an organic solvent
or flammable solution.
⚫ Avoid frequent exposure of the device to high
concentration gas which concentration is beyond
the detection range. Otherwise, the sensor life
will be shortened.
⚫ It is forbidden to disassemble, adjust or repair the
gas detector without permission. Any operation
inside the detector should be carried out by
professionals.
⚫ Avoid the detector from electric shock or severe
and continuous mechanical impact.
1. Product introduction
GTYQ-CX1200 series fixed gas detectors include
GTYQ-CX1200 and GTYQ-CX2200 (hereinafter
called CX1200 and CX2200), which are economical
detectors for checking gas leakage. CX1200 is with
LED indicators only, while CX2200 is with LED screen
and relay output.
The detectors are mainly used in industries such as
chemical plants, electricity, gas, and catering where
there may be flammable gas leaks. When the gas
concentration in the environment exceeds the set
alarm value, the detector will sound an alarm through
the indicator light, and can output a signal to drive the
valve equipment, protecting the personal and property
safety of users.
This detectors have the characteristics of small and
compact structure, explosion-proof, stable and
reliable, easy operation and maintenance, and flexible
wiring.
2. Technical Parameters
Measuring gas Flammable gas /Toxic Gas
Sensor
Catalytic sensor/Electrochemical sensor
principle
Sampling Diffuse naturally
method
Working DC24V±6V
voltage
Power ≤2.5W
consumption
T90≤30s (Flammable),
Response time
T90≤60s(O2&Toxic Gas)
Signal output 4-20mA or Power BUS (optional)
Working Continuously detection
method
Operation IR remote controller
method CX1200 has no relay output by
default, but can be configured with 1
relay output when placing the order.
Relay output
CX2200 has relay output (dry contact,
normally open, activated by low alarm,
capacity 1A @DC24V)
Yellow---Fault alert
Status
Red--Low alarm and high alarm
indicators
Green--Normal monitoring
Working Flammable: -40℃ to +70℃
temperature Toxic: 20℃ to +50℃
Working ≤95%RH (no condensation)
humidity
Air pressure 86kPa to 106kPa
Ingress IP66
protection Ex db II C T6 Gb
Ex-proof grade
Ex tb III C T80℃ Db
Enclosure Aluminum alloy
material
Dimension Stainless
115mm x steel optional
150mm x 60mm(GTQ-BS03)
Weight <800g
Thread screw NPT1/2
RVVP cable, 4 x 1.5mm2 (cable
Cable required diameter is suggested to be 6-9mm)
Transmission Within 1000 meters with the controller
Sensor life 3 years (depends on environment
factor
3. Structure and dimension drawings
)
3.1 Structure Drawing
The detectors are mainly composed of housing,
sensor module, transmitter, etc. The housing is mainly
composed of upper cover, O-ring, lower housing,
sealing plug, protective cover, bulkhead, and plug,
etc.
3.2 Dimension Drawing (Unit: mm)
4. Installation
4.1 Installation and working environment requirements
⚫ The environment where the detector is installed
must meet the atmospheric pressure: 86kPa~
106kPa, altitude below 2000m;
⚫ When the detector is located on the upwind side
of the minimum frequency wind direction of the
release source, the distance between the
combustible gas detector and the release source
should not be more than 15m, and the distance
between the toxic gas detector and the release
source should not be more than 2m;
⚫ When the detector is on the leeward side of the
minimum frequency wind direction of the release
source, the distance between the combustible
gas detector and the release source should not
be more than 5m, and the distance between the
toxic gas detector and the release source should
not be more than 1m;
⚫ If the combustible gas release source is in a
closed or poor ventilated semi-open factory
building, the detectors should be installed every
15m. And the distance between the detector and
any release source within its coverage area
should not be more than 7.5m. The toxic gas
detector should not be more than 1m away from
the release source;
⚫ For combustible gas or toxic gas lighter than air,
if the gas release source is in a closed or poor
ventilated semi-open workshop, besides install a
detector above the release source, a combustible
gas detector or toxic gas detector should also be
installed at the highest point in the workshop
where gas is likely to accumulate.
⚫ The installation height of the detector for
detecting combustible gas whose relative gravity
is heavier than air should be 0.3m~0.6m from
the ground (or floor). Detectors for detecting toxic
gases whose relative gravity is heavier than air
should be close to the leak point, and their
installation height should be 0.3m~0.6m from the
ground (or floor);
⚫ The installation height of the detector for
detecting combustible gas or toxic gas whose
relative gravity is lighter than air should be
0.5m~2m higher than the release source;
⚫ The detector should be installed in a place where
there is no impact, no vibration, no strong
electromagnetic field interference, and easy to
repair. There should be no less than 0.5m of
clearance and access channels between the
place where the detector is installed and the
surrounding pipelines or equipment;
⚫ For the underground integrated pipe gallery,
when the detected gas density is less than the air
density, the detector should be installed at a
position no more than 0.3m away from the top of
the pipe gallery. When the density is greater than
or equal to the air density, the detector should be
installed at a location 0.2m~0.3m from the pipe
gallery floor; the oxygen detector should be
installed at a location of 1.6m~1.8m away from
the pipe gallery floor.
4.2 Installation Method
Note: When installing the gas detector, make sure
that its sensor is downward. And it should be
equipped with a filler type cable entry device that has
obtained the explosion-proof certificate and the
explosion-proof mark is Ex d IIC Gb/Ex Td A21 IP66.
Method 1(Wall-mounting): Determine the hole
location according to the installation plate, and then
use two M6×70 expansion bolts to fix it firmly against
the installation hole of the detector.
Method 2 (Holding pipe fixing method): When there
is a pipeline on site, the U-shaped card matched with
the detector is used to fix the detector on the pipeline.
5. Internal wiring method
Caution: Be sure to perform wiring operations in
the event of a power outage. According to the on-
site conditions, users can first fix the detector and
then wire it, or wire it and then fix the detector.
5.1 Wiring steps
⚫ Rotate the upper cover of the detector
counterclockwise, and then you can see the
circuit board tray in the housing.
⚫ Turn counterclockwise to unscrew the plastic
plug, then screw on the explosion-proof gland
clockwise, and then put the four-core cable
through the explosion-proof gland and sealing
plug in turn, and pass it into the shell from the
wiring hole.
⚫ Connect the wires to the male plugs according to
the marks by following label instruction. And then
fasten the cable shielding layer to the outside of
the housing through a nut to ensure the reliable
grounding of the housing.
⚫ Tighten the rubber sealing ring and hold the cable
tightly. When using Ex hoses, it can also be
directly connected to the detector.
⚫ After ensuring that the first 4 steps are correct,
make sure that the O-ring is put on and tightly
integrated with the upper cover, and turn the
upper cover clockwise until it is tightened.
Remark: Connecting the control panel and the
detector by using the 4-core shielded cable with outer
diameter of 6-9mm (the maximum distance between
the detector and the controller is 1000m).
Note: According to explosion-proof requirements, do
not remove the explosion-proof gaskets from the
unused wiring holes, and don’t throw away the
components on the detector housing and internal
circuit board.
5.2 Terminal block explanation
The terminal block is tilted up 30 degrees for easy
wiring. The terminal block consists of two parts: the
power supply bit (DC24V) and the signal bit, which
cannot be connected incorrectly to each other. The
power supply bit can be positive or negative, usually
left negative and right positive. Signal bits “D+” and
“D-” cannot be connected incorrectly. “L-Alarm”
(optional) is a passive relay output.
4-core RS485 Power BUS detector wiring terminal:
from left to right
Block No. 4 3 2 1
Block D- D+ - 24 +
icon
3-core 4-20mA detector wiring terminal: from left to
right
Block No. 3 2 1
Block icon Iout - 24 +
Relay wiring terminal: from left to right
Block No. 2 1
Block icon L-Alarm
5.3 Wiring drawing with the control panel
5.3.1 Wiring connection of 4-20mA detector:
It can be connected any control panel or system
which supports 4-20mA signal input such as DCS,
PLC, etc. Pay attention that the transmission
distance of 4-20mA signal should be less than 1000
meters, and the loop resistance should not exceed
500 ohms.
5.3.2 Wiring connection of RS485 Power BUS
detector:
RS485 Power BUS is a new type of communication
method developed by our company. It has the
advantages of long communication distance and
stable communication signal. This type of gas
detectors can only be connected with our own panels
like KB100II, KB500 and KB9000 models. Pay
attention that the transmission distance should be less
than 1000 meters. Simultaneously ensuring the power
supply of the detector. The addressable ID of RS485
detector must be unique and not duplicated.
6. Menu operation
The operation and setting of the detector are carried
out by the IR07 remote controller which can be
supplied only by our company Hanwei Electronics
Group Corporation.
6.1 Parameters
Power source 2pcs of AAA alkaline batteries
Dimension 133mm x 50mm x 24mm
Working temp. - 10℃ ~ 50℃
Storage temp. - 20℃ ~ 60℃
Display 128x64 dot matrix LCD
6.2 Button explanation
6.3 Operation instruction
6.3.1 Power on:
Press “Power/Confirm” button to power on the
controller. The controller enters standby interface as
shown in below drawing:
6.3.2 Power off:
⚫ In standby interface, press “Power/Confirm”
button to power off the controller manually.
⚫ Automatically power off when battery voltage is
not enough.
⚫ Automatically power off if no operation within 120
seconds.
Caution: It is forbidden to replace the battery of
the remote controller and open the cover of the
instrument in a dangerous area! If it is not used
for a long time, the battery in the remote
controller should be taken out.
6.3.3 Language setting
In standby interface, press both “Power/Confirm”
button and figure “9” to switch the language between
Chinese and English.
6.3.4 Shortcut operation
In standby interface, user can quick access to zero
calibration, span calibration, and address settings.
Three shortcut keys are distributed on the 3, 4, and 5
numeric keys. If the setting is successful, the green
indicator light of the detector will flash three times. If
the setting fails, the yellow indicator light of the
detector will flash three times.
Zero calibration
After the detector have been used for a long time, or
the detector was put in a new type environment, it
may not display “0” in clean air. This phenomenon is
called “zero drift”. Zero drift is normally caused by big
change of temperature or humidity, and this
phenomenon can be corrected by zero calibration.
Zero calibration procedure is as below:
⚫ Put the detector in the clear air.
⚫ Press the numeric key 3, and the controller will
display the zero calibration interface.
⚫ Press to send the setting information to the
detector and then press to exit to the
standby interface.
Span calibration
Span calibration is the use of a certain concentration
of standard gas to calibrate the indication of a
detector, in order to ensure the detection accuracy
and reliability of the detector. Compared to zero
calibration, it can better correct the sensitivity
deviation caused by long-term use of the detector.
⚫ In standby mode, press the numeric key 4, and
the controller will display the span calibration
interface.
⚫ After setting the parameters, press to send
the set parameters, and then press to exit
to the standby interface (the span calibration
operation needs to be performed after the zero
calibration is successful).
Addressable code setting (of Power RS485 gas
detectors)
⚫ In standby mode, press the numeric key 5, and
the controller will display the address setting
interface.
⚫ After setting the addressable code (1 to 255),
press to send the set parameters, and then
press to exit to the standby interface.
7. Precautions for operation and maintenance
Caution: Operation and maintenance should be
carried out by trained persons.
⚫ In order to avoid personal injury, the detector
must be wired when the power is off.
⚫ The personnel on duty should regularly clean the
dust on the surface of the detector housing with a
dry cloth or vacuum cleaner. Liquid cleaning or
wet cloth is not adoptable.
⚫ In order to better ensure the detection accuracy
and reliability of the detector, it is recommended
to perform a zero calibration before the first use,
and then calibrate the sensor at least once every
6 months.
⚫ Avoid electric shocks or severe and continuous
mechanical shocks to the detector.
⚫ Do not use paint to wipe sensor components or
detectors.
⚫ There must be no fast-flowing gas directly blown
through the detector, otherwise it will affect the
test results.
⚫ Avoid frequent contact of the detector with high-
concentration gas samples whose concentration
exceeds the detection range, otherwise the life of
the sensor will be shortened.
⚫ Water or dust must be strictly prohibited from
entering the detector cavity through pipes or
wires to avoid damage to the detector.
⚫ If you need to repair or replace parts of the
detector, please contact your dealer or
manufacturer.
⚫ Before replacing sensor modules, the detector
must be power off and the sensor module be
unplugged from the detector main PCB.
8. Troubleshooting guidance
Fault Possible reason Solution
Warm-up doesn’t Wait until warm-up
end ends
No
response Contact seller for
to gas Sensor module fault service
Contact seller for
PCB fault
service
Yellow Sensor fault or bad
Replace or re-connect
indicator connection of
the sensor module
flashes sensor module
Replace sensor
E-02 Sensor fault
module
Bad connection of
Replace or re-connect
E-03 sensor module or
the sensor module
module fault
Hanwei Electronics Group Corporation
Address: No.169, Xuesong Road, Hi-Tech Zone,
Zhengzhou 450001, China
Tel.: 0086-371-67169080
Fax: 0086-371-67169090
E-mail: [email protected]
Website: www.hwsensor.com