2025 - 02 - 03 - AC SLD - 4MW - 295kVA and 300kVA

The document outlines the specifications for a 4 MW solar power plant, including details on module technology, inverter ratings, and plant capacities. It includes a single line diagram for indicative purposes and mentions various components such as transformers, surge arresters, and relays. The project is developed by Onix Renewable Limited in Metoda, Rajkot, Gujarat.

Uploaded by

pinak power
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views1 page

2025 - 02 - 03 - AC SLD - 4MW - 295kVA and 300kVA

The document outlines the specifications for a 4 MW solar power plant, including details on module technology, inverter ratings, and plant capacities. It includes a single line diagram for indicative purposes and mentions various components such as transformers, surge arresters, and relays. The project is developed by Onix Renewable Limited in Metoda, Rajkot, Gujarat.

Uploaded by

pinak power
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

W1 W2 W3 W4 W5 W6 W7 W8 W9 W10

SR.
NO.
DESCRIPTION DETAIL
A K
LEGENDS DESCRIPTION 1 MODULE TECHNOLOGY BI FACIAL
2 MODULE RATING - Wp

4 MW AC 3 TOTAL NO. OF INVERTER 7 + 7 NOS.

4 INVERTER RATING 295kVA @ 50°C


300kVA @ 50°C
5 PLANT DC CAPACITY - MWp
6 PLANT AC CAPACITY 4 MW
B L

LEGENDS DESCRIPTION

C TO EVACUATION 11kV
M

DOUBLE POLE
STRUCTURE SA 12kV, 10kA,
CL-2
ARRANGEMENT
SURGE ARRESTER
11kV,300A,
D RELAY TERMINAL BLOCK 25kA/1 Sec.
ISOLATOR
N
WITH E/S
XX kW

MASTER O/C & O/V &


ICOG PANEL TRIP E/F U/V WTIA_LV1
OTPD OPERATED OPERATED

63A OTIA PRVT WTIT_LV1

63T OTIT MOGA WTIA_HV

E 1H 2H 3H 4H 5H 6H 7H SPARE WTIT_LV1 WTIT_LV2 WTIT_HV


O
R Y B 8H 9H
16W ANNUNCIATOR

TO INVERTER DUTY TRANSFORMER (IDT) H


TNC LR
LINE PT MCB
27 59

3.3 kV XR/PH,1CX XX SQMM CORE 1: CL 0.2, 10VA*


AL. ARM. XLPE CABLE CORE 2: CL 3P, 10VA*

F LTP
SPD
11kV CT P2 P
TYPE 1+2 300A/1-1A
MFM
TYPE A&B 25kA FOR 1sec
TTB
CL:0.5s
A ASS V VSS

CORE-1

X2
CT 2000/1A, NUMERICAL RELAYS
CLASS 0.5S
MFM RS485 CLASS 0.5S
CL: 0.5s,10VA* RTB 50 50N 51 51N

800/240V MCB CORE-2


800 / 240V AC CONTROL CL: 5P20,10VA*
TRANSFORMER, TAP WOUND R Y B
P1

MCB EP 95 94 80AC80DC
800/240V VCB
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND
ON OFF TRIP 11kV,630A 86
25kA FOR 3SEC 63 MOG PRV
49WT 49WT
OTI 1. THIS DRAWING IS INDICATIVE ONLY. IT SHALL
G LI,L2,L3
_LV1

TRAFO. PROTECTION RELAYS


_HV

CHANGE AS PER CALCULATION, SCHEDULE & Q


ACB 2000A, 3P, 800V, 50kA, 12kV,10kA SITE REQUIREMENT.
WITH O/L, S/C, E/F CL-2
PROTECTION,MP BASED 2. (*), DETAILS TO BE PROVIDED BY RESPECTIVE
XC x XX sqmm AL, AR, XLPE, 11KV OEM BASED ON CALCULATION.
3. METERING SHALL BE DONE AT MSEDCL
SUBSTATION AND INFRA AND METERING SHALL BE
3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP DONE AS PER DIS-COM AND REGULATORY
BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED
INVERTER DUTY TRANSFORMER GUIDELINE.
WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C 125A,50kA
WITH O/C & 4000 kVA, 3 WINDING TRAFO.,
H ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP
S/C
ON OFF TRIP
11/0.8-0.8KV
REVISION NOTES SCALE:-N.T.S. R

INV-1 INV-2 INV-3 INV-4 INV-5 INV-6 INV-7


POWER LINE TRANSFORMER TRANSFORMER
COMMUNICATION CABLE BOX CABLE BOX
LOGGER

3.3 kV, AL XLPE 1 CORE


295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 3.3 kV 1R/PH,XCX XX AUX. CONNECTION
XR/Ph XXSQ MM
I SQMM AL. ARM. XLPE
CABLE
AUX. TRAFO. OUTDOOR S
1 1 1 1 1 1 1 1 1 1 1 1 1 1 XX KVA, 0.8KV/0.415kV
FROM LT PANEL FROM LT PANEL
2 2 2 2 2 2 2 2 2 2 2 2 2 2
TYPE A TYPE B 17-01-2024 R0 TENDERING
Aux.DB
TYPICAL
xx xx xx xx xx xx xx xx xx xx xx xx xx xx

DATE SUB. REVISION PARTICULARS


ISSUEDFOR
FOR TENDER

J PROJECT NAME: 4MW SOLAR POWER PLANT FOR TENDERING PLANT DC CAPACITY : - MWp REVISION
T
DEVELOPER DESIGN BY DRAWN BY CHECKED BY APPROVED BY DATE
ONIX RENEWABLE LIMITED SITE NAME: - PLANT AC CAPACITY : 04 MW R0
METODA, RAJKOT,
GUJARAT SHEET
DRAWING TITLE: SINGLE LINE DIAGRAM (INDICATIVE AND FOR TENDERING) DRAWING NO: 27122024 PK AJ PK AG 17-01-2025
01 OF 01