UXL 100-12
12V 100AH
Extended Life
UXL100-12 Physical Specification
Part Number: UXL100-12
Length: 330 ± 2 mm (12.99 inches)
Awaiting Image Width: 173 ± 2 mm (6.81 inches)
Container Height: 212 ± 2 mm (8.35 inches)
Total Height (with terminal): 220 ± 2 mm (8.66 inches)
Approx Weight: Approx 31.5kg (69.5lbs)
Specifications
Normal Voltage 12V
Normal Capacity (20HR) 100.0AH
Terminal Type Standard Terminal F11
Optional Terminal -
Container Material Standard Option ABS
Flame Retardant Option (FR) ABS(UL94:VO)
Rated Capacity 107.0 AH/5.35A (20hr, 1.80V/cell, 25°C / 77°F)
100.0 AH/10.0A (10hr, 1.80V/cell, 25°C / 77°F)
87.0 AH/17.4A (5hr, 1.75V/cell, 25°C / 77°F)
78.0 AH/26.0A (3hr, 1.75V/cell, 25°C / 77°F)
62.0 AH/62.0A (1hr, 1.60V/cell, 25°C / 77°F)
Max Discharge Current 1200A (5s)
Internal Resistance Approx 4.9mΩ
Discharge Characteristics Operating Temp. Range Discharge: -15 ~ 50°C (5 ~ 122°F)
Charge: 0 ~ 40°C (5 ~ 104°F)
Storage: -15 ~ 40°C (5 ~ 104°F)
Nominal Operating Temp. Range 25 ± 3°C (77 ± 5°F)
Cycle Use Initial Charging Current less than 30.0A.Voltage
14.4V ~ 15.0V at 25°C (77°F) Temp. Coefficient -30mV/°C
Standby Use No limit on Initial Charging Current Voltage
13.5V ~ 13.8V at 25°C (77°F) Temp. Coefficient -20mV/°C
Capacity affected by Temperature 40°C (104°F) 103%
25°C (77°F) 100%
0°C (32°F) 86%
Design Floating Life at 20°C 15 Years
Self Discharge Ultracell batteries may be stored for up to 6 months at 25°C(°77F) and then a refresh charge is required. For
higher temperatures the time interval will be shorter.
Dimensions
F11 Terminal
20 [0.787]
M8 [0.315]
6[0.236]
173 2
41.5
212 2
220 2
POS NEG
268 2
330 2
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
1
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: [email protected] ISO9001
www.ultracell.co.uk
Constant Current Discharge (Amperes) at 25°C (77°F)
F.V/Time 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 117.0 98.4 87.3 72.4 55.9 47.8 31.0 23.3 19.1 16.0 14.1 11.3 9.69 5.17
1.80V/cell 133.9 110.5 96.5 78.6 60.3 50.5 33.3 25.0 20.3 17.0 14.9 11.9 10.0 5.35
1.75V/cell 152.1 124.5 106.7 85.5 65.7 55.0 34.6 26.0 21.0 17.4 15.4 12.3 10.3 5.49
1.70V/cell 171.7 138.2 117.7 93.3 70.8 58.2 36.5 27.4 21.9 18.4 16.1 12.8 10.7 5.63
1.65V/cell 184.4 147.9 125.3 98.5 74.9 60.2 37.8 28.5 22.8 19.0 16.7 13.2 11.0 5.80
1.60V/cell 202.9 162.0 136.1 105.1 77.9 62.0 38.8 29.2 23.3 19.4 17.0 13.4 11.2 5.89
Constant Power Discharge (Watts) at 25°C (77°F)
F.V/Time 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 218.5 185.6 166.3 139.4 108.5 93.2 60.7 45.8 37.7 31.8 27.9 22.5 19.4 10.3
1.80V/cell 247.1 205.6 181.2 149.2 116.1 97.8 64.8 49.0 39.8 33.5 29.4 23.6 20.0 10.7
1.75V/cell 276.2 228.9 198.3 160.8 125.5 106.1 67.2 50.7 41.0 34.2 30.3 24.3 20.5 10.9
1.70V/cell 304.9 250.5 217.3 174.6 134.7 112.0 70.6 53.3 42.8 36.1 31.7 25.3 21.2 11.2
1.65V/cell 324.5 266.2 229.5 182.7 141.2 115.0 72.8 55.2 44.3 37.1 32.7 26.1 21.8 11.6
1.60V/cell 348.9 286.8 246.6 193.6 146.0 117.8 74.3 56.4 45.2 37.9 33.3 26.5 22.2 11.7
Discharge Characteristics Float Charging Characteristics
2V 6V 12V Charged Charged Charge
Battery Battery Battery Temperature:25 0C Volume Current Voltage
V V V % XCA V
0.1CA-2.25V/cell temperature25C
0
140
Terminal Voltage(V)
2.16 6.50 13.0
0.10
120
2.00 6.00 12.0 2.50 CHARGED VOLUME 15.0
1.84 5.50 11.0 100 0.08
0.1C 0.0535C 2.33 CHARGE VOLTAGE 14.0
0.263C
1.68 5.00 10.0 80
0.06
1.073C 0.62C
2.16 13.0
1.52 4.50 9.00 60
0.04
1.36 4.00 8.00 AFTER 50% DISCHARGE
3.5C 2.4C 40 2.00 12.0
AFTER 100% DISCHARGE
0.02
1 2 4 6 8 10 20 40 60 100 200 400 600 1000 2000 Min
20
1.83 11.0
0.1 0.2 0.3 0.4 0.5 1 2 3 4 5 10 20 (Hours) CHARGING CURRENT
0 0 0
0 4 8 12 20 24 28 31 36
Discharge Time 16
Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life
120 16
0.1CA 12
Life expectancy (year)
100 0.25CA 10
8 Charging voltage
0.6CA 2.25V/cell
Capacity %
80 6
60 4
40
1
20
0
20 30 40 50 °C
-20 -10 0 10 20 30 40 50 60 68 86 104 122 °F
Temperature( C)
0
Battery temperature
Self Discharge Characteristics
100
10 C
0
A A
No supplementary charge required
80 (Carry out supplementary charge before use if 100% capacity is required.)
Remaining Capacity(%)
25 C
0
Supplementary charge required before use.Optional charging way as below:
60
B
B 1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.
30 C
0
40 C
0
2.Charged for above 20hours at limited current 0. 25CA and constant volatge 2.45V/cell.
40
3.Charged for 8~10hours at limted current 0.05CA .
C Supplementary charge may often fail to recover the capacity.
20
C
The battery should never be left standing till this is reached.
0
0 2 4 6 8 10 12
Storage Time(Months)
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE