Bus Ele Cat 1007 FLC 2018 Sec 07 MV
Bus Ele Cat 1007 FLC 2018 Sec 07 MV
Contents
Section
Description page
Introduction 2
Bussmann series
Medium voltage
E-Rated, R-Rated and PT
fuses
medium voltage fuses
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries 7-1
7 — Medium voltage fuses
Introduction E- and R-Rated fuses
7-2 BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries
Medium voltage fuses — 7
2.75 kV E-Rated medium voltage ferrule fuses Dimensions — in (mm)
Catalog symbols C
•• 2CLE-_E
B
•• JCX-_E
Ratings
•• Volts 2.75 kV
•• Amps 10 to 450 A
3.31
•• Interrupting ratings (84.1)
•• 50 kA RMS Sym. (2CLE-_E) B
•• 40 kA RMS Sym. (JCX-_E)
A
Agency information
Recommended fuseclips
Description Fuse dia. — in (mm) Catalog no.
2 (51) A3354710*
Enclosed fuseclip
A3354730*
Open fuseclip 3 (76) 1A0065
Medium voltage
Spring loaded open fuseclip 9078A67G04
fuses
* For single barrel applications only. Not sold in pairs.
Catalog symbols C
•• General purpose B
•• 5CLE-_E-D (10-25 A)
•• 5CLE-_E (10-1350 A)
•• 5HLE-_E (10-450 A)
•• JCY-_E (1-25 A)
•• Full range (per ANSI C37.40) 3.31
(84.1)
•• MV055F_ (10-450 A)
B
Ratings*
A
•• Volts 5.5 kV
•• Amps 1 to 1350 A
•• Interrupting ratings 40 to 63 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Recommended fuseclips
Description Fuse dia. — in (mm) Catalog no.
2 (51) A3354710*
Enclosed fuseclip
A3354730*
Open fuseclip 3 (76) 1A0065
Spring loaded open fuseclip 9078A67G04
Medium voltage
10E-D–25E-D Non-disconnect 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —
fuses
30E–250E 3.0 (76.2) 14.0 (355.6) 17.9 (454.7)
Single barrel Disconnect †
5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
15E–25E Non-disconnect 5CLE-PNM-C 5CLE-GNM-C CLE-NL-C —
2.0 (50.8) 11.5 (292.1) 12.9 (327.7)
Single barrel Disconnect† 60 5CLE-PDM-C 5CLE-GDM-C CLE-DL-C CLE-DF-C
300E–450E Non-disconnect 5CLE-PNM-E 5CLE-GNM-E CLE-NL-E —
3.0 (76.2) 14.0 (355.6) 17.9 (454.7)
Double barrel Disconnect† 5CLE-PDM-E 5CLE-GDM-E CLE-DL-E CLE-DF-E
600E and 750E Consult factory
Double barrel
1100E and 4.0 (101.6) N/A N/A — — — —
1350E Consult factory —
Four barrel
HLE
10E-D–250E Non-disconnect 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —
Single barrel Disconnect 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D CLE-DF-D
60 3.0 (76.2) 12.0 (304.8) 15.9 (403.9)
300E–450E Non-disconnect 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
Double barrel Disconnect 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E CLE-DF-E
* Including live parts and end fittings, end fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a
disconnect mounting for load switching or fuse removal while energized.
Medium voltage
* For single barrel applications only. Not sold in pairs.
fuses
•• Volts 5.5 kV
•• Amps 10 to 900 A
•• Interrupting ratings 31 to 63 kA RMS Sym.
7.94 (201.7)
7.94 (201.7)
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
0.5 (12.7)
•• E-Rated fuses meet the performance characteristics of ANSI
C37.46
B C
A
10.18
Indicator to be
located here
1.19
3.31
(84.1)
20.0
B C
2.12
(53.8) A
Indicator to be
located here
3.31
(84.1) Note: 1100E and 1350E fuses require two double barrel fuses (4
total barrels) customer to parallel.
3.31
(84.1)
B C
2.12
(53.8) A
Medium voltage
250 5HCL-250E†
fuses
300 5HCL-300E†
400 22.8 (579) 5HCL-400E†
450 2 5HCL-450E†
500 5HCL-500E
600 5HCL-600E
† UL Listed, Guide JEEG, File E240398.
Catalog symbols C
•• 8CLE-_E-D (10-25 A)
B
•• 8CLE-_E (10-350 A)
•• 8HLE-_E (10-350 A)
Ratings*
•• Volts 8.3 kV
3.31
•• Amps 10 to 350 A (84.1)
•• IR 50 kA RMS Sym. B
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
A
Agency information
Medium voltage
HLE
fuses
10E-175E Non-disconnect 8HLE-PNM-D 8HLE-GNM-D CLE-NL-D —
Single barrel Disconnect† 8HLE-PDM-D 8HLE-GDM-D CLE-DL-D CLE-DF-D
75 3.0 (76) 12 (305) 15.9 (404)
200E–350E Non-disconnect 8HLE-PNM-E 8HLE-GNM-E CLE-NL-E —
Double barrel Disconnect† 8HLE-PDM-E 8HLE-GDM-E CLE-DL-E CLE-DF-E
* Including live parts and end fittings, end fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a
disconnect mounting for load switching or fuse removal while energized.
Ratings*
•• Volts 8.3 kV
•• Amps 10 to 350 A
•• Interrupting rating 50 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
B 2.12
(53.8)
0.44 x 0.91
Slots 0.44 (11.2) Dia. Hole A
(11.2 x 23.1) Indicator
C 0.5 (12.7)
B C 0.25
(6.4)
A
4.31 (109.5) 4.31 (109.5)
1.25 1.25
Indicator to be
(31.8) (31.8) B
located here
Medium voltage
3.31
(84.1)
fuses
7.94 (201.7)
7.94 (201.7)
B C
2.12
(53.8) A
0.5 (12.7)
Indicator to be
located here 11.62 (295.1)
11.62 (295.1) 0.38
(9.7)
3.31
(84.1)
Indicator 3.00
3.31
(76.2)
(84.1)
* Flush with surface in untripped position, trip force is 2 lb (0.9kg)
B C
2.12 Data sheet no. 10352
(53.8) A
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries 7-13
7 — Medium voltage fuses
AHLE Type fuses
Special dimension fuses for use with 7.2 kV rated, 800 amp AMPGARD motor starting assemblies.
•• Volts 15.5 kV A
•• Amps 10 to 300 A
•• Interrupting ratings 31.5 to 63 kA RMS Sym.
Dimensions — in (mm)
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number. Recommended fuseclips
Recommended fuse holders * For single barrel applications only. Not sold in pairs.
Catalog no.
Approx. dimensions — in (mm) Mounting* Live parts End fittings
Fuse mounting BIL Glass-polyester (with end (disconnect
Amps type (kV) Diameter Clip center Length Porcelain insulator insulator fittings) only)
CLE
95 15CLE-PNM-C 15CLE-GNM-C CLE-NL-C —
Non-disconnect
15E–25E 110 15CLE-HPNM-C — CLE-NL-C —
2 (51) 21.5 (546)
Single barrel 95 15CLE-PDM-C 15CLE-GDM-C CLE-DL-C CLE-DF-C
Disconnect†
110 15CLE-HPDM-C — CLE-DL-C CLE-DF-C
95 15CLE-PNM-D 15CLE-GNM-D CLE-NL-D —
10E-D–25E-D Non-disconnect 110
20 (508)
15CLE-HPM-D — CLE-NL-D —
30E–150E
Single barrel Disconnect† 95 15CLE-PDM-D 15CLE-GDM-D CLE-DL-D CLE-DF-D
3 (76) 23.9 (607)
110 15CLE-HPDM-D — CLE-DL-D CLE-DF-D
Medium voltage
175E–300E Non-disconnect 110 15CLE-PNM-E — CLE-NL-E —
Double barrel Disconnect† 110 15CLE-PDM-E — CLE-DL-E CLE-DF-E
fuses
HLE
10E-125E Non-disconnect 95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D —
Single barrel Disconnect† 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D
3 (76) 15 (381) 18.9 (480)
150E–250E Non-disconnect 95 15HLE-PNM-E — CLE-NL-E —
Double barrel Disconnect† 95 15HLE-PDM-E — CLE-DL-E CLE-DF-E
LHLE
65E–150E Non-disconnect — CLE-NL-D —
Single barrel Disconnect† — CLE-DL-D CLE-DF-D
3 (76) 18 (457) 20.53 (521) Not available Not available
175E–300E Non-disconnect — CLE-NL-E —
Double barrel Disconnect† — CLE-DL-E CLE-DF-E
* Including live parts and end fittings, end fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a
disconnect mounting for load switching or fuse removal while energized.
Medium voltage
fuses
Ratings*
•• Volts 15.5 kV
•• Amps 10 to 300 A
•• Interrupting ratings 50 to 63 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Dimensions — in (mm)
A X.XX (XX.X)
BHLE HCL
B 2.12
(53.8)
0.44 x 0.91
Slots 0.44 (11.2) Dia. Hole A
(11.2 x 23.1) Indicator
C 0.5 (12.7)
B C 0.25
(6.4)
A
4.31 (109.5) 4.31 (109.5)
1.25 1.25
Indicator to be
(31.8) (31.8) B
located here
3.31
(84.1)
7.94 (201.7)
7.94 (201.7)
B C
2.12
(53.8) A
0.5 (12.7)
Indicator to be
located here
11.62 (295.1) 0.38 11.62 (295.1)
(9.7)
3.31
(84.1)
3.31 Indicator 3.00
(84.1) (76.2)
B C
2.12
(53.8) A
Medium voltage
† UL Listed, Guide JEEG, File E240398.
fuses
Ratings
•• Volts 5.5 - 38 kV
•• Amps 10 - 450 A
•• Interrupting ratings 25 to 65 kA
Agency information
Striker force
•• 50 N (11 lbs)
Recommended fuseclips
Features
Typical applications
Dimensions — in (mm)
1.77 0.59
Diameter
(45) (15)
1.34 1.02
Length
(34) (26)
See catalog numbers tables for diameter and length values.
Medium voltage
25.8 kV
258GDQSJ10E 10
fuses
258GDQSJ15E 15
258GDQSJ20E 20 21.1 (537) 2 (51)
258GDQSJ25E 25
258GDQSJ30E 30
25
258GXQSJ40E 40
258GXQSJ50E 50 21.1 (537) 3.5 (89)
258GXQSJ65E 65
258GXZSJ80E 80
28.3 (718) 3.5 (89)
258GXZSJ100E 100
38 kV
38GFZSJ10E 10
38GFZSJ15E 15
38GFZSJ20E 20 25 28.3 (718) 3 (76)
38GFZSJ25E 25
38GFZSJ30E 30
•• 80 kA Asym.
C
•• File E60757: 5CLS-30, 5CLS-_R [2R-18R], 5ACLS-30, and 2.12
[53.8]
5ACLS-_R [2R-24R]
B
3.0 3.0
[76.2] [76.2] A
Recommended fuseclips and holders for standard
constructions Bolt-on — 5MCLS-_R-A
2 SLOTS (0.38X0.5)
17.7 (striker not extended)
0.25 C 16.5
BIL 0.25
0.25
Medium voltage
3.1
3” Open fuseclip — 1A0065 7.75
30-450A
3” Spring loaded open fuseclip 9078A67G04
fuses
2.25
Fuse holders for CLS / JCL / 5HCLS Ø3.0 (REF)
70-230A 60 7.01
Medium voltage
130 4R 8CLS-4R (325) 8ACLS-4R (325) 7BCLS-4R (325) 1
150 5R 8CLS-5R (390) 8ACLS-5R (390) 7BCLS-5R (390)
fuses
170 6R 8CLS-6R (500) 8ACLS-6R (500) 7BCLS-6R (500)
Catalog symbols (by maximum voltage rating) Recommended fuseclip and block
•• 2.475 kV •• 12 kV Description Catalog no.
•• 2NCLPT-_ •• 12ABCNA_ Open fuseclip for 0.8 (20 mm) dia. fuses 1A1837
Single-pole open fuse block with #10-32 phil-slot
•• 3.6 kV •• 12CAV_ screw terminals rated 2500 V, 5 A maximum and PTFB-2500-JCD
•• 3.6ABCNA_ •• 15.5 kV 63 kA withstand rating
•• 3.6ABWNA_ •• 15CLPT-_E
•• 3.6CAV_ •• 15NCLPT-_E-A
•• 5.5 kV •• 15NCLPT-_E-B
•• JCW-_ •• 15.5CAV_E
•• 5CLPT-_E •• 15.5CAVH_E
•• 5NCLPT-_E •• 17.5 kV
•• 5NCLPT-_E-A •• 17.5ABGNA_
•• 5.5ABWNA_E •• 17.5CAV_
•• 5.5AMWNA_E •• 24 kV
•• 5.5CAV_E •• 24ABGNA_
•• 5.5CAVH_E •• 24CAV_
•• 7.2 kV •• 25.5 kV
•• 7.2ABWNA_ •• 25CLPT-_E
•• 7.2ABCNA_ •• 36 kV
•• 7.2AMWNA_E •• 36ABGNA_
•• 7.2CAV_ •• 36CAV_
•• 8.3 kV •• 38 kV
•• 8CLPT-_E-A •• 38CAV_E
•• 8NCLPT-_E •• 38CAVH_E
•• 8NCLPT-_E-A •• 38CLPT-_E
•• 8NCLPT-_E-B
Ratings*
•• Volts 2.4 kV to 38 kV
•• Amps 0.25 to 15 A
•• Interrupting ratings 25 to 80 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Medium voltage
4 5.6 (142) 0.8 (20) 4.8 (122) — 5.5AMWNA4.0E (50) 1A1837
fuses
5 9.5 (241) 1.6 (41) 8.1 (206) 5CLPT-5E (50) 5NCLPT-5E-A (50) 1A0835
5 1 (25) 4.4 (112) — 5.5ABWNA5E (50) A3354705
5.6 (142)
5 0.8 (20) 4.8 (122) — 5.5AMWNA5.0E (50) 1A1837
5 7.3 (185) 5.9 (150) — JCW-5E (40)
10 9.5 (241) 1.6 (41) 8.1 (206) 5CLPT-10E (50) 5NCLPT-10E (50) 1A0835
15 7.4 (188) 6.2 (157) — 5.5CAV15E (50)
† Due to manufacturing variations, this fuse does not comply with ANSI C37.46 for "E" rating.
Catalog no.
Mounting (including live parts, end fittings)**
Fuse mounting BIL Live parts End fittings
Amps type* (kV) Porcelain insulator Glass-polyester insulator (including end fittings)*** (disconnect only)
5.5 kV maximum (4.8 kV nominal)†
Non-disconnect 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
0.5–10 60
Disconnect ††
5CLPT-PDM-A 5CLPT-GDM-A CLPT-DL CLPT-DF
8.3 kV maximum (7.2 kV nominal)†
Non-disconnect 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
0.5–2
Disconnect†† 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
75
Non-disconnect 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —
3–10
Disconnect†† 8CLPT-PDM-B 8CLPT-GDM-B CLPT-DL CLPT-DF
15.5 kV maximum (14.4 kV nominal)
Medium voltage
Non-disconnect 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL —
0.5–2
fuses
Disconnect†† 15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL CLPT-DF
95
Non-disconnect 15CLPT-PNM-B 15CLPT-GNM-B CLPT-NL CLPT-DF
3–10
Disconnect†† 15CLPT-PDM-B 15CLPT-GDM-B CLPT-DL —
25.5 kV Maximum (23 kV Nominal)
Non-disconnect 25CLPT-PNM-A 25CLPT-NL —
0.5–1 150 —
Disconnect ††
25CLPT-PDM-A 25CLPT-DL CLPT-DF
38 kV Maximum (34.5 kV Nominal)
Disconnect†† Not applicable CLPT-NL CLPT-DF
0.5 N/A Not applicable
Non-disconnect 38CLPT-PNM-A CLPT-DL —
* See page 7-35 for dimensions and diagrams of typical mountings.
** End fittings supplied only when required.
† Refers to 5CLPT, 5NCLPT, 8CLPT and 8NCLPT-A or -B fuses only.
†† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
Ratings*
•• Volts 1-10 kV
•• Amps 1/16-10 A
* See catalog number table for possible volt/amp combinations.
Features
Typical applications
Test specifications
Dimensions — in (mm)
Catalog symbol kV Amps Max. IR (amps) Diameter Length
HVA 1 1/16, 1/10, 1/8, 2/10, 1/4, 3/8, 1/2, 3/4, 1, 1-1/2, 2, 3, 4, 6, 10 20 DC / 30 AC 3 (76)
0.4 (10)
HVB 2.5 1/2, 3/4, 1, 1-1/2, 2, 3 8 DC / 12 AC 4.5 (114)
HVJ 5 1/16, 1/8, 1/4, 1/2, 3/4, 1, 1-1/2, 2, 4, 6* 4 DC / 6 AC 5 (126.9)
0.8 (21)
HVL 10 1/16, 1/8, 1/4, 1/2, 1, 1-1/2, 2, 3* 2 DC / 3 AC 10 (254)
HVR 1 1/2, 1, 2, 3, 4, 5 500 AC 3 (76)
HVW 1.2 1, 2, 3, 4, 5, 8 4 DC / 167 AC 0.4 (10) 2.3 (57)
HVT 2.5 1/2, 1, 2, 3, 5 500 AC 4.5 (114)
HVU 5 1/2, 1, 2, 3, 4, 5 500 AC 5 (127)
0.8 (20)
HVX 10 1/2, 1, 3, 5 1200 AC 10 (254)
* AC only.
Medium voltage
fuses
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries 7-31
7 — Medium voltage fuses
DIN dimensioned IEC fuses for transformer
protection
DIN dimension fuses to Specification DIN 43625 covering current-
limiting fuses with performance in compliance with IEC 60282-1.
These are in accordance with the R10 and, in some cases, the R20 Typical applications
series of preferred numbers.
•• Medium voltage IEC designed equipment
Ratings*
Recommended fuseclips
•• Volts 3.6-36 kV
•• Amps 6.3-100 A •• Catalog numbers 270303, A3354745, see page 7-36.
•• Interrupting ratings 20-50 kA
* See catalog number table for possible volt/amp combinations. Dimensions — in (mm)
Striker -in
Agency information operated position
0.59
Diameter
(15)
•• Compliant with DIN dimensional standard DIN 43625, VDE 0670 1.77
(45)
part 4, VDE 0670 part 40Z and with IEC 60282-1 (2005)
Features
Length 1.34 1.02
(34) (26)
For diameter and length values, see catalog number table.
•• DIN dimensioned for retrofitting in existing hardware
•• Open fuse indicator for ease in troubleshooting
•• Designed for use in IEC equipment
7-32 BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries
Medium voltage fuses — 7
Expulsion fuse links for use in high voltage Typical applications
distribution cut-outs •• Primary side transformer protection
Expulsion fuse links available in •• Feeder protection
a wide range of options from •• Capacitor bank protection
15 to 72 kV in ANSI Type T and
K characteristics. Expulsion Fuse label color coding
fuse link current ratings should
be selected on the basis of Type Color Type Color
maximum expected transient
no-damage currents rather than XA Pink T Green
on full load current. In addition, K Yellow S —
the selection of higher current
ratings will reduce the possibility Dimensions — mm (in)
of supply interruption due to
transient surges such as those A
125 (4.92)
due to lightning strikes.
Double tail
Links should be handled with a reasonable degree of care when Ø10 (0.39)
installing. Excessively rough handling may damage the element.
Universal
It is normal, under certain fault conditions, for arc extinguishing
material and/or metal particles to be expelled from the fuse Button head
assembly. It is therefore recommended that reasonable precautions
be taken to prevent the installation being approached by Ø7.5 (0.29)
unauthorized persons. Ø19 (0.75) Removeable button head
Medium voltage
Features
fuses
•• Wide range of options available from 15 kV to 72 kV in ANSI T and
K characteristics.
•• Extra rapid option also available.
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries 7-33
7 — Medium voltage fuses
FL — Type H, and EEI-NEMA Type K and T fuses Type H (high-surge), K and T universal tin element cutout
fuses rated to 27 kV
Medium voltage fuses: Type H (high surge), EEI-NEMA Type K (fast-
acting), EEI-NEMA Type T (time-delay). Catalog no.
7-34 BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries
Medium voltage fuses — 7
PT fuse mountings — in (mm)
Catalog no. Hole ctrs. A Hole ctrs. B Overall length C Hole Inset D Hole ctrs. E Contact hgt. F Overall hgt. G BIL (kV)
5.5 kV Disconnect†
5CLPT-GDM-A
9.37 (238) 6 (152.4) 18.63 (473.2) 0.75 (19) 1.75 (44.4) 4.5 (114.3) 9.56 (242.8) 60
5CLPT-PDM-A
5.5 kV Non-disconnect
5CLPT-GNM-A
9.37 (238) 6 (152.4) 18.63 (473.2) 0.75 (19) 1.75 (44.4) 4.5 (114.3) 6.94 (176.2) 60
5CLPT-PNM-A
8.3 kV Disconnect†
8CLPT-GDM-A
8CLPT-GDM-B 9.37 (238) 18.63 (473.2)
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 12.06 (306.3) 75
8CLPT-PDM-A
8CLPT-PDM-B 12.74 (323.6) 22 (558.8)
8.3 kV Non-disconnect
8CLPT-GNM-A
9.37 (238) 18.63 (473.2)
8CLPT-PNM-A
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 9.44 (239.8) 75
8CLPT-GNM-B
12.75 (323.8) 22 (558.8)
8CLPT-PNM-B
15.5 kV Disconnect†
15CLPT-GDM-A
12.74 (323.6) 22 (558.8)
15CLPT-PDM-A
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 12.06 (306.3) 95
15CLPT-GDM-B
17.46 (443.5) 26.63 (676.4)
15CLPT-PDM-B
15.5 kV Non-disconnect
15CLPT-GNM-A
12.74 (323.6) 22 (558.8)
15CLPT-PNM-A
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 9.44 (239.8) 95
15CLPT-GNM-B
17.46 (443.5) 26.63 (676.4)
15CLPT-PNM-B
25.5 kV Disconnect†
25CLPT-PDM-A 19.12 (485.6) 7 (177.8) 26.63 (676.4) 0.75 (19) 1.75 (44.4) 12 (304.8) 17.06 (433.3) 150
25.5 kV Non-disconnect
25CLPT-PNM-A 26.63 (676.4) 7 (177.8) 26.63 (676.4) 0.75 (19) 1.75 (44.4) 12 (304.8) 14.75 (374.6) 150
† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
E E
Medium voltage
fuses
A C A C
E E
D B
D B
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries 7-35
7 — Medium voltage fuses
Recommended fuseclips
Figure 1 Figure 2
ØC
A
D
B
26.5
6.5
Figure 3 Figure 4
7-36 BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018 Eaton.com/bussmannseries