FM12004 Electrical Plans

The document contains a comprehensive list of electrical abbreviations, symbols, and notes relevant to a construction project, including specifications for various electrical components and their installation. It outlines the responsibilities of the contractor and provides guidelines for wiring, conduit sizes, and equipment installation. Additionally, it emphasizes compliance with the National Electrical Code and other regulatory requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views5 pages

FM12004 Electrical Plans

The document contains a comprehensive list of electrical abbreviations, symbols, and notes relevant to a construction project, including specifications for various electrical components and their installation. It outlines the responsibilities of the contractor and provides guidelines for wiring, conduit sizes, and equipment installation. Additionally, it emphasizes compliance with the National Electrical Code and other regulatory requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

COPYRIGHT 2019

All rights reserved. Reproduction or translation of any part


of this work without written permission of
ARCHITECTS WEST INC.
is unlawful and subject to criminal prosecution.

AFC AVAILABLE FAULT CURRENT MCC MOTOR CONTROL CENTER


A B B R E V I A T I O N S AFG
AF
ABOVE FINISHED GRADE
AMP FRAME
MDP
MGAP
MAIN DISTRIBUTION PANEL
MEDICAL GAS ALARM PANEL
XX CONDUIT & WIRE TAG
COMMUNICATIONS S H E E T I N D E X G E N E R A L N O T E S

REFERENCE SYMBOLS
AFCI ARC FLASH CIRCUIT INTERRUPTER MLO MAIN LUGS ONLY XX FAULT CURRENT TAG (AIC)
AFF ABOVE FINISHED FLOOR MOCP MAXIMUM OVERCURRENT PROTECTION # WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF, E-001 GENERAL NOTES, ABBREVIATIONS, AND LEGENDS 1. "GENERAL NOTES" APPLY TO ALL DRAWINGS. "SHEET NOTES"
AIC AMPERE INTERRUPTING CAPACITY MS MOTOR STARTER 1 KEY NOTE UON. PROVIDE 4" BACKBOX AND 1"C ROUTED TO ACCESSIBLE APPLY TO ALL OF THE SHEETS ON WHICH THEY OCCUR.
AHJ AUTHORITY HAVING JURISDICTION MTD MOUNTED CEILING SPACE OR DIRECTLY TO MDF ROOM. DATA CABLING E-002 ELECTRICAL SPECIFICATIONS "KEYNOTES" APPLY ONLY WHERE CALLED OUT.
ATS AUTOMATIC TRANSFER SWITCH NAC NOTIFICATION APPLIANCE CABINET INSTALLED IN FUTURE PHASE.
DETAIL NUMBER
C
CATV
CONDUIT OR CEILING
CABLE TELEVISION
NEC
NIC
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
1 DETAIL E-101 POWER & SYSTEMS PLAN - DEMO / EXISTING 2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED BY
CONTRACTOR UNLESS OTHERWISE NOTED.
XXX P WALL PHONE 43" AFF E-201 POWER & SYSTEMS PLAN - NEW / EXISTING RISER DIAGRAM
CB CIRCUIT BREAKER NL NIGHT LIGHT
CCTV CLOSED CIRCUIT TELEVISION NTS NOT TO SCALE 3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL
SECTION LETTER SHEET WHERE SECTION E-801 LIGHTING SCHEDULE & ELECTRICAL DETAILS
CL CONNECTOR LIGHTING OC ON CENTER # FLOOR OR CEILING MOUNTED TELECOMMUNICATIONS OUTLET. CONTROL DEVICES TO LUMINAIRES FOR CONTROL OF
IS TAKEN FROM
CO CONDUIT ONLY OH OVERHEAD # INDICATES QUANTITY OF VOICE AND DATA JACKS. LUMINAIRES SHOWN.
COMM COMMUNICATIONS OS OCCUPANCY SENSOR
DDC DIRECT DIGITAL CONTROLS PIV POST INDICATOR VALVE SECTION A
PULLSTRING ALWAYS PROVIDED.
4. LUMINAIRES SHOWN ON DRAWINGS FOR QUANTITY AND
DP DISTRIBUTION PANELBOARD PNL PANEL SCALE XXX CIRCUITING ONLY. SEE ARCHITECTURAL REFLECTED CEILING
EC ELECTRICAL CONTRACTOR PS POWER SUPPLY SHEET WHERE SECTION PLANS FOR EXACT LOCATIONS.
EMERGENCY POLYVINYL CHLORIDE WAP WIRELESS ACCESS PORT; SEE SPECIAL SYSTEMS
EM PVC IS TAKEN FROM
ELECTRICAL METALLIC TUBING EXISTING TO BE REMOVED CONNECTION SCHEDULE, WHEN INCLUDED ON PLANS.
EMT R SECTION LETTER 5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN
ER EXISTING TO REMAIN RCPT RECEPTACLE S C WALL MOUNTED SPEAKER/CLOCK COMBINATION EQUIPMENT GROUND CONDUCTOR SIZED PER NEC TABLE
FAAP FIRE ALARM ANNUNCIATOR PANEL RMC RIGID METAL CONDUIT
FACP FIRE ALARM CONTROL PANEL SAC SMALL APPLIANCE CIRCUIT A I C WALL MOUNTED INTERCOM/CLOCK COMBINATION
250.122. ALL WIRING IS BASED ON CU COPPER PER NEC TABLE
310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS. IF
FATC FIRE ALARM TERMINAL CABINET SB,SWBD SWITCHBOARD XXX
ALUMINUM IS ALLOWED, CONTRACTOR IS RESPONSIBLE TO
FCIO FURNISHED BY CONTRACTOR, INSTALLED SG SWITCHGEAR SHEET ON WHICH IF PHOTO, ARROW DENOTES C WALL CLOCK - DIGITAL RE-SIZE ACCORDING TO NEC AMPACITIES FOR LOADS SHOWN
BY OWNER SPD SURGE PROTECTIVE DEVICE SECTION APPEARS DIRECTION TAKEN ON DRAWINGS.
FOIC FURNISHED BY OWNER, INSTALLED BY TEL TELEPHONE S WALL OR CEILING MOUNTED SPEAKER
CONTRACTOR TR TAMPER RESISTANT FIGURE OR PHOTO
6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED
GFCI GROUND FAULT CIRCUIT INTERRUPTER TYP TYPICAL 2 DETAIL NUMBER CABLE TRAY SHALL BE A MINIMUM 12 AWG FOR RUNS 70 FEET OR LESS AND
GFP GROUND FAULT PROTECTION UON UNLESS OTHERWISE NOTED XXX A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET.
GND GROUND UL UNDERWRITERS LABORATORIES TV TELEVISION OUTLET, 18" AFF UON. STUB 3/4" CO INTO
QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND
HTR HEATER UG UNDERGROUND DETAIL NUMBER ACCESSIBLE CEILING SPACE.
SHEET WHERE DETAIL CONTROL DEVICE(S) OR EQUIPMENT WITH A MAXIMUM VOLTAGE
IG ISOLATED GROUND VD VOLTAGE DROP
IMC INTERMEDIATE METALLIC CONDUIT VFD VARIABLE FREQUENCY DRIVE 1 IS TAKEN FROM
SHORT THROW PROJECTOR. MOUNT AT 86" AFF.
DROP OF THREE PERCENT. WHERE CONTRACTOR CHOOSES TO
RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS
JBOX JUNCTION BOX W WEATHERPROOF (WHILE IN USE) XXX
WITHIN ONE RACEWAY OR CABLE, CONDUCTORS SHALL BE
LCP LIGHTING CONTROL PANEL WP WEATHERPROOF A/V RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUIT
INCREASED IN SIZE TO COMPENSATE FOR THE DERATING
LTG LIGHTING XFMR TRANSFORMER SHEET ON WHICH REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES
MCA MINIMUM CIRCUIT AMPACITY DETAIL APPEARS SHALL BE TAKEN FROM THE 75°C COLUMN.
MCB MAIN CIRCUIT BREAKER DETAIL AREA
SECURITY 7. MINIMUM CONDUIT IN EXTERIOR AND UNDERGROUND
A ACCESS CONTROL PANEL LOCATIONS TO BE 1". MINIMUM CONDUIT FOR INTERIOR BRANCH

LIGHTING POWER C SECURITY CONTROLLER


CIRCUITS TO BE 3/4". CONDUITS FROM LUMINAIRES TO LOCAL STRUCTURAL
PROJECT SYMBOLS/LEGENDS/DESIGNATIONS

USER CONTROL DEVICES (SWITCHES, OCCUPANCY SENSORS,


IP SECURITY CAMERA. CONTRACTOR TO PROVIDE ETC.) MAY BE 1/2" OR AS INDICATED IN SPECIFICATIONS.
JUNCTION BOX AND 3/4" CONDUIT WITH NYLON PULL PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO
LUMINAIRE, PENDANT
VFD VARIABLE FREQUENCY DRIVE SCHEMATIC PLAN PTZ STRING TO ACCESSIBLE CEILING SPACE. LIGHTING LUMINAIRES WITH EMERGENCY POWER BATTERIES OR
LUMINAIRE, SURFACE PTZ = PAN TILT ZOOM GENERATOR TRANSFER DEVICES. MECHANICAL
IC PTZ NOT SHADED = INDOOR
CIRCUIT BREAKER, RATING/NO.
CB SHADED = OUTDOOR 8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER
LUMINAIRE, RECESSED SSS SOLID STATE STARTER, REDUCED 30A OF POLES WITH THERMAL
VOLTAGE WITH ISOLATION & BYPASS 2P MAGNETIC CIRCUIT BREAKER ADA PUSH BUTTON EMERGENCY EQUIPMENT SHALL BE KEPT ENTIRELY INDEPENDENT
CONTACTORS TRIP, UNLESS OTHERWISE OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL
STRIP, SURFACE OR PENDANT AS BP
INDICATED IN LUMINAIRE SCHEDULE NOTED DB DOOR BELL RECEPTACLES REQUIREMENTS OF NEC SECTION 700.10. ELECTRICAL
TRINDERA
LUMINAIRE, EMERGENCY CONDUCTORS NOT CONNECTED. GROUND ROD IN GROUND ROD CARD READER 9. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FOR ALL 1130 W HAYDEN AVE, SUITE #101
BOX SPECIAL PURPOSE RECEPTACLE, RATING AS INDICATED HAYDEN, IDAHO 83835
CIRCUITS SHOWN ON DRAWINGS. 208.676.8001
/ = TWISTLOCK
FR PROXIMITY FOB READER
LUMINAIRE, WALL MOUNT CONDUCTORS CONNECTED. - +
BATTERY STANDARD RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES: 10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE
KF COMBINATION KEYPAD/FOB READER SIMPLEX /DUPLEX /QUADRUPLEX /FLOOR DUPLEX /FLOOR PLANS THEY SHALL SUPERCEDE THE REQUIREMENTS OF THE
LIGHTED EXIT SIGN, ARROW QUADRUPLEX SPECIFICATIONS.
INDICATES DIRECTION PULL OUT SWITCH/PLUG-RECEPTACLE T TRANSFORMER R REQUEST TO EXIT
CONNECTION GFCI RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES: 11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE
EMERGENCY WALL PACK SIMPLEX /DUPLEX /QUADRUPLEX
NORMALLY OPEN CONTACT (WHEN W WINDOW CONTACT NOTED.
CURRENT TRANSFORMER,
DE-ENERGIZED) 3 X C = CEILING MOUNTED
LUMINAIRE, POLE MOUNTED CT NUMBER INDICATES NUMBER OF
D DOOR CONTACT S = HALF SWITCHED 12. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR ALL BRANCH
NORMALLY CLOSED CONTACT (WHEN C.T.'S

600 W. PRAIRIE AVE. BUILDING 1002, COEUR D ALENE, IDAHO 83815


I = ISOLATED GROUND CIRCUITS.
DE-ENERGIZED)
TR = TAMPER RESISTANT
OD OVERHEAD DOOR CONTACT
10
FIRE ALARM UNIT HEATER
MOTOR, NUMBER INDICATES
HORSEPOWER
DH MAGNETIC DOOR HOLD (SECURITY)
a = LOWER CASE LETTER INDICATES SWITCH
CONTROL
2" = MEASUREMENT INDICATES HEIGHT ABOVE
HARDWIRED CONNECTION BACKSPLASH/MILLWORK
FACP FIRE ALARM CONTROL PANEL 1/4 EXHAUST OR SUPPLY FAN, ML MAGNETIC LOCK A = INDICATES MOUNT ABOVE
NUMBER INDICATES H.P.
FAAP FIRE ALARM ANNUNCIATOR EQUIPMENT TO BE REMOVED BACKSPLASH/MILLWORK. COORDINATE
M MOTION DETECTOR HEIGHT WITH TRADES.
SD SMOKE DETECTOR SHUNT TRIP PUSHBUTTON OR USB = INDICATES 20A 120V DUPLEX RECEPTACLE
ST ELECTRIC HEATER, WATTAGE
KEY-SWITCH VI VIDEO/INTERCOM W/ INTEGRAL FOB READER WITH USB CHARGER.
150W INDICATED
SD DUCT SMOKE DETECTOR CT = SWITCHED RECEP, INDICATES FULL

ITD SECURITY LOBBY 19-100


T THERMOSTAT
D SMOKE/FIRE DAMPER CONNECTION ES ELECTRIC STRIKE CONTROLLED DEDICATED 20A 125V DUPLEX
PANELBOARD, SWITCHBOARD, OR CH = SWITCHED RECEP, INDICATES HALF
G GENERATOR
F MANUAL PULL STATION SWITCHGEAR. DASHED BOX INDICATES CONTROLLED DEDICATED 20A 125V DUPLEX
CODE REQUIRED WORKING CLEARANCE
CIRCUIT DESIGNATION (X) SURFACE METAL RACEWAY WITH RECEPTACLE @ X" O.C.

ITD - COEUR D ALENE


HEAT DETECTOR
CONDUIT CONCEALED IN WALL, CEILING, 2
HORN STROBE UNDER FLOOR, IN FLOOR SLAB, OR MAGNETIC MOTOR STARTER LUMINAIRE, TYPICAL: a X-X
ROUTED UNDERGROUND FVNR = FULL VOLTAGE E X-X
C HORN STROBE CEILING MOUNT

STROBE
CONDUIT EXPOSED
FVR =
NON-REVERSING
FULL VOLTAGE "1"
1 E NL a
INDICATES TYPE PER LUMINAIRE SCHEDULE.
a/E X-X
OUTLET MOUNTING HEIGHTS
REVERSING "NL" INDICATES NIGHT LIGHT LUMINAIRE.
E E EXISTING CONDUIT ROUTED SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS OR ON THE ARCHITECTURAL DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR
2 = NEMA SIZE

GENERAL NOTES, ABBREVIATIONS, AND LEGENDS


C STROBE CEILING MOUNT UNDERGROUND X-X INDICATES PANELBOARD AND CIRCUIT PROVIDING POWER REQUIRED, THEN LOCATE OUTLETS AS NOTED BELOW. OUTLET HEIGHTS ARE MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE OUTLET UNLESS
TO SWITCHLEG INDICATED FOR LUMINAIRES CONTAINED OTHERWISE NOTED.
S SPEAKER STROBE WALL MOUNT OE OVERHEAD ELECTRICAL MAGNETIC MOTOR STARTER
IN SAME ROOM/AREA.
W/DISCONNECT
F FIRE SPRINKLER WATER FLOW SWITCH EXTRA-HARD USAGE FLEXIBLE CORD "a" INDICATES CONTROL PER SWITCH. RECEPTACLES 18 INCHES (460 mm) VERTICALLY MOUNTED
DISCONNECT SWITCH, NON "E" INDICATES POWER TO EMERGENCY LIGHTING
K KITCHEN HOOD FIRE SUPPRESSION SYSTEM LIGHT SWITCHES 42 INCHES (1200 mm) VERTICALLY MOUNTED
60A 60A FUSED (60A) INDICATES CONTAINED IN SAME ROOM/AREA.
CONDUIT FLEXIBLE. AMPERAGE RATING
KX KNOX BOX CLOCK OUTLET 80 INCHES (2030 mm)
100AF RECEPTACLE, TYPICAL: PNL-4
CONDUIT TURNED UP OR TOWARD DISCONNECT SWITCH, FUSED
D MAGNETIC DOOR HOLD (FIRE ALARM) PANELBOARDS 72 INCHES (1830 mm) TO TOP OF PANELBOARD
200AS 200AS/ 200=SWITCH RATING, 100=FUSE "PNL" INDICATES POWER SOURCE.
100AF RATING "4" INDICATES CIRCUIT NUMBER. TELECOM OUTLET, DESK HANDSET 18 INCHES (460 mm) VERTICALLY MOUNTED
P PRESSURE SWITCH CONDUIT TURNED DOWN OR AWAY
TELECOM OUTLET, WALL HANDSET 42 INCHES (1370 mm) VERTICALLY MOUNTED
PC PULL CORD STATION

F PULL STATION WITH CLEAR PLASTIC COVER


CONDUIT CAPPED
CONDUIT SEALS. CLASS . I DIV. 1 OR DIV
60A
CIRCUIT BREAKER DISCONNECT
(60A) INDICATES AMPERAGE
RATING
LUMINAIRE CON TROLS FIRE ALARM PULL STATION 42 INCHES (1200 mm)
2 EXPLOSION PROOF 60A
SWITCH FIRE ALARM AUDIBLE NOTIFICATION DEVICES TOP EDGE NOT LESS THAN 90 INCHES (2300 mm) AFF AND NOT LESS THAN 6 INCHES (150 mm) BELOW
R ADDRESSABLE RELAY X
CEILING. 6 INCHES (150 mm) BELOW CEILING SHALL TAKE PRECEDENCE WHERE CEILING HEIGHT DOES NOT
2 = DOUBLE POLE SWITCH
CONDUIT HOME RUN 3/4"C, 2#12 & 1#12 M UTILITY WATT HOUR METER 3 = THREE WAY SWITCH ALLOW BOTH DIMENSIONS
A REMOTE ANNUNCIATOR
P1-1 GND. UNLESS SHOWN OTHERWISE. 4 = FOUR WAY SWITCH
N NOTIFICATION APPLIANCE CIRCUIT PS (EXAMPLE SHOWN: TO PANEL P1, CIRCUIT P = SWITCH AND PILOT LAMP
P1
1) K = KEY OPERATED SWITCH FIRE ALARM VISUAL AND COMBINATION BOTTOM EDGE SHALL BE AT 80 INCHES (2030 mm) AFF OR 6 INCHES (150 mm) BELOW CEILING HEIGHT,
V POST INDICATOR VALVE MOTOR RATED SWITCH. WHERE AUDIBLE/VISUAL NOTIFICATION DEVICES WHICHEVER IS LOWER
CONDUIT HOME RUN - SEE CONDUIT AND T = SWITCH WITH TIMER
M "M" INDICATED, PROVIDE A MS = MASTER SWITCH TO CONTROL ALL FIXED
T FIRE SPRINKLER TAMPER SWITCH WIRE SCHEDULE. MANUAL MOTOR STARTER LUMINAIRES IN GUEST UNIT FIRE ALARM CONTROL PANEL 72 INCHES (1830 mm) TO TOP OF PANELBOARD
W/OVERLOAD
HANDHOLE WITH DESIGNATION
B WATER FLOW BELL HH1 PC PHOTOCELL

M/C M ADDRESSABLE MODULE M = MONITOR JUNCTION BOX PE PHOTO ELECTRIC SENSOR


C = CONTROL EMERGENCY PUSH BUTTON
SWTICH # NEW LUMINAIRE CONTROL. SEE LIGHTING CONTROL LEGEND
FFH FIREFIGHTER 2-WAY VOICE COMMUNICATION MANUAL OR AUTOMATIC THE SYMBOLS, ABBREVIATIONS AND NOTES ON THIS SHEET PROJECT NO. 1859
LOCATED ON LIGHTING SHEETS.
SYSTEM HANDSET STATION TRANSFER SWITCH.
DESIGNED BY MWM
OS CEILING MOUNTED OCCUPANCY SENSOR(S). PROVIDE SHOP ARE INTENDED TO BE GENERAL AND COMPREHENSIVE
FFJ FIREFIGHTER 2-WAY VOICE DRAWINGS OF OCCUPANCY SENSOR SYSTEM AS PER DRAWN BY MWM
COMMUNICATION SYSTEM JACK 1130 W HAYDEN AVE, SUITE #101
PROJECT SPECIFICATION AS PART OF THE SUBMITTAL AND DO NOT ALL APPLY TO THIS PROJECT HAYDEN, IDAHO 83835 ISSUE DATE 9-24-2019
PROCESS PRIOR TO COMMENCEMENT OF LABOR. SEE (208) 676-8001 (208) 676-0100 PHASE 100% BID SET
DOORBELL LIGHT
LIGHTING CONTROL LEGEND LOCATED ON LIGHTING
SHEETS. CHECKED BY RL
REVISION
SHEET NO.
COPYRIGHT 2019
All rights reserved. Reproduction or translation of any part
of this work without written permission of
ARCHITECTS WEST INC.
is unlawful and subject to criminal prosecution.

ELECTRICAL SPECIFICATIONS 4) BUILDING STRUCTURE WIRING: SHALL ADHERE TO THE MOST CURRENTLY AVAILABLE BUILDING INDUSTRY FOR THE SYSTEM.
CONSULTING SERVICE INTERNATIONAL (BICSI) TELECOMMUNICATIONS DISTRIBUTION METHODS MANUAL,
2) ALL BRANCH CIRCUITS SHALL BE TAGGED IN THE PANELBOARDS FOR THE PURPOSE OF DISTINGUISHING THE
1. DRAWINGS AND SPECIFICATIONS ANSI/TIA/EIA TELECOMMUNICATIONS BUILDING WIRING STANDARDS ISBN: 0-9112702-73-7, NATIONAL
VARIOUS CIRCUITS. TAG ALL FEEDERS AND MAINS IN ALL PULLBOXES, IN THE PANELS, AND IN THE I. FINAL INSPECTION - AT THE FINAL INSPECTION, A MINIMUM NICET LEVEL II TECHNICIAN SHALL DEMONSTRATE THAT
ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) WC 25, AND NATIONAL ELECTRICAL CODE. TESTING OF
SWITCHBOARD. ADDITIONALLY, ELECTRICAL DEVICE COVER PLATES SHALL BE LABELED PER CIRCUIT THE SYSTEM FUNCTIONS PROPERLY IN EVERY RESPECT.
A. THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL, AND EQUIPMENT DRAWINGS AND SPECIFICATIONS ARE HEREBY COPPER UTP CABLES SHALL CONFORM TO THE REQUIREMENTS OF TIA 568-B.1. PROVIDE A WRITTEN TEST
IDENTIFICATION AT THE TOP MIDDLE OF THE PLATE. WIRE TAGS SHALL BE BRADY SELF-STICKING NUMBERED
INCORPORATED INTO AND BECOME A PART OF THIS DIVISION. CONTRACTOR SHALL EXAMINE ALL SUCH DRAWINGS REPORT TO OWNER. IDENTIFICATION OF CABLING, PATHWAYS AND HARDWARE SHALL CONFORM TO TIA 606-A. 9. EXECUTION
WIRED MARKERS OR APPROVED EQUAL.
AND SPECIFICATIONS AND BECOME THOROUGHLY FAMILIAR WITH PROVISIONS CONTAINED HEREIN AND THE
SUBMISSION OF HIS BID SHALL BE CONSTRUED AS INDICATING SUCH KNOWLEDGE. 5) ACCESS CONTROL CABLE(S): PROVIDE 1" CONDUIT WITH JUNCTION BOX. PROVIDE AND INSTALL CABLES
(CONDUCTORS) PER EXISTING EQUIPMENT MANUFACTURER REQUIREMENTS, CABLE SUPPORTS PER DEVICES AS 6. SUBMITTALS A. TESTS: CHECK MOTORS FOR PROPER ROTATION. MEASURE AND BALANCE LOADS ON EACH PANELBOARD PHASE.
B. ELECTRICAL DRAWINGS ARE IN PART DIAGRAMMATIC, INTENDING TO CONVEY SCOPE OF WORK, INDICATING DICTATED ON SYMBOLS SHEET, AND TERMINATIONS. LABEL ALL CABLES BACK AT THE MAIN HEAD END
GENERAL ARRANGEMENT OF PANELBOARDS, SWITCHES, EQUIPMENT, CONDUIT, OUTLETS, AND OTHER DEVICES. EQUIPMENT AND AGAIN ABOVE THE CEILING. EXISTING PANELS PROVIDED BY OWNER. CONTRACTOR TO
DUE TO THE DIAGRAMMATIC NATURE OF THE DRAWINGS, MANY OF THE NECESSARY INDIVIDUAL COMPONENT A. BEFORE ANY MATERIAL IS FABRICATED OR SHIPPED, FURNISH TO THE ENGINEER FULL DETAILS, SHOP B. INSTALLATION OF CONDUIT: CONDUIT, EXCEPT AS OTHERWISE SPECIFICALLY NOTED, SHALL BE CONCEALED.
CONFIRM AVAILABLE SPACE PRIOR TO COMMENCING WORK. COORDINATE LABELING WITH OWNER.
PARTS ARE NOT INDICATED BUT SHALL BE INCLUDED BY THE CONTRACTOR FOR A COMPLETE AND OPERABLE DRAWINGS, DIMENSIONS, CATALOG CUTS, SCHEMATIC (ELEMENTARY) DIAGRAMS, WIRING DIAGRAMS, AND OTHER EXPOSED CONDUIT SHALL BE RUN PARALLEL WITH SUPPORTING WALL, BEAM, OR CEILING AND WITH EACH OTHER;
COORDINATE EXISTING PORTS/TERMNALS TO USE WITH OWNER PRIOR TO COMMENCING WORK.
ELECTRICAL SYSTEM. FOLLOW DRAWINGS IN LAYING OUT WORK, AND VERIFY PLACES FOR INSTALLATION OF DESCRIPTIVE MATTER AS REQUIRED TO FULLY DESCRIBE THE PRODUCTS SPECIFIED UNDER THIS SECTION. WITH RIGHT ANGLE RUNS CONSISTING OF CAST METAL FITTINGS (LB CONDULETS SHALL NOT BE USED FOR
MATERIALS AND EQUIPMENT. WHENEVER A QUESTION EXISTS AS TO EXACT INTENDED LOCATION OF OUTLETS OR CONDUITS LARGER THAN 1-1/4 INCHES I.D.) OR SYMMETRICAL BENDS, AND WITH SUPPORTS SPACED AT NOT MORE
6) ALL WIRING ABOVE CEILINGS TO BE PLENUM RATED WHERE INTERSTITIAL SPACE IS USED AS A PLENUM AND
EQUIPMENT, OBTAIN INSTRUCTIONS FROM THE ENGINEER BEFORE PROCEEDING WITH WORK. THAN 5 FEET APART. ALL RUNS OF CONDUIT SHALL BE INSTALLED IN SUCH A MANNER AS TO AVOID TRAPPED
WHERE REQUIRED BY APPLICABLE CODE(S).
B. SUBMITTALS SHALL HAVE A TYPEWRITTEN INDEX, TABBED DIVIDER PAGES, PROJECT LABEL/DESCRIPTION ON CONDENSATION. NO JUNCTIONS OF SPLICES IN WIRE SHALL BE MADE IN CONDULETS. ALL CONDUIT EXPOSED IN
C. WHEREVER THE REQUIREMENTS OF THE SPECIFICATIONS OR DRAWINGS ARE IN CONFLICT, THE MORE BINDER SPINE AND ON FRONT COVER PAGE (LISTING PROJECT NAME, DATE, CONTRACTOR NAME AND CONTACT FINISHED SPACES SHALL BE PAINTED TO MATCH ADJACENT SURFACES.
D. ALL WIRING DEVICES ARE TO BE COMMERCIAL SPECIFICATION GRADE BY HUBBELL, LEVITON, OR APPROVED
STRINGENT REQUIREMENT SHALL PREVAIL. INFORMATION, GENERAL CONTRACTOR NAME AND CONTACT INFORMATION.) IF ELECTRONIC SUBMITTALS ARE
EQUAL.
BEING SUBMITTED, CONTRACTOR SHALL ASSEMBLE THE INFORMATION IN ONE PDF FILE MEETING ALL APPROPRIATE
REQUIREMENTS OF THE PAPER VERSION. C. ALL CONTROLS APPARATUS, OUTLET, OUTLET BOXES, JUNCTION AND PULL BOXES AND SIMILAR OUTLET
2. SCOPE OF WORK 1) DEVICE MOUNTING HEIGHTS UNLESS NOTED OTHERWISE ON THE DRAWINGS SHALL BE AS FOLLOWS (TO EQUIPMENT SHALL BE INSTALLED AND MAINTAINED IN ACCESSIBLE POSITIONS AND LOCATIONS.
CENTER OF DEVICE):
A. SUPPLY ALL LABOR AND MATERIAL TO COMPLETE ALL ELECTRICAL WORK SHOWN ON THE DRAWINGS, SPECIFIED
C. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND PRODUCT DATA (SUBMITTAL INFORMATION) COVERING THE
HEREIN OR REQUIRED TO COMPLETE THE CONSTRUCTION OF THE BUILDING AS SHOWN. 120V RECEPTACLE: 18" AFF D. ALL CONDUITS SHALL BE SUPPORTED TO THE BUILDING CONSTRUCTION WITH APPROVED PIPE STRAPS, SPACED
FOLLOWING TO THE ENGINEER FOR REVIEW AND APPROVAL:
LIGHT SWITCH: 42" AFF NOT TO EXCEED 5-FOOT INTERVALS. INSTALL CLAMPS APPROXIMATELY 18 INCHES FROM BOXES. CONDUIT LARGER
B. THE LISTING OF ARTICLE OR MATERIAL, OPERATION OR METHOD, REQUIRES THAT THE CONTRACTOR SHALL ACCESS CONTROL: 42" AFF THAN 1-1/2 INCH SHALL BE SUPPORTED WITH APPROVED PIPE STRAPS.
PROVIDE AND INSTALL, UNLESS NOTED TO BE SUPPLIED BY OTHERS, EACH ITEM LISTED OF QUALITY OR SUBJECT TELECOMMUNICATIONS OUTLET: 18" AFF ACCESS CONTROL DEVICES
TO QUALIFICATION NOTED. EACH OPERATION SHALL BE PERFORMED ACCORDING TO STANDARD PRACTICE,
FUSES E. A NYLON PULL ROPE SHALL BE INSTALLED IN ALL WIRING RACEWAYS WHICH DO NOT HAVE CONDUCTORS PULLED
MANUFACTURER'S INSTRUCTIONS AND CONDITIONS STATED, PROVIDING ALL NECESSARY LABOR, EQUIPMENT AND 2) DEVICE PLATES: FURNISH AND INSTALL WALL PLATES FOR ALL DEVICES. PLATES ARE TO BE NYLON WITH
INCIDENTALS. COLOR SELECTED BY THE ARCHITECT AND MATCHING DEVICE. USE GANG PLATES AS REQUIRED. WIRING DEVICES BY THIS CONTRACT. INNER DUCT WILL BE PROVIDED IN MAIN COMMUNICATION CONDUITS.
LUMINAIRES
C. THE PRINCIPAL ITEMS OF WORK INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING: 3) ALL ADJACENT SWITCHES, RECEPTACLES, ETC. MOUNTED IN A GIVEN LOCATION ARE TO BE ALIGNED LIGHTING CONTROLS F. PULLBOXES SHALL BE INSTALLED IN ALL CONDUIT RUNS WHEREVER REQUIRED TO KEEP THE MAXIMUM NUMBER
HORIZONTALLY AND VERTICALLY. DO NOT LOCATE DEVICES BACK-TO-BACK IN COMMON WALLS. OF BENDS TO 360 DEGREES OR LESS IN ORDER TO FACILITATE THE PULLING OR WIRES OR CABLES. ALL JUNCTION
1) COMPLETE BRANCH CIRCUIT WIRING SYSTEM GROUNDING
AND PULLBOXES SHALL BE GALVANIZED AND CONSTRUCTED WITH SUITABLE BARRIERS SEPARATING THE
E. LUMINAIRES: DIFFERENT SYSTEMS. BOXES SHALL BE PROVIDED WITH REMOVABLE COVERS, SECURED WITH MACHINE SCREWS.
2) COMPLETE RACEWAY SYSTEM
7. OTHER ALL JUNCTION AND PULLBOXES OF UNUSUAL SIZE OR SHAPE, AND AS DIRECTED, SHALL BE PROVIDED WITH
1) THE CONTRACTOR SHALL FURNISH AND INSTALL ALL LUMINAIRES AS SHOWN. THIS WORK INCLUDES THE INTERIOR ANGLE IRON BRACES AND PROPER SUPPORT.
3) COMPLETE INTERIOR LIGHTING SYSTEM FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT FOR THE COMPLETE INSTALLATION OF THE A. UTILITY COORDINATION - THE CONTRACTOR SHALL COORDINATE POWER, CABLE TV AND TELEPHONE SERVICES
LUMINAIRES, INCLUDING THE FURNISHING AND INSTALLATION OF ALL MOUNTING ACCESSORIES (I.E. STEMS WITH THE LOCAL SERVICE PLANNER. SERVICES SHALL COMPLY WITH UTILITY STANDARDS.
4) COMPLETE SPECIAL SYSTEMS PLASTER FRAMES, ETC.) WHETHER THESE ITEMS ARE SPECIFICALLY MENTIONED IN THE SPECIFICATIONS OR G. PROVIDE A JUNCTION BOX AT NEAREST ACCESSIBLE LOCATION FOR ALL RECESSED LUMINAIRES.
NOT.
5) TESTING OF ALL ELECTRICAL EQUIPMENT B. TEMPORARY LIGHTING AND POWER - THE CONTRACTOR SHALL PROVIDE TEMPORARY LIGHTING (A MINIMUM OF
10 FOOTCANDLES IN CONSTRUCTION AREAS) AND 120V POWER AT UP TO TEN LOCATIONS. H. LOCATIONS OF LUMINAIRES, ELECTRICAL OUTLETS, EQUIPMENT, AND OTHER ELECTRICAL SYSTEM COMPONENTS
2) LUMINAIRES SHALL BE COMPLETE INCLUDING ALL LAMPS, TRANSFORMERS, BALLASTS, DRIVERS, SUPPORTS,
D. RESPONSIBILITY: THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE WORK OF ALL HIS HANGERS, BRACKETS, CANOPIES, SOCKETS, REFLECTOR DIFFUSING MATERIAL, LOUVERS, END CAPS, COUPLING SHOWN ON DRAWINGS ARE APPROXIMATE UNLESS DIMENSIONED. CONTRACTOR IS TO CHECK FOR AND RESOLVE
SUB-CONTRACTORS AND THE MATERIALS OF ALL HIS SUPPLIERS. INCLUDE ALL MATERIALS, LABOR, AND PLATES, ETC., ALL WIRED AND ASSEMBLED, AND BEARING AN UNDERWRITERS' LABORATORY LABEL. CONFLICTS WITH OPENINGS, STRUCTURAL MEMBERS, AND EQUIPMENT HAVING FIXED LOCATIONS.
8. PERFORMANCE DIGITAL, ADDRESSABLE FIRE ALARM AND DETECTION SYSTEM
EQUIPMENT REQUIRED FOR A COMPLETE AND WORKING INSTALLATION. DO NOT SUPPLY MATERIALS THAT WILL NOT LUMINAIRES SHALL BE RIGIDLY SUPPORTED AS RECOMMENDED BY THE LUMINAIRE MANUFACTURER AND TO
WORK IN THE PARTICULAR SITUATION OF THIS PROJECT. MEET LOCAL SEISMIC CODES. I. DO NOT CUT OR NOTCH ANY STRUCTURAL MEMBER OR BUILDING SURFACE WITHOUT SPECIFIC APPROVAL OF THE
A.DESCRIPTION STRUCTURAL ENGINEER. CAREFULLY CARRY OUT ANY CUTTING, CHANNELING, CHASING, OR DRILLING OF FLOORS,
E. DEMOLISH ELECTRICAL DEVICES AND ASSOCIATED WIRING IN WALLS BEING REMOVED. MAINTAIN COMPLETE 3) BALLASTS SHALL BE TYPE 1 (LOCATION USE RATING), UL CLASS P (CASE OPERATING TEMPERATURE), SOUND
FUNCTIONALITY FOR ALL EQUIPMENT AND DEVICES THAT ARE "TO REMAIN". WALLS, PARTITIONS, CEILINGS, PAVING, OR OTHER SURFACES REQUIRED FOR THE INSTALLATION, SUPPORT, OR
RATING CLASS A AND SHALL BE ELECTRONIC PROGRAM START TYPE FOR FLUORESCENT APPLICATIONS. 1.) THIS PERFORMANCE SPECIFICATION DESCRIBES THE CHARACTERISTICS, MATERIAL QUALITY, AND ANCHORAGE OF CONDUIT, RACEWAYS, OR OTHER ELECTRICAL MATERIALS AND EQUIPMENT. FOLLOWING SUCH
INSTALLATION REQUIREMENTS FOR A COMPLETE FIRE ALARM AND DETECTION SYSTEM. EXTENDED FROM WORK, RESTORE SURFACES NEATLY TO NEW CONDITION USING SKILLED CRAFTSMEN OF THE TRADE INVOLVED, AT
F. OMISSION OF EXPRESS REFERENCE OF ANY PARTS NECESSARY FOR, OR REASONABLE INCIDENTAL TO, A 4) PROVIDE ALL SUPPORT AND RETENTION EQUIPMENT AS REQUIRED IN LIGHTING INSTALLATION DETAILS. THE EXISTING BUILDING FACP(GAMEWELL/FCI) UTILIZING SPARE OR SPACE DEDICATED ZONES FOR
COMPLETE INSTALLATION SHALL NOT BE CONSTRUED AS RELEASING CONTRACTOR FROM FURNISHING SUCH PARTS. NO ADDITIONAL COST TO THE OWNER. ANY PENETRATIONS TO FIRE RATED MATERIALS SHALL BE RESTORED TO STRUCTURAL
INITIATION AND ANNUNCIATION PER THE AHJ REQUIREMENTS AND, THE RESPONSIBILITIES OF THE FIRE EQUAL RATING AS REQUIRED BY THE STATE FIRE MARSHALL.
THE ELECTRICAL SYSTEM AS SUPPLIED SHALL BE COMPLETE AND FUNCTIONING, WITH ALL ELECTRICAL ITEMS 5) LAMPS SHALL BE AS SPECIFIED ON DRAWINGS. ALARM DESIGNER WHO WILL DETERMINE ALL THE SYSTEM COMPONENTS AND SERVICES THAT ARE TO BE
FURNISHED IN OPERABLE CONDITION.
PROVIDED AS PART OF THE SYSTEM IN ORDER TO MEET THE REQUIREMENTS OF THE AHJ (AUTHORITY
6) LAMP BURN-IN: OPERATE LAMPS AT FULL OUTPUT FOR PRESCRIBED PERIOD PER MANUFACTURER'S HAVING JURISDICTION). J. GROUNDING: CONNECT ALL ELECTRICAL EQUIPMENT TO GROUND SYSTEM AS DIRECTED. ALL PANELS AND
G. DEMOLISHED EQUIPMENT AND DEVICES SHALL BE SALVAGED FOR FUTURE USE AT DISCRETION OF OWNER. RECOMMENDATIONS PRIOR TO USE WITH ANY DIMMING CONTROLS, REPLACE LAMPS THAT FAIL PREMATURELY CONDUITS ENTERING PANELS SHALL BE ADEQUATELY CONNECTED TO BUILDING GROUNDING SYSTEM. ALL
OTHERWISE, DISPOSE OF PROPERLY. DUE TO IMPROPER BURN-IN. ELECTRICAL APPARATUS, EITHER STATIONARY OR PORTABLE, MUST BE ADEQUATELY GROUNDED BY THIS MECHANICAL
2.) THE GENERAL REQUIREMENTS ARE AS FOLLOWING: CONTRACTOR EITHER BY DIRECT CONNECT FROM FRAME OF THE APPARATUS OR AN APPROVED GROUND WIRE
3. CODES, PERMITS, AND INSPECTIONS 7) AFTER COMPLETION OF INSTALLATION OF LIGHTING CONTROL OR RELAY PANELS AND PROGRAMMING, CONNECTED SECURELY TO THE CONDUIT, OR BY AN APPROVED GROUNDED FLEXIBLE CORD THROUGH AN
a. PROVIDE COMPATIBLE ADDRESSABLE DEVICES.
DEMONSTRATE OPERATION OF SYSTEM TO OWNER'S DESIGNATED REPRESENTATIVE. PROVIDE NO LESS THAN APPROVED CAP AND RECEPTACLE. PULLBOXES SHALL BE BONDED TO CONDUIT. PROVIDE A GROUND WIRE IN ALL
A. INSTALL ALL WORK IN FULL ACCORDANCE WITH THE LATEST ADOPTED VERSION OF CODES, RULES AND TWO HOURS OF TRAINING FOR OWNER. TRAINING TO BE CONDUCTED BY MANUFACTURER CERTIFIED b. COORDINATE WITH THE AHJ TO DETERMINE SYSTEM AND SUBMITTAL REQUIREMENTS PRIOR TO BID. CONDUITS. PROVIDE BONDING BUSHINGS AS REQUIRED BY THE NEC.
REGULATIONS OF MUNICIPAL, CITY, COUNTY, STATE AND PUBLIC UTILITIES AND ALL OTHER AUTHORITIES HAVING REPRESENTATIVE.
JURISDICTION OVER THE PREMISES. THIS SHALL INCLUDE ALL REQUIREMENTS OF THE NATIONAL ELECTRICAL c. PROVIDE DUCT SMOKE DETECTORS FOR HVAC EQUIPMENT WITH CAPACITIES OVER 2000CFM.
CODE, AS INTERPRETED BY THE LOCAL INSPECTION DIVISION. ALL THESE CODES, RULES, AND REGULATIONS ARE F. LIGHTING CONTROL: d. INCLUDE ALL WORK TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM K. CLEANING: RESPECTIVE CONTRACTORS OR SUB-CONTRACTORS FOR VARIOUS PHASES OF ELECTRICAL WORK ELECTRICAL
HEREBY INCORPORATED INTO THIS SPECIFICATION. ALL CHANGES FROM THESE DRAWINGS NECESSARY TO MAKE
THE WORK CONFORM TO THE BUILDING AS CONSTRUCTED AND TO FIT THE WORK OF OTHER TRADES OR TO e. THE FIRE ALARM SHALL COMPLY WITH REQUIREMENTS OF NFPA STANDARD NO. 72 FOR LOCAL
SHALL CLEAR AWAY ALL DEBRIS AND REFUSE PRIOR TO THE END OF WORK EACH DAY. UPON COMPLETION OF TRINDERA
1) LIGHTING CONTROL SHALL BE INSTALLED AT LOCATION SHOWN ON DRAWINGS. THIS WORK INCLUDES THE WORK, SURPLUS MATERIALS, ETC. RESULTING FROM THEIR WORK SHALL ALSO BE REMOVED FROM THE JOB SITE AT 1130 W HAYDEN AVE, SUITE #101
CONFORM TO THE RULES AND REGULATIONS OF THE STATE, CITY, OR MUNICIPAL BODIES HAVING JURISDICTION, PROTECTED PREMISES SIGNALING SYSTEMS.
FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT FOR THE COMPLETE INSTALLATION OF THE SYSTEM, THE CONTRACTOR'S EXPENSE, LEAVING JOB AND EQUIPMENT FURNISHED UNDER ANY OR ALL CONTRACTS IN A HAYDEN, IDAHO 83835
ARE TO BE MADE BY ELECTRICAL CONTRACTOR, AT HIS OWN EXPENSE. INCLUDING THE FURNISHING AND INSTALLATION OF ALL MOUNTING ACCESSORIES. CLEAN AND FIRST CLASS CONDITION. 208.676.8001
3.) SUBMITTALS
B. LISTED OR LABELED EQUIPMENT SHALL BE USED OR INSTALLED IN ACCORDANCE WITH ANY INSTRUCTIONS 2) OCCUPANCY SENSORS SHALL BE DUAL TECHNOLOGY. LOW VOLTAGE UNITS SHALL BE SUPPLIED WITH A a. THE CONTRACTOR SHALL REQUEST BACKGROUND ACAD FILES FOR USE IN LAYING OUT AND
INCLUDED IN THE LISTING OR LABELING. IDENTIFYING THE FIRE ALARM COMPONENTS FROM THE ARCHITECT/ENGINEER. L. EXTERIOR AND INTERIOR REFLECTING AND TRANSMITTING SURFACES OF LUMINAIRES SHALL BE CLEANED SO AS
POWER PACK. POWER PACK SHALL HAVE A DRY CONTACT OUTPUT RATED FOR USE BY MECHANICAL EQUIPMENT.
TO BE REASONABLY FREE FROM CONSTRUCTION DEBRIS AND DUST. ALL LUMINAIRES USED AS CONSTRUCTION
WALL OCCUPANCY SWITCHES THAT ALSO PROVIDE MANUAL CONTROL SHALL HAVE THE BUTTON COUNT TO b. SUBMIT COPIES OF ALL SUBMITTALS TO THE ENGINEER FOR REVIEW AND APPROVAL.
C. THE CONTRACTOR SHALL SECURE ALL PERMITS AND CERTIFICATES OF INSPECTION INCIDENTAL TO HIS WORK, LIGHTING WILL HAVE ALL LAMPS REPLACED WITH NEW IMMEDIATELY PRIOR TO PROJECT CLOSEOUT AT
ACCOMMODATE SWITCHING SHOWN ON DRAWINGS.
REQUIRED BY THE FOREGOING AUTHORITIES. ALL SUCH CERTIFICATES SHALL BE DELIVERED TO THE OWNER IN c. SUBMIT PROOF THAT SUBSTITUTE EQUIPMENT EQUALS OR EXCEEDS THE FEATURES, FUNCTIONS, CONTRACTOR'S EXPENSE.
DUPLICATE, BEFORE FINAL PAYMENT ON CONTRACT WILL BE ALLOWED. THE CONTRACTOR SHALL PAY ALL FEES, 3) DIGITAL SWITCHES SHALL BE PROVIDED FOR USER OVER-RIDE OF SENSOR CONTROL. SWITCHES SHALL BE PERFORMANCE, AND QUALITY OF THE SPECIFIED EQUIPMENT FOR ENGINEER'S APPROVAL.
CHARGES AND OTHER EXPENSES IN CONNECTION THEREWITH.
FULLY ADDRESSABLE WITH STAR TOPOLOGY. SWITCHES THAT PROVIDE THE MANUAL CONTROL SHALL HAVE THE d. SUBMIT SHOP DRAWINGS THAT INCLUDE EQUIPMENT LAYOUT, DEVICE ARRANGEMENT, COMPLETE M. FINISH PAINTING OF ALL EXPOSED ELECTRICAL MATERIAL AND EQUIPMENT IS THE SOLE RESPONSIBILITY OF
BUTTON COUNT TO ACCOMMODATE SWITCHING SHOWN ON DRAWINGS. WIRING POINT-TO-POINT DIAGRAMS. THIS CONTRACTOR.
4. INTERFERENCES
e. SHOP DRAWINGS SHALL INCLUDE COMPLETE VOLTAGE DROP CALCULATIONS AND BATTERY
A. BEFORE INSTALLING ANY OF THIS WORK, THE CONTRACTOR SHALL SEE THAT IT DOES NOT INTERFERE WITH 4) PHOTOCELLS PROVIDED FOR DAYLIGHT HARVESTING SHALL BE CLOSED LOOP AND COMMISSIONED FOR 40 CALCULATIONS.

600 W. PRAIRIE AVE. BUILDING 1002, COEUR D ALENE, IDAHO 83815


CLEARANCES FOR THE ERECTION OF FINISH BEAMS, COLUMNS, PILASTERS, WALLS, DUCTS, AND OTHER FOOTCANDLES UNLESS OTHERWISE NOTED.
f. PROVIDE CATALOG CUT SHEETS THAT CLEARLY INDICATE THE MODEL NO. OF THE DEVICE TO BE 10. PROJECT CLOSEOUT: AT THE COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL:
STRUCTURAL, MECHANICAL, OR ARCHITECTURAL MEMBERS AS SHOWN ON THE DRAWINGS. IF ANY WORK IS SO
5) LIGHTING CONTROL SYSTEM TESTED TO ENSURE THAT CONTROL DEVICES, COMPONENTS, EQUIPMENT AND PROVIDED.
INSTALLED AND LATER THE ARCHITECTURAL DESIGN CANNOT BE FOLLOWED, THE ELECTRICAL CONTRACTOR SHALL,
AT HIS OWN EXPENSE, MAKE SUCH CHANGES IN HIS WORK AS THE ARCHITECT OR ENGINEER MAY DIRECT TO SYSTEMS ARE CALIBRATED, ADJUSTED AND OPERATE IN ACCORDANCE WITH APPROVED PLANS AND g. THE DESIGNER WHO IS TAKING RESPONSIBILITY FOR THE DESIGN AND SHALL SIGN SHOP DRAWINGS.
SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN A. SUBMIT OPERATION AND MAINTENANCE MANUALS, WITH TAB DIVIDERS SEPARATING SPECIFIC SYSTEMS OR
PERMIT THE COMPLETION OF THE OTHER WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. DRAWINGS SHALL BE “STAMPED” AS FOLLOWS: ITEMS OF EQUIPMENT. GUARANTEE AS DESCRIBED BELOW SHALL BE INCLUDED.
ACCORDANCE WITH PLANS AND SPECIFICATIONS. A COMPLETE REPORT OF TEST PROCEDURES AND RESULTS
B. IT SHALL BE THE DUTY OF THE CONTRACTOR TO REPORT ANY INTERFERENCES BETWEEN HIS WORK AND THAT OF SHALL BE PREPARED AND PROVIDED TO THE OWNER.
ANY OTHER CONTRACTOR TO THE ENGINEER AS SOON AS THEY ARE DISCOVERED. THE ENGINEER WILL DETERMINE
“ALL INFORMATION CONTAINED ON THIS DRAWING HAS BEEN DEVELOPED BY ME OR UNDER MY DIRECT
B. SUBMIT A LIST OF RECOMMENDED SPARE PARTS.
WHICH EQUIPMENT SHALL BE RELOCATED REGARDLESS OF WHICH WAS FIRST INSTALLED. 6) ALL EMERGENCY LIGHTING AND POWER EQUIPMENT SHALL BE UL 924 CERTIFIED. LIGHTING CONTROL PANEL SUPERVISION.”
SHALL PROVIDE AUTOMATIC FUNCTIONALITY TO OVERRIDE ALL EMERGENCY FIXTURES TO FULL BRIGHTNESS
BY: ______________________________________
5. MATERIALS AND WORKMANSHIP WHEN SUPPLIED BY EMERGENCY POWER REGARDLESS OF LOCAL SWITCH POSITION. C. SUBMIT MARKED UP 'AS-BUILT' DRAWINGS WITH FINAL INSTALLED ARRANGMENTS, INCLUDED EQUIPMENT
SIGNATURE: ______________________________ MODEL NUMBERS AND PERFORMANCE DATA. 'AS-BUILT' DRAWINGS SHALL BE PROVIDED TO THE OWNER ON A NEW
A. GENERAL 7) PROVIDE LIGHTING CONTROL COMMISSIONING REQUIRED BY AHJ BY MANUFACTURERS CERTIFIED DATE: ____________________________________ DRAWING SET, WITH FIELD CHANGES TRANSCRIBED FROM THE WORKING SET IN A NEAT AND PROFESSIONAL
REPRESENTATIVE. MANNER.
NICET CERTIFICATION NO: __________________”

ITD SECURITY LOBBY 19-100


1) WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY CRAFTSMEN SKILLED IN THE PARTICULAR
TRADE. WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS, G. PANELBOARDS: THE CONTRACTOR SHALL PROVIDE NEW PANELBOARD(S) OF SIZE (BOTH AMPERAGE RATING AND h. SUBMIT THE FOLLOWING AT COMPLETION OF PROJECT:
BREAKER SPACES) SHOWN IN THE PANELBOARD SCHEDULE(S). NEW PANEL(S) SHALL BE SQUARE D TYPES I-LINE, D. GUARANTEE: FULLY GUARANTEE MATERIALS AND WORK UNDER THIS SECTION, FOR PERIOD OF ONE YEAR FROM
MANUFACTURER'S RECOMMENDATIONS, AND THE BEST PRACTICE OF THE TRADE. COMPLETED WORK SHALL · RECORD DRAWINGS OF THE PROJECT THAT INCORPORATE ALL FIELD CHANGES.
NF, OR NQOD OR APPROVED EQUALS WITH LOCKING FRONT, CARD HOLDERS AND BAKED ENAMEL FINISH. IDENTIFY THE DATE OF FINAL ACCEPTANCE BY THE OWNER, AGAINST IMPERFECT WORKMANSHIP OR FAILURE OR
PRESENT A NEAT AND FINISHED APPEARANCE.
ALL CIRCUITS ON CARD (TYPEWRITTEN) AND PLACE IN CARDHOLDER. LOCATE PANEL(S) AS SHOWN ON PLANS. · MANUFACTURER'S NAME(S), INCLUDING TECHNICAL DATA SHEETS. MALFUNCTION OF MATERIALS AND/OR EQUIPMENT DUE TO FAULTY OR IMPERFECT WORKMANSHIP. PROVIDE THE
WHERE USED AS SERVICE ENTRANCE EQUIPMENT, PROVIDE PANELS HAVING UL APPROVAL FOR THAT USE. PROVIDE GUARANTEE IN WRITING TO THE OWNER AT THE TIME OF ISSUING THE FINAL CERTIFICATE. WORK FOUND TO BE
2) UNLESS EXPRESSLY SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY, ALL MATERIALS SHALL · WIRING DIAGRAMS SHALL INDICATE INTERNAL WIRING FOR EACH DEVICE AND THE INTERCONNECTIONS

ITD - COEUR D ALENE


PANELS WITH AVAILABLE SHORT CIRCUIT CURRENT SHOWN. DEFECTIVE WITHIN THIS PERIOD SHALL BE REPLACED WITHOUT COST TO THE OWNER.
BE NEW AND FREE FROM DEFECTS AND SHALL BE THE BEST OF THEIR SEVERAL KINDS. BETWEEN THE ITEMS OF EQUIPMENT.
H. MOTOR CIRCUITS: FURNISH AND INSTALL ALL WIRING AND CONNECTIONS TO MOTORS SHOWN ON THE PLANS. · PROVIDE A CLEAR AND CONCISE SEQUENCE OF OPERATION THAT GIVES, IN DETAIL, THE INFORMATION
3) SEAL ALL ELECTRICAL WALL PENETRATIONS IN FIRE/SMOKE RATED PARTITIONS USING MATERIALS AND END OF ELECTRICAL SPECIFICATIONS
FURNISH AND INSTALL DISCONNECT OR COMBINATION MOTOR STARTER/DISCONNECT SWITCHES FOR ALL MOTORS. REQUIRED TO PROPERLY OPERATE THE EQUIPMENT AND SYSTEM.
METHODS PROPERLY RATED FOR EACH APPLICATION. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF
RATED WALL ASSEMBLIES. SUBMIT SEALING MATERIALS FOR REVIEW AND APPROVAL. PROVIDE HAND-OFF-AUTO CONTROL AND GREEN RUN LIGHT FOR ALL COMBINATION STARTERS. · PROVIDE CUT SHEETS THAT CLEARLY INDICATE THE MODEL NO. OF THE DEVICES AND EQUIPMENT
PROVIDED.
B. CONDUIT I. EQUIPMENT PROVIDED BY OTHERS: THE CONTRACTOR SHALL ROUGH-IN AND CONNECT TO ALL EQUIPMENT INFORMATION ON THIS SHEET IS INTENDED TO BE
PROVIDED BY OTHERS. DISCONNECT SWITCHES AND STARTERS ARE BY THE CONTRACTOR UNLESS OTHERWISE B. THE SYSTEM SHALL FULLY COMPLY WITH THE LATEST ISSUE OF THESE STANDARDS, IF APPLICABLE.
1) GALVANIZED RIGID STEEL (RMC) CONDUIT SHALL BE USED IN ALL LOCATIONS WHERE EXPOSED TO PHYSICAL NOTED. COORDINATE WITH OTHER TRADES.
1.) NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) - USA: GENERAL AND COMPREHENSIVE AND DOES NOT ALL APPLY
DAMAGE, OR WHERE EXPOSED WITHIN 8' OF FINISHED FLOOR OR GRADE, AND FOR PANELBOARD FEEDERS.
MINIMUM CONDUIT SIZE FOR INDOOR APPLICATIONS SHALL BE 1/2", FOR EXTERIOR APPLICATIONS 3/4". J. FUSES: FUSES SHALL BE DUAL ELEMENT OR FUSETRON BY BUSSMAN, OR EQUIVALENT. PROVIDE 20% SPARE OF a. NFPA. 70 NATIONAL ELECTRIC CODE (NEC)
EACH SIZE AND TYPE OF FUSE USED (MINIMUM OF 5 EACH SIZE). b. NFPA. 72 NATIONAL FIRE ALARM CODE TO THIS PROJECT
2) ELECTRICAL METALLIC CONDUIT (EMT) SHALL BE USED WHEN CONCEALED.
K. TEMPERATURE CONTROL WIRING: CONTROL WIRING AND CONDUIT FOR MECHANICAL EQUIPMENT INCLUDING c. NFPA. 101 LIFE SAFETY CODE
3) FLEXIBLE STEEL CONDUIT SHALL BE USED FROM ADJACENT JUNCTION BOXES TO MOTORS AND IN LOCATIONS THERMOSTATS, RELAYS, ETC., WILL BE FURNISHED, INSTALLED AND WIRED BY THE MECHANICAL TRADES, UNLESS
NOTED OTHERWISE 2.) UNDERWRITERS LABORATORIES INC. (UL) - USA.
WHERE, FOR STRUCTURAL OR OTHER REASONS, IT IS IMPRACTICAL TO USED RIGID CONDUIT AND WHERE
APPROVED BY PROJECT ELECTRICAL ENGINEER. TO BE UTILIZED FOR SHORT RUNS ONLY NOT TO EXCEED 6'-0". 3.) COMPLY WITH THE LATEST ADOPTED EDITION OF ALL APPLICABLE CODES.
ALL WHIPS TO MECHANICAL EQUIPMENT SHALL BE IN LIQUIDTIGHT FLEXIBLE STEEL CONDUIT. L. TRANSFORMERS: PROVIDE SELF COOLED DRY-TYPE TRANSFORMERS, COPPER WINDINGS, BUILT IN ACCORDANCE
WITH LATEST IEEE, UL, ANSI, AND NEMA STANDARDS. TRANSFORMER INSULATION RISE SHALL NOT BE GREATER C. WARRANTY - ALL WORK PERFORMED AND ALL MATERIAL AND EQUIPMENT FURNISHED UNDER THIS CONTRACT
4) SCHEDULE 40 POLYVINYL CHLORIDE (PVC) MAY BE USED UNDER CONCRETE SLABS AND UNDERGROUND. THAN 115 DEGREES C FOR TRANSFORMERS 30KVA AND SMALLER. TRANSFORMERS USED OUTDOORS SHALL BE SHALL BE FREE FROM DEFECTS AND SHALL REMAIN SO FOR A PERIOD OF AT LEAST ONE (1) YEAR FROM THE
RISERS ARE TO BE TAPE-WRAPPED GRS. MINIMUM BURIAL DEPTH IS 24 INCHES. SUITABLY RATED. TRANSFORMERS 9KVA AND LARGER SHALL HAVE A MINIMUM OF FOUR TAPS PROVIDING AN DATE OF FINAL ACCEPTANCE. THE FULL COST OF MAINTENANCE, LABOR AND MATERIALS REQUIRED TO
ADJUSTMENT RANGE FROM 5% ABOVE TO 5% BELOW; SMALLER TRANSFORMERS SHALL HAVE TWO TAPS. ADJUST CORRECT ANY DEFECT DURING THIS ONE-YEAR PERIOD SHALL BE INCLUDED IN THE SUBMITTAL BID.
C. CABLES AND CONDUCTORS: ALL TAPS TO NOMINAL VOLTAGES.
M. COMBINATION MOTOR STARTERS/DISCONNECT SWITCHES: SHALL BE OF HEAVY DUTY CONSTRUCTION AND TYPE D. SYSTEM PERFORMANCE

ELECTRICAL SPECIFICATIONS
1) POWER SHOWN ON DRAWINGS.
1.) BASIC PERFORMANCE

a. ALL WIRING AND CABLE SHALL BE RATED FOR 600V UNLESS NOTED OTHERWISE AND MANUFACTURED BY N. GROUNDING a. THE EXISTING SECONDARY POWER SOURCE OF THE FIRE ALARM CONTROL PANEL WILL BE CAPABLE OF
GE, ROME, PHELPS-DODGE, ANACONDA, OKONITE, GENERAL CABLE, OR APPROVED EQUAL. ALL WIRE SHALL 1) ALL CONCRETE ENCASED OR DIRECT BURIED UNDERGROUND GROUNDING ELECTRODE CONDUCTORS SHALL PROVIDING AT LEAST 24 HOURS OF BACKUP POWER, IN NON-ALARM MODE WITH THE ABILITY TO SUSTAIN 5
BE DELIVERED TO JOB IN UNBROKEN PACKAGES EACH PACKAGE SHALL BEAR THE UL AND MANUFACTURER'S BE SOFT DRAWN BARE COPPER CABLE, CONFORMING TO ASTM B8. SIZED AS REQUIRED BY TABLE 250.66 OF THE MINUTES IN ALARM AT THE END OF THE BACKUP PERIOD.
LABELS, SHOWING DATE OF MANUFACTURE AND MAXIMUM ALLOWABLE VOLTAGE. NEC, EXCEPT WHERE A LARGER SIZE CONDUCTOR IS SHOWN ON THE CONTRACT DRAWINGS.
b. ALARM, TROUBLE AND SUPERVISORY SIGNALS FROM ALL INTELLIGENT REPORTING DEVICES SHALL BE
USE MINIMUM SIZE #12 AWG TYPE THROUGH SIZE #8, 600 VOLT RATED. ENCODED ON NFPA STYLE 4 (CLASS B), NFPA STYLE 6 (CLASS A) OR NFPA 7 (CLASS A) SIGNALING LINE
2) MINIMUM CONDUCTOR ALLOWED: 2/0.
CIRCUITS (SLC).
b. ALL WIRE TO BE COPPER AND SHALL HAVE 98% CONDUCTIVITY. WIRE SIZES #10 AWG AND SMALLER
SHALL BE SOLID CONDUCTOR. LARGER SIZES TO BE STRANDED CONDUCTOR. COLOR CODE AS FOLLOWS: 3) EQUIPMENT GROUNDING CONDUCTOR: c. ADDRESSABLE MONITOR MODULE FOR ONE ZONE OF NORMALLY-OPEN DRY-CONTACT INITIATING DEVICES.
COPPER CONDUCTOR: IDENTICAL INSULATION TO PHASE CONDUCTORS. PROVIDE AN EQUIPMENT GROUNDING MOUNTS IN STANDARD 4.0" (10.16 CM.) BOX. INCLUDES PLASTIC COVER PLATE AND END-OF-LINE RESISTOR.
c. METAL CLAD (MC) CABLE SHALL BE ALLOWED IN CONCEALED AREAS WHERE ACCESSIBLE. WHERE CONDUCTOR WITH ALL FEEDERS AND BRANCH CIRCUITS. SIZED AS REQUIRED BY TABLE 250.122 OF THE NEC, MODULE MAY BE CONFIGURED FOR EITHER A STYLE B (CLASS B) OR STYLE D (CLASS A) IDC.
APPROVED BY ENGINEER. EXCEPT WHERE A LARGER SIZE CONDUCTOR IS SHOWN ON THE CONTRACT DRAWINGS.
d. INITIATION DEVICE CIRCUITS (IDC) SHALL BE WIRED CLASS B (NFPA STYLE B) OR CLASS A (NFPA STYLE D)
4) GROUND ROD BOXES: PROVIDE GROUND ROD BOXES FOR EACH GROUND ROD. GROUND ROD BOXES SHALL AS PART OF AN ADDRESSABLE DEVICE CONNECTED BY THE SLC CIRCUIT.
d. 120/208V:
NEUTRAL WHITE BE CONCRETE WITH TRAFFIC RATE COVERS, FOGTITE SP-1, OR APPROVED EQUAL,UNLESS NOTED OTHERWISE. e. NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE WIRED CLASS B (NFPA STYLE Y) OR CLASS A (NFPA
GROUND GREEN STYLE Z) AS PART OF AN ADDRESSABLE DEVICE CONNECTED BY THE SLC CIRCUIT.
PHASE A BLACK 5) GROUNDING ELECTRODE RODS USED SHALL BE A MINIMUM OF 3/4" DIAMETER BY 10' LONG, STEEL CORE AND
E. EQUIPMENT AND MATERIAL - ALL EQUIPMENT AND COMPONENTS SHALL BE NEW, AND THE MANUFACTURER'S
PHASE B RED COPPER JACKET (COPPERCLAD) HEAVY UNIFORM COATING OF ELECTROLYTIC COPPER MOLECULARLY BONDED TO
CURRENT MODEL.
PHASE C BLUE A RIGID STEEL CORE.

O. ELECTRICAL EQUIPMENT IDENTIFICATION: F. WIRE - ALL FIRE ALARM SYSTEM WIRING SHALL BE NEW AND IN ACCORDANCE WITH LOCAL, STATE AND NEC AND
2) DATA COMMUNICATIONS CABLE: PROVIDE 1" CONDUIT WITH JUNCTION BOX. PROVIDE AND INSTALL CAT-6 1) PROVIDE ENGRAVED PHENOLIC PLATES FOR ALL SWITCHGEAR, PANELBOARDS, COMBINATION MOTOR AS RECOMMENDED BY THE MANUFACTURER OF THE FIRE ALARM SYSTEM. PROJECT NO. 1859
CABLE(S), COVER PLATE WITH PORTS AS DICTATED ON SYMBOLS SHEET, AND PUNCH DOWN. LABEL ALL CABLES STARTERS AND DISCONNECTS. NAMEPLATE INFORMATION TO INCLUDE EQUIPMENT SERVED AND SOURCE OF
ON WALL PLATES AS WELL AS PATCH PANEL. PATCH PANELS PROVIDED BY OWNER. COORDINATE LABELING
DESIGNED BY MWM
POWER (EQUIPMENT AND CIRCUIT).
WITH OWNER. G.INSTALLATION - INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, NFPA 72, LOCAL AND STATE CODES. DRAWN BY MWM
3) TELEPHONE COMMUNICATIONS CABLE: PROVIDE 1" CONDUIT WITH JUNCTION BOX. PROVIDE AND INSTALL ISSUE DATE 9-24-2019
H. TESTING - THE SERVICE OF A FACTORY-TRAINED ENGINEER OR TECHNICIAN AUTHORIZED BY THE MANUFACTURER
CAT-6 CABLE(S), COVER PLATE WITH PORTS AS DICTATED ON SYMBOLS SHEET, AND PUNCH DOWN. LABEL ALL
CABLES ON WALL PLATES AS WELL AS PATCH PANEL. PATCH PANELS PROVIDED BY OWNER. COORDINATE OF THE FIRE ALARM CONTROL PANEL SHALL BE PROVIDED TO SUPERVISE DURING ADJUSTMENTS AND TESTS PHASE 100% BID SET
LABELING WITH OWNER. CHECKED BY RL
REVISION
SHEET NO.
COPYRIGHT 2019
All rights reserved. Reproduction or translation of any part
of this work without written permission of
ARCHITECTS WEST INC.
is unlawful and subject to criminal prosecution.

1. SEE REFLECTED CEILING PLANS FROM ARCHITECT


FOR EXACT FIXTURE LOCATIONS.

2. SEE ARCHITECTURAL ELEVATIONS FOR MOUNTING


HEIGHTS FOR WALL MOUNTED DEVICES.

3. COORDINATE FIXTURE LOCATIONS IN AREAS WITH


GENERATOR EXPOSED CEILINGS WITH DUCTWORK AND PIPING.
ADJUST LOCATIONS AS REQUIRED FOR ACTUAL
ATS FIELD CONDITIONS.

4. SUPPORT LIGHTS IN ACCORDANCE WITH IBC


SEISMIC ZONE REQUIREMENTS.
GENERATOR
5. PROVIDE CABLE SUPPORTS IN CONJUNCTION WITH
EMERG
SWBD
ROOM MOST CURRENT BICSI STANDARDS AS SUGGESTED
PER THE ITS INSTALLATION METHODS MANUAL
5 (ITSIMM). COORDINATE WITH OWNER.

6. PROVIDE AND ALL STRUCTURE CABLING FOR


ACCESS CONTROL DEVICES AND MAKE ALL
EMERG MAIN BREAKER
TERMINATIONS. PROVIDE 2-PAIR TWISTED
SHIELDED CABLE PER MANUFACTURERS
REQUIREMENTS. PROVIDE POWER SUPPLIES FOR
ELECTRONIC LOCKS PER MANUFACTURERS
RECOMMENDATIONS.

MAIN
SWBD

5 HALLWAY 1 EXISTING RECESSED CONTINUOUS LUMINAIRE


WALL WASHER. SECTION TO BE DEMOLISHED FOR
MAIN INSTALLATION OF NEW DOOR FRAME. DEMO PER
EXISTING LENGTHS OF LUMINAIRE AVAILABLE
ELECTRICAL FOR DOOR FRAME. COORDINATE WITH
ARCHITECTURAL FOR EXACT LOCATION OF
ROOM FRAMING PRIOR TO DEMOLITION. MAINTAIN
EXISTING CIRCUIT AND CONTROLS FOR RE-USE. STRUCTURAL
REFERENCE ARCHITECTURAL FOR NEW
FRAMEWORK AND DETAIL 1/E-801 FOR EXISTING
INFORMATION. EXISTING FIXTURE CONTAINS
STAGGERED 4' FLUORESCENT T12 LAMPS.
MECHANICAL
2 EXISTING LUMINAIRE TO BE DEMOLISHED.
RETAIN EXISTING CIRCUIT AND CONTROLS FOR
REUSE. REPAIR SOFFIT TO MATCH EXSITING
CONDITIONS AND INSTALLATION OF NEW
FIXTURES. REFERENCE SHEET E-201 FOR NEW ELECTRICAL
WORK. TRINDERA
1130 W HAYDEN AVE, SUITE #101
HAYDEN, IDAHO 83835
3 EXISTING ELECTRICAL DEVICE/CONTROLS TO 208.676.8001
9 REMAIN. PROTECT IN PLACE. MAINTAIN EXISTING
PATHWAY AND CIRCUITING.

4 REMOVE EXISTING COMMUNICATIONS/SECURITY


DEVICE FOR RE-LOCATION. MAINTAIN EXISTING
PATHWAY AND CIRCUIT FOR REUSE. REFERENCE
A SHEET E-201 FOR NEW WORK AND DETAIL
6 2/E-801 FOR EXISTING INFORMATION.
A 5 EXISTING ROOM ON LEVEL BELOW

600 W. PRAIRIE AVE. BUILDING 1002, COEUR D ALENE, IDAHO 83815


6
ELEV EQUIP 6 EXISTING ACCESS CONTROL PANELS. HIRSCH
ELECTRONICS MODEL 8 SYSTEM WITH NET-MUX4
6 ROOM CONTROLLER. PROVIDE ADDITIONAL
CONTROLLER AND EXPAND SYSTEM AS REQUIRED
1 FOR NEW DOORS.

CR 5 8 7 HIRSCH IDENTIV MX CONTROLLER WITH POWER


SUPPLY.
3
ER
8 CEILING OPEN TO STRUCTURE IN SPACE ON LEVEL
5 10 A A Room BELOW.

ITD SECURITY LOBBY 19-100


7 7
COMPUTER 103 9 EXISTING CABLE TRAY ABOVE CEILING OF FLOOR
BELOW.
4
ROOM 10 DROPPED TILE CEILING ABOVE SPACE ON LEVEL
BELOW.
STAIR

ITD - COEUR D ALENE


ABOVE 4

SSSS
ER
CONFRENCE
104 3
105 ER
C
C
RECEPTION
2
5 8
102
MECHANICAL

POWER & SYSTEMS PLAN - DEMO / EXSITING


ROOM
2

LOBBY
101

VEST.
100

PROJECT NO. 1859


DESIGNED BY MWM
DRAWN BY MWM
ISSUE DATE 9-24-2019
PHASE 100% BID SET
CHECKED BY RL
REVISION
SHEET NO.
COPYRIGHT 2019
All rights reserved. Reproduction or translation of any part
of this work without written permission of
ARCHITECTS WEST INC.
is unlawful and subject to criminal prosecution.

1. SEE REFLECTED CEILING PLANS FROM ARCHITECT


FOR EXACT FIXTURE LOCATIONS.

2. SEE ARCHITECTURAL ELEVATIONS FOR MOUNTING


HEIGHTS FOR WALL MOUNTED DEVICES.

3. COORDINATE FIXTURE LOCATIONS IN AREAS WITH


EXPOSED CEILINGS WITH DUCTWORK AND PIPING.
ADJUST LOCATIONS AS REQUIRED FOR ACTUAL
FIELD CONDITIONS.

G 4. SUPPORT LIGHTS IN ACCORDANCE WITH IBC


SEISMIC ZONE REQUIREMENTS.

5. PROVIDE CABLE SUPPORTS IN CONJUNCTION WITH


MOST CURRENT BICSI STANDARDS AS SUGGESTED
PER THE ITS INSTALLATION METHODS MANUAL
(ITSIMM). COORDINATE WITH OWNER.
100NG
6. PROVIDE AND ALL STRUCTURE CABLING FOR
ACCESS CONTROL DEVICES AND MAKE ALL
TERMINATIONS. PROVIDE 2-PAIR TWISTED
SHIELDED CABLE PER MANUFACTURERS
REQUIREMENTS. PROVIDE POWER SUPPLIES FOR
ELECTRONIC LOCKS PER MANUFACTURERS
RECOMMENDATIONS.

1 EXTEND EXISTING LIGHTING CIRCUIT AND


STRUCTURAL
CONTROLS TO NEW FIXTURES.

2 EXTEND EXISTING CIRCUIT(S) TO RELOCATED


DEVICES AS SHOWN ON PLANS. COORDINATE
WITH ARCHITECTURAL FOR INSTALLATION OF
MECHANICAL
SECURITY WINDOW.

3 PROVIDE NEW ACCESS CONTROL DEVICE FOR


EXISTING SYSTEM. COORDINATE FINAL LOCATION
WITH ARCHITECTURAL PLANS AND DOOR
HARDWARE SCHEDULE PRIOR TO ROUGH-IN.
ELECTRICAL
PULL NEW CABLES TO EXISTING SYSTEM AS TRINDERA
1130 W HAYDEN AVE, SUITE #101
REQUIRED. COORDINATE WITH MANUFACTURER
9 HAYDEN, IDAHO 83835
AND IT DEPARTMENT. REFERENCE DETAILS 208.676.8001
3/E-801 AND 4/E-801

4 PROVIDE JUNCTION BOX WITH POWER SUPPLY FOR


ACCESS CONTROL POWER. EXTEND CIRCUIT FROM
PANEL AS INDICATED TO NEW ACCESS CONTROL
POWER SUPPLY ABOVE CEILING. REFERENCE DETAIL
3/E-801 FOR MORE INFORMATION.

5 EXTEND EXISTING LIGHTING CIRCUIT AND CONTROLS


AS REQUIRED AFTER DOOR FRAME INSTALLATION.

600 W. PRAIRIE AVE. BUILDING 1002, COEUR D ALENE, IDAHO 83815


6 PROVIDE NEW ACCESS CONTROL PANEL TO MATCH
EXISTING ADJACENT WITH 10% SPARE RELAY
A CAPACITY FOR FUTURE USE.

7 PROVIDE POWER SUPPLY CONTROLLER FOR ACCESS


ELEV EQUIP CONTROL PANEL TO MATCH EXISTING.

ROOM 8 REPLACE EXISTING LAMPS IN EXISTING WALL WASH


LUMINAIRE THE ENTIRE LENGTH AROUND PERIMETER
OF THE WALL. REFERENCE SHEET E-101 FOR MORE
INFORMATION.
CR 4 4

ITD SECURITY LOBBY 19-100


9 EXISTING PANEL TO BE USED AS PART OF SCOPE
ER J OF WORK. EXISTING SPARE CIRCUITS TO BE
CR-20 J 5 RE-USED ARE ASSOCIATED WITH PANEL.
A A A A
D ES D ES
Room

ITD - COEUR D ALENE


7 6 103

POWER & SYSTEMS PLAN - NEW / EXISTING RISER DIAGRAM


COMPUTER 3
2
ROOM 3
STAIR ABOVE 2

SSSS
ER
CONFRENCE
104
105 3
ER
CR-18 C
C
RECEPTION
ES
L01
102
1
D
J
4 D

L01
ES
1
LOBBY
101

VEST.
100
PROJECT NO. 1859
DESIGNED BY MWM
DRAWN BY MWM
ISSUE DATE 9-24-2019
PHASE 100% BID SET
CHECKED BY RL
REVISION
SHEET NO.
COPYRIGHT 2019
All rights reserved. Reproduction or translation of any part
of this work without written permission of
ARCHITECTS WEST INC.
is unlawful and subject to criminal prosecution.

REFERENCE SHEET E-201 REFERENCE


SHEET E-201

REFERENCE SHEET E-201

STRUCTURAL

MECHANICAL

ELECTRICAL
SCALE: NTS TRINDERA
1130 W HAYDEN AVE, SUITE #101
HAYDEN, IDAHO 83835
208.676.8001

1 EXISTING CONDITIONS 2 EXISTING CONDITIONS


- - SCALE: NTS

(EXISTING) HEAD END


ACCESS CONTROL
EQUIPMENT

600 W. PRAIRIE AVE. BUILDING 1002, COEUR D ALENE, IDAHO 83815


1" CONDUIT ONLY
(WIRING BY OTHERS)

ITD SECURITY LOBBY 19-100


(EXISTING) CABLE TRAY

ITD - COEUR D ALENE


TO ACCESS SYSTEM CONTROLLER

DOOR CONTROLLER WITH POWER SUPPLY


(4" SQUARE BOX WITH DOUBLE GANG MUD RING)

1/2" CONDUIT IN WALL


TO DOOR JAMB

LIGHTING SCHEDULE & ELECTRICAL DETAILS


REQUEST TO EXIT BACK BOX
(FIELD VERIFY LOCATION) (AS REQUIRED) 1" CONDUIT ONLY
(WIRING BY OTHERS)
DOOR POSITION BACK BOX
(ALTERNATE LOCATION)

1/2" CONDUIT IN WALL, TYP.

DOOR CONTROLLER

CARD READER
1/2" FLEX CONDUIT,
(WIRE BY OTHERS)
4"x 2-1/8" BACKBOX W/
SINGLE GANG MUD RING
DETAIL NOTES DETAIL NOTES CARD READER
1. DETAIL IS DIAGRAMMATIC AND REQUIREMENTS MAY 1. DETAIL IS DIAGRAMMATIC AND REQUIREMENTS MAY
CHANGE DEPENDING ON SELECTION OF ACCESS CHANGE DEPENDING ON SELECTION OF ACCESS
SYSTEM. COORDINATE WITH SELECTED ACCESS SYSTEM. COORDINATE WITH SELECTED ACCESS
SYSTEM VENDOR FOR EXACT REQUIREMENTS AND SYSTEM VENDOR FOR EXACT REQUIREMENTS AND
REVISE INSTALLATION AS NEEDED. 1/2" CONDUIT TO REVISE INSTALLATION AS NEEDED.
DOOR JAMB
2. FURNISH AND INSTALL ADDITIONAL DEVICES AS 2. FURNISH AND INSTALL ADDITIONAL DEVICES AS
INDICATED ON PLAN DRAWINGS FOR LOCATIONS WITH INDICATED ON PLAN DRAWINGS FOR LOCATIONS WITH PROJECT NO. 1859
BACK BOX (TYPICAL)
DOUBLE DOORS. DOUBLE DOORS. DESIGNED BY MWM
ELECTRIC DOOR REQUEST DOOR ELECTRIC
STRIKE DRAWN BY MWM
TO POSITION DOOR
EXIT STRIKE ISSUE DATE 9-24-2019
PHASE 100% BID SET
CHECKED BY RL
REVISION
SHEET NO.
3 ACCESS CONTROL CONDUIT ROUTING 4 ACCESS CONTROL SCHEMATIC DIAGRAM
- SCALE: NTS - SCALE: NTS