Instructions
Web tension controller DC 600.
Assembly and commissioning
Controller type 1, motor drive
1. Safety 2
2. Input/ouput functions 3
2.1 Analog inputs 3
2.2 Digital inputs 4
2.3 Analog outputs 5
2.4 Digital outputs 6
2.5 Controller status table 7
3. Operator panel RT 4101 7
4. Assembly 9
5. Installation 10
6. Commissioning 11
6.1 Setup editor 11
6.2 Setup mode 11
6.3 Commissioning sequence 13
6.4 Setting controller type 13
6.5 Setting parameters 13
6.6 Parameter listing 14
6.7 Parameter description 19
6.8 Calibrating the measuring amplifier 32
6.9 Synchronising drives 32
6.10 Optimising controller 37
7. Special functions 39
8. Operation 41
9. Error code 42
10. Control diagram 44
BEA--221853-E-02
Web tension controller DC 600.
1. Safety
1.1 Intended usage The controller may only be used to control web tension.
The controller is built to state-of-the-art technology.
The controller should only be used
- in perfect technical condition,
- for use as intended, in accordance with the operating instructions.
Work relating to the operation, production gearing, conversion or ad-
justment of the web tension controller as well as its inspection,
maintenance and repair may be performed by trained personnel only.
1.2 Operating manual Please keep this manual in a safe place, accessible to personnel at
all times.
1.3 Safety instructions Never reach into rotating rollers with your hand or tools.
1.4 Assembly and installation When installing controller DC 600. you must observe the locally appli-
cable and professional safety and accident prevention requirements
(e.g VDE 0100, EN 294, EN 349, IEC )
Electrical components must be adequately protected.
Please ensure that:
- electrical components without enclosures are protected according
to the locally applicable safety regulations, e.g. VDE 0100,
- when running electrical cables that the insulation is not damaged
and the cables correctly secured and protected,
- signal lines are run separately from heavy current-carrying leads.
2
Web tension controller DC 600.
Please refer to the connection diagram for the exact terminal assign-
2. Input/ouput ments.
functions Free, unassigned analog inputs must be grounded.
2.1 Analog inputs The analog inputs are works set as voltage inputs. On re-
quest, E+L can also supply current inputs (conversion volta-
ge to current may only be performed ex works).
Analog inputs
Input Terminal Terminal X 10 Signal connected
DC 6000 DC 6001
+ - + -
1 24c 26c 7 8 F-target external
or
F-actual external
or
7 8 Start diameter
2 22a 24a 3 4 N-batch actual
or
3 4 D-batch actual
3 26a 28a 5 6 V-web target
F-target external
Using this analog input an analog voltage of 0 to 10 V DC (or 0 to
20 mA) may be preset and stored for the tension set point. 10 V is
the equivalent of the maximum web tension (Parameter .24.).
The external target value is accepted by the controller when the ap-
propriate digital input is high and the value of the external set point is
stored on the negative edge.
Set point adjustment from the operator panel is blocked as long as
the digital input is high.
F-actual external
This input allows one to enter an actual tension value in the form of
an analog voltage of 0 to 10 V DC (or 0 to 20 mA) - e.g. a previously
established web tension. 10 V corresponds to the maximum web ten-
sion (Parameter .24.).
The external actual value is only effective as long as the digital input
for the actual value is high.
3
Web tension controller DC 600.
N-batch actual
This analog input is used to input the batch speed in the form of an
analog voltage of 0 to10 V DC. 10 V DC is the equivalent of the maxi-
mum batch speed (Parameter .28.)
The actual batch speed is only used for diameter calculation, in
conjunction with a set line speed signal.
D-batch actual
This analog input is used to enter the batch diameter directly in the
form of analog voltage of 0 to 10 V DC (Parameter .30. and .31.).
2.2 Digital inputs Digital inputs are to be used as appropriate to the application.
Please refer to the connection diagram attached for terminal as-
+ 24 V DC external signments.
(logic "0" -5 V to +3 V DC)
Digital inputs
Input Input Terminal Terminal X 1 Function
DC 6000 DC 6001
DE 0 6c 3 Not assigned
DE 1 8a 4 Automatic
DE 2 8c 5 Synchronous mode
DE 3 10a 6 F-target accepted
DE 4 10c 7 Start diameter accepted
Reference potential
(DC 6000 terminal 6a, DE 5 12a 8 F-actual accepted
DC 6001 terminal 2) DE 6 12c 9 Batch change
Digital input - 6a 2 digital reference potential
Automatic Automatic
(green) The tension controller is switched on via the digital input "automatic".
The indicator lights up green. The web tension is now controlled in
accordance with the preset value.
4
Web tension controller DC 600.
Synchronous mode
- multidrive configuration: if the synchronous mode digital input is
high, the set external line speed signal is switched automatically to
the analog output "actuator signal V, N" (∆V = 0).
- batch drive: when the synchronour mode digital input is high, in
automatic mode when calculating the diameter, the external set
line speed signal is divided by the start diameter and switched to
the analog actuator signal (V, N) as the set batch N:
Set line speed V
Set batch N =
Start diameter
When entering the diameter by sensor, the external set line speed
signal is divided by the actual diameter and switched to the analog
actuator output signal (V, N) as the set batch N:
Set batch N = Set line speed V
Actual diameter
F-target accepted
When this digital input is high, the analog set web tension is enabled.
F-actual accepted
When this digital input is high, the analog set actual web tension value
is enabled.
Batch change
If this digital input is high, pres the "start diameter" button (or min.
start diameter parameter) to actuate the preset diameter for web
tension control. A batch change is only possible when "automatic" is
switched off.
2.3 Analog outputs Please refer to the attached connection diagram for the exact terminal
assignments.
The analog output for the actuator signal (V, N)" is works set as a
voltage output. On request, E+L can also supply it as a current out-
put (voltage - current conversion may only be performed ex works).
Analog outputs
Output Terminal Terminal X 11 Signal connected Voltage / current
DC 6000 DC 6001
1 28c 30c 2 3 Actuating signal (V, N) Uoutput 0 bis ±10 V DC
Ioutput 0 (4) to 20 mA optional
2 32a 32c 5 4 Monitor output (D actual or F actual) Uoutput 0 to 10 V DC
5
Web tension controller DC 600.
Monitor output
The monitor output is used for measuring purposes or the graphic
representation of the actual value of the batch diameter or web tensi-
on. It is available in 8 bit resolution. Due to circuit-related reasons,
the zero point can waver by 5 % to 6 % (Parameter .35.).
2.4 Digital outputs Please refer to the attached connection diagram for the installation
terminal assignments.
+24 V DC external
(DC 6000 terminal 4c; Digital outputs
DC 6001 X 2 terminal 2)
Output Terminal Terminal X 2 Function
DC 6000 DC 6001
DA 0 14a 3 Not assigned
Output
(Imax = 500 mA) DA 1 14c 4 Not assigned
DA 2 16a 5 Not assigned
DA 3 16c 6 F-actual limit value
DA 4 18a 7 N-batch actual limit value
DA 5 18c 8 V-web target limit value
Digital output DA 6 20a 9 System operational
- 4c 2 +24 V DC external
System operational
Output 6 indicates that the controller is operational.
Output: logic 1 = system operational
logic 0 = error; controller malfunction
The type of error is indicated in parameter . .5. by an error code (see
error code section).
Output 6 may also be used as an error indicator for the following con-
trols.
6
Web tension controller DC 600.
Synchronous mode
Synchronous mode
in service mode
Batch change
Automatic
Automatic
Manual
Controller off 0 0 0 0 0 0
Controller off 0 0 X 0 0
Controller on 1 0 X X X 0
Controller on 0 0 X 0 0
Synchronous mode 1 1 X X X 0
Synchronous mode X X X X X
Batch change 0 X 1 X X X
Automatic Automatic
(green) When automatic mode is enabled by the digital input of the same
name, the indicator lights up. The web tension is controlled in accor-
dance with the preset values.
The "automatic" key only selects the automatic function directly in
service mode (expanded setup, parameter .4.1.).
7
Web tension controller DC 600.
F-target F-target
(green) Press key "F-target" and the "Up/Down" key to set the desired web
tension target value. The indicator lights up when this function is selec-
ted.
Press the "F-target" key...
- once, the LED lights up, the display is selected.
- twice, the LED flashes, change the F-target value.
- three times, the LED lights up, the F set point is stored.
Diameter Diameter
(green) Press the diameter key and the "Up/Down" key to set the start diame-
ter.
Press the "diameter" key...
- once, the LED lights up, the display is selected.
- twice, the LED flashes, change diameter.
- three times, the LED lights up, store diameter.
8
Web tension controller DC 600.
Down key
Use this key to reduce the value indicated on the digital display (set
value, parameter number or diameter etc.).
Up key
Use this key to increase the value indicated on the digital display.
4.1 Load cells ➜ See load cell description PD 21, 22, 23, 25.
9
Web tension controller DC 600.
5.2 Analog current output and The controller output is works set as a voltage output, the analog in-
analog current inputs puts as voltage inputs. On request E+L can also supply current out-
puts (conversion voltage to current only possible ex works).
5.3 CAN bus networking for See "CAN bus, serial bus and setup editor" description.
tension controller ➜ Run the CAN bus lines away from noisy or heavy current-carrying
cables (e.g. motor cables).
The CAN-Bus may not exceed a maximum total length of 200 m.
5.4 Address setting when On digital controllers designed by E+L the hardware address
networking tension con- (group and device number) of the web controller(s) is preset
trollers (see block diagram for addresses), further address settings
are not necessary. The device number must always be set
Device number DIP switches 1 - 4 to 5!
Group number DIP switches 5 - 7 The address is set via an 8-pole DIP switch on control card RK 4101.
5 dec. 0 dec.
The address consists of two parts:
1 2 3 4 5 6 7 8
- the group number from 0 to 7
ON (is set on DIP switches 5 to 7)
OFF
- the device number from 1 to F (hex)
The device number must always be set to 5 = web controller!
Binary value: (is set via DIP switches 1 to 4)
1 2 4 8 1 2 4
Example: address 2.5 2 = group number
DIP switches
5 = device number
Control card RK 4101 works setting: address 0.5
10
Web tension controller DC 600.
5.6 Address setting on web The 19" rack housing must be opened in order to set the address
controller DC 6000 (see fig. on left).
Operator panel RT 4101 ➜ Loosen the four securing screws "A" on the operator panel
➜ Loosen the two securing screws "B" on the pcb.
Analog card AK 4101
➜ Pull out the pcb by a half and unplug connectors X 1, X 2 and X 3.
➜ Loosen the securing screws on analog card AK 4101 and remove
the analog card.
➜ Set the address on the RK 4101 control card 8-pole DIP switch.
➜ Reassemble the device in reverse order.
6.1 Setup editor The setup editor is a software tool for setting and initialising E+L con-
trollers and CAN bus cards (e.g. control card RK 4101). The setup
editor may be started from operator panel RT 4101 or remote control
DO 6000 by setting the command device in setup or expanded setup
mode.
11
Web tension controller DC 600.
800
Parameter value
12
Web tension controller DC 600.
Set parameters
Synchronise drives
Wind or No
unwind
Yes
Adjust diameter capture
Insert web
Optimise controller
6.4 Setting controller type ➜ Select expanded setup mode (set "42" in parameter ..3. ).
➜ Set "1" in parameter .3.3. for controller type "1".
➜ Initiate a reset in parameter ..3. (set a "1" and change parameter).
➜ Select expanded setup mode (set "42" in parameter ..3.).
➜ Set "2" in parameter ..2. and change parameter.
6.5 Setting parameters ➜ Set parameters. See chapter "Parameter listing" and "Parameter
description".
The values listed in the Default column are internal values which
must be optimized during the initial test runs (see chapter "Optimi-
zing").
➜ Make a note of the changed parameter values.
13
Web tension controller DC 600.
6.6 Parameter listing The field Name shows the abbreviated parameter name. The field
Default shows the standard settings, Min and Max are the respecti-
ve limit values. The unit is shown in the Unit field. The field Explana-
tion describes the parameter functions.
..0. edit device X.5 X.1 X.F hex Selection of equipment number
Device number see block diagram.
..1. edit group 0.X 0.X 7.X hex Selection of group number
Group number see block diagram.
..5. error code 0 0 21 Error code (also refer to chapter Error Codes)
0 = No error, output „System operational“ logic 1
1 = Unidentified error, contact E+L Service
2 = Internally computed measuring range smaller than set
measuring range. Reduce parameter .24. F max
3 = Input offset of last analog input calibrated bigger than ±1 V,
reduce line offset.
4 = Value of last analog input calibrated bigger than ±10 V,
check and recude input voltage.
14
Web tension controller DC 600.
..9. F-target at D0% 100 0 100 % F-target factor for a batch diameter D = 0 %
Web tension target value in relation to batch diameter D
Example:
F-target = 300 N (..8.)
F-target factor for D 0% = 50 % (..9.)
If batch diameter D is 0% web tension target is 150 N.
.10. F-target at D20% 100 0 100 % F-target factor for a batch diameter D = 20%
.11. F-target at D40% 100 0 100 % F-target factor for a batch diameter D = 40%
.12. F-target at D60% 100 0 100 % F-target factor for a batch diameter D = 60%
.13. F-target at D80% 100 0 100 % F-target factor for a batch diameter D = 80%
.14. F-target at D100% 100 0 100 % F-target factor for a batch diameter D = 100%
15
Web tension controller DC 600.
.24. F-actual range .... 0 9999 F max (measuring and control range)
Highest F-target value of the system which must be controlled.
The unit is freely selectable, e.g. N, kp, lbf
This parameter must be entered only after the calibration of the
measuring amplifier.
.27. V-web limit 10,0 1,0 100,0 % V-web target limit value
If the limit value entered here is not reached,
the digital output of same name will be set to logic 1.
16
Web tension controller DC 600.
17
Web tension controller DC 600.
18
Web tension controller DC 600.
Works settings
. . . .2. 0 = no change
1 = customer-optimised values
2 = internal set value (default)
If you enter "1" in this parameter, the values stored by you after opti-
misation will be implemented, if you enter "2", the internal (default)
values are implemented. "0" means no change.
Entries in parameter ..2. are only effective if you then select a new
parameter number (e.g. parameter number ..3.). A wrong or invalid
entry may cause a system malfunction!
Start Service
. . . .3.
In this parameter various calibrating and service routines may be cal-
led up.
- "1" Reset controller
- "6" Exit expanded setup mode
- "10" Perform tare compensation
- "11" Calibrate measuring amplifier
- "12 to 19" Calibrate analog inputs (see chapter 7 "special
functions")
- "20" Compensate diameter calculation (see chapter 6.9)
- "42" Select extended Setup Mode
- "44" store changed (current) parameter values as customer-
optimised values
The Calibration or Service Routines 6, 10, 11 and 12 to 20 can be re-
called only in the Extended Setup Mode.
Entries in parameter ..3. are only effective if you then select a new
parameter number (e.g. parameter number ..4.). A wrong or invalid
entry may cause a system malfunction!
19
Web tension controller DC 600.
20
Web tension controller DC 600.
. . . .6.
Press material-specific
parameter record
Acknowledge entry
yes
enter new parameter
record yes/no
no
proceed with
commissioning
Start diameter
....7. Actual batch diameter when control is initiated.
Diameter This parameter must be set for winding/ unwinding only.
(green) No input of start diameter required if diameter sensor is used.
Entry range: D min to D max (D min is set in parameter .30., D max
in parameter .3.1.)
The start diameter may also be entered directly with the key of same
name on operator panel RT 4101. In this case the value in parameter
..7. will be overwritten.
F-target
. . . .8. Enter the F-target value according to which the web tension controller
should operate.
F-target
(green) Entry range: 0 to F maximum (F maximum is set in parameter .2.4.)
The F-target value may also be entered directly using the key of the
same name on operator panel RT 4101. In this case the value in pa-
rameter ..8. will be overwritten.
21
Web tension controller DC 600.
F-target value F
E.g. 100 % = 300 N
100 %
50 %
0 20 40 60 80 100
min. max.
Batch diameter in %
Example of a set winder characteristic
Example:
F-target value = 300 N
F-target factor when D 0 % = 50 %
Given a batch diameter of 0 %, F-target value of 300 N is effective.
22
Web tension controller DC 600.
P-term
. . .1.5. The P-term specifies the amplification for your controller, 100 % cor-
responds to an amplification of 1. We recommend you set an amplifi-
cation of 10 % during commissioning which may be optmised later
on.
Entry range: 0 - 100 %
If 0 is entered into parameter ..15. this specific parameter series
will be suppressed; in other words it can no longer be selected via
key "material-specific parameter record".
I-term
. . .1.6. The I-term specifies the reset time Tn in secs and prevents a perma-
nent control deviation. We recommend you set an I-term of 0.2 secs
during commissioning which may be optimised later on.
Entry range: 0.001 - 2.000 secs
D-term
. . .1.7. The D-term specifies the rate time Tv in secs. The D component is
used for mass inertia compensation. We recommend you set a
D-term of 0 secs during commissioning which may be optimised later
on.
Entry range: 0 - 0.100 secs
23
Web tension controller DC 600.
Fabric thickness
. . .1.8.
This parameter must be set only for winding/ unwinding without
diameter sensor. Enter the fabric thickness in mms.
Entry range: 0, 1, 2, 3, 4, 5 mm
Controller correction signal ∆V normal (0) Controller correction signal ∆V inverted (1)
F set > F actual = ∆V positive F set > F actual = ∆V negative
F-target F
F maximum
100
Time t/s
Example for parameter .2.1.
1 30
F-target ramp
Calibration weight
. . .2.2. Enter the weight being applied to the measuring roller to calibrate the
measuring amplifier (step 6.8 of commissioning) - unit form freely
selectable, e.g. N, kp, lbf.
24
Web tension controller DC 600.
25
Web tension controller DC 600.
Actuating signal
+10
26
Web tension controller DC 600.
Diameter form
. . .3.2.
This parameter must be set for winding/ unwinding only.
Enter a value only after having calibrated the measuring amplifier
(chapter 6.8 Calibrating the measuring amplifier).
This parameter is used to indicate in which form the batch diameter
is being acquired.
27
Web tension controller DC 600.
28
Web tension controller DC 600.
29
Web tension controller DC 600.
+10 V
Actuating
signal
5,5 V
5V
4,5 V
V-web target
5V +10 V
Service mode
. . .4.1. Controller DC 600. must be set to service mode for commissioning. In
this mode, automatic, manual or synchronous mode may be selected
by pressing the key of the same name on the operator panel. In addi-
tion, various values are indicated on the display.
0 = Service mode off
1 = Service mode on
30
Web tension controller DC 600.
31
Web tension controller DC 600.
6.8 Calibrating the measuring The measuring amplifier may only be calibrated in expanded setup
amplifier mode.
Initially, the measuring roller must be unloaded.
6.9 Synchronising drives The drives must be synchronised differently depending on whether
you are using an electrical batch drive (winding/unwinding), an elec-
trical transport drive or a superimposed gearing with electrical
actuator.
Synchronisation is always performed before the web is inserted!
➜ Increase the machine to maximum line speed.
➜ Check the set line speed voltage on the analog input of the same
name: the voltage measured must not exceed 10 V (DC 6000 ter-
mina 26a and 28a; DC 6001 terminal X 10.5 and X 10.6).
➜ Measure the maximum line speed on the main drive with a hand-
held tachometer and enter in parameter .2.6..
➜ Stop the machine.
32
Web tension controller DC 600.
6.9.1 Synchronising winds ➜ Check whether value 1 or 2 (V, N, analog; V, N, pulsed) is set in
and unwinds and setting parameter .3.2. "select diameter form".
batch calculator with set ➜ Check the error code. If 18 is set in parameter .5.. , the diameter
diameter V, N, analog and constant is incorrect. Select parameter ..3. "Start Service" in ex-
V, N, pulsed panded setup mode and enter 20 (diameter calibration), then
change parameter.
➜ Clamp the core to the batch axle.
➜ Measure the speed on the batch shaft with a speed counter and
set the speed controller to max. actual batch speed at 10 V signal
voltage (see fig. on left).
Speed counter ➜ Set the measured speed value in parameter .2.8. "Batch speed
range N-batch actual".
Adjust batch speed
33
Web tension controller DC 600.
c. Diameter adjustment
Diameter calibration may only be performed in expanded setup
mode.
Diameter ➜ Set the current diameter (e.g. core diameter) on the operator pa-
(green) nel when the machine is at a standstill.
➜ Enter 20 in parameter ..3. "Start Service" to adjust the batch cal-
culator and then select parameter ..4..
➜ Increase the machine speed to approx. 20 % . After approx. 10 se-
conds the atuomatic batch calculator adjustment is completed, the
machine may be stopped again.
➜ Adjustment is now completed. The web tension controller may
now be optimised (section 6.10)
Core diameter
D min
0 Sensor voltage
0V 1,5 V 10 V
Example: Absolute set diameter
34
Web tension controller DC 600.
D max
Display range DC 600.
Core diameter
D min
0 Sensor voltage
Example: 0V 1,5 V 10 V
Absolute inverted set diameter
35
Web tension controller DC 600.
n max.
➜ Accelerate machine speed to 50 % to 100 % .
➜ Measure the line speed on the main drive with a handheld tacho-
meter and set the synchronous speed on the transport drive
speed setter (check with handheld tachometer, see fig. on left).
10 V a. Sychronising actuator
➜ Adjust actuator speed setter.
Example: given a 100 % controller actuating signal, set the maxi-
n max. mum speed n2 on the speed setter so that 5 % of the maximum
line speed may be measured on the web tension generating roller
(use a handheld tachometer for measuring, see fig. on left).
n2
n1 n1 n1
b. Check actuating signal effective direction
➜ Switch from synchronous to automatic mode. Check the controller
n3 n1 effective direction at half line speed. Change the setting in para-
meter .2.0. "controller correction signal ∆V" in the event of positive
feedback.
➜ Insert the web and optimise the web tension controller.
Main drive
n3 = n1 + n2
Synchronising actuator
36
Web tension controller DC 600.
Basic premise
PID control characteristic on a step
change Voltage V
D-term
I-term
Controller output
(V oder N) P-term
t
Tv Time
t
Time
Set value deviation negative
(Set - actual = error) set value deviation
Voltage V
37
Web tension controller DC 600.
F
F-target F-actual
slow
t
F
F-target F-actual
optimized
t
F
F-target F-actual
oszillates
t
38
Web tension controller DC 600.
39
Web tension controller DC 600.
Inputs 7 6 5 4 3 2 1 0
Binary value 8 4 2 1 8 4 2 1
Input 7, 3, 2 I 0 0 0 I I 0 I bin.
and 0 inverted
40
Web tension controller DC 600.
➜ Insert web.
8. Operation
➜ Enter tension set point, press the tension set point key
- once, LED lights up. In the first line of the display the web tension
set point is indicated, in the second line the web tension actual
value.
- twice, LED flashes. Use the "Increase value, decrease value"
keys to set the desired tension set point.
- three times, LED lights up, the tension set point is stored.
or specify web tension set point via the analog input of the same
name.
or control according to a material-specific parameter record, press
material-specific parameter record key
- once, LED lights up. The number of the current parameter record
is indicated in both lines of the display.
- twice, LED flashes. Use the "Increase value, decrease value"
keys to set the new parameter record (0-7). The number is indica-
ted in the first line.
- three times, LED lights up. The parameter record is adopted, the
number is indicated in both lines. If you try to set an invalid para-
meter record, the LED will flash.
41
Web tension controller DC 600.
0 No error
Output "System operational" logic "1"
1 Not recognized:
Contact E+L service center
42
Web tension controller DC 600.
43
44
0
F-target +/- dV scale
1
0
signal-output
1
scale
F-actual
0.26.
0.26.
0.28.
0.30.
D=V/N 0.32. 0.31. 0.35.
N-winder scale
D-86136 Augsburg
Postfach 10 15 40
D-actual 0 D-actual
3
0.27.
V-limit
0.29.
N-limit
0.25.
F-actual-limit