D22-49A-La Mer - 100% DD - Updated MEP Requirements

The document outlines the MEP requirements for pools and water features in the La Mer project, detailing specifications such as power loads, water demands, and pump room sizes for various pool types. It includes general notes on pump room location, drainage flow rates, and equipment installation considerations. The total electrical load for the project is specified as 940.17 KW, with specific temperature and humidity requirements for the plant room.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views1 page

D22-49A-La Mer - 100% DD - Updated MEP Requirements

The document outlines the MEP requirements for pools and water features in the La Mer project, detailing specifications such as power loads, water demands, and pump room sizes for various pool types. It includes general notes on pump room location, drainage flow rates, and equipment installation considerations. The total electrical load for the project is specified as 940.17 KW, with specific temperature and humidity requirements for the plant room.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Pools & Water Features MEP Requirements Date: 25.02.

2025
Detailed Design Stage 230V / 50Hz / 1ph
Project: D22-49A - La Mer 400V / 50Hz / 3ph

Heat Exchanger Data


Water demand
for each pool
Total Power Total Power
Area Filtration Drainage Pump Room Size
Water Body Volume Load for each Load for all
# Item (L x W) Flow rate Flow rate No. of Pools Maximum LxWxH
Type (m3) Daily Water Fresh water Pool pools Pool Required Chilled Water
(m2) (m3/h) (L/S) Working (m)
Demand supply (KW) (KW) Temperature Flow rate
pressure
(m3) (L/S) (KW) (m3/hr)
(bar)
Level 00 - Ground Floor
Chalet Pool (Balcony) - Elevated
1 Skimmer 8 8 8 0.13 0.03 0.19 23.63 2 47.25 28 (+/-1) 3.00 0.15 3.5 x 2.5 x 2.6
(Skimmer Type) Typical
Chalet Pool (Balcony) - Flush
2 Skimmer 8 8 8 0.13 0.03 0.19 23.63 5 118.13 28 (+/-1) 3.00 0.15 3.5 x 2.5 x 2.6
(Skimmer Type) Typical
3 Elevated Linear Pool Skimmer 17 17 9 0.27 0.07 0.39 42.53 1 42.53 28 (+/-1) 3.00 0.30 3.5 x 2.5 x 2.6
Heat Cool unit Data
Water demand
for each pool
Total Power
Area Filtration Drainage Total Power Pump Room Size
Water Body Volume Load for each Heat Cool unit
# Item (L x W) Flow rate Daily Water Fresh water Flow rate No. of Pools Load for all Outdoor Space Machine sound LxWxH
Type (m3) Pool Dimensions
(m2) (m3/h) Demand supply (L/S) pools for Heat pump pressure (m)
(KW) LxWxH
(m3) (L/S) (m) (dB)
(m)

The 18th floor Pool


4 Amenity floor Pool (Curved Pool) Skimmer 87 78 20 1.37 0.30 1.81 48.30 1 48.30 2 x 0.95 x 2.1 4x3 69.00 3.5 x 2.5 x 2.6
Level 00 - Ground Floor

5 Main Cascade Water Feature Overflow Cascade 337 202 51 5.31 0.78 4.68 51.45 1 51.45 N/A N/A N/A
17 x 9 x 3
6 Kids Pool Overflow 13 7 13 0.20 0.03 0.15 29.93 1 29.93 1.48 x 0.85 x 1 3.5 x 3 56.00
7 Main Pool Overflow 542 650 163 8.54 2.51 5.02 247.80 1 247.80 2.8 x 2.2 x 2.05 8 x 4.5 69.00
8 Indoor Kids Pool Overflow 23.2 12 12 0.37 0.05 0.09 26.78 1 26.78 N/A N/A N/A 4 x 3 x 2.6
Level 01 - First Floor
Drop-off/Entrance Mirror Water
9 Overflow Cascade 669 549 137 10.54 2.12 4.23 86.10 1 86.10 N/A N/A N/A
Feature (Cascade WF) 14.5 x 9.5 x 3
10 Entrance Island Water Feature Overflow 220 110 28 3.47 0.48 2.55 18.90 1 18.90 N/A N/A N/A
The Bridge Private Terrace Pool
Bridge private Terrace Apartment pool
11 Skimmer 29 29 10 0.46 0.11 0.67 18.59 12 223.02 1.5 x 0.9 x 1 3.5 x 3 56 3.5 x 2.5 x 1.2
(Skimmer) Typical
Total Electrical Load 940.17

Plant room Ventilation requirments

1 Plant Room Temp. : Maximum 28 C


2 Humidity : 40%-50%

General Notes:

1 Pump room sizes are including the balancing tank.


2 Pump room location should be maximum 20 meter away from the pool.
3 Pump room should be in a level below the pool water level.
4 Pump room FFL should be minimum 1 meter below pool bottom level.
5 Power load in KW already includes the required load for the heating/cooling units.
6 Heat cool units should be placed in open space not more than 40 m Horizontal and 10 m vertically from the pump room, the area should have a gravity floor drain.
7 Drainage flow rates considering fully emptying the pool by gravity in 1 day (12 hours working time), except Main pool & Drop-off water feature to be drained in 3 days (36 hours working time).
8 Sump pits should be installed in all plant rooms located in the basement or landscape areas. However, for pump rooms situated on typical floors, elevated drains can be used as an alternative.
9 All pool electrical equipment including control panel should be connected to earthing bar and earthing network/pits as well.
10 For the typical pools, the given load is for single pool only.
11 The mentioned height is the required clear height, HVAC team should consider/add their own space.
12 Pump room space requirements has been calculated considering equipment installation, piping connections, daily maintenance access, future replacement of equipment, proper ventilation, and we also
consider the services from other trades (plumbing, HVAC, etc), space optimization can be verified according to final design information which will not exceed 10% minimization.
13 Chemical storage room should be as per Authority and operator requirements.
14 Chilled Water Supply & Return for pools is 6 C° & 14 C° respectively.
15 Ceiling Hock should be provided at the pump room for any future maintenance operation for the pool/Jacuzzi equipment.
16 Above inputs are preliminary and subject to changes based on the final design.