3-Phase Wall-Box 11KW
with 5m standard charger cable
Quick Installation Guide
DN-3P16-050 – Rev 1.0
Please read this manual carefully before installation and use,
otherwise, it may interfere with the normal use of the equipment
and even risk causing personal injury.
1. Safety and Points for Attention
1.1. Installation
Installation must be carried out by personnel with
professional qualification, otherwise there is a risk of
electric shock.
It shall be installed in the place without violent vibration
and impact and placed vertically to facilitate ventilation.
It shall be installed on noncombustible materials such
as metal, or there is a risk of fire.
Do not drop any foreign objects, especially metal
objects, into the inside of the charging station or there
is a risk of fire. The lead nose of the charging station
must be securely attached or there is a risk of damaging
the equipment.
The power supply input cable should have at least
5G2.5mm² (minimum) copper cable while it is
recommended 5G4mm² copper input cable.
1.2. Maintenance
It is recommended that routine safety inspection visits
to charging station be conducted at least once a week.
Please do not attempt to disassemble, repair, or modify
the charger by yourself. If there is a need for
maintenance or modification, please contact certified
2
Electrician/Installers. Improper operation may cause
damage to the equipment.
Do not put inflammable, explosive or combustible
materials, chemicals, combustible steam and other
dangerous goods near the charging station, otherwise
there is a risk of fire.
Please keep the charging adapter clean and dry and
wipe with a clean, dry cloth if soiled. Do not touch the
charging station with your hand when charged.
1.3. Operation
Strictly forbidden for Children or persons of restricted
capacity to approach the charging station to avoid
injury.
Forced charging is strictly forbidden when the electric
vehicle or charging station fails.
Electric vehicle can only be charged with the engine is
off and stationary. Do not charge in rainy and
thunderous weather.
It is strictly prohibited to use the charging station when
the charging adapter or charging cables are defective,
cracked, worn, broken or the charging cables is
exposed. If you find any, please contact the supplier in
time.
In case of rain or thunder, please charge with care.
DO not use the device in extreme temperatures outside
the normal operating range at -30°C to 55°C.
3
Flame
Lightning-proof
resistance
Overvoltage Waterproof
protection IP55
Overcurrent Leakage
protection protection
Overheat IEC 62196-2
protection (Type 2) connector
4
2. Feature
• Compact size design with charging power up-to 11kW.
• Charging plug meet IEC 62196-2 (Type 2) standard.
• Charging adapter is with IP55 waterproof rating for
outdoor usage.
• EV Charger meets IEC 61851 control principle
• Long durability: Charging adapter at no-load plug in/
pull out > 10000 times
• High impact of external force resistance
3. Package Content
• AC EV Charging Station including charging cable x 1pc
• Mounting accessory set including screws x 1set
• Cable management hook x 1pc
• User manual x 1pc
5
4. Technical Specification
Charging mode Mode 3
Input Voltage 3-phase AC, 400V±15%
Rated frequency 50/60Hz
Electric Branch breaker N/A
parameters Input circuit L1/ L2/ L3/ N/ PE
conductor
Copper cable is
recommended with
appropriate conductor
size.
Charging control Direct “Plug-and-
charge”
Display screen N/A
Indicator lights LED light indicator
with 3-color (status,
connect, charging and
fault)
Functional Communication Onboard RS-485
description interface interface
Safety Surge protection,
precautions Over temperature
protection,
RCD Type A + DC6mA,
Over/under voltage
protection, over
current protection,
groundprotection
6
Mounting Wall-mounted
Charging adapter IEC 62196-2, Type 2
Charging cable 5m
Mechanical length
parameters Dimension 310mm × 161mm ×
(H×W×D) 79.8mm
Weight ≤5kg
IP rating IP55
Operational Indoor or outdoor,
environment good ventilation, no
flammable, explosive
gases
Vibration No violent vibration
Environmental and impact
conditions Storage -40~75°C
temperature
Operating -30~55°C
temperature
Operating 95%RH, no water
humidity droplet condensation
7
5. Product Dimension
6. Internal Wiring on AC Terminal Block
AC Input Cable Pin Definition
L3 L2 L1 N PE
8
7. Installation process
1. Position the mounting bracket at the desired height or
following the recommendation below. Install the
bracket onto the wall with the screws packed inside the
package
9
2. Open the back-cover of the Charger and pre-install the
AC input cables following the pin definition on the
Terminal Block.
AC Input Cable Pin Definition
L3 L2 L1 N PE
10
3. Mount the EV Charger onto the wall by hanging it on the
installed bracket. Install another screw from the front to
lock it.
11
4. It is recommended to install the Charging adapter hook
onto the wall at an installation height of 800mm from
the ground
12
5. To complete the installation with an external circuit
breaker at the input side.
13
8. Power-on inspection
8.1. Check before operation
Before operation, please check carefully and ensure the
following:
• The installation position of the EV Charger is convenient
for operation and maintenance
• The EV Charger and its accessories are correctly
connected and installed firmly
• Reasonable selection of leakage protection switch for AC
inlet
• No external objects or parts are left on the top or inside
the Charging Station
8.2. Power on the device
1. Switch on the AC power inlet leakage protection circuit
breaker
2. Power on the Charger: It would take 5 seconds initially
for power-on self-check.
3. After the power-on self-check is completed, the LED
indicator would show the status:
a. Normal standby:
the green light is always (constant) ON.
b. Equipment failure:
Red light is always (constant) ON.
4. When the EV Charger is showing GREEN light constant
ON, then you can take out the Charging adapter to start
charge your Electric Vehicles.
14
5. If your EV Charger is showing RED color, please check
below LED status for error code or contact the
manufacturer
8.3. Start charging
1. Park the electric car into place, turn off the engine, and
put the car under braking.
2. Pick up the charging adapter from the Charger after
Charger is showing Green light constant ON after power-
on self-test.
3. Plug the charging adapter into the AC charging socket of
the electric vehicle and you will see Blue light flashes
indicating charging in progress.
4. As this is direct “plug-and-charge” charging station, it
will automatically enter the charging process.
8.4. Normal stop charging
1. There are two ways to stop charging:
a. Automatic stop when fully charged.
b. Manually stop by removing the charging adapter
from the car socket.
2. Pull the charging adapter out from the vehicle to
complete charging process. If you can't pull out the
adapter, usually because the vehicle is locked, press the
unlock button of the vehicle key and the adapter can be
pulled out.
15
8.5. Abnormally stop charging
1. Forced fault stop: A fault stop initiated by the onboard
charger of vehicle.
2. Automatic fault stop: A fault stop initiated by the
charging station due to internal protection mechanisms
9. LED indicator for Status and Error codes
LED Color Indicator
Index Description Definition
Green Blue Red
Ready to be used
after 5 seconds of
Power-On
Initial
1 ON Off Off Initialization.
Power-on
When LED is
Green, it is ready
to be used.
After self-test, the
device is READY to
plug into Electric
Connecting Carsocket. During
(hand- connection, there
2 shaking Flashes Off Off is a handshaking
with EV) process with EV
which the Green
LED will flashes
quickly.
16
During charging,
Charging the Blue light
3 Off Flashes Off
starts flashes as charging
inprogress
When charging
Charging finishes, the Blue
4 Off On Off
finishes light will be
constant ON
When Control
Pilot pin detects
Control Fault
error during
5 Pilot Off Off (0.5s)
handshaking
Pin Error 1 time
with Electric
vehicle
Fault Error detected:
Under
6 Off Off (0.5s) when Voltage
Voltage
2 time < 304Vac
Fault Error detected:
Over
7 Off Off (0.5s) When Voltage
Voltage
3 time > 456Vac
17
When RCD detects
leakage, the relay
automatically
disconnected the
system. It needs to
Fault
Leakage be re-powered
8 Off Off (0.5s)
Detected after the fault is
4 time
removed before
the relay is allowed
to close to function
again
When over current
is detected, the
relay is
disconnectedthen
Fault
it will automatically
Over (0.5s)
9 Off Off restart after 10s.
Current 5 time
When over
current is detected,
the charging would
be ended.
Temperature >85
degrees, it will
disconnect the
relayautomatically.
Fault
Over Wait for the device
10 Off Off (0.5s)
Temp to cool down
6 time
before turning on
the EV
Charger again
18
When wall-box is
powered-on each
time, it will trigger
RCD leakage Fault a self-check for
11 detection Off Off (0.5s) RCD leakage
self-check 7 time detection. If RCD is
not working, it will
flash red color LED
7x times.
When the
emergency stop
button is pressed
on the side of the
wall-box, it will
flash 8x times red
Fault
Emergency LED to indicate this
12 Off Off (0.5s)
Stop button situation. Please
8 time
release the
Emergency Stop
button after all
fault is removed to
return back to
normal state.
19
Hereby Assmann Electronic GmbH, declares that the
Declaration of Conformity is part of the shipping content. If
the Declaration of Conformity is missing, you can request it
by post under the below mentioned manufacturer address.
www.assmann.com
Assmann Electronic GmbH
Auf dem Schüffel 3,
58513 Lüdenscheid
Germany
20