PCS-931S X Settings+Guide EN Overseas+General X R1.10
PCS-931S X Settings+Guide EN Overseas+General X R1.10
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. Reserves all rights and benefits
afforded under P.R. China and international copyright and patent laws in its products, including but
not limited to software, firmware and documentation. NR Engineering Co., Ltd. Is licensed to use
this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd,
including but not limited to copyright, rights in inventions, patents, know-how, trade secrets,
trademarks and trade names, service marks, design rights, database rights and rights in data, utility
models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered sufficiently
for your purposes, please do not hesitate to contact us.
Preface
Preface
The setting guide will give instructions about the setting values of various functions (including the
protection, automation, control, and supervision functions) that is equipped with the device, mainly
in these aspects: brief introduction of the element, calculation principle of the element according to
the setting value related, and partial recommended value based upon domestic usage and
experience. However, the empirical value may not be fully applicable for the power system of other
country, it should be checked according to the practical requirements of local power system. All
settings are only a reference and are not used as final commissioning settings.
For these calculation results of settings for each function, they are calculated based on the
parameters provided by primary equipment manufacturer and system parameters from the field,
which should be confirmed based on on-site specific application and checked Iarefully.
Planning
Ordering
Engineering
Installing
Commissioning
Operation
Maintenance
Disposal
The datasheet (DS) contains describes the control, protection, measurement and supervision
The selection guide (SLG) contains the explanation about the application option, the firmware
option, the software option, the hardware option and etc., and is instructive about how to order the
device based on expected configurations.
The technical manual I contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.
The application manual (AM) contains application descriptions and instructions on how to
engineer the device using the configuration tool PCS-Studio. The manual can be used to find out
when and for what purpose a typical protection function can be used. The manual also recommends
a sequence for the engineering of protection, control, measurement and supervision functions, HMI
functions as well as communication engineering.
The communication protocol manual (CPM) describes the communication protocols supported
by the device. The manual concentrates on the vendor-specific implementations.
The operation and commissioning manual (OCM) contains instructions on how to operate and
commission the device. The manual describes how to identify disturbances and how to view
calculated and measured power grid data to determine the cause of a fault. The manual also
describes the process of testing the device in a substation which is not in service.
The installation and maintenance manual (IMM) contains instructions on how to install, maintain
and disposal the device. The manual provides procedures for mechanical and electrical installation,
lifecycle maintenance and repairing, and scrap disposal when decommissioning.
The cybersecurity manual (CM) describes the process for handling cyber security when
communicating with the device. Certification, Authorization with role-based access control, and
product engineering for cyber security related events are described and sorted by function. The
guideline can be used as a technical reference during the engineering phase, commissioning phase,
and during normal service.
The settings guide (STG) contains instructions on how to calculate the device's settings of various
functions (including the protection, automation, control, and supervision functions) according to the
different system parameters and fault conditions.
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for personal
safety, as well as to avoid material damage. Information is highlighted and illustrated as follows
according to the degree of danger:
Indicates that property damage can result if the measures specified are
not taken.
Contact with instrument terminals can cause electrical shock that can result
in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not qualified
to service this equipment, you can injure yourself or others, or cause
equipment damage.
DO NOT look into the end of an optical cable connected to an optical output.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage can
result otherwise.
The guide is not involving of the functions′ configuration and principle, and
the detailed description of relevant contents can be found in the
corresponding technical manual and application manual. Before carrying
out any setting work on the device, the user should be familiar with the
contents of this guide, and this guide must be thoroughly read and
understood.
Document Conventions
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫ Binary input signals, binary output signals, analogues, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
Symbols
OR Gate Comparator
>=2
2-out-of-3 2 inputs
Logic Input
Timer
Fixed delay pickup (10ms), fixed Settable delay pickup, fixed delay
delay dropout (2ms) dropout
Primary Equipment
G M 52
Current Voltage
Earth Bus
transformer transformer
Basic
A, B, C L1, L2, L3 R, Y, B
AN, BN, CN L1N, L2N, L3N RN, YN, BN
ABC L123 RYB
U (voltage) V U
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
Warranty
NR can provide up to 10-year warranty for this product. For warranty details, please consult the
manufacturer or agent for more information.
Document Structure
This manual provides detailed instructions for setting the PCS-931S, which covers all functions,
such as protection, control, supervision, measurement, etc., and general device setup. Read the
sections that pertain to your application to gain valuable information about using the PCS-931S. To
concentrate on the target sections of this manual as your job needs and responsibilities dictate. An
overview of each manual section and section topics follows.
1 Introduction
Introduces summarizes functions and full view about the settings in the device.
2 Global Settings
Describs the access path, settings list (name, range, unit and step) of global settings, including
system setting, device setting, communication setting, disturbance fault recording setting, label
setting and clock synchronization setting supervision setting, and some important setting principles
are also provided.
3 Protection Settings
Describes the access path, settings list (name, range, unit and step) of protection settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided. Some application examples are provided to help familiarize and understand the
calculation process, and to assist you with your own protection settings calculations.
4 Control Settings
Describes the access path, settings list (name, range, unit and step) of control settings. The detailed
setting calculation guidelines and the recommended value of some settings are also provided.
5 Measurement Settings
Describes the access path, settings list (name, range, unit and step) of measurement settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided.
8 Supervision Settings
Describes the access path, settings list (name, range, unit and step) of supervision settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided.
9 Logic Links
Describes the access path, settings list (name, range, unit and step) of logic links. The detailed
setting calculation guidelines and the recommended value of some settings are also provided.
Corresponding Version
Release Date Description of change
Document Software
1 Introduction
1
Table of Contents
List of Figures
Figure 1.1-1 Typical application of single circuit breaker (single busbar)............................ 1-1
Figure 1.1-2 Typical application of single circuit breaker (double busbars) ........................ 1-1
Figure 1.1-4 Sampled analogue values from MU and conventional CT/VT .......................... 1-2
1.1 Overview
PCS-931S protect overhead and underground lines, feeders, and cables on all voltage levels with
1
highest possible selectivity. The availability of various protection and automation functions permits
its utilization in all domains of line protection. The devices contain all important auxiliary functions
that are necessary today for safe network operation. This includes control, measurement and
monitoring functions. The large number of communication interfaces and communication protocols
satisfies the requirements of communication-based selective protection and automation operation.
Its modular structure permits line protection devices always to be adapted flexibly to the individual
requirements.
3CT 3CT
52 * * 52
3VT 3VT
CH1 CH1
PCS-931S Optical fibre channel PCS-931S
CH2 CH2
1VT 1VT
Communication channel via direct dedicated fibre or MUX
3CT 3CT
52
* * 52
1VT 1VT
CH1 CH1
PCS-931S Optical fibre channel PCS-931S
CH2 CH2
3VT 3VT
PCS-931S is a high-speed transmission line differential relay featuring single-pole & three-pole
tripping and reclosing with synchronism check. The device features extensive metering & data
recording including high-resolution data capture and reporting. PCS-931S features expanded
control equation programming for easy and flexible implementation of custom protection and
control schemes.
PCS-931S can be configured to support single circuit breaker application or double circuit breakers
application by PCS-Studio. If the device is applied to double circuit breakers mode, all protection
functions related to the number of circuit breaker will be affected.
The PCS-931S is widely adopted not only for conventional substations, but also for digital
substations. It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network
interfaces with high real-time performance. The process level network supports peer-to-peer (P2P)
mode and networking mode, including single network mode and dual network mode. The station
1 level network could also receive and send MMS messages (such as interlocking signals) or process
level GOOSE messages (such as circuit breakers or disconnectors positions and trip signals).
52 52
1VT 1VT
*
*
3CT 3CT
3VT 3VT
CH1 CH1
52 52
PCS-931S Optical fibre channel PCS-931S
CH2 CH2
3CT 3CT
*
*
1VT Communication channel via direct dedicated fibre or MUX 1VT
1VT 1VT
52 52
The PCS-931S allow the use of digital quantities (SV sampled signals), conventional quantities
(wired analog signals) or mixed implementations in networking mode. Time synchronization is
available in the device by the external clock source.
Line 1 Line 2
52
MU
1VT
AC Module SV Module
PCS-931S
For the mixed mode, the digital quantities (SV sampled signals) is acquired 1
by CPU module and the conventional quantities (wired analog signals) is
acquired by analog input module. The sampling mode should be selected
according to the actual project application. If the mixed mode is selected,
SV sampled signals must adopt the networking mode, analog input module
must adopt 4CT/4VT (4 current inputs & 4 voltage inputs), and the external
clock source must be available. For voltage selection of the mixed mode,
the switched voltages must adopt the same sampling signal (SV sampled
signals or wired analog signals).
1.2 Functions
The functional overview of the device is shown in Figure 1.2-1.
Busbar
3VT
52
*
85 21L 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
78 FR 27P
FL 59G
81U 81R
Line
1 Protection
⚫ CT saturation detection
1
⚫ Capacitive current compensation
scheme
Pilot directional earth-fault
⚫ PTT, Blocking and Unblocking
protection
⚫ Current reversal logic
⚫ Up to 6 zones
each zone
each zone
zone
46BC Broken conductor protection sequence current (Ι2/Ι1) to detect the broken conductor.
circuit breaker
62PD Pole discrepancy protection
⚫ Optional auxiliary criterion (zero-sequence current
overcurrent element)
lines
2 Control
⚫ Voltage selection
3 Synchrophasor measurement
⚫ Calculate synchronized phasors, including: Ua, Ub, Uc, U1, U2, U0, Ia, Ib, Ic, I1, I2, I0
⚫ Calculate analog values, including: active power (P), reactive power (Q), frequency,
ROCOF (df/dt)
⚫ Transmit binary status of the IED to PDC (Phasor Data Concentrator) according to IEEE
C37.118 standard
⚫ Realize high accurate measurement of the phasors and analogs according to the IEEE
C37.118.1-2011 and IEEE C37.118.1a-2014 standard.
⚫ Energy metering (active and reactive energy are calculated in import respectively export
direction)
⚫ Power (Apparent/Real/Reactive)
⚫ Power factor
⚫ Frequency
5 Recording
⚫ Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
⚫ 64 travelling wave fault location (TWFL) records (The file format of disturbance recorder is
compatible with international COMTRADE file.)
6 Supervision
⚫ VT circuit supervision
⚫ CT circuit supervision
⚫ Self diagnostic
⚫ Circuit breaker supervision (contact travel time, interrupted current, trip counter, remaining
8 Communication interface
9 Communication protocol
⚫ IEC 60870-5-103
⚫ DNP3.0
⚫ Modbus
10 Digital application
⚫ IEC 61850-9-2LE SV
11 Clock synchronization
⚫ IRIG-B: IRIG-B via serial port (RS-485 or TTL level) or BNC port (TTL level)
⚫ PPS: Pulse per second (PPS) via serial port (RS-485 or TTL level), BNC port (TTL level)
or binary input 1
⚫ IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
⚫ SNTP: Unicast (point-to-point) & broadcast SNTP mode via Ethernet network
⚫ Clock messages: IEC 60870-5-103 protocol, Modbus protocol and DNP3.0 protocol
12 Cyber security
⚫ NERC CIP
⚫ IEC 62351
⚫ IEC 62443
⚫ IEEE 1686
13 User interface
⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment
⚫ Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
⚫ Configuration tool—PCS-Studio
14 Miscellaneous
Settings
1 System Settings
Device Settings
Communication Settings
IEC61850 Settings
IEC103 Settings
DNP Settings
Modbus Settings
SV Settings
DFR Settings
Label Settings
ClockSyn Settings
Superv Settings
FD Settings
Line Settings
Function Settings
Syn Settings
DPS Settings
Control Settings
Interlocking Settings
AC Calbr Settings
SCBR Settings
TWFL Settings
PMU Settings
Logic Links
Function Links
SV Recv Links
2 Global Settings
Table of Contents
List of Tables
⚫ LCD
Active_Grp 1~20 1
Opt_SysFreq 50, 60 Hz
ABC
Opt_PhSeq
ACB
Prot.CB1.I1n 0~60000 1 A
Prot.CB1.I2n 1 or 5 A
Prot.CB2.I1n 0~60000 1 A
Prot.CB2.I2n 1 or 5 A
3I0Adj.I1n 0~60000 1 A
3I0Adj.I2n 1 or 5 A
Disabled
Prot.CB1.En_RevCT
Enabled
Disabled
Prot.CB2.En_RevCT
2 Enabled
Disabled
3I0Adj.En_RevCT
Enabled
Disabled
Prot.En_VT
Enabled
NoVoltSel
DblBusOneCB
CB1.VoltSel.Opt_CBConfig 3/2BusCB1
3/2TieCB
3/2BusCB2
NoVoltSel
DblBusOneCB
CB2.VoltSel.Opt_CBConfig 3/2BusCB1
3/2TieCB
3/2BusCB2
1. Active_Grp
It is used to set the number of active setting group, and several setting groups (20 at most) can be
configured for protection settings and measurement & control settings, but only one is active at a
time.
The settings in different group can be changed to suit the needs of actual application. The default
settings have been chosen according to established practice but will usually require adjustment to
suit the requirements of individual applications.
2. PrimaryEquip_Name
It is used to set the name of the protected primary equipment, such as busbar, transformer, line,
capacitor, etc. It will be displayed in the printed result and the DFR (Disturbance Fault Recording)
file.
This setting is case sensitive, and its maximum permissible length of this setting is 20 characters.
All the allowed characters in this setting are listed as below:
A a B b C c D d E e F f
G g H h I i J j K k L l
2
M m N n O o P p Q q R r
S s T t U u V v W w X x
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
3. Opt_SysFreq
It is used to set the system frequency. It can be set to either 50Hz or 60 Hz according to the system
frequency.
4. Opt_PhSeq
It is used to inform the device of the actual system phase sequence, either "ABC" or "ACB". CT
and VT inputs on the device, labeled as A, B and C, must be connected to system phase A, B and
C for correct operation. This will affect positive/negative-sequence quantities calculated by the
device and will also affect functions that are dependent on phase quantities.
5. Prot.U1n
It is used to set primary rated voltage of VT (protection voltage), and it should be set based on
phase-to-phase value.
6. Prot.U2n
It is used to set secondary rated voltage of VT (protection voltage), and it should be set based on
phase-to-phase value.
7. Prot.CB*.I1n
It is used to set primary rated value of CT corresponding to circuit breaker * (protection current, *=1
or 2).
8. Prot.CB*.I2n
It is used to set secondary rated value of CT corresponding to circuit breaker * (protection current,
*=1 or 2).
9. UB1.Syn.U1n
It is used to set primary rated voltage of busbar No.1 VT (synchronism voltage), and it should be
set based on phase-to-phase value.
10. UB1.Syn.U2n
It is used to set secondary rated voltage of busbar No.1 VT (synchronism voltage), and it should
2 be set based on phase-to-phase value.
11. UL2.Syn.U1n
It is used to set primary rated voltage of line No.2 VT (synchronism voltage), and it should be set
based on phase-to-phase value.
12. UL2.Syn.U2n
It is used to set secondary rated voltage of line No.2 VT (synchronism voltage), and it should be
set based on phase-to-phase value.
13. UB2.Syn.U1n
It is used to set primary rated voltage of busbar No.2 VT (synchronism voltage), and it should be
set based on phase-to-phase value.
14. UB2.Syn.U2n
It is used to set secondary rated voltage of busbar No.2 VT (synchronism voltage), and it should
be set based on phase-to-phase value.
15. 3I0Adj.I1n
It is used to set primary rated value of CT. (residual current for mutual coupling compensation)
16. 3I0Adj.I2n
It is used to set secondary rated value of CT. (residual current for mutual coupling compensation)
17. Prot.CB*.En_RevCT
18. 3I0Adj.En_RevCT
19. Prot.En_VT
It is used to enable/disable VT connect to the device, which is used for protection calculation.
20. CB*.VoltSel.Opt_CBConfig
It is used to select the configuration mode of circuit breaker *, and it should be set as "NoVoltSel"
if no voltage selection is adopted. (*=1 or 2)
3/2BusCB1: bus 1 side circuit breaker for one and a half breakers
2
3/2TieCB: line side circuit breaker for one and a half breakers
3/2BusCB2: bus 2 side circuit breaker for one and a half breakers
⚫ PCS-Studio
Disabled
En_DebugPort
Enabled
Disabled
En_TelnetPort
Enabled
Disabled
En_VirtualLCDPort
Enabled
Ctrl_Password 000~999 1
Disabled
En_NoCtrlPwd
Enabled
Disabled
En_PopupRecord_Blkd
Enabled
Un_BinaryInput 24~250 1 V
DC
Opt_Pwr_BI AC50Hz
2 AC60Hz
Num_Blk_Jitter 2~500000 1
Num_Reblk_Jitter 1~500000 1
Disabled
En_Jitter_Blk
Enabled
Disabled
En_BICheckInstP
Enabled
1. En_DebugPort
It is used to enable/disable the debugging port of this device, which is used for debugging tool
connection, program download, variable debugging, etc. via PCS-Studio configuration tool.
If all the unnecessary ports (including the debugging port) are required to be disabled to ensure
cyber security, please configure this setting as "Disabled".
2. En_TelnetPort
If the Telnet port needs to be used, please configure this setting as “Enabled”.
If all the unnecessary ports (including the Telnet port) are required to be disabled to ensure cyber
security, please configure this setting as "Disabled"'.
3. En_VirtualLCDPort
The virtual LCD port is used to simulate a virtual HMI to acquire device information via PCS-Studio
configuration tool. If all the unnecessary ports (including the virtual LCD port) are required to be
disabled to ensure cyber security, please configure this setting as "Disabled".
4. Ctrl_Password
It is used to set the password when executing the control operation via the device's LCD.
Only digits from "000" to "999" can be accepted. If the setting [En_NoCtrlPwd] is configured as
"Enabled", this setting will be invalid even if it is configured.
5. En_NoCtrlPwd
It is used to determine whether it is necessary to input the password when executing the control
2
operation via the device's LCD.
Disabled: it is necessary to input the password when executing the control operation via the
device's LCD.
Enabled: the control operation to switchgear (CB or DS) via the device's LCD can be directly
executed without the password verification.
6. En_PopupRecord_Blkd
If all the event records (including disturbance records, supervision events, IO events, control events,
etc.) are forbidden to pop up in the main graph of local LCD automatically, i.e.: they can only be
viewed by entering corresponding menus, please configure this setting as "Enabled".
7. Un_BinaryInput
It must be the same as the voltage level of the binary inputs which are connected to this device.
8. Opt_Pwr_BI
Three options are available: DC, AC50Hz and AC60Hz. It must be the same as the power supply
mode of the binary inputs which are connected to this device.
9. U_Pickup_BI
This setting is expressed as a percentage value. It must be smaller than the minimum normal binary
input voltage of the binary inputs connected to this device. Base on engineering experience, it is
recommended to be configured as "63.0%".
10. U_Dropoff_BI
This setting is expressed as a percentage value. It must be smaller than the value of the setting
[U_Pickup_BI] in this device. Base on engineering experience, it is recommended to be configured
as "55.0%".
11. Mon_Window_Jitter
In the time span defined by this setting, the state changes of binary input will be recorded. If the
binary input jitter processing is required, this setting must be configured as a value greater than 0.
When the setting [En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be
2 configured.
12. Num_Blk_Jitter
It is used to set the times threshold to block the state changes of binary input due to jitter.
If the binary input jitter processing is required, this setting must be configured as a value greater
than 0. If the setting [Mon_Window_Jitter] is modified to a bigger value, the setting [Num_Blk_Jitter]
is recommended to be modified to a bigger value, too. When the setting [En_Jitter_Blk] is set as
"Disabled", this setting will be unnecessary to be configured.
13. Blk_Window_Jitter
In the time span defined by this setting, the state changes of binary inpu will be recorded. If the
binary input jitter processing is required, this setting must be configured as a value greater than 0.
When the setting [En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be
configured.
14. Num_Reblk_Jitter
It is times threshold to initiate immediately another blocking window of the state changes of binary
input due to continuous jitter.
If the binary input jitter processing is required, this setting must be configured as a value greater
than 0. If the setting [Blk_Window_Jitter] is modified to a bigger value, the setting
[Num_Reblk_Jitter] is recommended to be modified to a bigger value, too. When the setting
[En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be configured.
15. En_Jitter_Blk
It is used to enable/disable the jitter processing function in case of binary input voltage variation.
If binary input jitter processing is required, please configure this setting as "Enabled".
16. En_BICheckInstP
If the binary input the rated voltage of binary input is 110Vdc or above is applied to acquire the
mechanical signal, for example, the binary signal from winding temperature relay, oil temperature
relay or Buchholz relay. The conducting mode of each binary input is switched into the high-power
mode to improve the anti-interference ability when the setting [En_BICheckInstP] is set as
"Enabled". The binary input will not be considered as being energized unless the instantaneous
active power rises to a certain value and during time is larger than 20ms, so as to avoid mistaken
signal.
This conducting mode is only available in the device equipped with some certain BI plug-in modules
(NR6604A or NR6611A) and the rated voltage of binary input is 110Vdc or above. Otherwise, this
conducting mode will be unavailable and this setting will be hidden.
When the setting [En_BICheckInstP] is set as "Enabled", and the debouncing time should be larger
than the during time (20ms) of the instantaneous active power.
2
2.3 Communication Settings
⚫ LCD
⚫ PCS-Studio
IP_LAN1 0.0.0.0~255.255.255.255
Mask_LAN1 0.0.0.0~255.255.255.255
Disabled
En_LAN1
Enabled
IP_LAN2 0.0.0.0~255.255.255.255
Mask_LAN2 0.0.0.0~255.255.255.255
Disabled
En_LAN2
Enabled
IP_LAN3 0.0.0.0~255.255.255.255
Mask_LAN3 0.0.0.0~255.255.255.255
Disabled
En_LAN3
Enabled
IP_LAN4 0.0.0.0~255.255.255.255
Mask_LAN4 0.0.0.0~255.255.255.255
Disabled
En_LAN4
Enabled
2 Gateway 0.0.0.0~255.255.255.255
4800
9600
19200
Baud_Printer bps
38400
57600
115200
Disabled
En_AutoPrint
Enabled
IEC103
Protocol_RS485-1
Modbus
IEC103
Protocol_RS485-2
Modbus
4800
9600
19200
Baud_RS485-1 bps
38400
57600
115200
4800
9600
19200
Baud_RS485-2 bps
38400
57600
115200
Addr_RS485-1 1~254 1
Addr_RS485-2 1~254 1
Normal
B01.Grp01.Opt_NetMode
PRP 2
HSR
Bond
Normal
PRP
B01.Grp02.Opt_NetMode HSR
RSTP
Bond
IP_SyslogServer01 0.0.0.0~255.255.255.255
IP_SyslogServer02 0.0.0.0~255.255.255.255
IP_SyslogServer03 0.0.0.0~255.255.255.255
IP_SyslogServer04 0.0.0.0~255.255.255.255
Disabled
En_IP_Whitelist
Enabled
IP**_Whitelist 0.0.0.0~255.255.255.255
Disabled
En_ARP_Bind
Enabled
1. IP_LAN*
It is used to set IP address of Ethernet port * in the CPU plug-in module (*=1, 2, 3, 4).
This setting adopts dotted-decimal notation of IPv4. If the setting [En_LAN*] is configured as
"Disabled", this setting will be unnecessary to be configured. Please configure this setting
according to actual requirements.
2. Mask_LAN*
It is used to set subnet mask of Ethernet port * in the CPU plug-in module (*=1, 2, 3, 4).
This setting adopts dotted-decimal notation of IPv4. If the setting [En_LAN*] is configured as
"Disabled", this setting will be unnecessary to be configured. Please configure this setting
according to actual requirements.
3. En_LAN*
It is used to enable/disable Ethernet port * in the CPU plug-in module (*=1, 2, 3, 4).
4. Gateway
If there is no gateway, please configure this setting as "0.0.0.0". This setting adopts dotted-decimal
notation of IPv4.
5. Baud_Printer
It must be the same as the baud rate of the printer that is connected to this device.
6. En_AutoPrint
When the setting is set as "Enabled", they will be printed automatically when the event records
(such as, disturbance records, supervision events, IO events, etc.) are generated.
7. Protocol_RS485-1, Protocol_RS485-2
It must be the same as corresponding setting value of the communication client (for example, local
SCADA system, etc.).
8. Baud_RS485-1, Baud_RS485-2
It is used to set baud rate of rear RS-485 serial port 1 (2) in the CPU plug-in module.
It must be the same as corresponding setting value of the communication client (for example, local
SCADA system, etc.).
9. Addr_RS485-1, Addr_RS485-2
It is used to set communication address of rear RS-485 serial port 1 (2) in the CPU plug-in module.
It must be the same as corresponding setting value of the communication client (for example, local
SCADA system, etc.).
10. B01.Grp01.Opt_NetMode
It is used to select the network method of the first group of ports (port 1 & port 2) of the CPU module
located in slot No.1. Four options are available, please configure this setting according to actual
requirements.
1) Normal
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU module adopt "Normal" 2
mode. In the "Normal" mode, there is no data redundancy mechanism.
2) PRP
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module adopt adopt
"PRP" mode (IEC 62439-3 Parallel Redundancy Protocol) to realize data redundancy.
In the "PRP" mode, the data redundancy is realized in this way: the communication is performed
in parallel, i.e., the same data package is transmitted on both channels simultaneously. The
received package identity from one channel is compared with data package identity from the other
channel. If they are the same, the last package will be discarded.
3) HSR
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module adopt
"HSR" mode (IEC 62439-3 High-availability Seamless Redundancy) to realize data redundancy.
In the "HSR" mode, the principle of parallel operation to a single ring is applied to realize data
redundancy. For each message sent, the node sends two frames, one through each port. Both the
2 frames circulate in opposite directions over the ring. Every node forwards the frames it receives
from one port to another to reach the next node. When the originating sender node receives the
frame it sent, the sender node discards the frame to avoid loops.
4) Bond
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module are used
as hot standby each other to ensure reliable communication of dual networks (i.e., network 1 and
network 2). When both network 1 and network 2 are normal, any of them is used to communicate
between the device and SAS. The device will automatically switch to the other healthy network
when one network is abnormal, which will not affect normal communication.
Ethernet port 1 is connected to network 1 while Ethernet port 2 is connected to network 2, and the
switching logic is:
⚫ After the device is powered on, only Ethernet port 1 is activated when both network 1 and
network 2 are normal.
⚫ If Ethernet port 2 is working, the device will maintain this state even if network 1 has been
11. B01.Grp02.Opt_NetMode
It is used to select the network method of the first group of ports (port 3 & port 4) of the CPU module
located in slot No.1. Five options are available, please configure this setting according to actual
requirements.
2 1) Normal
If this option is selected, Ethernet port 3 and Ethernet port 4 of the CPU module adopt "Normal"
mode. In the "Normal" mode, there is no data redundancy mechanism.
2) PRP
If this option is selected, Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt adopt
"PRP" mode (IEC 62439-3 Parallel Redundancy Protocol) to realize data redundancy.
In the "PRP" mode, the data redundancy is realized in this way: the communication is performed
in parallel, i.e., the same data package is transmitted on both channels simultaneously. The
received package identity from one channel is compared with data package identity from the other
channel. If they are the same, the last package will be discarded.
3) HSR
If this option is selected, Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt
"HSR" mode (IEC 62439-3 High-availability Seamless Redundancy) to realize data redundancy.
In the "HSR" mode, the principle of parallel operation to a single ring is applied to realize data
redundancy. For each message sent, the node sends two frames, one through each port. Both the
2 frames circulate in opposite directions over the ring. Every node forwards the frames it receives
from one port to another to reach the next node. When the originating sender node receives the
frame it sent, the sender node discards the frame to avoid loops.
4) RSTP
If this option is selected, Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt
"RSTP" mode (Rapid Spanning Tree Protocol).
In the "RSTP" mode, the data redundancy is realized in this way: RSTP serves for the
reorganization of the network structure in case of network path error. In other words, RSTP reroutes
the data to another path after the failure of a network path.
5) Bond
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module are used
as hot standby each other to ensure reliable communication of dual networks (i.e., network 1 and
network 2). When both network 1 and network 2 are normal, any of them is used to communicate
between the device and SAS. The device will automatically switch to the other healthy network
when one network is abnormal, which will not affect normal communication.
Ethernet port 1 is connected to network 1 while Ethernet port 2 is connected to network 2, and the
⚫ After the device is powered on, only Ethernet port 1 is activated when both network 1 and
network 2 are normal.
12. IP_SyslogServer**
It is used to set IP address of syslog server ** (**=01, 02, 03, 04), and the device can upload audit
log to syslog server. The setting is invalid unless cyber security is configured in the device. This
setting adopts dotted-decimal notation of IPv4.
Syslog is a communication protocol for message logging, it is used for security auditing in this
device.
13. t_Send_Heartbeat_Syslog
It is used to configure the period to send the heartbeat messages to the syslog server. If the interval
between two data messages is more than the setting, the heartbeat message will be sent with the
time delay of this setting.
If this device is not required to send heartbeat messages to the syslog server, please configure this
setting as "0".
If this device is required to send heartbeat messages to the syslog server, please configure this
setting according to actual requirements.
14. En_IP_Whitelist
A whitelist is a list of IP addresses that are granted access to a certain system or protocol. When a
whitelist is used, all IP addresses are denied access, except those included in the whitelist. Please
configure this setting according to actual requirements
15. IP**_Whitelist
It is used to set No. ** IP address of the whitelist. (**=01...16) This setting is effective only when the
setting [En_IP_Whitelist] is enabled.
This setting adopts dotted-decimal notation of IPv4. Please configure this setting according to
actual requirements.
16. En_ARP_Bind
The IP address is bound with the MAC address of this device when the setting is set as "Enabled".
⚫ LCD
⚫ PCS-Studio
IEDNAME
Disabled
En_Send_MMS_Qual_Chg
Enabled
IEC61850
Opt_DualNetMode_MMS
GB32890
Disabled
En_IEC62351_TCP_Port
Enabled
Disabled
En_IEC61850_TCP_Port
Enabled
1. IEDNAME
It cannot be an empty string and shall be unique within an SCL file. Its length should be less than
20 characters comprising letters or digits or underline ( _ ). The setting must start with an alpha
character and it is case sensitive.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
S s T t U u V v W w X x
Y y Z z _ 0 1 2 3 4 5 6
7 8 9 2
If this setting is modified, the IED name in the CID file of this device will be changed simultaneously
and vice versa.
As shown in the following figure, the length of the setting [IEDNAME] is also limited by the length
of "LDName":
Length of LDName
In IEC 61850 Ed1: the length of "LDName" is not more than 32 characters.
In IEC 61850 Ed2: the length of "LDName" is not more than 64 characters.
2. En_Send_MMS_Qual_Chg
When the setting is set as "Enabled", and the "quality-change" attribute of "TrgOps" is enabled,
once any IEC 61850 MMS quality changes, this device will send the new quality spontaneously to
the communication client.
3. Opt_DualNetMode_MMS
It is used to select the MMS network communication mode with SCADA via network A and B of the
device.
IEC61850: Network mode with IEC 61850 protocol. In this mode, the instances of Report Control
Block (RCB) cannot be shared, so different clients should use different report instances to send
reports. The "IEC61850" mode is preferred overseas.
2 GB32890: Network mode with GB32890 standard. In this mode, for different clients meeting the
redundancy conditions of A and B networks, if one client enables an RCB instance, the device will
only send a report to the enabled client. When the enabled client is interrupted, another redundant
client will cancel and re-enable the RCB instance, and the device will send a report to the re-
enabled redundant client. The "GB32890" mode is a special mode widely used in China, which
needs to be used with clients supporting.
4. Pcnt_Deadband
It is used to set the change detection threshold for suddenly sending measurement value to the
SCADA via the device's Ethernet port using IEC 61850.
Only when the measurement value change which is greater than this setting will be sent to the
communication client (e.g.: local SCADA system, etc.) via the device's Ethernet port by using IEC
61850. It is expressed as a percentage value.
If the measurement values sent to the communication client changed within a small range too
frequently, but the communication client needs to ignore these frequent changes, please set this
setting to a bigger value.
If the measurement values sent to the communication client are required to be more precise, please
set this setting to a smaller value.
5. Threshold_ZeroDrift
For any measurement value which is sent to the communication client (for example, local SCADA
system, etc.) via the device's Ethernet port by using IEC 61850, if it is smaller than this setting, it
will be processed as "0".
If the measurement values sent to the communication client are relatively big, please set this setting
to a big value, so as to eliminate influence of zero drift.
If the measurement values sent to the communication client are relatively small, please set this
setting to a small value, so as to avoid too many measurement values being processed as "0"
mistakenly.
6. En_IEC62351_TCP_Port 2
It is used to enable/disable TCP port when using IEC62351 protocol.
To realize the station level IEC 62351 cyber security communication, please enable this setting and
configure certificate, private key, etc. of this device and corresponding IEC 62351 client.
If station level IEC 62351 cyber security communication is not required, please configure this setting
as "Disabled" to close the listening port of IEC 62351 protocol.
7. En_IEC61850_TCP_Port
If station level IEC 61850 communication is not required, please configure this setting as
"Disabled" to close the MMS listening port of IEC 61850 protocol.
⚫ LCD
⚫ PCS-Studio
Current_Language
Opt_Caption_103 Fixed_Chinese
Fixed_English
Disabled
En_Broadcast_LAN1
Enabled
Disabled
En_Broadcast_LAN2
Enabled
Disabled
En_Broadcast_LAN3
2 Enabled
Disabled
En_Broadcast_LAN4
Enabled
DisturbData
Format_Wave_Sent
File
Period_Measmt_Net 0~65535 1 s
Disabled
En_103_TCP&UDP_Port
Enabled
1. Opt_Caption_103
It is used to select the language of group caption of IEC 60870-5-103 protocol and NR network 103
protocol.
The standard application of IEC 60870-5-103 protocol adopts a twisted pair EIA-485 connection
over a distance up to 500m. This device also supports the NR network 103 protocol that is an
alternative to IEC 60870-5-103 and is applicable through Ethernet network.
2. En_Broadcast_LAN*
This setting is only used for NR network 103 protocol. If NR network IEC103 protocol is used, the
setting must be set as "Enabled".
Disabled: the device does not send UDP (User Datagram Protocol) messages through Ethernet
port * (*=1, 2, 3, 4) of the CPU plug-in module.
Enabled: the device sends UDP messages through Ethernet port * (*=1, 2, 3, 4).
3. Format_Wave_Sent
It is used to set the data format for sending waveform list using NR network 103 protocol.
4. Pcnt_Deadband_Net
It is used to set the change detection threshold for suddenly sending measurement value to the
SCADA via the device's Ethernet port using IEC 60870-5-103
Only when the measurement value change which is greater than this setting will be sent to the
communication client (for example, local SCADA system, etc.) via the device's Ethernet port using
NR network 103 protocol. It is expressed as a percentage value.
If the measurement values sent to the communication client changed within a small range too
frequently, but the communication client needs to ignore these frequent changes, please set this
setting to a bigger value.
If the measurement values sent to the communication client are required to be more precise, please
set this setting to a smaller value.
If the measurement value change is not required to be sent to the communication client, please
configure this setting as "0".
5. Period_Measmt_Net
It is used to set the time period for sending the measurement value to the communication client (for
example, local SCADA system, etc.) via the device's Ethernet port by using NR network 103
protocol.
If this device is not required send all measurement values to the communication client
spontaneously based on the integrity period, please configure this setting as "0".
6. En_103_TCP&UDP_Port
It is used to enable/disable the TCP port and the UDP port when using NR network 103 protocol.
If NR network 103 communication is not required, please configure this setting as "Disabled" to
close the listening port of NR network 103 protocol.
When using NR network 103 protocol (network mode), al the settings in the
submenu MainMenu→Settings→Global Settings→Comm
Settings→IEC103 Settings need to be configued.
⚫ LCD
⚫ PCS-Studio
Disabled
En_TCP1_DNP
Enabled
Addr_Slave_TCP1_DNP 0~65519 1
Addr_Master_TCP1_DNP 0~65519 1
IP_Master_TCP1_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP1_DNP 0~4 1
t_AppLayer_TCP1_DNP 1~5 1 s
t_KeepAlive_TCP1_DNP 0~7200 1 s
Disabled
En_UR_TCP1_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP1_DNP
Enabled 2
Num_URRetry_TCP1_DNP 2~10 1
t_UROfflRetry_TCP1_DNP 1~5000 1 s
Class_BI_TCP1_DNP 0~3 1
Class_AI_TCP1_DNP 0~3 1
t_Select_TCP1_DNP 0~240 1 s
t_TimeSynIntvl_TCP1_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP1_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP1_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
1-AI32Int
2-AI16Int
Obj30DefltVar_TCP1_DNP 3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP1_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP1_DNP 2-AO16Int
3-AO32Flt
Disabled
En_TCP2_DNP
Enabled
Addr_Slave_TCP2_DNP 0~65519 1
Addr_Master_TCP2_DNP 0~65519 1
IP_Master_TCP2_DNP 0.0.0.0~255.255.255.255
2 Opt_Map_TCP2_DNP 0~4 1
t_AppLayer_TCP2_DNP 1~5 1 s
t_KeepAlive_TCP2_DNP 0~7200 1 s
Disabled
En_UR_TCP2_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP2_DNP
Enabled
Num_URRetry_TCP2_DNP 2~10 1
t_UROfflRetry_TCP2_DNP 1~5000 1 s
Class_BI_TCP2_DNP 0~3 1
Class_AI_TCP2_DNP 0~3 1
t_Select_TCP2_DNP 0~240 1 s
t_TimeSynIntvl_TCP2_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP2_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP2_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
1-AI32Int
2-AI16Int
Obj30DefltVar_TCP2_DNP 3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP2_DNP
2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP2_DNP 2-AO16Int
3-AO32Flt 2
Disabled
En_TCP3_DNP
Enabled
Addr_Slave_TCP3_DNP 0~65519 1
Addr_Master_TCP3_DNP 0~65519 1
IP_Master_TCP3_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP3_DNP 0~4 1
t_AppLayer_TCP3_DNP 1~5 1 s
t_KeepAlive_TCP3_DNP 0~7200 1 s
Disabled
En_UR_TCP3_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP3_DNP
Enabled
Num_URRetry_TCP3_DNP 2~10 1
t_UROfflRetry_TCP3_DNP 1~5000 1 s
Class_BI_TCP3_DNP 0~3 1
Class_AI_TCP3_DNP 0~3 1
t_Select_TCP3_DNP 0~240 1 s
t_TimeSynIntvl_TCP3_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP3_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP3_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
Obj30DefltVar_TCP3_DNP 1-AI32Int
2-AI16Int
3-AI32IntWoutF
4-AI16IntWoutF
2 5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP3_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP3_DNP 2-AO16Int
3-AO32Flt
Disabled
En_TCP4_DNP
Enabled
Addr_Slave_TCP4_DNP 0~65519 1
Addr_Master_TCP4_DNP 0~65519 1
IP_Master_TCP4_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP4_DNP 0~4 1
t_AppLayer_TCP4_DNP 1~5 1 s
t_KeepAlive_TCP4_DNP 0~7200 1 s
Disabled
En_UR_TCP4_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP4_DNP
Enabled
Num_URRetry_TCP4_DNP 2~10 1
t_UROfflRetry_TCP4_DNP 1~5000 1 s
Class_BI_TCP4_DNP 0~3 1
Class_AI_TCP4_DNP 0~3 1
t_Select_TCP4_DNP 0~240 1 s
t_TimeSynIntvl_TCP4_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP4_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP4_DNP 2-BIChWithAbsTime 2
3-BIChWithRelTime
1-AI32Int
2-AI16Int
Obj30DefltVar_TCP4_DNP 3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP4_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP4_DNP 2-AO16Int
3-AO32Flt
1. En_TCP*_DNP
It is used to enable/disable TCP port * when using DNP protocol (*=1, 2, 3, 4).
If network DNP communication is not required, please configure this setting as "Disabled" to close
the listening port of the network DNP protocol.
2. Addr_Slave_TCP*_DNP
It is used to set the device's DNP address for the network DNP session * (*=1, 2, 3, 4).
It should be consistent with corresponding setting value of the communication client (for example,
local SCADA system, master station in control center, etc.) for the network DNP session *.
3. Addr_Master_TCP*_DNP
It is used to set the DNP address of the master (i.e., the communication client) for the network DNP
session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
4. IP_Master_TCP*_DNP
It is used to set the IP address of the master (i.e., the communication client) for the network DNP
session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
5. Opt_Map_TCP*_DNP
It is used to configure the DNP communication point map for the network DNP session * (*=1, 2, 3,
4).
Five options are available, each of them corresponds to a communication point map pre-configured
by the PCS-Studio configuration tool.
6. t_AppLayer_TCP*_DNP
It is used to set the timeout duration of the application layer for the network DNP session * (*=1, 2,
3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
7. t_KeepAlive_TCP*_DNP
It is used to set the heartbeat time interval for the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
8. En_UR_TCP*_DNP
It is used to to enable/disable the UR (Unsolicited Response) message function for the network
DNP session * (*=1, 2, 3, 4).
For the network DNP session *, if the communication client requires this device to support sending 2
UR (Unsolicited Response) messages, please configure this setting as "Enabled".
9. En_MsgCtrlUR_TCP*_DNP
The setting is used to determine the mode of sending Class 1, 2, 3 events from the network DNP
session * to the communication client spontaneously (*=1, 2, 3, 4).
Enabled: the communication client must activate UR reporting by enabling unsolicited application
function (Function code: 20). After activation, the network DNP session * of this device begins to
send Class 1, 2, 3 events to the communication client spontaneously.
Disabled: this device will send Class 1, 2, 3 events spontaneously to the communication client for
the network DNP session *.
10. Num_URRetry_TCP*_DNP
It is used to set the online retransmission number for sending the UR messages to the
communication client for the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
11. t_UROfflRetry_TCP*_DNP
It is used to set the offline retransmission interval for sending the UR messages to the
communication client for the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
12. Class_BI_TCP*_DNP
It is used to select the default event class generated by the binary input points to the communication
client for the network DNP session * (*=1, 2, 3, 4).
0: If this option is selected, all the binary input points of this device will NOT generate any event to
2 the communication client for the network DNP session *.
1: If this option is selected, all the binary input points of this device will generate class 1 events to
the communication client for the network DNP session *.
2: If this option is selected, all the binary input points of this device will generate class 2 events to
the communication client for the network DNP session *.
3: If this option is selected, all the binary input points of this device will generate class 3 events to
the communication client for the network DNP session *.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
13. Class_AI_TCP*_DNP
It is used to select the default event class generated by the binary input points to the communication
client for the network DNP session * (*=1, 2, 3, 4).
0: If this option is selected, all the binary input points of this device will NOT generate any event to
the communication client for the network DNP session *.
1: If this option is selected, all the binary input points of this device will generate class 1 events to
the communication client for the network DNP session *.
2: If this option is selected, all the binary input points of this device will generate class 2 events to
the communication client for the network DNP session *.
3: If this option is selected, all the binary input points of this device will generate class 3 events to
the communication client for the network DNP session *.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
14. t_Select_TCP*_DNP
It is used to set the selection timeout duration of the remote control and the remote regulation for
the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
15. t_TimeSynIntvl_TCP*_DNP
It is used to set the time interval of the time synchronization function for the network DNP session 2
* (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
16. Obj01DefltVar_TCP*_DNP
It is used to select the default variation for object group 1 ("Obj01") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 1, variation 1" will be adopted to report the current value
of a binary input point. Variation 1 objects contain a single-bit binary input state without status flags.
If this option is selected, "Object group 1, variation 2" will be adopted to report the current value
of a binary input point. Variation 2 objects contain a status octet that includes the state of the binary
input.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
17. Obj02DefltVar_TCP*_DNP
It is used to select the default variation for object group 2 ("Obj02") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 2, variation 1" will be adopted to report events related to
a binary input point. Variation 1 objects contain an octet for reporting the state of the input and
status flags.
If this option is selected, "Object group 2, variation 2" will be adopted to report events related to
a binary input point. Variation 2 objects contain an octet for reporting the state of the input and
status flags, and the absolute time when the event occurred.
2 If this option is selected, "Object group 2, variation 3" will be adopted to report events related to
a binary input point. Variation 3 objects contain an octet for reporting the state of the input and
status flags, and the relative time when the event occurred. A preceding common time-of-
occurrence (CTO) object, group 51, establishes the basis of the relative time.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
18. Obj30DefltVar_TCP*_DNP
It is used to select the default variation for object group 30 ("Obj30") for the network DNP session
* (*=1, 2, 3, 4).
If this option is selected, "Object group 30, variation 1" will be adopted to report the current value
of an analog input point. Variation 1 objects contain a flag octet and a 32-bit, signed integer value.
If this option is selected, “"Object group 30, variation 2" will be adopted to report the current value
of an analog input point. Variation 2 objects contain a flag octet and a 16-bit, signed integer value.
If this option is selected, "Object group 30, variation 3" will be adopted to report the current value
of an analog input point. Variation 3 objects contain a 32-bit, signed integer value.
If this option is selected, "Object group 30, variation 4" will be adopted to report the current value
of an analog input point. Variation 4 objects contain a 16-bit, signed integer value.
If this option is selected, "Object group 30, variation 5" will be adopted to report the current value
of an analog input point. Variation 5 objects contain a flag octet and a 32-bit single-precision,
floating-point value.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
19. Obj32DefltVar_TCP*_DNP
It is used to select the default variation for object group 32 ("Obj32") for the network DNP session
* (*=1, 2, 3, 4).
If this option is selected, "Object group 32, variation 1" will be adopted to report events related to
an analog input point. Variation 1 objects contain a flag octet and a 32-bit, signed integer value.
If this option is selected, "Object group 32, variation 2" will be adopted to report events related to
an analog input point. Variation 2 objects contain a flag octet and a 16-bit, signed integer value.
If this option is selected, "Object group 32, variation 5" will be adopted to report events related to
an analog input point. Variation 5 objects contain a flag octet and a 32-bit single-precision, floating-
point value.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
20. Obj40DefltVar_TCP*_DNP
It is used to select the default variation for object group 40 ("Obj40") for the network DNP session
* (*=1, 2, 3, 4).
If this option is selected, "Object group 40, variation 1" will be adopted to report the status of an
analog output point. Variation 1 objects contain a flag octet and a 32-bit, signed integer value.
If this option is selected, "Object group 40, variation 2" will be adopted to report the status of an
analog output point. Variation 2 objects contain a flag octet and a 16-bit, signed integer value.
If this option is selected, "Object group 40, variation 3" will be adopted to report the status of an
analog output point. Variation 3 objects contain a flag octet and a 32-bit single-precision, floating-
point value.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
⚫ LCD
⚫ PCS-Studio
Disabled
En_Modbus_TCP_Port
Enabled
1. En_Modbus_TCP_Port
If network Modbus communication is not required, please configure this setting as "Disabled" to
close the listening port of network Modbus protocol.
⚫ LCD
⚫ PCS-Studio
SampleRate_SV 0~65535 1
t_Dly_Interp_Net_SV 1500~15000 1 μs
t_Dly_Interp_P2P_SV 600~1500 1 μs
NetMode
P2P
Opt_RecvMode_SV
Resv
2
None
4k_50Hz
Opt_MixedSmpl
4.8k_50Hz
4.8k_60Hz
Num_Point_Interp_MixedSmpl 3~7 1
t_Comp_Interp_MixedSmpl -100~100 1 μs
1. SampleRate_SV
It is used to set sampling rate of the received SV data from the merging units.
It must be the same as the sampling rate of the transmitted SV data of the merging units.
2. t_Dly_Interp_Net_SV
It is used to set the backward time delay of SV interpolation for networking mode. This backward
time delay is used to meet the data quantity & quality requirements by the SV interpolation.
Base on engineering experience, its value is recommended to be kept as the default value "2000μs".
Please consult our engineer if modification is required.
3. t_Dly_Interp_P2P_SV
It is used to set the backward time delay of SV interpolation for peer-to-peer (P2P) mode. This
backward time delay is used to meet the data quantity & quality requirements by the SV
interpolation.
Base on engineering experience, its value is recommended to be kept as the default value "850μs".
Please consult our engineer if modification is required.
4. Opt_RecvMode_SV
If there is communication equipment (e.g., Ethernet switch, etc.) in the SV communication link,
please select "NetMode".
If "NetMode" is selected, all the devices must share the same clock source.
Resv: reserved
2 5. Opt_MixedSmpl
It is used to set sampling rate in mixed sampling mode. This setting is available only in mixed
sampling mode.
4k_50Hz: 4kHz SV sampling rate in 50Hz power system (i.e.: 80 samples in fundamental power
system).
4.8k_50Hz: 4.8kHz SV sampling rate in 50Hz power system (i.e.: 96 samples in fundamental power
system).
4.8k_60Hz: 4.8kHz SV sampling rate in 60Hz power system (i.e.: 80 samples in fundamental power
system).
6. Num_Point_Interp_MixedSmpl
It is used to set backward interrupt point number for mixed sampling mode (24 samples per cycle).
This setting is available only in mixed sampling mode.
Please configure this setting according to actual requirements. Its recommended value is 0.3A base
on engineering experience.
7. t_Comp_Interp_MixedSmpl
It is used to set the backward compensation time for the mixed sampling mode, so as to realize the
synchronization via tiny adjustment between SV sampling data and conventional sampling data in
the mixed sampling mode. This setting is available only in mixed sampling mode.
Please configure this setting according to actual requirements. Its recommended value is 0μs base
on engineering experience.
⚫ PCS-Studio
It is used to set the waveform recorded duration before the trigger element operates.
⚫ If this setting is configured as a too big value, the waveform file size will be too large, and more
storage space and transmission bandwidth will be required.
⚫ If this setting is configured as a too small value, the waveform file may be insufficient for fault
analysis.
2. RecDur_PostFault
It is used to set the waveform recorded duration after the DFR trigger element drops off.
If there are 2 or more DFR trigger elements, this setting refers to the waveform recorded duration
after the last trigger element drops off.
⚫ If this setting is configured as a too big value, the waveform file size will be too large, and more
storage space and transmission bandwidth will be required.
⚫ If this setting is configured as a too small value, the waveform file may be insufficient for fault
analysis.
Its recommended value is 0.100s for "Level trigger" (Including high-level trigger, low-level trigger).
Its recommended value is 1.000s for "Edge trigger" (Including falling-edge trigger, rising-edge
Its recommended value is 1.000s for the combination of "Level trigger" and "Edge trigger".
3. MaxRecDur_PostTrigDFR
It is used to set the maximum waveform recorded duration after the trigger element operates.
2 If there are 2 or more DFR trigger elements, this setting refers to the maximum waveform recorded
duration after the 1st trigger element operates.
⚫ If this setting is configured as a too big value, the waveform file size will be too large, and more
storage space and transmission bandwidth will be required.
⚫ If this setting is configured as a too small value, the waveform file may be insufficient for fault
analysis.
⚫ LCD
⚫ PCS-Studio
1. Bxx.Name_**_GCommLink
It is used to set the user-defined part of GOOSE communication link** in the module located in slot
No.xx, and this user-defined part is designed to customize the GOOSE communication link name.
It will determine the corresponding part of the alarm signals, logic link settings, statistic data, etc.
The maximum permissible length of this setting is 30 characters, and this setting is case sensitive.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
S s T t U u V v W w X x 2
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
2. Bxx.Name_**_SVCommLink
It is used to set the user-defined part of SV communication link** in the module located in slot No.xx,
and this user-defined part is designed to customize the SV communication link name. It will
determine the corresponding part of the alarm signals, logic link settings, statistic data, etc.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
S s T t U u V v W w X x
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
⚫ LCD
⚫ PCS-Studio
Conventional
2 Opt_TimeSyn SAS 1
NoTimeSyn
OffsetHour_UTC -12~12
OffsetMinute_UTC 0~60
IP_Server_SNTP 0.0.0.0~255.255.255.255
IP_StandbyServer_SNTP 0.0.0.0~255.255.255.255
Enabled
En_ConvModeSNTP
Disabled
Enabled
DST.En
Disabled
DST.OffsetMinute 0~255 1
Jan
Feb
Mar
Apr
May
Jun
DST.MonthInYear_Start 1
Jul
Aug
Sep
Oct
Nov
Dec
1st
DST.WeekInMonth_Start 1
2nd
3rd
4th
Last
Sunday 2
Monday
Tuesday
DST.DayInWeek_Start Wednesday 1
Thursday
Friday
Saturday
DST.HourInDay_Start 0~23 1
Jan
Feb
Mar
Apr
May
Jun
DST.MonthInYear_End 1
Jul
Aug
Sep
Oct
Nov
Dec
1st
2nd
DST.WeekInMonth_End 3rd 1
4th
Last
Sunday
Monday
Tuesday
2 DST.DayInWeek_End Wednesday 1
Thursday
Friday
Saturday
DST.HourInDay_End 0~23 1
1. Opt_TimeSyn
⚫ Conventional
When the setting [Opt_TimeSyn] is set as "Conventional", the following clock synchronization
signals can be accepted by this device. However, if none of the following signals is received, an
alarm signal named “Alm_TimeSyn” will be issued, and the clock synchronization mode will
change to the "SAS" mode automatically.
IRIG-B: IRIG-B via serial port (RS-485 or TTL level) or BNC port (TTL level)
PPS: Pulse per second (PPS) via serial port (RS-485 or TTL level), BNC port (TTL level) or binary
input
IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
⚫ SAS
When the setting [Opt_TimeSyn] is set as "SAS", the following clock synchronization signals can
be accepted by this device. However, if none of the following signals is received, an alarm signal
named "Alm_TimeSyn" will be issued.
SNTP: Unicast (point-to-point) & broadcast SNTP mode via Ethernet network
Clock messages: IEC 60870-5-103 protocol, Modbus protocol and DNP3.0 protocol
⚫ NoTimeSyn
If the clock synchronization function is not required, please select "NoTimeSyn", and the device
will not send time synchronization alarm signal.
The clock message via IEC103 protocol is INVALID when the device
receives the IRIG-B signal through RS-485 port.
2. OffsetHour_UTC
3. OffsetMinute_UTC
The settings [OffsetHour_UTC] and [OffsetMinute_UTC] cooperate to determine the local time zone
of this device.
4. IP_Server_SNTP
It is used to set the IP address of the server when SNTP time synchronization mode is selected.
5. IP_StandbyServer_SNTP
It is used to set the IP address of the standby server when SNTP time synchronization mode is
selected.
When device failed to connect the SNTP server, it will try to connect the standby SNTP server.
It must be the same as corresponding setting value of the standby SNTP server.
6. En_ConvModeSNTP
It is used to enable/disable receive the SNTP message as the backup clock synchronization source
while hardware-based clock (IRIG-B, IEEE 1588 or PPS) is lost when the setting [OptTimeSyn] is
configured as "Conventional". However, the alarm "Alm_TimeSyn" will still be issued, so as to
indicate the failure of the conventional clock synchronization.
7. DST.En
8. DST.OffsetMinute
It is used to set the minute offset of DST, i.e. the difference between DST time and local time.
2 If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
9. DST.MonthInYear_Start
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
10. DST.WeekInMonth_Start
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
11. DST.DayInWeek_Start
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
12. DST.HourInDay_Start
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
13. DST.MonthInYear_End
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
14. DST.WeekInMonth_End
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
15. DST.DayInWeek_End
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
16. DST.HourInDay_End
2
It is used to set the hour in day when daylight time ends.
If the setting [DST.En] is configured as "Disabled", this setting will be unnecessary to be configured.
3 Protection Settings
Table of Contents
List of Tables
For the setting calculation in relation to power system operating conditions, it shall base on the
usual operating conditions as its calculation reference. Usual operating conditions usually refer to
normal operating conditions or the maintenance case that adjacent line or a component protected
is out of service. For the system whose operating mode changes greatly, the operating conditions
which setting calculation refers to should be confirmed by dispatching department according to
specific cases.
For all the calculation equations listed in this instruction manual, the results including current,
voltage and impedance are all expressed in the form of secondary actual value, unless it is 3
specifically mentioned. Setting values of the line protection shall be transformed into secondary
side value before inputting in the relay.
Formulas for converting primary settings to secondary ones are shown as below:
1
⚫ 𝐼SEC = 𝐼PRIM ×
CT ratio
Where:
I1n
CT ratio = ( I1n : Primary rated current; I2n : Secondary rated current).
I 2n
1
⚫ 𝑈SEC = 𝑈PRIM ×
VT ratio
Where:
U1n
VT ratio = ( U1n : Primary rated voltage; U2n : Secondary rated voltage)
U 2n
CT ratio
⚫ 𝑍SEC = 𝑍PRIM × VT ratio
Where:
All current settings, voltage settings and impedance settings are secondary
value converted from primary value by CT ratio and VT ratio.
⚫ LCD
⚫ PCS-Studio
Disabled
FD.NOC.En
Enabled
1. FD.DPFC.I_Set
It should be higher than maximum variation of load current and typically 0.2In. For line with heavy
load fluctuation like those for electric railway, rolling mill or aluminum-smelting, the setting should
be increased properly so that frequent pickup of the device could be avoided.
2. FD.ROC.3I0_Set
It should be greater than maximum three phases unbalance current. All protection functions
relevant to zero-sequence current will be controlled by this setting. Therefore, it is the most sensitive
among all zero-sequence overcurrent elements.
The settings of fault detector element at both ends should be set based on
the same primary value.
3
3. FD.NOC.I2_Set
It should be greater than maximum negative-sequence unbalance current. All protection functions
relevant to negative-sequence current will be controlled by this setting. Therefore, it is the most
sensitive among all negative-sequence overcurrent elements.
4. FD.NOC.En
⚫ LCD
⚫ PCS-Studio
FO.LocID 0~65535 1
FO.RmtID 0~65535 1
64
FO.BaudRate kbps
2048
FO.Protocol G.703
C37.94
FOx.Nx64k_C37.94 1-12 1
Ext
FOx.Opt_ClkSrc
Int
Disabled
FOx.En
Enabled
3 Disabled
FOx.En_Latch_Comp_AsymDly
Enabled
The setting principle is same with the setting [FO.RmtID] which is shown as bellow.
2. FO.RmtID
In order to ensure reliability of the device when digital communication channel is applied, settings
[FO.LocID] and [FO.RmtID] are provided as identity code to distinguish uniquely the device at
remote end using same channel.
Under normal conditions, the identity code of the device at local end should be different with that
at remote end. In addition, it is recommended that the identity code of all devices, i.e., the setting
[FO.LocID], should be unique in the substation. The setting range is from 0 to 65535.
The setting [FO.LocID] should be different between the local device and the remote device.
The local device's [FO.LocID] should be as same as the remote device's [FO.RmtID].
The end with greater [FO.LocID] is chosen as the master end for sampling synchronism, the other
end with smaller [FO.LocID] is slave end.
⚫ Loopback test
The setting [FO.LocID] is packaged in the message frame and transmitted to the remote end. When
the [FO.LocID] of the device at remote end received by local device is same to the setting
[FO.RmtID] of local device, the message received from the remote end is valid, and protection
information involved in message is read. When these settings are not matched, the message is
3. FO.BaudRate
For the dedicated optical fiber connection, both 64kbits/s and 2048kbits/s are suitable. But
2048kbits/s is recommended under this situation.
For the multiple connection with external communication equipment such as PCM or SDH, it should
be set as the requirement of communication equipment. 3
4. FO.Protocol
G.703 is the protocol which is used to define data frame transferred via physical/electrical
characteristic of hierarchical digital interfaces.
C37.94 is the protocol which used to define data frame transferred via optical fiber interfaces.
For the dedicated optical fiber connection, both G.703 and C37.94 are suitable. And C37.94 is
recommended under this situation.
For the multiple connection with external communication equipment such as PCM or SDH, And
G.703 is recommended under this situation. By the way, the MUX equipment should be used as
photoelectric conversion device.
For double channels, if one channel uses dedicated optical fiber and the other channel uses
multiple connection, G.703 is recommended under this situation.
5. FOx.Nx64k_C37.94
It is the times of 64kbits/s, which is an N×64kbits/s standard defined by IEEE C37.94 standard.
6. FOx.Opt_ClkSrc
It is used to select the communication clock used by sampling synchronization in current differential
protection, internal clock or external clock.
The device can communicate in two modes via multiplex channel or dedicated optical fibre.
The device transmits and receives messages based on respective clocks, which are called transmit
clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be extracted
from message frame, which can ensure no slip frame and no error message received. Clock TX
⚫ Use internal crystal clock, which is called internal clock (master clock)
Depend on the clock used by the device at both ends, there are three modes.
⚫ Mode 3: Master-slave mode (one of them uses internal clock, the other uses external clock)
3 If the device uses multiplex PCM/SDH channel, the setting [FOx.Opt_ClkSrc] at both ends should
be set accordingly.
⚫ The setting [FOx.Opt_ClkSrc] is recommended set as "Int" when the function, "Retiming", of
the communication equipment is disabled.
⚫ The setting [FOx.Opt_ClkSrc] is recommended set as "Ext" when the function, "Retiming", of
the communication equipment is enabled.
If the device uses dedicated optical fibre channel, mode 1 and mode 3 can be used. Mode 1 is
recommended in considering simplification to user, i.e. the setting [FOx.Opt_ClkSrc] at both ends
should be set as "Int".
7. FOx.En
8. FOx.En_Latch_Comp_AsymDly
It is used to enable/disable the asymmetric propagation delay compensation of channel x with the
frozen propagation delay time when the external clock is lost.
⚫ LCD
⚫ PCS-Studio
87L.XC1L (40~60000)/In 1 Ω
87L.XC0L (40~60000)/In 1 Ω
87L.Z_LocReac (40~60000)/In 1 Ω
87L.Z_LocGndReac (40~60000)/In 1 Ω
87L.Z_RmtReac (40~60000)/In 1 Ω
87L.Z_RmtGndReac (40~60000)/In 1 Ω
Disabled
87L.En
Enabled
Disabled
87L.En_DPFC1
Enabled
Disabled
87L.En_DPFC2
Enabled
Disabled
87L.En_Biased1
Enabled
Disabled
87L.En_Biased2
Enabled
Disabled
87L.En_Neutral
Enabled
87L.En_InterTrp Disabled
Enabled
Disabled
87L.En_LocDiff
Enabled
Disabled
87L.En_CapCurrComp
Enabled
Disabled
87L.En_CTS_Blk
Enabled
3
3.4.3 Calculation Principle
1. 87L.I_Pkp
It should be greater than the maximum unbalance current under the normal load conditions. If the
capacitive current is too big to be ignored, it should be considered. Considering the CT errors and
other measuring errors, additional safety margin should be also added. It also should consider the
sensitivity for the internal minmum fault. Normally, the corresponding primary current is
recommended to set as 400A~700A.
When the setting [87L.En_CapCurrComp] is set as "Disabled", the sensitivity will be decreased,
and the setting can be appropriately increased. The corresponding primary current is
recommended to set as 500A~800A.
𝐼𝑝𝑚𝑖𝑛
𝐾𝑠𝑒𝑛 =
𝐾𝑐𝑡 × 𝐼_𝑠𝑒𝑡
𝐼𝑝𝑚𝑖𝑛 is the minimum phase current of the faulty point for an internal fault
2. 87L.I_Alm
When the propagation delay of the channel is uncertain, so the currents at both ends cannot
accurately be synchronized. For large load current, larger differential current may be generated so
as to lead to undesired operation of current differential protection. Hence, differential current needs
to be supervised.
According to unbalanced differential current under load conditions, if differential current is greater
than the threshold value, the device will issue an alarm to indicate that differential current is
abnormal.
The threshold of discriminating differential current abnormality needs to cooperate with pickup
setting of current differential protection, at the same time it should be greater than unbalanced
current under normal conditions and also should be greater than the capacitive current.
3. 87L.I_Pkp_CTS
If the setting [87L.En_CTS_Blk] is set as "Enabled", current differential protection will be blocked
even the differential current exceed the setting [87L.I_Pkp_CTS]. Generally, this setting should be
greater than the maximal load current to prevent the possible maloperation under heavy load
condition. Normally it is set as 1.3 times of the maximum load current. It reduces the sensitivity, but
the reliability is increased.
4. 87L.K_Cr_CT
If CTs' ratio at two ends of the transmission line is different, the currents be converted to one
reference value. Regarding local end as the referenced end, differential current and restraint
current can be calculated since the current of the opposite end is converted by the setting.
[87L.K_Cr_CT]. If the CT ratio on both ends are same, this setting should be set as "1" on both
ends, and its recommended value is 1.
IM1n and IM2n are primary rated current and secondary rated current of terminal M respectively
IN1n and IN2n are primary rated current and secondary rated current of terminal N respectively
The secondary rated current is considered internally, so only primary rated current should be
calculated.
Suppose CT ratio is as below, and then, IM1n is not less than IN1n
Terminal M Terminal N
𝐼𝑀1𝑛 𝐼𝑁1𝑛
𝐾M = 𝐾𝑁 =
𝐼𝑀2𝑛 𝐼𝑁2𝑛
𝐼𝑁1𝑛
[87L.K_Cr_CT]=1.00 [87𝐿. 𝐾_𝐶𝑟_𝐶𝑇] =
𝐼𝑀1𝑛
For example:
Terminal M Terminal N
K M = 2500: 1 𝐾𝑁 = 1250: 5
[87L.K_Cr_CT]=1.00 [87L.K_Cr_CT]=0.50
5. 87L.I_Knee1
It is used to set current setting of knee point 1 for steady-state current differential element.
It should be greater than the restrained current corresponding to point A as shown in figure below.
The sensitivity and reliability should be considered, and the undesired operation for external fault
3 with CT saturation should be avoided.
The other values can be chosen in order to increase or decrease the sensitivity if there is other
calculation principle. If the result of the calculated setting exceeds the upper limit, then the setting
should be set as the upper limit.
If the calculated value is out of the setting range, please set it as the upper
limit or the lower limit.
IDiffΦ
k=1
k2
k1
IH
IBiasΦ
A Knee1 Knee2
Where:
Knee1 and Knee2 are the restraint current setting [87L.I_Knee1] and [87L.I_Knee2] respectively.
6. 87L.I_Knee2
It is used to set current setting of knee point 2 for steady-state current differential element.
It should be greater than the setting [87L.I_Knee1]. It is indicated in the figure as above. The
sensitivity and reliability should be considered, and the undesired operation for external fault with
CT saturation should be prevented.
If more reliability is required, the setting could be decreased, for example, 1A (the secondary rated
current is 1A). If more sensitivity is required, the setting could be increased accordingly. Because
the DPFC differential element can meet the sensitivity requirement, it is not recommended to
increase the setting too large. The setting is recommended not to exceed 2A (the secondary rated
current is 1A), and if the calculated value exceeds 2A, then the setting should be set as 2A.
If the calculated value is out of the setting range, please set it as the upper
limit or the lower limit.
7. 87L.Slope1 3
It is used to set the slope 1 of steady-state current differential element. It is indicated in the figure
as above.
The sensitivity and reliability should be considered, and the unwanted operation for external fault
with CT error should be prevented.
If more reliability is required, the setting could be increased, for example, 0.6. Normally it should
be less than the setting [87L.Slope2]. Because the DPFC differential element can meet the
sensitivity requirement, it can not be less than 0.5.
The other values can be chosen in order to increase or decrease the sensitivity if there is other
calculation principle. If the result of the calculated setting exceeds the lower limit, then the setting
should be set as the lower limit.
If the calculated value is out of the setting range, please set it as the upper
limit or the lower limit.
8. 87L.Slope2
It is used to set the slope 2 of steady-state current differential element. It is indicated in the figure
as above.
The sensitivity and reliability should be considered, and the unwanted operation for external fault
with CT saturation should be prevented.
If more reliability is required, the setting could be increased, for example, 0.8. If more sensitivity is
required, the setting could be increased, for example, 0.6. Normally, it should be greater than the
setting [87L.Slope1].
The other values can be chosen in order to increase or decrease the sensitivity if there is other
calculation principle. If the result of the calculated setting exceeds the lower limit, then the setting
If the calculated value is out of the setting range, please set it as the upper
limit or the lower limit.
9. 87L.t_Op_Neutral
It is used to set the time delay for neutral current differential element.
The setting principle is same with the [87L.XC0L] which is shown as bellow.
11. 87L.XC0L
If the setting [87L.En_CapCurrComp] is set as "Enabled", they should be set based on actual
parameters of the whole line (secondary value). If actual parameters are not available, the following
data can be used as a reference. The capacitive impedance and capacitive current of overhead
line per 100km based on different voltage class:
If the setting [87L.En_CapCurrComp] is set as "Disabled", the setting will not be used in caculation.
They can be set as any value within their setting range.
If the transmission line is very short, then the capacitive current is very small, then there is no need
to compensate capacitve current. Its recommended value is 10000Ω (secondary value).
Its recommended value is 10000Ω. Normally, zero-sequence capacitive impedance must be equal
to or greater than positive-sequence capacitive impedance.
12. 87L.Z_LocReac
If shunt reactor is equipped with the local substation, it shall be set as the secondary value of shunt
reactor of local substation, otherwise, it can be set as "60000Ω" (the upper limit). When the logic
setting [87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation
and can be set as any value within its setting range.
If the setting [87L.En_CapCurrComp] is set as "Enabled", and there is only one shunt reactor on
one end, then the setting on the other end which is not equipped with the reactor should be set as
the upper limit.
13. 87L.Z_LocGndReac
It is used to set the impedance setting of ground reactor of the local end.
If ground reactor is equipped with the local substation, it shall be set as the secondary value of
ground reactor of local substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and can
be set as any value within its setting range.
3
If the setting [87L.En_CapCurrComp] is set as "Enabled", and there is only one shunt reactor on
one end, then the setting on the other end which is not equipped with the reactor should be set as
the upper limit.
14. 87L.Z_RmtReac
If shunt reactor is equipped with the remote substation, it shall be set as the secondary value of
shunt reactor of remote substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and
can be set as any value within its setting range.
If the setting [87L.En_CapCurrComp] is set as "Enabled", and there is only one shunt reactor on
one end, then the setting on the other end which is not equipped with the reactor should be set as
the upper limit.
15. 87L.Z_RmtGndReac
If ground reactor is equipped with the remote substation, it shall be set as the secondary value of
ground reactor of remote substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and
can be set as any value within its setting range.
If the setting [87L.En_CapCurrComp] is set as "Enabled", and there is only one shunt reactor on
one end, then the setting on the other end which is not equipped with the reactor should be set as
the upper limit.
16. 87L.En
17. 87L.En_DPFC1
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
3 18. 87L.En_DPFC2
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
19. 87L.En_Biased1
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
20. 87L.En_Biased2
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
21. 87L.En_Neutral
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
22. 87L.En_InterTrp
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
When a fault associated with high resistance occurs in the outlet of long transmission line, the
device of local end, which is near the fault, can pick up immediately, but, considering the influence
of a considerable power source, the device of the remote end, which is far from the fault, cannot
pick up due to inapparent fault component. In order to avoid this case, any protection (such as
distance protection, overcurrent protection and etc.) of local end operates, inter-trip signal of
corresponding phase will be sent to the remote end. After receiving the inter-trip signal, the device
of the remote end can pick up, if corresponding basic differential condition is met and the setting
[87L.En_InterTrp] is set as "Enabled", the faulty phase will be inter-tripped. This setting is generally
set as "Enabled".
23. 87L.En_LocDiff
If the setting [87L.En_LocDiff] is set as "Enabled", then independent current differential protection
is enabled which means local current differential protection can operate without permissive signal
from remote end.
When CT circuit failure occurs at one end, FD and current differential protection on the end may
operate. However, FD on the other end will not operate and not send any permissive signal of
current differential protection. Therefore, the current differential protection will not maloperate.
3
If the operation is not allowed for differential protection during CT circuit failure under normal
condition, then [87L.En_LocDiff] should be set as "Disabled".
24. 87L.En_CapCurrComp
If the capacitive current should be compensated to increase the sensitivity, it should be set as
"Enabled".
25. 87L.En_CTS_Blk
If CT circuit failure associated with internal fault or pickup due to system disturbance is detected,
the device will show two kinds of behavior.
If logic setting [87L.En_CTS_Blk] (differential protection being blocked during CT circuit failure) is
set as "Enabled", the current differential protection will be blocked.
If logic setting [87L.En_CTS_Blk] is set as "Disabled" and the current differential current of the
faulty phase is more than the differential current setting [87L.I_Pkp_CTS] during CT circuit failure,
the current differential protection will operate.
⚫ LCD
⚫ PCS-Studio
Master Mode
Disabled
87L.En
Enabled
Disabled
87L.En_DPFC1
Enabled
Disabled
87L.En_DPFC2
Enabled
Disabled
87L.En_Biased1
Enabled
Disabled
87L.En_Biased2
Enabled
Disabled
87L.En_Neutral
Enabled
Disabled
87L.InterTrp
Enabled
Disabled
87L.En_LocDiff
Enabled
Disabled
87L.En_CTS_Blk
Enabled
Disabled
87L.En_Chx
Enabled
Slave Mode
Disabled
87L.En
Enabled
Disabled
87L.En_Chx
Enabled
Master Mode
1. 87L.I_Pkp
It should be greater than the maximum unbalance current under the normal load conditions. If the 3
capacitive current is too big to be ignored, it should be considered. Considering the CT errors and
other measuring errors, additional safety margin should be also added. Normally, the corresponding
primary current is recommended to set as 400A~700A.
2. 87L.I_Alm
When the propagation delay of the channel is uncertain, so the currents at both ends cannot
accurately be synchronized. For large load current, larger differential current may be generated to
lead to undesired operation of current differential protection. Hence, differential current needs to be
supervised.
According to unbalanced differential current under load conditions, if differential current is greater
than the threshold value, the device will issue an alarm to indicate that differential current is
abnormal.
The threshold of discriminating differential current abnormality needs to cooperate with pickup
setting of current differential protection, at the same time it should be greater than unbalanced
current under normal conditions.
3. 87L.I_Pkp_CTS
When CT circuit fails, this pickup setting of current differential protection will be switched into
[87L.I_Pkp_CTS] if the setting [87L.En_CTS_Blk] is set as "Disabled".
If the setting [87L.En_CTS_Blk] is set as "Enabled", current differential protection will be blocked
even the differential current exceed the setting [87L.I_Pkp_CTS]. Generally, this setting should be
greater than the maximal load current to prevent the possible maloperation under heavy load
condition. It reduces the sensitivity, but the reliability is increased.
4. 87L.K_Cr_CT
If all CT ratio of the multi-terminal transmission line are not same, the currents be converted to one
reference value. Regarding local end as the referenced end, differential current and restraint
current can be calculated since the current of the other end is converted by the setting.
[87L.K_Cr_CT]. If all CT ratio are same, this setting should be set as "1" on all ends, and its
recommended value is 1.
3 IM1n and IM2n are primary rated current and secondary rated current of terminal M respectively
IN1n and IN2n are primary rated current and secondary rated current of terminal N respectively
IQ1q and IQ2q are primary rated current and secondary rated current of terminal Q respectively
The secondary rated current is considered internally, so only primary rated current should be
calculated.
Suppose CT ratio is as below, and IM1n is the max primary value among them, then the CT ratio
factor [87L.K_Cr_CT] can be calculated according to the equition in the table.
𝐼𝑁1𝑛 𝐼𝑄1𝑞
[87L.K_Cr_CT]=1.00 [87𝐿. 𝐾_𝐶𝑟_𝐶𝑇] = [87𝐿. 𝐾_𝐶𝑟_𝐶𝑇] =
𝐼𝑀1𝑛 𝐼𝑀1𝑛
For example:
5. 87L.t_Op_Neutral
It is used to set the time delay for neutral current differential element.
6. 87L.En
7. 87L.En_DPFC1
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
8. 87L.En_DPFC2
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
9. 87L.En_Biased1
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
3
"Enabled".
10. 87L.En_Biased2
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
11. 87L.En_Neutral
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
12. 87L.InterTrp
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
When a fault associated with high resistance occurs in the outlet of long transmission line, the
device of local end, which is near the fault, can pick up immediately, but, considering the influence
of a considerable power source, the device of the remote end, which is far from the fault, cannot
pick up due to inapparent fault component. In order to avoid this case, any protection (such as
distance protection, overcurrent protection etc.) of local end operates, inter-trip signal of
corresponding phase will be sent to the remote end. After receiving the inter-trip signal, the device
of the remote end can pick up, if corresponding basic differential condition is met and the setting
[87L.En_InterTrp] is set as "Enabled", the faulty phase will be inter-tripped. This setting is generally
set as "Enabled".
13. 87L.En_LocDiff
If the setting [87L.En_LocDiff] is set as "Enabled", then independent current differential protection
is enabled which means local current differential protection can operate without permissive signal
from remote end.
When CT circuit failure occurs at one end, FD and current differential protection on the end may
operate. However, FD on the other end will not operate and not send any permissive signal of
current differential protection. Therefore, the current differential protection will not maloperate.
If the operation is not allowed for current differential protection during CT circuit failure under normal
condition, then [87L.En_LocDiff] should be set as "Disabled".
14. 87L.En_CTS_Blk
3 It is used to enable/disable current differential protection blocked during CT circuit failure.
If CT circuit failure associated with internal fault or pickup due to system disturbance is detected,
the device will show two kinds of behavior.
If logic setting [87L.En_CTS_Blk] (differential protection being blocked during CT circuit failure) is
set as "Enabled", the current differential protection will be blocked.
If logic setting [87L.En_CTS_Blk] is set as "Disabled" and the current differential current of the
faulty phase is more than the differential current setting [87L.I_Pkp_CTS] during CT circuit failure,
the current differential protection will operate.
15. 87L.En_Chx
For multi-terminal transmissl line, the master end calculates the differential current, so the
corresponding setting [87L.En_Chx] should be set as "Enabled".
For some situations, the corresponding setting [87L.En_Chx] should be set as "Disabled" if that
end is out of service.
Slave Mode
1. 87L.K_Cr_CT
2. 87L.En
3. 87L.En_Ch1
For multi-terminal transmissl line, the slave end receives the tripping command through channel 1,
hence its recommended value is "Enabled" under normal condition.
For some situations, the corresponding setting [87L.En_Ch1] should be set as "Disabled" if that
end is out of service.
⚫ LCD
⚫ PCS-Studio 3
Project NodeDevice NodeSettingGroup*Protection SettingsPilot Scheme Settings
POTT
85.Opt_Mode PUTT
Blocking
Disabled
85.En_Ch_PhSeg
Enabled
Disabled
85.En_WI
Enabled
Disabled
85.En_WI_Pkp
Enabled
Disabled
85.En_Trp_Send
Enabled
Disabled
85.En_PilotTrp_Send
Enabled
Disabled
85.En_52b_Send
Enabled
85.En_52b_Echo Disabled
Enabled
Disabled
85.Z.En
Enabled
Disabled
85.En_Unblocking1
Enabled
Phase-to-phase
3 85.Opt_Ch1
Phase-to-ground
Disabled
85.ZX.En
Enabled
1. 85.Opt_Mode
2. 85.En_Ch_PhSeg
Generally, for parallel lines or multi-circuits, this setting is recommended to be set as "Enabled".
The permissive scheme can use PLC channel or optic fiber channel as communication channel.
These signals, which are used to initiate sending permissive signal, can use phase-segregated
signal scheme or common signal scheme. For pilot protection adopting common signal scheme,
the signal "85-x.Recv1" is used. For pilot protection adopting phase-segregated signal scheme,
three signals are used, they are "85-x.Recv1" for phase A, "85-x.RecvB" for phase B and "85-
x.RecvC" for phase C.
3. 85.En_WI
If the device locates on weak end, it should be enabled. Otherwise, it should be disabled.
4. 85.U_UV_WI
This setting is set to be lower than the minimum voltage value under normal operation condition.
Usually, it is recommeded be set as 60% rated phase voltage.
In case of an internal fault on the line, the fault current supplied to the fault point from the weak
power source is very small or even nil, both forward and reverse element do not operate. Thus, the
3
pilot distance protection could not operate at both ends of the line. The weak infeed logic is used
for this condition.
When the weak infeed logic is enabled ([85.En_WI] is set as "Enabled"), ,if the voltage is lower
than the setting [85.U_UV_WI] after the device picks up, upon receiving the signal from the remote
end, the weak infeed end will echo the signal back for 200ms. In this way, the pilot distance
protection on the other end can operate.
5. 85.En_WI_Pkp
This setting is recommended to be set as "Enabled" for the weak infeed end when the device can
not pick up for internal faults in some extreme situations.
6. 85.En_Trp_Send
It is used to enable/disable sending permissive signals by any tripping. If only the pilot protection
(pilot distance protection and pilot directional earth-fault protection) is required to trigger sending
permissive signal, this setting can be set as "Disabled".
7. 85.En_PilotTrp_Send
It is used to enable/disable sending permissive signals when the pilot protection (pilot distance
protection and pilot directional earth-fault protection) operates.
This logic is a supplement for the pilot protection. When the pilot protection operates, the permissive
signal will be extended to make sure the device on the other end can reliably receive the permissive
signal and operate.
8. 85.En_52b_Send
It is used to enable/disable sending permissive signals by the circuit breaker open position when
the device picks up.
9. 85.En_52b_Echo
It is used to enable/disable echo permissive signals by the circuit breaker open position when the
device does not pick up.
10. 85.Z.En
11. 85.En_Unblocking1
3 This setting is recommended to be set as "Enabled" when unblocking scheme is required due to
pilot channel failure.
When pilot channel fails, the device may not receive signal from the remote end. For this case, pilot
distance protection can adopt unblocking scheme. While pilot channel is blocked, the signaling
equipment will provide a contact to the device as unblocking signal. When the device receives
unblocking signal from the signaling equipment, it will recognize channel failure, and unblocking
signal will be taken as permissive signal temporarily.
12. 85.Opt_Ch1
It is recommended that the blocking logic adopts phase-to-ground channel, and the permissive
logic adopts phase-to-phase channel.
There is no similar setting for pilot channel 2, because pilot directional earth-
faut protection adopts phase-to-ground mode, and does not check fault
types in unblocking scheme.
13. 85.t_Unblocking1
It is used to set the releasing time of unblocking scheme for pilot channel 1 when the setting
[85.En_Unblocking1] is set as "Enabled".
14. 85.t_DPU_Blocking1
It is used to set time delay for blocking scheme of pilot distance protection operation.
If the setting [85.Opt_PilotMode] is set as "Blocking", blocking scheme will operate with a time delay
[85.t_DPU_Blocking1] if both forward element operates and blocking signal is not received. This
time delay should be longer than the summation of the propagation time delay of pilot channel and
pickup time of fault detector element. In addition, the time dalay should prevent from maloperation
under current reversal condtion. The recommended setting principle is as follows.
[85.t_DPU_Blocking1]=t1+t2+Δt
Where:
Δt is the margin time, in order to prevent pilot distance protection from undesired operating under
current reversal condtion, it normally should be more than 50ms
15. 85.t_DPU_CR1
[85.t_DPU_CR1]=T1-T2-T3
Where:
T1 indicates that the transfer time during which the direction judgement of the device that is near
the fault in local line changes from reverse direction to forward direction when a fault happens to
the adjacent line. It is necessary to consider the operating time of the device that is near the fault
in the adjacent line, the operating time of the contact, the operating time of the circuit breaker and
the operating time of the forward direction element.
T2 indicates the channel delay, which shall be set according to the actual channel delay.
T3 indicates the time during which the remote device sends the signal, which shall be set according
to the actual sending time of the remote device.
Based on the above setting principles, if the fastest operating time of the device in the adjacent line
is calculated as 10ms, the fastest operating time of the contact is calculated as 5ms, the fastest
operating time of the circuit breaker is calculated as 25ms, and the fastest operating time of the
forward direction element is calculated as 15ms, then:
T1=10ms+5ms+25ms+15ms=55ms
[85.t_DPU_CR1]=55ms-15ms-20ms=20ms
The setting should be not less than 10ms, which ensure that the current reversal logic does not
incorrectly detect for internal fault.
16. 85.t_DDO_CR1
[85.t_DDO_CR1]=T1+T2
Where:
T1 indicates the transfer time difference between local device whose direction judgement changes
from reverse direction to forward direction and remote device whose direction judgement changes
from forward direction to reverse direction, and a certain time margin shall be considered.
T2 indicates the dropoff time of the channel delay, which shall be set according to the actual
situation of the channel.
Based on the above setting principles, if the transfer time difference between local device and
3 remote device is calculated as 10ms, the dropoff time of the channel delay is calculated as 15ms,
then:
[85.t_DDO_CR1]=10ms+15ms=25ms
If the dropoff of the forward direction element of the remote device is slow, T2 needs to increase
the margin appropriately according to the actual situation.
17. 85.ZX.En
Zone extension is usually used in combination with automatic reclosure. It can be activated
internally by pilot protection, the integrated automatic reclosure or externally by a binary input.
When pilot protection is out of service due to pilot channel failure or no pilot protection is provided,
as a supplement of pilot protection, zone extension can clear the fault within the whole line
instantaneously. Different from pilot distance protection, zone extension can also operate for
external close up fault in parallel line, but power supply can be restored by AR. So zone extension
should be blocked when AR is out of service and is not ready.
18. 85.t_DPU_ZX
It is used to set pickup time delay for zone extension of pilot distance protection
The delay time is set in accordance with the application type, usually to zero or a very small delay.
⚫ LCD
⚫ PCS-Studio
Disabled
85.DEF.En
Enabled
Disabled
85.DEF.En_BlkAR
Enabled
Disabled
3
85.DEF.En_IndepCh
Enabled
Disabled
85.En_Unblocking2
Enabled
1. 85.DEF.En
2. 85.DEF.En_BlkAR
3. 85.DEF.En_IndepCh
Disabled: pilot directional earth-fault protection sharing same channel with pilot distance protection
Pilot directional earth-fault protection can share the channel with pilot distance protection or use
independent channel to initiate sending signal.
When the setting [85.DEF.En_IndepCh] is set as "Disabled", pilot directional earth-fault protection
which comprises permissive scheme and blocking scheme can share pilot channel 1 with pilot
distance protection.
When the setting [85.DEF.En_IndepCh] is set as "Enabled", pilot directional earth-fault protection
which comprises permissive scheme and blocking scheme uses independent pilot channel 2.
For underreach mode (PUTT), pilot directional earth-fault should adopt independent pilot channel
2 and work as overreach mode. That means [85.DEF.En_IndepCh] should set as "Enabled".
4. 85.En_Unblocking2
3 It is used to enable/disable unblocking scheme for pilot DEF via pilot channel 2. This setting is
recommended to be set as "Enabled" when unblocking scheme is required due to pilot channel
failure.
If pilot directional earth-fault protection uses independent channel 2 to initiate sending and receiving
signal, the signal will not be received from remote end when pilot channel fails. For this case, pilot
protection can adopt unblocking scheme. While pilot channel is blocked, the signaling equipment
will provide a contact to the device as unblocking signal. When the device receives unblocking
signal from the signaling equipment, it will recognize channel failure, and unblocking signal will be
taken as permissive signal temporarily.
5. 85.t_Unblocking2
It is used to set pickup releasing time delay of unblocking scheme for pilot channel 2.
It is used to set the releasing time of unblocking scheme for pilot channel 2 when the setting
[85.En_Unblocking2] is set as "Enabled".
6. 85.DEF.3I0_Set
It should ensure that pilot directional earth-fault protection is sensitive enough when an earth fault
happens in the remote end of the line.
7. 85.DEF.t_DPU
8. 85.t_DPU_CR2
It is used to set time delay pickup for current reversal logic when pilot directional earth-fault
protection adopts independent pilot channel 2.
Generally, there is a time delay in pilot directional earth-fault protection. Hence, the setting can be
decreased appropriately if the time delay can meet the requirement of corret operation during
current reversal. Otherwise, the setting shall be set refer to the setting [85.t_DPU_CR1].
9. 85.t_DDO_CR2
It is used to set time delay dropoff for current reversal logic when pilot directional earth-fault
Generally, there is a time delay in pilot directional earth-fault protection. Hence, the setting can be
decreased appropriately if the time delay can meet the requirement of corret operation during
current reversal. Otherwise, the setting shall be set refer to the setting [85.t_DDO_CR1].
In the case of parallel lines, pilot distance protection shall have the capability
to protect the whole line when an earth fault happens.
⚫ LCD
⚫ PCS-Studio
Disabled
21D.En
Enabled
1. 21D.Z_Set
It is an additional function of distance zone1 protection to accelerate its operation for the close-up
fault. It is set according to underreaching scheme, usually take 60%~70% of the line impedance,
and as for double-circuit lines, 50% of the line impedance is recommended.
2. 21D.Z_Overreach
It is used to set impedance setting of DPFC distance protection with overreaching characteristic.
The setting can ensure the directionality of DPFC distance protection for series compensated lines,
and it should be set as the impedance from local side to the power supply of opposite end. It can
be set as the local line impedance plus 1.5 times of power supply impedance of opposite end under
maximum operation mode.
3 3. 21D.En
It is a logic setting, which is used to enable or disable DPFC distance protection. If the line length
is too short (for example, less than 10km) or the SIR (Source Impedance Ratio) is too large
(SIR>30).
⚫ LCD
⚫ PCS-Studio
21L.Ang_Alpha 5~30 1 °
21L.Ang_Beta 5~30 1 °
21L.LoadEnch.ZG.phi 5~50 1 °
21L.LoadEnch.ZP.phi 5~50 1 °
Mho
21L.ZG.Opt_Characteristic
Quad
Mho
21L.ZP.Opt_Characteristic
Quad
21L1.phi1_Reach 30~89 1 °
3
21L1.ZG.RCA 0~45 1 °
21L1.ZG.phi_Shift 0~30 1 °
Disabled
21L1.ZG.En
Enabled
Disabled
21L1.ZG.En_BlkAR
Enabled
Disabled
21L1.ZG.En_3I0
Enabled
Disabled
21L1.ZG.En_NeuDir_Blk
Enabled
Disabled
21L1.ZG.En_NegDir_Blk
Enabled
Disabled
21L1.LoadEnch.ZG.En
Enabled
21L1.ZP.RCA 0~45 1 °
21L1.ZP.phi_Shift 0~30 1 °
Disabled
21L1.ZP.En
Enabled
Disabled
3 21L1.ZP.En_BlkAR
Enabled
Disabled
21L1.ZP.En_NegDir_Blk
Enabled
Disabled
21L1.LoadEnch.ZP.En
Enabled
Disabled
21L1.LoadEnch.En
Enabled
Disabled
21L1.En_PSBR
Enabled
Disabled
21L1.En_ReacLine
Enabled
Forward
21L2.DirMode Reverse
Non_Directional
21L2.phi1_Reach 30~89 1 °
21L2.ZG.RCA 0~45 1 °
21L2.ZG.phi_Shift 0~30 1 °
Disabled
21L2.ZG.En
Enabled
Disabled
21L2.ZG.En_BlkAR
Enabled
3
Disabled
21L2.ZG.En_3I0
Enabled
Disabled
21L2.ZG.En_NeuDir_Blk
Enabled
Disabled
21L2.ZG.En_NegDir_Blk
Enabled
Disabled
21L2.LoadEnch.ZG.En
Enabled
21L2.ZP.RCA 0~45 1 °
21L2.ZP.phi_Shift 0~30 1 °
Disabled
21L2.ZP.En
Enabled
Disabled
21L2.ZP.En_BlkAR
Enabled
21L2.ZP.En_NegDir_Blk Disabled
Enabled
Disabled
21L2.LoadEnch.ZP.En
Enabled
Disabled
21L2.En_ShortDly
Enabled
Disabled
3 21L2.LoadEnch.En
Enabled
Disabled
21L2.En_PSBR
Enabled
Disabled
21L2.En_ReacLine
Enabled
Forward
21L3.DirMode Reverse
Non_Directional
21L3.phi1_Reach 30~89 1 °
21L3.ZG.RCA 0~45 1 °
21L3.ZG.phi_Shift 0~30 1 °
Disabled
21L3.ZG.En
Enabled
21L3.ZG.En_BlkAR Disabled
Enabled
Disabled
21L3.ZG.En_3I0
Enabled
Disabled
21L3.ZG.En_NeuDir_Blk
Enabled
Disabled
21L3.ZG.En_NegDir_Blk
Enabled
3
Disabled
21L3.LoadEnch.ZG.En
Enabled
21L3.ZP.RCA 0~45 1 °
21L3.ZP.phi_Shift 0~30 1 °
Disabled
21L3.ZP.En
Enabled
Disabled
21L3.ZP.En_BlkAR
Enabled
Disabled
21L3.ZP.En_NegDir_Blk
Enabled
Disabled
21L3.LoadEnch.ZP.En
Enabled
Disabled
21L3.En_ShortDly
Enabled
21L3.LoadEnch.En Disabled
Enabled
Disabled
21L3.En_PSBR
Enabled
Disabled
21L3.En_ReacLine
Enabled
Forward
3 21L4.DirMode Reverse
Non_Directional
21L4.phi1_Reach 30~89 1 °
21L4.ZG.RCA 0~45 1 °
21L4.ZG.phi_Shift 0~30 1 °
Disabled
21L4.ZG.En
Enabled
Disabled
21L4.ZG.En_BlkAR
Enabled
Disabled
21L4.ZG.En_3I0
Enabled
Disabled
21L4.ZG.En_NeuDir_Blk
Enabled
21L4.ZG.En_NegDir_Blk Disabled
Enabled
Disabled
21L4.LoadEnch.ZG.En
Enabled
21L4.ZP.RCA 0~45 1 °
21L4.ZP.phi_Shift 0~30 1 °
Disabled
21L4.ZP.En
Enabled
Disabled
21L4.ZP.En_BlkAR
Enabled
Disabled
21L4.ZP.En_NegDir_Blk
Enabled
Disabled
21L4.LoadEnch.ZP.En
Enabled
Disabled
21L4.En_ShortDly
Enabled
Disabled
21L4.LoadEnch.En
Enabled
Disabled
21L4.En_PSBR
Enabled
Disabled
21L4.En_ReacLine
Enabled
21L5.DirMode Forward
Reverse
Non_Directional
21L5.phi1_Reach 30~89 1 °
21L5.ZG.RCA 0~45 1 °
3 21L5.ZG.Z_Set (0.000~4Unn)/In 0.001 Ω
21L5.ZG.phi_Shift 0~30 1 °
Disabled
21L5.ZG.En
Enabled
Disabled
21L5.ZG.En_BlkAR
Enabled
Disabled
21L5.ZG.En_3I0
Enabled
Disabled
21L5.ZG.En_NeuDir_Blk
Enabled
Disabled
21L5.ZG.En_NegDir_Blk
Enabled
Disabled
21L5.LoadEnch.ZG.En
Enabled
21L5.ZP.RCA 0~45 1 °
21L5.ZP.phi_Shift 0~30 1 °
Disabled
21L5.ZP.En
Enabled
3
Disabled
21L5.ZP.En_BlkAR
Enabled
Disabled
21L5.ZP.En_NegDir_Blk
Enabled
Disabled
21L5.LoadEnch.ZP.En
Enabled
Disabled
21L5.En_ShortDly
Enabled
Disabled
21L5.LoadEnch.En
Enabled
Disabled
21L5.En_PSBR
Enabled
Disabled
21L5.En_ReacLine
Enabled
Forward
21L6.DirMode Reverse
Non_Directional
21L6.phi1_Reach 30~89 1 °
21L6.ZG.RCA 0~45 1 °
21L6.ZG.phi_Shift 0~30 1 °
Disabled
21L6.ZG.En
Enabled
Disabled
21L6.ZG.En_BlkAR
Enabled
Disabled
21L6.ZG.En_3I0
Enabled
Disabled
21L6.ZG.En_NeuDir_Blk
Enabled
Disabled
21L6.ZG.En_NegDir_Blk
Enabled
Disabled
21L6.LoadEnch.ZG.En
Enabled
21L6.ZP.RCA 0~45 1 °
21L6.ZP.phi_Shift 0~30 1 °
21L6.ZP.En Disabled
Enabled
Disabled
21L6.ZP.En_BlkAR
Enabled
Disabled
21L6.ZP.En_NegDir_Blk
Enabled
Disabled
21L6.LoadEnch.ZP.En
Enabled
3
Disabled
21L6.En_ShortDly
Enabled
Disabled
21L6.LoadEnch.En
Enabled
Disabled
21L6.En_PSBR
Enabled
Disabled
21L6.En_ReacLine
Enabled
21L.PilotFwd.phi1_Reach 30~89 1 °
21L.PilotFwd.ZG.RCA 0~45 1 °
Disabled
21L.PilotFwd.ZG.En_3I0
Enabled
Disabled
21L.PilotFwd.ZG.En_NeuDir_Blk
Enabled
Disabled
21L.PilotFwd.ZG.En_NegDir_Blk
Enabled
Disabled
21L.PilotFwd.LoadEnch.ZG.En
Enabled
21L.PilotFwd.ZP.RCA 0~45 1 °
Disabled
21L.PilotFwd.LoadEnch.ZP.En
Enabled
Disabled
21L.PilotFwd.En_PSBR
Enabled
Disabled
21L.PilotFwd.En_ReacLine
Enabled
21L.PilotRev.phi1_Reach 30~89 1 °
21L.PilotRev.ZG.RCA 0~45 1 °
Disabled
21L.PilotRev.ZG.En_3I0
Enabled
Disabled
21L.PilotRev.LoadEnch.ZG.En
Enabled
21L.PilotRev.ZP.RCA 0~45 1 °
Disabled
21L.PilotRev.LoadEnch.ZP.En
Enabled
Disabled
21L.PilotRev.En_PSBR
Enabled
Disabled
21L.PilotRev.En_ReacLine
Enabled
3
3.9.3 Calculation Principle
1. 21L.Ang_Alpha
It is used to set the angle of directional line in the second quadrant (when the setting [21Lx.DirMode]
is set as "Forward") or fourth quadrant (when the setting [21Lx.DirMode] is set as "Reverse") for
quadrilateral phase-to-ground distance element.
If the line positive-sequence angle is large, for example, more than 80 degree, or the system behind
the device is weak power source, this setting should be increaseded appropriately, considering the
error of line paramter and measured impedance.
2. 21L.Ang_Beta
It is used to set the angle of directional line in the fourth quadrant (when the setting [21Lx.DirMode]
is set as "Forward") or second quadrant (when the setting [21Lx.DirMode] is set as "Reverse") for
quadrilateral distance element.
3. 21L.LoadEnch.ZG.phi
[21L.LoadEnch.ZG.phi]>φLoad_Max+φθ
4. 21L.LoadEnch.ZG.R_Set
It should be less than the minimum impedance measured during heavy load conditions.
Assume that the maximum permissive load is Smax (MVA), and corresponding minimum voltage is
Umin (kV) and then under this operation condition, the recommended setting principle is as below:
2
𝑈𝑚𝑖𝑛
[21𝐿. 𝐿𝑜𝑎𝑑𝐸𝑛𝑐ℎ. 𝑍𝐺. 𝑅_𝑆𝑒𝑡] < 𝐾𝑟𝑒𝑙 × 𝑅𝑚𝑖𝑛 = 𝐾𝑟𝑒𝑙 ×
𝑆𝑚𝑎𝑥
5. 21L.LoadEnch.ZP.phi
[21L.LoadEnch.ZP.phi]>φLoad_Max+φθ
6. 21L.LoadEnch.ZP.R_Set
It should be less than the minimum impedance measured during heavy load conditions.
Assume that the maximum permissive load is Smax (MVA), and corresponding minimum voltage is
Umin (kV) and then under this operation condition, the recommended setting principle is as below:
2
𝑈𝑚𝑖𝑛
[21𝐿. 𝐿𝑜𝑎𝑑𝐸𝑛𝑐ℎ. 𝑍𝑃. 𝑅_𝑆𝑒𝑡] < 𝐾𝑟𝑒𝑙 × 𝑅𝑚𝑖𝑛 = 𝐾𝑟𝑒𝑙 ×
𝑆𝑚𝑎𝑥
7. 21L.I_PSBR
8. 21L.ZG.Opt_Characteristic
9. 21L.ZP.Opt_Characteristic
10. 21L*.DirMode
11. 21L*.Real_K0 3
It is used to set real component of zero-sequence compensation coefficient for zone * of distance
protection (*=1~6)
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿 ∗. 𝑅𝑒𝑎𝑙_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
12. 21L*.Imag_K0
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿 ∗. 𝐼𝑚𝑎𝑔_𝐾0] = 𝐼𝑚𝑎𝑔 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
13. 21L*.phi1_Reach
It is used to set phase angle of positive-sequence impedance for zone i of distance protection.
(*=1~6)
𝑋1
[21𝐿𝑖. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1( )
𝑅1
It is used to set downward offset angle of the reactance line for zone * of quadrilateral phase-to-
ground distance element. (*=1~6)
The setting is used to prevent phase-to-ground distance element from overreaching during the fault
with resistance. The setting is associated with the setting [21L*.En_ReacLine]. And its value is valid
when the setting [21L*.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
15. 21L*.ZG.Z_Set
➢ For Zone 1
Zone1 is expected to protect the most part of the line. The recommended setting principle is:
Where overhead lines are connected in parallel or operate in close proximity for the whole or part
of their length, mutual coupling exists between the two circuits. For the case where one circuit of a
parallel line is out of service and earthed at both ends, an earth fault on the remote busbar may
result in maloperation of phase-to-ground zone 1.
In this case, it is recommended to reduce the setting. Krel is recommended to be set as 0.7 or
less. It should prevent maloperation when a fault occurs on the remote busbar of line.
➢ For Zone 2
The setting should be sensitive enough to the earth fault on the remote end of the protected line,
and coordinates with the setting of zone 1 of the adjacent line. For more complex power system,
for instance, If there is a transformer or there are many adjacent lines connected to the remote bus,
the coordination should be changed accordingly.
To coordinate with zone 1 of the adjacent line, the recommended setting principle is:
[21L2.ZG.Z_Set]=K1×(ZL+KZmin×Zdz1)
KZmin is the minimum value between positive-sequence infeed coefficient and zero-sequence infeed 3
coefficient under all the operation conditions.
KZ=Iadj/Iloc
Iadj is positive-sequence current on the adjacent line when a fault happens to the adjacent line.
Iloc is positive-sequence current on the protected line when a fault happens to the adjacent line.
It should be noted that the setting should be greater than 1.2×ZL to make sure adequate sensitivity
is acheived. If it is not satisfied based on above setting rule, then zone2 of the protected line should
coordinate with zone2 of the adjacent line, in both impedance setting and time delay setting.
For parallel circuit, the setting tends to underreach due to mutual coupling. Therefore, it is
recommended to increase the setting.
➢ For Zone 3
Zone3 is both the backup for the protected line and the remote back for the adjacent line. Thus, it
should coordinate with the setting of zone 2 of the adjacent line. For more complex power system,
for instance, if there is a transformer or there are many adjacent lines connected to the remote end
of the adjacent line, the coordination should be changed accordingly.
To coordinate with zone 2 of the adjacent line, the recommended setting principle is:
[21L3.ZG.Z_Set]=K1×(ZL+KZmin×Zdz2)
It should be noted that, if ZL2 is the line impedance of the adjacent line, then the setting should be
greater than 1.2×(ZL+ KZmax×ZL2) to make sure adequate sensitivity is acheived. If it is not satisfied
based on above setting rule, then zone3 of the protected line should coordinate with zone3 of the
adjacent line, in both impedance setting and time delay setting.
16. 21L*.ZG.Z_Offset
It is used to set shift impedance setting of zone * of phase-to-ground distance element (*=2~6)
It is common offset impedance setting of phase-to-ground distance element (Mho and Quad
characteristics)
It is associated with the setting [21L*.DirMode]. It is valid when the direction setting [21L*.DirMode]
is set as "Non-directional". Because Zone1 is internally fixed in forward direction, this setting is
avalaible for Zone2~Zone6.
If this setting is too large compared with [21L*.ZG.Z_Set], then overreach is likely to happen. Thus,
the recommended setting principle is:
[21L*.ZG.R_Set]≤4×[21L*.ZG.Z_Set]
18. 21L*.ZG.R_Offset
It is used to set shift resistance setting of zone * of phase-to-ground distance element. (Quad
characteristics, *=1~6)
⚫ For the Quad characteristic distance protection with direction, it is used to cut off the unwanted
area in second quadrant.
⚫ For the Quad characteristic distance protection without direction, it is used for the offset
boundary of the operation area.
Please set this setting according to the application condition. Normally, it is calculated as 0.25 times
of the resistance setting [21L*.ZG.R_Set].
19. 21L*.ZG.phi_Shift
It is used to set phase shift of zone * of phase-to-ground distance element. (Mho characteristics,
*=1~6)
In order to improve the performance against high resistance fault, phase shift is applied to polarized
voltage in phase-to-ground distance element and phase-to-phase distance element.
⚫ Line length is not smaller than 10km and smaller than 40km: 0°~15°
20. 21L*.ZG.t_Op
It is common time delay setting of phase-to-ground distance protection. (Mho and Quad
characteristics)
➢ For Zone 1
➢ For Zone 2
Otherwise, this setting shall coordinate with the time delay of phase-to-ground distance element of
zone 2 in the adjacent line, and the recommended setting principle is:
[21L2.ZG.t_Op]=t2+Δt
Where:
➢ For Zone 3
[21L3.ZG.t_Op]=t2+Δt
Otherwise, this setting shall coordinate with the time delay of phase-to-ground distance element of
zone 3 in the adjacent line, and the recommended setting principle is:
[21L3.ZG.t_Op]=t3+Δt
Where:
21. 21L*.ZG.t_ShortDly
3 It is used to set short time delay of zone * of phase-to-ground distance element (*=2~6)
It is common short time delay of phase-to-ground distance element. (Mho and Quad characteristics)
Under some situation, distance protection with normal time delay should operate with a shorter
time delay. For example, main protection is lost on the downstream line and distance protection on
local line should be accelerated to operate.
22. 21L*.ZG.En
23. 21L*.ZG.En_BlkAR
AR will be blocked when phase-to-ground distance element operates if the setting is set as
"Enabled".
24. 21L*.ZG.En_3I0
Phase-to-ground distance element will be controlled by the signal "FD.ROC_Pkp" if the setting is
set as "Enabled".
25. 21L*ZG.En_NeuDir_Blk
26. 21L*.ZG.En_NegDir_Blk
28. 21L*.ZP.RCA
It is used to set downward offset angle of the reactance line for zone * of quadrilateral phase-to-
phase distance element. (*=1~6).
The setting is used to prevent phase-to-phase distance element from overreaching during the fault
with resistance. The setting is associated with the setting [21L*.En_ReacLine]. And its value is valid
when the setting [21L*.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-phase fault.
29. 21L*.ZP.Z_Set
➢ For Zone 1
Zone1 is expected to protect the most part of the line. The recommended setting principle is:
Where overhead lines are connected in parallel or run in close proximity for the whole or part of
their length, mutual coupling exists between the two circuits. For the case where one circuit of a
parallel line is out of service and earthed at both ends, an earth fault on the remote busbar may
➢ For Zone 2
The setting should be sensitive enough to the earth fault on the remote end of the protected line,
and coordinates with the setting of zone 1 of the adjacent line. For more complex power system,
for instance, If there is a transformer or there are many adjacent lines connected to the remote bus,
the coordination should be changed accordingly.
To coordinate with zone 1 of the adjacent line, the recommended setting principle is:
3 [21L2.ZP.Z_Set]=K1×(ZL +KZ×Zdz1)
KZ = Iadj/Iloc
Iadj is positive-sequence current on the adjacent line when a fault happens on the adjacent line.
Iloc is positive-sequence current on the protected line when a fault happens on the adjacent line.
It should be noted that, the setting should be greater than 1.2×ZL to make sure adequate sensitivity
is acheived. If it is not satisfied based on above setting rule, then zone2 of the protected line should
coordinate with zone2 of the adjacent line, in both impedance setting and time delay setting.
For parallel circuit, the setting tends to underreach due to mutual coupling. Therefore, it is
recommended to increase the setting.
➢ For Zone 3
Zone3 is both the backup for the protected line and the remote back for the adjacent line. Thus, it
should coordinate with the setting of zone 2 of the adjacent line. For more complex power system,
for instance, If there is a transformer or there are many adjacent lines connected to the remote end
of the adjacent line, the coordination should be changed accordingly.
To coordinate with zone 2 of the adjacent line, the recommended setting principle is:
[21L3.ZP.Z_Set]=K1×(ZL +KZmin×Zdz2)
It should be noted that, if ZL2 is the line impedance of the adjacent line, then the setting should be
greater than 1.2×(ZL+ KZmax×ZL2) to make sure adequate sensitivity is acheived. If it is not satisfied
based on above setting rule, then zone3 of the protected line should coordinate with zone3 of the
30. 21L*.ZP.Z_Offset
It is used to set shift impedance setting of zone * of phase-to-phase distance element. (Mho or
Quad characteristics, *=2~6)
It is associated with the setting [21L*.DirMode]. It is valid when the direction setting [21L*.DirMode]
is set as "Non-directional". Because Zone1 is internally fixed in forward direction, this setting is
avalaible for Zone2~Zone6. 3
Please set this setting according to the application condition.
31. 21L*.ZP.R_Set
If this setting is too large compared with [21L*.ZP.Z_Set], then overreach is likely to happen. Thus,
the recommended setting principle is:
[21L*.ZP.R_Set]≤4×[21L*.ZP.Z_Set]
32. 21L*.ZP.R_Offset
It is used to set shift resistance setting of zone * of quadrilateral phase-to-phase distance element.
( *=1~6)
⚫ For the Quad characteristic distance protection with direction, it is used to cut off the unwanted
area in second quadrant.
⚫ For the Quad characteristic distance protection without direction, it is used for the offset
boundary of the operation area.
Please set this setting according to the application condition. Normally, it is calculated as 0.25 times
of the resistance setting [21L*.ZP.R_Set].
33. 21L*.ZP.phi_Shift
It is used to set phase shift of zone * of Mho phase-to-phase distance element. (*=1~6)
In order to improve the performance against high resistance fault, phase shift is applied to polarized
voltage in phase-to-phase distance element and phase-to-phase distance element.
⚫ Line length is not smaller than 10km and smaller than 40km: 0°~15°
34. 21L*.ZP.t_Op
It is common time delay setting of phase-to-phase distance element. (Mho and Quad characteristics)
➢ For Zone 1
➢ For Zone 2
3 When phase-to-phase distance element of zone 2 coordinates with phase-to-phase distance
element of zone 1 of the adjacent line, the setting rule is as follows:
[21L2.ZG.t_Op]=Δt
Otherwise, this setting shall coordinate with the time delay of phase-to- phase distance element of
zone 2 in the adjacent line, and the setting rule is as follows:
[21L2.ZG.t_Op] = t2+Δt
Where:
t2 is the time delay of phase-to- phase distance element of zone 2 in adjacent line.
➢ For Zone 3
[21L3.ZG.t_Op]=t2+Δt
Otherwise, this setting shall coordinate with the time delay of phase-to-phase distance element of
zone 3 in the adjacent line, and the setting rule is as follows:
[21L3.ZG.t_Op]=t3+Δt
Where:
35. 21L*.ZP.t_ShortDly
It is used to set short time delay of zone * of phase-to-phase distance element (Mho or Quad
characteristics,*=2~6)
Under some situation, distance protection with normal time delay should operate with a shorter 3
time delay. For example, main protection is lost on the downstream line and distance protection on
local line should be accelerated to operate.
No setting rule is recommended for this setting. Please set this setting according to the application
condition.
36. 21L*.ZP.En
37. 21L*.ZP.En_BlkAR
It is used to enable/disable zone * of phase-to-phase distance element operating to block AR. (Mho
or Quad characteristics, *=1~6)
AR will be blocked when phase-to-phase distance element operates if the setting is set as
"Enabled".
38. 21L*.ZP.En_NegDir_Blk
39. 21L*.LoadEnch.ZP.En
40. 21L*.En_ShortDly
Normally, Zone 1 is used as instant distance protection, so this setting is only used for Zone 2~Zone
6.
41. 21L*.En_PSBR
When the setting is set as "Enabled", the power swing blocking for distance protction will be
3 released if corresponding conditions are satisfied.
42. 21L*.En_ReacLine
It is used to enable/disable zone * of distance protection controlled by the reactance line. (Mho or
Quad characteristics, *=1~6)
43. 21L.PilotFwd.Real_K0
It is used to set real component of zero-sequence compensation coefficient for forward pilot
distance zone.
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝐹𝑤𝑑. 𝑅𝑒𝑎𝑙_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
44. 21L.PilotFwd.Imag_K0
It is used to set imaginary component of zero-sequence compensation coefficient for forward pilot
distance zone.
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝐹𝑤𝑑. 𝐼𝑚𝑎𝑔_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
45. 21L.PilotFwd.phi1_Reach
It is used to set phase angle of positive-sequence impedance for forward pilot distance zone.
𝑋1
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝐹𝑤𝑑. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1( )
𝑅1
X1 and R1 are positive sequence reactance and resistance of the line respectively
46. 21L.PilotFwd.ZG.RCA
It is used to set downward offset angle of the reactance line for quadrilateral forward phase-to-
ground pilot distance element.
The setting is used to prevent phase-to-ground distance element from overreaching during the fault
with resistance. The setting is associated with the setting [21L.PilotFwd.En_ReacLine]. And its
value is valid when the setting [21L.PilotFwd.En_ReacLine] is set as "Enabled".
3
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
47. 21L.PilotFwd.ZG.Z_Set
It is used to set impedance setting of forward pilot distance zone. (Mho or Quad characteristics,
phase-to-ground)
This setting shall be sensitive enough to the fault in the remote end of the protected line. For lines
longer than 60km, it is usually set 1.3~1.5 times the impedance of whole line, for shorter lines,
1.5~2.0 times the impedance of whole line is recommended.
For parallel lines, phase-to-ground zone element of pilot distance protection will tend to underreach
due to mutual coupling. Therefore, it is recommended to increase the setting.
48. 21L.PilotFwd.ZG.R_Set
It is used to set resistance setting of quadrilateral forward phase-to-ground pilot distance element.
If this setting is too large compared with [21L.PilotFwd.ZG.Z_Set], then overreach is likely to
happen. Thus, the recommended setting principle is:
[21L.PilotFwd.ZG.R_Set]≤4×[21L.PilotFwd.ZG.Z_Set]
49. 21L.PilotFwd.ZG.R_Offset
It is used to set shift resistance setting of quadrilateral forward phase-to-ground pilot distance
element.
50. 21L.PilotFwd.ZG.En_3I0
It is used to enable/disable forward pilot distance zone controlled by residual current fault detector
element. (Mho or Quad characteristics, phase-to-ground)
Forward pilot distance zone (phase-to-ground) will be controlled by the signal "FD.ROC_Pkp" if the
setting is set as "Enabled".
51. 21L.PilotFwd.ZG.En_NeuDir_Blk
3 52. 21L.PilotFwd.ZG.En_NegDir_Blk
53. 21L.PilotFwd.LoadEnch.ZG.En
It is used to enable/disable phase-to-ground load trapezoid characteristics for forward pilot distance
zone. (Mho or Quad characteristics)
54. 21L.PilotFwd.ZP.RCA
It is used to set downward offset angle of the reactance line for quadrilateral forward phase-to-
phase pilot distance element.
The setting is used to prevent phase-to-phase distance element from overreaching during the fault
with resistance. The setting is associated with the setting [21L.PilotFwd.En_ReacLine]. And its
value is valid when the setting [21L.PilotFwd.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-phase fault.
55. 21L.PilotFwd.ZP.Z_Set
It is used to set impedance setting of forward phase-to-phase pilot distance element. (Mho or Quad
characteristics)
This setting shall be sensitive enough to the fault in the remote end of the protected line. For lines
longer than 60km, it is usually set 1.3~1.5 times the impedance of whole line, for shorter lines,
1.5~2.0 times the impedance of whole line is recommended.
For parallel lines, phase-to-phase zone element of pilot distance protection will tend to underreach
56. 21L.PilotFwd.ZP.R_Set
It is used to set resistance setting of quadrilateral forward phase-to-phase pilot distance element.
If this setting is too large compared with [21L.PilotFwd.ZP.Z_Set], then overreach is likely to happen.
Thus, the recommended setting principle is:
[21L.PilotFwd.ZP.R_Set]≤4×[21L.PilotFwd.ZP.Z_Set]
57. 21L.PilotFwd.ZP.R_Offset
It is used to set shift resistance setting of quadrilateral forward phase-to-phase pilot distance
element.
3
It is used to cut off the unwanted area in second quadrant.
58. 21L.PilotFwd.ZP.En_NegDir_Blk
59. 21L.PilotFwd.LoadEnch.ZP.En
It is used to enable/disable phase-to-phase load trapezoid characteristics for forward pilot distance
zone. (Mho or Quad characteristics)
60. 21L.PilotFwd.En_PSBR
It is used to enable/disable forward pilot distance zone controlled by PSBR. (Mho or Quad
characteristics)
When the setting is set as "Enabled", the power swing blocking for forward pilot distance zone will
be released if corresponding conditions are satisfied.
61. 21L.PilotFwd.En_ReacLine
It is used to enable/disable forward pilot distance zone controlled by the reactance line. (Mho or
Quad characteristics)
62. 21L.PilotRev.Real_K0
It is used to set real component of zero-sequence compensation coefficient for reverse pilot
distance zone.
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝑅𝑒𝑣. 𝑅𝑒𝑎𝑙_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Where:
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
63. 21L.PilotRev.Imag_K0
It is used to set imaginary component of zero-sequence compensation coefficient for reverse pilot
distance zone.
Where:
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
64. 21L.PilotRev.phi1_Reach
It is used to set phase angle of positive-sequence impedance for reverse pilot distance zone.
𝑋1
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝑅𝑒𝑣. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1 ( )
𝑅1
Where:
X1 and R1 are positive sequence reactance and resistance of the line respectively
65. 21L.PilotRev.ZG.RCA
It is used to set downward offset angle of the reactance line for reverse pilot distance zone. (phase-
to-ground)
It is used to prevent reverse pilot distance zone (phase-to-ground) from overreaching during the
fault with resistance. The setting is associated with the setting [21L.PilotRev.En_ReacLine]. And it
is valid only if the setting [21L.PilotRev.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
66. 21L.PilotRev.ZG.Z_Set
It is used to set impedance setting of reverse pilot distance zone. (Mho or Quad characteristics,
phase-to-ground)
Under weak power source condition, when an internal fault occurs, the device at weak power
source end could not detect the fault, then pilot distance protection could not operate for internal
fault. The problem is eliminated by the weak infeed logic based on the impedance setting of pilot
distance protection in reverse direction. Shown as following figure, if permissive signal from remote
side is received by weak infeed end, while the pilot reverse zone doesn’t start, then it is confirmed
as internal fault.
21L.PilotFwd.ZG.Z_Set
ZL
21L.PilotRev.ZG.Z_Rev
EM M A Fault B N EN
3
21L.PilotRev.ZG.Z_Rev
21L.PilotFwd.ZG.Z_Set
The protection area of reverse pilot distance element should overlap the protection area of the
fowward pilot distance element in reverse direction. Thus, the recommended setting principle is:
Where:
67. 21L.PilotRev.ZG.R_Set
It is used to set resistance setting of quadrilateral reverse phase-to-phase pilot distance element.
If this setting is too large compared with [21L.PilotRev.ZG.Z_Set], then overreach is likely to happen.
Thus, the recommended setting principle is:
[21L.PilotRev.ZG.R_Set]≤4×[21L.PilotRev.ZP.G_Set]
68. 21L.PilotRev.ZG.R_Offset
It is used to set shift resistance setting of quadrilateral reverse phase-to-ground pilot distance zone.
69. 21L.PilotRev.ZG.En_3I0
It is used to enable/disable reverse pilot distance zone controlled by residual current fault detector
element. (phase-to-ground)
Reverse pilot distance zone (phase-to-ground) will be controlled by the signal "FD.ROC_Pkp" if
the setting is set as "Enabled".
70. 21L.PilotRev.LoadEnch.ZG.En
It is used to enable/disable phase-to-ground load trapezoid characteristics for reverse pilot distance
71. 21L.PilotRev.ZP.RCA
It is used to set downward offset angle of the reactance line for reverse phase-to-phase pilot
distance element.
It is used to prevent reverse phase-to-ground pilot distance element from overreaching during the
fault with resistance. The setting is associated with the setting [21L.PilotRev.En_ReacLine]. And it
is valid only if the setting [21L.PilotRev.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
3 phase-to-ground fault.
72. 21L.PilotRev.ZP.Z_Set
Under weak power source condition, when an internal fault occurs, the device at weak power
source end could not detect the fault, then pilot distance protection could not operate for internal
fault. The problem is eliminated by the weak infeed logic based on the impedance setting of pilot
distance protection in reverse direction. Shown as following figure, if permissive signal from remote
side is received by weak infeed end, while the pilot reverse zone doesn′t start, then it is confirmed
as internal fault.
21L.PilotFwd.ZP.Z_Set
ZL
21L.PilotRev.ZP.Z_Rev
EM M A Fault B N EN
21L.PilotRev.ZP.Z_Rev
21L.PilotFwd.ZP.Z_Set
The protection area of reverse pilot distance element should overlap the protection area of the
fowward pilot distance element in reverse direction. Thus, the recommended setting principle is:
Where:
73. 21L.PilotRev.ZP.R_Set
It is used to set resistance setting of quadrilateral reverse phase-to-phase pilot distance element.
If this setting is too large compared with [21L.PilotRev.ZP.Z_Set], then overreach is likely to happen.
[21L.PilotRev.ZP.R_Set]≤4×[21L.PilotRev.ZP.Z_Set]
74. 21L.PilotRev.ZP.R_Offset
It is used to set shift resistance setting of quadrilateral reverse phase-to-phase pilot distance zone.
75. 21L.PilotRev.LoadEnch.ZP.En
It is used to enable/disable phase-to-phase load trapezoid characteristics for reverse pilot distance
zone. (Mho or Quad characteristics)
3
76. 21L.PilotRev.En_PSBR
When the setting is set as "Enabled", the power swing blocking for reverse pilot distance zone will
be released if corresponding conditions are satisfied.
77. 21L.PilotRev.En_ReacLine
It is used to enable/disable reverse pilot distance zone controlled by the reactance line.
⚫ LCD
⚫ PCS-Studio
Disabled
78.En
Enabled
Disabled
78.En_Trp
Enabled
78.phi1_Reach 30~89 1 °
78.phi_Start 0~180 1 °
78.phi_Trp 0~180 1 °
78.N_Limit 1~20 1
1. 78.En
2. 78.En_Trp
3. 78.Z_Fwd
4. 78.Z_Rev
In order to locate the distance between the oscillation center and where the device is equipped,
setting impedance measurement element is used to confirm the operation range of separation
device, the operation characteristic of zone relay is based on impedance discrimination. Out-of-
step protection will operate when both zone relay and out-of-step relay operate.
ZM * ZLine ZN
EM G 52 52 G EN
I U
IED
ZRev ZFwd
Where:
ZFwd is the impedance from zone relay location to side-N system, i.e., [78.Z_Fwd]
ZRev is the impedance from zone relay location to side-M system, i.e., [78.Z_Rev]
5. 78.phi1_Reach
It is used to set the system impedance angle for the zone detector.
The impedance angle is calculated based on the line parameters. The equation is as bellow.
𝑋1
[78. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1 ( )
𝑅1
Where:
X1 and R1 are positive sequence reactance and resistance of the line respectively.
6. 78.phi_Start
3
It is used to set the minimum start angle of out-of-step condition.
7. 78.phi_Trp
It is used to set the maximum tripping angle after out-of-step protection operating, which is used to
prevent the circuit breaker from incorrect operation due to too large current during tripping.
8. 78.N_Limit
If the device detects the out-of-step condition and issues tripping command after the time delay
(i.e., the setting [78.N_Limit]), performing separation. The setting depends on the coordination of
the out of step relays.
⚫ LCD
⚫ PCS-Studio
Disabled
21SOTF.En
Enabled
3 Disabled
21SOTF.Z2.En_ManCls
Enabled
Disabled
21SOTF.Z3.En_ManCls
Enabled
Disabled
21SOTF.Z4.En_ManCls
Enabled
Disabled
21SOTF.Z2.En_3PAR
Enabled
Disabled
21SOTF.Z3.En_3PAR
Enabled
Disabled
21SOTF.Z4.En_3PAR
Enabled
Disabled
21SOTF.Z2.En_PSBR
Enabled
Disabled
21SOTF.Z3.En_PSBR
Enabled
Disabled
21SOTF.Z4.En_PSBR
Enabled
Disabled
21SOTF.Z2.En_1PAR
Enabled
21SOTF.En_PDF Disabled
Enabled
ManClsBI
CBPos
SOTF.Opt_Mode_ManCls ManClsBI/CBPos
AutoInit
3
All
1. SOTF.t_En
It should be more than the fixed time of closing the circuit breaker, but should not be too long. Its
recommended value is 3s.
The setting is shared by distance SOTF protection, phase current SOTF protection and residual
current SOTF protection.
2. 21SOTF.t_ManCls
It is used to set time delay of distance protection accelerating to trip when manual closing.
3. 21SOTF.t_3PAR
It is used to set time delay of distance protection accelerating to trip when 3-pole reclosing.
4. 21SOTF.t_1PAR
It is used to set time delay of distance protection accelerating to trip when 1-pole reclosing.
5. 21SOTF.En
6. 21SOTF.Z2.En_ManCls
7. 21SOTF.Z3.En_ManCls
8. 21SOTF.Z4.En_ManCls
9. 21SOTF.Z2.En_3PAR
10. 21SOTF.Z3.En_3PAR
11. 21SOTF.Z4.En_3PAR
12. 21SOTF.Z2.En_PSBR
3 It is used to enable/disable zone 2 controlled by PSB of distance SOTF protection for 3-pole
reclosing.
13. 21SOTF.Z3.En_PSBR
It is used to enable/disable zone 3 controlled by PSB of distance SOTF protection for 3-pole
reclosing.
14. 21SOTF.Z4.En_PSBR
It is used to enable/disable zone 4 controlled by PSB of distance SOTF protection for 3-pole
reclosing.
15. 21SOTF.Z2.En_1PAR
16. 21SOTF.t_PDF
It is used to set time delay of distance protection operating under pole discrepancy conditions.
This setting is the time delay for distance SOTF protection for another fault on the healthy phase
during pole discrepancy condition. The setting is recommended to set as 150ms.
17. 21SOTF.En_PDF
Under pole discrepancy condition after single-phase tripping, distance SOTF protection for pole
discrepancy will operate with the time delay [21SOTF.t_PDF] if another fault happens to the healthy
phase. This function is provided based on the high possibility that the late fault might be at the
same point with the previous fault, which could reduce the fault clearing time.
Distance SOTF protection for pole discrepancy will operate for external fault
on healthy phase during pole discrepancy condition after a time delay of
150ms, however the fault will be cleared in 150ms, so the possibility of
maloperation for external fault is very low. But users should evaluate
carefully.
18. SOTF.U_Ddl
When manual SOTF mode is set as "AutoInit", i.e., initiated by no voltage detection, distance
SOTF protection will be initiated by dead line check. When three phases currents are all smaller
3
than 0.04In and no fault detector element operates, SOTF logic will be enabled with the time delay
[SOTF.t_Ddl] if three phase voltages are all smaller than the setting [SOTF.U_Ddl].
19. SOTF.t_Ddl
20. SOTF.Opt_Mode_ManCls
The setting provides the selection for accelerated tripping mode, which can be from circuit breaker
position, external binary signal of manual closing or dead line check, the options are shown as
follows.
All: initiated by both binary input of manual closing, CB position, or initated by no voltage detection
⚫ LCD
⚫ PCS-Studio
50/51P.DIR.RCA -180~179 1 °
3 50/51P.DIR.RCA_NegOC -180~179 1 °
50/51P.DIR.phi_Min_Fwd 10~90 1 °
50/51P.DIR.phi_Max_Fwd 10~90 1 °
50/51P.DIR.phi_Min_Rev 10~90 1 °
50/51P.DIR.phi_Max_Rev 10~90 1 °
U2
Upp
50/51P.DIR.Opt_PolarizedVolt
Up
U1
Disabled
50/51P.En_VTS_Blk
Enabled
PhaseBlk
50/51P.HMB.Opt_Blk CrossBlk
MaxPhaseBlk
50/51P1.En_Volt_Blk Disabled
Enabled
Non_Directional
50/51P1.Opt_Dir Forward
Reverse
Disabled
50/51P1.En_Hm_Blk
Enabled
Disabled
3
50/51P1.En
Enabled
Trp
50/51P1.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P1.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P1.Opt_Curve_DropOut
DefTime
IDMT
Disabled
50/51P2.En_Volt_Blk
Enabled
Non_Directional
50/51P2.Opt_Dir Forward
Reverse
Disabled
50/51P2.En_Hm_Blk
Enabled
Disabled
50/51P2.En
Enabled
Trp
50/51P2.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
50/51P2.Opt_Curve
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
3
UserDefine
Inst
50/51P2.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P3.En_Volt_Blk
Enabled
Non_Directional
50/51P3.Opt_Dir Forward
Reverse
Disabled
50/51P3.En_Hm_Blk
Enabled
Disabled
50/51P3.En
Enabled
Trp
50/51P3.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
3 ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P3.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P3.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P4.En_Volt_Blk
Enabled
Non_Directional
50/51P4.Opt_Dir Forward
Reverse
Disabled
3
50/51P4.En_Hm_Blk
Enabled
Disabled
50/51P4.En
Enabled
Trp
50/51P4.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P4.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P4.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P5.En_Volt_Blk
Enabled
Non_Directional
50/51P5.Opt_Dir Forward
Reverse
Disabled
50/51P5.En_Hm_Blk
Enabled
Disabled
50/51P5.En
Enabled
Trp
50/51P5.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
50/51P5.Opt_Curve
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
3
IECLT
IECDefTime
UserDefine
Inst
50/51P5.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P6.En_Volt_Blk
Enabled
Non_Directional
50/51P6.Opt_Dir Forward
Reverse
Disabled
50/51P6.En_Hm_Blk
Enabled
Disabled
50/51P6.En
Enabled
Trp
50/51P6.Opt_Trp/Alm
Alm
ANSIE
ANSIV
3 ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P6.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P6.Opt_Curve_DropOut DefTime
IDMT
Phase overcurrent protection is provided with six stages, each stage has independent current
setting, time delay and control logic. Generally, stage 1 of phase overcurrent protection requires
instantaneously operating, and the protected range shall not be less than 20% of the total line.
Stage 2 of phase overcurrent protection shall protect the whole line. Stage 3 and stage 4 of phase
overcurrent protection can be backup protection for the line, and also can be remote backup
protection for the adjacent line.
1. 50/51P.VCE.Upp
𝑈𝑚𝑖𝑛
[50/51𝑃. 𝑉𝐶𝐸. 𝑈𝑝𝑝] =
𝐾𝑟𝑒𝑙
Where:
Umin is the possible minimum phase-to-phase voltage during normal operation, which can be
normally taken as 0.9Un. (Un is secondary value of the rated phase-to-phase voltage)
2. 50/51P.VCE.U2
The setting should be greater than the imbalanced voltage during normal operation, the imbalanced
voltage value can be determined through actual measurement.
3. 50/51P.VCE.3U0
The setting should be larger than the maximum residual voltage during normal operation.
4. 50/51P.DIR.RCA
Ua
[50/51P.DIR.phi_Min_Fwd]
Non-operating Ia
area
[50/51P.DIR.RCA]
Operating area in
3
reverse direction
[50/51P.DIR.phi_Max_Fwd]
[50/51P.DIR.phi_Min_Rev] Non-operating
area
By setting the characteristic angle to determine the most sensitive forward angle of phase current,
using phase current with phase polarized voltage to determine the direction of phase current in
forward direction or reverse direction. The setting defines the system impedance angle of positive-
sequence circuit.
5. 50/51P.DIR.RCA_NegOC
By setting the characteristic angle to determine the most sensitive forward angle of negative-
sequence current, using negative-sequence current with negative-sequence voltage to determine
the direction of negative-sequence current in forward direction or reverse direction.
6. 50/51P.DIR.phi_Min_Fwd
It is used to set the minimum boundary in forward direction of phase overcurrent protection.
7. 50/51P.DIR.phi_Max_Fwd
It is used to set the maximum boundary in forward direction of phase overcurrent protection.
8. 50/51P.DIR.phi_Min_Rev
It is used to set the minimum boundary in reverse direction of phase overcurrent protection.
9. 50/51P.DIR.phi_Max_Rev
It is used to set the maximum boundary in reverse direction of phase overcurrent protection.
10. 50/51P.DIR.Opt_PolarizedVolt
It is used to select the voltage polarization mode of direction control element for phase overcurrent
protection.
11. 50/51P.DIR.I_Min
It is used to set the minimum operating current setting of direction control element.
12. 50/51P.DIR.U_Min
It is used to set the minimum operating voltage setting of direction control element.
13. 50/51P.En_VTS_Blk
When VT circuit fails, phase overcurrent protection will be blocked if the setting is set as "Enabled".
Phase overcurrent protection is not controlled by direction control element and voltage control
element if the setting is set as "Disabled".
14. 50/51P.HMB.K_Hm2
In order to prevent phase overcurrent protection from maloperation during the transformer
energized for transformer-in-line application, harmonic control element can be used to block phase
overcurrent protection. When the percentage of second harmonic component to fundamental
component in phase current is larger than the setting [50/51P.HMB.K_Hm2], harmonic control
element operates to block phase overcurrent protection if the setting [50/51Pi.En_Hm_Blk] is set
as "Enabled".
If second harmonic component of phase current is lower than 0.04In, then harmonic calculation is
not carried out and harmonic control element does not operate.
15. 50/51P.HMB.I_Rls
16. 50/51P.HMB.Opt_Blk
17. 50/51P*.I_Set
It is used to set the current setting for stage * of phase overcurrent protection. (*=1~6)
Where:
Imax is the maximum three-phase short-circuit current measured at the location where the device is
installed in case of short circuit at the end of the protected line.
Krel is reliable coefficient, considering relay setting value error, short-circuit current calculation error,
as well as influence of non-periodic component on protection in short-circuit current, taking 1.2~1.3
or above.
⚫ Phase overcurrent protection with definite time delay requires protecting the whole line and
cooperating with phase overcurrent protection of adjacent line. According to the specific
condition of adjacent line protection, the setting calculation principle is as follows:
Where:
Kb.max is branch coefficient of current, which is equal to the ratio of the current passing through the
device to the current passing through the faulty line during an earth fault at the end of protected
range of the coordinated stage of overcurrent protection of the line.
⚫ Phase overcurrent protection with definite time delay requires being used as backup protection
of the transformer equipped with transformer current differential protection, the setting shall be
set and calculated according to the following equation.
Where:
Imax is the maximum three-phase short-circuit current of the local line when a fault happens to the
other sides of the transformer for phase overcurrent protection which is permitted to cover the
transformer.
𝐾𝑟𝑒𝑙 × 𝐾𝑠𝑠
[50/51𝑃 ∗. 𝐼_𝑆𝑒𝑡] = × 𝐼𝐿.𝑚𝑎𝑥
𝐾𝑟𝑒
Where:
Kss is self-starting coefficient, determined by specific connection and load property via network.
18. 50/51P*.t_Op
It is used to set the operating time delay for stage * of phase overcurrent protection. (*=1~6)
⚫ When the operating current is in coordination with instantaneous overcurrent protection of the
adjacent line, the operating time of definite-time phase overcurrent protection is:
[50/51P*.t_Op]=t1+Δt
Where:
t1 is the fixed operating time of instantaneous overcurrent protection of the adjacent line, about
0.06~0.1s, or neglected sometimes
⚫ When the operating current is in coordination with definite-time stage of phase overcurrent
protection of adjacent line, the operating time of definite-time phase overcurrent protection is:
[50/51P*.t_Op]=t2+Δt
Where:
t2 is the fixed operating time of the coordinated stage of phase overcurrent protection of adjacent
line.
19. 50/51P*.t_DropOut
It is used to set the dropout time delay for stage * of phase overcurrent protection. (*=1~6)
The definite-time dropout characteristic can refer to corresponding section in "Technical Manual".
20. 50/51P*.En_Volt_Blk
21. 50/51P*.Opt_Dir
It is used to select the direction characteristic for stage * of phase overcurrent protection. (*=1~6)
Non_Directional: no direction
22. 50/51P*.En_Hm_Blk
23. 50/51P*.En
24. 50/51P*.Opt_Trp/Alm
It is used to enable/disable stage * of phase overcurrent protection operate to trip or alarm. (*=1~6)
25. 50/51P*.Opt_Curve
It is used to select the operating characteristics curve for stage * of phase overcurrent protection.
(*=1~6)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
26. 50/51P*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of phase overcurrent protection.
(*=1~6)
When the operating characteristics curve is selected as definite-time, IEC inverse-time or user-
defined inverse-time characteristics, the dropout characteristic curve can only be selected as
instantaneous dropout characteristics or definite-time dropout characteristics. The alarm signal
"Fail_Settings" will be issued and the device will be blocked if inverse-time dropout characteristics
is selected.
When the operating characteristics curve is selected as ANSI inverse-time characteristic, the
dropout characteristic curve can be selected as instantaneous dropout characteristics, definite-time
dropout characteristics and ANSI inverse-time dropout characteristics.
27. 50/51P*.TMS
It is used to set time multiplier setting for stage * of inverse-time phase overcurrent protection.
(*=1~6)
This setting can be deduced according to the operating time required by inverse-time phase
overcurrent protection.
28. 50/51P*.tmin
It is used to set the minimum operating time for stage * of inverse-time phase overcurrent protection.
(*=1~6)
When inverse-time characteristic is selected, if calculated operating time is less than the setting
3 [50/51P*.tmin], then the operating time changes to the value of the setting [50/51P*.tmin]
automatically.
Where:
29. 50/51P*.K
It is used to set the constant "K" for stage * of customized inverse-time phase overcurrent protection.
(*=1~6)
The setting shall be set according to the expected inverse-time characteristics of phase overcurrent
protection. It is valid only if the setting [50/51P*.Opt_Curve] is set as "UserDefine".
30. 50/51P*.Alpha
It is used to set the constant "α" for stage * of customized inverse-time phase overcurrent protection.
(*=1~6)
The setting shall be set according to the expected inverse-time characteristics of phase overcurrent
protection. It is valid only if the setting [50/51P*.Opt_Curve] is set as "UserDefine".
31. 50/51P*.C
It is used to set the constant "C" for stage * of customized inverse-time phase overcurrent protection.
(*=1~6)'
The setting shall be set according to the expected inverse-time characteristics of phase overcurrent
protection. It is valid only if the setting [50/51P*.Opt_Curve] is set as "UserDefine".
⚫ LCD
⚫ PCS-Studio
1. 50PSOTF.I_Set
2. 50PSOTF.t_Op
3. 50PSOTF.Up_Set
In order to improve the reliability, phase current SOTF protection can select phase voltage element
as auxiliary criterion.
4. 50PSOTF.Upp_Set
In order to improve the reliability, phase current SOTF protection can select phase-phase voltage
element as auxiliary criterion.
In order to improve the reliability, phase current SOTF protection can select negative-sequence
voltage element as auxiliary criterion.
6. 50PSOTF.3U0_Set
In order to improve the reliability, phase current SOTF protection can select zero-sequence voltage
element as auxiliary criterion.
7. 50PSOTF.En_Up_UV
It is used to enable/disable phase undervoltage supervision logic for phase current SOTF protection.
If the setting is set as "Disabled", the phase undervoltage criterion will not take effect.
8. 50PSOTF.En_Upp_UV
It is used to enable/disable phase-phase undervoltage supervision logic for phase current SOTF
protection.
If the setting is set as "Disabled", the phase-phase undervoltage criterion will not take effect.
9. 50PSOTF.En_U2_OV
If the setting is set as "Disabled", the negative-sequence overvoltage criterion will not take effect.
10. 50PSOTF.En_3U0_OV
It is used to enable/disable zero-sequence overvoltage supervision logic for phase current SOTF
protection.
If the setting is set as "Disabled", the zero-sequence ovevoltage criterion will not take effect.
11. 50PSOTF.En
It is used to enable/disable second harmonic blocking for phase overcurrent SOTF protection.
For in-line transformer application, large inrush current generated during manual closing and auto-
reclosing will lead to an undesired operation of phase current SOTF protection. Second harmonic
blocking can be selected by the setting [50PSOTF.En_Hm2_Blk] to prevent maloperation due to
inrush current. 3
3.14 Earth Fault Protection (50/51G)
⚫ LCD
⚫ PCS-Studio
50/51G.DIR.RCA -180~179 1 °
50/51G.DIR.phi_Min_Fwd 10~90 1 °
50/51G.DIR.phi_Max_Fwd 10~90 1 °
50/51G.DIR.phi_Min_Rev 10~90 1 °
50/51G.DIR.phi_Max_Rev 10~90 1 °
3U0
50/51G.DIR.Opt_PolarizedVolt
U2
50/51G.En_VTS_Blk Disabled
Enabled
50/51G1.Opt_Dir Forward
Reverse
Disabled
50/51G1.En_Hm_Blk
Enabled
Disabled
50/51G1.En
Enabled
Trp
50/51G1.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
50/51G1.Opt_Curve ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G1.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G2.Opt_Dir Forward
Reverse
Disabled
50/51G2.En_Hm_Blk
Enabled
Disabled
50/51G2.En
Enabled
Trp
50/51G2.Opt_Trp/Alm
Alm
ANSIE
ANSIV
50/51G2.Opt_Curve ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
3 IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G2.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G3.Opt_Dir Forward
Reverse
Disabled
50/51G3.En_Hm_Blk
Enabled
50/51G3.En Disabled
Enabled
Trp
50/51G3.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
3
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51G3.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G3.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G4.Opt_Dir Forward
Reverse
Disabled
3 50/51G4.En_Hm_Blk
Enabled
Disabled
50/51G4.En
Enabled
Trp
50/51G4.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51G4.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
50/51G4.Opt_Curve_DropOut Inst
DefTime
IDMT
Non_Directional
50/51G5.Opt_Dir Forward
Reverse
Disabled
50/51G5.En_Hm_Blk
Enabled
Disabled
50/51G5.En
Enabled
Trp
50/51G5.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
50/51G5.Opt_Curve ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
3 UserDefine
Inst
50/51G5.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G6.Opt_Dir Forward
Reverse
Disabled
50/51G6.En_Hm_Blk
Enabled
Disabled
50/51G6.En
Enabled
Trp
50/51G6.Opt_Trp/Alm
Alm
50/51G6.Opt_Curve ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
3
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G6.Opt_Curve_DropOut DefTime
IDMT
1. 50/51G.DIR.RCA
-U0
[50/51G.DIR.phi_Min_Fwd]
Non-operating I0
area
Operating area in
[50/51G.DIR.phi_Max_Rev] forward direction
[50/51G.DIR.RCA]
Operating area in
3
reverse direction
[50/51G.DIR.phi_Max_Fwd]
Non-operating
area
[50/51G.DIR.phi_Min_Rev]
By setting the characteristic angle to determine the most sensitive forward angle of zero-sequence
current, using zero-sequence current with zero-sequence voltage to determine the direction of zero-
sequence current in forward direction or reverse direction.
For line protection, when the CT polarity is on the busbar side, its recommended value is 45°.
2. 50/51G.DIR.phi_Min_Fwd
It is used to set the minimum boundary in forward direction of earth fault protection.
3. 50/51G.DIR.phi_Max_Fwd
It is used to set the maximum boundary in forward direction of earth fault protection.
4. 50/51G.DIR.phi_Min_Rev
It is used to set the minimum boundary in reverse direction of earth fault protection.
5. 50/51G.DIR.phi_Max_Rev
It is used to set the maximum boundary in reverse direction of earth fault protection.
6. 50/51G.DIR.Opt_PolarizedVolt
7. 50/51G.DIR.3I0_Min
It is used to set the minimum operating current setting of direction control element.
8. 50/51G.DIR.3U0_Min
It is used to set the minimum operating voltage setting of direction control element.
Its recommended value is 4V. Considering the sensitivity of earth fault with high resistance, the
recommended value is 0.5~2V. When it cooperates with other protection with direction control
element, it is recommended to add 0.5~1V on the basis of the similar setting of other protection.
3
9. 50/51G.DIR.Z0_Comp
C1 C2 C3
L1 L2 L3 L4
M N
VT2 VT3 VT5
VT1 VT4
L5 L6
C4 C5 C6
O
The setting should make zero-sequence directional element not mal-operate when a fault happens
in forward direction. Usually it can be set according to the secondary value of capacitive reactance
of the series capacitors connected to local line behind VT in series.
⚫ For IED1, IED3 and IED8, there is no series capacitor behind the corresponding VT, the setting
[50/51G.DIR.Z0_Comp] of IED1, IED3 and IED8 should be set as "0".
⚫ For IED2 and IED4, there are series capacitors behind the corresponding VT, but the series
are installed in adjacent lines, usually the series compensations for HV line is
undercompensated mode, the system impedance behind IED2 and IED4 is still inductive
impedance. Hence, the setting [50/51G.DIR.Z0_Comp] of IED2 and IED4 should be set as "0".
⚫ For IED5, if the protection VT is from busbar VT1, when line L5, series capacitor C4 and C5
are in service, there are series capacitors behind the corresponding VT, but C4 and C5 are
undercompensated relative to line L5, so the setting [50/51G.DIR.Z0_Comp] of IED5 should
be set as "0". When line L5, or series capacitor C4 and C5 are out of service, there is no series
capacitor behind the corresponding VT, so the setting [50/51G.DIR.Z0_Comp] of IED5 should
be set as "0". If the protection VT is from line VT2, there is series capacitor C1 behind the
⚫ For IED6, if the protection VT is from busbar VT4, similar to IED5, so the setting
[50/51G.DIR.Z0_Comp] of IED6 should be set as "0". If the protection VT is from line VT3,
there is series capacitors C2 behind the corresponding VT, so the setting
[50/51G.DIR.Z0_Comp] of IED6 should be set as "XC2".
⚫ For IED7, if the protection VT is from busbar VT4, similar to IED5, so the setting
[50/51G.DIR.Z0_Comp] of IED7 should be set as "0". If the protection VT is from line VT5,
there is series capacitor C3 behind the corresponding VT, so the setting
[50/51G.DIR.Z0_Comp] of IED7 should be set as "XC3".
3 10. 50/51G.En_VTS_Blk
It is used to enable/disable earth fault protection is blocked by VT circuit failure when VT circuit
supervision is enabled and VT circuit fails.
When VT circuit fails, earth fault protection will be blocked if the setting is set as "Enabled". Earth
fault protection is not controlled by direction control element if the setting is set as "Disabled".
11. 50/51G.HMB.K_Hm2
In order to prevent earth fault protection from maloperation during the transformer energized for
transformer-in-line application, harmonic control element can be used to block earth fault protection.
When the percentage of second harmonic component to fundamental component in phase current
is larger than the setting [50/51G.HMB.K_Hm2], harmonic control element operates to block phase
overcurrent protection if the setting [50/51Gi.En_Hm_Blk] is set as "Enabled".
If second harmonic component of residual current is lower than 0.04In, then harmonic calculation
is not carried out and harmonic control element does not operate.
12. 50/51G.HMB.I_Rls
It shall be greater than possible maximum inrush current of the transformer. It is recommended to
set as 20In.
13. 50/51G*.3I0_Set
It is used set the zero-sequence current setting for stage * of earth fault protection. (*=1~6)
1) When stage * of earth fault protection is used as fast protection, the following conditions should
be considered.
⚫ It shall be greater than the maximum residual current under pole disagreement condition.
⚫ It shall be greater than the maximum residual current when internal fault happens to the end
of the line.
Where:
2) When stage * of earth fault protection is used as definite-time protection, it should coordinate
with the protection of other adjacent line.
⚫ It shall be greater than the maximum residual current under pole disagreement condition.
3
⚫ It shall coordinate with the measurement element in the adjacent line and ensure sensitive
enough for the fault happening to the end of the line.
Where:
Kbr is the branching coefficient of residual current, which is equal to ratio of residual current passing
through the device to passing through the faulty line during an earth fault at the end of protected
section of coordinated stage of earth fault protection of the line. Maximum value among various
operation conditions can be taken
3) When earth fault protection is used as backup protection for ground fault of this line through
resistor and ground fault of adjacent elements, and its primary current value should not be more
than 300A. Under the condition of avoidance from the maximum unbalance current of three-
phase short circuit at other sides of the transformer at the end of this line, it is necessary to
meet the requirement that the fault at the end of the adjacent lines has sufficient sensitivity; it
is necessary to check the coordination condition with the definite-time earth fault protection of
the adjacent line, and the operating time is set according to the coordination relation.
Where:
Kst is same type coefficient, taken as 0.5 when the transformer is of the same type.
4) When earth fault protection is used as inverse-time protecton, the calculation principle is
Where:
14. 50/51G*.t_Op
It is used to set the operating time delay for stage * of earth fault protection. (*=1~6)
3 ⚫ When earth fault protection as definite-time protection coordinates with adjacent line, this
setting should be set according to coordinate with time delay of earth fault protection of the
subordinate line.
Where:
⚫ If it is used independently, it should be greater than maximum operation time of system pole
discrepancy.
15. 50/51G*.t_DropOut
It is used to set the dropout time delay for stage * of earth fault protection. (*=1~6)
16. 50/51G*.Opt_Dir
It is used to select the direction characteristic for stage * of earth fault protection. (*=1~6)
Non_Directional: no direction
17. 50/51G*.En_Hm_Blk
It is used to enable/disable stage * of earth fault protection controlled by harmonic control element.
(*=1~6)
18. 50/51G*.En
19. 50/51G*.Opt_Trp/Alm
It is used to enable/disable stage * of earth fault protection operate to trip or alarm. (*=1~6)
20. 50/51G*.Opt_Curve
It is used to select the operating characteristics curve for stage * of earth fault protection. (*=1~6)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
21. 50/51G*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of earth fault protection. (*=1~6)
When the operating characteristics curve is selected as definite-time, IEC inverse-time or user-
defined inverse-time characteristics, the dropout characteristic curve can only be selected as
instantaneous dropout characteristics or definite-time dropout characteristics. The alarm signal
"Fail_Settings" will be issued and the device will be blocked if inverse-time dropout characteristics
is selected.
When the operating characteristics curve is selected as ANSI inverse-time characteristic, the
dropout characteristic curve can be selected as instantaneous dropout characteristics, definite-time
dropout characteristics and ANSI inverse-time dropout characteristics.
22. 50/51G*.TMS
It is used to set time multiplier setting for stage * of inverse-time earth fault protection. (*=1~6)
This setting can be deduced according to the operating time required by inverse-time earth fault
3 protection.
23. 50/51G*.tmin
It is used to set the minimum operating time for stage * of inverse-time earth fault protection. (*=1~6)
When inverse-time characteristic is selected, if calculated operating time is less than the setting
[50/51G*.tmin], then the operating time changes to the value of the setting [50/51G*.tmin]
automatically.
Where:
24. 50/51G*.K
It is used to set the constant “K” for stage * of customized inverse-time earth fault protection. (*=1~6)
The setting shall be set according to the expected inverse-time characteristics of earth fault
protection. It is valid only if the setting [50/51G*.Opt_Curve] is set as "UserDefine".
25. 50/51G*.Alpha
It is used to set the constant “α” for stage * of customized inverse-time earth fault protection. (*=1~6)
The setting shall be set according to the expected inverse-time characteristics of earth fault
protection. It is valid only if the setting [50/51G*.Opt_Curve] is set as "UserDefine".
26. 50/51G*.C
It is used to set the constant “C” for stage * of customized inverse-time earth fault protection. (*=1~6)
The setting shall be set according to the expected inverse-time characteristics of earth fault
protection. It is valid only if the setting [50/51G*.Opt_Curve] is set as "UserDefine".
⚫ LCD
⚫ PCS-Studio
Disabled
50GSOTF.En
Enabled
Disabled
50GSOTF.En_Hm2_Blk
Enabled
The setting should ensure sufficient sensitivity to ground fault with high impedance at the end of
the line.
2. 50GSOTF.t_Op_1P
It is used to set time delay for residual current SOTF protection when 1 pole closed.
3. 50GSOTF.t_Op_3P
It is used to set time delay for residual current SOTF protection when 3 pole closed.
4. 50GSOTF.En
5. 50GSOTF.En_Hm2_Blk
For in-line transformer application, large inrush current generated during manual closing and auto-
reclosing will lead to an undesired operation of residual current SOTF protection. Second harmonic
blocking can be selected by the setting [50GSOTF.En_Hm2_Blk] to prevent maloperation due to
inrush current.
3
3.16 Negative-sequence Overcurrent Protection (50/51Q)
⚫ LCD
⚫ PCS-Studio
50/51Q.DIR.RCA -180~179 1 °
50/51Q.DIR.phi_Min_Fwd 10~90 1 °
50/51Q.DIR.phi_Max_Fwd 10~90 1 °
50/51Q.DIR.phi_Min_Rev 10~90 1 °
50/51Q.DIR.phi_Max_Rev 10~90 1 °
Disabled
50/51Q.En_VTS_Blk
Enabled
Non_Directional
50/51Q1.Opt_Dir Forward
Reverse
Disabled
50/51Q1.En
Enabled
Trp
3
50/51Q1.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51Q1.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51Q1.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51Q2.Opt_Dir Forward
Reverse
Disabled
50/51Q2.En
Enabled
Trp
50/51Q2.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
50/51Q2.Opt_Curve
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51Q2.Opt_Curve_DropOut DefTime
IDMT
1. 50/51Q.DIR.RCA
-U2
[50/51Q.DIR.phi_Min_Fwd]
Non-operating I2
area
[50/51Q.DIR.phi_Max_Rev]
Operating area in
forward direction
[50/51Q.DIR.RCA]
Operating area in
reverse direction
[50/51Q.DIR.phi_Max_Fwd]
Non-operating
area
[50/51Q.DIR.phi_Min_Rev]
By setting the characteristic angle to determine the most sensitive forward angle of negative-
sequence current, using negative-sequence current with negative-sequence voltage to determine
the direction of negative-sequence current in forward direction or reverse direction.
2. 50/51Q.DIR.phi_Min_Fwd
3. 50/51Q.DIR.phi_Max_Fwd
4. 50/51Q.DIR.phi_Min_Rev
3 It is use to set the minimum boundary in reverse direction of negative-sequence overcurrent
protection.
5. 50/51Q.DIR.phi_Max_Rev
6. 50/51Q.DIR.I2_Min
It is use to set the minimum operating current setting of direction control element.
7. 50/51Q.DIR.U2_Min
It is use to set the minimum operating voltage setting of direction control element.
8. 50/51Q.DIR.Z2_Comp
The setting should make negative-sequence directional element not mal-operate when a fault
happens in forward direction. Usually it can be set according to the secondary value of capacitive
reactance of the capacitors connected to local line behind VT in series. Please refer to the setting
[50/51G.DIR.Z0_Comp] about setting principle.
9. 50/51Q.En_VTS_Blk
When VT circuit fails, negative-sequence overcurrent protection will be blocked if the setting is set
as "Enabled". Negative-sequence overcurrent protection is not controlled by direction control
10. 50/51Q*.I2_Set
1
𝐼2.2𝑃 = 𝐼3𝑃
2
Where:
For line protection, only when the pickup current of negative-sequence overcurrent element is equal
to 0.5 times the pickup setting of phase overcurrent element fixedly, the relative sensitivity
coefficient of two-phase short circuit is equal to 1. During setting calculation, the coordination of
sensitivity can be carried out only according to the three-phase short circuit and the overcurrent
protection with adjacent lines.
The setting of negative-sequence overcurrent protection can be referred to the setting of phase
overcurrent protection.
Where:
11. 50/51Q*.t_Op
It is used to set the operating time delay for stage * of negative-sequence overcurrent protection.
(*=1 or 2)
It should be set being identical with the time delay of phase overcurrent protection. Because the
fault happens in the same point, the protection with higher sensitivity between phase overcurrent
protection and negative-sequence overcurrent protection will operate in priority.
12. 50/51Q*.t_DropOut
It is used to set the dropout time delay for stage * of negative-sequence overcurrent protection.
(*=1 or 2)
13. 50/51Q*.Opt_Dir
Non_Directional: no direction
14. 50/51Q*.En
15. 50/51Q*.Opt_Trp/Alm
16. 50/51Q*.Opt_Curve
It is used to select the operating characteristics curve for stage * of negative-sequence overcurrent
protection. (*=1 or 2)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
17. 50/51Q*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of negative-sequence overcurrent
protection. (*=1 or 2)
When the operating characteristics curve is selected as definite-time, IEC inverse-time or user-
defined inverse-time characteristics, the dropout characteristic curve can only be selected as
instantaneous dropout characteristics or definite-time dropout characteristics. The alarm signal 3
"Fail_Settings" will be issued and the device will be blocked if inverse-time dropout characteristics
is selected.
When the operating characteristics curve is selected as ANSI inverse-time characteristic, the
dropout characteristic curve can be selected as instantaneous dropout characteristics, definite-time
dropout characteristics and ANSI inverse-time dropout characteristics.
18. 50/51Q*.TMS
It is used to set time multiplier setting for stage * of inverse-time negative-sequence overcurrent
protection. (*=1 or 2)
The setting can be deduced according to the operating time required by inverse-time negative-
sequence overcurrent protection.
19. 50/51Q*.tmin
It is used to set the minimum operating time for stage * of inverse-time negative-sequence
overcurrent protection. (*=1 or 2)
When inverse-time characteristic is selected, if calculated operating time is less than the setting
[50/51Q*.tmin], then the operating time changes to the value of the setting [50/51Q*.tmin]
automatically.
20. 50/51Q*.K
It is used to set the constant "K" for stage * of customized inverse-time negative-sequence
overcurrent protection (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of negative-
sequence overcurrent protection. It is valid only if the setting [50/51Q*.Opt_Curve] is set as
"UserDefine".
21. 50/51Q*.Alpha
It is used to set the constant "α" for stage * of customized inverse-time negative-sequence
overcurrent protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of negative-
sequence overcurrent protection. It is valid only if the setting [50/51Q*.Opt_Curve] is set as
"UserDefine".
22. 50/51Q*.C
It is used to set the constant "C" for stage * of customized inverse-time negative-sequence
overcurrent protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of negative-
sequence overcurrent protection. It is valid only if the setting [50/51Q*.Opt_Curve] is set as
"UserDefine".
3
3.17 Phase Overvoltage Protection (59P)
⚫ LCD
⚫ PCS-Studio
Up
59P1.Opt_Up/Upp
Upp
3P
59P1.Opt_1P/3P
1P
Disabled
59P1.En
Enabled
Trp
59P1.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
59P1.Opt_Curve
UserDefine
InvTime_U
Inst
59P1.Opt_Curve_DropOut
DefTime
Up
59P2.Opt_Up/Upp
Upp
3P
59P2.Opt_1P/3P
1P
Disabled
59P2.En
Enabled
Trp
59P2.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
59P2.Opt_Curve
UserDefine
InvTime_U
59P2.Opt_Curve_DropOut Inst
DefTime
1. 59P*.Opt_Up/Upp
It is used to select the calculation voltage used by stage * of phase overvoltage protection. (*=1 or
2)
2. 59P*.Opt_1P/3P
It is used to select the voltage criterion used by stage * of phase overvoltage protection. (*=1 or 2)
3P: 3-out-of-3 mode, i.e., phase overvoltage protection detects three-phase voltages or three
phase-to-phase voltages.
1P: 1-out-of-3 mode, i.e., phase overvoltage protection detects any phase voltage or phase-to-
phase voltage.
3. 59P*.U_Set
It is used to set the voltage setting for stage * of phase overvoltage protection. (*=1 or 2)
The setting should be set according to the actual isolation requirements of the system equipment.
and the setting [59P*.Opt_Up/Upp].
If the setting [59P*.Opt_Up/Upp] is set as "Upp", then phase-to-phase voltage will be used for
calculation, [59P*.U_Set] should be set as phase-to-phase voltage.
If the setting [59P*.Opt_Up/Upp] is set as "Up", then phase voltage will be used for calculation,
[59P*.U_Set] should be set as phase voltage.
Application example:
If the operating criterion adopts phase-to-phase voltage, Un=110V, 1.3 times Un is assigned for
overvoltage protection. The setting will be given as below:
[59P*.Opt_Up/Upp]=Upp
[59P*.U_Set]=143V
If the operating criterion adopts phase-to-ground voltage, Un=63.5V, 1.3 times Un is assigned for
overvoltage protection. The setting will be given as below:
[59P*.Opt_Up/Upp]=Up
[59P*.U_Set]=82.55V
3
⚫ For inverse-time characteristics
Where:
Umax is the minimum voltage under which the protected equipment can operate for a long term. If
the operating criterion adopts phase-to-phase voltage, the Umax is the phase-to-phase voltage,
otherwise it is the phase-to-ground voltage.
4. 59P*.K_DropOut
It is used to set the dropout coefficient for stage * of phase overvoltage protection. (*=1 or 2)
5. 59P*.t_Op
It is used to set the operating time delay for stage * of phase overvoltage protection. (*=1 or 2)
It shall be set according to the withstanding voltage ability of protected equipment, and its
recommended value is 0.3s~1s.
6. 59P*.t_DropOut
It is used to set the dropout time delay for stage * of phase overvoltage protection. (*=1 or 2)
The setting is valid when definite-time dropout characteristics is selected, and its recommended
value is 0.
7. 59Pi.En
8. 59P*.Opt_Trp/Alm
It is used to enable/disable stage * of phase overvoltage protection operate to trip or alarm (*=1 or
2)
9. 59P*.Opt_Curve
It is used to select the operating characteristics curve for stage * of phase overvoltage protection.
(*=1 or 2)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
10. 59P*.Opt_Curve_DropOut
It is used to set the dropout characteristics curve for stage * of phase overvoltage protection (*=1
or 2)
11. 59P*.TMS
It is used to set time multiplier setting for stage * of inverse-time phase overvoltage protection. (*=1
or 2)
The setting can be deduced according to the operating time required by inverse-time phase
overvoltage protection.
12. 59P*.tmin
It is used to set the minimum operating time for stage * of inverse-time phase overvoltage protection.
(*=1 or 2)
When inverse-time characteristics is selected, if calculated operating time is less than the setting
[59P*.tmin], then the operating time changes to the setting [59P*.tmin] automatically. Its
recommended value is 0.02s.
13. 59P*.K
It is used to set the constant “K” for stage * of customized inverse-time phase overvoltage protection.
(*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse overvoltage
protection. It is valid only if the setting [59P*.Opt_Curve] is set as "UserDefine".
14. 59P*.Alpha
It is used to set the constant “C” for stage * of customized inverse-time phase overvoltage protection.
(*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse overvoltage
protection. It is valid only if the setting [59P*.Opt_Curve] is set as "UserDefine".
15. 59P*.C
It is used to set the constant “α” for stage i of customized inverse-time phase overvoltage protection.
(*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse overvoltage 3
protection. It is valid only if the setting [59P*.Opt_Curve] is set as "UserDefine".
⚫ LCD
⚫ PCS-Studio
Disabled
59G1.En
Enabled
Trp
59G1.Opt_Trp/Alm
Alm
Disabled
59G2.En
Enabled
Trp
59G2.Opt_Trp/Alm
Alm
3
3.18.3 Calculation Principle
1. 59G*.3U0_Set
It is used to set the voltage setting for stage * of residual overvoltage protection. (*=1 or 2)
It shall be greater than maximum unbalanced residual voltage under normal conditions.
The residual overvoltage protection is generally used for alarm. It shall be greater than maximum
unbalanced residual voltage under normal conditions.
0.5 × 𝑈2𝑛
[59𝐺 ∗ .3𝑈0_𝑆𝑒𝑡] =
1.732
2 × 𝑈2𝑛
[59𝐺 ∗ .3𝑈0_𝑆𝑒𝑡] =
1.732
1.2 × 𝑈2𝑛
[59𝐺 ∗ .3𝑈0_𝑆𝑒𝑡] =
1.732
2. 59G*.K_DropOut
It is used to set the dropout coefficient for stage * of residual overvoltage protection. (*=1 or 2)
3. 59G*.t_Op
It is used to set the operating time delay for stage * of residual overvoltage protection. (*=1 or 2)
It shall be set to keep residual overvotlage protection away from the influence of transient
characteristics and its recommended value is 0.3s~0.5s.
4. 59G*.t_DropOut
It is used to set the dropout time delay for stage * of residual overvoltage protection. (*=1 or 2)
5. 59G*.En
6. 59G*.Opt_Trp/Alm
It is used to enable/disable stage * of residual overvoltage protection operate to trip or alarm. (*=1
or 2)
3
Trp: for tripping purpose
⚫ LCD
⚫ PCS-Studio
Disabled
59Q1.En
Enabled
Trp
59Q1.Opt_Trp/Alm
Alm
Disabled
59Q2.En
Enabled
Trp
3 59Q2.Opt_Trp/Alm
Alm
1. 59Q*.U2_Set
It is used to set the voltage setting for stage * of negative-sequence overvoltage protection. (i=1 or
2)
The setting should be set according to negative-sequence voltage. The calculation principle is as
below.
𝐾𝑟𝑒𝑙 × 𝑈2𝑛
[59𝑄 ∗. 𝑈2_𝑆𝑒𝑡] =
1.732
Where:
Krel needs to be set according to the specific application. If the negative-sequence overvoltage
protection is used to release the relevant current protection when detecting the reverse phase
sequence connection or the asymmetric fault, the setting can be not very sensitive, and Krel is
recommended to be set as 0.1.
If the negative-sequence overvoltage protection is used to detect the unbalance of the rotating
motor and prevent the motor from overheating and burning out, Krel is recommended to be set as
0.03.
Application example:
0.1 × 100
[59𝑄 ∗. 𝑈2𝑆𝑒𝑡 ] = = 5.78𝑉
1.732
In addition, the setting should be more thant the maximum unbalance negative-sequence voltage
during normal operation.
2. 59Q*.K_DropOut
It is used to set the dropout coefficient for stage * of negative-sequence overvoltage protection.
(*=1 or 2)
The setting can be appropriately reduced to prevent frequent jitter if the negative-sequence voltage
setting is too small.
3. 59Q*.t_Op
It is used to set the operating time delay for stage * of negative-sequence overvoltage protection.
(*=1 or 2) 3
The time delay can be appropriately reduced if the operating threshold of negative-sequence
voltage is large, for example, 1s.
If the negative-sequence voltage setting is small, it is recommended to set this setting as a larger
value, for example, 5s.
4. 59Q*.t_DropOut
It is used to set the dropout time delay for stage * of negative-sequence overvoltage protection.
(*=1 or 2)
5. 59Q*.En
6. 59Q*.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Up
27P1.Opt_Up/Upp
Upp
3P
3 27P1.Opt_1P/3P
1P
None
Curr
27P1.Opt_LogicMode CBPos
CurrOrCBPos
CurrAndCBPos
Disabled
27P1.En_VTS_Blk
Enabled
Disabled
27P1.En
Enabled
Trp
27P1.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
27P1.Opt_Curve
UserDefine
InvTime_U
Inst
27P1.Opt_Curve_DropOut
DefTime
Up
27P2.Opt_Up/Upp
Upp
3
3P
27P2.Opt_1P/3P
1P
None
Curr
27P2.Opt_LogicMode CBPos
CurrOrCBPos
CurrAndCBPos
Disabled
27P2.En_VTS_Blk
Enabled
Disabled
27P2.En
Enabled
Trp
27P2.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
27P2.Opt_Curve
UserDefine
InvTime_U
Inst
27P2.Opt_Curve_DropOut
DefTime
1. 27P*.Opt_Up/Upp
It is used to select the calculation voltage used by stage * of phase undervoltage protection. (*=1
or 2)
2. 27P*.Opt_1P/3P
It is used to select the voltage criterion used by stage * of phase undervoltage protection. (*=1 or
2)
3P: 3-out-of-3 mode, i.e., phase undervoltage protection detects three-phase voltages or three
phase-to-phase voltages.
1P: 1-out-of-3 mode, i.e., phase undervoltage protection detects any phase voltage or phase-to-
phase voltage.
3. 27P*.Opt_LogicMode
The option of auxiliary criterion mode for stage * of phase undervoltage protection (*=1 or 2)
None: no check
When the load current is relatively fixed and is larger than 0.04In, the current criterion is
recommended, such as the capacitor and reactor load. Otherwise, the breaker position criterion is
recommended.
When the breaker position can be acquired, and the load current is also larger than 0.04In,
comprehensive criterion can also be used.
When the circuit breaker of the incoming line has been tripped and the busbar loses voltage, phase
undervoltage protection is still desired to operate at this time, so the breaker position criterion needs
to be selected.
4. 27P*.U_Set
It is used to set the voltage setting for stage * of phase undervoltage protection. (*=1 or 2)
The setting should be set according to the actual stability level of power system, but it should ensure
sensitive enough to the fault at the end of the line and not be greater than the minimum operation
voltage under normal conditions.
3
The setting should also be set according to the setting [27P*.Opt_Up/Upp].
If the setting [27P*.Opt_Up/Upp] is set as "Upp", then phase-to-phase voltage will be used for
calculation, [27P*.U_Set] should be set as phase-to-phase voltage.
If the setting [27Pi.Opt_Up/Upp] is set as "Up", then phase voltage will be used for calculation,
[27P*.U_Set] should be set as phase voltage.
Application example:
If the operating criterion adopts phase-to-phase voltage, Un=110V, 0.7 times Un is assigned for
undervoltage protection. The setting will be given as below:
[27P*.Opt_Up/Upp]=Upp
[27P*.U_Set]=77V
If the operating criterion adopts phase-to-ground voltage, Un=63.5V, 0.7 times Un is assigned for
undervoltage protection. The setting will be given as below:
[27P*.Opt_Up/Upp]=Up
[27P*.U_Set]=44.45V
5. 27P*.K_DropOut
It is used to set the dropout coefficient for stage * of phase undervoltage protection. (*=1 or 2)
6. 27P*.t_Op
It is used to set the operating time delay for stage * of phase undervoltage protection. (*=1 or 2)
7. 27P*.t_DropOut
It is used to set the dropout time delay for stage * of phase undervoltage protection. (*=1 or 2)
This setting is valid when definite-time drop-out characteristic is selected, and its recommended
value is 0.
8. 27P*.En_VTS_Blk
When the setting [27P*.En_VTS_Blk] is set as "Enabled", phase undervoltage protection will be
blocked if VT circuit fails.
9. 27P*.En
It is used to enable/disable stage * of phase undervoltage protection operate to trip or alarm. (*=1
or 2)
11. 27P*.Opt_Curve
It is used to select the operating characteristics curve for stage * of phase undervoltage protection.
(*=1 or 2)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
12. 27P*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of phase undervoltage protection.
(*=1 or 2)
13. 27P*.TMS
It is used to set time multiplier setting for stage * of inverse-time phase undervoltage protection.
(*=1 or 2)
The setting can be deduced according to the operating time required by inverse-time phase
undervoltage protection.
14. 27P*.tmin
It is used to set the minimum operating time for stage * of inverse-time phase undervoltage
protection. (*=1 or 2)
When inverse-time characteristics is selected, if calculated operating time is less than the setting
[27P*.tmin], then the operating time changes to the setting [27P*.tmin] automatically. Its
recommended value is 0.03s.
15. 27P*.K
It is used to set the constant “K” for stage * of customized inverse-time phase undervoltage
protection. (*=1 or 2)
3
The setting shall be set according to the expected inverse-time characteristics of pahse
undervoltage protection. It is valid only if the setting [27P*.Opt_Curve] is set as "UserDefine".
16. 27P*.Alpha
It is used to set the constant “α” for stage * of customized inverse-time phase undervoltage
protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
undervoltage protection. It is valid only if the setting [27P*.Opt_Curve] is set as "UserDefine".
17. 27P*.C
It is used to set the constant “C” for stage * of customized inverse-time phase undervoltage
protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
undervoltage protection. It is valid only if the setting [27P*.Opt_Curve] is set as "UserDefine".
⚫ LCD
⚫ PCS-Studio
Disabled
81O1.En
Enabled
Trp
81O1.Opt_Trp/Alm
Alm
3 81O2.f_Set 50.000~65.000 0.001 Hz
Disabled
81O2.En
Enabled
Trp
81O2.Opt_Trp/Alm
Alm
Disabled
81O3.En
Enabled
Trp
81O3.Opt_Trp/Alm
Alm
Disabled
81O4.En
Enabled
Trp
81O4.Opt_Trp/Alm
Alm
1. 81.Upp_Blk
It is used to set the phase-to-phase voltage setting used to block frequency protection (including
overfrequency protection, underfrequency protection and frequency rate-of-change protection).
When any phase-to-phase voltage is smaller than the setting [81.Upp_Blk], the frequency
protection will be blocked. It is a general setting and shared by overfrequency protection,
underfrequency protection and frequency rate-of-change protection.
The setting should be set according to the phase-to-phase voltage. Its recommended value is
0.7Unn (Unn is rated phase-to-phase voltage).
2. 81O*.f_Set
It is used to set the frequency setting for stage * of overfrequency protection. (*=1~4)
All stages can be set based on the same graduation. After rejecting some power supplies and each
stage operating, the system frequency should be restored near rated frequency. Because
compound mode of generators (hydroelectric, thermal power, nuclear power with different capacity
3
and proportion, different adaptability to abnormal frequency), system structure and operation mode
are different in different power system, they should be set according to system frequency and
stability control strategy.
3. 81O*.t_Op
It is used to set the time delay for stage * of overfrequency protection. (*=1~4)
4. 81O*.En
5. 81O*.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Disabled
81U1.En
Enabled
Trp
3 81U1.Opt_Trp/Alm
Alm
Disabled
81U2.En
Enabled
Trp
81U2.Opt_Trp/Alm
Alm
Disabled
81U3.En
Enabled
Trp
81U3.Opt_Trp/Alm
Alm
Disabled
81U4.En
Enabled
Trp
81U4.Opt_Trp/Alm
Alm
2. 81U*.f_Set
It is used to set the frequency setting for stage * of underfrequency protection. (*=1~6)
All stages can adopt cascade connection, and small graduation can be set among them, for
example, taking 0.2Hz. Selecting one special stage, it can avoid system frequency always keeping
in a certain frequency. When some loads are shed after other stages of underfrequency protection
operate to shed major loads and make system frequency restore to normal value.
3. 81U*.t_Op
It is used to set the time delay for stage * of underfrequency protection. (*=1~6)
5. 81U*.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Disabled
81R1.En
Enabled
Trp
81R1.Opt_Trp/Alm
Alm
Disabled
81R2.En
Enabled
Trp
81R2.Opt_Trp/Alm
Alm
Disabled
81R3.En
Enabled
Trp
81R3.Opt_Trp/Alm
Alm
Disabled
81R4.En
Enabled
Trp
81R4.Opt_Trp/Alm
Alm
2. 81R*.df/dt_Set
It is used to set the frequency rate-of-change setting for stage * of frequency rate-of-change
protection. (*=1~6)
If the system frequency quickly decreases due to large active power shortage after the system fault,
it is required to remove the overload line as soon as possible, to avoid frequency collapse, and its
recommended value is -0.8~-2Hz/s.
If the system frequency quickly increases due to surplus system power (more than 20%), the
generator rejection should be executed, to avoid the frequency increasing, and its recommended
value is 0.8~2Hz/s.
3. 81R*.t_Op
3
It is used to set the time delay for stage * of frequency rate-of-change protection. (*=1~6)
4. 81R*.f_Pkp
It is used to set the pickup frequency setting for stage * of frequency rate-of-change protection.
(*=1~6)
5. 81R*.En
6. 81R*.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Disabled
32R1.En
Enabled
Trp
32R1.Opt_Trp/Alm
Alm
Disabled
32R2.En
Enabled
Trp
32R2.Opt_Trp/Alm
Alm
1. 32R*.U1_VCE
It is used to set the positive-sequence voltage setting which is used to block stage * of reverse
power protection. (*=1or 2)
2. 32R*.I1_CCE
It is used to set the positive-sequence current setting which is used to block stage * of reverse
power protection. (*=1or 2)
3. 32R*.U2_VCE
It is used to set the negative-sequence voltage setting which is used to block stage * of reverse
power protection. (*=1or 2)
4. 32R*.P_Set
It is used to set the power setting for stage * of reverse power protection. (*=1or 2)
Generally, it should be set according to the minimum measurable power under reverse power
conditions.
3
The recommended value is 0.01 p.u.~0.03 p.u..
5. 32R*.t_Op
The operating time delay for stage * of reverse power protection (*=1or 2)
6. 32R*.En
7. 32R*.Opt_Trp/Alm
It is used to enable/disable stage * of reverse power protection operate to trip or alarm. (*=1 or 2)
⚫ LCD
⚫ PCS-Studio
Disabled
49P1.En_Trp
Enabled
Disabled
49P1.En_Alm
Enabled
Maintain
49P1.Opt_Accu_CurreLos
Dissipate
Disabled
49P2.En_Trp
Enabled
Disabled
49P2.En_Alm
Enabled
Maintain
49P2.Opt_Accu_CurreLos
Dissipate
It is generally recommended to be set equal to the rated current of the protected equipment.
2. 49P*.K_Trp
It is used to set the tripping factor of thermal capacity for stage * of thermal overload protection.
3. 49P*.K_Alm
It is used to set the alarm factor of thermal capacity for stage * of thermal overload protection.
It is used to set the time constant of the thermal model for stage * of thermal overload protection.
5. 49P*.K_T_Diff
It is used to set the convertor coefficient from the current to the temperature for stage * of thermal
overload protection.
It is used to calculate the temperature difference between transformer windings and oil, which
should be provided by transformer manufacturers.
6. 49P*.Alpha_Cold
It is used to set the cooling mode for stage * of thermal overload protection. Usually, for different
cooling mode:
For the thermal overload protection using method 1, its recommended value is 2.
For the thermal overload protection using method 2, its recommended value is 1.6 for natural
cooling and 2 for forced cooling based on different cooling conditions.
7. 49P*.C_Disspt
It is used to set the time constant of heat dissipation for stage * of thermal overload protection.
When the equivalent heating current is lower than 0.04In, the thermal time constant adopts the
value of [49Pi.Tau]×[49Pi.C_Disspt]. The time constants of heat accumulation and heat dissipation
are different in the case. When the setting is set as "1", the same time constant is used for heat
accumulation and heat dissipation.
8. 49P*.En_Trp
9. 49P*.En_Alm
10. 49P*.Opt_Accu_CurreLos
⚫ LCD
⚫ PCS-Studio
1P
37.Opt_1P/3P
3P
None
Curr
37.Opt_LogicMode CBPos
CurrOrCBPos
CurrAndCBPos
Disabled
37.En
Enabled
Trp
37.Opt_Trp/Alm
Alm
1. 37.I_Set
3
It is used to set the current setting of undercurrent protection.
The setting should ensure that undercurrent protection can reliably operate after the bus connected
with the capacitor loses the voltage, and undercurrent protection can reliably drop off after the bus
voltage returns to normal
2. 37.t_Op
It should coordinate with the operating time of backup protection of outgoing line at local end.
[37. 𝑡_𝑂𝑝] = 𝑡 ′ + ∆𝑡
Where:
𝑡 ′ is the operating time of backup protection which undercurrent protection need to coordinate
with.
3. 37.Opt_1P/3P
If the setting is set as "1P", undercurrent protection will discriminate any phase current with the
current criterion. If the setting is set as "3P", undercurrent protection will discriminate three-phases
currents with the current criterion.
4. 37.Opt_LogicMode
None: no check
When the load current is relatively constant and is larger than 0.04In, the setting is recommende
3 to set as "Curr", such as the capacitor and reactor load. Otherwise, it is recommended to set as
"CBPos".
When the CB position can be acquired, and the load current is also larger than 0.04In, the setting
is recommende to set as "CurrAndCBPos".
When the circuit breaker of incoming line has been tripped and the busbar loses voltage,
undercurrent protection is still desired to operate at this time, the setting is recommended to set as
"CBPos".
If the CB position cannot be acquired, the setting is recommended to set as "None". However, the
other method should be adopted to ensure that undercurrent protection will not always operate
before the equipment is put into operation because the circuit breaker is not closed and there is no
current at this time, and undercurrent protection can reliably drop off after the abnormal condition
disappears.
5. 37.En
6. 37.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Disabled
CBx.50BF.En
Enabled
Disabled
CBx.50BF.En_ReTrp
Enabled
Disabled
CBx.50BF.En_t1
Enabled
Disabled
CBx.50BF.En_t2
Enabled
Disabled
CBx.50BF.En_3I0_1P
Enabled
Disabled
CBx.50BF.En_Ip
Enabled
Disabled
CBx.50BF.En_3I0_3P
Enabled
Disabled
CBx.50BF.En_I2_3P
Enabled
Disabled
CBx.50BF.En_CB_Ctrl
Enabled
Disabled
CBx.50BF.En_Alm_Init
Enabled
None
Curr
CBx.50BF.Opt_LogicMode CBPos
CurrAndCBPos
Disabled
CBx.50BF.En_InTrp_Init
Enabled
1. CBx.50BF.I_Set
It is used to set the phase current setting of detecting breaker failure protection.
The measured phase current is used to detect the circuit breaker failure. The setting should can
3 detect the fault with small fault current. It could be chosen in accordance with the most sensitive
protection function that initiate the breaker failure protection.
2. CBx.50BF.3I0_Set
It is used to set the zero-sequence current setting of detecting breaker failure protection.
In the grouded systems via high impedance, the residual current is normally much smaller than the
short-circuit currents for the single-phase earth fault. In order to reliably detect the circuit breaker
failure under the single-phase earth fault, it is necessary to add the zero-sequence current detection
by the setting [CBx.50BF.En_3I0_1P] (set as "Enabled"). At this time, the phase current setting
[CBx.50BF.I_Set] could be set more sensitive.
Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, zero-sequence current
criterion and negative-sequence current criterion are provided in addition to the phase overcurrent
element for breaker failure protection initiated by input signal [CBx.50BF.ExTrp3P] from external
tripping. They can be enabled or disabled by the settings [CBx.50BF.En_3I0_3P] and
[CBx.50BF.En_I2_3P] respectively.
The setting [CBx.50BF.3I0_Set] shall be greater than maximum zero-sequence unbalance current
(3I0) under normal operation condition.
3. CBx.50BF.I2_Set
It is used to set the negative-sequence current setting of detecting breaker failure protection.
4. CBx.50BF.t_ReTrp
The setting defines the time delay of re-tripping for breaker failure protection, generally set as
5ms~50ms.
5. CBx.50BF.t1_Op
It is used to set the time delay for the first stage of breaker failure protection.
Breaker failure protection will send three-phase tripping command to trip local circuit breaker when
the time delay of [CBx.50BF.t1_Op] is expired. The setting [CBx.50BF.t1_Op] is set as short as
possible on the premise that the selectivity of breaker failure protection is warrantable.
[CBx.50BF.t1_Op]=t0+tB+Δt
Where:
tB is the drop off time of the operation element, generally taken as 0.02~0.04s.
3
Δt is safety margin time, generally taken as 0.03s.
Normally, it is used to trip local circuit breaker again before the second stage of breaker failure
protection operating in case that the local circuit breaker could open to prevent to trip the adjacent
circuit breakers.
6. CBx.50BF.t2_Op
It is used to set the time delay for the second stage of breaker failure protection.
Breaker failure protection will send three-phase tripping command to trip adjacent circuit breakers
when the time delay of [CBx.50BF.t2_Op] is expired. The setting [CBx.50BF.t2_Op] is set as short
as possible on the premise that the selectivity of breaker failure protection is warrantable and
undesired operation must be avoided. Besides, the setting should be greater than the setting
[CBx.50BF.t1_Op] with safety margin.
[CBx.50BF.t2_Op]=t0+tB+Δt
Where:
tB is the drop off time of the operation element, generally taken as 0.02~0.04s.
7. CBx.50BF.En
8. CBx.50BF.En_ReTrp
When the setting is set as "Enabled", the instantaneous re-tripping function is in service.
After receiving tripping signal from the device and the corresponding current criterion or CB position
3 criterion is met, then the re-trip command will be issued to trip local circuit breaker.
9. CBx.50BF.En_t1
10. CBx.50BF.En_t2
11. CBx.50BF.En_3I0_1P
12. CBx.50BF.En_Ip
It is used to enable/disable phase overcurrent criterion of breaker failure protection via external
three-phases initiating signal "CBx.50BF.ExTrp3P".
When the seting is set as "Enabled", the phase current criterion via external three-phases initiating
signal "CBx.50BF.ExTrp3P" is valid.
13. CBx.50BF.En_3I0_3P
14. CBx.50BF.En_I2_3P
15. CBx.50BF.En_CB_Ctrl
It is used to enable/disable breaker failure protection be initiated by CB open position via external
three-phases initiating signal "CBx.50BF.ExTrp3P".
For some special protection (for example, mechanical protection or voltage protection), the fault
current maybe is too small to meet the current criterion when they operate. In order to make breaker
failure protection can also operate under the above situation, CB open position is used instead of
the current criterion. The precondition is that binary input signal [CBx.50BF.ExTrp_WOI] should be
assigned by external trip signal.
16. CBx.50BF.En_Alm_Init
It is used to enable/disable the supervision of binary input initiating signal of breaker failure
protection. If the setting is set as "Enabled", and the initiating status of the binary input signal
maintains more than 10s, then the binary input initiating signal will be considered as invalid and an
alarm "CBx.50BF.Alm_Int" will be issued. If it is set as "Disabled", then the binary input signal will 3
not be supervised.
17. CBx.50BF.Opt_LogicMode
None: no check
18. CBx.50BF.En_InTrp_Init
⚫ LCD
⚫ PCS-Studio
Disabled
87STB.En
Enabled
Disabled
87STB.En_Diff_Alm
Enabled
3 Disabled
87STB.En_CTS_Blk
Enabled
It shall be greater than the maximal unbalance current under normal rated load, i.e.,
[87STB.I_Pkp]=KRel×(Ker+Δm)×In
Where:
Ker is the ratio errors of CT (k=0.03X2 for class 10P, k=0.01X2 for clase 5P and TP).
Δm is the error caused by the difference between CT ratios at two sides, and 0.05 is recommended.
This setting should ensure sensitive enough for internal fault with the minimum operation mode and
the sensitivity coefficient is not smaller than 1.5.
Generally, the fault current for stub zone fault is high, the recommended setting value is not less
than 0.5In.
2. 87STB.I_Alm
The setting is used to detect the abnormal current condition, such as CT circuit fail, it should be
greater than the maximal unbalance current under normal load operation condition.
3. 87STB.Slope
The setting is the slope of current differential protection operate-restrain characteristic. This setting
should be given according to the system condition and its application.
4. 87STB.t_Op
Generally, this setting is set as zero. In special cases, it can be set with additional time delay, for
example for reverse interlocking.
5. 87STB.En
6. 87STB.En_Diff_Alm
3
It is used to enable/disable differential current alarm function.
7. 87STB.En_CTS_Blk
If the alarm signal of differential current abnormality [87STB.Alm_Diff] is issued, stub differential
protection will be blocked if [87STB.En_CTS_Blk] is set as "Enabled"
⚫ LCD
⚫ PCS-Studio
Disabled
CBx.50DZ.En
Enabled
Disabled
CBx.50DZ.En_Alm_Init
Enabled
1. CBx.50DZ.I_Set
2. CBx.50DZ.t_Op
4. CBx.50DZ.En_Alm_Init
It is used to enable/disable abnormality check of initiating signal for dead zone protection.
⚫ LCD
⚫ PCS-Studio
Disabled
46BC.En
Enabled
Trp
46BC.Opt_Trp/Alm
Alm
1. 46BC.I_Min
2. 46BC.I2/I1_Set
The network of single-phase broken condition is similar to that of two-phases earthing fault, 3
positive-sequence, negative-sequence and zero-sequence network is connected in parallel,
I2/I1=Z0/(Z0+Z2), generally, zero-sequence impedance is larger than positive-sequence
impedance, i.e., I2/I1>0.5. The network of two-phases broken condition is similar to that of single-
phase earthing fault, positive-sequence, negative-sequence and zero-sequence network is
connected in series, so I2/I1=1. Hence, broken conductor protection based on the ratio of negative-
sequence current to positive-sequence current can detect the broken-conductor fault.
3. 46BC.t_Op
4. 46BC.En
5. 46BC.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Disabled
3 CBx.62PD.En
Enabled
Disabled
CBx.62PD.En_3I0/I2_Ctrl
Enabled
Disabled
CBx.62PD.En_Init_Alm
Enabled
1. CBx.62PD.3I0_Set
In order to improve the reliability of pole discrepancy protection, zero-sequence current element
can be selected as auxiliary criterion.
2. CBx.62PD.I2_Set
3. CBx.62PD.t_Op
4. CBx.62PD.En
5. CBx.62PD.En_3I0/I2_Ctrl
It is used to enable/disable residual current criterion and negative-sequence current criterion for
If the setting is set as "Enabled" pole discrepancy protection can operate only when the zero-
sequence current element or negative-sequence current element meet the criterion.
6. CBx.62PD.En_Alm_Init
It is used to enable/disable abnormality check of initiating signal for pole discrepancy protection.
⚫ PCS-Studio
Disabled
CBx.50F.En -
Enabled
Disabled
CBx.50F.En_Ip -
Enabled
Disabled
CBx.50F.En_3I0 -
Enabled
Disabled
CBx.50F.En_I2 -
Enabled
1. CBx.50F.I_Set
The setting should be larger than the load current after the generator paralleling or before the
generator separation, while keeping a certain margin to ensure reliability.
2. CBx.50F.3I0_Set
3 The setting shall be greater than maximum zero-sequence unbalance current (3I0) under normal
operation condition.
3. CBx.50F.I2_Set
The setting shall be greater than maximum negative-sequence unbalance current (I2) under normal
operation condition.
4. CBx.50F.t1_Op
The stage 1 of flashover protection is usually used to trip the circuit breaker or field suppression.
The setting shall be greater than the three-phase discrpancy time when the circuit breaker is closed
or opened, and keeping a certain margin, its recommended value is 0.1s.
5. CBx.50F.t2_Op
The stage 2 of flashover protection is usually used to initiate breaker failure protection.
The setting should be greater than the setting [CBx.50F.t1_Op], and keeping a certain margin, its
recommended value is 0.15s
6. CBx.50F.En
7. CBx.50F.En_Ip
When flashover protection adopts phase current criterion, the settings should be set as "Enabled".
The circuit breaker flashover is generally single-phase or two-phase flashover, three-phase
flashover is very rare, so the setting is generally set as "Disabled".
8. CBx.50F.En_3I0
When flashover protection adopts residual current criterion, the settings should be set as "Enabled".
9. CBx.50F.En_I2
When flashover protection adopts negative-sequence current criterion, the settings should be set
as "Enabled".
⚫ LCD
⚫ PCS-Studio
Disabled
TT.En
Enabled
Disabled
TT.En_FD_Ctrl
Enabled
Disabled
TT.En_BlkAR
Enabled
Disabled
TT.En_CB_Ctrl
Enabled
10. TT.t_Op
11. TT.En
12. TT.En_FD_Ctrl
If the setting is set as "Enabled", transfer trip can operate only when the device picks up.
13. TT.En_BlkAR
If the setting is set as "Enabled", transfer trip can operate only when the circuit breaker of any
phase is in closed position.
⚫ LCD
⚫ PCS-Studio
Disabled
En_MPF_Blk_AR
Enabled
Disabled
En_3PF_Blk_AR
Enabled
Disabled
Line.En_PhSFail
Enabled
Line.En_PhSF_Blk_AR Disabled
Enabled
Disabled
CBx.En_Trp3P
Enabled
1. En_MPF_Blk_AR
3
It is used to enable/disable auto-reclosing blocked when multi-phase fault happens.
2. En_3PF_Blk_AR
3. Line.t_PhSFail
It is used to set the time delay of confirming faulty phase selection failure.
4. Line.En_PhSFail
5. Line.En_PhSF_Blk_AR
6. t_Dwell_Trp
The tripping contact shall drop off when the faulty current disappears or the protection element
drops off. It ensures that the tripping pulse will be kept as same as the setting [t_Dwell_Trp] at least
after the tripping signal is issued.
7. CBx.En_Trp3P
It is used to enable/disable three-phase tripping mode of circuit breaker No.x for any fault conditions.
⚫ LCD
⚫ PCS-Studio
Config
CBx.79.Opt_RSYN_ValidMode
Setting
3 Disabled
CBx.79.En_SynChk
Enabled
Disabled
CBx.79.En_SynDd_RefDd
Enabled
Disabled
CBx.79.En_SynLv_RefDd
Enabled
Disabled
CBx.79.En_SynDd_RefLv
Enabled
Disabled
CBx.79.En_NoChk
Enabled
CBx.79.Num 1~4 1
Disabled
CBx.79.En_AddDly
Enabled
3
Disabled
CBx.79.En_FailCheck
Enabled
Disabled
CBx.79.En_PDF_Blk
Enabled
Disabled
CBx.79.En_CutPulse
Enabled
Disabled
CBx.79.En
Enabled
Setting
CBx.79.Opt_Enable
Setting&Config
Disabled
CBx.79.En_CBInit
Enabled
None
CBx.79.Opt_Priority High
Low
Config
CBx.79.Opt_ValidMode
Setting
Disabled
CBx.79.En_1P
Enabled
Disabled
CBx.79.En_3P
Enabled
Disabled
CBx.79.En_1P/3P
Enabled
1. CBx.79.Opt_RSYN_ValidMode
It is used to select the control source of synchronism check mode for AR.
3 Synchronism check mode can be selected by external signal via binary inputs or internal logic
settings. If the setting [CBx.79.Opt_RSYN_ValidMode] set as "Setting", synchronism check mode
is determined by the internal logic settings. If the settings [CBx.79.Opt_RSYN_ValidMode] set as
"Config", AR mode is determined by the input signals
CBx.79.Sel_SynChk
CBx.79.Sel_SynDd_RefDd
CBx.79.Sel_SynLv_RefDd
CBx.79.Sel_SynDd_RefLv
CBx.79.Sel_NoChk
If the settings [CBx.79.Opt_RSYN_ValidMode] set as "Config", and there is on binary input was
energized, then the synchronism check mode for AR is abnormal and the alarm signal will be issued.
CBx.79.En_SynChk
CBx.79.En_SynDd_RefDd
CBx.79.En_SynLv_RefDd
CBx.79.En_SynDd_RefLv
CBx.79.En_NoChk
If the settings [CBx.79.Opt_RSYN_ValidMode] set as "Setting", and all corresponding settings are
set as "Disabled", then the synchronism check mode for AR is abnormal and the alarm signal will
be issued.
2. CBx.79.En_SynChk
3. CBx.79.En_SynDd_RefDd
It is used to enable/disable dead synchronization voltage and dead reference voltage check for AR.
4. CBx.79.En_SynLv_RefDd.
It is used to enable/disable live synchronization voltage and dead reference voltage check for AR.
5. CBx.79.En_SynDd_RefLv
It is used to enable/disable dead synchronization voltage and live reference voltage check for AR.
7. CBx.79.Num
The AR function could be set as one-shot or multi-shot. Through the setting [CBx.79.N_Rcls], the
maximum number of reclosing attempts can be set up to 4 times. Generally, only one-shot AR is
selected.
The table below shows the number of reclose attempts with respect to the settings and AR modes.
1 1 0 0 1 1 1
2 1 0 0 2 1 2
3 1 0 0 3 1 3
4 1 0 0 4 1 4
8. CBx.79.t_Dd_1PS1
The setting should be set according to system stability requirement, meanwhile, arc-extinguishing
of instantaneous fault and insulation recovery ability should also be considered. Generally, this
setting is greater than 0.5s, 1.0s is recommended.
9. CBx.79.t_Dd_3PS1
11. CBx.79.t_Dd_3PS3
12. CBx.79.t_Dd_3PS4
13. CBx.79.t_CBClsd
It is used to set the waiting time needed by the circuit-breaker to obtain the AR ready state after the
circuit breaker is closed.
It is the minimum time delay for circuit breaker in closed position before AR gets ready. The duration
of the circuit breaker in closed position before fault occurrence is not less than the setting
[CBx.79.t_CBClsd] for a successful reclosing.
14. CBx.79.t_CBReady
It is used to set time delay to wait for CB healthy, and begin to timing when the input signal
[CBx.79.CB_Healthy] is de-energized and if it is not energized within this time delay, AR will be
blocked.
The input signal [CBx.79.CB_Healthy] must be energized before auto-reclosure gets ready.
Because most circuit breakers can finish one complete process: open-closed-open, it is necessary
that circuit breaker has enough energy before reclosing. When the dead time delay of AR is
exhausted, if the input signal [CBx.79.CB_Healthy] is still not energized within time delay
[CBx.79.t_CBReady], AR will be blocked. If this function is not required, the input signal
[CBx.79.CB_Healthy] can be not to configure, and its logical state will be thought as "1" by default.
15. CBx.79.t_Wait_Chk
The setting is the maximum allowable time used for synchronism check. It is valid only if the
synchronism check mode is selected. If the synchronism check condition is not met after the delay
time elapsed, the synchronism check failed and the auto-reclosing will be blocked.
The reset time of circuit breaker after auto-reclosing operation. With the assignment of the close
command, the automatic reclosing function goes into the reclaim time state. During this time, it is
decided if the current reclosing cycle was successful or not.
⚫ If during the reclaim time no further tripping occurs, the currently running automatic reclosing
cycle was successful.
⚫ If during the reclaim time another tripping occurred, the currently running automatic reclosing
cycle was not successful. If other automatic reclosing cycles are permitted, one of these cycles
will be used to continue the process. In contrast, if the currently executed cycle was the last
permissible cycle, the automatic reclosing process will end and be reported as unsuccessful.
17. CBx.79.t_DDO_Blk
It is used to set dropout time delay of blocking AR, when blocking signal for AR disappears, AR
blocking condition drops out after this time delay.
AR will be blocked immediately once the blocking condition of AR appears, and the blocking
condition of AR will drop off with a time delay [CBx.79.t_DDO_BlkAR] after blocking signal
disappears.
18. CBx.79.t_AddDly
AR will be initiated by the tripping of the device. In the process of channel abnormality, an internal
fault occurs on the transmission line, backup protection at both ends of line will operate to trip the
circuit breaker at each end. The operation time of backup protection at both ends of the line is
possibly inconsist, while the time delay of AR needs to consider the arc-extinguishing and insulation
recovery ability for transient fault, so the time delay of AR shall be considered comprehensively
according to the operation time of the device at both ends. When the communication channel of
main protection is abnormal (input signal [CBx.79.PLC_Lost] is energized), and the setting
[CBx.79.En_AddDly] is set as "Enabled", then the dead time delay of AR shall be equal to the
original dead time delay of AR plus the extra time delay [CBx.79.t_AddDly], so as to ensure the
recovery of insulation intensity of fault point when reclosing after transient fault. This extra time
delay [CBx.79.t_AddDly] is only valid for the first shot AR. This time should consider the operation
time difference between both sides.
19. CBx.79.t_WaitMaster
It is used to set maximum wait time for reclosing permissive signal from master AR.
3 The setting defines the maximum wait time for reclosing permissive signal from master AR. To
prevent further impacts by slave AR reclosing, the output signal "CBx.79.WaitToSlave" of master
AR is usually configured to the signal "CBx.79.WaitMaster" of slave AR. Slave AR is permissible to
reclosing only if master AR is reclosed successfully.
This setting should cooperate with the setting [CBx.79.Opt_Priority]. It is invalid if the setting
[CBx.79.Opt_Priority] is set as "None".
20. CBx.79.t_SecFault
It is used to set the time delay of discriminating another fault in the AR inprogress period. The timer
starts count after 1-pole AR initiated, if another fault happens during this time delay, 3-pole AR will
be initiated. If another fault happens after that time, It will be recognized as the second fault and
AR will be blocked if the setting [CBx.79.En_PDF_Blk] is set as "Enabled".
21. CBx.79.t_PersistTrp
When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and exceeds the time delay
[CBx.79.t_PersistTrp], AR will be blocked. This setting should be longer than the longest tripping
time of circuit breaker plus safety margin.
22. CBx.79.t_Fail
It is used to set the time delay waiting for CB close position to conform reclosing successful.
The setting is the time delay from reclosing command sent to unsuccessful reclosing, which shall
be greater than the reclosing operation time of circuit breaker. This time will be valid if the setting
[CBx.79.En_FailCheck] is set as "Enabled".
⚫ If during the time CB is closed, the currently running automatic reclosing cycle was successful.
⚫ If during the time CB remains open, the currently running automatic reclosing cycle was not
successful, the automatic reclosing process will end and be reported as fail.
If the reclosing is considered as unsuccessful, the device will issue a signal (CBx.79.Fail_Rcls) to
indicate that the reclosing is unsuccessful. AR will not enter the ready state unless the circuit
breaker position drops off, and can only begin to enter the ready state again after the circuit breaker
is closed.
23. CBx.79.t_PW
The setting shall be set according to actual requirements, if no tripping latch circuit, then the value
should be greater than the reclosing time of circuit breaker.
For the circuit breaker without anti-pump interlock, the setting [CBx.79.En_CutPulse] is available
to control the reclosing pulse. When this function is enabled, if the device operates to trip during
3
reclosing, the reclosing pulse will drop off immediately, so as to prevent multi-shot reclosing onto
fault.
24. CBx.79.En_AddDly
25. CBx.79.En_FailCheck
26. CBx.79.En_PDF_Blk
It is used to enable/disable auto-reclosing blocked when a fault occurs under pole discrepancy
condition.
27. CBx.79.En_CutPulse
For the circuit breaker without anti-pump interlock, a setting [CBx.79.En_CutPulse] is available to
control the reclosing pulse. When this function is enabled, if the device operates to trip during
reclosing, the reclosing pulse will drop off immediately, so as to prevent multi-shot reclosing onto
fault.
28. CBx.79.En
29. CBx.79.Opt_Enable
Setting: only the setting, which means AR function is controlled only by setting [CBx.79.En].
Setting&Config: the setting and configuration signal, which means AR function is controlled not only
by setting [CBx.79.En], but also by external binary input which could be configured by PCS-Studio.
30. CBx.79.En_CBInit
This setting is available for selection if AR is initiated by CB status. Under normal conditions, when
AR is ready to reclosing, AR will be initiated if circuit breaker is open and corresponding phase
current is nil. AR initiated by CB status can be divided into initiating 1-pole AR and 3-pole AR. For
more details, please refer to "PCS-931S Technical Manual".
31. CBx.79.Opt_Priority
The output signal "CBx.79.WaitToSlave" of master AR will be usually configured to the input signal
"CBx.79.WaitMaster" of slave AR. Slave AR is permissible to reclosing only if master AR is reclosed
successfully.
32. CBx.79.Opt_ValidMode
AR mode can be selected by external signal via binary input signals or internal logic settings. If the
setting [CBx.79.Opt_ValidMode] set as "Setting", AR mode is determined by the settings. If the
settings [CBx.79.Opt_ValidMode] set as "Config", AR mode is determined by the binary input
signals.
CBx.79.Sel_1PAR
CBx.79.Sel_3PAR
CBx.79.Sel_1P/3PAR
CBx.79.En_1PAR
CBx.79.En_3PAR
CBx.79.En_1P/3PAR
33. CBx.79.En_1P 3
It is used to enable/disable 1-pole AR mode.
34. CBx.79.En_3P
35. CBx.79.En_1P/3P
⚫ LCD
⚫ PCS-Studio
Disabled
En_SerCmp
Enabled
1. X1L
It is used for calculation of fault location, and it should be set the same as actual value.
2. R1L
It is used for calculation of fault location, and it should be set the same as actual value.
3. X0L
It is used for calculation of fault location, and it should be set the same as actual value.
4. R0L
It is used for calculation of fault location, and it should be set the same as actual value.
5. X0M
It is used for calculation of fault location, and it should be set the same as actual value.
6. R0M
It is used to set zero-sequence mutual resistance of the whole line. (secondary value)
It is used for calculation of fault location, and it should be set the same as actual value.
When an earth fault occurred on a line of parallel lines arrangement, for cases where precise fault
location is required for long lines with high mutual coupling, mutual compensation is then required
to improve the distance measurement. The residual current from the parallel line should be added
to the device, and the settings of mutual zero-sequence reactance, mutual zero-sequence
resistance should be set as the practical value. If the residual current from the parallel line isn’t
injected to the device, then the settings of mutual zero-sequence reactance, mutual zero-sequence
resistance should be set as 0.
7. LineLength 3
It is used to set total length of the whole line.
It is used for calculation of fault location, and it should be set the same as actual value.
8. U_MOV_Prot
It is used to set voltage setting of MOV (Metal-oxide Varistor) in series compensated line.
Assuming that:
⚫ The protection voltage of series capacitor C1 is Upl1, and its capacitive reactance is XC1.
⚫ The protection voltage of series capacitor C2 is Upl2, and its capacitive reactance is XC2.
⚫ …..
⚫ The protection voltage of series capacitor C6 is Upl6, and its capacitive reactance is XC6.
IED1 IED2 IED3 IED4 IED5 IED6 IED7 IED8
C1 C2 C3
L1 L2 L3 L4
M N
VT2 VT3 VT5
VT1 VT4
L5 L6
C4 C5 C6
O
The setting should be set according to the peak value of MOV′s protection voltage in forward
direction based on local protection VT.
If there is no series compensation in forward direction based on local protection VT, the setting
[U_MOV_Prot] can should be set as "0". If there is any series compensation in forward direction on
the basis of local protection VT, the setting [U_MOV_Prot] should be set to make the zone 1 of
distance protection not overreach for an external fault due to the shrinkage of the protected zone
by the setting [U_MOV_Prot]. The following examples are illustrated according to each specific
condition.
⚫ For IED2 and IED4, no matter the protection voltage is from busbar VT or line VT, there is no
series compensation in forward direction based on local protection VT, the setting
[U_MOV_Prot] of IED2 and IED4 should be set as "0".
⚫ For IED3, no matter the protection voltage is from busbar VT or line VT, there are series
capacitors C1 and C4 in forward direction based on local protection VT, the setting
[U_MOV_Prot] of IED3 can be set as "max(Upl1, Upl4)" to make sure that IED3's zone 1 of
distance protection will not overreach for an external fault in L3 or L5. If any series
3 compensation or any series compensated line is out of service, the corresponding setting
[U_MOV_Prot] should be set as "0". For example, if the series capacitor C4 or the series
compensated line L5 is out of service, corresponding Upl4 taking "0", the setting [U_MOV_Prot]
of IED3 should be set as "Upl1".
⚫ For IED5, if the protection voltage is from busbar VT1, there are series capacitors C1, C2, C3,
C5 and C6 in forward direction based on local protection VT, the setting [U_MOV_Prot] of IED5
can be set as "Upl1+Upl2+max(Upl3, Upl5, Upl6)" to make sure that IED5's zone 1 of distance
protection will not overreach for an external fault in line L4, L5 or L6. If the protection voltage
is from line VT2, there are series capacitors C2, C3, C5 and C6 in forward direction based on
local protection VT, the setting [U_MOV_Prot] of IED5 can be set as "Upl2+max(Upl3, Upl5,
Upl6)" to make sure that IED5's zone 1 of distance protection will not overreach for an external
fault in line L4, L5 or L6.
⚫ For IED6, if the protection voltage if from busbar VT4, there are series capacitors C1, C2 and
C4 in forward direction based on local protection VT, the setting [U_MOV_Prot] of IED6 can
be set as "Upl1+Upl2+Upl4" to make sure that zone 1 of IED6 will not overreach for an external
fault in line L2 or L5. If the protection voltage is from line VT3, there are series capacitors C1
and C4 in forward direction based on local protection VT, the setting [U_MOV_Prot] of IED6
can be set as "Upl1+Upl4" to make sure that IED6's zone 1 of distance protection will not
overreach for an external fault in line L2 or L5.
⚫ For IED7, if the protection voltage is from busbar VT4, there are series capacitor C3 in forward
direction based on local protection VT, the setting [U_MOV_Prot] of IED7 can be set as "Upl3".
If the protection voltage is from line VT5, there is no series capacitor in forward direction based
on local protection VT, the setting [U_MOV_Prot] of P4 can be set as "0".
⚫ For IED8, no matter the protection voltage is from busbar VT or line VT, there are series
capacitors C2, C3, C5 and C6 in forward direction based on local protection VT, the setting
[U_MOV_Prot] of IED8 can be set as "Upl3+max(Upl2, Upl5, Upl6)".
⚫ For IED1, there are some special conditions. When line L2 is shorter but line L3 or L5 is longer,
XC1 or XC4 may be greater than the reactance of line L2, or XC1 (XC4) may be greater than the
reactance of line L2 after infeeding by the adjacent line, then IED's zone 1 of distance
protection maybe overreach for an external fault in line L3 or L5, so the setting [U_MOV_Prot]
of IED1 can be set as "max(Upl1, Upl4)" to make sure that IED's zone 1 of distance protection
will not overreach for an external fault in line L3 or L5. If there is no overreaching risk for IED's
zone 1 of distance protection, the setting [U_MOV_Prot] of IED1 can be set as "0".
9. En_SerCmp
4 Control Settings
Table of Contents
List of Tables
⚫ LCD
⚫ PCS-Studio
Disabled
CBx.25.En_SynChk
Enabled
Disabled
CBx.25.En_DdChk
Enabled
Ua
Ub
Uc
CBx.25.Opt_U_SynChk
Uab
Ubc
Uca
SynDdRefDd
SynLvRefDd
SynDdRefLv
CBx.25.Opt_Mode_DdChk RefDd
SynDd
SynLvRefDd/SynDdRefLv
4 AnySideDd
CBx.25.t_Reset 0~60 1 s
CBx.25.t_Close_CB 0~2000 1 ms
Disabled
CBx.25.En_f_Diff_Chk
Enabled
Disabled
CBx.25.En_df/dt_Chk
Enabled
1. CBx.25.Opt_ValidMode
Setting: the mode of synchronism check is determined by the settings [CBx.25.En_SynChk] and
[CBx.25.En_DdChk];
Config: the mode of synchronism check is determined by the input signals "in_syn_chk" and
"in_vol_chk" via PCS-Studio configuration tool.
2. CBx.25.En_SynChk
3. CBx.25.En_DdChk
4. CBx.25.U_UV
It should be set according to the pecentage of secondary rated phase voltage (Un) or secondary
rated phase-to-phase votlage (Unn) based on the value of the setting [CBx.25.Opt_U_SynChk].
When the voltage at reference side or synchronous side is less than the setting, the synchro-check
will be blocked.
5. CBx.25.U_OV 4
Percentage threshold of over voltage for CB closing blocking
It should be set according to the pecentage of secondary rated phase voltage (Un) or secondary
rated phase-to-phase votlage (Unn) based on the value of the setting [CBx.25.Opt_U_SynChk].
When the voltage at reference side or synchronous side is more than the setting, the synchro-
check will be blocked.
6. CBx.25.f_UF
When the system frequency is less than the setting, the synchro-check will be blocked.
7. CBx.25.f_OF
When the system frequency is more than the setting, the synchro-check will be blocked.
8. CBx.25.Opt_U_SynChk
The setting is valid only when the synchronization side or the reference side voltage is three-phase.
Please set it according to the actual synchronization voltage.
4 9. CBx.25.U_Diff_Set
10. CBx.25.f_Diff_Set
11. CBx.25.df/dt_Set
It is used to set the threshold of rate-of-change of frequency difference for synchronism check.
12. CBx.25.phi_Diff_Set
𝑑∆𝑓
[𝐶𝐵𝑥. 25. 𝑝ℎ𝑖_𝐷𝑖𝑓𝑓_𝑆𝑒𝑡] > |∆𝛿 + ∆𝛿𝐶𝑜𝑚𝑝 − (2𝜋∆𝑓 × 𝑡𝐶𝑙𝑜𝑠𝑒_𝐶𝐵 + 𝜋 × 𝑡𝐶𝑙𝑜𝑠𝑒_𝐶𝐵 2)|
𝑑𝑡
∆𝛿 is the phase angle difference between the reference side and the synchronous side
13. CBx.25.phi_Comp
14. CBx.25.Opt_Mode_DdChk
15. CBx.25.U_DdChk
16. CBx.25.U_LvChk
17. CBx.25.t_Reset
The window starts from the receiving moment of synchronous closing command and ends when all
synchronous closing criteria are met or timeout. The timeout causes the synchronism check failure.
18. CBx.25.t_Close_CB
It is used to set circuit breaker closing time. It is the time from receiving closing command pulse till
the CB is completely closed. Please set it according to the mechanism operating time of the circuit
breaker, which usually is provided by the CB's manufacturer.
19. 25.En_f_Diff_Chk
20. 25.En_df/dt_Chk
⚫ LCD
⚫ PCS-Studio
NoVoltSel
DblBusOneCB
CBx.VoltSel.Opt_CBConfig 3/2BusCB1
3/2TieCB
3/2BusCB2
1. CBx.VoltSel.Opt_CBConfig
It is used to select the circuit breaker No.x arrangement for voltage selection.
3/2BusCB1: bus 1 side circuit breaker for one and a half breakers
3/2TieCB: line side circuit breaker for one and a half breakers
3/2BusCB2: bus 2 side circuit breaker for one and a half breakers
Please set it according to the actual the circuit breaker arrangement, and it should be set as
"NoVoltSel" if no voltage selection is adopted and the voltage selection logic is disabled.
⚫ LCD
⚫ PCS-Studio
CB**.DPS.t_DPU 0~60000 1 ms
Disabled
CB**.DPS.En_Alm
Enabled
CB**.DPS.t_Alm 0~60000 1 ms
DS**.DPS.t_DPU 0~60000 1 ms
Disabled
DS**.DPS.En_Alm
Enabled
DS**.DPS.t_Alm 0~60000 1 ms
1. CB**.DPS.t_DPU
It is used to set the DPU (delay pick up) time of DPS (double point status), i.e. debounce time. (for
circuit breaker No.**)
The setting value should be greater than the CB operating time to avoid the intermediate state in
the process of CB opening or closing.
2. CB**.DPS.En_Alm
3. CB**.DPS.t_Alm
It is used to set time delay of DPS alarm. (for circuit breaker No.**)
4. DS**.DPS.t_DPU
It is used to set the DPU (delay pick up) time of DPS, i.e. debounce time. (for circuit breaker No.**)
The setting value should be greater than the DS operating time to avoid the intermediate state in
the process of DS opening or closing.
5. DS**.DPS.En_Alm
It is used to set time delay of DPS alarm. (for circuit breaker No.**)
⚫ LCD
⚫ PCS-Studio
CB**.t_PW_Opn 0~60000 1 ms
CB**.t_PW_Cls 0~60000 1 ms
DS**.t_PW_Opn 0~60000 1 ms
DS**.t_PW_Cls 0~60000 1 ms
DirCtrl**.t_PW_Opn 0~60000 1 ms
DirCtrl**.t_PW_Cls 0~60000 1 ms
1. CB**.t_PW_Opn
It is used to set pulse width (PW), i.e. holding time, for opening output of circuit breaker No.**.
The setting value should be long enough to start the relay in the CB opening circuit.
2. CB**.t_PW_Cls
It is used to set pulse width (PW), i.e. holding time, for closing output of circuit breaker No.**.
The setting value should be long enough to start the relay in the CB closing circuit.
DS**.t_PW_Opn
4
3.
It is used to set pulse width (PW), i.e. holding time, for opening output of disconnector switch No.**.
The setting value should be long enough to start the relay in the DS opening circuit.
4. DS**.t_PW_Cls
It is used to set pulse width (PW), i.e. holding time, for closing output of disconnector switch No.**.
The setting value should be long enough to start the relay in the DS closing circuit.
5. DirCtrl**.t_PW_Opn
It is used to set pulse width (PW), i.e. holding time, for opening output of direct control object No.**.
The setting value should be long enough to start the relay in the direct control opening circuit.
6. DirCtrl**.t_PW_Cls
It is used to set pulse width (PW), i.e. holding time, for closing output of direct control object No.**.
The setting value should be long enough to start the relay in the direct control closing circuit.
⚫ LCD
⚫ PCS-Studio
Disabled
CB**.En_CILO_Opn
Enabled
Disabled
CB**.En_CILO_Cls
Enabled
Disabled
4 DS**.En_CILO_Opn
Enabled
Disabled
DS**.En_CILO_Cls
Enabled
Disabled
DirCtrl**.En_CILO_Opn
Enabled
Disabled
DirCtrl**.En_CILO_Cls
Enabled
1. CB**.En_CILO_Opn
It is used to enable/disable open output of circuit breaker No.** controlled by the interlocking logic.
2. CB**.En_CILO_Cls
It is used to enable/disable closing output of circuit breaker No.** controlled by the interlocking logic.
3. DS**.En_CILO_Opn
It is used to enable/disable open output of disconnector switch No.** controlled by the interlocking
logic.
4. DS**.En_CILO_Cls
It is used to enable/disable closing output of disconnector switch No.** controlled by the interlocking
logic.
5. DirCtrl**.En_CILO_Opn
It is used to enable/disable open output of direct control object No.** controlled by the interlocking
logic.
6. DirCtrl**.En_CILO_Cls
It is used to enable/disable closing output of direct control object No.** controlled by the interlocking
logic.
5 Measurement Settings
Table of Contents
List of Tables
5.1 Function
⚫ LCD
⚫ PCS-Studio
Disabled
Prot.En_Alm_ROV
Enabled
Disabled
Prot.En_Alm_ROC
Enabled
Disabled
Prot.En_Alm_ROV
Enabled
Disabled
Prot.En_Alm_UV
Enabled
Disabled
Prot.En_Alm_ROC
Enabled
Disabled
5 Prot.CB1.En_Alm_ROC
Enabled
Disabled
Prot.CB2.En_Alm_ROC
Enabled
Ia-Ib-Ic
Prot.Opt_CT_Measmt
Ia-Ic
Ia-Ib-Ic
Prot.CB1.Opt_CT_Measmt
Ia-Ic
Ia-Ib-Ic
Prot.CB2.Opt_CT_Measmt
Ia-Ic
1. Prot.En_Alm_ROV
2. Prot.3U0_Alm_ROV
It is used to set the threshold of residual overvoltage supervision, which is indicated by the
percentage of the rated value.
4. Prot.U_Alm_UV
It is used to set the threshold of phase undervoltage supervision, which is indicated by the
percentage of the rated value.
5. Prot.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the protection voltage due to the
temperature or other environmental factors. The measured value less than this setting will be
regarded as a zero drift and ignored.
6. Prot.En_Alm_ROC
7. Prot.CB1.En_Alm_ROC
It is used to enable/disable residual overcurrent supervision of circuit breaker No.1. (double CBs
application)
8. Prot.CB2.En_Alm_ROC
It is used to enable/disable residual overcurrent supervision of circuit breaker No.2. (double CBs
application)
9. Prot.3I0_Alm_ROC
It is used to set the threshold of residual overcurrent supervision, which is indicated by the
percentage of the rated value. (single CB application)
10. Prot.CB1.3I0_Alm_ROC
It is used to set the threshold of residual overcurrent supervision for circuit breaker No.1, which is
indicated by the percentage of the rated value. (double CBs application)
11. Prot.CB2.3I0_Alm_ROC
It is used to set the threshold of residual overcurrent supervision for circuit breaker No.2, which is
indicated by the percentage of the rated value. (double CBs application)
12. Prot.Opt_CT_Measmt
5 It is used to select CT wiring mode which used by current measurement. (single CB application)
13. Prot.CB1.Opt_CT_Measmt
It is used to select CT wiring mode for circuit breaker No.1 which used by current measurement.
(double CBs application)
14. Prot.CB2.Opt_CT_Measmt
It is used to select CT wiring mode for circuit breaker No.2 which used by current measurement.
(double CBs application)
15. Prot.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the current due to the temperature
or other environmental factors. A measured value less than this setting will be regarded as a zero
16. Prot.CB1.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the current due to the temperature
or other environmental factors. A measured value less than this setting will be regarded as a zero
drift and ignored. (double CBs application)
17. Prot.CB2.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the current due to the temperature
or other environmental factors. A measured value less than this setting will be regarded as a zero
drift and ignored. (double CBs application)
18. Prot.ZeroDrift_PQ
It is used to set the threshold to limit the zero-drift influence of the power due to the temperature or
other environmental factors. A measured value less than this setting will be regarded as a zero drift 5
and ignored. (single CB application)
19. Prot.CB1.ZeroDrift_PQ
It is used to set the threshold to limit the zero-drift influence of the power due to the temperature or
other environmental factors. A measured value less than this setting will be regarded as a zero drift
and ignored. (double CBs application)
20. Prot.CB2.ZeroDrift_PQ
It is used to set the threshold to limit the zero-drift influence of the power due to the temperature or
other environmental factors. A measured value less than this setting will be regarded as a zero drift
and ignored. (double CBs application)
21. 3I0Adj.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the residual current from parallel line
due to the temperature or other environmental factors. A measured value less than this setting will
be regarded as a zero drift and ignored.
22. UB1.USyn.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the synchronism voltage (UB1) due
to the temperature or other environmental factors. A measured value less than this setting will be
regarded as a zero drift and ignored.
23. UL2.USyn.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the synchronism voltage (UL2) due
to the temperature or other environmental factors. A measured value less than this setting will be
regarded as a zero drift and ignored.
24. UB2.USyn.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the synchronism voltage (UB2) due
to the temperature or other environmental factors. A measured value less than this setting will be
regarded as a zero drift and ignored.
⚫ LCD
⚫ PCS-Studio
Prot.CBx.K_Calbr_Ia 9000~11000 1
Prot.CBx.K_Calbr_Ib 9000~11000 1
Prot.CBx.K_Calbr_Ic 9000~11000 1
Prot.K_Calbr_Ua 9000~11000 1
Prot.K_Calbr_Ub 9000~11000 1
Prot.K_Calbr_Uc 9000~11000 1
Prot.K_Calbr_Uab 9000~11000 1
Prot.K_Calbr_Ubc 9000~11000 1
Prot.K_Calbr_Uca 9000~11000 1
Prot.CBx.K_Calbr_Pa -900~11000 1
Prot.CBx.K_Calbr_Pb -900~11000 1
Prot.CBx.K_Calbr_Pc -900~11000 1
Prot.CBx.K_Calbr_Qa -900~11000 1
Prot.CBx.K_Calbr_Qb -900~11000 1
Prot.CBx.K_Calbr_Qc -900~11000 1
UB1.K_Calbr_U 9000~11000 1
Analog input accuracy has been calibrated before delivery, and these 5
settings generally do not need to be set.
1. Prot.CBx.K_Calbr_Ia
It is used to set phase-A current input calibration coefficients for circuit breaker No.x.
2. Prot.CBx.K_Calbr_Ib
It is used to set phase-B current input calibration coefficients for circuit breaker No.x.
3. Prot.CBx.K_Calbr_Ic
It is used to set phase-C current input calibration coefficients for circuit breaker No.x.
4. Prot.K_Calbr_Ua
5. Prot.K_Calbr_Ub
6. Prot.K_Calbr_Uc
7. Prot.K_Calbr_Uab
8. Prot.K_Calbr_Ubc
9. Prot.K_Calbr_Uca
10. Prot.CBx.K_Calbr_Pa
It is used to set phase-A active power calibration coefficients for circuit breaker No.x.
11. Prot.CBx.K_Calbr_Pb
It is used to set phase-B active power calibration coefficients for circuit breaker No.x.
12. Prot.CBx.K_Calbr_Pc
It is used to set phase-C active power calibration coefficients for circuit breaker No.x.
13. Prot.CBx.K_Calbr_Qa
It is used to set phase-A reactive power calibration coefficients for circuit breaker No.x.
14. Prot.CBx.K_Calbr_Qb
It is used to set phase-B reactive power calibration coefficients for circuit breaker No.x.
5 15. Prot.CBx.K_Calbr_Qc
It is used to set phase-C reactive power calibration coefficients for circuit breaker No.x.
16. UB1.K_Calbr_U
It is used to set single-phse voltage input calibration coefficient for synchronization check, double
bus, etc.
⚫ LCD
⚫ PCS-Studio
MMTR.I2n 1~5 1 A
1. MMTR.U2n
2. MMTR.I2n
Table of Contents
List of Tables
⚫ LCD
⚫ PCS-Studio
Disabled
En_PMU
Enabled
P_Class
Opt_Class_PMU
M_Class
N_Chgd_CFG 0~65535 1
Port_TCP 0~65535 1
Port_UDP 1024~65535 1
1. En_PMU
2. Opt_Class_PMU
This algorithm adopts a short time window, so its response speed is fast. It is suitable for fast
protection and control applications, but the ability of suppressing the out-of-band signals is poor.
This algorithm adopts a long time window, so its accuracy is high for measuring steady and dynamic
signal, and can suppress the out-of-brand signals. However, its response speed is slower than that
when adopting P_Class.
3. DataRate
It is used to set data transmission rate of PMU reporting synchrophasor data to the parent IEDs
(such as, PDC or PMU master station).
The rate is generally equal to or less than the rated frequency of power system.
For the 50Hz system, the selectable rates are 100, 50, 25, 10 frames per second.
For the 60Hz system, the selectable rates are 120, 60, 30, 20, 15, 12, 10 frames per second.
4. Substation_PMU
5. N_Chgd_CFG
It is used to indicate the version of CFG of PMU, and inform the client when the CFG-1 has changed.
6 The starting value of the setting is 0, and it should increase by 1 every time CFG-1 is adjusted. For
example, changing the branch name or rating will cause the change of CFG-1, so the setting should
be modified.
6. Port_TCP
It is used to set TCP port for PMU based on IEEE C37.118 standard.
There are three kinds of communication modes available for PMU, TCP, UDP and TCP-UDP mode.
When adopting the TCP or TCP-UDP mode, the TCP port will be used. The port values of all TCP
clients should be consistent with the setting value.
The default port of TCP is 4712, and it is invalid when the setting [PDC**.Opt_Protocol] is set as
"Spontaneous-UDP" or "Commanded-UDP")
7. Port_UDP
It is used to set UDP port for PMU based on IEEE C37.118 standard.
There are three kinds of communication modes available for PMU, TCP, UDP and TCP-UDP mode.
When adopting the UDP or TCP-UDP mode, the UDP port will be used. The port values of all UDP
receivers should be consistent with the setting value.
The default port of TCP is 4713, and it is invalid when the setting [PDC**.Opt_Protocol] is set as
"TCP")
⚫ LCD
⚫ PCS-Studio
PDC01.Name
PDC01.IP_TCP 0.0.0.0~255.255.255.255
PDC01.IP_UDP_Dest 0.0.0.0~255.255.255.255
6
PDC01.IP_MulticastSrc 0.0.0.0~255.255.255.255
None
TCP
PDC01.Opt_Protocol Spontaneous-UDP
TCP-UDP
Commanded-UDP
Unicast
PDC01.Opt_UDP Broadcast
Multicast
PDC01.IDCODE 1~65534
PDC02.Name
PDC02.IP_TCP 0.0.0.0~255.255.255.255
PDC02.IP_UDP_Dest 0.0.0.0~255.255.255.255
PDC02.IP_MulticastSrc 0.0.0.0~255.255.255.255
None
PDC02.Opt_Protocol
TCP
Spontaneous-UDP
TCP-UDP
Commanded-UDP
Unicast
PDC02.Opt_UDP Broadcast
Multicast
PDC02.IDCODE 1~65534
PDC03.Name
PDC03.IP_TCP 0.0.0.0~255.255.255.255
PDC03.IP_UDP_Dest 0.0.0.0~255.255.255.255
PDC03.IP_MulticastSrc 0.0.0.0~255.255.255.255
None
TCP
PDC03.Opt_Protocol Spontaneous-UDP
TCP-UDP
Commanded-UDP
Unicast
6 PDC03.Opt_UDP Broadcast
Multicast
PDC03.IDCODE 1~65534
PDC04.Name
PDC04.IP_TCP 0.0.0.0~255.255.255.255
PDC04.IP_UDP_Dest 0.0.0.0~255.255.255.255
PDC04.IP_MulticastSrc 0.0.0.0~255.255.255.255
None
TCP
PDC04.Opt_Protocol Spontaneous-UDP
TCP-UDP
Commanded-UDP
Unicast
PDC04.Opt_UDP Broadcast
Multicast
PDC04.IDCODE 1~65534
1. PDC**.Name
It is used to set the name of PDC (Phasor Data Concentrators) connecting with PMU.
2. PDC**.IP_TCP
It is used to set destination IP address of connected PDC** using TCP communication protocol.
This setting is valid when the setting [PDC**.Opt_Protocol] is set as "TCP" or "TCP-UDP". The
communication of PMU is based on whitelisting, only when the IP address of the TCP client has
been set in the PMU, the client has the right to communicate with PMU using TCP communication
protocol.
If the PDC does not exist or the TCP or TCP-UDP mode is not adopted, the IP address can be set
as "0.0.0.0".
3. PDC**.IP_UDP_Dest
It is used to set destination IP address of connected PDC** using UDP communication protocol.
4. PDC**.IP_MulticastSrc
It is used to set the multicast source IP address of PDC** using UDP communication protocol, it is
consistent with some network interface IP address of the device. This network interface uses this
IP address to transmit UDP message to multicast group. Since the IP addresss of the muticast
group and any network interface of the device have the different network segments, this setting
essentially informs the PMU which network interface to send UDP multicast message.
It should be set as IP address of the Ethernet port which is chosen to tranmitting UDP multicast
message.
5. PDC**.Opt_Protocol
TCP: in TCP communication mode, configuration frames (CFG-1/2), command frames (CMD), and
DATA frames (DATA) defined in the IEEE C37.118 standard are transmitted via TCP connections.
When using TCP mode, the settings [Port_TCP] and [PDC**.IP_TCP] need to be set.
UDP: in UDP communication mode, configuration frames (CFG-1/2), command frames (CMD), and
DATA frames (DATA) defined in the IEEE C37.118 standard are transmitted via UDP messages.
It shall be consistent with the communication protocol of the PDC at the opposite end. Its
recommended value is "TCP".
6. PDC**.Opt_UDP
The setting is valid when the setting [PDC**.Opt_Protocol] is set as "UDP" or "TCP-UDP". For the
communication between the PMU and the third-party PDCs, the setting is recommended to be set
as "Multicast".
7. PDC**.IDCODE
The setting can identify each PDC for the protocol. Please set the setting according to the site
IDCODE planning, and it should be consistent with the IDCODE of the PDC at the opposite end.
⚫ LCD
⚫ PCS-Studio
None
Bay
xx.Opt_UnitType 1
Bus(U_3P)
Bus(U_1P)
U1
Ua
xx.Opt_U_MeasFreq 1
Ub
Uc
Disabled
xx.En_TrigDFR
Enabled
1. Name_PMUBay
This setting together with the [Name_**] (in submenu "PMU Label Settings") form a complete
measurement name, and the total length is no more than 16 characters.
The name of PMU bay is generally composed of station code and bay name, with a total length of
no more than 12 characters, and it is recommended to set the name according to 12 characters.
2. xx.U1n
3. xx.I1n
4. xx.Opt_UnitType
Bus(U_3P): measuring three-phases voltage, the current and power quantities are not measured
and displayed.
6 Bus(U_1P): measuring single-phase voltage, the current and power quantities are not measured
and displayed. Besides, zero-sequence and negative-sequence voltage are not calculated, their
values are fixed as "0".
When the setting is set as "Bus(U_1P)", it is recommended to use the phase-A voltage.
5. xx.Opt_U_MeasFreq
Its recommended value is "U1", because the frequency measurement function will not be affected
in case of single-phase or two-phase VT failure.
6. xx.En_TrigDFR
It is used to enable/disable trigger disturbance fault recording function in case any following over
limit situation
If the setting is set as "Enabled", the triggering flag will be mapped in "STAT" field of PMU data
frame with a time delay of four power-frequency cycles when the triggering condition is satisfied.
For an independent PMU device, the recording will be performed in the above-mentioned case, but
for the device integrating with the PMU function, the above-mentioned case will not affect the
recording function, the device starts the recording function according to its own criterion.
7. xx.Up_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
8. xx.U1_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
9. xx.U2_UpLmt
6
It is used to set the upper limit of negative-sequence voltage.
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
10. xx.U0_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
11. xx.Up_LowLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
12. xx.U1_LowLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
13. xx.Ip_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
14. xx.I1_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
15. xx.I2_UpLmt
6 It is used to set the upper limit of negative sequence current.
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
16. xx.I0_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
17. xx.f_Diff_Lmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
18. xx.df/dt_Lmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
⚫ LCD
⚫ PCS-Studio
Disabled
Link_BI_TrigDFR
Enabled
6
Disabled
BI_**.En_TrigDFR
Enabled
1. Name_BI_**
The setting generally composed of station name and binary input name. Its total length should not
exceed 16 characters.
2. Link_BI_TrigDFR
It is used to enable/disable disturbance fault recording function in case status changing of any
binary signal for PMU.
If the setting is set as "Enabled", the status of the binary input is changed and its corresponding
setting [BI_**.En_TrigDFR] is set as "Enabled", the triggering flag will be mapped in "STAT" field
of PMU data frame. For an independent PMU device, the recording will be performed in the above-
mentioned case, but for the device integrating with the PMU function, the above-mentioned case
will not affect the recording function, the device starts the recording function according to its own
criterion.
3. BI_**.En_TrigDFR
It is used to enable/disable disturbance fault recording function in case status changing of the binary
signal BI_** for PMU.
If the setting is set as "Enabled", the status of the binary input is changed and its corresponding
setting [BI_**.En_TrigDFR] is set as "Enabled", the triggering flag will be mapped in "STAT" field
of PMU data frame. For an independent PMU device, the recording will be performed in the above-
mentioned case, but for the device integrating with the PMU function, the above-mentioned case
will not affect the recording function, the device starts the recording function according to its own
criterion.
⚫ PCS-Studio
1. Name_Amp_Ua
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
2. Name_Amp_Ub
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
3. Name_Amp_Uc
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
4. Name_Amp_U0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
6 It is recommended to adopt the form "-" + "the type of the measurement quantity".
5. Name_Amp_U1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
6. Name_Amp_U2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
7. Name_Amp_Ia
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
8. Name_Amp_Ib
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
9. Name_Amp_Ic
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
6
Please set the setting according to the actual measured quantity.
10. Name_Amp_I0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
11. Name_Amp_I1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
12. Name_Amp_I2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
13. Name_Ang_Ua
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
14. Name_Ang_Ub
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
6 It is recommended to adopt the form "-" + "the type of the measurement quantity".
15. Name_Ang_Uc
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
16. Name_Ang_U0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
17. Name_Ang_U1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
18. Name_Ang_U2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
19. Name_Ang_Ia
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
6
Please set the setting according to the actual measured quantity.
20. Name_Ang_Ib
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
21. Name_Ang_Ic
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
22. Name_Ang_I0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
23. Name_Ang_I1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
24. Name_Ang_I2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
6 It is recommended to adopt the form "-" + "the type of the measurement quantity".
25. Name_f
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
26. Name_df/dt
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
27. Name_P
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
28. Name_Q
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
Table of Contents
List of Tables
⚫ LCD
MainMenuSettingsTWFL Settings
⚫ PCS-Studio
TWFL.Rmt.Substation
Disabled
TWFL.En_HybridLine
Enabled
Disabled
TWFL.En_Alm
Enabled
1. TWFL.Rmt.Substation
Please set the setting according to the actual substation name in the remote end.
2. TWFL.Velocity_Set
It is valid when the setting [TWFL.En_HybridLine] is set as "0". If the setting [TWFL.En_HybridLine]
is set as "1", the velocity of different section is determined by the settings
[TWFL.SectionA.Velocity_Set], [TWFL.SectionB.Velocity_Set], [TWFL.SectionC.Velocity_Set]
respectively.
It recommends measuring the actual TW velocity when commissioning the device. With the circuit
breakers open at both sides, close the local circuit breaker to energize the line. Check the local TW
recording, find the first moment (t1) when the current obviously changes, and find the second
L
moment (t2) when the current obviously changes near the time t1 + 2 ×
C
Where:
C is the estimated TW velocity, 294m/us for the overhead line, 150m/us for the cable
𝐿
[𝑥𝑥. 𝑇𝑊𝐹𝐿. 𝑉𝑒𝑙𝑜𝑐𝑖𝑡𝑦_𝑆𝑒𝑡] = 2 ×
𝑡2 − 𝑡1
3. TWFL.I_set
It is used to set the pickup threshold of TW current. Usually, it can adopt the default value.
The settin can be set as 8% of the maximum TW current. The maximum traveling wave current can
be calculated according to the rated voltage of the line and the line's characteristic impedance. The
equation is as follows:
√2 × 𝑈𝐿
7 𝑖𝑡𝑤_𝑚𝑎𝑥 = 2 ×
√3
/𝑍𝑐
Where:
The factor 2 is multiplied to consider that if the traveling wave has positive total reflection at the
busbar of the measuring point, the amplitude of the traveling wave will be twice that of the incident
wave.
Where:
4. TWFL.En_HybridLine
It is used to enable/disable travelling-wave fault location for hybrid lines, and the device supports
M N
5. TWFL.Section*.LineLength (*=A, B, C)
It is used to respectively set the length of section A, section B, section C in hybrid lines. They are
valid after the setting [TWFL.En_HybridLine] is set as "Enabled"
For 3-sections hybrid lines, the settings of local side and remote side should be set according the 7
table as below.
TWFL.SectionA.LineLength L1 L3
TWFL.SectionB.LineLength L2 L2
TWFL.SectionC.LineLength L3 L1
For 2-sections hybrid lines, the settings of local side and remote side should be set according the
table as below.
TWFL.SectionA.LineLength L1 L2
TWFL.SectionB.LineLength L2 L1
TWFL.SectionC.LineLength 0 0
When the setting [TWFL.En_HybridLine] is set as "0", the line length adopts
the value of the setting [LineLength].
6. TWFL.Section*.Velocity_Set (*=A, B, C)
It is used to respectively set the TW velocity of section A, section B, section C in hybrid lines. They
are valid after the setting [TWFL.En_HybridLine] is set as "Enabled"
Because the refraction and reflection rule of travelling wave in hybrid lines is very complicated, it
will be difficult to use the above calculation method of the setting [TWFL.Velocity_Se]. It is
suggested to estimate the wave velocity of each section according to the exact inductance and
capacitance parameters of the line: 𝑣 = 1/√𝐿𝐶
For 3-sections hybrid lines, the settings of local side and remote side should be set according the
table as below.
TWFL.SectionA.Velocity_set v1 v3
TWFL.SectionB.Velocity_set v2 v2
TWFL.SectionC.Velocity_set v3 v1
For 2-sections hybrid lines, the settings of local side and remote side should be set according the
7 table as below.
TWFL.SectionA.Velocity_set v1 v2
TWFL.SectionB.Velocity_set v2 v1
7. TWFL.En_Alm
It is used to enable/disable TW alarm. When the setting is set as "0", all alarms of TWFL will not be
issued.
8 Supervision Settings
Table of Contents
List of Tables
⚫ LCD
⚫ PCS-Studio
Disabled
VTS.En Enabled
Enabled
Bus
VTS.Opt_VT Bus
Bay
2. VTS.Opt_VT
It is used to select voltage source for protection calculation, busbar VT or line VT.
Bus: busbar VT
Bay: bay VT
3. VTS.t_DPU
4. VTS.t_DDO
5. VTS.U1_Set
6. VTS.3U0_Set
7. VTS.U2_Set
⚫ LCD
⚫ PCS-Studio
Disabled
CBx.CTS.En
Enabled
1. CBx.CTS.3I0_Set
It should be greater than the maximum unbalanced current and less than load current, at the same
time, it should be sensitive enough.
2. CBx.CTS.3U0_Set
It should be greater than the maximum unbalanced voltage, and it should be sensitive enough.
3. CBx.CTS.t_DPU
4. CBx.CTS.t_DDO
5. CBx.CTS.En
⚫ LCD
CBx.SCBR.I1n 1~60000 1 A
CBx.SCBR.I2n 1~5 1 A
CBx.SCBR.N_Opn_Init 0~1000000 1
Disabled
CBx.SCBR.En_Alm_N_Opn
Enabled
CBx.SCBR.Th_Alm_N_Opn 0~1000000 1
Disabled
CBx.SCBR.En_Wrn_N_Opn
Enabled
CBx.SCBR.Th_Wrn_N_Opn 0~1000000 1
CBx.SCBR.t_Opn_Comp 0~500 1 ms
CBx.SCBR.t_Cls_Comp 0~500 1 ms
Disabled
CBx.SCBR.En_Alm_t_Opn
Enabled
CBx.SCBR.Th_Alm_t_Opn 0~10000 1 ms
Disabled
CBx.SCBR.En_Wrn_t_Opn
Enabled
CBx.SCBR.Th_Wrn_t_Opn 0~10000 1 ms
Disabled
CBx.SCBR.En_Alm_t_Cls
Enabled
CBx.SCBR.Th_Alm_t_Cls 0~10000 1 ms
Disabled
CBx.SCBR.En_Wrn_t_Cls
8
Enabled
CBx.SCBR.Th_Wrn_t_Cls 0~10000 1 ms
CBx.SCBR.RemainLife_Init 0~100000 1
Disabled
CBx.SCBR.En_Alm_RemainLife
Enabled
CBx.SCBR.Th_Alm_RemainLife 0~10000 1 ms
CBx.SCBR.Num_Rated_Life 0-100000 1
CBx.SCBR.Num_02_Life 0-100000 1
CBx.SCBR.Num_03_Life 0-100000 1
CBx.SCBR.Num_04_Life 0-100000 1
CBx.SCBR.Num_05_Life 0-100000 1
CBx.SCBR.Num_06_Life 0-100000 1
CBx.SCBR.Num_07_Life 0-100000 1
8
CBx.SCBR.Num_08_Life 0-100000 1
CBx.SCBR.Num_09_Life 0-100000 1
CBx.SCBR.Num_10_Life 0-100000 1
CBx.SCBR.Num_11_Life 0-100000 1
CBx.SCBR.Num_12_Life 0-100000 1
CBx.SCBR.Num_13_Life 0-100000 1
CBx.SCBR.Num_14_Life 0-100000 1
CBx.SCBR.Num_15_Life 0-100000 1
CBx.SCBR.Num_Fault_Life 0-100000 1
Disabled
CBx.SCBR.En_Alm_Abr
Enabled
Disabled
CBx.SCBR.En_Wrn_Abr
Enabled
1. CBx.SCBR.I1n
It is used to set the primary rated current for the circuit breaker supervision.
2. CBx.SCBR.I2n
It is used to set the secondary rated current for the circuit breaker supervision.
3. CBx.SCBR.N_Opn_Init
4. CBx.SCBR.En_Alm_N_Opn
It is used to enable/disable the out-of-limit alarm for the counting result of CB's trip counter.
5. CBx.SCBR.Th_Alm_N_Opn
8 It is used to set the threshold of out-of-limit alarm for the counting result of CB's trip counter.
6. CBx.SCBR.En_Wrn_N_Opn
It is used to enable/disable the out-of-limit warning for the counting result of CB's trip counter.
7. CBx.SCBR.Th_Wrn_N_Opn
It is used to set the threshold of the out-of-limit warning for the counting result of CB's trip counter.
8. CBx.SCBR.t_Opn_Comp
It is used to set the compensation factor for the travel time of CB's opening contact.
9. CBx.SCBR.t_Cls_Comp
It is used to set the compensation factor for the travel time of CB's closing contact.
10. CBx.SCBR.En_Alm_t_Opn
It is used to enable/disable the overtime alarm for the travel time of CB's opening contact.
11. CBx.SCBR.Th_Alm_t_Opn
It is used to set the threshold of overtime alarm for the travel time of CB's opening contact.
12. CBx.SCBR.En_Wrn_t_Opn
It is used to enable/disable the overtime warning for the travel time of CB's opening contact.
13. CBx.SCBR.Th_Wrn_t_Opn
It is used to set the threshold of overtime warning for the travel time of CB's opening contact.
14. CBx.SCBR.En_Alm_t_Cls
It is used to enable/disable the overtime alarm for the travel time of CB's closing contact.
15. CBx.SCBR.Th_Alm_t_Cls
It is used to set the threshold of overtime alarm for the travel time of CB's closing contact.
16. CBx.SCBR.En_Wrn_t_Cls
It is used to enable/disable the overtime warning for the travel time of CB's closing contact.
17. CBx.SCBR.Th_Wrn_t_Cls
It is used to set the threshold of overtime warning for the travel time of CB's closing contact.
18. CBx.SCBR.RemainLife_Init
Generally, the setting shall be set according to the actual number of available operations
19. CBx.SCBR.En_Alm_RemainLife
21. CBx.SCBR.I_Rated_Life
It is used to set the rated current of the initial point on CB maintenance curve.
It is used to set the characteristic current of the point No.** on CB maintenance curve
Generally, the setting shall be set according to the curve of operation times and tripping current.
23. CBx.SCBR.I_Fault_Life
It is used to set the fault current of the terminal point on CB maintenance curve.
24. CBx.SCBR.Num_Rated_Life
It is used to set the operating times corresponding to the rated current of the initial point on CB
maintenance curve.
It is used to set the operating times corresponding to the characteristic current of the point No.**
on CB maintenance curve.
26. CBx.SCBR.Num_Fault_Life
It is used to set the operating times corresponding to the fault current of the terminal point on CB
maintenance curve.
27. CBx.SCBR.CurrExponent
It is used to set the current exponent factor to calculate CB's accumulated abrasion.
28. CBx.SCBR.Abr_Init
29. CBx.SCBR.En_Alm_Abr
30. CBx.SCBR.Th_Alm_Abr
31. CBx.SCBR.En_Wrn_Abr
32. CBx.SCBR.Th_Alm_Abr
9 Logic Links
Table of Contents
List of Tables
⚫ LCD
⚫ PCS-Studio
Disabled
Link_01
Enabled
Disabled
Link_02
Enabled
Disabled
Link_03
Enabled
Disabled
Link_04
Enabled
Disabled
Link_05
Enabled
Disabled
Link_06
Enabled
Disabled
Link_07
Enabled
9
Disabled
Link_08
Enabled
1. Link_xx
These function link settings can be used for logic programming via PCS-Studio configuration tool
to convenient to enable or disable the function element, please refer to "Function Link in Application
Manual"
This logic link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
⚫ LCD
⚫ PCS-Studio
Disabled
**.GLink_Send
Enabled
1. Bxx.Name_**_GCommLink.GLink_Send
** can be defined by editing the "English Description" in the "Basic Information" page. Now
corresponding ** in the above table will change simultaneously. Please refer to "Logic Symbols in
Application Manual".
This link setting can also be configured by remote control command from local SCADA system,
9 master station in control center, etc.
If this logic link setting is configured as "Disabled", all the sent GOOSE data will be cleared to 0.
These settings will be invisible unless the following operations are executed.
2. Instantiate the logic symbol of logic link for GOOSE sending. PCS-
Studio provides configurable logic symbols of logic link for sending
(single input or multiple input). The corresponding setting item (GOOSE
sending link) can be automatically added to "GOOSE Send Links"
when each adding a logic symbol, and its name can be defined by
editing the "English Description". Please refer to "Logic Symbols in
Application Manual"
⚫ LCD
⚫ PCS-Studio
Disabled
GLink_RecvSim
Enabled
Disabled
Bxx.Name_**_GCommLink.GLink_Recv
Enabled
1. GLink_RecvSim
This logic link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
2. Bxx.Name_**_GCommLink.GLink_Recv
This link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
If this logic link setting is configured as "Disabled", the alarm signals "GAlm_ADisc",
"GAlm_BDisc", "GAlm_Maint_Unmatched" of this GOOSE communication link will NOT be
processed and issued.
⚫ LCD
⚫ PCS-Studio
Disabled
SVLink_RecvSim
Enabled
Disabled
Bxx.Name_**_SVCommLink.SVLink_Recv
Enabled
1. SVLink_RecvSim
This logic link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
2. Bxx.Name_**_SVCommLink.SVLink_Recv
This link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
If this logic link setting is configured as "Disabled", the alarm signals "SVAlm_ADisc",
"SVAlm_BDisc", "SVAlm_Maint_Unmatched" of this SV communication link will NOT be
processed and issued.