P443 Quad Distance Zones A3
P443 Quad Distance Zones A3
2007 Page 1 of 48
Issue A.3
24 January 2007
QUADRILATERAL CHARACTERISTICS
Summary:
This document will enable the reader to construct the MiCOM P443 Quadrilateral characteristics
using the Omicron Test Universe, Advanced Distance test module v2.11.
T&D
Automation & Information Systems - St Leonards Avenue – Stafford – ST17 4LX – England
Tel: +44 (0)1785 223251 – Fax: +44 (0)1785 212232
AREVA T&D UK LTD. Registered Office: St Leonards Avenue – Stafford – ST17 4LX
Registered in England: 4955841
CUSTOMER TRAINING
Page 2 of 48
Issue A.3
Table of Contents
1. INTRODUCTION .............................................................................................................3
1.1. RELAY CONNECTIONS .................................................................................................4
2. QUADRILATERAL CHARACTERISTICS ......................................................................5
2.1. QUADRILATERAL CHARACTERISTIC SHAPE.............................................................5
2.1.1. Directional quadrilateral...................................................................................................5
2.1.2. Offset quadrilateral ..........................................................................................................5
2.1.3. Default Settings ...............................................................................................................6
2.1.4. Selecting Quadrilateral Characteristics in the relay.........................................................7
2.1.5. Removing the Residual Compensation ...........................................................................8
2.1.6. Fault Locator ...................................................................................................................8
2.2. CONSTRUCTING THE ADVANCED DISTANCE TEST MODULE.................................9
2.2.1. System Settings ............................................................................................................11
2.2.2. Phase-Earth Fault Zone 1 .............................................................................................13
2.2.3. Phase-Phase Fault Zone 1............................................................................................14
2.2.4. Phase-Earth Fault Zone 2 .............................................................................................15
2.2.5. Phase-Phase Fault Zone 2............................................................................................16
2.2.6. Phase-Earth Fault Zone 3 .............................................................................................17
2.2.7. Phase-Phase Fault Zone 3............................................................................................18
2.2.8. Phase-Earth Fault Zone 4 .............................................................................................19
2.2.9. Phase-Phase Fault Zone 4............................................................................................20
2.2.10. XRIO Files .....................................................................................................................21
2.2.11. Test Settings .................................................................................................................22
2.2.12. Hardware Configuration ................................................................................................23
2.3. SHOT TESTING THE DISTANCE ZONE CHARACTERISTICS...................................24
2.3.1. Test Setup .....................................................................................................................24
2.3.2. Shot Testing ..................................................................................................................24
2.3.3. Specific Zone Testing....................................................................................................26
2.4. SEARCH TESTING FOR ZONE P ................................................................................28
2.4.1. Performing a Search Test .............................................................................................30
2.4.2. Phase-Earth Fault Zone P .............................................................................................32
2.4.3. Phase-Phase Fault Zone P ...........................................................................................33
2.4.4. Zone 1 Extension ..........................................................................................................34
2.5. QUADRILATERAL X/R ZONE PLOTS..........................................................................35
2.5.1. Phase-Earth ..................................................................................................................35
2.5.2. Phase-Phase.................................................................................................................35
3. TESTING QUAD CHARACTERISTIC RESIDUAL COMPENSATION.........................36
3.1. CALCULATING THE RESIDUAL COMPENSATION ....................................................37
3.1.1. Residual Compensation kZN = 1, kZN Angle = 0.0o .....................................................39
3.1.2. Search Testing the Residual Compensation without Omicron Compensation ..............40
3.1.3. Search Testing the Residual Compensation with Test Module Compensation.............42
3.1.4. Residual Compensation kZN = 1.06, kZN Angle = -39o ................................................44
4. SUMMARY ....................................................................................................................47
CUSTOMER TRAINING
Page 3 of 48
Issue A.3
1. INTRODUCTION
This document will enable the reader to construct the MiCOM P443 Quadrilateral characteristics
using the Omicron Test Universe, Advanced Distance test module v2.11.
Initially the quadrilateral characteristics are constructed and then tested using a fixed current
source. Shot testing the scheme and individual zone checks are described. Zone P is determined
by performing a search test within zone 3.
The residual compensation is then examined and the enlargements calculated and entered into the
test module. Search testing is used to perform boundary checks and the effect of the earth fault
return path characteristic angle is demonstrated.
Finally the test module ‘grounding factor’ feature is utilized, which will neutralise the residual
compensation enlargement for simplified user testing.
CUSTOMER TRAINING
Page 4 of 48
Issue A.3
C3 P443
IA
IA
IB C2
C6
IC
IB
N C5
C9
IC
Test Set C8
C19
VA
VA
C20
VB
VB
C21
VC
VC
VN C22
M5
Timer
Stop RLY3
M6
CUSTOMER TRAINING
Page 5 of 48
Issue A.3
2. QUADRILATERAL CHARACTERISTICS
The quadrilateral elements are constructed from combinations of reactance lines, directional lines
and load blinders.
The offset is formed from two reactance lines and two resistive reach blinders. The upper and
lower reactance lines and the left and right resistive blinders are arranged to operate for faults
between them.
CUSTOMER TRAINING
Page 6 of 48
Issue A.3
Z4 (t = 1s)
Z3 (t = 0.6s)
Z2 (t = 0.2s)
Z1 (t = inst)
Z1
Z2
Z3
Z4
The relay by default has Mho characteristics for both the phase and ground zones. Therefore
these settings need to be changed to Quadrilateral.
Locate the DISTANCE SETUP column heading.
Then navigate down to Phase Chars and select Quad
Then navigate down to Ground Chars and select Quad
Remember to confirm the setting changes.
The setting file modifications are shown below.
The default zone reaches are suitable to allow testing and so no further modifications are required
at this stage.
CUSTOMER TRAINING
Page 8 of 48
Issue A.3
Select the Zone Settings tab, then select New Edit and start entering the quadrilateral
characteristic zones as detailed in the following sections.
CUSTOMER TRAINING
Page 13 of 48
Issue A.3
The forward reach (8 ) is 80% of the line length 10 ; the forward resistive reach (8 ) is 80% of
the fault resistance 10 . The negative resistive reach (-2 ) is 25% of the forward resistive reach.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone 1 is visible.
CUSTOMER TRAINING
Page 14 of 48
Issue A.3
The forward reach (8 ) is 80% of the line length, the forward resistive reach (4 ) is half of the 80%
of the fault resistance, this is to compensate for the fault path to the relay being out and back on
the line. The negative resistive reach (-1 ) is half of the 25% of the full forward resistive reach of
8 .
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone 1 is visible.
CUSTOMER TRAINING
Page 15 of 48
Issue A.3
The forward reach (15 ) is 150% of the line length; the forward resistive reach (15 ) is 150% of
the fault resistance. The negative resistive reach (-3.75 ) is 25% of the 150% of the fault resistive
reach.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone 2 is visible.
CUSTOMER TRAINING
Page 16 of 48
Issue A.3
The forward reach (15 ) is 150% of the line length, the forward resistive reach (7.5 ) is half of the
150% of the fault resistance, this is to compensate for the fault path to the relay being out and back
on the line. The negative resistive reach (-1.875 ) is half of the 25% of the fault resistive reach
15 .
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone 2 is visible.
CUSTOMER TRAINING
Page 17 of 48
Issue A.3
The forward reach (25 ) is 250% of the line length; the forward resistive reach (25 ) is 250% of
the fault resistance. The negative resistive reach (-1 ) and the reverse reach are as setting.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone 3 is visible.
CUSTOMER TRAINING
Page 18 of 48
Issue A.3
The forward reach (25 ) is 250% of the line length, the forward resistive reach (12.5 ) is half of
the 250% of the fault resistance, this is to compensate for the fault path to the relay being out and
back on the line. The negative resistive reach (-0.5 ) is half of the setting, whilst the reverse reach
is as setting.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone 3 is visible.
CUSTOMER TRAINING
Page 19 of 48
Issue A.3
This zone is a reverse zone and if the impedance plot is inverted as shown above, it can be seen
that zone 4 is a reversed zone 2 in this application.
The reverse reach (-15 ) is 150% of the line length; the negative fault resistive reach (-15 ) is
150% of the fault resistance. The positive resistive reach (3.750 ) is 25% of the 150% of the fault
resistive reach.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line. Select the settings shown below so the following configured zone 4 is visible.
CUSTOMER TRAINING
Page 20 of 48
Issue A.3
This zone is a reverse zone and if the impedance plot is inverted as shown above, it can be seen
that zone 4 is a reversed zone 2 in this application.
The reverse reach (-15 ) is 150% of the line length; the negative fault resistive reach (-7.5 ) is
half of the 150% of the fault resistance. The positive resistive reach (1.875 ) is half of the 25% of
the 150% of the fault resistive reach.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line. Select the settings shown below to configured zone 4 and press OK.
CUSTOMER TRAINING
Page 21 of 48
Issue A.3
We shall not use this functionality in this demonstration, consult the appropriate Omicron manual or
ask your supervisor for a demonstration.
A constant test current is going to be used with a 2A setting, the option to allow a reduction should
be selected to ensure all reaches are available. The pre, post and max fault times should also be
modified to more suitable values.
CUSTOMER TRAINING
Page 23 of 48
Issue A.3
This setting allows the Omicron to be switched off when the relay trips.
CUSTOMER TRAINING
Page 24 of 48
Issue A.3
1 4
3
2
CUSTOMER TRAINING
Page 25 of 48
Issue A.3
If the test is successful, the relay will trip and the following test result should be visible, with a
green cross at the test location.
Interrogate the relay by pressing the Read key and verify that the fault record matches the applied
fault.
If the test is unsuccessful, then the following result will be visible, with a red cross at the test
location. If the relay does not trip, check the analogue wiring, if the relay has tripped, check that
the trip relay R3 is wired to the Omicron binary input 1.
Reposition the test location within a different zone (Z1, Z2, Z3 or Z4) and with a different fault type
(L2-N, L1-L2, L3-N etc..) and perform more single shot tests and very them with the fault record.
CUSTOMER TRAINING
Page 26 of 48
Issue A.3
Press OK and return to the Test Module, only zone 3 should be visible on the X/R plot.
The relay will still operate for all zones, therefore the other zones have to be disabled in the relay
settings.
CUSTOMER TRAINING
Page 27 of 48
Issue A.3
Select the DISTANCE SETUP column header and navigate down to Zone 1 Ph status and select
Disabled. Repeat for zones 2, and 4; zone P should already be disabled. Continue down to the
ground fault zones Zone 1 Gnd Stat. and disable, repeat for zones 2 and 4.
The equivalent modifications to the setting file are shown below.
Then enable zone P and disable zones 1, 2, 3 and 4 in the relay for phase-phase and phase-earth
faults. The equivalent modifications to the setting file are shown below.
CUSTOMER TRAINING
Page 30 of 48
Issue A.3
1 7
2 5
4
3
6
Before the search is executed, right click on the X/R plot and make sure only the following options
are selected. Then start the test by pressing the execute arrow (7) shown above.
CUSTOMER TRAINING
Page 31 of 48
Issue A.3
The test should complete, as shown below. The red crosses indicate that the tests failed, which is
correct because we are searching for zone P and not zone 3.
It can be seen that the boundaries have been found.
The reach can be seen to be 20 along the line angle of 70o and along the resistive reach.
Clear the test results by pressing the X marked above and then these settings can now be entered
as a distance zone as shown below.
CUSTOMER TRAINING
Page 32 of 48
Issue A.3
The forward reach (20 ) is 200% of the line length; the forward resistive reach (20 ) is 200% of
the fault resistance. The negative resistive reach (-5 ) is 25% of the 2000% of the fault resistive
reach.
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone P is visible. The zone has been
entered as zone 8.
CUSTOMER TRAINING
Page 33 of 48
Issue A.3
The forward reach (20 ) is 200% of the line length, the forward resistive reach (10 ) is half of the
200% of the fault resistance, this is to compensate for the fault path to the relay being out and back
on the line. The negative resistive reach (-2.5 ) is half of the 25% of the fault resistive reach 20 .
The angles correspond to the -3 degree tilt, the line characteristic angle and the approximate
directional line.
Select the settings shown below so the following configured zone P is visible. The zone has been
entered as zone 8.
CUSTOMER TRAINING
Page 34 of 48
Issue A.3
Add the following logic to the PSL note the DDB number may vary between software versions.
Control Input 1
DDB #160 Reset Zone 1 Ext
> 1 DDB #446
2.5.1. Phase-Earth
2.5.2. Phase-Phase
CUSTOMER TRAINING
Page 36 of 48
Issue A.3
[
Compensated Reach = Reach Setting × 1 + KZn ]
Where:
The enlargement of the quad due to the residual compensation will be calculated, entered into the
Omicron Advanced Distance test module and verified.
CUSTOMER TRAINING
Page 37 of 48
Issue A.3
Therefore the actual zone 1 earth fault reach will be extended to:
[ ]
Compensated Reach = Reach Setting × 1 + KZn = 8Ω∠70° × [1 + 1.0∠0°] = 16Ω∠70°
If default settings have been applied to the relay, then the residual compensation values required
are the default values, otherwise enter the following into the relay.
Locate the LINE PARAMETERS column heading.
Change kZN Res Comp to 1.0.
Change kZN Res Angle to 0.0o.
Remember to confirm the setting change.
The setting file modifications are shown below.
CUSTOMER TRAINING
Page 38 of 48
Issue A.3
Only zone 1 should be enabled within the relay, therefore disable zones 2, 3, P and 4 for both
phase and ground characteristics.
Remember to confirm the setting change.
The setting file modifications are shown below.
CUSTOMER TRAINING
Page 39 of 48
Issue A.3
Delete zone 8, which is zone P from the first section. Rename the new zone, zone 5 and only
activate the new zone 5 and zone 1 so that the following is visible. Remember to complete the
settings shown for the new zone 5.
CUSTOMER TRAINING
Page 40 of 48
Issue A.3
To perform the Search test, select the Search tab (1). Then to apply the search line, select L1-N
type fault (2), then left click the mouse at the X/R origin (3) and drag the mouse along the line
characteristic angle to the boundary as shown (4). Press the Add button (5), so the test appears
(6). Then start the test by pressing the execute arrow (7).
7
1
5
2
4
3.1.3. Search Testing the Residual Compensation with Test Module Compensation
The Omicron test module residual compensation (called grounding factor) will be enabled and this
will automatically amend the enlarged quad.
Delete the previous test results and select the System Settings tab and check that the grounding
factor is set as follows, which matches the relay setting.
CUSTOMER TRAINING
Page 43 of 48
Issue A.3
Repeat the search test and as can be seen tripping is at the original characteristic without the
residual compensation enlargement, because the Omicron is correctly compensating for it.
CUSTOMER TRAINING
Page 44 of 48
Issue A.3
Calculate KZn .
Z 0 − Z1 (40Ω∠40°) − (10Ω∠70°) 31.7Ω∠30.9°
KZn = = = = 1.06∠ − 39°
3Z1 3 × (10Ω∠70°) 30Ω∠70°
Therefore the actual zone 1 earth fault reach will be extended to:
[ ]
Compensated Reach = Reach Setting × 1 + KZn = 8Ω∠70° × [1 + 1.06∠ − 39°] = 15.5Ω∠50°
Select the Zone Settings and complete the settings as shown below and press OK.
The new zone should default to zone 6 and the following should be visible. Remember to
complete the settings shown for the new zone 6 and disable zone 5.
CUSTOMER TRAINING
Page 46 of 48
Issue A.3
Perform suitable search testing to verify the characteristic with and without the Omicron residual
compensation feature enabled. The following should result.
Without the Omicron residual compensation feature enabled.
4. SUMMARY
When testing the quadrilateral characteristics, either constant source impedance or current is
suitable.
The residual compensation for the earth fault return path will cause the earth quad characteristics
to enlarge, unless the residual compensation factors are entered into the Omicron grounding
factors for the test module to amend.
AUTOMATION SUPPORT
Page 48 of 48
Issue A.3
VERSION CONTROL
Issue Author(s) Reason for change Date
A.1 CA Smith Original 13-02-06
A.2 CA Smith Updated for Omicron software v2.11 13-12-06
A.3 CA Smith Update 24-01-07