SCHEDULE OF LOADS FOR DAO WIND POWER PLANT
BRANCH GROUND
SHORT CIRCUIT ANALYSIS FOR DAO WIND POWER PLANT
BREAKER CONDUIT
CKT.
DESCRIPTION OF LOADS VA V AB BC CA KAIC
CONDUCTOR CONDUCTOR LINE IMPEDANCE \ SHORT
N0. AT AF P mm² TYPE mm² TYPE mm² TYPE CONDUCT IMPEDANCE VOLTAGE
LINE DESCRIPTION LENGTH CONDUCTOR P CIRCUIT KAIC
OR (mm²) (Ω\m) L-L (v)
1 LIGHTING OUTLET 8 X 15W LED 120 230 0.65 5 20 100 2 3.5 THHN 3.5 THHN 20 PVC
(m) (Ω\m) CURRENT (A)
2 LIGHTING OUTLET 4 X 15W LED 60 230 0.33 5 20 100 2 3.5 THHN 3.5 THHN 20 PVC TAPPING POINT - FAULT 1 5 22.0 0.00105246 0.00526230 230 2 14569.0414 15
3 LIGHTING OUTLET 10 X 100W LED 1000 230 5.43 5 20 100 2 3.5 THHN 3.5 THHN 20 PVC
TAPPING POINT - FAULT 2 29.5 3.5 0.00672131 0.19827865 230 2 579.9919 5
4 LIGHTING OUTLET 8 X 100W LED 800 230 4.35 5 20 100 2 3.5 THHN 3.5 THHN 20 PVC
TAPPING POINT - FAULT 3 16.5 3.5 0.00672131 0.11090162 230 2 1036.9551 5
5 LIGHTING OUTLET 4 X 15W LED 60 230 0.33 5 20 100 2 3.5 THHN 3.5 THHN 20 PVC
TAPPING POINT - FAULT 4 35 3.5 0.00672131 0.23524585 230 2 488.8503 5
6 DUPLEX CONVENIENCE OUTLET 9 x 360W 3240 230 17.61 5 30 100 2 3.5 THHN 3.5 THHN 20 PVC
TAPPING POINT - FAULT 5 27 3.5 0.00672131 0.18147537 230 2 633.6948 5
7 DUPLEX CONVENIENCE OUTLET 7 x 360W 2520 230 13.70 5 30 100 2 3.5 THHN 3.5 THHN 20 PVC
TAPPING POINT - FAULT 6 16 3.5 0.00672131 0.10754096 230 2 1069.3600 5
8 DUPLEX CONVENIENCE OUTLET 4 x 360W 1440 230 7.83 5 30 100 2 3.5 THHN 3.5 THHN 20 PVC TAPPING POINT - FAULT 7 43 3.5 0.00672131 0.28901633 230 2 397.9014 5
9 DUPLEX CONVENIENCE OUTLET 6 x 360W 2160 230 11.74 5 30 100 2 3.5 THHN 3.5 THHN 20 PVC TAPPING POINT - FAULT 8 18 3.5 0.00672131 0.12098358 230 2 950.5422 5
10 DUPLEX CONVENIENCE OUTLET 6 x 360W 2160 230 11.74 5 30 100 2 3.5 THHN 3.5 THHN 20 PVC TAPPING POINT - FAULT 9 16 3.5 0.00672131 0.10754096 230 2 1069.3600 5
11 A.C.U. 2.5 HP 3335 230 18.13 5 30 100 2 8.0 THHN 8.0 THHN 20 PVC
TAPPING POINT - FAULT 10 24 3.5 0.00672131 0.16131144 230 2 712.9067 5
TAPPING POINT - FAULT 11 28 3.5 0.00672131 0.18819668 230 2 611.0629 5
12 A.C.U. 2.5 HP 3335 230 18.13 5 30 100 2 8.0 THHN 8.0 THHN 20 PVC
TAPPING POINT - FAULT 12 9 8.0 0.00265246 0.02387214 230 2 4817.3310 5
13 A.C.U. 2.5 HP 3335 230 18.13 5 30 100 2 8.0 THHN 8.0 THHN 20 PVC
TAPPING POINT - FAULT 13 18 8.0 0.00265246 0.04774428 230 2 2408.6655 5
14 A.C.U. 2.5 HP 3335 230 18.13 5 30 100 2 8.0 THHN 8.0 THHN 20 PVC
TAPPING POINT - FAULT 14 16 8.0 0.00265246 0.04243936 230 2 2709.7487 5
15 EXAUST FAN 750 230 3.26 5 30 100 2 5.5 THHN 5.5 THHN 20 PVC
TAPPING POINT - FAULT 15 22 8.0 0.00265246 0.05835412 230 2 1970.7263 5
16 EXAUST FAN 750 230 3.26 5 30 100 2 5.5 THHN 5.5 THHN 20 PVC
17 EXAUST FAN 750 230 3.26 5 30 100 2 5.5 THHN 5.5 THHN 20 PVC TAPPING POINT - FAULT 16 25 5.5 0.00422951 0.10573775 230 2 1087.5964 5
TOTAL 29150 51.25 51.38 53.34 (53.34)(√3)(0.80) = 73.91 A TAPPING POINT - FAULT 17 33 5.5 0.00422951 0.13957383 230 2 823.9367 5
TAPPING POINT - FAULT 18 41 5.5 0.00422951 0.17340991 230 2 663.1686 5
DAO WIND POWER PLANT VOLTAGE DROP ANALYSIS BRANCH CIRCUIT COMPUTATION
CKT. 1 CKT. 10
= LIGHTING (8x15W) = Duplex Convenience Outlet (6*360W)
VOLTAGE VOLTAG = (120W / 230V)(1.25) = 0.65217 = (2160W / 230V)(1.25) = 11.73913 A
CKT. AMPERES IMPEDANCE VOLTAGE Use 3.5 mm² THHN copper wire and 20 AT Ckt. Breaker in 20mm² conduit pvc pipe.
LENGTH (m) CONDUCTOR PHASE DROP E ( L-L ) Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
N0. (A) (Ω/m) DROP (%) CKT. 2
(V) (V) = LIGHTING (4x15W)
CKT. 11
= ACU 2.5
= (60W / 230V)(1.25) = 0.32609 A = (3335W / 230V)(1.25) = 18.125 A
Use 3.5 mm² THHN copper wire and 20 AT Ckt. Breaker in 20mm² conduit pvc pipe. Use 8.0 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
1 24.5 0.65 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 0.21407372 230 0.09308 CKT. 3 CKT. 12
= LIGHTING (10x100W) = ACU 2.5
= (1000W / 230V)(1.25) = 5.43478 A = (3335W / 230V)(1.25) = 18.125 A
2 11.5 0.33 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 0.05101474 230 0.02218 Use 3.5 mm² THHN copper wire and 20 AT Ckt. Breaker in 20mm² conduit pvc pipe. Use 8.0 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
3 30 5.43 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 2.18980280 230 0.95209 CKT. 4
= LIGHTING (8x100W) CKT. 13
4 22 4.35 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 1.28645873 230 0.55933 = (800W / 230V)(1.25) = 4.34783 A = ACU 2.5
Use 3.5 mm² THHN copper wire and 20 AT Ckt. Breaker in 20mm² conduit pvc pipe. = (3335W / 230V)(1.25) = 18.125 A
5 11 0.33 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 0.04879671 230 0.02122 CKT. 5 Use 8.0 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
= Lighting Outlet (4*15W)
6 38 17.61 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 8.99553245 230 3.91110 = (60W / 230V)(1.25) = 0.32609 A CKT. 14
Use 3.5 mm² THHN copper wire and 20 AT Ckt. Breaker in 20mm² conduit pvc pipe. = ACU 2.5
7 13 13.70 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 2.39413062 230 1.04093 CKT. 6
= (3335W / 230V)(1.25) = 18.125 A
Use 8.0 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
= Duplex Convenience Outlet ( 9*360W)
8 11 7.83 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 1.15781286 230 0.50340 = (3240 / 230V)(1.25) = 17.60870A CKT. 15
Use 3.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
9 19 11.74 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 2.99851082 230 1.30370 = Exhaust fan (750 W)
= (750 / 230V) = 3.26087 A
10 23 11.74 3.5 mm² THHN Copper wire conductor 1Φ 0.00672131 3.62977625 230 1.5782 CKT. 7
= Duplex Convenience Outlet (7*360W)
Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
11 4 18.13 8.0 mm² THHN Copper wire conductor 1Φ 0.00265246 0.38471280 230 0.16727 = (2520W / 230V)(1.25) = 13.69770 A
Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
CKT. 16
= Exhaust fan (750 W)
12 13 18.13 8.0 mm² THHN Copper wire conductor 1Φ 0.00265246 1.25031660 230 0.54361 CKT. 8
= (750 / 230V)= 3.26087 A
Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
= Duplex Convenience Outlet (7*360W)
13 11 18.13 8.0 mm² THHN Copper wire conductor 1Φ 0.00265246 1.05796020 230 0.45998 = (2520W / 230V)(1.25) = 13.69770 A
Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe. CKT. 17
14 17 18.13 8.0 mm² THHN Copper wire conductor 1Φ 0.00265246 1.63502939 230 0.71088 CKT. 9
= Exhaust fan (750 W)
= (750 / 230V) = 3.26087 A
= Duplex Convenience Outlet (6*360W) Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
15 20 3.26 5.5 mm² THHN Copper wire conductor 1Φ 0.00422951 0.55152810 230 0.23979 = (2160W / 230V)(1.25) = 11.73913 A
Use 5.5 mm² THHN copper wire and 30 AT Ckt. Breaker in 20mm² conduit pvc pipe.
16 28 3.26 5.5 mm² THHN Copper wire conductor 1Φ 0.00422951 0.77213935 230 0.33571 MAIN FEEDER
TOTAL CURRENT
17 36 3.26 5.5 mm² THHN Copper wire conductor 1Φ 0.00422951 0.99275059 230 0.43163 MCCB = 29150W/ 230V =53.34(80%)(√3)
=126.73913A (0.80 df ) = 73.910072 A
= 101.3913043 A
JOEVANI BRIAN B. BAISA
JOEVANI BRIAN B. BAISA
ENGR. LEONARD PETER SAMILLANO
BS in ELECTRICAL ENGINEERING 4-A
DANAWAN WIND POWERPLANT As Shown
DECEMBER 28, 2024 ENGR. LEONARD PETER SAMILLANO
ADDRESS: SUPA, SAN JOSE, ANTIQUE