105U/905U-G-PR1 Profibus Slave
PURPOSE
The purpose of this document is to illustrate an application setup using a Siemens S7–
300 PLC communicating via Profibus to an Elpro 105U/905U-G-PR1 module.
BACKGROUND
The 105U/905U-G-PR1 acts as a Profibus DP Slave - the network host a Siemens S7–
300 PLC is a Profibus Master. If using is a 105U/905U-G with a PLC, the PLC will require
an Anybus GSD file so it can recognize the Profibus interface in the 105U/905U-G. This
file loads into the PLC. The file is available on the same CD as the configuration software
or from the Elpro web page www.elprotech.com
Configuration of the Profibus data bus comprises of allocating a Profibus Slave address
to the
905G and configuring links between the I/O registers and the Profibus bytes in the
Anybus Interface module.
MATERIALS USED
PC with RS232 comms port
1 x Siemens CPU314C-2 DP
1 x Simatic S7 PC adapter
S7 Simatic Manager software
1 x 105U/905U-G-PR1
1 x 105U/905U-1
Profibus network connection cable
Power supplies for 105U/905U units
E-Series Configuration Utility (Build 148 or higher)
RS232 DB9 serial cable
Anybus GSD file hms_1003.gsd
app_105-905-G-PR1_1.3.docx 1 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
APPLICATION
This application should be read in conjunction with the 105U/905U/105S and the
105U/905U-G User Manuals, this provides extensive details on hardware setup and
configuration of the 105U/905U Radio’s. It is expected the reader have a firm
understanding of both the S7 Simatic software tool and the E-Series Configuration Utility.
To view the Elpro configuration save the file Profibus e-series config example .zip to a
folder on your PC. Open the E-series configuration utility build 148 or higher, select file/
restore project and locate the zip file saved on PC, select ok leaving Project Name blank.
This will extract the files into this folder and load the configuration into the utility program.
To review E-Series Fieldbus Configuration, highlight “Fieldbus Config” as below.
Area PLC reads from
Area PLC writes to
The first Fieldbus mapping is a write bytes command for an I/O count of 4 from I/O
registers 0,1,2,3. The PLC will read from Fieldbus location 0 for a count of 4 bytes. I/O
registers 0,1,2,3 will have values that remote modules will have had mapped to. i.e. A
level from remote module will send to I/O register 0 which is then Fieldbus mapped to a
location for the PLC to read from.
The second Fieldbus mapping is the area that the PLC will write to. There are separate
IN and OUT Fieldbus areas in the Gateway as to why you can see the same Fieldbus
location address.
app_105-905-G-PR1_1.3.docx 2 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Open Simatic Manager software and follow through Step 7 Wizard: “New Project”.
Select Valid PLC Hardware and MPI address, in this example CPU314C-2DP, MPI
address 2, and select Next >
Add OB’s and Language in accordance with your program structure, then select Next >
app_105-905-G-PR1_1.3.docx 3 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Define project name Profibus example and select Finish. Wait while project is created.
Open Project Menu, highlight project Profibus example created, click OK
app_105-905-G-PR1_1.3.docx 4 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Select Hardware and right click mouse
Click on “Open Object”, the HW configuration screen as below will appear
app_105-905-G-PR1_1.3.docx 5 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Select Options on Menu bar and New GSD, find and select hms_1003.gsd and Open
Under View on menu bar, ensure Catalog is ticked. This will allow route directory on right
side of directory screen to be viewed as below. Click on the General folder, expand the
ANYBUS_S PDP file for the below screen capture to appear.
At the (0) UR screen, below CPU314C-DP, select and right click X2 DP, choose Add
Master System. With the Parameters TAB selected below screen will appear, ensure
Address is 2. Select New.
app_105-905-G-PR1_1.3.docx 6 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Select Network Settings TAB and ensure Transmission Rate = 1.5Mbps, Profile = DP,
click OK
app_105-905-G-PR1_1.3.docx 7 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Subnet data screen will appear, with network setup, click OK
Next configuration screen will appear, with pictorial Profibus (1): DP master system (1)
setup.
app_105-905-G-PR1_1.3.docx 8 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Drag ANYBUS-S PDP folder in route directory and to Profibus (1): DP master system (1)
line and enter address 1. Note this Address 1 needs to be the same address entered
in the E-series configuration under Fieldbus Config.
Screen will show (1) ANYBUS connected to Profibus (1): DP master system (1) line and
ANYBUS-S PDP object addressing menu at the bottom.
Drag IN/OUT 4 byte into Slot 1,
Input PLC addresses I: 256 to I: 259 are written to ANYBUS registers location 0, 1, 2, 3 -
IN Area.
The Output PLC addresses Q: 256 to Q259 are read from ANYBUS register location 0, 1,
2, 3 – OUT Area.
app_105-905-G-PR1_1.3.docx 9 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Note: It is important when configuring objects that these objects are embedded efficiently
as there is a total of 24 slots available only.
Select Save and Compile under Station on Menu Bar. With Siemens hardware readied,
that is, Simatic S7 PC adapter connected to serial cable and PC comm’s port and PLC
power cycled on, select the Download icon and proceed with downloading project to the
PLC. Select Target Module as below and click OK.
app_105-905-G-PR1_1.3.docx 10 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Select Node address when prompted and click OK
OK if applicable.
Download continue screen
app_105-905-G-PR1_1.3.docx 11 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
Click Yes
Profibus Configuration is download to the PLC is complete.
Using the Monitor/ Modify Screen you
can verify Profibus operations in
combination with the diagnostics screen
for the Profibus Slave gateway.
app_105-905-G-PR1_1.3.docx 12 of 13
Application Note 105U/905U-G-PR1 Profibus Slave
The Diagnostics screen of the Profibus gateway allows
you to Read Image Array (Values from PLC to I/O
registers 0 – 3).
Also Write Image Array to allow you to enter in a value
for a specific I/O register ( I/O registers 10 – 13) which
will then be made available for the PLC to read.
Amendment Register:
Issue No. Date Details of Amendment
1.0 05/01/04 Draft Issue
1.1 10/04/06 Combined 105U & 905U into one document
1.2 11/11/08 Added Diagnostics screenshot
1.3 11/02/19 Elpro Branding/Formatting
app_105-905-G-PR1_1.3.docx 13 of 13