RXUQ6AY

The document provides specifications for two cooling-only VRV A series models, RXQ6AYM(W) and RXQ8AYM(W), detailing their power supply, cooling capacities, dimensions, and components. Both models utilize R410A refrigerant and feature hermetically sealed scroll compressors with soft start methods. Additional information includes sound pressure levels, safety devices, and standard accessories included with the units.

Uploaded by

binkei.bdx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views1 page

RXUQ6AY

The document provides specifications for two cooling-only VRV A series models, RXQ6AYM(W) and RXQ8AYM(W), detailing their power supply, cooling capacities, dimensions, and components. Both models utilize R410A refrigerant and feature hermetically sealed scroll compressors with soft start methods. Additional information includes sound pressure levels, safety devices, and standard accessories included with the units.

Uploaded by

binkei.bdx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

RXQ6-20AYM(W) / RXQ18-60AMYM(W) EDRMT341773D

1.
1.1 Cooling Only 50/60 Hz VRV A SERIES (RXQ-A(M))

Model Name RXQ6AYM(W) RXQ8AYM(W)


Power supply 3 phase, 380-415/380 V, 50/60 Hz 3 phase, 380-415/380 V, 50/60 Hz
kcal/h 13,800 19,300
1 Cooling capacity Btu/h 54,600 76,400
kW 16.0 22.4
Casing color Ivory white (5Y7.5/1) (Metallic brown 3) Ivory white (5Y7.5/1) (Metallic brown 3)
Dimensions: (H×W×D) mm 1,657×930×765 1,657×930×765
Heat exchanger
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output×
Compressor Number of units kW 2.3×1 3.4×1

Starting method Soft start Soft start


Type Propeller fan Propeller fan
Motor output kW 0.55×1 0.55×1
Fan
m³/min 119 178
Drive Direct drive Direct drive
Connecting Liquid pipe mm 9.5 C1220T (Brazing connection) 9.5 C1220T (Brazing connection)
pipes Gas pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Mass kg 175 (180 3) 175 (180 3)
2 Sound pressure level dB(A) 56 56
High pressure switch, Fan driver overload High pressure switch, Fan driver overload
Safety devices protector, Over current relay, Inverter overload protector, Over current relay, Inverter overload
protector protector
Capacity control % 25-100 20-100
Refrigerant name R410A R410A
Refrigerant Charge kg 5.9 5.9
Control Electronic expansion valve Electronic expansion valve
Refrigerator oil Refer to the nameplate of compressor Refer to the nameplate of compressor

Standard accessories Installation manual, Operation manual, Installation manual, Operation manual,
Connection pipes, Clamps Connection pipes, Clamps
C: 3D111543E (C: 3D121761 3) C: 3D111543E (C: 3D121761 3)
Drawing No.
Sound level C: 4D112438B C: 4D112439D

Notes:
Conversion formulae
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
During actual operation, these values are normally somewhat higher as a result of ambient conditions and Btu/h=kW×3412
oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating