2025 - 02 - 03 - AC SLD - 15MW - 295kVA and 300kVA

The document outlines the single line diagram for a 15 MW solar power plant, detailing various components such as inverters, transformers, and protection devices. It includes specifications for module technology, inverter ratings, and plant capacities. The drawing is intended for tendering purposes and is indicative of the system layout and requirements.

Uploaded by

pinak power
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views1 page

2025 - 02 - 03 - AC SLD - 15MW - 295kVA and 300kVA

The document outlines the single line diagram for a 15 MW solar power plant, detailing various components such as inverters, transformers, and protection devices. It includes specifications for module technology, inverter ratings, and plant capacities. The drawing is intended for tendering purposes and is indicative of the system layout and requirements.

Uploaded by

pinak power
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

W1 W2 W3 W4 W5 W6 W7 W8 W9 W10

A
15 MW AC LEGENDS DESCRIPTION
SR.
NO.
DESCRIPTION DETAIL
K
1 MODULE TECHNOLOGY BI FACIAL
2 MODULE RATING - Wp
TO INVERTER DUTY TRANSFORMER (IDT) 3 TOTAL NO. OF INVERTER 8 + 9 NOS.
8 + 9 NOS.
8 + 9 NOS.
4 INVERTER RATING 295kVA @ 50°C
3.3 kV XR/PH,1CX XX SQMM
AL. ARM. XLPE CABLE
300kVA @ 50°C
5 PLANT DC CAPACITY - MWp
B SPD
L
6 PLANT AC CAPACITY 15 MW
LTP
TYPE 1+2
TYPE A CT 2500/1A,
CLASS 0.5S
MFM RS485 CLASS 0.5S

800/240V MCB
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND R Y B
LEGENDS DESCRIPTION
800/240V MCB
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND ON OFF TRIP

C M
ACB 2500A, 3P, 800V, 50kA,
WITH O/L, S/C, E/F
PROTECTION,MP BASED

SURGE ARRESTER
3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP
BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED RELAY TERMINAL BLOCK
WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C 125A,50kA
WITH O/C &
S/C XX kW

ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP
D X N

INV-1 INV-2 INV-3 INV-4 INV-5 INV-6 INV-7 INV-8


POWER LINE
TO EVACUATION 11kV
COMMUNICATION
LOGGER

295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 3.3 kV 1R/PH,XCX XX
SQMM AL. ARM. XLPE DOUBLE POLE
CABLE
STRUCTURE SA 12kV, 10kA,
CL-2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
ARRANGEMENT
E
X3 O
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

11kV,400A,
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx 25kA/1 Sec.
ISOLATOR
WITH E/S

TO INVERTER DUTY TRANSFORMER (IDT) ICOG PANEL MASTER O/C &


TRIP E/F
O/V &
U/V WTIA_LV1
OTPD OPERATED OPERATED

63A OTIA PRVT WTIT_LV1

F 1H 2H 3H 4H 5H 6H 7H
63T OTIT MOGA WTIA_HV
SPARE WTIA_LV1WTIA_LV2 WTIT_HV
P
3.3 kV XR/PH,1CX XX SQMM
AL. ARM. XLPE CABLE R Y B 8H 9H
16W ANNUNCIATOR
H
SPD TNC LR
LTP LINE PT MCB
TYPE 1+2
TYPE B CT 3200/1A,
27 59

CLASS 0.5S
MFM RS485 CLASS 0.5S

CORE 1: CL 0.2, 10VA*


MCB
CORE 2: CL 3P, 10VA*
800/240V
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND R Y B

G 800 / 240V AC CONTROL


800/240V MCB
11kV CT P2
380A/1-1A
Q
TTB MFM A ASS V VSS
TRANSFORMER, TAP WOUND ON OFF TRIP 25kA FOR 1sec CL:0.5s
CORE-1 NUMERICAL RELAYS
CL: 0.5s,10VA* RTB 50 50N 51 51N

ACB 3200A, 3P, 800V, 50kA,


CORE-2
WITH O/L, S/C, E/F
PROTECTION,MP BASED CL: 5P20,10VA* 1. THIS DRAWING IS INDICATIVE ONLY. IT SHALL
P1 CHANGE AS PER CALCULATION, SCHEDULE &
VCB
EP 95 94 80AC80DC SITE REQUIREMENT.
11kV,630A 86 2. (*), DETAILS TO BE PROVIDED BY RESPECTIVE
25kA FOR 3SEC 63 MOG PRV
49WT 49WT
OTI OEM BASED ON CALCULATION.
_LV1 _HV
3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP

H BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED 320A,50kA
WITH O/C & S/C
BASED
125A,50kA
LI,L2,L3
12kV,10kA
TRAFO. PROTECTION RELAYS
REVISION NOTES SCALE:-N.T.S. R
WITH O/C & CL-2
S/C
ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP XC x XX sqmm AL, AR, XLPE,11KV

INVERTER DUTY TRANSFORMER


5000 kVA, 3 WINDING TRAFO.,
INV-1 INV-2 INV-3 INV-4 INV-5 INV-6 INV-7 INV-8 INV-9
POWER LINE 11/0.8-0.8KV
COMMUNICATION
LOGGER

I 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 3.3 kV 1R/PH,XCX XX
SQMM AL. ARM. XLPE
S
CABLE
TRANSFORMER TRANSFORMER
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
CABLE BOX CABLE BOX
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
17-01-2024 R0 TENDERING

xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx 3.3 kV, AL XLPE 1 CORE


XR/Ph XXSQ MM
AUX. CONNECTION DATE SUB. REVISION PARTICULARS
AUX. TRAFO. OUTDOOR
XX KVA, 0.8KV/0.415kV ISSUEDFOR
FROM LT PANEL FROM LT PANEL
TYPE A TYPE B FOR TENDER
Aux.DB
TYPICAL

J PROJECT NAME: 15MW SOLAR POWER PLANT FOR TENDERING PLANT DC CAPACITY : - MWp REVISION
T
DEVELOPER DESIGN BY DRAWN BY CHECKED BY APPROVED BY DATE
ONIX RENEWABLE LIMITED SITE NAME: - PLANT AC CAPACITY : 15 MW R0
METODA, RAJKOT,
GUJARAT SHEET
DRAWING TITLE: SINGLE LINE DIAGRAM (INDICATIVE AND FOR TENDERING) DRAWING NO: 27122024 PK AJ PK AG 17-01-2025
01 OF 01