PCS-931S X Operation+and+Commissioning+Manual EN Overseas+General X R1.00
PCS-931S X Operation+and+Commissioning+Manual EN Overseas+General X R1.00
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and benefits
afforded under P.R. China and international copyright and patent laws in its products, including but
not limited to software, firmware and documentation. NR Engineering Co., Ltd. is licensed to use
this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd,
including but not limited to copyright, rights in inventions, patents, know-how, trade secrets,
trademarks and trade names, service marks, design rights, database rights and rights in data, utility
models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered sufficiently
for your purposes, please do not hesitate to contact us.
Preface
Preface
The manual describes operation and commissioning for PCS-931S Line Differential Relay. The
operation part contains instructions on how to operate the device. It provides instructions for the
monitoring, controlling and setting of the device. The commissioning part provides procedures for
the checking function and configuration as well as verifying settings by secondary injection. It
describes the process of testing device in a substation which is not in service and can also be used
by engineers and maintenance personnel for assistance during the service and maintenance
activities.
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for personal
safety, as well as to avoid material damage. Information is highlighted and illustrated as follows
according to the degree of danger:
Indicates that property damage can result if the measures specified are
not taken.
Contact with instrument terminals can cause electrical shock that can result
in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have ONLY qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
DO NOT look into the end of an optical cable connected to an optical output.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage can
result otherwise.
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.
Document Conventions
⚫ The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.
For example: the access path of protection settings is: MainMenu -> Settings -> Protection
Settings
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫ Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
Symbols
⚫ AND Gate
⚫ OR Gate
⚫ Comparator
BI xxx
⚫ Signal input
SIG xxx
⚫ Setting input
SET xxx
⚫ Enable input
EN xxx
⚫ Timer
Timer
t
t
⚫ Timer
10ms 2ms
⚫ Timer
[Tset1] 0ms
⚫ Timer
0ms [Tset2]
⚫ Timer
[Tset1] [Tset2]
⚫ Generator
⚫ Transformer
⚫ Reactor
⚫ Motor
⚫ Capacitor
⚫ Busbar
⚫ Circuit breaker
52
⚫ Current transformer
3CT
*
⚫ Voltage transformer
3VT
⚫ Disconnector
⚫ Earth
Basic
A, B, C L1, L2, L3 R, Y, B
AN, BN, CN L1N, L2N, L3N RN,YN, BN
ABC L123 RYB
U (voltage) V U
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This document describes how to view and operate the device. And How to test the device at
different stages to verify that the hardware and software functions of the device are intact, and the
function configuration meets the requirements.
1 Introduction
Introduces summarizes functions and typical applications of the device.
2 HMI Overview
Introduce the hardware of the human machine interface (HMI) module.
3 HMI Operation
Introduces a detailed guide for the user how to use this relay through HMI. It also lists all the
information which can be view through HMI, such as settings, measurements, all kinds of reports
etc.
4 PCS-Studio Operation
Introduce the online viewing and operation of PCS-Studio software
5 Test Preparation
Preparation before test, including test principle, precautions, and test equipment.
Version
Release Date Description of change
Document Firmware
1 Introduction 1
Table of Contents
1.1 Application 1
PCS-931S protect overhead and underground lines, feeders, and cables on all voltage levels with
highest possible selectivity. The devices contain all important auxiliary functions that are necessary
today for safe network operation. This includes control, measurement and monitoring functions.
The PCS-931S is widely adopted not only for conventional substations, but also for digital
substations.
1.2 Functions
Busbar
3VT
52
85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
*
78 FL
81O 27P
81U 81R
Line
1.2.1 Protection
⚫ CT saturation detection
85 Pilot distance protection ⚫ Independent pilot zone (forward direction and reverse
scheme
Pilot directional earth-fault
⚫ PTT, Blocking and Unblocking
protection
⚫ Current reversal logic
⚫ Up to 6 zones
each zone
each zone
characteristics
circuit breaker
62PD Pole discrepancy protection
⚫ Optional auxiliary criterion (zero-sequence current
lines
1.2.2 Control
⚫ Circuit breaker & disconnector control (Remote/local)
⚫ Calculate synchronized phasors, including: Ua, Ub, Uc, U1, U2, U0, Ia, Ib, Ic, I1, I2, I0
⚫ Calculate analog values, including: active power (P), reactive power (Q), frequency,
ROCOF (df/dt)
⚫ Transmit binary status of the IED to PDC (Phasor Data Concentrator) according to IEEE
C37.118 standard
⚫ Realize high accurate measurement of the phasors and analogs according to the IEEE
C37.118.1-2011 and IEEE C37.118.1a-2014 standard.
1.2.4 Measurement
⚫ Current and voltage measurement at a 2.4KHz sampling rate
⚫ Energy metering (active and reactive energy are calculated in import respectively export
direction)
⚫ Power (Apparent/Real/Reactive)
⚫ Power factor
⚫ Frequency
1.2.5 Recording
⚫ Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
⚫ 64 travelling wave fault location (TWFL) records (The file format of disturbance recorder
is compatible with international COMTRADE file.)
⚫ VT circuit supervision
⚫ CT circuit supervision
⚫ Self diagnostic
⚫ IEC 60870-5-103
⚫ DNP3.0
⚫ Modbus
⚫ IEC 61850-9-2LE SV
⚫ PPS: Pulse per second (PPS) via RS-485 differential level, binary input or BNC
⚫ PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
⚫ IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
⚫ NERC CIP
⚫ IEC 62351
⚫ IEC 62443
⚫ IEEE 1686
⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment
⚫ Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
⚫ Configuration tool—PCS-Studio
1.2.14 Miscellaneous
1
⚫ User programmable logic
2 HMI Overview
Table of Contents 2
2.1 General Description......................................................................................... 2-1
2.2 LCD Display ..................................................................................................... 2-2
2.2.1 Overview ............................................................................................................................... 2-2
List of Figures
The operator can access the device from the front panel. Local communication with the device is
possible using a computer via a multiplex RJ45 port on the front panel. Furthermore, remote
communication is also possible using a PC with the substation automation system via rear Ethernet
port or rear RS485 port. The operator can check the protective device status at any time.
2
2.1 General Description
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user.
1 LCD Local LCD screen for device status and information display
2 2 Keypad Easy-to-use keypad aids simple navigation and set-point adjustment
Push buttons for opening/closing operation and switching of local/remote
3 Shortcut Key
control mode
4 Shortcut Key Push button for user login/logout of authority management
5 Function Key 4 Programmable operator pushbuttons with user-configurable labels
6 Communication port Front RJ45 multiplex port for debugging
7 Shortcut Key Target reset
Two LED indictors for device running status
8 Fixed LED
“HEALTHY” (green) and “ALARM” (yellow)
Programmable LED indicators with configurable labels (18 for 1/1 or 1/2
9 Programmable LED
variant, 15 for 1/3 variant)
2.2.1 Overview
There are some kinds of LCD display, SLD (single line diagram) display, disturbance records,
supervision events, IO events, control logs and device logs. Disturbance records and supervision
events will not disappear until them are acknowledged by pressing the “RESET” button in the
protection panel (i.e. energizing the binary input [BI_RstTarg]). If any event is detected, the
corresponding event display will pop up automatically, and user can keep pressing “ENT” and then
press “ESC” to switch between normal display and event display. IO events will be displayed for 5s
and then it will return to the previous display interface automatically. Device logs will not pop up
and can only be viewed by navigating the corresponding menu.
After the device is powered and entered into the initiating interface, it takes tens of seconds to
complete the initialization of the device. During the initialization of the device, the “HEALTHY”
indicator lamp of the device goes out.
Under normal condition, LCD will display the following interface. LCD adopts white color as its
backlight that is activated if once there is any keyboard operation, moreover, the backlight will be
extinguished automatically if no keyboard operation is detected for a duration.
Q1
Ua:
Ub:
135.15
134.39
kV
kV
2
Uc: 135.29 kV
Ia : 358.15 A
Q0
Ib : 359.35 A
Ic : 360.28 A
Q3
The content displayed on the screen contains: the current date and time of the device (with a format
of yyyy-mm-dd hh:mm:ss:), the active setting group number The device can also display single line
diagram (SLD) and primary operation information if that had been configured by PCS-Studio tool.
If all information cannot be fully displayed within one screen, they will be scrolling-displayed
automatically from the top to the bottom.
If IP address of Ethernet A is “xxx.xxx.a.b”, the displayed address equals to (a×256+b). For example,
If IP address of Ethernet A is “198.087.095.023”, the displayed address will be “95×256+23 =
24343”.
If the device has detected any abnormal state, it′ll display the self-check alarm information.
“S” indicates that device clock is synchronized. If “S” disappears, it means that device clock is not
synchronized.
This device can store up to 32 groups of disturbance records with fault waveform. Each group
consists of disturbance records of operation elements and corresponding fault detector elements.
Up to 1024 disturbance records can be stored in this device. If there is protection element operation,
LCD will automatically display the latest group of disturbance records, and two kinds of LCD display
interfaces will be available depending on whether there are supervision events or not.
For the situation that the disturbance records and the supervision events coexist, the upper half
part is the disturbance record, and the lower half part is the supervision event. The following items
are listed in the upper half part: record No., record name, generation time of the disturbance record.
If there is protection element operation, faulty phase and relative operation time (with reference to
the corresponding fault detector element) will be displayed. If the disturbance records can not be
displayed in one page, they will be displayed in several pages alternately.
If there is no supervision event, disturbance records will be displayed as shown in the following
figure.
0000ms FD.DPFC.Pkp
2 0024ms AB 21Q.Z1.Op
If the device has the supervision event, the display interface will show the disturbance record and
the supervision event at the same time.
0000ms FD.DPFC.Pkp
0024ms AB 21Q.Z1.Op
Superv Events
Alm_Device
2021-01-15 13:22:23:669 shows the time of the disturbance record, the format is “yyyy-mm-
dd hh:mm:ss:fff”.
0000ms FD.DPFC.Pkp shows fault detector element and its operation time (set as
“0000ms” fixedly).
0024ms AB 21Q.Z1.Op shows operation element and its relative operation time (with
reference to the corresponding fault detector element).
All the protection elements have been listed in chapter “Operation Theory”, and please refer to
each protection element for details. The reports related to oscillography function are showed in the
following table.
This device can store 1024 pieces of supervision events. During the running of the device, the
supervision event of hardware self-check errors or system running abnormity will be displayed
immediately.
S Superv Events
Alm_Device
Alm_Version
Alm_Version
This device can store 1024 pieces of binary events. During the running of the device, the binary
input will be displayed once its state has changed, i.e. from “0” to “1” or from “1” to “0”.
BI_Maintenance 0 1
2021-01-15 13:31:24:339 shows date and time when the report occurred, the format is “yyyy-
mm-dd hh:mm:ss:fff”.
BI_Maintenance 0→1 shows the state change of binary input, including binary input
name, original state and final state.
2.3 Keypad
E NT
1. “MENU”
2. “ESC”:
3. “ENT”:
◼ Page up/down
This device provides the following keys on the front HMI panel to quickly realize frequently-used
functions.
Switching of Remote and Local Two LEDs are equipped to indicate current remote/local control
control mode for control function mode.
This device provides four keys (F1, F2, F3 and F4) for programmable rapid functions, such as an
2 input signal, a quick execution of menu command or a direct access to sub-level menu path.
F1
F2
F3
F4
◼ Input signal: an unlatched signal (500ms pulse, programmable) or a latched signal (flip-
flop mechanism, programmable).
◼ Command Menu: a pre-set execution operation from device LCD menu for local command,
device debugging, authority management, etc.
◼ View Menu: a pre-set access operation from device LCD menu for visualization of
measured quantities, recorded events, signal status, etc.
Front RJ45 debug port for connection to a portable computer is at the bottom left of the panel.
By default, the IP address of front debugging port is “100.100.100.100” with the subnet mask
“255.255.000.000”.
HEALTHY
ALARM 2
Steady Green Lit when the equipment is in service and ready for operation.
Other LED indicators with no labels are configurable and user can configure
them to be lit by signals of operation element, alarm element and binary
output contact according to requirement through PCS-Studio software, but
as drawn in figure, “HEALTHY” LED is fixed as green, 19 LEDs are
configurable with selectable color among green, yellow and red. And the
3 HMI Operation
Table of Contents
List of Figures
Press “MENU” and enter the main menu. The menu is divided into 10 sections:
3
Measurements
Status
Records
Settings
Print
Local Cmd
Information
Test
Clock
Language
The command menu adopts a tree shaped content structure. The above diagram provides the
integral structure and all main menus (first-level menus) under menu tree of the device.
The name of menu structure directory expresses the function of this menu. For detailed menu
operation, please refer to chapter 3.2 Keypad Operation.
The menu will not be displayed if the function is disable into the public
configuration.
MainMenu
Language
Clock
Quick Menu
For the first powered device, there is no record in quick menu. Press “MENU” to enter the main
menu with the interface as shown in the following diagram:
Measurements
Status
Records
Settings
Print
Local Cmd
Information
Test
Clock
Language
Press “MENU” and enter the main menu. Select different submenu by “▲” and “▼”. Enter the
selected submenu by pressing “ENT” or “►”. Press “◄” and return to the previous menu. Press
“ESC” back to main menu directly. For sake of entering the command menu again, a command
menu will be recorded in the quick menu after its execution. Five latest command menus can be
recorded in the quick menu. When five command menus are recorded, the latest command menu
will cover the earliest one, adopting the “first in first out” principle. It is arranged from top to bottom
and in accordance with the execution order of command menus.
The descriptions about menu are based on the maximized configuration, for a specific project, if
some function is not available, the corresponding submenu will be hidden.
This menu is used to display real-time measured values, including AC voltage, AC current, phase
angle and calculated quantities. These data can help users to acquaint the device′s status.
3 This menu comprises following submenus.
Display primary voltage, current, phase angle and calculated quantities. It has several
1 Primary Values submenus, General_Values, Angle_Values, SeqComponent_Values, Power_Values,
Power_Values.
Display secondary voltage, current, phase angle and calculated quantities. It has
2 Secondary Values several submenus, General Values, Angle Values, SeqComponent Values, Power
Values, Power Values.
2. Press the “▲” or “▼” to move the cursor to the “Measurements” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to
enter the menu;
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one display
screen, one screen can display 14 lines of information at most);
6. Press the “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu).
This menu is mainly used to display the state of binary inputs (including binary inputs via opto-
coupler and GOOSE binary inputs) and alarm signals in the device. This menu and “Analog” menu
fully reflect the running environment of the device. This menu is set to greatly facilitate the
debugging and maintenance of people on site.
Enter the menu through the MENU of the panel, select status to enter the status view interface.
3 Superv States
Display supervision alarm states. It has several submenus such as
Device_Superv, GOOSE_Superv, SV_Superv, etc.
3
4 Logic Links Status Display logic links status
2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one display
screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu).
The device can store the latest 1024 time-stamped disturbance records, 1024 time-stamped binary
events, 1024 time-stamped supervision events, 256 time-stamped control logs and 1024 time-
stamped device logs. All the records are stored in non-volatile memory, and when the available
space is exhausted, the oldest record is automatically overwritten by the latest one.
This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.
Enter the menu through the MENU of the panel, select records to enter the records view interface.
The device is under automatic supervision all the time. If there are any failure or
abnormal condition detected, such as, chip damaged, VT circuit failure and so
2 Superv Events
on, it will be logged in event records. Supervision events include signal name, its
value before and after changing, and the time precision is up to 1ms.
When there is a binary input is energized or de-energized, i.e., its state has
changed from “0” to “1” or from “1” to “0”, it will be logged in event records. Binary
3 IO Events
3 events include signal name, its value before and after changing, and the time
precision is up to 1ms.
If an operator executes some operations on the device, such as reboot protective
device, modify setting, etc., they will be logged in event records. Device logs
4 Device Logs
include signal name, its value before and after changing, and the time precision
is up to 1ms.
When an operator executes a control command via local LCD, PCS-Studio or
communication client, it will be logged in control logs. Control logs include time
5 Control Logs
stamp, controlled object, control origination, control position, operation condition,
interlocking condition, control command and operation result.
When an operator executes a regulation command via local LCD, PCS-Studio or
communication client, it will be logged in regulation logs. Regulation logs include
6 Regulation Logs
time stamp, controlled object, control origination, operation condition ,and
operation result.
7 Clear Records Clear all records
2. Press the “▲” or “▼” to move the cursor to the “Records” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT”
to enter the menu;
7. Press the “ENT” or “ESC” to exit this menu (returning to the “Records” menu).
Before putting into operation, we can clear all the reports during commissioning, the operation to
clear the records is as follows:
2. Press the “▲” or “▼” to move the cursor to the “Records” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the “Clear Records” menu, and then press
the “ENT”.
The operation of deleting device message will delete all messages saved
by the protection device, including disturbance records, supervision events,
binary events, but not including device logs. Furthermore, the message is
irrecoverable after deletion, so the application of the function shall be
cautious. 3
Shortcut for clearing record: Exit the main menu, press the “+”, “-”, “+”,
“-” and “ENT”.
2. Press the “+”, “-”, “+”, “-” and “ENT”; Press the “ESC” to exit this menu (returning to
the original state). Press the “ENT” to carry out the deletion.
The operation of deleting device message will delete all messages saved
by the protection device, including disturbance records, supervision events,
binary events, but not including device logs. Furthermore, the message is
irrecoverable after deletion, so the application of the function shall be
cautious.
This menu is used to check the device setup, system parameters, protection settings and logic links
settings, as well as modifying any of the above setting items. Moreover, it can also execute the
setting copy between different setting groups.
3 Meas Control Settings Check or modify the measurement and control settings
Check or modify the logic links settings, including function links, SV links,
4 Logic Links
3 GOOSE links and spare links
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT”
to enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “Settings”).
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT”
to enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “Settings”);
8. If selecting the command menu “System Settings”, move the cursor to the setting item
to be modified, and then press the “ENT”;
Press the “+” or “-” to modify the value (if the modified value is of multi-bit, press the “◄”
or “►” to move the cursor to the digit bit, and then press the “+” or “-” to modify the
value), press the “ESC” to cancel the modification and return to the displayed interface of
the command menu “System Settings”. Press the “ENT” to automatically exit this menu
(returning to the displayed interface of the command menu “System Settings”).
Move the cursor to continue modifying other setting items. After all setting values are
modified, press the “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”. Directly
press the “ESC” or press the “◄” or “►” to move the cursor. Select the “Cancel”, and then
press the “ENT” to automatically exit this menu (returning to the displayed interface of the
command menu “System Settings”). 3
Press the “◄” or “►” to move the cursor. Select “No” and press the “ENT”, all modified
setting item will restore to its original value, exit this menu (returning to the menu
“Settings”).
Press the “◄” or “►” to move the cursor to select “Yes”, and then press the “ENT”, the
LCD will display password input interface.
Password:
____
Input a 4-bit password (“+”, “◄”, “▲” and “-”). If the password is incorrect, continue
inputting it, and then press the “ESC” to exit the password input interface and return to the
displayed interface of the command menu “System Settings”. If the password is correct,
LCD will display “Save Setting Now…”, and then exit this menu (returning to the displayed
interface of the command menu “System Settings”), with all modified setting items as
modified values.
For different setting items, their displayed interfaces are different, but their modification
methods are the same. The following is ditto.
9. If selecting the submenu “Protection Settings”, and press “ENT” to enter. After selecting
different command menu, the LCD will display the following interface: (take “BFP Settings”
as an example)
BFP Settings
Active Group: 01
Selected Group: 01
Press the “+” or “-” to modify the value, and then press the “ENT” to enter it. Move the
cursor to the setting item to be modified, press the “ENT” to enter.
Take the setting [CB1. 50BF.I_Set] as an example is selected to modify, then press the
“ENT” to enter and the LCD will display the following interface. Press “+” or “-” to modify
the value and then press the “ENT” to confirm.
CB1. 50BF.I_Set
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “Copy Settings”, and
then press the “ENT” to enter the menu.
3
Copy Settings
Active Group: 01
Copy To Group: 02
Press the “+” or “-” to modify the value. Press the “ESC” and return to the menu “Settings”. Press
the “ENT”, the LCD will display the interface for password input, if the password is incorrect,
continue inputting it, press the “ESC” to exit the password input interface and return to the menu
“Settings”. If the password is correct, the LCD will display “Settings Copied!”, and exit this menu
(returning to the menu “Settings”).
3.2.9 Print
The device can print out settings, device information, etc., through a directly connected
parallel port printer. The operation is as follows:
2. Press the “▲” or “▼” to move the cursor to the “Print” menu, and then press the “ENT” or
“►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT”
to enter the menu;
Selecting the “Disturb Records”, and then press the “+” or “-” to select pervious
or next record. After pressing the key “ENT”, the LCD will display “Start Printing...”,
and then automatically exit this menu (returning to the menu “Print”). If the printer
does not complete its current print task and re-start it for printing, and the LCD will
display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the menu
“Print”).
Selecting the command menu “Superv Events” or “IO Events”, and then press the
key “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and
ending numbers of printing message. After pressing the key “ENT”, the LCD will
display “Start Printing…”, and then automatically exit this menu (returning to the menu
“Print”). Press the key “ESC” to exit this menu (returning to the menu “Print”).
4. If selecting the command menu “Device Info”, “Device Status” or “IEC103 Info”, press
the key “ENT”, the LCD will display “Start printing..”, and then automatically exit this menu
(returning to the menu “Print”).
3 5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu.
6. After entering the submenu “Settings”, press the key “▲” or “▼” to move the cursor, and
then press the key “ENT” to print the corresponding default value. If selecting any item to
printing:
Press the key “+” or “-” to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu
(returning to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the
menu “Settings”).
7. After entering the submenu “Waveforms”, press the “+” or “-” to select the waveform
item to be printed and press “ENT” to enter. If there is not any waveform data, the LCD
will display “No Waveform Data!” (Before executing the command menu “Waveforms”, it
is necessary to execute the command menu “Trig Oscillograph” in the menu “Local
Cmd”, otherwise the LCD will display “No Waveform Data!”). With waveform data existing:
Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing…”, and then automatically exit this menu (returning to
the menu “Waveforms”). If the printer does not complete its current print task and re-start
it for printing, and the LCD will display “Printer Busy…”. Press the key “ESC” to exit this
menu (returning to the menu “Waveforms”).
This menu is used to input several commands to the device, such as reset target, trigger
oscillograph, change setting group, etc.
1 Reset Target Reset Target, the same function with shortcut key of “Target Reset”
Trigger the recording manually, then the device will record the analog and
2 Trig Oscillograph
digital quantities, and form a disturb record
2. Press the “▲” or “▼” to move the cursor to the “Local Cmd” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command “Change Setting Grp”, and
3
then press the “ENT”;
Active Group: 01
Change To Group: 02
Press the “+” or “-” to modify the value, and then press the “ESC” to exit this menu (returning to
the main menu). After pressing the “ENT”, the LCD will display the password input interface. If the
password is incorrect, continue inputting it, and then press the “ESC” to exit the password input
interface and return to its original state. If the password is correct, the “HEALTHY” indicator lamp
of the protection device will go out, and the protection device will re-check the protection setting. If
the check doesn’t pass, the protection device will be blocked. If the check is successful, the LCD
will return to its original state.
This menu is used to view the device version, board, and selection.
Enter the menu through the MENU of the panel, select Information to enter the information view
interface.
2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the
“ENT” to enter the submenu.
3. Press the key “▲” or “▼” to move the cursor to the command menu “Version Info”, and
then press the key “ENT” to display the software version.
2. Press the key “▲” or “▼” to move the cursor to the command menu “Local Cmd”, and
then press the key “ENT” to enter submenus. Press the key “▲” or “▼” to move the cursor
to the command menu “Control”, and then press the key “ENT” to enter and the following
display will be shown on LCD.
Password:
000
Input a 3-bit password (“111”). If the password is incorrect, continue inputting it, and then press the
“ESC” to exit the password input interface and return to the displayed interface of the command
menu “Control”. If the password is correct, it will go to the following step.
3. Press the key “▲” or “▼” to move the cursor to the control object and press the key “ENT”
to select control object.
Control
Step1: select Control Object
1. CSWI01
2. CSWI02
3. CSWI03
4. CSWI04
5.
6.
CSWI05
CSWI06 3
7. CSWI07
8. CSWI08
9. CSWI09
10. CSWI10
4. Press the key “◄” or “►” to select control command press the key “ENT” to the next step.
3) Stop: Reserved
CSWI01
Step2: select Control Command
InterlockChk InterlockNotChk
Result
5. Press the key “◄” or “►” to select synchronism check mode and press the key “ENT” to
the next step.
4) LoopCheck: Reserved
CSWI01
Step3: select Execution Condition
3 NoCheck
LoopCheck
SynchroCheck
EF Line Selection
DeadCheck
InterlockChk InterlockNotChk
Result
6. Press the key “◄” or “►” to select interlock mode and press the key “ENT” to next step.
CSWI01
Step4: select Interlock Condition
InterlockChk InterLockNotChk
Result
7. Press the key “◄” or “►” to select control type and press the key “ENT”.
As shown in the following figure, operation results will be shown after “Result” at the bottom of the
LCD.
CSWI01
Step5: select Control Type
InterlockChk InterLockNotChk
3
Select Execute Cancel
Result
The control operation (close or open) also can be executed on the single line diagram (SLD) of the
default display under normal operation condition. The signs of the circuit breaker (abbreviated as
CB) and switch (DS or ES) are listed in the following table.
An example of normal display with SLD is shown in the following figure. The single line diagram of
the default display on the LCD is shown as below when the device is in normal situation if this
device adopts the single line diagram as default display.
Bus1
Bus2
M011 M0112
3
M0131
M01
M0151
M0171
Feeder M01
In SLD display, press "▲" or "▼" to select a switchgear to be opened/closed, and then press key
"ENT" to control selected CB/switch. After the selection of an open or close operation, the
confirmation window will be valid for a short duration after inputting the correct control password.
This password is configurable by the setting [Ctrl_Password] in the menu “Device Settings”. A
control operation result of success or fail will be returned at last.
2) Note: From the last step, press “ENT” to popup this operation selection window.
CSWI**
Open Close 3
CSWI** open/close
Password: xxx
4) Use "←", "→" and "ENT" to confirm or cancel the control operation.
CSWI** open/close
Open Close
5) Check the operation success or fail result from the control report.
CSWI** open/close
In SLD display, press "▲" or "▼" to select a switchgear to be opened/closed, and then press key
"ENT" to control selected CB/switch. Press the open or close button on the HMI panel and the
confirmation window will be valid for a short duration after inputting the correct control password.
This password is configurable by the setting [Ctrl_Password] in the menu “Device Settings”. A
control operation result of success or fail will be returned at last.
2) From the last step, press a control button to popup this window. Consult or modify the
password through [Ctrl_Password] in "Device Settings".
CSWI** open/close
Password: xxx
3
3) Use "←", "→" and "ENT" to confirm or cancel the control operation.
CSWI** open/close
Open Close
4) Check the operation success or fail result from the control report.
CSWI** open/close
2. Press the key “▲” or “▼” to move the cursor to the “Test” menu, and then press the key
“ENT” or “►” to enter the menu.
3 3. Press the key “▲” or “▼” to move the cursor to the submenu “Device Test”, and then
press the key “ENT” to enter the submenu, to select test item. If “Disturb Events” “Superv
Events” or “IO Events” is selected, two options “All Test” and “Select Test” are provided.
4. Press the key “▲” or “▼” to move the cursor to select the corresponding command menu
“All Test” or “Select Test”. If selecting the “All Test”, press the “ENT”, and the device will
successively carry out all operation element message test one by one.
5. If “Select Test” is selected, press the key “ENT”. Press the “+” or “-” to page up/down,
and then press the key “▲” or “▼” to move the scroll bar. Move the cursor to select the
corresponding protection element. Press the key “ENT” to execute the communication test
of this protection element, the substation automatic system (SAS) will receive the
corresponding message.
Press the key “ESC” to exit this menu (returning to the menu “Test”, at this moment, the LCD will
display “Communication Test Exiting…”.
2. Press the “▲” or “▼” to move the cursor to the “Clock” menu, and then press the “ENT”
to enter clock display
3. Press the “▲” or “▼” to move the cursor to the date or time to be modified;
4. Press the “+” or “-” to modify value, and then press the “ENT” to save the modification and
return to the main menu;
5. Press the “ESC” to cancel the modification and return to the main menu.
Move the cursor to select the item “Format” to setup time display format.
2. YYYY/MM/dd
3. DD-MM-YYYY
4. DD/MM/YYYY
3
5. MM-DD-YYYY
6. MM/DD/YYYY
Clock
Year: 2020
Month: 11
Day: 28
Hour: 20
Minute: 59
Format: YYYY/MM/DD
2. Press the key “▲” or “▼” to move the cursor to the command menu “Language”, and
then press the key “ENT” to enter the menu and the following display will be shown on
LCD.
1. 中文
2. English Configured by
3. XXXX PCS-Stuido
3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press the
key “ENT” to execute language switching. After language switching is finished, LCD will
return to the menu “Language”, and the display language is changed. Otherwise, press
the key “ESC” to cancel language switching and return to the menu “Language”.
3
LCD interface provided in this chapter is only a reference and available for
explaining specific definition of LCD. The displayed interface of the actual
device may be some different from it, so you shall be subject to the actual
protection device.
4 PCS-Studio Operation
Table of Contents
List of Figures
4.1 Overview
The device can be remotely debugged through the TelDevice tool integrated in PCS-Studio.
Connect the commissioning laptop with the device through an Ethernet cable. Then open PCS-
Studio tool and select “Tools” →“Online Status Tool” →“TelDevice”, type device name and
device address to connect with the device. After connected, it will display as below:
Zone 1: LED status display zone: which is used to display the LED status of the device. If no LED
is configured in the PCS-Studio tool, only the default Healthy and Alarm LED will be
displayed here.
Zone 2: Menu display zone: which is used to display the corresponding submenu of this device.
Zone 3: Detailed information display zone: which is used to display specific information under the
submenu.
Through the PCS-Studio tool user can view the setting value.
Through the PCS-Studio tool user can modify the setting value.
Take the modification of CB1. 50BF.I_Set as an example.
1. Select “Settings” → “Protection Settings” → “BFP Settings” in the menu.
4
Figure 4.5-4 Modify settings diagram 4
Right click on a disturb records and select “Records”, the tool will upload waveform. After the
waveform upload is completed, it will be automatically opened. Wave files are saved in the file
“PCS-Studio-Customer\bin\wave\directory\”.
The device can switch the setting group by modifying “Active_Grp” in “Settings”-> “Global
5 Test Preparation
Table of Contents
5.1 Overview
This relay is fully numerical in their design, implementing all protection and non-protection functions
in software. The relay employs a high degree of self-checking and in the unlikely event of a failure,
will give an alarm. Because of this, the commissioning test does not need to be as extensive as
with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.
The on-site installation and commissioning test mainly check whether the equipment is correctly
set, and verifies that the wiring of all external circuits is correct. The setting test includes the on-
site configuration, the reasonableness and correctness of the protection settings. The external
circuit detection can detect the correctness of the sampling circuit by Inject the current and voltage
on the primary side of CT and VT, and the correctness of the tripping, opening, and alarming circuits
through the transmission test.
Periodic maintenance tests during operation mainly check whether the equipment is operating
normally and whether the external circuit is normal.
Only qualified personnel should work on or in the vicinity of this device. The
personnel should be familiar with all safety regulations and service
procedures described in this manual. During operating of electrical device,
certain part of the device is under high voltage. Severe personal injury and
Before performing any operation on the device, the user should be familiar
with the contents of the safety instructions, the technical parameter chapters,
and the rated parameters marked on the device nameplate.
⚫ Before making other electrical wiring, you must ensure that the device's grounding post is
reliably connected to the protective ground.
5 ⚫ Hazardous voltages may exist in all circuits and components associated with the unit's
power supply and sampling circuits, and even when the power is disconnected, dangerous
voltages (in storage capacitors) may exist.
⚫ During the debugging process, the input voltage and current must be within the range
specified in the technical parameter table, and must not exceed the specified range.
⚫ When the device is tested with a secondary test device, it must be ensured that no other
AC quantities are added.
⚫ Unless otherwise specified, it is necessary to disconnect the trip / close circuit connected
to the circuit breaker or other primary switch from the device.
⚫ Because the CT secondary circuit may generate high voltage that may cause personal
injury or damage the equipment, it is necessary to ensure that the CT secondary circuit
must be shorted before disconnecting the current Inputted to the device.
⚫ Transient (dynamic) switching between pre-fault and post-fault conditions (to generate
delta conditions),
⚫ A portable computer, installed with appropriate software to liaise with the equipment under
test (EUT). Typically this software will be proprietary to the product’s manufacturer (for
example PCS-Studio).
The device has several sets of protection settings to correspond to different system operation
modes. Only a set of current settings is effective. However, communication settings, system
settings, device settings, logical link settings, and measurement and control settings are common.
Device global settings include system settings, equipment settings, communication settings,
recording settings, clock synchronization settings, and alarm settings.
5
The device measurement and control settings include function settings, synchronization settings,
dual position settings, control settings, interlocking values, and power settings.
Device commissioning software is PCS-Studio. The software can connect with the device through
an ethernet cable directly. The IP address of the console port on the front side of the device is fixed
as 100.100.100.100. Through the connection of the tool and the device, operations such as
remotely checking data and setting values, modifying the setting values, and uploading the record
waves can be realized.
Table of Contents
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed is
necessary.
⚫ Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct
for the installation.
⚫ Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section meeting 6
the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
⚫ Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipment on the panel to make sure that they are well
installed into the equipment without any screw loosened.
⚫ Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation tester
at a DC voltage not exceeding 500V, the circuits need to be tested should include:
⚫ DC power supply
⚫ Output contacts
⚫ Communication ports
Test method:
To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each circuit
above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
6
Check whether the external wiring of the device is consistent with the device wiring diagram and
engineering design drawing, and at the same time ensure that the actual phase sequence of the
wiring is the same as the pre-designed phase sequence.
Check the wiring against the installation principle drawing to ensure that the wiring is consistent
with the customer's actual application.
The device can work normally with DC/AC power supply, and the power supply voltage depends
on the rated power supply parameters. The input power supply voltage must be within the range
specified in the following table to ensure the normal operation of the device.
110Vdc/125Vdc/ 100Vac/110Vac/115Vac/120Vac/
Rated voltage
220Vdc/250Vdc 127Vac/220Vac/230Vac/240Vac/250Vac
IEC 61000-4-11:2017
IEC 61000-4-29:2000
IEC 61000-4-29:2000
Permissible voltage range
IEC 60255-26:2013
88~300Vdc
≤15% of the nominal auxiliary voltage
NR6311A DC Supply
24Vdc/30Vdc/
Rated voltage
48Vdc/60Vdc
Before powering on the device, make sure that the power supply voltage is
within the specified operating voltage range..
Table of Contents
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that they are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “Clock”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore, when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being re-
energized, the time and date should be correct.
7
7.3 LED Indicators
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that the
relay is healthy.
The relay has latched signal relays which remember the state of the trip when the relay was last
energized from an auxiliary supply. Therefore, these indicators may also illuminate when the
auxiliary supply is applied. If any of these LEDs are on then they should be reset before proceeding
with further testing. If the LED successfully reset, the LED goes out.
Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We need
to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment finds serious errors in it.
Produce one of the abnormal conditions, the “ALARM” LED will light in yellow. When abnormal
condition reset, the “ALARM” LED extinguishes.
Enter the menu "Test"-"HMI Setup"-"SupervLED" to check whether the programmable LEDs are
normal.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relay menu.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relay menu.
The measurement accuracy of the relay is 2.5% or 0.1V. However, an additional allowance must
be made for the accuracy of the test equipment being used.
7
While testing VT secondary circuit and associated secondary equipment,
care shall be exercised to isolate the VT from the circuit being tested to
avoid back charging the VT from the secondary side.
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for terminal
numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
Test method:
The status of each binary input can be viewed using relay menu. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input.
To unplug all the terminals sockets of this protective device, and do the insulation resistance test
for each circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
When the device undergoes an operational check, a tripping pulse is normally obtained on one or
more of the output contacts and preferably on the test switch. The healthy circuit is of utmost
importance for the protection operation. If the circuit is not provided with a continuous trip-circuit
supervision, it is possible to check that circuit is really closed when the test-plug handle has been
removed by using a high-ohmic voltmeter and measuring between the plus and the trip output. The
measurement is then done through the trip coil of the circuit breaker and therefore the complete
trip circuit is checked.
Enter the menu "Test"-"Device Test"-"Contact Outputs" to check the binary output one by one.
The binary outputs test will trip the switch, and when the binary outputs are
connected to the binary input of other devices, the input of other devices will
be energized.
Connect the standard time synchronization source to the corresponding interface of the device,
such as IRIG-B, IEEE1588 or SNTP synchronization source. After a few minutes, the "S" mark will
7
display in the upper left corner of the LCD, indicating that the clock of the device is synchronized
normally.
The LED configured for time out of step alarm will be active when the source of the time
synchronization is lost. The device can hold the time for a period and the device has full
functionality without time synchronization, but the clock may have some deviation. The time
source and network connection need to be checked. After troubleshooting, the device keeps
consistent with the time source.
The device supports multiple protocols to communicate with the SCADA system. The protocols
include IEC61850 Ed1 & Ed2, Modbus, DNP3.0, and IEC60870-5-103.
Table of Contents
8.1 Report Records ................................................................................................ 8-1
8.2 Test Content and Purpose .............................................................................. 8-1
8.3 Differential protection (87L) ............................................................................ 8-1
8.3.1 Setting List ............................................................................................................................ 8-1
During the operation of the device, it can record the information such as the input position, abnormal
alarm, operation log, as well as fault recording and fault event report. Opening position change and
abnormal alarm information can be cyclically recorded 1024, fault record and fault event report can
be cyclically recorded 64.
Through the MENU → Records → Disturb Records, you can view the fault event report, and you
can find the previous fault event report by pressing the “+” or “-” button. Superv Events or IO
Events can be viewed in the same way.
You can also use a PC with the TelDevice online tool to read device event records and fault records.
By connecting the debug port (RJ45) on the front panel or the communication port on the back
panel, the report records will be automatically sent to the TelDevice. The fault record data is a
standard COMTRADE format file, which can be analyzed using any waveform analysis tool that
supports this format.
Protection function test verify the correctness of protection logic, and puts forward suggestions on
8
the settings for commissioning.
The test data is calculated according to the device accuracy and tester
accuracy, so the test results may be different when using different test
instruments. For example: Max {1% × 50 / 51p1. I_ Set, 0.01A} means that
the current value to be injected is the larger value of 1% current accuracy
and 0.01A.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
N of three phase and connect it back to the “In” of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
IDiffΦ
k=1
k2
k1
IH
IBiasΦ
Knee1 Knee2
̇ + 𝐼NΦ
𝐼DiffΦ = |𝐼MΦ ̇ |
̇ | + |𝐼NΦ
𝐼BiasΦ = |𝐼MΦ ̇ |
Where:
𝐼𝐻 : max(1.5×[87L.I_Pkp], 1.5UN/XC1L)
Put a jumper to connect the RX and TX of the relay by a single mode FO to make a loopback circuit.
In this case, if we inject 1A current to the relay, there will be 2A differential current . The settings of
the FO communication channel should be as follows.
The pickup value for stage 1 of 87_Biased is 1.5 times of [87L.I_Pkp] setting. 8
Using “State Sequencer” testing module with two states:
1.5 1.5
Fault 1: The faulty phase current = ×[87L.I_Pkp]+ ×Max {5%×[87L.I_Pkp], 0.02In}
2 2
1.5 1.5
Fault 2: The faulty phase current = ×[87L.I_Pkp]- ×Max {5%×[87L.I_Pkp], 0.02In}
2 2
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
100ms
Inject IA /IB /IC with 0A. Trigger condition is set to timed trigger, state duration = 6s
Simulate the single-phase grounding fault, The faulty phase current = 2×1.5× [87L.I_Pkp].
The trigger condition can be set to binary input or timed trigger, and the state duration =
50ms.
The The 87L _Biased1 should operate reliably, the operation time ≤30ms.
In this test, we put two devices in one place .Connect two relays with two single mode FO jumpers.
The Rx and Tx of FO module on two relays connect crosswise. Set the local relay FO ID as 1 and
the remote relay FO ID as 2.The setting of FO communication is as follows:
RmtCommCh Settings
Local Remote
No. Symbol Value No. Symbol Value
1 FO.LocID 1 1 FO.LocID 2
2 FO.RmtID 2 2 FO.RmtID 1
3 FO.BaudRate 2048KBPS 3 FO.BaudRate 2048KBPS
4 FO.Protocol G.703 4 FO.Protocol G.703
5 FO1.Nx64k_C37.94 12 5 FO1.Nx64k_C37.94 12
6 FO1.Opt_ClkSrc Int 6 FO1.Opt_ClkSrc Int
7 FO1.En Enabled 7 FO1.En Enabled
No. 87L.I_Knee Local (A) Remote (A) I_diff (A) I_res (A)
Simulate the single-phase grounding fault, the phase angle between two sides is 180°.
Fault 1: The faulty phase current of local side = 1.05×0.7 = 0.735A, the faulty phase
current of remote side = 0.1A.
8
Fault 2: The faulty phase current of local side = 0.95×0.7 = 0.665A, the faulty phase
current of remote side = 0.1A.
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
100ms
According to the above table, complete the test from Case 01 to Case 06.
8
“Protection Device” should be set as follows:
Add the low slope and the high slope characteristics line.
8
“Test View” should be set as follows:
Choose the “Search Test”→“Add Sweep...” →“Add Multiple”to add test items. Set the parameter
as the following picture. Choose the faulty type as “L1-E”.
According to the same method as above,we can test the phase-segregated DPFC current
differential element,phase-segregated steady-state current differential element and neutral current
differential element protection in sequence.
[87L.En_CTS_Blk] = Disable
Ia/Ib/Ic = 1.1×[CTS.3I0_Set]
Simulate failure of single-phase on CT, the abnormal phase current = 0 A, the current of
other two phase and the voltage of three phase keeps the same with that in stage 1.
8
The trigger condition can be set to “timed trigger”, and the state duration > [CTS.t_DPU].
1 1
Fault 1: The faulty phase current = ×[87L.I_Pkp_CTS]+ ×Max {5%×[87L.I_Pkp_CTS],
2 2
0.02In}
1 1
Fault 2: The faulty phase current = ×[87L.I_Pkp_CTS]- ×Max {5%×[87L.I_Pkp_CTS],
2 2
0.02In}
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
50ms
[87L.En_CTS_Blk] = Enable
Ia/Ib/Ic = 1.1×[CTS.3I0_Set]
Simulate failure of single-phase on CT, the abnormal phase current = 0 A, the current of
other two phase and the voltage of three phase keeps the same with that in stage 1.
The trigger condition can be set to “timed trigger”, and the state duration > [CTS.t_DPU].
1
The faulty phase current = ×1.1×[87L.I_Pkp_CTS]
2
8
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
50ms
3 21L1.phi1_Reach 78
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
function disabling signal must be de-energized.
When m=1.4, 21D will trip, when m=0.9, 21D will not trip.
Fault 1: The faulty phase voltage = 5×( 1 + 0.66 )×5 + ( 1 - 1.4 )×57.74 = 18.4V
Inject faulty current with 5A, the angle of faulty voltage leads the faulty current 78
degrees ([21L1.phi_Reach]).
The trigger condition can be set to “binary input or timed trigger”, and the state duration
= 100ms
Fault 2: The faulty phase current = 5×( 1 + 0.66 )×5 + ( 1 - 0.9 )×57.74 = 47.3V
Inject faulty current with 5A, the angle of faulty voltage leads the faulty current 78
degrees ([21L1.phi_Reach]).
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
100ms
When the DPFC Distance setting is small, it is possible that UØ and UØØ are
calculated as negative numbers. At this time, the fault current needs to be
increased to meet the non-negative values of UØ and UØØ.
When m=1.4, 21D will trip, when m=0.9, 21D will not trip.
Inject faulty phase to phase current with 10A, the angle of faulty phase to phase voltage
leads the faulty phase to phase current 78 degrees ([21L1.phi_Reach]).
The trigger condition can be set to “binary input or timed trigger”, and the state duration
= 100ms
Fault 2: The faulty phase to phase current = 10×5 + ( 1 - 0.9 )×100 = 60V
Inject faulty phase to phase current with 10A, the angle of faulty phase to phase voltage
leads the faulty phase to phase current 78 degrees ([21L1.phi_Reach]).
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
100ms
When the DPFC Distance setting is small, it is possible that UØ and UØØ are
calculated as negative numbers. At this time, the fault current needs to be
increased to meet the non-negative values of UØ and UØØ.
8 6
7
21L.ZG.Opt_Characteristic
21L.ZP.Opt_Characteristic
Quad
Quad
23 21L1.ZP.Z_Set
24 21L1.ZP.R_Set
5.000
9.6
8 21L1.Real_K0 0.660 25 21L1.ZP.R_Offset 1.000
9 21L1.Imag_K0 0.000 26 21L1.ZP.phi_Shift 0
10 21L1.phi1_Reach 78 27 21L1.ZP.t_Op 0.000
11 21L1.ZG.RCA 12 28 21L1.ZP.En Enabled
12 21L1.ZG.Z_Set 5.000 29 21L1.ZP.En_BlkAR Disabled
13 21L1.ZG.R_Set 9.6 30 21L1.ZP.En_NegDir_Blk Enabled
14 21L1.ZG.R_Offset 1.000 31 21L1.LoadEnch.En Enabled
15 21L1.ZG.phi_Shift 0 32 21L1.En_PSBR Enabled
16 21L1.ZG.t_Op 0.000 33 21L1.En_ReacLine Enabled
17 21L1.ZG.En Enabled
… ……
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
N of three phase and connect it back to the “In” of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
When m =0.95, 21L1 will trip, when m=1.05, 21L1 will not trip.
Inject faulty current with 2A, the angle of faulty voltage leads the faulty current 78
degrees.
Inject faulty current with 2A, the angle of faulty voltage leads the faulty current 78
degrees.
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
[21L1.ZG.t_Op] + 50ms
When m =0.95, 21L1 will trip, when m=1.05, 21L1 will not trip.
Inject faulty phase -to- phase current with 2A, the angle of faulty phase -to- phase
voltage leads the faulty phase -to- phase current 78 degrees.
Inject faulty phase -to- phase current with 2A, the angle of faulty phase -to- phase
voltage leads the faulty phase -to- phase current 78 degrees.
8 The trigger condition can be set to “binary input or timed trigger”, and the state duration =
[21L1.ZP.t_Op] + 50ms
[21L.LoadEnch.R_Set] = 7Ω.
When m =0.95, 21L1 will trip, when m=1.05, 21L1 will not trip.
Inject faulty current with 2A, the angle of faulty voltage leads to the faulty current θ.
-[21L.LoadEnch.phi]≤θ≤+[21L.LoadEnch.phi].
Inject faulty current with 2A, the angle of faulty voltage leads to the faulty currentθ.
-[21L.LoadEnch.phi]≤θ≤+[21L.LoadEnch.phi].
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
[21L1.ZG.t_Op] + 50ms
[21L.LoadEnch.R_Set] = 7Ω.
When m =0.95, 21L1 will trip, when m =1.05, 21L1 will not trip.
Inject faulty phase -to- phase current with 2A, the angle of faulty phase -to- phase
voltage leads to the faulty phase -to- phase current θ.
-[21L.LoadEnch.phi]≤θ≤+[21L.LoadEnch.phi].
Inject faulty phase -to- phase current with 2A, the angle of faulty phase -to- phase
voltage leads to the faulty phase -to- phase current θ.
-[21L.LoadEnch.phi]≤θ≤+[21L.LoadEnch.phi].
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
[21L1.ZP.t_Op] + 50ms
When m =0.7, measure 21L operation time. the operation error time ≤ 1%×Setting+30ms
Inject faulty current with 2A, the angle of faulty voltage leads the faulty current 78
degrees.
The trigger condition can be set to binary input or timed trigger, and the state duration =
50ms.
The 21L1 should operate reliably, the operation error time ≤ Max {1%×[21L1.ZG.t_Op],
30ms }
Set the “line length” and the “line angle” in “System Settings”,and then set the “KL magnitude” and
the “ KL angle”.
Accorde to the setting:impedance of zone-1 is 5Ω, resistance 9.6Ω, phase angle of positive-
sequence impedance of zone-1 is 78 degrees,etc.
Choose the mode as “Line Cartesian”, set R and X as (0, 0 )and the angle as -15°.
Choose the mode as “Line Cartesian”, set R and X as (9.6, 0 )and the angle as 78°.
Choose the mode as “Line polar”, set Z and Phi as (5, 78° ), and the angle as -12°.
Choose the mode as “Line polar”, set Z and Phi as (5, 78° ), and the angle as 180°.
Choose the mode as “Line cartesian”, set R and X as (-1, 0 )and the angle as 90°.
Choose the mode as “Line cartesian”, set R and X as (0, 0 )and the angle as 110°.
Choose “Append”→“Sequence” →“Add search lines to”to add the test item.
Set the original point R and X as (0, 0) to set the start point of search test.
Set the range of angle, set start angle as 0°and end angle as 330°, angle step as 30°.
After the test finished, the results and reports will be shown.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
N of three phase and connect it back to the “In” of tester.
8 4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
function disabling signal must be de-energized.
When m =0.95, 85.Z will trip, when m=1.05, 85.Z will not trip.
Inject faulty current with 2A, the angle of faulty voltage leads the faulty current 78
degrees . At the same time, the pilot distance element receive a signal which the tester
outputs to simulate the permissive signal from the remote end.
Inject faulty current with 2A, the angle of faulty voltage leads the faulty current 78
degrees. At the same time, the pilot distance element receive a signal which the tester
outputs to simulate the permissive signal from the remote end.
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
100ms
When m =0.7, measure 85.Z operation time. the operation error time ≤1%×Setting+30ms
Inject faulty current with 2A, the angle of faulty voltage leads the faulty current 78
degrees .At the same time, the pilot distance element receive a signal which the tester
outputs to simulate the permissive signal from the remote end.
The trigger condition can be set to “binary input or timed trigger”, and the state duration
= 50ms.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
N of three phase and connect it back to the “In” of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
function disabling signal must be de-energized.
Simulate the single-phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
Inject faulty current, the angle of faulty voltage leads the faulty current 78 degrees . At
the same time, the pilot directional earth-fault element receive a signal which the tester
outputs to simulate the permissive signal from the remote end.
Inject faulty current, the angle of faulty voltage leads the faulty current 78 degrees. At
the same time, the pilot distance element receive a signal which the tester outputs to
simulate the permissive signal from the remote end.
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
[85.DEF.t_DPU] +100ms
Simulate the single-phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
Inject faulty current, the angle of faulty voltage leads the faulty current 78 degrees . At
the same time, the pilot directional earth-fault element receive a signal which the tester
outputs to simulate the permissive signal from the remote end.
The 85.DEF should operate reliably, the operation error time≤ Max {1%×[85.DEF.t_DPU],
30ms }
8 8
9
50/51P.DIR.phi_Min_Rev
50/51P.DIR.phi_Max_Rev
90 deg
90 deg
24
25
50/51P1.Opt_Trp/Alm
50/51P1.Opt_Curve
Trp
IECDefTime
10 50/51P.DIR.Opt_PolarizedVolt U1 26 50/51P1.Opt_Curve_DropOut Inst
11 50/51P.DIR.I_Min 0.050 A 27 50/51P1.TMS 0.100
12 50/51P.DIR.U_Min 10.000 V 28 50/51P1.tmin 0.000 s
13 50/51P.DIR.En_VTS_Blk Disabled 29 50/51P1.K 0.1400
14 50/51P.HMB.K_Hm2 0.200 30 50/51P1.Alpha 0.0200
15 50/51P.HMB.I_Rls 20.000 A 31 50/51P1.C 0.0000
16 50/51P.HMB.Opt_Blk PhaseBlk
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 50/51P1 of the
device. Parallel the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 50/51P1 of the device.
Parallel the N of three phase and connect it back to the “In” of tester.
3. Please set the tripping logic setting for 50/51P1 according to the configuration of PCS-
931S, and connect the corresponding binary output of 50/51P1 to the binary input of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
function disabling signal must be de-energized.
Simulate the single phase grounding fault, the faulty voltage can set between 0V~0.9Un
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
Max{1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}
Simulate the single phase grounding fault, the faulty voltage can be set between
0V~0.9Un.
The trigger condition can be set to binary input or timed trigger, and the state duration =
[50/51P1.t_Op]+100ms.
The 50/51P1 should operate reliably, the operation error time should be:
≤ Max{30ms, 1%×[50/51P1.t_Op]}
In this section, we take IEC normal inverse operation characteristic as a testing example. Modify
the testing settings as follow:
[50/51P1.Opt_Curve] = IECN
At first, configuring the “Test Object” of “Overcurrent” module, the “Tolerances” should be
set as follows:
8 The Inverse-time characteristic settings are shown as follows. If the inverse time
characteristic of the test is not in the predefined characteristics, you can customize the
new inverse time. In the figure, “I pick-up” corresponds to the setting 50/51P1.I_Set, and
time index is 50/51P1.TMS, please pay attention to the unit (Iref) of I pick-up, it’s related
with I nom (Secondary) in Test Object Device.
Add the new test project to “Overcurrent” testing module, shown as follows. tnom is
theoretical operate time of inverse-time protection, Tmax and tmin correspond to the
upper and lower action time allowed by the error. tact is the record of actually action time.
The error of the actual action time is within the range set above only when
the testing current between 1.2~30×[I_set].
The corresponding relationship between phase-segregated overcurrent element and the voltage
control element is as follows. The relationship between Phase-to-phase criterion, Negative-
sequence criterion and Zero-sequence criterion is “or”. The negative-sequence voltage is U2, the
zero-sequence voltage is 3U0.
Voltage control
Phase A Phase B Phase C
criterion
Uab<[50/51P.Upp_VCE] Uab<[50/51P.Upp_VCE] Ubc<[50/51P.Upp_VCE]
Phase-to-phase criterion
Uca<[50/51P.Upp_VCE] Ubc<[50/51P.Upp_VCE] Uca<[50/51P.Upp_VCE]
Negative-sequence
U2>[50/51P.U2_VCE] U2>[50/51P.U2_VCE] U2>[50/51P.U2_VCE]
criterion
U0_Cal>[50/51P.3U0_VC U0_Cal>[50/51P.3U0_VC U0_Cal>[50/51P.3U0_VC
Zero-sequence criterion
E] E] E]
[50/51P1.En_Volt_Blk] = Enabled
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO]).
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}
[50/51P.VCE.Upp] = 10V
[50/51P.VCE.3U0] = 57V
[50/51P.VCE.U2] = 4V
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate the phaseA grounding fault, the faulty phase current =2×[50/51P1.I_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
[50/51P.VCE.Upp] = 10V
[50/51P.VCE.U2] = 57V
[50/51P.VCE.3U0] = 8V
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO]) 8
The state 2 is the fault state:
Simulate the phaseA grounding fault, the faulty phase current =2×[50/51P1.I_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}
[50/51P1.Opt_Dir] = Forward
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate three phase shorting fault, the faulty phase current = 2× [50/51P1.I_Set], faulty
phase voltage = 50V
[50/51P.DIR.RCA]-[50/51P.DIR.phi_Min_Fwd]+3°
[50/51P.DIR.RCA]-[50/51P.DIR.phi_Min_Fwd]-3°
[50/51P.DIR.RCA]+[50/51P.DIR.phi_Max_Fwd]-3°
8 [50/51P.DIR.RCA]+[50/51P.DIR.phi_Max_Fwd]+3°
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}
[50/51P1.Opt_Dir] = Reverse
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate three phase shorting fault, the faulty phase current = 2×[50/51P1.I_Set], faulty
phase voltage = 50V
180°+[50/51P.DIR.RCA]-[50/51P.DIR.phi_Min_Rev]+3°
180°+[50/51P.DIR.RCA]-[50/51P.DIR.phi_Min_Rev]-3°
180°+[50/51P.DIR.RCA]+[50/51P.DIR.phi_Max_Rev]-3°
180°+[50/51P.DIR.RCA]+[50/51P.DIR.phi_Max_Rev]+3°
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}
[50/51P1.En_Hm_Blk] = Enabled
[50/51P.HMB.Opt_Blk] = PhaseBlk
Connect phase A and C of the tester in parallel to the phase A analog input of the device. The
fundamental current is exported by phase A of the tester, the second harmonic component current
is exported by phase C of the tester.
When modifying the phase-C frequency, you need to uncheck the “Link
Frequencies” of the right-click menu to modify the frequency value
separately for each phase.
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Fault 1: Ic = 0.95×[50/51P.HMB.K_Hm2]×IF
Fault 2: Ic = 1.05×[50/51P.HMB.K_Hm2]×IF
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}
In this section, we only take VT circuit failure alarm (VTS.Alm) block 50/51P1 as an example.
‘VTS.Alm’ block the direction Control Element has the same function, which will not be described
here.
[50/51P.En_VTS_Blk] = Enabled
[50/51P1.En_Volt_Blk] = Enabled
[50/51P.DIR.En_VTS_Blk] = Disabled
Trigger condition is set to timed trigger, the state duration should be greater than
[VTS.t_DDO] (Delay drop off setting for the alarm of VT circuit supervision).
Simulate three phase short circuit fault, the faulty phase current = 2×[50/51P1.I_Set], the
faulty phase voltage = 0.7×[50/51P.VCE.Upp]/1.732 (except the VT abnormal phase).
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51P1.t_Op], [50/51P1.t_Op]+100ms}.
[50/51P1.Opt_Curve_DropOut] = Inst
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2×[50/51P1.I_Set], fault
voltage should be set between 0V~0.9Un
the faulty phase current should be less than 0.95×[50/51P1.I_Set], here set to
0.9×[50/51P1.I_Set]
Simulate single phase grounding fault, the faulty phase current = 2×[50/51P1.I_Set], fault
voltage should be set between 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, the state duration = Tmax
(the maximum operation time within the error tolerance) – t (the duration of status 2) +
0.05 s, (which should be less than the minimum operation time within the error tolerance)
Where:
[50/51P1.Opt_Curve_DropOut] = DefTime
[50/51P1.t_DropOut] = 1s
Inject Ua/Ub/Uc with the rated positive-sequence voltage, inject Ia/Ib/Ic with 0A.
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2×[50/51P1.I_Set], fault
voltage should be set between 0V~0.9Un
the faulty phase current should be less than 0.95×[50/51P1.I_Set], here set to
0.9×[50/51P1.I_Set]
[50/51P1.t_DropOut]-Max{1%×[50/51P1.t_DropOut], 30ms}
[50/51P1.t_DropOut]+Max{1%×[50/51P1.t_DropOut], 30ms}
Simulate single phase grounding fault, the faulty phase current = 2×[50/51P1.I_Set], fault
voltage should be set between 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(the maximum operation time within the error tolerance) –t (the duration of status 2) + 0.05
s, which should be less than the minimum operation time within the error tolerance.
Where:
[50/51P1.Opt_Curve_DropOut] = IDMT
[50/51P1.Opt_Curv] = ANSIN
[50/51P1.TMS] = 0.5
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
8
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2×[50/51P1.I_Set], fault
voltage should be set between 0V~0.9Un
Trigger condition is set to timed trigger, the state duration = 0.8 × T_cal. In which T_cal is
operation time in ANSIN
𝑘 0.0086
T_cal = { + 𝑐} × 𝑇𝑀𝑆 = { + 0.0185} × 0.5 = 0.317𝑠
(𝐼 ⁄𝐼𝑃 ) − 1
𝑎 (2⁄1)0.02 − 1
The fault phase current should be less than 0.95×[50/51P1.I_Set], here set to
0.8×[50/51P1.I_Set].
Trigger condition is set to timed trigger, the state duration = 0.5 × T_dr,in which T_dr is
the theoretical calculated dropout time from 100% droping to 0:
𝑡𝑟 0.46
T_dr = × 𝑇𝑀𝑆 = × 0.5 = 0.639𝑠
1 − (𝐼 ⁄𝐼𝑃 )2 1 − 0.82
Simulate single phase grounding fault, the faulty phase current set as 2×[50/51P1.I_Set],
voltage should be set between 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(the maximum operation time within the error tolerance)
The 50/51P1 should operate reliably, and the tripping time which is counted from the begin of
state 4 should be (1-(0.8-0.5))×T_op, where T_op is the theoretical calculated tripping time,
and it should be less than T_max and larger than T_min.
Where T_max (the maximum operation time within the error tolerance) and T_min (the
minimum operation time within the error tolerance) are:
k
T_max = (1 + 5%) × T_cal + Max (( + c) × TMS − T_cal, 0.035s)
((I − 1% × I)⁄IP )a − 1
k
T_min = (1 − 5%) × T_cal − Max (T_cal − ( + c) × TMS, 0.035s)
((I + 1% × I)⁄IP )a − 1
= (1 − 5%) × 0.317s − 0.035s = 0.266s
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 50/51G1 of the
device. Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 50/51G1 of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 50/51G1 according to the configuration of PCS-
931S, and connect the corresponding binary output of 50/51G1 to the binary input of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51G1.t_Op], [50/51G1.t_Op]+100ms}
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un. The faulty phase current = 2× [50/51G1.3I0_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
[50/51G1.t_Op]+100ms
The 50/51G1 should operate reliably, the error of operation time should be:
In this section, we take IEC normal inverse operation characteristic as a testing example.
[50/51G1.Opt_Curve] = IECN
Add the new test project to “Overcurrent” testing module, shown as follows. tnom is
theoretical operate time of inverse-time protection, Tmax and tmin correspond to the
upper and lower action time allowed by the error. tact is the record of actually action time. 8
The error of the actual operation time is within the range set above only
when the testing current between 1.2~30×[I_set]
The test result: the operation time should be within {tmin, tmax} for each test.
[50/51G1.Opt_Dir] = Forward
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
[50/51G.DIR.RCA]+ [50/51G.DIR.phi_Max_Fwd]-3°
[50/51G.DIR.RCA]+ [50/51G.DIR.phi_Max_Fwd]+3°
[50/51G.DIR.RCA]- [50/51G.DIR.phi_Min_Fwd]+3°
[50/51G.DIR.RCA]- [50/51G.DIR.phi_Min_Fwd]-3°
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51G1.t_Op], [50/51G1.t_Op]+100ms}
[50/51G1.Opt_Dir] = Reverse
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
180°+[50/51G.DIR.RCA]+[50/51G.DIR.phi_Max_Rev]-3°
180°+[50/51G.DIR.RCA]+[50/51G.DIR.phi_Max_Rev]+3°
180°+[50/51G.DIR.RCA]-[50/51G.DIR.phi_Min_Rev]+3°
180°+[50/51G.DIR.RCA]-[50/51G.DIR.phi_Min_Rev]-3°
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51G1.t_Op], [50/51G1.t_Op]+100ms}
[50/51G1.En_Hm_Blk] = Enabled
Connect phase A and C of the tester in parallel to the phase A analog input of the device. The
fundamental current is exported by phase A of the tester, the second harmonic component current
is exported by phase C of the tester.
Notice: When modifying the C-phase frequency, you need to uncheck the “Link Frequencies” of the
right-click menu to modify the frequency value separately for each phase.
Inject Ua/Ub/Uc with the rated positive-sequence voltage, inject Ia/Ib/Ic with 0A.
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate phase A grounding fault, the faulty phase voltage should be set between
0V~0.9Un. Faulty phase current: IF = 2×[50/51G1.3I0_Set],
Fault 1: Ic = 0.95×[50/51G.HMB.K_Hm2]×IF
Fault 2: Ic = 1.05×[50/51G.HMB.K_Hm2]×IF
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51G1.t_Op], [50/51G1.t_Op]+100ms}
[50/51G.En_VTS_Blk] = Enabled
[50/51G1.Opt_Dir] = Forward
Fault 2: Inject U A-N = 0V, UB-N/U C-N with the rated positive-sequence voltage.
Trigger condition is set to timed trigger, the state duration should be greater than
[VTS.t_DDO] (Delay drop off setting for the alarm of VT circuit supervision)
Simulate phase A grounding fault, the faulty phase current = 2× [50/51G1.3I0_Set], the
faulty phase voltage should be set between 0V,the angle of phase A current lags behind
voltage by [50/51G.DIR.RCA]
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51G1.t_Op], [50/51G1.t_Op]+100ms}
[50/51G1.Opt_Curve_DropOut] = Inst
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2× [50/51G1.3I0_Set],
voltage should be set between 0V~0.9Un
The faulty phase current should be less than 0.95× [50/51G1.3I0_Set], here set to 0.9×
[50/51G1.3I0_Set], voltage should be set between 0V~0.9Un.
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(the maximum operation time within the error tolerance) – t (the duration of status 2) +
0.05 s, (which should be less than the minimum operation time within the error tolerance)
[50/51G1.Opt_Curve_DropOut] = DefTime
[50/51G1.t_DropOut] = 1s
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2× [50/51G1.3I0_Set],
voltage should be set between 0V~0.9Un
The faulty phase current should be less than 0.95× [50/51G1.3I0_Set], here set to 0.9×
[50/51G13.I0_Set] , voltage should be set between 0V~0.9Un.
[50/51G1.t_DropOut]-Max{1%×[50/51G1.t_DropOut], 30ms}
[50/51G1.t_DropOut]+Max{1%×[50/51G1.t_DropOut], 30ms}
Simulate single phase grounding fault, the faulty phase current = 2× [50/51G1.3I0_Set],
voltage should be set between 0V~0.9Un
8 The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(Maximum operation time within the error tolerance) –t (the duration of status 2) + 0.05 s,
which should be under the minimum operation time within the error tolerance.
Where:
[50/51G1.Opt_Curve_DropOut] = IDMT
[50/51G1.Opt_Curv] = ANSIN
[50/51G1.TMS] = 0.5
Simulate single phase grounding fault, the faulty phase current = 2× [50/51G1.3I0_Set],
voltage should be set between 0V~0.9Un
Trigger condition is set to timed trigger, the state duration = 0.5×T_cal. In which T_cal is
operate time in ANSIN
𝑘 0.0086
T_cal = { + 𝑐} × 𝑇𝑀𝑆 = { + 0.0185} × 0.5 = 0.317𝑠
(𝐼 ⁄𝐼𝑃 ) − 1
𝑎 (2⁄1)0.02 − 1
The fault phase current should be less than 0.95× [50/51G1.3I0_Set], here set to 0.8×
[50/51G1.3I0_Set]
Trigger condition is set to timed trigger, the state duration = 0.5 × T_dr, in which T_dr is
the theoretical calculated dropout time from 100% droping to 0:
T_dr =
𝑡𝑟
1 − (𝐼 ⁄𝐼𝑃 )2
× 𝑇𝑀𝑆 =
0.46
1 − 0.82
× 0.5 = 0.639𝑠 8
The status 4 is the fault state:
Simulate single phase grounding fault, the faulty phase current = 2× [50/51G1.I_Set],
voltage should be set between 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(Maximum operation time within the error tolerance)
The 50/51G1 should operate reliably, and the tripping time which is counted from the begin of
state 4 should be (1-(0.8-0.5))×T_op, where T_op is the theoretical calculated tripping time,
and it should be less than T_max and larger than T_min.
Where T_max (the maximum operation time within the error tolerance) and T_min (the
minimum operation time within the error tolerance) are:
k
T_max = (1 + 5%) × T_cal + Max (|T_cal − ( + c) × TMS| , 0.035s)
((I − 1% × I)⁄IP )a − 1
= (1 + 5%) × 0.317s + 0.035s = 0.368s
k
T_min = (1 − 5%) × T_cal − Max (|T_cal − ( + c) × TMS| , 0.035s)
((I − 1% × I)⁄IP )a − 1
= (1 − 5%) × 0.317s − 0.035s = 0.266s
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 50/51Q1 of the
device. Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 50/51Q1 of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 50/51Q1 according to the configuration of PCS-
931S, and connect the corresponding binary output of 50/51Q1 to the binary input of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
The trigger condition can be set to binary input or timed trigger, with a duration time of
Max {1.01×[50/51Q1.t_Op],[50/51Q1.t_Op] +100ms}
Inject Ia/Ib/Ic as 0 A.
8
The trig condition as time trig with a duration time of 2s
Simulate single phase to earth fault with fault voltage set as 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, with a duration time of
[50/51Q1.t_Op] +100ms
Earth fault protection should operate and the error of time delay should be ≤Max{30ms,
1%×[50/51Q1.t_Op] }
[50/51Q1.Opt_Curve] = IECN
Add the new test project to “Overcurrent” testing module, shown as follows. tnom is
theoretical operate time of inverse-time protection, Tmax and tmin correspond to the
upper and lower action time allowed by the error. tact is the record of actually action time.
The error of the actual operation time is within the range set above only
when the testing current between 1.2~30×[I_set]
The test result: the operation time should be within {tmin, tmax} for every test.
[50/51Q1.Opt_Dir] = Forward
Inject Ia/Ib/Ic as 0
Simulate sigle phase grounding fault with fault phase current of 2×3×[50/51Q1.I2_Set],
and fault phase voltage of 30V (be higher than [50/51Q.DIR.U2_Min], and phase angle is
same with state 1)
[50/51Q.DIR.RCA]+[50/51Q.DIR.phi_Max_Fwd]+3°
[50/51Q.DIR.RCA]-[50/51Q.DIR.phi_Min_Fwd]+3°
[50/51Q.DIR.RCA]-[50/51Q.DIR.phi_Min_Fwd]-3°
(For single phase grounding fault, the direction of polarized voltage −𝑈2 is same with
fault phase voltage.)
The trigger condition can be set to binary input or timed trigger, with a duration time of
Max{1.01×[50/51Q1.t_Op],[50/51Q1.t_Op]+100ms}
[50/51Q1.Opt_Dir] = Reverse
Simulate single phase grounding fault with fault phase current of 2×3×[50/51Q1.I2_Set],
and fault phase voltage of 50V (be higher than 50/51Q.DIR.U_Min, and phase angle is
same with State 1)
180°+[50/51Q.DIR.RCA]+([50/51Q.DIR.phi_Max_Rev]-3°
180°+[50/51Q.DIR.RCA]+([50/51Q.DIR.phi_Max_Rev]+3°
180°+[50/51Q.DIR.RCA]-([50/51Q.DIR.phi_Min_Rev]+3°
180°+[50/51Q.DIR.RCA]-([50/51Q.DIR.phi_Min_Rev]-3°
(For single phase grounding fault, the direction of polarized voltage −𝑈2 is same with
fault phase voltage.)
The trigger condition can be set to binary input or timed trigger, with a duration time of
Max{1.01×[50/51Q1.t_Op],[50/51Q1.t_Op]+100ms}
[50/51Q.DIR.En_VTS_Blk] = Enabled
[50/51Q1.Opt_Dir] = Forward
Fault 2: Inject U A-N = 0V, UB-N/U C-N with the rated positive-sequence voltage.
Trigger condition is set to timed trigger, the state duration should be greater than
[VTS.t_DDO] (Delay drop off setting for the alarm of VT circuit supervision)
Simulate phase A grounding fault, the faulty phase current = 2×3× [50/51Q1.I2_Set], the
faulty phase voltage should be set between 0V,the angle of phase A current lags behind
voltage by [50/51Q.DIR.RCA]
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50/51Q1.t_Op], [50/51Q1.t_Op]+100ms}
8
The test result:
[50/51Q1.Opt_Curve_DropOut] = Inst
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2×3× [50/51Q1.I2_Set],
voltage should be set between 0V~0.9Un
The faulty phase current should be less than 0.95×3× [50/51Q1.I2_Set], here set to 0.9×
[50/51G1.3I0_Set], voltage should be set between 0V~0.9Un.
Simulate single phase grounding fault, the faulty phase current set as
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(the maximum operation time within the error tolerance) – t (the duration of status 2) +
0.05 s, (which should be less than the minimum operation time within the error tolerance)
[50/51Q1.t_DropOut] = 1s
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate single phase grounding fault, the faulty phase current = 2×3× [50/51Q1.I2_Set],
voltage should be set between 0V~0.9Un
The faulty phase current should be less than 0.95×3× [50/51Q1.I2_Set], here set to 0.9×
3× [50/51Q1.I2_Set] , voltage should be set between 0V~0.9Un.
[50/51Q1.t_DropOut]-Max{1%×[50/51Q1.t_DropOut], 30ms}
[50/51Q1.t_DropOut]+Max{1%×[50/51Q1.t_DropOut], 30ms}
Simulate single phase grounding fault, the faulty phase current = 2×3× [50/51Q1.I2_Set],
voltage should be set between 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(Maximum operation time within the error tolerance) –t (the duration of status 2) + 0.05 s,
which should be under the minimum operation time within the error tolerance.
Where:
[50/51Q1.Opt_Curve_DropOut] = IDMT
8
[50/51Q1.Opt_Curv] = ANSIN
[50/51Q1.TMS] = 0.5
Simulate single phase grounding fault, the faulty phase current =2×3× [50/51Q1.I2_Set],
Trigger condition is set to timed trigger, the state duration = 0.5×T_cal. In which T_cal is
operate time in ANSIN
𝑘 0.0086
T_cal = { + 𝑐} × 𝑇𝑀𝑆 = { + 0.0185} × 0.5 = 0.317𝑠
(𝐼 ⁄𝐼𝑃 ) − 1
𝑎 (2⁄1)0.02 − 1
The fault phase current should be less than 0.95× 3× [50/51Q1.I2_Set], here set to 0.8×
3× [50/51Q1.I2_Set]
Trigger condition is set to timed trigger, the state duration = 0.5 × T_dr, in which T_dr is
the theoretical calculated dropout time from 100% droping to 0:
𝑡𝑟 0.46
T_dr = × 𝑇𝑀𝑆 = × 0.5 = 0.639𝑠
1 − (𝐼 ⁄𝐼𝑃 )2 1 − 0.82
Simulate single phase grounding fault, the faulty phase current = 2×3× [50/51Q1.I2_Set],
voltage should be set between 0V~0.9Un
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(Maximum operation time within the error tolerance)
The 50/51Q1 should operate reliably, and the tripping time which is counted from the begin of
state 4 should be (1-(0.8-0.5))×T_op, where T_op is the theoretical calculated tripping time,
and it should be less than T_max and larger than T_min.
8 Where T_max (the maximum operation time within the error tolerance) and T_min (the
minimum operation time within the error tolerance) are:
k
T_max = (1 + 5%) × T_cal + Max (|T_cal − ( + c) × TMS| , 0.035s)
((I − 1% × I)⁄IP )a − 1
= (1 + 5%) × 0.317s + 0.035s = 0.368s
k
T_min = (1 − 5%) × T_cal − Max (|T_cal − ( + c) × TMS| , 0.035s)
((I − 1% × I)⁄IP )a − 1
= (1 − 5%) × 0.317s − 0.035s = 0.266s
3. Please set the tripping logic setting for 50PSOTF/50GSOTF according to the configuration of
PCS-931S, and connect the corresponding binary output of 50PSOTF/50GSOTF/21SOTF to
the binary input of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[50PSOTF.En]=Enabled
[50GSOTF.En]=Disabled
[21SOTF.En]=Disabled
Make sure the CB is open or short the 52b_PhA/52b_PhB/52b_PhC with DC power supply
positive terminal.
Trigger condition is set to timed trigger, the state duration =2s (Should be larger than the
setting [VTS.t_DDO]).
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un.
The trigger condition can be set to binary input or timed trigger, and the state duration
=[50PSOTF.t_Op]+100ms .
The 50PSOTF should operate reliably, the operation time should under the error tolerance.
[50PSOTF.En]= Disabled
8
[50GSOTF.En]= Enabled
[21SOTF.En]=Disabled
Trigger condition is set to timed trigger, the state duration =2s (Should be larger than the
setting [VTS.t_DDO])
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un.
The trigger condition can be set to binary input or timed trigger, and the state duration
=[50GSOTF.t_Op_3P]+100ms.
The 50GSOTF should operate reliably, the operation time should under the error tolerance.
[50PSOTF.En]= Disabled
[50GSOTF.En]= Disabled
[21SOTF.En]= Enabled
Trigger condition is set to timed trigger, the state duration =2s (Should be larger than the
setting [VTS.t_DDO])
The trigger condition can be set to binary input or timed trigger, and the state duration
=[21SOTF.t_ManCls]+100ms.
The 21SOTF should operate reliably, the operation time should under the error tolerance.
[50PSOTF.En]=Enabled
[50GSOTF.En]=Disabled
[21SOTF.En]=Disabled
[CBx.79.Opt_ValidMode]=setting
[CBx.79.En_3P]= Enabled
Trigger condition is set to timed trigger, the state duration =11s (should be greater than
the [VTS.t_DDO] and [79.t_CBClsd]).
Simulate single phase grounding fault, voltage can be set between 0V~0.9Un.
Simulate single phase grounding fault, voltage should be set between 0V~0.9Un.
The trigger condition can be set to binary input or timed trigger, the state duration =
[50PSOTF.t_Op]+100ms.
The 50/51P1 should operate at the first fault, after the 79.Colse, the 50PSOTF should operate
reliably and the operate time should under the error tolerance.
[50PSOTF.En]= Disabled
[50GSOTF.En]= Enabled
[21SOTF.En]=Disabled
[CBx.79.Opt_ValidMode]=setting
[CBx.79.En_3P]= Enabled
Trigger condition is set to timed trigger,the state duration=11s (should be greater than the
[VTS.t_DDO] and [79.t_CBClsd]).
Simulate single phase grounding fault, voltage should be set between 0V~0.9Un.
Simulate single phase grounding fault, voltage should be set between 0V~0.9Un.
The trigger condition can be set to binary input or timed trigger, the state duration =
[50GSOTF.t_Op]+100ms.
The 50/51G1 should operate at the first fault, after the AR, the 50GSOTF should operate
reliably and the operate time should under the error tolerance.
[50PSOTF.En]= Disabled
[50GSOTF.En]= Disabled
[21SOTF.En]= Enabled
[CBx.79.Opt_ValidMode]=setting
[CBx.79.En_3P]= Enabled
Trigger condition is set to timed trigger,the state duration=11s (should be greater than the
[VTS.t_DDO] and [79.t_CBClsd]).
The trigger condition can be set to binary input or timed trigger, the state duration =
[21SOTF.t_3PAR]+100ms.
The 21L2 should operate at the first fault, after the AR, the 21SOTF should operate reliably
and the operate time should under the error tolerance.
2. Please set the tripping logic setting for 59P1 according to the configuration of PCS-931S,
and connect the corresponding binary output of 59P1 to the binary input 1 of tester. (In
the Hardware Configuration of Test Universe Software, set Binary Input 1 to the type ‘Trip’)
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate the single phase overvoltage fault, the faulty phase voltage:
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[59P1.t_Op], [59P1.t_Op]+100ms}
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
8 setting [VTS.t_DDO]).
Simulate the single phase overvoltage fault, the faulty phase voltage =1.1×[59P1.U_Set].
The trigger condition can be set to binary input or timed trigger, and the state duration =
[59P1.t_Op]+100ms.
The 59P1 should operate reliably, the error of operation time should be:
≤ Max{35ms, 1%×[59P1.t_Op]}
[59P1.Opt_Curve] = InvTime_U
Using “State Sequencer” to test module to test 1.1(1.2/1.5)×[59P1.U_Set] respectively, each test
point should be set with two states in relay tester.
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO]).
Simulate the single phase overvoltage fault, the trigger condition can be set to binary input
or timed trigger, the faulty phase voltage should be set:
Where:
𝑘 1
T_cal = { + 𝑐} × 𝑇𝑀𝑆 = { + 0} × 0.5 = 5𝑠
(𝑈⁄𝑈𝑃 )𝑎 − 1 (1.1)1 − 1
k
T1min = 95% × Tcal − Max {Tcal − { + c} × TMS, 0.04s}
((U + 1% × U)⁄UP )a − 1
≈ (1 − 5%) × 5s − 0.495s = 4.255s
The 59P1 should operate reliably for each fault, the error of operation time should meet the
follow condition:
[59P1.Opt_Curve_DropOut] = DefTime
[59P1.Opt_Curve_DropOut] = Inst
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO]).
Simulate single phase overvoltage fault, the faulty phase voltage = 1.1× [59P1.U_Set]
The faulty phase voltage = 0.9×[59P1.U_Set], the rest of two phase with the rated positive-
sequence voltage
Simulate single phase overvoltage fault, the faulty phase voltage should be set:
1.1×[59P1.U_Set].
The trigger condition can be set to binary input or timed trigger, and the state duration =
T_max (Maximum operation time within the error tolerance) – t (the duration of status 2)
+ 0.05s, (which should be less than the minimum operation time within the error tolerance)
[59P1.Opt_Curve_DropOut] = DefTime
[59P1.t_DropOut] = 1s
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO]).
Simulate single phase overvoltage fault, the faulty phase voltage set as 1.1× [59P1.U_Set].
The faulty phase voltage = 0.9×[59P1.U_Set], the rest of two phases with the rated
positive-sequence voltage
[59P1.t_DropOut]-Max{1%×[59P1.t_DropOut], 30ms}
[59P1.t_DropOut]+Max{1%×[59P1.t_DropOut], 30ms}
8
The status 4 is the fault state:
Simulate single phase overvoltage fault, the faulty phase voltage = 1.1× [59P1.U_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
T_max (the maximum operation time within the error tolerance) –t (the duration of status
2) + 0.05 s, which should be less than the minimum operation time within the error
tolerance)
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 59G1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Please set the tripping logic setting for 59G1 according to the configuration of PCS-931S,
and connect the corresponding binary output of 59G1 to the binary input of tester.
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Simulate the single phase earth fault, the faulty phase voltage:
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[59G1.t_Op], [59G1.t_Op]+100ms}
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO])
Simulate the single phase earth fault, the faulty phase voltage = Un-1.1×[59G1.3U0_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
[59G1.t_Op]+100ms
The 59G1 should operate reliably, the error of operation time should be:
≤ Max{35ms, 1%×[59G1.t_Op]}
[59G1.t_DropOut] = 1s
Trigger condition is set to timed trigger, the state duration = 2s (Should be larger than the
setting [VTS.t_DDO]).
The faulty phase voltage = Un - 0.9×[59G1.3U0_Set], the rest of two phases with the rated
positive-sequence voltage
[59G1.t_DropOut]-Max{1%×[59G1.t_DropOut], 30ms}
[59G1.t_DropOut]+Max{1%×[59G1.t_DropOut], 30ms}
Un-1.1×[59G1.3U0_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
T_max (the maximum operation time within the error tolerance) –t (the duration of status
2) + 0.05 s, which should be less than the minimum operation time within the error
tolerance.
8 1
2
59Q1.U2_Set
59Q1.K_Drop-out
15
0.98
4
5
59Q1.t_Drop-out
59Q1.En
0
Enabled
3 59Q1.t_Op 1 6 59Q1.Opt_Trp/Alm Trp
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 59Q1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Please set the tripping logic setting for 59Q1 according to the configuration of 59Q1 of PCS-
931S, and connect the corresponding binary output of 59Q1 to the binary input of tester.
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Trigger condition is set to timed trigger, the state duration =2s (Should be larger than the
setting [VTS.t_DDO])
Simulate the single phase earth fault, the faulty phase voltage:
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[59Q1.t_Op], [59Q1.t_Op]+100ms}
Trigger condition is set to timed trigger, the state duration =2s (Should be larger than the 8
setting [VTS.t_DDO])
Simulate the single phase earth fault, the faulty phase voltage=
Un-1.1×3×[59Q1.U2_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
[59Q1.t_Op]+100ms
The 59Q1 should operate reliably, the error of operation time should be:
≤ Max{35ms, 1%×[59Q1.t_Op]}
[59Q1.t_DropOut] = 1s
Trigger condition is set to timed trigger, the state duration =2s (Should be larger than the
setting [VTS.t_DDO])
Un-1.1×3×[59Q1.U2_Set]
the faulty phase voltage = Un-0.9×3×[59Q1.U2_Set], the rest of two phases with the rated
positive-sequence voltage
Fault1: Trigger condition is set to timed trigger, the state duration = 59Q1.t_DropOut-
Max{1%×59Q1.t_DropOut, 30ms}
Un-1.1×3×[59Q1.U2_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
T_max (the maximum operation time within the error tolerance) –t (the duration of status
2) + 0.05 s, which should be less than the minimum operation time within the error
tolerance.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 27P1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 27P1 of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 27P1 according to the configuration of PCS-931S,
and connect the corresponding binary output of 27P1 to the binary input 1 of tester. (In
the Hardware Configuration of Test Universe Software, set Binary Input 1 to the type ‘Trip’)
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
8
8.15.3 Definite-time Phase Undervoltage Test
8.15.3.1 Voltage settings test
Inject Ua/Ub/Uc with the rated positive-sequence voltage, Ia/Ib/Ic with 0.1A (>0.04In).
Trigger condition is set to timed trigger, state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
Simulate the three phase undervoltage fault, the current remains the same,The faulty
phase voltage should be set:
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[27P1.t_Op], [27P1.t_Op]+100ms}
Inject Ua/Ub/Uc with the rated positive-sequence voltage, Ia/Ib/Ic with 0.1A (>0.04In)
Trigger condition is set to timed trigger, the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
Simulate the three phase undervoltage fault, the faulty phase voltage should be set =
0.9×[27P1.U_Set]
The trigger condition can be set to binary input or timed trigger, and the state duration =
[27P1.t_Op]+100ms
The 27P1 should operate reliably, the error of operation time should be:
[27P1.Opt_Curve] = InvTime_U
Using “State Sequencer” testing module to test 0.9(/0.7/0.5)×[27P1.U_Set] respectively, each one
with two states:
Inject Ua/Ub/Uc with the rated positive-sequence voltage, Ia/Ib/Ic = 0.1A (>0.04In).
Trigger condition is set to timed trigger,the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
Simulate the three phase undervoltage fault, the trigger condition can be set to binary
input or timed trigger, the faulty phase voltage should be set:
Where:
𝑘 1
T_cal = { + 𝑐} × 𝑇𝑀𝑆 = { + 0} × 0.5 = 5𝑠
1 − (𝑈⁄𝑈𝑃 )𝑎 1 − (0.9)1
k
T1_max = 105% × T_cal + Max {{ + c} × TMS − T_cal, 0.05s}
1− ((U + 1% × U)⁄UP )a
k
T1_min = 95% × T_cal − Max {{ + c} × TMS − T_cal, 0.05s}
1 − ((U − 1% × U)⁄UP )a
Inject Ua/Ub/Uc with the rated positive-sequence voltage, Ia/Ib/Ic with 0.1A(>0.04In).
Trigger condition is set to timed trigger, the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
Simulate three phase undervoltage fault, the faulty phase voltage = 0.9×[27P1.U_Set]
Simulate three phase undervoltage fault, the faulty phase voltage = 0.9×[27P1.U_Set].
The trigger condition can be set to binary input or timed trigger, the state duration = T_max
(the maximum operation time within the error tolerance)– t (the duration of status 2) + 0.05
s, (which should be less than the minimum operation time within the error tolerance)
[27P1.Opt_Curve_DropOut] = DefTime
[27P1.t_DropOut] = 1s
Inject Ua/Ub/Uc with the rated positive-sequence voltage, Ia/Ib/Ic with 0.1A (>0.04In).
Trigger condition is set to timed trigger,the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
Simulate three phase undervoltage fault, the faulty phase voltage = 0.9×[27P1.U_Set]
[27P1.t_DropOut]-Max{1%×[27P1.t_DropOut], 30ms}
[27P1.t_DropOut]+Max{1%×[27P1.t_DropOut], 30ms}
Simulate three phase undervoltage fault, the faulty phase voltage =0.9×[27P1.U_Set].
The State Termination set as Timeout or Binary Input, the duration = T_max (the maximum
operation time within the error tolerance) –t (the duration of status 2) + 0.05 s, which
should be less than the minimum operation time within the error tolerance)
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 81O1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
8
2. Please set the tripping logic setting for 81O1 according to the configuration of PCS-931S,
and connect the corresponding binary output of 81O1 to the binary input 1 of tester.
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[81O1.f_Set] = 51Hz
Trigger condition is set to timed trigger,the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
f = [81O1.f_Set]+0.01Hz
f = [81O1.f_Set]-0.01Hz
The trigger condition can be set to binary input or timed trigger, and the state duration =
1.01×[81O1.t_Op]+100ms
[81O1.t_Op] = 0.100 s
8 Trigger condition is set to timed trigger,the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
f = [81O1.f_Set]+0.1Hz
The 81O1 should operate reliably, the operation error time ≤Max{70ms, 1%×[81O1.t_Op]}.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
2. Please set the tripping logic setting for 81U1 according to the configuration of PCS-931S,
and connect the corresponding binary output of 81U1 to the binary input 1 of tester. (In
the Hardware Configuration of Test Universe Software, set Binary Input 1 to the type ‘Trip’)
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[81U1.f_Set] = 49Hz
Trigger condition is set to timed trigger, the state duration = 5s (Should be larger than the
setting [VTS.t_DDO]) 8
The state 2 is the fault state:
f = [81U1.f_Set]-0.01Hz
f = [81U1.f_Set]+0.01Hz
The trigger condition can be set to binary input or timed trigger, and the state duration =
1.01×[81U1.t_Op]+100ms
[81O1.t_Op] = 0.100 s
Trigger condition is set to timed trigger,the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
f = [81U1.f_Set] - 0.1Hz
The 81U1 should operate reliably, the operation error time ≤Max{25ms, 1%×[81U1.t_Op]}.
8 1
2
81.Upp_Blk
81R1.df/dt_Set
70.000 V
0.500 Hz/s
4
5
81R1.f_Pkp
81R1.En
45.000 Hz
Enabled
3 81R1.t_Op 0.100 s
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 81R1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Please set the tripping logic setting for 81R according to the configuration of PCS-931S,
and connect the corresponding binary output of 81R to the binary input 1 of tester.
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Disable 81O and 81U to prevent from affecting the test results.
Inject Ua/Ub/Uc with the rated positive-sequence voltage, frequency 50Hz (until VTS.Alm
returns).
Fault 1: The frequency changed from 50Hz to 51Hz, the stepsize Delta=11mHz / dt=20ms
(d/dt=0.55Hz/s)
Fault 2: The frequency changed from 50Hz to 51Hz, the stepsize Delta=9mHz / dt=20ms
(d/dt=0.45Hz/s)
[81R1.t_Op] = 0.100 s
Trigger condition is set to timed trigger,the state duration = 5s (Should be larger than the
setting [VTS.t_DDO])
8
The state 2 is the fault state:
Fault 1: The frequency changed from 50Hz to 51Hz, the stepsize Delta=20mHz / dt=20ms
(d/dt=1Hz/s)
The 81R1 should operate reliably, the operation error time ≤Max{70ms, 1%×[81R1.t_Op]}.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 32R1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 32R1 of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 32R according to the configuration of PCS-931S,
and connect the corresponding binary output of 32R to the binary input 1 of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[32R1.P_Set] = 0.2 pu
Trigger condition is set to timed trigger, the state duration=11s (make sure the VTS.Alm is
canceled)
Fault 1: The angle of current Ia/Ib/Ic lag to the voltage by 180°, the amplitude=
([32R1.P_Set]+Max(5%×[32R1.P_Set], 0.01))/U××In
Fault 2: The angle of current Ia/Ib/Ic lag to the voltage by 180°, the amplitude=
([32R1.P_Set]-Max(5%×[32R1.P_Set], 0.01))/U××In
Where:
U× is per-unit value
[32R1.t_Op] = 0.100 s
Trigger condition is set to timed trigger, the state duration=11s (make sure the VTS.Alm is
canceled)
Fault 1: The angle of current Ia/Ib/Ic lag to the voltage by 180°, the amplitude=
1.2 × [32R1.P_Set] / U× × In
The 32R1 should operate reliably, the operation error time ≤Max{25ms, 1%×[32R1.t_Op]}.
8
The power setting is three phase power, which should calculate by the sum
of three phase active power.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 49P1 of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 49P1 of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 49P1 according to the configuration of PCS-931S,
and connect the corresponding binary output of 49P1 to the binary input of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Simulate overload fault with the voltage can set as same as state 1
The 49P1 protection should operate reliably, and the operation time should be:
And
Where:
Tau = [49P1.t_Tau]
Alpha = [49P1.Alpha_Cold]
I_Set = [49P1.Ib_Set]×[49P1.K_Trp]
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 37 protection of the
device. Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 37 protection of the
device. Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 37 according to the configuration of PCS-931S,
and connect the corresponding binary output of 37 to the binary input of tester.
4. Connect the binary output of tester to CB normally open position of PCS-931S to simulate
CB close position. 8
5. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[37.t_Op], [37.t_Op]+100ms}.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[37.t_Op], [37.t_Op]+100ms}.
The 37 should operate reliably, the operation error time ≤Max{25ms, 1%×[37.t_Op]}.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 50BF of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 50BF of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. According to the configuration of PCS-931S, set the output map of the 50BF and connect
the binary output 50BF.ReTrp3P, 50BF.op1 and 50BF.op2 with the trip binary input 1, 2
and 3 of tester.
4. Connecting the tester output 1/2 to the device input 50BF.ExtTrp3P and 50BF.ExtTrp_WOI
respectively
5. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[50BF.En_3I0_3P] = Disabled
[50BF.En_I2_3P] = Disabled
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[50BF.t2_Op], [50BF.t2_Op] +100ms}
[50BF.En_3I0_3P] = Enabled
[50BF.En_Ip] = Disabled
[50BF.En_I2_3P] = Disabled
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50BF.t2_Op], [50BF.t2_Op] +100ms}
[50BF.En_I2_3P] = Enabled
[50BF.En_3I0_3P] = Disabled
[50BF.En_Ip] = Disabled
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50BF.t2_Op], [50BF.t2_Op] +100ms}
[50BF.En_CB_Ctrl] = Enabled
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50BF.t2_Op], [50BF.t2_Op] +100ms}
[50BF.En_ReTrp] = Enabled
[50BF.En_Ip] = Enabled
Simulate the single phase grounding fault, the faulty phase voltage should be set between
0V~0.9Un
8 Simulate the Trp3P signal, initiate output 1 of the tester
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[50BF.t_ReTrp], [50BF.t_ReTrp] +100ms}
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 46BC of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 46BC of the device.
Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 46BC according to the configuration of PCS-931S,
and connect the corresponding binary output of 46BC to the binary input of tester.
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
The healthy phase current is Ip, the broken-conductor phase current is Ibc
Ibc< Ip×(1-2×[46BC.I2/I1_Set])/(1+[46BC.I2/I1_Set])
Fault 1:
Ip×(1-2×([46BC.I2/I1_Set]+0.02))/(1+([46BC.I2/I1_Set]+0.02))
Fault 2:
Ip×(1-2×([46BC.I2/I1_Set]-0.02))/(1+([46BC.I2/I1_Set]-0.02))
Fault 3:
Fault 4:
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[46BC.t_Op], [46BC.t_Op]+100ms}
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max{1.01×[46BC.t_Op], [46BC.t_Op]+100ms}.
The 46BC should operate reliably, the operation error time ≤Max{30ms, 1%×[46BC.t_Op]}.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 62PD protection of
the device. Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 62PD protection of the
device. Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 62PD according to the configuration of PCS-931S,
and connect the corresponding binary output of 62PD to the binary input of tester.
[62PD.En_3I0/I2_Ctr] = Enabled
[62PD.I2_Set] =50A
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[62PD.t_Op], [62PD.t_Op] +100ms}
[62PD.En_3I0/I2_Ctr] = Enabled
[62PD.3I0_Set] =50A
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[62PD.t_Op], [62PD.t_Op] +100ms}
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[62PD.t_Op], [62PD.t_Op] +100ms}
The 62PD should operate reliably, the operation error time ≤Max{30ms, 1%×[62PD.t_Op]}.
Stub differential protection is mainly designed for one and a half breakers arrangement.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the 87STB
protection . Parallel the N of three phase and connect it back to the “Un” of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the 87STB protection.
Parallel the N of three phase and connect it back to the “In” of tester.
4. Short-circuit the positive terminal of the DC power to the normally closed auxiliary contact
of line disconnector input of PCS931 to simulate line out of service.
5. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
Where:
• •
𝐼𝜑1 , 𝐼𝜑2 are secondary phase currents corresponding to both circuit breakers, are formed by phase
A, B, C
Inject IA1 /IB1 /IC1 and IA2 /IB2 /IC2 with 0A.
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
87STB.t_Op + 100ms
Inject IA1 /IB1 /IC1 and IA2 /IB2 /IC2 with 0A.
The trigger condition can be set to binary input or timed trigger, and the state duration =
87STB.t_Op + 100ms.
The The 87STB should operate reliably, the operation error time ≤Max{30ms, 1%×
[87STB.t_Op]}.
Short-circuit the positive terminal of the DC power to “87STB.89b_DS” input of PCS931 to Initiate
8
Stub Differential Protection.
CB1 and CB2 represent the bus breaker and the tie breaker respectively.
Simulate the single-phase grounding fault, the phase angle between two CT1 and CT2 is
180°.
Fault 1: The faulty phase of CT1 current = 0.945A, the faulty phase of CT2 current =
0.3A.
Fault 2: The faulty phase of CT1 current = 0.855A, the faulty phase of CT2 current =
0.3A.
The trigger condition can be set to “binary input or timed trigger”, and the state duration =
87STB.t_Op + 100ms
According to the above table, complete the test from No.01 to No.03.
Test the Stub differential protection automatically by “Diff Operating Characteristic” module.
Add the low slope characteristics line,and the high slope characteristics line.
Choose the “Search Test”→“Add Sweep...” →“Add Multiple”to add test items. Set the parameter
as the follow picture.Choose the faulty type as “L1-E”.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of 50DZ protection of
the device. Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of 50DZ protection of the
device. Parallel the N of three phase and connect it back to the In of tester.
3. Please set the tripping logic setting for 50DZ according to the configuration of PCS-931S,
and connect the corresponding binary output of 50DZ to the binary input of tester.
4. Connect the binary output 1 of tester to the tripping signal input of PCS-931S to initiate
50DZ protection .
5. Short-circuit the positive terminal of the DC power to CB normally close position of Phase
A/ B/ C input of PCS931 to simulate three-phase breaker open condition.
6. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
Short-circuit the positive terminal of the DC power to CB normally close position of Phase
A/ B/ C input of PCS931S to simulate three-phase breaker open condition.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50DZ.t_Op], [50DZ.t_Op] +100ms}
Short-circuit the positive terminal of the DC power to CB normally close position of Phase
A/ B/ C input of PCS931 to simulate three-phase breaker open condition.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[50DZ.t_Op], [50DZ.t_Op] +100ms}
The 50DZ should operate reliably, the operation error time ≤Max{30ms, 1%×[50DZ.t_Op]}.
In this section, we take 50/51P1 to initiate AR, please configure ‘50/51P1.op’ to initiate 79.Trp3P in
the configuration.
Auto-Reclosure Settings
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Enable the second group voltage output of tester, using as Usyn, connect it to Ux of the
device.
3. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
N and connect it back to the “In” of tester.
4. According to the configuration of PCS-931S, set the output map of the 79.Close and
connect the binary output with the trip binary input of tester. (In the Hardware Configuration
8 of Test Universe Software, set Binary Input 1 as Close)
5. Keep the CB closed, which means 52b = 0.
6. Keep 79.CB_Healthy = 1, without any blocking binary input initiated.(If these signals are
not configured, it will satisfy the demands as default)
7. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[79.En_SynChk] = Enabled.
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (the duration should be
greater than the VTS.t_DDO and make sure that 79.Ready = 1)
Simulate the single-phase grounding fault, the faulty phase voltage can set between
0V~0.9Un
(Notice: the voltage amplitude in this status should be larger than 25.U_LvChk)
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Wait_Chk + 1s
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (the duration should be
greater than the VTS.t_DDO and make sure that 79.Ready = 1)
Simulate the single-phase grounding fault, The faulty phase voltage can set between
0V~0.9Un
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Wait_Chk + 1s
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (the duration should be
greater than the VTS.t_DDO and make sure that 79.Ready = 1)
Simulate the single-phase grounding fault, the faulty phase voltage can set between
0V~0.9Un
Fault 1:Inject UA-N/UB-N/UC-N with positive-sequence voltage, the angle of UB-N is different
from Usyn by: 25. phi_Diff_Set + 2°
Fault 2: Inject UA-N/UB-N/UC-N with positive-sequence voltage, the angle of UB-N is different
from Usyn by: 25. phi_Diff_Set − 2°
The trigger condition can be set to binary input or timed trigger, and the state duration =
8
79. t_Wait_Chk + 1s
8.27.4.1 Live check for synchronization side and dead check for reference side
(SynLvRefDd)
[79.En_SynLv_RefDd] = Enabled
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
Simulate the single-phase grounding fault, the faulty phase voltage can set between
0V~0.9Un
Fault 1:
25. U_LvChk + max{1% × 25. U_LvChk, 0.1V}, same phase angle with UB-N.
Fault 2:
25. U_LvChk + max{1% × 25. U_LvChk, 0.1V}, same phase angle with UB-N.
Fault 3:
25. U_LvChk − max{1% × 25. U_LvChk, 0.1V}, same phase angle with UB-N.
Fault 4:
25. U_LvChk − max{1% × 25. U_LvChk, 0.1V}, same phase angle with UB-N .
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1 + 1s
8.27.4.2 Dead check for synchronization side and live check for reference side
(SynDdRefLv)
[79.En_SynDd_RefLv] = Enabled
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting VTS.t_DDO and make sure that 79.Ready = 1)
Fault 1:
25. U_DdChk − max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Fault 2:
25. U_DdChk − max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Fault 3:
25. U_DdChk + max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Fault 4:
25. U_DdChk + max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1 + 1s
8.27.4.3 Dead check for both the reference and the synchronization sides(SynDdRefDd)
[79.En_SynDd_RefDd] = Enabled.
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting VTS.t_DDO and make sure that 79.Ready = 1)
Simulate the single-phase grounding fault, the faulty phase voltage can set between
0V~0.9Un
Fault 1:
25. U_DdChk − max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Fault 2:
25. U_DdChk − max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Fault 3:
25. U_DdChk + max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Fault 4:
25. U_DdChk + max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1 + 1s
[79.Num] = 2.
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same Amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting VTS.t_DDO and make sure that 79.Ready = 1)
Simulate the single-phase grounding fault, the faulty phase voltage can set between
0V~0.9Un
Inject Usync = Un, the same phase angle, amplitude, and frequency with UB-N
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1(2) + 1s
(The voltage state of this status must match with synchronization settings mode.)
The 79.Close should operate reliably in the first two faults, as to the third fault, the
79.Close should not operate after the 50/51P1 operated.
1. 79.t_Dd_3PS1
[79.En_NoChk] = Enabled
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting VTS.t_DDO and make sure that 79.Ready = 1)
Usync = Un, same amplitude, frequency and phase angle between U B-N
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1 + 1s
8
The test result:
The 79.Close should operate reliably, the error of operation time≤ 1% × 79. t_Dd_3PS1 +
20ms
2. 79.t_Reclaim
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting VTS.t_DDO and make sure that 79.Ready = 1)
Usync = Un, same amplitude, frequency, and phase angle between UB-N
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1(2) + 1s
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same amplitude
and phase angle between UB-N
Fault 1: The State Termination using Timeout, the duration = 79. t_Reclaim −
{1% × 79. t_Reclaim + 20ms}
Fault 2: The State Termination using Timeout, the duration = 79. t_Reclaim +
{1% × 79. t_Reclaim + 20ms}
Fault 2: In the status 6, the second 79.Close should not operate reliably.
3. 79.t_Wait_Chk
[79.En_SynChk] = Enabled
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting VTS.t_DDO and make sure that 79.Ready = 1)
Usync = Un, different amplitude, frequency, and phase angle with UB-N
Fault 1: The State Termination using Timeout, the duration = 79. t_Wait_Chk − 0.2s
Fault 2: The State Termination using Timeout, the duration = 79. t_Wait_Chk + 0.2s
Usync = Un, same amplitude, frequency, and phase angle between UB-N
4. 79.t_PersistTrp
Inject UA-N/UB-N/UC-N with the rated positive-sequence voltage, Usyn with same amplitude
and phase angle between UB-N
Trigger condition is set to timed trigger, the state duration = 12s (should be greater than
the setting the VTS.t_DDO and make sure that 79.Ready = 1)
Usync = Un, same amplitude, frequency, and phase angle between UB-N
The trigger condition can be set to binary input or timed trigger, and the state duration =
79. t_Dd_3PS1 + 1s
1. Connecting the tester current output Ia/Ib/Ic to the current input of TT protection of the
device. Parallel the N of three phase and connect it back to the In of tester.
2. Please set the tripping logic setting for TT according to the configuration of PCS-931S,
and connect the corresponding binary output of TT to the binary input of tester.
3. Connect the binary output 1 of tester to the “TT.Init_3P” input of PCS-931S to initiate TT
protection .
4. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
[FD.DPFC.I_Set] = 1A .
Fault 1: The faulty phase current = 1.05×[FD.DPFC.I_Set]/1.732, Inject Ia/Ib/Ic with the
positive-sequence current. 8
Fault 2: The faulty phase current = 0.95×[FD.DPFC.I_Set]/1.732, Inject Ia/Ib/Ic with the
positive-sequence current.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[TT.t_Op], [TT.t_Op] +100ms}
The faulty phase current = 2×[FD.DPFC.I_Set]/1.732. Inject Ia/Ib/Ic with the positive-
sequence current.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[TT.t_Op], [TT.t_Op] +100ms}
The TT should operate reliably, the operation error time ≤Max{5ms, 1%×[TT.t_Op]}.
8 4 R0L 3.872
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of FL of the device.
Parallel the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of FL of the device. Parallel
the N of three phase and connect it back to the In of tester.
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal should be energized and the protection
function disabling signal should be de-energized.
According to the above line setting, the line impedance ZL and K0 can be obtained through
calculation:
ZL = 6.25 Ω.
𝑋1𝐿 6.113
𝐴𝑟𝑐𝑡𝑎𝑛 = 𝐴𝑟𝑐𝑡𝑎𝑛 = 78°
𝑅1𝐿 1.299
Inject faulty current with 5A (𝐼∅ = 5𝐴) , the angle of faulty voltage leads the faulty current
𝑋
78 °(𝐴𝑟𝑐𝑡𝑎𝑛 𝑅1𝐿 ).
1𝐿
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[21Li.ZG.t_Op], [21Li.ZG.t_Op] +100ms}
Inject faulty current with 5A (𝐼𝑎𝑏𝑐 = 5𝐴), the angle of faulty voltage leads to the faulty
𝑋1𝐿
current 78°(𝐴𝑟𝑐𝑡𝑎𝑛 ).
𝑅1𝐿
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[21Li.ZP.t_Op], [21Li.ZP.t_Op] +100ms}
Simulate phase A grounding fault with large resistance occurs at m×100% of the line.
𝑋
𝑚×𝐼∅ ×( 1 + 𝐾0 )×𝑍𝐿 ×𝑆𝑖𝑛(𝐴𝑟𝑐𝑡𝑎𝑛𝑅1𝐿 )
1𝐿
The faulty phase voltage =
𝑆𝑖𝑛𝜃
Inject faulty current with 5A(𝐼∅ = 5𝐴). θ is the angle at which the faulty voltage leads the
faulty current.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[21Li.ZG.t_Op], [21Li.ZG.t_Op] +100ms}
Simulate 3 phase fault with large resistance occurs at m×100% of the line.
𝑋
𝑚×𝐼∅ ×𝑍𝐿 ×𝑆𝑖𝑛(𝐴𝑟𝑐𝑡𝑎𝑛 𝑅1𝐿 ) 𝑚×5×6.25×𝑆𝑖𝑛78°
The faulty phase voltage =
𝑆𝑖𝑛𝜃
1𝐿
=
𝑆𝑖𝑛𝜃
(V), 8
0 < m <1.
𝑚×5×6.25×𝑆𝑖𝑛78°
Inject faulty phase voltage with V.
𝑆𝑖𝑛𝜃
Inject faulty current with 5A(𝐼𝑎𝑏𝑐 = 5𝐴), θ is the angle at which faulty voltage leads to the
faulty current.
The trigger condition can be set to binary input or timed trigger, and the state duration =
Max {1.01×[21Li.ZP.t_Op], [21Li.ZP.t_Op] +100ms}
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the Un of tester.
2. If the function signal “VTS.Enable” and “VTS.Block” are configured, “VTS.Enable” must
be energized and “VTS.Block” must be de-energized.
The trigger condition can be set to “timed trigger”, and the state duration > [VTS.t_DPU].
(The voltage of other two phase keeps the same with that in stage 1.)
The trigger condition can be set to “timed trigger”, and the state duration > [VTS.t_DPU].
[VTS.3U0_Set] = 100V
(The voltage of other two phase keeps the same with that in stage 1.)
The trigger condition can be set to “timed trigger”, and the state duration > [VTS.t_DPU].
3 CTS.t_DPU 1.25 s
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the Un of tester.
2. Connecting the tester current output Ia/Ib/Ic to the current input of the device. Parallel the
N of three phase and connect it back to the In of tester.
3. If the function signal “CTS.Enable” and “CTS.Block” are configured, “CTS.Enable” must
be energized and “CTS.Block” must be de-energized.
Simulate failure of single-phase on CT, the abnormal phase current = 0 A, the current of
other two phase and the voltage of three phase keeps the same with that in stage 1.
The trigger condition can be set to “timed trigger”, and the state duration > [CTS.t_DPU].
Table of Contents
List of Figures
Figure 9.2-1 Three Phase Busbar Voltage of 1 CB with 2 Busbars ....................................... 9-3
Figure 9.2-3 Single Phase Busbar Voltage of 1 CB with 2 Busbars ...................................... 9-4
Figure 9.2-6 Configuration for busbar side CB (Busbar1 CB) ................................................ 9-6
The switchgear control function is mainly used to realize operation of primary equipment such as
circuit breaker (CB), disconnect switch (DS) and earthing switch (ES). This function can be divided
into remote control and local control according to the control source location. A remote control
mainly refers to remote control commands from substation automation system (SAS) or network
control center (NCC).
When the device is in the remote-control mode, the control command may be sent via
communication protocol; when it is in the local control mode, the local operation may be performed
on the device LCD or panel handle.
If the test requires the operation of primary equipment, ensure that these devices have been out of
operation.
The one-to-one match closing or opening contact shall be closed as soon as the command received,
either the command is from remote or local.
If the switch needs to be closed or opened, check whether the corresponding interlock output that 9
allows operation.
The voltage selection function can be used to switch the reference and synchronization voltages
for the synchronism check function in double busbars and one-and-half circuit breakers scenarios,
or to switch three-phase voltages among double busbars used by protection calculations or
measurements.
In order to verify whether the voltage switching logic is correct, ensure that the voltage switching
logic works according to the designer’s intent.
The voltage selection function can be used for the synchronism check function in one-and-half
circuit breakers arrangement scenario and for three-phase protection or measurement voltage
selection in double busbars scenario.
⚫ The voltage input channels should be connected to the voltage selection function input
terminals in the page Project Node → IED Node → Program → Function_Logic →
UserPage_Meas_App*. Locate the functional input/output channels under the path: Variable
DB → Source or Destination → Function_Logic → Page: UserPage_VoltSel_CB** →
Component: CB**.VoltSel.
⚫ The relevant disconnectors position states should be inputted in the page Project Node →
IED Node → Program → Function_Logic → UserPage_VoltSel_CB**. Locate the binary
inputs under the path: Variable DB → Source → Function_Logic → Page: UserPage_DS**
→ Component: DS**.
9 For single circuit breaker with double busbars, the selection of appropriate voltage from both
busbars for synchronism check is required. The bus voltage to be switched can be either three
phase or single phase. The three phase voltages after switching is used as the reference voltage,
and single-phase voltage after switching is used as the synchronization voltage.
Busbar 1
Busbar 2
DS1 DS2
3VTs 3VTs
CB0 1
1VT
3CTs
*
1CT
*
Case 3&4: The device is alarm with the report “Alm_Invalid_Sel”, and the reference
voltage displayed by the device is the voltage of the previous state.
Busbar 1
Busbar 2
DS1 DS2
1VT 1VT
CB0 1
3VTs
3CTs
*
1CT
*
9
Figure 9.2-3 Single Phase Busbar Voltage of 1 CB with 2 Busbars
Case 3&4: The device is alarm with the report “Alm_Invalid_Sel”, and the synchronization
displayed by the device is the voltage of the previous state.
For the tie CB of one-and-half breakers arrangement in the application scenario of a complete
diameter, the selection of voltage from Line1_VT & Bus1_VT and Line2_VT & Bus2_VT is the
reference voltage and synchronization voltage respectively to check synchronism for the closing
operation.
Busbar1
9
Bus1
CB
1VT
3VTs *
3CTs
DS1
*
3CTs
1VT Tie
CB
DS2
Bus2
CB
1VT
Busbar2
Case 1: The reference voltage is displayed as UL1, the Syn voltage is UB1;
Case 2: The reference voltage is displayed as UL2, the Syn voltage is UB1;
Case 3: The reference voltage is displayed as UB2, the Syn voltage is UB1;
Case 4: The device is alarm with the report “Alm_Invalid_Sel”, and the reference and syn
voltage displayed by the device is the voltage of the previous state.
Case 1: The reference voltage is displayed as UL1, the Syn voltage is UB2;
Case 2: The reference voltage is displayed as UB1, the Syn voltage is UL2;
Case 3: The reference voltage is displayed as UL1, the Syn voltage is UL2;
Case 4: The device is alarm with the report “Alm_Invalid_Sel”, and the reference and syn
voltage displayed by the device is the voltage of the previous state.
This section contains instructions on how to test synchrocheck, energizing check and synchronizing
function for single, double and 1½ breaker arrangements.
1. Connecting the tester voltage output Ua/Ub/Uc to the voltage input of the device. Parallel
the N of three phase and connect it back to the “Un” of tester.
2. Enable the second group voltage output of tester, using as Usync after volage switching,
connect it to Ux of the device.
3. If the protection function enabling signal and the protection function disabling signal are
configured, the protection function enabling signal must be energized and the protection
function disabling signal must be de-energized.
[25.f_Diff_Set] = 0.2Hz
The setting [25.U_UV], [25.U_OV], [25.f_UF], [ 25.f_OF] are the limit values
of voltage amplitude and frequency. If the voltage exceed the range of
settings, the device determines that as abnormal state and is not allowed to
synchronize.
[25.U_Diff_Set] = 10V
[25.phi_Diff_Set] = 15 deg
The setting [25.U_UV], [25.U_OV], [25.f_UF], [ 25.f_OF] are the limit values
of voltage amplitude and frequency. If the voltage exceed the range of
settings, the device determines that as abnormal state and is not allowed to
9
synchronize.
1. Live Check for Synchronization Side and Dead Check for Reference Side(SynLvRefDd)
[Opt_Mode_DdChk] = SynLvRefDd
[25.U_DdChk] = 30V
[25.U_LvChk] = 40V
2. Dead Check for Synchronization Side and Live Check for Reference Side(SynDdRefLv)
[Opt_Mode_DdChk] = SynDdRefLv
[25.U_DdChk] = 30V
[25.U_LvChk] = 40V
Case 1:
Usync = 25. U_DdChk − max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Inject UA-N/UB-N/UC-N with positive-sequence voltage, the amplitude is
9 25. U_LvChk + max{1% × 25. U_LvChk, 0.1V}
Case 2:
Usync = 25. U_DdChk − max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Inject UA-N/UB-N/UC-N with positive-sequence voltage, the amplitude is
25. U_LvChk − max{1% × 25. U_LvChk, 0.1V}
Case 3:
Usync = 25. U_DdChk + max{1% × 25. U_DdChk, 0.1V}, same phase angle with UB-N
Inject UA-N/UB-N/UC-N with positive-sequence voltage, the amplitude is
25. U_LvChk + max{1% × 25. U_LvChk, 0.1V}
3. Dead Check for Both the Reference and the Synchronization Sides(SynDdRefDd)
[Opt_Mode_DdChk] = SynDdRefLv
[25.U_DdChk] = 30V
[25.U_LvChk] = 40V
In order to verify whether the interlock logic is correct, ensure that the interlock logic works
according to the designer’s intent.
1. After finishing the Interlock logic, connecting it with “xxx.CILO.EnaOpn” and “xxx.CILO.EnaCls”
which is located in the “Destination” menu. In addition, an input is defined as “xxx.
in_CILO_Bypass”, for example, a panel switch or a remote command signal to release interlock
function.
3. The external input wiring is correct to ensure that the device input collection is normal.
Change the state of the relevant input to simulate the blocking condition, and determine whether
the logic blocking result is correct by setting the interlocking state value of the LCD liquid crystal
panel.
If the input of “xxx. in_CILO_Bypass” is on, the interlock function of the switch is released.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform the wiring verification tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram.
If the configuration was changed for testing, the original configuration must be downloaded to
device.
Restore settings to their original value, if they were changed for testing purposes.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero.
If a test block is installed, remove the test plug and replace the cover so that the protection is put
into service.
It is necessary to exit the maintenance state before putting the device into operation. If 61850 ed2.0
LD mode is used to set the maintenance status, it needs to be controlled in SCADA to exit the
maintenance state.
Ensure that all event records, fault records, disturbance records and alarms have been cleared and
LEDs have been reset before leaving the device. Once secondary testing has been completed, it
should be checked that no self-supervision signals are activated continuously or sporadically.
Especially check the time synchronization system and communication signals, both station
communication and remote communication.
10
10
Appendix A Glossary
The abbreviations adopted in this manual are listed as below.
DC Direct Current
B
DLLB Dead Line Live Bus
"b" Contact is breaker auxiliary contact (ANSI
DNP Distributed Network Protocol as per IEEE
Standard Device Number 52B) that closes
Std 1815-2012
when the breaker is open and opens when the
breaker is closed. DPFC Deviation of Power Frequency
Component–In case of a fault occurred in the
BFP Breaker failure protection
power system, the fault component could be
BI Binary Input analyzed into three parts: the power frequency
components before the fault, the power
BO Binary Output
frequency variables during the fault and the
transient variables during the fault. DPFC is the IRIG-B InterRange Instrumentation Group
power frequency variable during the fault. Time code format B
FR Fault Recorder
O
G
OLTC On-load Tap Changer
A list of function numbers used to represent electrical protection and control element. The device
function numbers used in this manual include the following:
These numbers are frequently used within a suffix letter to further designate their application. The
P Phase element
G Residual/Ground element
N Neutral/Ground element
Q Negative-sequence element