0% found this document useful (0 votes)
13 views8 pages

Cable High Voltage Report - 1600 Mm2 Cu (Concreto) - sensibilidadPE

The document presents a study on the sensitivity of a buried high voltage cable installation, detailing the current rating, thermal resistivity, and electrical properties of the cable. Circuit 1, using a 1600 mm² copper conductor, has a maximum operating temperature of 75 ºC and a current rating of 990 A. The report includes calculations of electrical losses, thermal resistances, and permissible short-circuit currents for the cable system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views8 pages

Cable High Voltage Report - 1600 Mm2 Cu (Concreto) - sensibilidadPE

The document presents a study on the sensitivity of a buried high voltage cable installation, detailing the current rating, thermal resistivity, and electrical properties of the cable. Circuit 1, using a 1600 mm² copper conductor, has a maximum operating temperature of 75 ºC and a current rating of 990 A. The report includes calculations of electrical losses, thermal resistances, and permissible short-circuit currents for the cable system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

ELEK Cable High Voltage V7.

5 30-07-2025, 14:37

Concreto (sensibilidad)

Title of study : MC Arenales Sensibilidad PE


Installation : Buried
Grouping calculation method : Unequally loaded
Calculation method : IEC 60287, EI-Kady
No. of iterations : 4
Convergence tolerances : 0.05 ºC, 0.05 A

SUMMARY OF RESULTS FOR ALL CIRCUITS


CONDUCTOR CABLE
NO. NAME CURRENT RATING
TEMPERATURE SYSTEM NO.

1 Circuit 1 75 ºC 990 A (999.14 A) 1

Figure 1 Buried installation arrangement (m)


Software Licensed to I-SEP

Software by Page 1 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

Figure 2 Temperature contour plot


Software Licensed to I-SEP

Software by Page 2 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

CONCRETO (SENSIBILIDAD) - CIRCUIT 1 DATA


SUMMARY OF RESULTS

CURRENT RATING OF CIRCUIT 1 990 A (999.14 A)


Cable model no. 1
Cable model description 1600 mm2 Cu
Maximum conductor operating
temperature 75 ºC

Grouping calculation method Unequally loaded


Soil thermal resistivity 4.21 K.m/W
Ambient soil temperature 25.8 ºC
CABLE COORDINATES

Phase A (lagging) X: -0.5, Y: 1.081 m


Phase B (middle) X: 0.5, Y: 1.081 m
Phase C (leading) X: 1.501, Y: 1.081 m
BACKFILL

Backfill thermal resistivity 1 K.m/W


X, centre of backfill -0.0047754 m
Y, centre of backfill 0.948165 m
Height of backfill area 0.7 m
Width of backfill area 3.5 m
DUCTS

Duct arrangement Separate duct per phase


Duct material PE
Thermal resistivity 3.5 K.m/W
Outside diameter 250 mm
Inside diameter 240 mm
Fill inside duct Air
Filler thermal resistivity 40 K.m/W
CALCULATION

Based on Temperature limit


Target cable object Conductor
Same as cable insulation FALSE
Temperature 75 ºC
Load factor (daily) 1
BONDING

Arrangement Single point bonded


ELECTRICAL LOSSES PER CABLE (IEC 60287-1-1)
Software Licensed to I-SEP

Total losses 18.663 W/m


Conductor loss 18.2029 W/m
Dielectric loss 0.10197 W/m
Sheath loss 0.358111 W/m
LOSS FACTORS

Sheath/screen circulating loss factor,


lambda1' 0

Software by Page 3 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

Sheath/screen eddy current loss factor,


lambda1'' 0.0196733

Sheath/screen total loss factor, lambda1 0.0196733


ELECTRICAL PROPERTIES PER CABLE

Conductor AC resistance 1.82342E-5 Ohms/m


Conductor DC resistance 1.37425E-5 Ohms/m
Conductor Skin effect factor 0.325293
Conductor Proximity effect factor 0.0015548
Insulation capacitance 2.01187E-10 F/m
Sheath AC resistance 3.66359E-5 Ohms/m
STANDING VOLTAGE AND CIRCULATING CURRENTS

Sheath/screen standing voltage 0.176782 V/m


SEQUENCE IMPEDANCES

Positive sequence, Z1 0.0181872 +0.263682 i Ohms/km


Negative sequence, Z2 0.0181872 +0.263682 i Ohms/km
Zero sequence, Z0 0.166232 +1.50879 i Ohms/km
Soil electrical resistivity 100 Ohms.m
Reduction factor (Magnitude) 0.206558
Reduction factor (Phase) 78.0793 º
Surge impedance 62.8179 Ohms
PERMISSIBLE SHORT-CIRCUIT CURRENTS (NON-ADIABATIC)

Short-circuit times 0.1, 0.2, 0.3, 0.5, 1, 3, 5 s


Conductor 765.7, 541.8, 442.6, 343.1, 243, 140.9, 109.4 kA
Sheath 222.3, 157.8, 129.2, 100.6, 71.8, 42.3, 33.3 kA
THERMAL RESISTANCES

T1, between conductor and first metallic


layer 0.613874 K.m/W

T1 scaling factor 1
T2, between first and last metallic layers 0 K.m/W
T3, outer covering 0.0996491 K.m/W
T3 scaling factor 1
T4, external surroundings 0.947618 K.m/W
Temperature rise due to other cables and
circuits 4.8383 ºC

DUCTS OR PIPE

T4', between cable and duct/pipe 0.22009 K.m/W


T4'', duct/pipe itself 0.0227396 K.m/W
T4''', duct/pipe external surroundings
Software Licensed to I-SEP

0.704788 K.m/W
BACKFILL

Thermal resistance correction 0.988547 K.m/W


TEMPERATURES

Conductor temperature 75 ºC
Sheath temperature 63.7944 ºC
Jacket temperature 61.9346 ºC

Software by Page 4 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

Duct/pipe filling temperature 59.8809 ºC


Duct/pipe temperature 57.4027 ºC
Software Licensed to I-SEP

Software by Page 5 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

CONCRETO (SENSIBILIDAD) - CABLE MODEL 1 IMAGE

CABLE MODEL 1 DATA


Used by Circuit 1
GENERAL

Description of cable 1600 mm2 Cu


Manufacturer datasheet file
Append datasheet with report FALSE
Cable type Extruded
Software Licensed to I-SEP

Cores Single-core

Phases Three-phase
Voltage (phase to phase) 220 kV
Frequency 50 Hz

Software by Page 6 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

CONDUCTOR

Diameter 49.2 mm
Range Metric - IEC 60228
Conductor size 1600 mm²
IEC class Class 2 stranded
Material Copper, plain wires
Conductor type Copper_Round, stranded (Extruded/Mineral insulation)
Skin effect coefficient, ks 1
Proximity effect coefficient, kp 1
DC resistance Standard
Maximum DC resistance at 20 ºC 0.0113 Ohms/km
Electrical resistivity at 20 ºC 1.7241E-8 Ohm.m
Electrical temperature coefficient of metal 0.00393 per K at 20 ºC
Thermal conductivity 384.615 W/(m.K)
Specific heat capacity 3.45E+6 J/(m³.K)
Reciprocal of temperature coefficient of
resistance 234.5 K

CONDUCTOR SCREEN

Diameter 54.1 mm
Thickness 2.45 mm
Material Extruded semi-conductor
Thermal resistivity 3.3 K.m/W
Specific heat capacity 2.4E+6 J/(m³.K)
INSULATION

Diameter 102.1 mm
Thickness 24 mm
Maximum operating temperature 90 °C
Insulation type Custom
Relative permittivity, epsilon 2.3
Loss factor, tandelta 0.0001
Thermal resistivity 3.3 K.m/W
Specific heat capacity 2.4E+6 J/(m³.K)
Maximum short-circuit temperature 250 °C
Electrical capacitance Calculate
INSULATION SCREEN

Diameter 104.5 mm
Thickness 1.2 mm
Material Extruded semi-conductor
Software Licensed to I-SEP

Thermal resistivity 3.3 K.m/W


Specific heat capacity 2.4E+6 J/(m³.K)
WATER BLOCKING

Diameter 110.5 mm
Thickness 3 mm
Combined with main insulation FALSE
Material Tape_Water blocking

Software by Page 7 of 8
- www.elek.com
ELEK Cable High Voltage V7.5 30-07-2025, 14:37

Thermal resistivity 12 K.m/W


Specific heat capacity 2E+6 J/(m³.K)
Maximum short-circuit temperature 250 °C
SHEATH

Construction Corrugated
Diameter 129 mm
Wave height 5 mm
Thickness of metal 2.6 mm
Pitch Length 30 mm
Area 978.135 mm²
Material Aluminium
DC resistance Calculate
Maximum DC resistance at 20 ºC 0.029034851 Ohms/km
Corrugation factor Calculate
Corrugation factor 1.073
Electrical resistivity at 20 ºC 2.84E-8 Ohm.m
Electrical temperature coefficient of metal 0.00403 per K at 20 ºC
Thermal conductivity 204.082 W/(m.K)
Specific heat capacity 2.5E+6 J/(m³.K)
Reciprocal of temperature coefficient of
resistance 228 K

ANTI CORROSION

Diameter 129.5 mm
Thickness 0.25 mm
Combined with main insulation FALSE
Material Protective coverings_PVC/bitumen on corrugated aluminium sheaths
Thermal resistivity 6 K.m/W
Specific heat capacity 1.7E+6 J/(m³.K)
Maximum short-circuit temperature 140 °C
JACKET

Diameter 139.5 mm
Thickness 5 mm
Material Polyethylene
Thermal resistivity 3.5 K.m/W
Specific heat capacity 2.4E+6 J/(m³.K)
Maximum short-circuit temperature 130 °C
SEMI-CONDUCTING LAYER

Diameter 140.5 mm
Software Licensed to I-SEP

Thickness 0.5 mm
Combined with main insulation FALSE
Material Insulation_PE (HD and LD)
Thermal resistivity 3.5 K.m/W
Specific heat capacity 2.4E+6 J/(m³.K)
Maximum short-circuit temperature 130 °C

Software by Page 8 of 8
- www.elek.com

You might also like