BY-CX Series

Zamil Central Air Conditioners Co. (L.L.C.), established in 1974, is a leading manufacturer of air conditioning systems in the Middle East, with operations in over 55 countries. The company produces a wide range of air conditioning units, including consumer and industrial models, and has received multiple quality certifications. Their air handling units feature high energy efficiency, customizable options, and advanced microprocessor controls for optimal performance.

Uploaded by

Mohamed Rehan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views41 pages

BY-CX Series

Zamil Central Air Conditioners Co. (L.L.C.), established in 1974, is a leading manufacturer of air conditioning systems in the Middle East, with operations in over 55 countries. The company produces a wide range of air conditioning units, including consumer and industrial models, and has received multiple quality certifications. Their air handling units feature high energy efficiency, customizable options, and advanced microprocessor controls for optimal performance.

Uploaded by

Mohamed Rehan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 41

Air Handling Units

Direct Expansion
BY Series
(Matching with CX series Condensing units)
BY03 thru BY25
2.5 TR thru 30 TR
9 kW thru 105 kW
Company Business
Zamil Central Air Conditioners Co. (L.L.C.) was founded in 1974 as one of the first air conditioning companies to be established in Saudi
Arabia and today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.

Zamil Central Air Conditioners Co. (L.L.C.) manufactures both consumer and central air conditioners and has sales operations
in over 55 countries in the Middle East, Europe, Africa and Asia.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:


1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance, retrofit
& operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operations from
the corporate headquarters in Dammam, Saudi Arabia.

Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.

Factories and Productions


Zamil Central Air Conditioners Co. (L.L.C.) has two manufacturing plants in Dammam, Saudi Arabia and has one specialty
production facility in Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.

Quality & Product Certificates


The Quality systems and policies at Zamil Central Air Conditioners Co. (L.L.C.) comply with the required ISO 9001:2008 certification.

Zamil Central Air Conditioners Co. (L.L.C.) is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard
Organization) Certificate for Room Air Conditioners. Zamil Central Air Conditioners Co. (L.L.C.) products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (for Fan coil Units & Air Handling Units, see www.eurovent-certification.com)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.

Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Central Air Conditioners
Co. (L.L.C.) manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the
Concealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin Air
Handling Units up to 138,316 CFM and the Water Chillers up to 600 TR cooling capacity. In addition, centrifugal chillers -
powered by MHI compressors - are available up to 5,000 TR.
INDEX
Contents Page

Outstanding features ................................................................................................................................. 2

Model decoding ......................................................................................................................................... 3

Blower drive options .................................................................................................................................. 4

Standard specifications .......................................................................................................................... 4-5

Options and accessories ........................................................................................................................ 5-6

Physical data ............................................................................................................................................ 7

Cooling capacities ................................................................................................................................ 8-15

Fan performance data .........................................................................................................................16-17

Electrical data ..................................................................................................................................... 18-20

Dimensions, indoor units ..................................................................................................................... 21-24

Dimensions, optional items ................................................................................................................. 25-26

Dimensions, heater box .......................................................................................................................... 27

Dimensions, outdoor units ................................................................................................................... 28-32

Typical schematic wiring diagram ....................................................................................................... 33-36

Controls and sequence of operation ........................................................................................................ 37

Installation instructions ........................................................................................................................... 38

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
OUTSTANDING FEATURES
* HIGH EER (ENERGY EFFICIENCY RATIO)
* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS
* LOW CEILING HEIGHT REQUIREMENTS
* MICROPROCESSOR BASED CONTROLS
* ONE SIDE TOTAL SERVICE ACCESSIBILITY
* SINGLE POINT POWER ENTRY
* UV FLOW™ LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)
* NUMBERED CODED WIRES
* INSULATED DRAIN PAN
* FACTORY INSTALLED OPTIONS UPON REQUEST
* SMALL FOOTPRINT
* LIGHT WEIGHT
* PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION
* LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION
* STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION
* ALUMINUM OR SYNTHETIC FILTERS
* UL LISTED MAJOR COMPONENTS

2
MODEL DECODING
MODELS: BY03 - BY05
1& 2 3&4 5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL REFRIGERATION MODE BLOWER DRIVE HEATER EVAPORATOR FILTER OTHER OPTIONS THERMOSTAT
(SQ. FT.) SUPPLY CIRCUIT MOTOR OPTIONS COIL OPTION
OPTIONS
(V-Ph-Hz) (kW/STAGE)

BY 03 H : HORIZONTAL C : 208/230-1-60 S : SINGLE C : COOL ONLY U : 0.5 HP ODP N : DIRECT N : NO HEATER A : ALUMINUM N : NO FILTER N : NO OPTION S : UNIT WITH
DRIVE FIN THERMOSTAT
AIR
V : VERTICAL H : 208/230-3-60 W : 0.75 HP ODP A : 5/1 E : 1/2" ALUMINUM V : VOLT FREE
HANDLING CONTACTS* D : UNIT WITHOUT
UNIT B : COATED
THERMOSTAT
05 M : 380-3-60 W : 0.75 HP ODP B : 6/1 ALUMINUM F : 1/2" SYNTHETIC
(4 WIRE) FIN
Y : 1 HP ODP C : 7.5 /1** A : 1" ALUMINUM
F : 460-3-60 C : COPPER FIN
C : 1" SYNTHETIC

NOTES: * – Blower motor RUN & TRIP indication.


** – Heater capacity will be 7kW for single phase power supply.

MODELS: BY07 - BY25


1& 2 3&4 5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL REFRIGERATION MODE BLOWER DRIVE HEATER EVAPORATOR FILTER OTHER OPTIONS THERMOSTAT
(SQ. FT.) SUPPLY CIRCUIT MOTOR OPTIONS COIL
OPTIONS OPTION
(V-Ph-Hz) (kW/STAGE)

3
BY 07 H : HORIZONTAL H : 208/230-3-60 FOR BY07 - BY14 C : COOL ONLY FOR BY07 FOR BY07 -BY14 A : ALUMINUM FOR BY07 N : NO OPTION S : UNIT WITH
J : ALT. I
AIR FIN N : NO FILTER THERMOSTAT
S : SINGLE D : 2 HP ODP N : NO HEATER
V : VERTICAL M : 380-3-60 K : ALT. II E : 1/2" ALUMINUM V : VOLT FREE
HANDLING E : 3 HP ODP A : 5/1 F : 1/2" SYNTHETIC CONTACTS* D : UNIT WITHOUT
UNIT (4 WIRE) D : DUAL B : 6/1 B : COATED
A : 1" ALUMINUM THERMOSTAT
C : 7.5 /1 ALUMINUM
10 FOR BY10 C : 1" SYNTHETIC
F : 460-3-60 D : 10 /2 FIN
D : 2 HP ODP
E : 12/2 FOR BY10, 14 & 18
E : 3 HP ODP C : COPPER FIN
F : 15 /2 N : NO FILTER
G : 20 /2
FOR BY14/18 A : 1" ALUMINUM
14 H : 25/2
B : 2" ALUMINUM
G : 5 HP ODP J : 30/2
C : 1" SYNTHETIC
J : 7.5 HP ODP FOR BY18 -BY25
FOR BY18 - BY25 D : 2"SYNTHETIC
18 N : NO HEATER
D : DUAL
E : 12/2
FOR BY25 F : 15 /2 FOR BY25
25 G : 20 /2
J : 7.5 HP ODP N : NO FILTER
H : 25/2
L : 10 HP ODP J : 30/2 B : 2" ALUMINUM
K : 35/2 D : 2"SYNTHETIC
L : 40/2

NOTE: * –Blower motor RUN & TRIP indication.


BLOWER DRIVE OPTIONS
MOTOR BLOWER APPROX. SPEED
MODEL CHANGE PER
OPTION PULLEY SPEED RANGE (RPM) PULLEY PULLEY
NUMBER PITCH DIA. PITCH DIA.
HP RPM TURN (RPM)
(INCH) MINIMUM MAXIMUM (INCH)
ALT. I 2 1750 2.7 - 3.7 893 1156 5.6 62
BY07
ALT. II 3 1750 2.7 - 3.7 964 1321 4.9 71
BY10 ALT. I 2 1750 3.1 - 4.1 733 970 7.4 40
ALT. II 3 1750 3.1 - 4.1 875 1157 6.2 47
ALT. I 5 1750 3.7 - 4.7 809 1028 8.0 37
BY14
ALT. II 7.5 1750 4.3 - 5.5 940 1203 8.0 44
ALT. I 5 1750 3.7 - 4.7 809 1028 8.0 37
BY18
ALT. II 7.5 1750 4.3 - 5.5 875 1120 8.6 40
ALT. I 7.5 1750 4.3 - 5.5 685 880 11 38
BY25
ALT. II 10 1750 4.3 - 5.5 800 1023 9.4 44

STANDARD SPECIFICATIONS
A. General
These Zamil Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with
blower motor, DX coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applications.
The unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts or
plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-
ments.

B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation from
forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and
errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conform-
ing to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. Coils
Coils are of the enhanced louvered fin-and-tube type, constructed of copper tubes, mechanically bonded to aluminum
fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided. End plates and tube support
sheets are 18 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory at
not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain Pans
Drain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection. Drain outlets of 3/4" NPT is provided for field connection.

E. Evaporator Fan
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor
(except for BY03 & BY05, which have direct drive motors) is mounted on an adjustable base and secured by a locking
device. Fan drive is through adjustable motor pitch pulley and belt-driven. Fan shafts are designed to operate at less than
2/3rds of the first critical speed when the unit comes up to rated revolutions per minute (RPM). Units have sealed,
permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing during final
assembly. Fan motors are of the open drip-proof type (totally enclosed types are optional) and conform to NEMA MG-
1 & MG-2. Motor starters are magnetic contactor, across-the-line type.

4
F. Microprocessor controller
These Air handling units are provided with a microprocessor control board incorporating the following features:
• BALANCE LOADING OF COMPRESSORS: The unit’s electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compres-
sor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable through
dip switch setting on control board).
• PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoid’s opening and compressor starting to equalize the pressure in the system necessary for compressor to start-
up. (Selectable through dip switch setting on control board).
• COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermo-
stat due to load demand.
• COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system condi-
tions.
• FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.
• DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.
• SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequen-
tial order: supply fan – condenser fan – compressor; at a pre-determined timings.

G. Control Panel
A complete factory-wired control panel is provided to ensure safe and proper operation.

OPTIONS AND ACCESSORIES


A. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switches
are provided to shut-off power to heaters in case of airflow failure.

B. Filters
Filters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum
type (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units.

C. Discharge Air Plenum & Return Air Grille


As an accessory, discharge air plenum with return air grilles can be provided on vertical units.

D. UV Flow™ Light Emitters


The damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The
UV flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth
of these microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow™.
To order the UV flow™ use the kit numbers in the table below:

MODEL NUMBER BY03 BY05 BY07 BY10 BY14 BY18 BY25

KIT PART NUMBER 700-391-16 700-391-17 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22

5
F. Electronic Thermostats
General information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermo-
stat normally displays room temperature and mode of operation.

The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to
select continuous fan operation, or have the fan on intermittent operation with the equipment.

The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and
should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/
diffusers.

The recommended wire length between the controller and the thermostat should not be more than 50 meters.

• Single/dual stage - Cooling & heating.


• Low voltage control - 24 VAC (nominal).
• Room temperature display - in C or F.
0 0

• Mode of operation - FAN/COOL/HEAT/AUTO.


• Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
• Heating & cooling setpoint is permissible.
• Temperature set button - Up for increasing & down for decreasing temperature.
• Built-in compressor fault & clogged filter indication led lights.
• Remote sensing function as an option. Duct sensor is provided with the thermostat.
TYPICAL THERMOSTAT
Heating Cooling Selector Switch Positions
Part No.
Stages Stages Mode Switch Fan Switch

800-652-61 1&2 1&2 OFF-HEAT/COOL ON - AUTO

G. Anti-Corrosive Coating
Special ResisTec Anti-Corrosive Coating can be applied as an optional item on coils or panels upon order.

6
PHYSICAL DATA
MODEL NUMBER BY03 BY05 BY07 BY10 BY14 BY18 BY25

EVAPORATOR BLOWER Type Centrifugal

Nominal airflow CFM (L/S) 1200 (566) 2000 (944) 2800 (1321) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)

Motor HP (Std/Alt) 0.5/0.75 0.75/1 2/3 3/2 5/7.5 5/7.5 7.5/10

Drive type Direct Direct Belt Belt Belt Belt Belt

Blower size 10x10 10x10 12x12 15x15 15x15 15x12 18x18

Quantity 1 1 1 1 1 2 2

EVAPORATOR COIL Type Corrugated Fin & Tube

Tube dia. - Rows - FPI 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14

Face area, Sq. ft. (Sq. m.) 3.2 (0.3) 4.6 (0.43) 7 (0.65) 10 (0.93) 14 (1.3) 17.4 (1.62) 25 (2.32)

REFRIGERANT LINES Suction line size O.D. (inch) 7/8 7/8 1-1/8 1-3/8 1-3/8 - -
SINGLE COMPRESSOR
Liquid line size O.D. (inch) 3/8 3/8 5/8 5/8 5/8 - -

REFRIGERANT LINES Suction line size O.D. (inch) - - 7/8 7/8 1-1/8 1-3/8 1-3/8
DUAL COMPRESSOR
Liquid line size O.D. (inch) - - 1/2 1/2 5/8 5/8 7/8

RETURN AIR FILTER Size (inch) 24 x 20 x 1/2 16 x 20 x 1/2 20 x 20 x 1/2 18 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 2

Quantity 1 1 3 3 3 3 3

SHIPPING WEIGHT kg. (approx.) 80 120 165 225 300 340 420

7
COOLING CAPACITIES
(Single compressor units)
BY03 INDOOR UNIT WITH CX030 OUTDOOR UNIT BY03 INDOOR UNIT WITH CX036 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR EVAPORATOR AIRFLOW, CFM/DR
CONDENSER CONDENSER 1230/0.138
1045/0.117
ENTERING AIR ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (0F) EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F) TEMP. (0F)
62 67 72 62 67 72
TC 30.42 33.25 36.30 TC 37.57 40.90 44.43
85 SC 27.36 22.62 17.82 85 SC 35.55 29.51 23.35
kW 3.42 3.57 3.71 kW 4.05 4.26 4.46
TC 28.82 31.58 34.55 TC 35.59 38.82 42.25
95 SC 26.95 22.34 17.51 95 SC 34.63 28.64 22.54
kW 3.58 3.75 3.92 kW 4.31 4.55 4.78
TC 26.82 29.49 32.34 TC 33.34 36.42 39.71
105 SC 25.25 21.75 16.92 105 SC 32.67 27.68 21.63
kW 3.84 4.04 4.24 kW 4.56 4.81 5.08
TC 25.13 27.64 30.31 TC 31.19 34.13 37.27
115 SC 23.75 21.17 16.32 115 SC 30.57 26.80 20.79
kW 4.0 4.22 4.44 kW 4.73 5.0 5.3
TC 23.50 25.87 28.47 TC 29.05 31.78 34.78
125 SC 22.17 20.49 15.71 125 SC 28.47 25.89 19.94
kW 4.18 4.41 4.66 kW 4.94 5.24 5.56

BY05 INDOOR UNIT WITH CX048 OUTDOOR UNIT BY05 INDOOR UNIT WITH CX060 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR EVAPORATOR AIRFLOW, CFM/DR
CONDENSER CONDENSER 2000/0.153
1680/0.130
ENTERING AIR ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (0F) EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F) TEMP. (0F)
62 67 72 62 67 72
TC 46.12 50.69 55.61 TC 58.04 63.40 69.17
85 SC 43.86 36.24 28.49 85 SC 57.51 47.65 37.66
kW 4.65 4.83 4.99 kW 6.09 6.36 6.61
TC 43.85 48.29 53.08 TC 54.80 60.01 65.54
95 SC 41.76 35.42 27.69 95 SC 53.71 46.46 36.47
kW 4.86 5.07 5.28 kW 6.48 6.8 7.11
TC 40.85 45.08 49.68 TC 50.87 55.74 61.04
105 SC 39.06 34.38 26.69 105 SC 49.85 44.65 34.79
kW 5.11 5.36 5.6 kW 6.77 7.11 7.47
TC 38.21 42.24 46.63 TC 47.64 52.27 57.33
115 SC 36.56 33.40 25.73 115 SC 46.68 43.26 33.46
kW 5.34 5.6 5.88 kW 7.03 7.41 7.81
TC 35.65 39.48 43.67 TC 44.75 49.22 54.04
125 SC 34.11 32.41 24.78 125 SC 43.86 42.22 32.42
kW 5.54 5.84 6.14 kW 7.37 7.79 8.25

MULTIPLIERS FOR HIGHER/LOWER CFM


MODEL No.: BY03
% of rated airflow 70% 80% 90% 100% 110% 120%

TC 0.94 0.96 0.98 1 1.015 1.03


SC 0.82 0.88 0.94 1 1.05 1.1
kW 0.94 0.96 0.98 1 1.017 1.035

MODEL No.: BY05


% of rated airflow 80% 90% 100% 110% 120%
TC 0.965 0.985 1 1.015 1.03
SC 0.89 0.945 1 1.05 1.1

kW 0.975 0.987 1 1.012 1.025

TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input 0


DBE – Dry Bulb Temp. ( F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.15 ESP.

8
COOLING CAPACITIES
(Single compressor units)
BY07 INDOOR UNIT WITH CX075 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 1900/0.102 2400/0.126 2900/0.148
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 67.89 74.05 80.67 71.22 77.83 84.83 73.67 80.46 87.88
85 SC 58.18 48.86 39.38 66.25 54.91 43.33 71.22 60.41 46.94
kW 6.98 7.35 7.7 7.34 7.69 8.07 7.9 8.25 8.64
TC 65.32 71.33 77.72 68.39 74.81 81.72 70.64 77.32 84.50
95 SC 57.12 47.83 38.35 65.13 53.80 42.32 68.34 59.32 45.85
kW 7.42 7.81 8.21 7.78 8.17 8.58 8.34 8.73 9.16
TC 62.26 68.04 74.36 65.15 71.27 78.00 67.10 73.67 80.63
105 SC 55.93 46.64 37.27 63.18 52.59 41.16 65.07 58.15 44.69
kW 7.91 8.34 8.78 8.27 8.7 9.18 8.84 9.28 9.77
TC 59.28 64.83 70.84 61.91 67.84 74.28 63.81 70.03 76.75
115 SC 54.79 45.51 36.13 60.19 51.45 40.02 62.04 56.97 43.56
kW 8.45 8.92 9.42 8.82 9.29 9.82 9.39 9.88 10.43
TC 56.05 61.37 67.07 58.56 64.09 70.24 60.27 66.13 72.63
125 SC 53.55 44.32 34.93 57.10 50.20 38.79 58.77 55.71 42.37
kW 9.03 9.55 10.1 9.42 9.93 10.52 9.99 10.52 11.14

BY07 INDOOR UNIT WITH CX090 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2250/0.118 2800/0.144 3350/0.168
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 76.47 83.50 90.97 79.79 87.16 94.98 82.18 89.75 98.05
85 SC 65.81 55.14 44.24 74.21 61.35 48.26 78.58 66.98 51.96
kW 7.97 8.39 8.81 8.58 8.99 9.41 9.13 9.54 9.98
TC 73.04 79.79 86.99 76.01 83.15 90.76 78.24 85.69 93.57
95 SC 64.56 53.87 42.98 72.85 60.03 46.99 75.03 65.75 50.65
kW 8.45 8.9 9.35 9.06 9.5 9.98 9.62 10.06 10.55
TC 67.55 73.84 80.59 70.27 76.84 84.12 72.25 79.15 86.64
105 SC 61.66 51.10 40.39 66.76 57.15 44.40 68.64 62.80 47.98
kW 8.66 9.13 9.61 9.27 9.73 10.24 9.82 10.3 10.82
TC 62.84 68.77 75.06 65.27 71.50 78.33 67.15 73.63 80.72
115 SC 59.52 49.07 38.43 61.82 55.08 42.41 63.59 60.72 46.02
kW 9.11 9.61 10.14 9.72 10.22 10.77 10.27 10.79 11.36
TC 58.43 63.89 69.83 60.64 66.40 72.78 62.33 68.40 74.94
125 SC 55.37 47.30 36.73 57.46 53.30 40.67 59.06 58.97 44.25
kW 9.53 10.05 10.62 10.14 10.67 11.27 10.7 11.25 11.87

BY10 INDOOR UNIT WITH CX100 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2800/0.05 3400/0.066 4000/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 91.75 101.12 111.16 95.56 105.54 116.36 98.47 108.90 120.17
85 SC 85.49 71.22 56.66 91.80 79.36 62.08 94.60 87.13 67.08
kW 9.69 10.09 10.51 9.98 10.38 10.83 10.41 10.81 11.29
TC 86.62 95.77 105.72 90.22 99.94 110.50 92.90 103.01 114.14
95 SC 84.18 69.95 55.41 87.68 78.17 60.81 90.28 85.95 65.89
kW 10.33 10.81 11.34 10.64 11.13 11.7 11.08 11.57 12.18
TC 81.99 90.80 100.41 85.33 94.63 104.93 87.67 97.46 108.28
105 SC 81.55 69.64 54.83 84.88 77.98 60.34 87.20 85.89 65.48
kW 10.78 11.32 11.93 11.1 11.67 12.33 11.54 12.13 12.84
TC 77.72 86.18 95.47 80.74 89.77 99.66 82.96 92.43 102.76
115 SC 77.44 67.95 53.19 80.45 76.26 58.65 82.66 84.18 63.75
kW 11.25 11.85 12.54 11.58 12.21 12.96 12.04 12.68 13.48
TC 72.47 80.48 89.19 75.26 83.72 93.06 77.39 86.18 96.03
125 SC 72.40 65.96 51.15 75.18 74.21 56.58 77.31 82.14 61.75
kW 11.52 12.17 12.92 11.86 12.55 13.36 12.32 13.03 13.9
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

9
COOLING CAPACITIES
(Single compressor units)
BY10 INDOOR UNIT WITH CX120 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 3200/0.059 4000/0.076 4800/0.092
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 106.95 118.06 129.79 111.72 123.64 136.21 115.24 127.56 140.69
85 SC 97.88 81.82 65.34 107.05 92.32 72.23 110.42 102.11 78.52
kW 11.01 11.66 12.33 11.63 12.28 12.98 12.37 13.02 13.75
TC 101.23 111.82 123.17 105.80 117.05 129.14 108.97 120.69 133.45
95 SC 95.51 79.44 63.08 101.43 89.92 69.92 104.48 99.68 76.26
kW 11.51 12.21 12.94 12.13 12.84 13.61 12.88 13.59 14.39
TC 95.37 105.57 116.41 99.69 110.46 121.90 102.69 113.83 126.00
105 SC 91.66 77.26 60.91 95.82 87.73 67.68 98.70 97.48 74.07
kW 11.96 12.71 13.49 12.6 13.35 14.19 13.35 14.12 14.98
TC 89.38 98.91 109.24 93.25 103.53 114.48 96.00 106.75 118.14
115 SC 86.00 74.80 58.54 89.73 85.31 65.37 92.38 95.15 71.65
kW 12.38 13.18 14.02 13.03 13.83 14.72 13.78 14.61 15.54
TC 83.10 92.12 101.79 86.62 96.24 106.55 89.10 99.26 109.86
125 SC 80.09 72.42 56.14 83.48 82.81 62.90 85.87 92.68 69.13
kW 12.77 13.61 14.51 13.42 14.28 15.24 14.18 15.06 16.05

BY10 INDOOR UNIT WITH CX150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.076 4600/0.088 5000/0.095
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 130.02 142.54 156.21 133.29 146.38 160.80 135.29 148.70 163.15
85 SC 114.45 95.14 75.62 122.16 102.29 80.37 123.99 107.02 83.29
kW 13.72 14.37 15.06 14.27 14.92 15.62 14.67 15.32 16.05
TC 123.92 136.30 149.83 127.28 139.99 154.06 128.98 141.98 156.47
95 SC 111.86 92.79 73.48 116.60 99.99 78.16 118.16 104.56 81.17
kW 14.65 15.39 16.21 15.19 15.95 16.8 15.6 16.36 17.23
TC 117.82 129.71 142.76 120.66 133.21 146.72 122.44 135.04 149.14
105 SC 108.04 90.49 71.23 110.65 97.71 75.89 112.28 102.26 78.97
kW 15.65 16.5 17.45 16.21 17.08 18.08 16.63 17.51 18.52
TC 110.68 122.08 134.66 113.45 125.24 138.40 115.03 127.02 140.52
115 SC 101.47 87.73 68.62 104.01 94.86 73.29 105.46 99.47 76.28
kW 16.74 17.7 18.79 17.32 18.3 19.44 17.73 18.73 19.89
TC 103.36 114.10 126.03 105.83 117.06 129.47 107.19 118.57 131.25
125 SC 94.76 84.93 65.88 97.03 92.08 70.52 98.27 96.57 73.40
kW 17.85 18.93 20.16 18.43 19.54 20.83 18.86 19.99 21.3

BY14 INDOOR UNIT WITH CX150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.050 4800/0.062 5800/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 140.31 154.16 169.31 145.78 160.44 176.69 150.62 166.21 183.50
85 SC 122.35 102.38 82.14 135.93 112.88 89.15 140.44 125.29 97.27
kW 14.42 15.11 15.88 15.05 15.75 16.57 16.03 16.77 17.65
TC 133.33 147.05 161.90 138.46 152.95 168.83 143.04 158.16 175.00
95 SC 119.56 99.83 79.72 129.30 110.33 86.69 133.58 122.59 94.67
kW 15.3 16.1 17.02 15.95 16.78 17.77 16.96 17.83 18.89
TC 125.84 138.90 153.28 130.51 144.42 159.72 134.70 149.36 165.75
105 SC 116.35 96.63 76.70 121.75 107.09 83.60 125.66 119.40 91.69
kW 16.23 17.15 18.21 16.9 17.85 18.99 17.92 18.93 20.14
TC 118.17 130.58 144.31 122.35 135.68 150.21 126.36 140.31 155.75
115 SC 110.48 93.76 73.87 114.39 104.21 80.70 118.14 116.56 88.74
kW 17.2 18.23 19.42 17.89 18.96 20.25 18.93 20.07 21.44
TC 109.46 121.21 134.14 113.36 125.90 139.66 116.76 130.00 144.50
125 SC 102.42 90.43 70.59 106.07 100.86 77.44 109.25 113.08 85.30
kW 18.17 19.31 20.66 18.88 20.08 21.52 19.94 21.2 22.74

TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

10
COOLING CAPACITIES
(Dual compressor units)
BY07 INDOOR UNIT WITH CX075 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 1900/0.102 2400/0.126 2900/0.148
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 69.05 75.04 81.49 72.47 78.76 85.55 74.93 81.47 88.50
85 SC 57.49 48.24 38.86 65.41 54.10 42.68 70.94 59.52 46.15
kW 6.6 6.93 7.24 6.95 7.27 7.59 7.51 7.82 8.15
TC 66.07 71.99 78.21 69.33 75.54 82.14 71.52 78.07 85.00
95 SC 56.31 47.15 37.77 64.27 53.02 41.61 67.83 58.43 45.12
kW 7.0 7.37 7.73 7.36 7.72 8.09 7.92 8.27 8.66
TC 61.26 66.88 72.81 64.21 70.13 76.45 66.21 72.42 79.00
105 SC 54.39 45.28 35.98 61.04 51.15 39.83 62.94 56.54 43.29
kW 7.49 7.9 8.32 7.86 8.26 8.7 8.43 8.83 9.28
TC 57.46 62.77 68.47 60.13 65.76 71.90 62.04 67.89 74.25
115 SC 52.91 43.80 34.58 57.28 49.64 38.44 59.10 55.03 41.88
kW 7.88 8.32 8.77 8.25 8.69 9.17 8.82 9.27 9.76
TC 53.32 58.40 63.80 55.84 61.18 66.93 57.62 63.11 69.13
125 SC 50.86 42.24 33.07 53.27 48.09 36.89 54.97 53.45 40.34
kW 8.28 8.76 9.25 8.66 9.14 9.66 9.24 9.72 10.28

BY07 INDOOR UNIT WITH CX090 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2250/0.118 2800/0.144 3350/0.168
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 80.29 88.08 96.40 84.06 92.25 101.14 86.85 95.42 104.69
85 SC 68.17 57.52 46.62 76.74 63.88 50.84 83.89 69.74 54.66
kW 8.03 8.43 8.79 8.63 9.01 9.36 9.18 9.54 9.89
TC 75.98 83.50 91.55 79.42 87.40 95.95 82.03 90.33 99.34
95 SC 66.47 55.86 45.02 75.00 62.23 49.21 79.46 68.09 53.06
kW 8.65 9.09 9.51 9.25 9.68 10.09 9.81 10.23 10.64
TC 69.61 76.57 84.18 72.71 80.12 88.10 75.03 82.78 91.11
105 SC 63.21 52.72 42.11 69.88 59.03 46.21 72.10 64.83 49.97
kW 8.93 9.39 9.85 9.53 9.99 10.45 10.09 10.55 11.01
TC 64.31 70.82 77.88 67.10 74.05 81.59 69.19 76.39 84.33
115 SC 60.71 50.31 39.75 64.17 56.55 43.87 66.16 62.23 47.59
kW 9.38 9.89 10.39 10 10.5 11.02 10.57 11.07 11.59
TC 59.41 65.55 72.16 61.98 68.46 75.55 63.93 70.73 77.97
125 SC 56.95 48.48 37.94 59.41 54.68 42.03 61.28 60.45 45.69
kW 9.87 10.43 10.99 10.5 11.05 11.63 11.07 11.63 12.21

BY10 INDOOR UNIT WITH CX100 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2800/0.05 3400/0.066 4000/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 93.82 103.66 114.41 97.93 108.49 120.03 100.92 112.02 124.14
85 SC 86.39 72.19 57.80 94.06 80.46 63.31 96.93 88.23 68.38
kW 9.48 9.99 10.54 9.82 10.34 10.93 10.26 10.8 11.43
TC 87.97 97.60 108.02 91.70 102.00 113.14 94.47 105.26 117.07
95 SC 84.01 69.97 55.66 88.23 78.16 61.08 90.89 85.89 66.19
kW 10.15 10.73 11.37 10.5 11.09 11.77 10.96 11.57 12.3
TC 82.35 91.53 101.50 85.78 95.66 106.40 88.37 98.67 110.00
105 SC 79.53 67.89 53.60 82.84 76.11 59.08 85.34 83.84 64.15
kW 10.69 11.32 12.03 11.04 11.7 12.46 11.51 12.19 12.99
TC 76.98 85.70 95.22 80.15 89.47 99.66 82.61 92.25 103.10
115 SC 74.49 65.83 51.57 77.56 73.97 56.95 79.94 81.68 62.06
kW 11.18 11.85 12.62 11.53 12.25 13.08 12.01 12.75 13.63
TC 71.49 79.87 88.83 74.52 83.28 93.06 76.69 86.01 96.21
125 SC 69.23 63.72 49.45 72.16 71.76 54.86 74.26 79.61 59.92
kW 11.28 11.99 12.8 11.65 12.39 13.25 12.12 12.89 13.82
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC= 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

11
COOLING CAPACITIES
(Dual compressor units)
BY10 INDOOR UNIT WITH CX120 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 3200/0.059 4000/0.076 4800/0.092
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 111.55 122.64 134.62 116.78 128.50 141.38 120.47 132.76 146.48
85 SC 97.65 81.75 65.57 109.41 92.00 72.32 112.87 101.65 78.66
kW 11.71 12.34 12.99 12.32 12.95 13.64 13.05 13.69 14.41
TC 105.13 115.70 127.17 109.98 121.21 133.62 113.36 125.27 138.21
95 SC 95.16 79.27 63.14 103.26 89.55 69.94 106.44 99.28 76.18
kW 12.39 13.09 13.82 13.02 13.72 14.51 13.75 14.48 15.3
TC 98.86 108.90 119.86 103.36 114.10 125.86 106.46 117.78 130.14
105 SC 92.68 76.82 60.76 97.21 87.14 67.53 100.13 96.79 73.77
kW 12.95 13.72 14.54 13.6 14.38 15.26 14.34 15.15 16.07
TC 93.00 102.52 112.97 97.08 107.34 118.45 99.97 110.71 122.48
115 SC 87.66 74.61 58.58 91.51 84.91 65.27 94.23 94.52 71.52
kW 13.44 14.27 15.17 14.09 14.94 15.91 14.85 15.73 16.74
TC 86.87 95.72 105.52 90.63 100.23 110.69 93.28 103.21 114.41
125 SC 82.11 72.32 56.26 85.67 82.66 63.00 88.18 92.18 69.24
kW 14.03 14.94 15.92 14.7 15.63 16.69 15.47 16.43 17.55

BY10 INDOOR UNIT WITH CX150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.076 4600/0.088 5000/0.095
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 128.45 140.46 153.45 131.69 144.18 157.63 133.55 146.10 159.91
85 SC 115.13 95.48 75.58 122.08 102.74 80.25 123.81 107.29 83.21
kW 14.33 15.09 15.92 14.89 15.66 16.52 15.3 16.08 16.95
TC 122.88 134.74 147.41 126.07 138.20 151.48 127.67 140.03 153.66
95 SC 112.82 93.40 73.59 116.93 100.61 78.31 118.41 105.18 81.28
kW 15.24 16.07 17.01 15.8 16.66 17.63 16.21 17.08 18.08
TC 117.12 128.32 140.69 119.86 131.62 144.34 121.35 133.53 146.55
105 SC 108.58 90.98 71.35 111.12 98.21 75.96 112.50 102.92 79.01
kW 16.25 17.17 18.22 16.82 17.77 18.87 17.24 18.21 19.33
TC 111.20 121.91 133.62 113.65 124.84 137.21 115.25 126.59 139.22
115 SC 103.19 88.76 69.10 105.46 95.87 73.80 106.95 100.55 76.81
kW 17.36 18.38 19.55 17.95 18.99 20.22 18.37 19.43 20.7
TC 104.92 115.14 126.38 107.43 118.06 129.67 108.71 119.65 131.47
125 SC 97.31 86.27 66.74 99.64 93.51 71.39 100.83 98.16 74.33
kW 18.59 19.71 21.03 19.19 20.34 21.71 19.62 20.79 22.2

BY14 INDOOR UNIT WITH CX150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.05 4800/0.062 5800/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 136.99 150.00 164.31 142.22 155.86 171.10 146.83 161.43 177.25
85 SC 121.60 101.32 80.87 133.34 111.79 87.77 137.67 124.34 95.76
kW 14.53 15.32 16.22 15.19 16.01 16.97 16.2 17.07 18.09
TC 130.54 143.24 157.07 135.32 148.79 163.45 139.50 153.63 169.25
95 SC 119.01 98.84 78.43 126.96 109.33 85.30 130.88 121.59 93.28
kW 15.44 16.32 17.34 16.11 17.03 18.13 17.13 18.11 19.29
TC 124.10 136.30 149.66 128.42 141.50 155.59 132.43 146.09 161.25
105 SC 116.46 96.34 76.01 120.63 106.82 82.82 124.40 119.11 90.91
kW 16.45 17.42 18.57 17.13 18.15 19.4 18.17 19.26 20.59
TC 117.65 129.36 142.07 121.73 134.01 147.72 125.35 138.29 152.75
115 SC 110.56 93.81 73.49 114.39 104.11 80.33 117.80 116.38 88.23
kW 17.56 18.64 19.92 18.26 19.39 20.78 19.31 20.52 22
TC 110.85 122.08 134.14 114.61 126.31 139.45 118.02 130.50 144.00
125 SC 104.28 91.25 70.95 107.82 101.46 77.78 111.02 113.91 85.59
kW 18.78 19.98 21.4 19.5 20.76 22.3 20.57 21.91 23.55
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

12
COOLING CAPACITIES
(Dual compressor units)
BY14 INDOOR UNIT WITH CX180 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4400/0.056 5500/0.073 6600/0.088
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 166.22 180.64 196.10 173.51 188.84 205.30 178.59 194.57 211.94
85 SC 141.12 118.19 94.89 160.18 132.32 104.07 168.80 145.53 112.60
kW 16.4 16.76 17.09 17.29 17.61 17.96 18.53 18.86 19.25
TC 159.90 173.97 188.90 166.80 181.69 197.72 171.69 187.13 203.97
95 SC 138.51 115.70 92.43 157.59 129.80 101.63 162.48 143.03 110.13
kW 17.75 18.13 18.48 18.62 18.97 19.36 19.87 20.21 20.66
TC 153.57 167.10 181.69 160.09 174.54 190.13 164.50 179.69 196.29
105 SC 135.99 113.15 90.02 151.71 127.31 99.23 155.88 140.54 107.84
kW 19.34 19.74 20.14 20.2 20.58 21.03 21.44 21.82 22.33
TC 147.05 160.42 174.67 153.14 167.38 182.54 157.59 172.25 188.33
115 SC 133.35 110.76 87.73 145.33 124.86 96.85 149.56 138.08 105.41
kW 21.11 21.54 21.99 21.96 22.38 22.89 23.2 23.62 24.2
TC 140.34 152.98 166.90 145.95 159.52 174.48 150.12 164.24 179.79
125 SC 130.67 107.93 85.09 138.58 121.97 94.26 142.54 135.28 102.72
kW 23.05 23.52 24.03 23.89 24.35 24.95 25.12 25.6 26.27

BY18 INDOOR UNIT WITH CX180 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 5050/0.052 6300/0.067 7550/0.082
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 173.83 189.16 205.70 180.90 197.19 215.07 185.87 203.26 221.94
85 SC 155.56 129.23 102.57 171.49 145.30 113.09 176.20 160.79 122.99
kW 17.45 17.8 18.19 18.14 18.48 18.94 19.05 19.42 19.94
TC 167.23 182.15 198.30 173.76 189.82 207.19 178.63 195.41 213.81
95 SC 152.70 126.49 99.97 164.66 142.57 110.45 169.27 157.92 120.37
kW 19.03 19.41 19.85 19.71 20.09 20.62 20.62 21.02 21.63
TC 160.63 175.14 191.12 167.18 182.72 199.59 171.73 187.88 205.67
105 SC 150.05 123.94 97.65 158.64 140.21 108.11 162.95 155.43 117.89
kW 20.47 20.87 21.37 21.13 21.56 22.15 22.04 22.49 23.17
TC 153.81 168.14 183.50 160.04 175.07 191.72 164.16 180.02 197.54
115 SC 146.19 121.55 95.22 152.11 137.63 105.75 156.03 152.91 115.55
kW 22.28 22.73 23.3 22.95 23.42 24.1 23.85 24.36 25.14
TC 146.77 160.48 175.66 152.63 167.15 183.30 156.59 171.84 188.75
125 SC 139.62 118.72 92.68 145.20 134.88 103.10 148.97 150.16 112.86
kW 24.28 24.78 25.43 24.94 25.47 26.25 25.84 26.41 27.31

BY18 INDOOR UNIT WITH CX220 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 5050/0.054 6300/0.069 7550/0.085
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 197.82 214.55 232.26 206.71 224.51 243.58 212.85 231.41 251.56
85 SC 166.78 139.90 112.50 188.92 156.33 123.30 202.67 171.70 133.23
kW 20.44 20.85 21.2 21.16 21.52 21.89 22.05 22.4 22.83
TC 190.34 206.67 223.98 198.75 216.04 234.62 204.95 222.90 242.45
95 SC 163.63 136.92 109.68 185.74 153.28 120.38 195.43 168.87 130.43
kW 22.18 22.62 23.01 22.89 23.28 23.71 23.77 24.16 24.64
TC 182.64 198.13 215.06 190.51 207.30 225.12 196.40 213.73 232.68
105 SC 160.49 133.65 106.63 181.90 150.20 117.29 187.53 165.74 127.39
kW 24.12 24.61 25.04 24.83 25.26 25.73 25.7 26.14 26.67
TC 174.49 189.59 205.70 182.00 198.01 215.34 187.52 204.24 222.59
115 SC 157.13 130.51 103.45 174.00 146.87 114.15 179.28 162.52 124.28
kW 26.28 26.82 27.3 26.98 27.47 28 27.87 28.34 28.93
TC 165.69 179.96 195.69 172.67 188.18 204.75 177.65 193.77 211.53
125 SC 153.59 126.92 100.13 165.34 143.49 110.80 170.11 158.93 120.89
kW 28.71 29.29 29.84 29.4 29.93 30.52 30.27 30.8 31.46
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

13
COOLING CAPACITIES
(Dual compressor units)
BY18 INDOOR UNIT WITH CX240 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 5600/0.061 7000/0.078 8400/0.094
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 222.29 241.32 261.17 232.72 252.49 273.66 240.10 260.74 282.78
85 SC 183.63 154.41 124.47 208.00 172.25 136.12 226.22 189.23 146.98
kW 22.9 23.47 23.9 23.84 24.32 24.73 24.99 25.42 25.86
TC 214.73 233.31 252.72 224.49 243.99 264.61 231.32 251.64 273.00
95 SC 180.49 151.41 121.61 204.75 169.30 133.23 218.24 186.14 143.93
kW 24.89 25.48 25.93 25.81 26.32 26.77 26.95 27.41 27.9
TC 206.92 224.81 243.55 216.25 234.88 254.96 222.54 242.17 263.22
105 SC 177.42 148.30 118.54 201.78 166.14 130.20 210.34 183.02 141.06
kW 27.07 27.71 28.22 27.98 28.54 29.07 29.12 29.64 30.21
TC 198.14 215.34 233.66 206.80 224.87 244.40 213.02 231.97 252.00
115 SC 173.52 144.49 115.02 195.39 162.31 126.61 201.27 179.32 137.33
kW 29.48 30.18 30.76 30.38 31 31.61 31.51 32.1 32.76
TC 189.59 206.12 223.52 197.65 215.16 233.84 203.14 221.41 241.14
125 SC 170.28 141.24 111.69 187.09 159.11 123.36 192.28 175.79 134.15
kW 32.1 32.86 33.52 33 33.68 34.39 34.12 34.78 35.55

BY25 INDOOR UNIT WITH CX240 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 6000/0.041 7500/0.054 9000/0.067
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 227.97 247.37 268.19 239.54 260.44 282.87 247.45 269.22 292.89
85 SC 192.01 160.52 128.63 219.15 180.87 142.09 230.75 199.71 154.30
kW 22.43 22.88 23.27 23.06 23.45 23.88 23.87 24.26 24.76
TC 219.87 238.79 259.14 230.72 251.01 272.84 238.43 259.47 282.80
95 SC 188.44 157.12 125.42 215.09 177.27 138.67 222.28 196.18 151.07
kW 24.41 24.88 25.31 25.01 25.44 25.94 25.81 26.24 26.83
TC 211.24 229.68 249.31 221.57 241.26 262.50 228.63 249.32 271.55
105 SC 184.82 153.70 122.06 206.63 173.78 135.34 213.21 192.72 147.48
kW 26.57 27.1 27.6 27.17 27.66 28.25 27.97 28.47 29.16
TC 202.35 220.32 239.22 212.09 231.18 251.83 218.82 238.79 260.30
115 SC 181.07 150.17 118.61 197.82 170.14 131.88 204.10 189.03 143.94
kW 28.94 29.53 30.12 29.54 30.09 30.8 30.33 30.91 31.72
TC 193.20 210.43 228.62 202.29 220.77 240.52 208.63 227.86 248.66
125 SC 177.56 146.67 115.20 188.99 166.69 128.41 194.91 185.51 140.54
kW 31.52 32.18 32.86 32.11 32.74 33.56 32.9 33.57 34.51

BY25 INDOOR UNIT WITH CX300 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 7200/0.052 9000/0.067 10800/0.082
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 285.80 309.95 335.79 299.22 325.01 352.24 308.71 335.24 364.03
85 SC 239.93 201.44 162.41 272.08 225.42 177.91 294.45 247.63 192.30
kW 28.62 29.3 29.89 29.59 30.2 30.82 30.92 31.51 32.18
TC 275.45 299.03 324.00 287.84 312.92 339.44 296.47 322.60 350.53
95 SC 235.48 197.21 158.24 267.39 220.91 173.62 282.98 243.14 187.96
kW 31.3 31.99 32.59 32.24 32.85 33.49 33.54 34.14 34.86
TC 264.16 287.17 311.59 276.08 300.43 326.64 284.71 309.95 337.03
105 SC 230.76 192.72 154.01 262.81 216.44 169.56 272.21 238.93 183.81
kW 34.16 34.91 35.58 35.08 35.76 36.51 36.38 37.05 37.87
TC 252.24 274.68 298.55 263.53 287.17 312.67 271.53 296.38 322.60
115 SC 225.65 187.88 149.47 252.07 211.53 164.91 259.73 234.17 179.21
kW 37.31 38.12 38.89 38.22 38.97 39.83 39.5 40.26 41.2
TC 240.31 261.88 284.90 250.98 273.90 298.32 258.35 282.33 307.71
125 SC 221.07 183.26 144.95 240.54 207.10 160.42 247.61 229.56 174.73
` kW 40.73 41.62 42.5 41.63 42.47 43.45 42.92 43.77 44.85
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

14
COOLING CAPACITIES
(Dual compressor units)
BY25 INDOOR UNIT WITH CX360 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 9000/0.065 10500/0.079 12000/0.092
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 323.14 350.38 379.01 333.07 360.98 390.58 340.39 369.36 399.83
85 SC 276.99 230.76 183.70 302.51 249.42 195.70 318.43 267.30 207.12
kW 34.57 35.42 36.11 35.73 36.5 37.18 37.02 37.75 38.44
TC 311.37 337.89 365.43 320.72 347.77 376.55 327.84 355.84 385.34
95 SC 271.78 225.84 178.88 297.22 244.36 190.91 306.52 262.30 202.32
kW 37.49 38.36 39.07 38.63 39.43 40.13 39.91 40.66 41.39
TC 298.82 324.23 351.47 307.45 333.66 361.62 314.25 341.27 370.34
105 SC 266.86 220.89 174.42 287.87 239.45 186.24 294.23 257.37 197.85
kW 40.71 41.65 42.44 41.84 42.7 43.5 43.11 43.93 44.76
TC 286.27 310.97 337.11 294.64 320.01 347.13 300.65 326.71 354.83
115 SC 261.76 216.06 169.66 276.04 234.70 181.68 281.67 252.24 192.97
kW 44.33 45.34 46.22 45.44 46.39 47.29 46.71 47.61 48.56
TC 273.33 296.92 321.98 280.92 305.44 331.29 286.54 311.62 338.79
125 SC 256.53 211.24 164.90 263.64 229.90 176.84 268.92 247.36 188.27
kW 48.3 49.39 50.38 49.39 50.43 51.46 50.66 51.65 52.74

TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

15
FAN PERFORMANCE DATA
DIRECT DRIVE MOTORS
MODEL No.: BY03
BLOWER MOTOR HP BLOWER MOTOR CFM @ External Static Pressure (inch wg.)
SPEED 0.1 0.2 0.3 0.4 0.5 0.6
HIGH 1350 1290 1220 1160 1070 990
0.5 MEDIUM 1260 1200 1125 1060 1000 900
LOW 1070 1020 960 900 830 740
HIGH 1660 1480 1300 1230 1140 1060
0.75 MEDIUM 1570 1375 1180 1120 1060 960
LOW 1500 1320 1130 940 870 780

MODEL No.: BY05


BLOWER MOTOR HP BLOWER MOTOR CFM @ External Static Pressure (inch wg.)
SPEED 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
HIGH 2010 1920 1820 1730 1620 1490 1350 1230
0.75 MEDIUM 1830 1740 1660 1570 1470 1360 1240 1100
LOW 1710 1650 1570 1490 1390 1300 1170 975
HIGH 2252 2215 2180 2140 2105 2065 2020 1950
1.0 MEDIUM 2021 1990 1950 1920 1880 1840 1795 1700
LOW 1820 1805 1790 1735 1700 1665 1630 1530
NOTE: 1. Values include losses for dry coil, filter & unit casing.
2. Direct drive motors have single speed connection only. Thermostats are also single speed type only. Refer to the unit wiring diagram for connecting to other motor speeds.

BELT DRIVEN MOTORS


MODEL No.: BY07
External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 (849)
2000 (944)
820*
824*
0.62*
0.7*
900
905
I 0.71
0.79
965
970
0.82
0.91
1020
1026
0.88
1.0
1102
1107
1.03
1.12
1145
1152
1.14
1.25
1220
1225
1.26
1.35
2200 (1038) 853 0.81 927 0.91 986 1.02 1041 1.13 1111 1.25 1160 1.36 1237 1.48
2400 (1133) 950 0.94 1004 1.05 1059 1.21 1132 1.27 1155 1.38 1244 1.5 1297 1.65
2600 (1227) 968 1.1 1032 1.22 1086 1.33 1150 1.45 1194 1.57 1250 1.69 1305 1.82
2800 (1321) 1054 1.4 1106 1.5 1160 1.61 1216 1.76 1261 1.88 1323 2.02 1380* 2.2*
3000 (1416) 1066 1.55 1133 1.7 1180 1.82 1234 1.94 1276 2.09 1334* 2.23* 1400* 2.3*
3200 (1510) 1091 1.75 1157 1.91 1202 2.02 1255 2.2 1307 2.33 1359* 2.47*
3400 (1605) 1116 1.96 1171 2.1 1228 2.3 1276 2.45 1329 2.6 1368* 2.73* II
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY10


External Static Pressure (inch wg.)
Airflow, 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2800 (1321)
3000 (1416)
610
625
0.62
0.69
710
720
0.75
0.80
745
760 I 0.87
0.95
760
810
0.95
1.12
850
865
1.2
1.25
905
915
1.32
1.4
965
970
1.5
1.6
1000
1013
1.6
1.75
1054
1065
1.8
2.0
1100
1115
2.0
2.15
3200 (1510) 636 0.77 734 0.92 780 1.06 820 1.26 870 1.38 925 1.51 978 1.73 1023 1.86 1073 2.1 1122 2.28
3400 (1605) 660 0.88 746 1.01 805 1.18 833 1.34 881 1.5 939 1.67 983 1.84 1033 2.02 1083 2.25 1128 2.44
3600 (1699) 675 1.0 760 1.16 820 1.32 848 1.48 900 1.66 950 1.82 995 1.98 1043 2.21 1090 2.41 1131 2.6
3800 (1793) 700 1.13 778 1.3 840 1.43 868 1.63 913 1.8 966 2.0 1006 2.18 1056 2.39 1100 2.58 1143 2.78
4000 (1888) 727 1.28 790 1.45 865 1.62 882 1.8 926 1.96 980 2.18 1023 2.4 1066 2.6 1108 2.77
4200 (1982) 772 1.41 843 1.62 880 1.78 921 1.96 968 2.16 1011 2.36 1054 2.56 1096 2.76
4400 (2076) 791 1.58 864 1.79 887 1.94 934 2.14 979 2.34 1024 2.54 1067 2.77 II
4600 (2170) 840 1.79 890 1.96 931 2.2 975 2.38 1017 2.59 1058 2.77
4800 (2265) 857 1.95 906 2.17 947 2.4 988 2.57 1035 2.76
5000 (2360) 876 2.15 920 2.38 961 2.6 1005 2.76
NOTES (For BY07/BY10): 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.

16
FAN PERFORMANCE DATA (BELT DRIVEN MOTORS)
MODEL No.: BY14
External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 (1888)
4200 (1982)
4400 (2076)
694*
705*
719*
1.21*
1.33*
1.43*
743*
761*
774
1.3*
1.45*
1.6
797
811
823
I 1.52
1.67
1.8
845
857
869
1.66
1.81
1.97
890
903
918
1.83
2.0
2.17
937
951
963
2.03
2.19
2.33
975
992
1006
2.25
2.43
2.58
992
1002
1010
2.4
2.6
2.78
1075
1080
1093
2.64
2.82
2.97
II1102
1110
1133
2.85
3.05
3.2
4600 (2170) 735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34 971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41
4800 (2265) 748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52 979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62
5000 (2360) 761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70 989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86
5200 (2454) 778 2.06 823 2.27 873 2.48 917 2.70 959 2.91 1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.08
5400 (2548) 800 2.31 846 2.5 894 2.72 934 2.94 979 3.15 1019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.36
5600 (2643) 808 2.46 858 2.7 903 2.90 945 3.12 987 3.38 1028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.57
5800 (2737) 826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65 1041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.78
6000 (2832) 837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9 1047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.05
6200 (2926) 850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17 1061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.4
6400 (3020) 879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45 1078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.76
6600 (3115) 894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68 1091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08

MODEL No.: BY18


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5000 (2360)
5200 (2454)
715*
718*
1.33*
1.42*
731*
737*
1.56*
1.68*
787*
793* I 1.82*
1.96*
850
856
2.07
2.26
902
905
2.4
2.53
955
961
2.66
2.83
1005
1010
2.96
3.15
1057
1060
3.3
3.46 II 1104
1107
3.6
3.76
1153*
1155*
3.88*
4.04*
5400 (2548) 721* 1.53* 750* 1.81* 802* 2.07* 860 2.35 911 2.66 966 2.96 1012 3.23 1062 3.57 1109 3.88 1157* 4.27*
5600 (2643) 725* 1.68* 756* 1.92* 807 2.21 866 2.5 916 2.79 968 3.07 1015 3.38 1065 3.73 1110 4.07 1158* 4.4*
5800 (2737) 729* 1.81* 762* 2.03* 816 2.35 872 2.64 921 2.9 970 3.23 1020 3.53 1066 3.84 1113 4.18 1159* 4.59*
6000 (2832) 733* 1.9* 775* 2.14* 833 2.42 877 2.78 930 3.02 980 3.4 1025 3.69 1070 4.0 1118 4.4 1162* 4.72*
6200 (2926) 738* 2.03* 788* 2.35* 839 2.57 888 2.92 935 3.24 985 3.56 1030 3.84 1080 4.27 1120 4.63 1163* 4.95*
6400 (3020) 745* 2.15* 795* 2.5* 850 2.71 900 3.08 940 3.41 990 3.72 1036 4.04 1082 4.45 1126 4.82 1165* 5.09*
6600 (3115) 753* 2.38* 800* 2.64* 855 2.92 905 3.25 950 3.58 1000 3.88 1045 4.23 1083 4.6 1127 5 1170* 5.3*
6800 (3209) 761* 2.5* 810 2.78 863 3.08 910 3.41 960 3.75 1004 4.14 1050 4.47 1090 4.83 1134 5.16 1175* 5.51*
7000 (3303) 772* 2.69* 820 2.92 875 3.33 918 3.58 967 3.95 1012 4.28 1054 4.66 1095 5.04 1135 5.39 1179* 5.72*
7200 (3398) 777* 2.84* 830 3.08 880 3.41 927 3.75 976 4.14 1017 4.47 1059 4.85 1100 5.19 1141* 5.58* 1183* 5.95*
7400 (3492) 794* 2.96* 845 3.3 890 3.62 936 3.95 985 4.4 1021 4.68 1065 5.09 1108 5.47 1150* 5.8* 1185* 6.12*
7600 (3587) 805 3.18 850 3.5 900 3.83 941 4.2 990 4.57 1026 4.85 1069 5.23 1112 5.66 1154* 6* 1193* 6.42*
7800 (3681) 820 3.36 870 3.69 909 4.1 954 4.5 1002 4.9 1041 5.14 1083 5.47 1125 5.9 1158* 6.36* 1200* 6.78*
8000 (3775) 830 3.59 880 3.86 922 4.25 963 4.65 1008 5.05 1046 5.33 1087 5.75 1128 6.12 1164* 6.6*
8200 (3870) 867 3.77 890 4.1 936 4.5 972 4.9 1016 5.25 1054 5.56 1100 6 1132 6.36 1172* 6.84*
8400 (3964) 890 4.05 904 4.42 945 4.75 986 5.1 1025 5.45 1066 5.85 1107 6.24 1140 6.72
NOTES (For BY14/BY18): 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
MODEL No.: BY25
External Static Pressure (inch wg.)
Airflow, 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
700 2.6 762 3.12 812 3.6 847 4.0 870 4.5 940 5.0 980 5.46 1010 6.0 1059* 6.6*
6000 (2832)
6400 (3020) 706 2.8 764 3.3 I 813 3.78 848 4.22 871 4.73 942 5.23 981 5.71 1011II 6.3 1060* 6.92*
6800 (3209) 716 3.05 766 3.5 814 4.0 849 4.42 872 4.96 944 5.45 982 5.97 1013 6.6 1062* 7.22*
7200 (3398) 722 3.24 768 3.7 815 4.19 850 4.64 873 5.2 945 5.68 983 6.23 1014 6.95 1063* 7.51*
7600 (3587) 732 3.4 770 3.82 816 4.35 851 4.88 874 5.45 947 5.9 985 6.5 1016 7.25 1064* 7.78*
8000 (3775) 740 3.6 772 4.0 818 4.56 852 5.18 875 5.65 948 6.12 986 6.8 1018 7.5 1065* 8.05*
8400 (3964) 751 3.9 778 4.35 821 4.85 853 5.5 876 5.97 949 6.48 988 7.2 1019 7.8 1066* 8.35*
8800 (4152) 759 4.2 784 4.65 824 5.16 857 5.81 878 6.3 951 6.8 990 7.6 1020 8.1 1067* 8.65*
9200 (4341) 770 4.5 790 5.0 828 5.5 862 6.14 880 6.75 953 7.15 992 8.0 1021 8.45 1068* 9.0*
9600 (4530) 779 4.9 796 5.35 832 5.84 870 6.45 900 7.1 955 7.6 994 8.35 1022 8.75 1069* 9.45*
10000 (4719) 790 5.2 806 5.67 838 6.15 878 6.7 915 7.4 957 8.06 996 8.71 1023 9.25 1070* 9.8*
10400 (4907) 801 5.55 813 6.1 849 6.6 890 7.1 920 7.85 965 8.4 1003 9.1 1034* 9.7*
10800 (5096) 809 5.9 825 6.5 870 7.0 898 7.5 928 8.3 973 8.8 1009 9.5
11200 (5286) 821 6.4 856 6.9 876 7.4 906 7.95 936 8.7 981 9.25 1014 9.9
11600 (5474) 852 6.8 872 7.3 885 7.9 914 8.45 944 9.15 989 9.6
12000 (5663) 870 7.2 885 7.8 892 8.5 925 9.0 952 9.6 996 10.1
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
NOTES: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.

17
ELECTRICAL DATA
MODEL No.: BY03 MODEL No.: BY07
POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
RANGE ELECTRIC HEATER ELECTRIC HEATER
SUPPLY MOTOR ** MCA MOCP SUPPLY RANGE MOTOR
MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 2.3 15 – – 8.3 15
5 21.7 29.4 30
0.50 1.8 6/7 26.1/30.4 34.9/40.3 40/45 5 12.6 24 25
(STD.) 10*/12* 43.5/52.2 56.6/67.5 60/70 2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35
14* 60.9 78.4 80 (STD.)
208/230-1-60 187 253 10*/12* 25.1/30.1 39.6/45.9 40/50
– – 5.9 15
5 21.7 33 35 15*/20* 37.7/50.2 55.4/71 60/80
0.75 4.7 6/7 26.1/30.4 38.5/43.9 40/45 25*/30* 62.8/75.3 86.8/102.4 90/110
(ALT.) 10*/12* 43.5/52.2 60.3/71.1 70/80 208/230-3-60 187 253
14* 60.9 82 90 – – 11 20
– – 2.3 15 5 12.6 26.8 30
5 12.6 18 20 3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35
0.50 1.8 6/7.5 15.1/18.8 21.1/25.8 25/30
(ALT.) 10*/12* 25.1/30.1 42.4/48.6 45/50
(STD.) 10*/12* 25.1/30.1 33.6/39.9 35/40
15* 37.7 49.4 50 15*/20* 37.7/50.2 58.1/73.8 60/80
208/230-3-60 187 253 – – 5.9 15
25*/30* 62.8/75.3 89.5/105.1 90/110
5 12.6 21.6 25
0.75 4.7 6/7.5 15.1/18.8 24.8/29.4 30/35 – – 5 15
(ALT.) 10*/12* 25.1/30.1 37.3/43.5 40/45 5 7.6 14.5 15
15* 37.7 53 60
– – 2.3 15 2 4 6/7.5 9.1/11.4 16.4/19.3 20/20
5 7.6 11.8 15 (STD.) 10*/12* 15.2/18.2 24/27.8 25/30
0.50 1.8 6/7.5 9.1/11.4 13.6/16.5 15/20 15*/20* 22.8/30.4 33.5/43 35/45
(STD.) 10*/12* 15.2/18.2 21.3/25 25/30
15* 22.8 30.8 35 25*/30* 38/45.6 52.5/62 60/70
380-3-60 342 418 380-3-60 342 418
– – 5.9 15 – – 6.4 15
(4 WIRE) (4 WIRE)
5 7.6 15.4 20 5 7.6 15.9 20
0.75 4.7 6/7.5 9.1/11.4 17.3/20.1 20/25
(ALT.) 10*/12* 15.2/18.2 24.9/28.6 30/30 3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25
15* 22.8 34.4 35 (ALT.) 10*/12* 15.2/18.2 25.4/29.2 30/30
– – 1.3 15
15*/20* 22.8/30.4 34.9/44.4 40/45
5 6.3 9.1 15
0.50 1.0 6/7.5 7.5/9.4 10.6/13 15/20 25*/30* 38/45.6 53.9/63.4 60/70
(STD.) 10*/12* 12.6/15.1 17/20.1 20/25 – – 4.4 15
15* 18.8 24.8 30
460-3-60 414 506 – – 3.3 15 5 6.3 12.3 15
5 6.3 11.1 15 2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20
0.75 2.6 6/7.5 7.5/9.4 12.6/15 15/20 (STD.) 10*/12* 12.6/15.1 20.1/23.3 25/25
(ALT.) 10*/12* 12.6/15.1 19/22.1 20/25
15* 18.8 26.8 30 15*/20* 18.8/25.1 27.9/35.8 30/40
25*/30* 31.4/37.7 43.6/51.5 45/60
460-3-60 414 506 – – 5.1 15
MODEL No.: BY05 5 6.3 13 15
POWER VOLTAGE BLOWER 3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20
RANGE ELECTRIC HEATER (ALT.)
SUPPLY MOTOR ** MCA MOCP 10*/12* 12.6/15.1 20.9/24 25/25
(V-Ph-Hz) 15*/20* 18.8/25.1 28.6/36.5 30/40
MIN. MAX. HP FLA kW FLA
25*/30* 31.4/37.7 44.4/52.3 45/60
– – 5.9 15
5 21.7 33 40
0.75 4.7 6/7 26.1/30.4 38.5/43.9 45/50
(STD.) 10*/12* 43.5/52.2 60.3/71.1 70/80
14* 60.9 82 90
208/230-1-60 187 253 – – 10.3 15 LEGEND
5 21.7 37.4 40
1.0 8.2 6/7 26.1/30.4 42.9/48.3 45/50 FLA – Full Load Amps
(ALT.) 10*/12* 43.5/52.2 64.6/75.5 70/80
14* 60.9 86.4 90 HP – Horse Power
– – 5.9 15
5 12.6 21.6 25
MCA – Minimum Circuit Amps
0.75 4.7 6/7.5 15.1/18.8 24.8/29.4 25/30
(STD.) 10*/12* 25.1/30.1 37.3/43.5 40/45
15* 37.7 53 60 MOCP – Maximum Over Current Protection
208/230-3-60 187 253 – – 10.3 15
5 12.6 26 30 * Combination of 2 heater modules
1.0 8.2 6/7.5 15.1/18.8 29.1/33.8 30/35
(ALT.) 10*/12* 25.1/30.1 41.6/47.9 45/50 ** Single phase motors
15* 37.7 57.4 60
– – 5.9 15
(208/230V-1Ph-60Hz for 208/230V-3Ph-60Hz & 380V-3Ph-60Hz power supply.
5 7.6 15.4 20 460V-1Ph-60Hz for 460V-3Ph-60Hz power supply).
0.75 4.7 6/7.5 9.1/11.4 17.3/20.1 20/25
(STD.) 10*/12* 15.2/18.2 24.9/28.6 25/30
15* 22.8 34.3 35
380-3-60 342 418 – – 10.3 15
(4 WIRE) 5 7.6 19.8 25
1.0 8.2 6/7.5 9.1/11.4 21.6/24.5 25/30
(ALT.) 10*/12* 15.2/18.2 29.3/33 30/35
15* 22.8 38.8 40
– – 3.8 15
5 6.3 11.6 15
0.75 3.0 6/7.5 7.5/9.4 13.1/15.5 15/20
(STD.) 10*/12* 12.6/15.1 19.5/22.6 20/25
15* 18.8 27.3 30
460-3-60 414 506 – – 5.5 15
5 6.3 13.4 15
1.0 4.4 6/7.5 7.5/9.4 14.9/17.3 20/20
(ALT.) 10*/12* 12.6/15.1 21.3/24.4 25/25
15* 18.8 29 30

18
ELECTRICAL DATA
MODEL No.: BY10 MODEL No.: BY14
POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
RANGE MOTOR ELECTRIC HEATER RANGE MOTOR ELECTRIC HEATER
SUPPLY SUPPLY
MCA MOCP MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 8.3 15 – – 17.3 30
5 12.6 24 25 5 12.6 33 40
2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35 5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45
(ALT.) 10*/12* 25.1/30.1 39.6/45.9 40/50 (STD.) 10*/12* 25.1/30.1 48.6/54.9 50/60
15*/20* 37.7/50.2 55.4/71 60/80 15*/20* 37.7/50.2 64.4/80 70/90
25*/30* 62.8/75.3 86.8/102.4 90/110 25*/30* 62.8/75.3 95.8/111.4 100/125

208/230-3-60 187 253 208/230-3-60 187 253


– – 11 20 – – 24.4 40
5 12.6 26.8 30 5 12.6 40.1 50
3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35 7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60
(STD.) (ALT.)
10*/12* 25.1/30.1 42.4/48.6 45/50 10*/12* 25.1/30.1 55.8/62 60/70
15*/20* 37.7/50.2 58.1/73.8 60/80 15*/20* 37.7/50.2 71.5/87.1 80/90
25*/30* 62.8/75.3 89.5/105.1 90/110 25*/30* 62.8/75.3 102.9/118.5 110/125

– – 5 15 – – 11.3 20
5 7.6 14.5 15 5 7.6 20.8 25
2 4 6/7.5 9.1/11.4 16.4/19.3 20/20 5 9 6/7.5 9.1/11.4 22.6/25.5 25/30
(ALT.) (STD.)
10*/12* 15.2/18.2 24/27.8 25/30 10*/12* 15.2/18.2 30.3/34 35/35
15*/20* 22.8/30.4 33.5/43 35/45 15*/20* 22.8/30.4 39.8/49.3 45/50
25*/30* 38/45.6 52.5/62 60/70 25*/30* 38/45.6 58.8/68.3 60/70

380-3-60 342 418 380-3-60 342 418


(4 WIRE) – – 6.4 15 (4 WIRE) – – 15.6 25
5 7.6 15.9 20 5 7.6 25.1 35
3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25 7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
(STD.) 10*/12* 15.2/18.2 25.4/29.2 30/30 (ALT.) 10*/12* 15.2/18.2 34.6/38.4 40/45
15*/20* 22.8/30.4 34.9/44.4 40/45 15*/20* 22.8/30.4 44.1/53.6 50/60
25*/30* 38/45.6 53.9/63.4 60/70 25*/30* 38/45.6 63.1/72.6 70/80

– – 4.4 15 – – 8.6 15
5 6.3 12.3 15 5 6.3 16.5 20
2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20 5 6.9 6/7.5 7.5/9.4 18/20.4 20/25
(ALT.) (STD.)
10*/12* 12.6/15.1 20.1/23.3 25/25 10*/12* 12.6/15.1 24.4/27.5 30/30
15*/20* 18.8/25.1 27.9/35.8 30/40 15*/20* 18.8/25.1 32.1/40 35/45
25*/30* 31.4/37.7 43.6/51.5 45/60 25*/30* 31.4/37.7 47.9/55.8 50/60

460-3-60 414 506 460-3-60 414 506


– – 5.1 15 – – 12.2 20
5 6.3 13 15 5 6.3 20.1 25
3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20 7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30
(STD.) (ALT.)
10*/12* 12.6/15.1 20.9/24 25/25 10*/12* 12.6/15.1 27.9/31.1 30/35
15*/20* 18.8/25.1 28.6/36.5 30/40 15*/20* 18.8/25.1 35.7/43.6 40/45
25*/30* 31.4/37.7 44.4/52.3 45/60 25*/30* 31.4/37.7 51.4/59.3 60/70

LEGEND
FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

19
ELECTRICAL DATA
MODEL No.: BY18 MODEL No.: BY25
POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
RANGE MOTOR ELECTRIC HEATER RANGE MOTOR ELECTRIC HEATER
SUPPLY SUPPLY
MCA MOCP MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 17.3 30 – – 25.5 45
5 12.6 33 40 5 12.6 41.2 50
5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45 7.5 20.4 6/7.5 15.1/18.8 44.3/49 60/60
(STD.) (STD.)
10*/12* 25.1/30.1 48.6/54.9 50/60 10*/12* 25.1/30.1 56.9/63.2 70/70
15*/20* 37.7/50.2 64.4/80 70/90 15*/20* 37.7/50.2 72.6/88.3 80/90
25*/30* 62.8/75.3 95.8/111.4 100/125 25*/30* 62.8/75.3 103.9/119.6 110/125
35*/40* 87.9/100.4 127.1/142.8 150/150 35*/40* 87.9/100.4 135.3/151 150/175
208/230-3-60 187 253 208/230-3-60 187 253
– – 24.4 40 – – 32.6 50
5 12.6 40.1 50 5 12.6 48.3 70
7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60 10 26.1 6/7.5 15.1/18.8 51.5/56.2 70/70
(ALT.) (ALT.)
10*/12* 25.1/30.1 55.8/62 60/70 10*/12* 25.1/30.1 64/70.3 80/80
15*/20* 37.7/50.2 71.5/87.1 80/90 15*/20* 37.7/50.2 79.7/95.4 90/100
25*/30* 62.8/75.3 102.9/118.5 110/125 25*/30* 62.8/75.3 111.1/126.8 125/150
35*/40* 87.9/100.4 134.3/149.9 150/175 35*/40* 87.9/100.4 142.4/158.1 150/175
– – 11.3 20 – – 15.6 25
5 7.6 20.8 25 5 7.6 25.1 35
5 9 6/7.5 9.1/11.4 22.6/25.5 25/30 7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
(STD.) (STD.)
10*/12* 15.2/18.2 30.3/34 35/35 10*/12* 15.2/18.2 34.6/38.4 40/45
15*/20* 22.8/30.4 39.8/49.3 45/50 15*/20* 22.8/30.4 44.1/53.6 50/60
25*/30* 38/45.6 58.8/68.3 60/70 25*/30* 38/45.6 63.1/72.6 70/80
35*/40* 53.2/60.8 77.8/87.3 80/90 35*/40* 53.2/60.8 82.1/91.6 90/100
380-3-60 342 418 380-3-60 342 418
(4 WIRE) – – 15.6 25 (4 WIRE) – – 20 35
5 7.6 25.1 35 5 7.6 29.5 40
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35 10 16 6/7.5 9.1/11.4 31.4/34.2 45/45
(ALT.) (ALT.)
10*/12* 15.2/18.2 34.6/38.4 40/45 10*/12* 15.2/18.2 39/42.8 50/50
15*/20* 22.8/30.4 44.1/53.6 50/60 15*/20* 22.8/30.4 48.5/58 50/60
25*/30* 38/45.6 63.1/72.6 70/80 25*/30* 38/45.6 67.5/77 70/80
35*/40* 53.2/60.8 82.1/91.6 90/100 35*/40* 53.2/60.8 86.5/96 90/100
– – 8.6 15 – – 12.8 20
5 6.3 16.5 20 5 6.3 20.6 25
5 6.9 6/7.5 7.5/9.4 18/20.4 20/25 7.5 10.2 6/7.5 7.5/9.4 22.2/24.5 30/30
(STD.) (STD.)
10*/12* 12.6/15.1 24.4/27.5 30/30 10*/12* 12.6/15.1 28.4/31.6 35/35
15*/20* 18.8/25.1 32.1/40 35/45 15*/20* 18.8/25.1 36.3/44.1 40/45
25*/30* 31.4/37.7 47.9/55.8 50/60 25*/30* 31.4/37.7 52/59.8 60/60
35*/40* 43.9/50.2 63.5/71.4 70/80 35*/40* 43.9/50.2 67.7/75.5 70/80
460-3-60 414 506 460-3-60 414 506
– – 12.2 20 – – 16.3 25
5 6.3 20.1 25 5 6.3 24.1 35
7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30 10 13 6/7.5 7.5/9.4 25.7/28 35/35
(ALT.) (ALT.)
10*/12* 12.6/15.1 27.9/31.1 30/35 10*/12* 12.6/15.1 31.9/35.1 40/40
15*/20* 18.8/25.1 35.7/43.6 40/45 15*/20* 18.8/25.1 39.8/47.6 45/50
25*/30* 31.4/37.7 51.4/59.3 60/70 25*/30* 31.4/37.7 55.5/63.3 60/70
35*/40* 43.9/50.2 67.1/74.9 70/80 35*/40* 43.9/50.2 71.2/79 80/80

LEGEND
FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

20
DIMENSIONS
BY03 - BY14 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS
MODEL
A B C D E F G H J K L M S
BY03 1092(43) 648(25.5) 575(22.64) 483(19.02) 143(5.63) 406(15.98) 45(1.77) 542(21.34) 524(20.63) 297(11.69) 553(21.77) 151(5.94) 38(1.5)
BY05 1092(43) 813(32) 600(23.62) 483(19.02) 224(8.82) 406(15.98) 45(1.77) 707(27.83) 550(21.65) 297(11.69) 553(21.77) 183(7.2) 38(1.5)
BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 182(7.16) 406(15.98) 66(2.6) 995(39.17) 550(21.65) 378(14.88) 721(28.38) 123(4.84) 45(1.75)
BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 332(13.1) 406(15.98) 42(1.65) 1295(51) 625(24.61) 378(14.88) 721(28.38) 198(7.8) 45(1.75)
BY14 1625(64) 1600(63) 705(27.75) 1321(52) 187(7.36) 406(15.98) 55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 153(6.02) 45(1.75)

21
DIMENSIONS
BY03 - BY14 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M S
BY03 1092(43) 648(25.5) 575(22.64) 483(19.02) 134(5.28) 406(15.98) 35(1.38) 543(21.38) 502(19.76) 285(11.22) 553(21.77) 154(6.06) 38(1.5)
BY05 1092(43) 813(32) 600(23.62) 483(19.02) 229(9.02) 406(15.98) 32(1.26) 712(28.03) 502(19.76) 300(11.81) 553(21.77) 195(7.68) 38(1.5)
BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 213(8.4) 406(15.98) 85(3.34) 991(39) 504(19.83) 302(11.87) 697(27.53) 110(4.33) 45(1.75)
BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 365(14.38) 406(15.98) 35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 123(4.84) 45(1.75)
BY14 1625(64) 1600(63) 705(27.75) 1321(52) 224(8.82) 406(15.98) 49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 110(4.33) 45(1.75)

22
DIMENSIONS
BY18 - BY25 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M S
BY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 382(15.04) 483(19.02) 35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 153(6.02) 45(1.75)
BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 590(23.23) 483(19.02) 50(1.97) 2257(88.86) 790(31.1) 503(19.8) 913(35.94) 288(11.34) 45(1.75)

23
DIMENSIONS
BY18 - BY25 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M S
BY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 422(16.61) 483(19.02) 46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 110(4.33) 45(1.75)
BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 625(24.61) 483(19.02) 74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 110(4.33) 45(1.75)

24
OPTIONALACCESSORIES (BAG FILTER, MIXING BOX & PLENUM) - HORIZONTAL DISCHARGE
25

MODEL
N P Q
NUMBER
BY03 N.A. 508(20) 381(15)
BY05 N.A. 508(20) 381(15)
BY07 551(21.69) 552(21.73) 508(20)
BY10 679(26.7) 635(25.4) 508(20)
NOTES: 1. Single blower for BY03 - BY14.
BY14 711(28) 689(27.12) 508(20)
2. Double blowers for BY18 - BY25.
BY18 711(28) 690(27.16) 508(20)
3. Supply air grille quantity is 3 for BY03 - BY05, 4 for BY07 - BY14 & 5 for BY18 - BY25.
BY25 711(28) 690(27.16) 508(20) 4. Return air grille quantity is 1 for BY03 - BY05, 2 for BY07 - BY14 & 3 for BY18 - BY25.
NOTE: All dimensions are in mm (dimensions in brackets are in inches). 5. Additional 0.6 ESP to be added for bag filter option.
OPTIONAL ACCESSORIES (BAG FILTER, MIXING BOX & PLENUM) - VERTICAL DISCHARGE

MODEL
N O P Q
NUMBER
BY03 N.A. 559(22) 700(27.55) 381(15)
BY05 N.A. 559(22) 700(27.55) 381(15)
BY07 552(21.75) 604(23.8) 650(25.59) 508(20)
BY10 685(27) 668(26.3) 750(29.52) 508(20)
BY14 685(27) 668(26.3) 900(35.43) 508(20)
BY18 685(27) 668(26.3) 863(34) 508(20)
BY25 685(27) 668(26.3) 863(34) 508(20)
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
26

NOTES: 1. Single blower for BY03 - BY14.


2. Double blowers for BY18 - BY25.
3. Supply air grille quantity is 3 for BY03 - BY05, 4 for BY07 - BY14 & 5 for BY18 - BY25.
4. Return air grille quantity is 1 for BY03 - BY05, 2 for BY07 - BY14 & 3 for BY18 - BY25.
5. Additional 0.6 ESP to be added for bag filter option.
DIMENSIONS - HEATER BOX
BY03 - BY05
)
(1 6.3"
415

(1")
25.4 YP
T

205 (8.1")

490
(19.3
")

HEATER CONTROLS MTG HEATER CONTROLS MTG


PLATE
COVER

BY07 - BY14
.2 ")
(16
412

YP
") T
4 (1
25.
205 (8.1")

DIMENSIONS
MODEL
A HEATER ACCESS COVER
BY07 818 (32.2) HEATER CONTROLS MTG
BY10 818 (32.2)
COVER
HEATER CONTROLS MTG
BY14 1326(52.2) PLATE

BY18 - BY25
")
9.4
49 2 (1

YP
") T
4 (1
25.
205 (8.1")

1581 (6
2.3")

HEATER ACCESS COVER


(BOTH SIDES) HEATER CONTROLS MTG
COVER
HEATER CONTROLS MTG
PLATE

NOTES: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Heater box is an optional feature.

27
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX030 - CX060

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches). MODEL NUMBER A B C D E F G H
2. Allow 32" (812mm) clearance to service end of the unit,
CX030 - CX036 711 610 708 596 440 175 86 57
12" (305mm) on remaining sides and 24" (610mm) be-
tween units for proper airflow. CX042 - CX060 889 813 806 695 538 216 99 72

28
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX075 - CX120

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units for
proper airflow.

29
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX150 - CX220

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

30
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX240 & CX300

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

31
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX360
[61.0"]
1550

[8.0"]
203

2121 73 943 943


[83.50"] [2.88"] [37.13"] [37.13"]

2197 2032
[86.50"] [80.0"]

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

32
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with single compressor units)
CONNECTION APPLICABLE FOR 1PH BM

REFER TO UNIT
NAMEPLATE FOR
POWER SUPPLY

BM

TO CONDENSSING UNIT ATB

AFS
HC NC
28 C

NO

BMC

TO CONDENSING UNIT ATB

230V

LOCK2(RED) LOCK1(RED) ECB


SYSTEM2(ORG) SYSTEM1(YEL)
30

29
PRI

FUSE

P3_##
TRANS

ON DIP
SEC

DIP SWITCH
POWER(GRN) W2 W1 Y1 G C R TO CONDENSING UNIT ATB

J_PROG

THERMOSTAT / DDC CONTROLLER


(by others)
LVTB
R
R
24Vac C
C
BM CONTROL G
G
STG1 COOLING Y1
Y1
STG1 HEATING W1
W1
W2

ECB DIP SWITCH SETTINGS & LED INDICATORS


DIP SWITCH FUCTIONS FACTORY SETTINGS OF DIP SWITCHES LED INDICATORS
Green power on/off indicator
S1 OFF=TEST MODE DISABLE ON= TEST MODE ENABLE Red system lock-out due to system fault
DIP SWITCH # S1 S2 S3 S4
LOAD BALANCE ON system 1 fault diagnostic
S2 OFF= (Comp1&2 Auto Lead Lag) ON= COMPRESSOR 1 LEAD
OFF Yellow blinking slow - LPS1/ HPS1/ SSPS1/
OLR1/CB1 ckt fault
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION note:
Set dip switch # 3 according to unit's option system 2 fault diagnostic
S4 on-board programming function (always set to on) (pump down or no pump down) Orange blinking slow - LPS2/ HPS2/ SSPS2/
OLR2/ CB2 ckt fault

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

33
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with single compressor units)

TO HVTB TO HVTB TO HVTB TO HVTB LEGEND


L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
AI ANTI ICE THERMOSTAT
AFS AIRFLOW SWITCH
ATB AUXILIARY TERMINAL BLOCK
CB11 CB12 CB13 CB14 CB11 CB13 CB11 CB12 AR AUXILIARY RELAY

71A
72A
73A
BM BLOWER MOTOR
74A
75A
76A

74A
75A
76A
71A
72A
73A

71B
72B
73B

74B
75B
76B

74A
75A
76A
71A
72A
73A
HC1 HC2 BMC BLOWER MOTOR CONTACTOR
HC1 HC2 HC3 HC4 HC1 HC3
CAP CAPACITOR

T1H
T2H
T3H
T1F
T2F
T3F
T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I

ECB ELECTRONIC CONTROL BOARD


HEATER1 HEATER2 HEATER3 HEATER4 HEATER1 HEATER3

T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I
FL FUSE LINK
29 HC1 28 30 HC3 28 HEATER1 HEATER2 HEATER3 HEATER4
29 HC1 28 30 HC3 28
HC HEATER CONTACTOR
HC2 HC4
29 HC1 28 30 HC2 28 HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
HEATER OPTION-1 (SEE TABLE) HEATER OPTION-2 (SEE TABLE) HEATER OPTION-3 (SEE TABLE)
L1 LINE 1
L2 LINE 2
L3 LINE 3
LVTB LOW VOLTAGE TERMINAL BLOCK
LUG LUG GROUND
HEATER TYPES
OHT OHT
HEATER DATA TABLE OPTIONS MOHT MANUAL RESET OHT
HEATER DATA TABLE
FL FL NTB NEUTRAL TERMINAL BLOCK
H1 1) ANTI ICE OPTION
HTR OPT# STG I STG II STG OHT OVERHEAT THERMOSTAT
5 K.W 2 1 5 K.W
COMP OLR OVER LOAD RELAY
6 K.W 2 1 6 K.W
OHT OHT 21A AI-1 23A SM SYSTEMIZER
7.5 K.W 2 1 7.5 K.W
LPS VFC VOLT FREE CONTACT
H2 ___
10 K.W 2 2 5 K.W 5 K.W FIELD WIRING
12 K.W 2 2 6 K.W 6 K.W + DISCONNECT TAB - 1/4"
CONNECTION APPLICABLE FOR ANTI ICE
OHT 15 K.W 2 2 7.5 K.W 7.5 K.W FL OR MOHT
(#1) FL
20 K.W 2 2 10 K.W 10 K.W 2) VFC OPTION FOR BM RUN &TRIP INDICATION W/O OLR NOTES
H3 FL 25 K.W 2 2 12.5 K.W 12.5 K.W
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
OHT FL 30 K.W 2 2 15 K.W 15 K.W BMCA-2A 50
(#2) 48 48B THERMOSTAT CONTROL VOLTAGE - 24VAC.
35 K.W 2 7.5+10 K.W 7.5+10 K.W
OHT * BMCA-1A 49 2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C
40 K.W 2 2*10 K.W 2*10 K.W 48A OR ITS EQUIVALENT.
H4 FL FL
*
NOTES: HTR-35 & 40KW IS APPLICABLE FOR USE COPPER CONDUCTOR WIRES ONLY.
FL BY 18 MODEL ONLY.
BM ON 3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLE
USE OPTION 1 FOR 230V-3PH UNIT MODEL
OHT * USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL BM TRIP PROTECTION FOR COMPRESSOR IS AVAILABLE IN
* ZAMIL ELECTRONIC THERMOSTAT.

VFC OPTION FOR BM RUN &TRIP INDICATION WITH OLR 4. IF HEATERS ARE FACTORY INSTALLED, PLEASE
APPLICABLE FOR BM WITH READ BROKEN LINES AS CONTINUOUS LINES.
EXTERNAL OLR (OPTION) 48 BMCA-1A 49
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO HVTB TO BE PROVIDED BY CONSUMER WITH RATING AS
BM ON RECOMMENDED BY ZAMIL.
L1
L2
L3

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE


51 OLR-2 52 ACROSS TERMINAL X1, X2 & 2 IS 230VAC.
BMC

OLR 7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER


BM TRIP SUPPLY ONLY.
68
69
70

BM

34
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with dual compressor units)
APPLICABLE FOR 1PH BM APPLICABLE FOR BM WITH EXTERNAL OLR

TO HVTB

L1
L2
L3
BMC
HVTB BMC OLR
L1 68
L2 69
BM
REFER TO UNIT
NAMEPLATE FOR
POWER SUPPLY L3 70

68
69
70
LUG
BM

NTB
N (SEE NOTE-7)

TO CONDENSSING UNIT ATB

HC2
NC
28 C
HC1
NO

BMC

TO CONDENSING UNIT ATB


230V
TO CU ATB
41B

41A

4B

4A

3B

3A
30

29

14
OUTFAN2

OUTFAN1

HEATER2

HEATER1
NEUTRAL

COMP1
COMP2
INFAN
LIVE

X2

X1

P2

P1

LOCK2(RED) LOCK1(RED) ECB


SYSTEM2(ORG) SYSTEM1(YEL)
30

29
PRI

FUSE

HP1
240v (HP1)
TRANS

12v-0-12v
HP2
(HP2)

LP1 26A 13
SEC

DIP SWITCH
(LP1) 23A
POWER(GRN) 14 TO CONDENSING UNIT ATB
J_PROG LP2 22B 15
(LP2) 23B
16

THERMOSTAT / DDC CONTROLLER

LVTB

ECB DIP SWITCH SETTINGS & LED INDICATORS


DIP SWITCH FUCTIONS FACTORY SETTINGS OF DIP SWITCHES LED INDICATORS
Green power on/off indicator
S1 OFF=TEST MODE DISABLE ON= TEST MODE ENABLE
DIP SWITCH # S1 S2 S3 S4 Red system lock-out due to system fault
LOAD BALANCE ON system 1 fault diagnostic
S2 OFF= ON= COMPRESSOR 1 LEAD
(Comp1&2 Auto Lead Lag) OFF Yellow blinking slow - LPS1/ HPS1/ SSPS1/
OLR1/CB1 ckt fault
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION note:
system 2 fault diagnostic
Set dip switch # 3 according to unit's option
on-board programming function (always set to on) (pump down or no pump down) Orange blinking slow - LPS2/ HPS2/ SSPS2/
S4
OLR2/ CB2 ckt fault

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

35
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with dual compressor units)

TO HVTB TO HVTB TO HVTB TO HVTB LEGEND


L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
AI ANTI ICE THERMOSTAT
AFS AIRFLOW SWITCH
ATB AUXILIARY TERMINAL BLOCK
CB11 CB12 CB13 CB14 CB11 CB13 CB11 CB12 AR AUXILIARY RELAY
BM BLOWER MOTOR

71A
72A
73A
74A
75A
76A

74A
75A
76A
71A
72A
73A

71B
72B
73B

74B
75B
76B

74A
75A
76A
71A
72A
73A
BMC BLOWER MOTOR CONTACTOR
HC1 HC1 HC3 HC1 HC2
HC2 HC3 HC4 ECB ELECTRONIC CONTROL BOARD

T1H
T2H
T3H
T1F
T2F
T3F
T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

FL FUSE LINK
T1I
T2I
T3I

HEATER1 HEATER2 HEATER3 HEATER4 HEATER1 HEATER3 HC HEATER CONTACTOR

T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I
29 HC1 28 30 HC3 28 HEATER1 HEATER2 HEATER3 HEATER4 HVTB HIGH VOLTAGE TERMINAL BLOCK
29 HC1 28 30 HC3 28
HTR HEATER
HC2 HC4 HC1 28 30 HC2 28
29
L1 LINE 1
HEATER OPTION-1 (SEE TABLE) HEATER OPTION-2 (SEE TABLE) HEATER OPTION-3 (SEE TABLE) L2 LINE 2
L3 LINE 3
LVTB LOW VOLTAGE TERMINAL BLOCK
HEATER TYPES
HEATER DATA TABLE OPTIONS LUG LUG GROUND
OHT OHT
HEATER DATA TABLE
FL FL
H1 HTR OPT# STG I STG II STG
1) ANTI ICE OPTION LLS LEAD LAG SWITCH
5 K.W 2 1 5 K.W MOHT MANUAL RESET OHT
COMP1
6 K.W 2 1 6 K.W AI-1 23A NTB NEUTRAL TERMINAL BLOCK
OHT OHT 21A
7.5 K.W 2 1 7.5 K.W OHT OVERHEAT THERMOSTAT
H2
LPS1
10 K.W 2 2 5 K.W 5 K.W OLR OVER LOAD RELAY
12 K.W 2 2 6 K.W 6 K.W COMP2 SM SYSTEMIZER
OHT 15 K.W 2 2 7.5 K.W 7.5 K.W 21B AI-2 23B VFC VOLT FREE CONTACT
(#1) FL ___
20 K.W 2 2 10 K.W 10 K.W LPS2 FIELD WIRING
H3 FL + DISCONNECT TAB - 1/4"
25 K.W 2 2 12.5 K.W 12.5 K.W
OHT FL FL OR MOHT
(#2) 30 K.W 2 2 15 K.W 15 K.W 2) VFC OPTION FOR BM RUN &TRIP INDICATION W/O OLR
35 K.W 2 7.5+10 K.W 7.5+10 K.W
OHT * 50
NOTES
40 K.W
* 2 2*10 K.W 2*10 K.W
48 48B
H4 FL FL 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
NOTES: HTR-35 & 40KW IS APPLICABLE FOR
FL BY 18 & 25 MODELS ONLY. 49 THERMOSTAT CONTROL VOLTAGE - 24VAC.
48A
OHT * USE OPTION 1 FOR 230V-3PH UNIT MODEL
* USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL 2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C
OR ITS EQUIVALENT.
BM ON USE COPPER CONDUCTOR WIRES ONLY.
BM TRIP 3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLE
VFC OPTION FOR BM RUN &TRIP INDICATION WITH OLR / CB PROTECTION FOR COMPRESSOR IS AVAILABLE IN
ZAMIL ELECTRONIC THERMOSTAT.
48 49 4. IF HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.

BM ON 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER


TO BE PROVIDED BY CONSUMER WITH RATING AS
51 52
RECOMMENDED BY ZAMIL.

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE


ACROSS TERMINAL X1, X2 & 2 IS 230VAC.
BM TRIP
7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER
SUPPLY ONLY.

36
CONTROLS & SEQUENCE OF OPERATION
Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct
rotation when the system is operated. Verification of correct rotation is by observing that the suction pressure drops and
discharge pressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low
current draw and by interchanging power supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.
GENERAL
The thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit
allow complete control of the thermostat. The thermostat also allows to select continuous fan operation (useful when
using an air cleaner) or have the fan come on with the compressor.
SWITCH FUNCTION
- On/Off Key : Switch the system On or Off.
- Up Key : To increases the set temperature.
- Down Key : To decreases the set temperature.
- Mode Key : Changes the mode to Fan, Cool, Heat or Auto.
- Fan Key : Changes the Fan Operation to Auto or Continuous.
- °C/°F selection : By pressing Mode & UP key together, toggles between °C to °F or vice versa.
USER CONTROLS
Mode:
Select the desired mode of operation by pressing of the mode button:

F
A
N

H
E
A
T
C
O
O
L

A
U
T
O
Fan: In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.

Cool: In this mode of operation, the compressor will be ON after a delay depending on the differential of room
temperature & Set temperature.
Heat: In this mode of operation, Fan is ON.
Auto: In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Ther-
mostat automatically switches to maintain the desired temperature.
DIP SWITCH OPTIONS AND FUNCTIONS
There are 4 small DIP (Dual in line package) switches on the back of the circuit board which must be configured by
the installer.
HOOK-UP WIRING DIAGRAM
DIP SWITCH SELECTION ( THERMOSTAT CONTROLLER TO AIR HANDLING UNIT )
SWITCH ON OFF
1 N. A. - THERMOSTAT
(ZAC P/N 80065261)

2 N. A. -
3 N. A. - NOTE: OPTIONAL CONNECTION :
Y2
IF REMOTE TEMPERATURE SENSING W1
4 INDOOR SENSOR REMOTE SENSOR FUNCTION IS REQUIRED.
Y1
SENSOR
ACCU CONTROL PANEL REMOTE G
Note: SENSOR
24V(R)
Keep DIP SWITCH 1, 2 & 3 in OFF COMPRESSOR FAULT SIGNAL
(VOLT-FREE CONTACT) ATB 24V(C)

position only. COMP 1

COMP 2
( OPTIONAL CONNECTION )
FAULT 1
FAULT 2
W2

(COMMON)

AHU CONTROL PANEL

LVTB
R
24V ac
C
SUPPLY FAN CONTROL
G
STG1 COOLING
Y1
STG2 COOLING
Y2
LEGEND: STG1 HEATER
W1
ATB AUXILIARY TERMINAL BLOCK STG2 HEATER
W2
LVTB LOW VOLTAGE TERMINAL BLOCK

37
INSTALLATION INSTRUCTIONS
A. GENERAL
Blower units are shipped completely wired. Only external power, interconnecting control wiring between outdoor and indoor
units and refrigerant pipe connections are needed to complete the installation. For detailed instructions/informations, please
refer to corresponding IOM manual.

B. UNIT LOCATION & ACCESS SPACE


The placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be kept
on the service access side and return air side.
When making tubing connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATION
Do not remove plugs from the compression fittings until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required with a tube cutter carefully. Do not use a hacksaw.
c. Remove burr from inside and outside using file or deburring tool.
NOTE: Always use a gear type tube bender when making bends in suction line.
When installing tubing through walls or along side of any structural members, be sure the tubing is isolated from these
members or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
NOTE: Use copper wires of proper rating for all field wiring.
Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one
disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram. Connect ground wire to the ground lug inside the control box.
C) Wiring
1. All wiring must comply with the "National Electric Code" and local electrical standards.
2. The power supply, voltage, frequency and phase must coincide with the unit nameplate.
3. Power wiring to the equipment must be adequately sized for maximum ampacity as shown on unit name plate; but not
less than 14 gauge (2.5 mm2) for lower amps.
4. For control wiring, Use 16 gauge color-coded wire between the indoor and outdoor units. Use approved thermostat wire
[minimum 18 gauge (0.75 mm2)], color coded wires. Then match the auxiliary terminal block (ATB) numbers (indoor and outdoor
units) to interconnect the two units. Never use telephone wire for this purpose.
5. Install adequate branch disconnect switch as per NEC size requirements to handle unit starting current. Locate discon-
nect switch within sight and readily accessible from the unit.

STEP 2: START-UP
Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging method details.
STEP 3: SEQUENCE OF OPERATION
With power supplied to indoor and outdoor units, the unit starts responding to the thermostat mode requirement.
Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on. The compressor
contactor is energized to start the compressor and condenser fan.
As the conditioned space approaches the thermostat cooling set point, the unit cycles off.
Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor for
electric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heaters
installed, the second heater also will be energized.
Once, the conditioned space approaches the desired temperature set point, the heating stages cycles off.
Fan mode: In this mode the indoor unit blower motor is switched on alone.

38
PL-AP-BYS-13-2M-E