2025 - 02 - 03 - AC SLD - 9MW - 295kVA and 300kVA

The document outlines the electrical specifications and configurations for a power system, including details on transformers, inverters, circuit breakers, and protection relays. It specifies capacities, ratings, and arrangements for various components such as double pole structures and isolators. Additionally, it includes notes on the indicative nature of the drawing and the need for adjustments based on calculations and site requirements.

Uploaded by

pinak power
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views1 page

2025 - 02 - 03 - AC SLD - 9MW - 295kVA and 300kVA

The document outlines the electrical specifications and configurations for a power system, including details on transformers, inverters, circuit breakers, and protection relays. It specifies capacities, ratings, and arrangements for various components such as double pole structures and isolators. Additionally, it includes notes on the indicative nature of the drawing and the need for adjustments based on calculations and site requirements.

Uploaded by

pinak power
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

W1 W2 W3 W4 W5 W6 W7 W8 W9 W10

TO EVACUATION 11kV

LEGENDS DESCRIPTION SR.


A
9 MW AC DOUBLE POLE
STRUCTURE
ARRANGEMENT
SA 30kV, 12kA,
CL-2

33kV,400A,
25kA/1 Sec.
NO.
1
2
DESCRIPTION
MODULE TECHNOLOGY
MODULE RATING
DETAIL
BI FACIAL
- Wp
K
ISOLATOR
WITH E/S
3 TOTAL NO. OF INVERTER 7 + 7 NOS.
8 + 9 NOS.
ICOG PANEL MASTER O/C & O/V &
4 INVERTER RATING 295kVA @ 50°C
TRIP E/F U/V WTIA_LV1
OTPD

63A
OPERATED OPERATED

OTIA PRVT WTIT_LV1


300kVA @ 50°C
MOGA
1H 2H 3H 4H 5H 6H 7H
63T OTIT
SPARE WTIA_LV1WTIA_LV2 WTIT_HV
WTIA_HV
5 PLANT DC CAPACITY - MWp
R Y B 8H 9H

B H
TNC LR
16W ANNUNCIATOR
6 PLANT AC CAPACITY 9 MW L
LINE PT MCB
27 59

CORE 1: CL 0.2, 10VA*


CORE 2: CL 3P, 10VA*

11kV CT P2
380A/1-1A
TTB MFM A ASS V VSS
25kA FOR 1sec CL:0.5s
CORE-1 NUMERICAL RELAYS
CL: 0.5s,10VA* RTB 50 50N 51 51N LEGENDS DESCRIPTION
CORE-2
CL: 5P20,10VA*
P1

C VCB
11kV,630A
25kA FOR 3SEC
EP

86
95 94 80AC80DC

49WT 49WT
M
63 MOG PRV
_LV1 _HV
OTI
LI,L2,L3 TRAFO. PROTECTION RELAYS
12kV,10kA
CL-2

XC x XX sqmm AL, AR, XLPE,11KV TO EVACUATION 11kV


INVERTER DUTY TRANSFORMER
5000 kVA, 3 WINDING TRAFO.,
11/0.8-0.8KV DOUBLE POLE
STRUCTURE SA 12kV, 10kA,
CL-2
SURGE ARRESTER ARRANGEMENT

11kV,300A,
RELAY TERMINAL BLOCK 25kA/1 Sec.

D TRANSFORMER
CABLE BOX
TRANSFORMER
CABLE BOX
ISOLATOR
WITH E/S N
XX kW

3.3 kV, AL XLPE 1 CORE


AUX. CONNECTION
XR/Ph XXSQ MM

AUX. TRAFO. OUTDOOR


X
XX KVA, 0.8KV/0.415kV MASTER O/C & O/V &
FROM LT PANEL FROM LT PANEL ICOG PANEL TRIP E/F U/V WTIA_LV1
OTPD OPERATED OPERATED
TYPE A TYPE B
Aux.DB 63A OTIA PRVT WTIT_LV1
TYPICAL 63T OTIT MOGA WTIA_HV

1H 2H 3H 4H 5H 6H 7H SPARE WTIT_LV1 WTIT_LV2 WTIT_HV

TO INVERTER DUTY TRANSFORMER (IDT) R Y B 8H 9H


H
16W ANNUNCIATOR

TNC LR
LINE PT MCB
27 59
3.3 kV XR/PH,1CX XX SQMM
AL. ARM. XLPE CABLE

E SPD
CORE 1: CL 0.2, 10VA*
CORE 2: CL 3P, 10VA* O
LTP
TYPE 1+2
TYPE A 11kV CT P2
CT 2500/1A, 300A/1-1A
CLASS 0.5S
MFM RS485 CLASS 0.5S
TTB MFM A ASS V VSS
25kA FOR 1sec CL:0.5s
CORE-1 NUMERICAL RELAYS

MCB
CL: 0.5s,10VA* RTB 50 50N 51 51N
800/240V
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND R Y B CORE-2
CL: 5P20,10VA*
800/240V MCB P1
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND ON OFF TRIP EP 95 94 80AC80DC
VCB
11kV,630A 86
25kA FOR 3SEC 63 MOG PRV
49WT 49WT
OTI
_LV1 _HV
ACB 2500A, 3P, 800V, 50kA,
WITH O/L, S/C, E/F LI,L2,L3 TRAFO. PROTECTION RELAYS
PROTECTION,MP BASED 12kV,10kA
CL-2

F XC x XX sqmm AL, AR, XLPE, 11KV


P
3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP
BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED
WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C 125A,50kA
WITH O/C &
S/C
INVERTER DUTY TRANSFORMER
ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP 4000 kVA, 3 WINDING TRAFO.,
11/0.8-0.8KV

INV-1 INV-2 INV-3 INV-4 INV-5 INV-6 INV-7 INV-8


POWER LINE
COMMUNICATION
LOGGER TRANSFORMER TRANSFORMER
CABLE BOX CABLE BOX

295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 3.3 kV 1R/PH,XCX XX
SQMM AL. ARM. XLPE
CABLE 3.3 kV, AL XLPE 1 CORE
AUX. CONNECTION
XR/Ph XXSQ MM

G
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
FROM LT PANEL FROM LT PANEL
AUX. TRAFO. OUTDOOR
XX KVA, 0.8KV/0.415kV Q
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx TYPE A TYPE B
Aux.DB
TYPICAL

TO INVERTER DUTY TRANSFORMER (IDT) TO INVERTER DUTY TRANSFORMER (IDT)


1. THIS DRAWING IS INDICATIVE ONLY. IT SHALL
3.3 kV XR/PH,1CX XX SQMM
CHANGE AS PER CALCULATION, SCHEDULE &
AL. ARM. XLPE CABLE 3.3 kV XR/PH,1CX XX SQMM
AL. ARM. XLPE CABLE SITE REQUIREMENT.
SPD SPD 2. (*), DETAILS TO BE PROVIDED BY RESPECTIVE
LTP LTP
TYPE 1+2 TYPE 1+2 OEM BASED ON CALCULATION.
TYPE B TYPE A&B
H CT 3200/1A,
MFM RS485 CLASS 0.5S

X2
CLASS 0.5S CT 2000/1A,

MCB
CLASS 0.5S
MFM RS485 CLASS 0.5S
REVISION NOTES SCALE:-N.T.S. R
800/240V 800/240V MCB
800 / 240V AC CONTROL 800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND R Y B TRANSFORMER, TAP WOUND R Y B

800/240V MCB 800/240V MCB


800 / 240V AC CONTROL
800 / 240V AC CONTROL
TRANSFORMER, TAP WOUND ON OFF TRIP ON OFF TRIP
TRANSFORMER, TAP WOUND

ACB 3200A, 3P, 800V, 50kA, ACB 2000A, 3P, 800V, 50kA,
WITH O/L, S/C, E/F WITH O/L, S/C, E/F
PROTECTION,MP BASED PROTECTION,MP BASED

3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP 3P MCCB,MP
BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED 320A,50kA BASED

I
WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C 125A,50kA WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C WITH O/C & S/C 125A,50kA
WITH O/C & WITH O/C &

ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP
S/C
ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP
S/C
ON OFF TRIP S
17-01-2024 R0 TENDERING
INV-1 INV-2 INV-3 INV-4 INV-5 INV-6 INV-7 INV-8 INV-9 INV-1 INV-2 INV-3 INV-4 INV-5 INV-6 INV-7
POWER LINE POWER LINE
COMMUNICATION COMMUNICATION
LOGGER LOGGER
DATE SUB. REVISION PARTICULARS
295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 3.3 kV 1R/PH,XCX XX 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 295/300kW 3.3 kV 1R/PH,XCX XX
SQMM AL. ARM. XLPE
CABLE
SQMM AL. ARM. XLPE
CABLE
ISSUEDFOR
FOR TENDER
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx

J PROJECT NAME: 9MW SOLAR POWER PLANT FOR TENDERING PLANT DC CAPACITY : - MWp REVISION
T
DEVELOPER DESIGN BY DRAWN BY CHECKED BY APPROVED BY DATE
ONIX RENEWABLE LIMITED SITE NAME: - PLANT AC CAPACITY : 09 MW R0
METODA, RAJKOT,
GUJARAT SHEET
DRAWING TITLE: SINGLE LINE DIAGRAM (INDICATIVE AND FOR TENDERING) DRAWING NO: 27122024 PK AJ PK AG 17-01-2025
01 OF 01