The Rondo Professional Series provides extensive technical knowledge and practical insights for the efficient use of Rondo's lightweight steel wall and ceiling framing products, organized into separate books for easy access. The Red Book serves as a comprehensive technical publication offering fire, acoustic, and thermal information to support design professionals in the construction industry. CSR Gyprock and Rondo are committed to sustainability, partnering with the Foundation for National Parks & Wildlife to enhance environmental efforts.

Uploaded by

jidaw60309
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views334 pages

The Red Book Design Guide - CSR

The Rondo Professional Series provides extensive technical knowledge and practical insights for the efficient use of Rondo's lightweight steel wall and ceiling framing products, organized into separate books for easy access. The Red Book serves as a comprehensive technical publication offering fire, acoustic, and thermal information to support design professionals in the construction industry. CSR Gyprock and Rondo are committed to sustainability, partnering with the Foundation for National Parks & Wildlife to enhance environmental efforts.

Uploaded by

jidaw60309
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 334

APRIL 2025

DESIGN
GUIDE
FIRE, ACOUSTICS
AND THERMAL
The Rondo Professional Series compiles extensive technical knowledge, testing
data, and practical insights for efficient utilisation of Rondo’s innovative building
systems. This invaluable resource benefits professionals involved in designing,
or constructing with Rondo’s advanced lightweight rolled-formed steel wall and
ceiling framing products. Organised into separate books, the series enables easy
access to the specific knowledge required for each system or product.

106914 SERIES B2 Cover OCT 2023.pdf 1 30/10/2023 11:13 am C1 cover.pdf 1 10/1/2024 3:43 pm G1- Cert-R-Fix cover.pdf 1 29/1/2024 10:55 am

SERIES B2: SERIES C1: SERIES G1:


V2
KEY-LOCK ® CONCEALED CEILING SYSTEMS WALL DESIGN DATA CERT-R-FIX ®

1 1

DO WNLOAD YOUR COP Y


R O N D O.COM.AU/ P ROS ERIES
We are mindful of the impact on the environment
when printing The Red Book. We limit the printing
of editions of The Red Book and have a digital
version available. CSR Gyprock® and Rondo®
have partnered with the Foundation for National
Parks & Wildlife (FNPW) to plant one tree each for
every printed edition.
The Red Book is one of the industry’s most
recognised and respected technical publications.
It provides fire, acoustic and thermal information
on hundreds of wall and ceiling systems to
support architects, engineers, and other design
professionals in their day-to-day design work. As
a result of the revisions and expansions to the
original 1999 edition, The Red Book continues to
provide comprehensive design information and
complete system solutions from CSR Gyprock,
Australia’s leading Plasterboard Manufacturer.

Photo Credit; Rebecca Collins

Backed By a Trusted Name This is in addition to the paper the book has
been printed on being certified by the Forest
CSR has proudly been a part of the Stewardship Council® (FSC®) as having come
Australian building market since 1942 and from responsible sources.
is the name behind some of Australia’s
most recognised building products brands.
We have a strong history of creating
innovative and sustainable building
materials that work together to provide
better whole-of-project solutions across
the Australian commercial and residential
construction industries.
Why partner with CSR DesignLINK

In an increasingly complex CSR DesignLINK is a unique team of


professionals including engineers and
building world, you need a building designers working to support the
trusted partner that offers specifications of CSR projects. DesignLINK
partners with customers to:
proven quality and expertise • workshop complex design issues
to help you achieve your • provide value engineering with estimating
and design tools
project goals. One that • rationalise system specifications to
is dedicated to continual meet specific fire, thermal, acoustic and
innovation and leading the footprint needs
• offer compliance support through the
building industry into a provision of complex test data
sustainable future. To that • deliver better building performance
• provide installation guidance for builders
end, we have a multitude and contractors
of resources available,
including;
Digital Tools Compliance

We have developed, and continue As leaders in the building industry, we understand


to expand, a suite of digital that compliance is at the core of building
tools that enables you to specify requirements. Our portfolio covers such a breadth
systems, manage your orders and of brands and products, we have the knowledge,
access all compliance documents expertise and capability to offer compliance details
and installation manuals. Recent on an extensive number of complete system
digital additions to the toolbox solutions. When you partner with CSR, you can
include the CSR System Selector rest easy knowing what’s specified fulfills all your
and Thermal Calculator. compliance requirements.

Industry-leading warranty

All CSR products and systems are of an industry-


leading standard. As such they are guaranteed
to perform and are backed by a comprehensive
warranty, whether they are manufactured in
Australia or sourced from a trusted international
partner. All products are covered by warranties
that provide buyer confidence and peace of mind.

Sustainability Our efforts have seen us gain accreditation


and certification with a number of regulatory
Sustainability is an increasingly important topic and industry bodies. For a complete picture
in the building industry from both a product of our commitment to sustainability, we invite
and design perspective. We are proud to focus you to look at our ‘Sustainability Report 2022 –
on developing sustainable manufacturing Building Solutions for a better future’.
processes, products that produce minimal CSR is a member of Green Building Council
environmental impact and systems that enable of Australia, an association that fosters
building efficiency. environmental sustainability amongst
commercial building and construction industry
Scan to download
companies and is an HIA GreenSmart leader
– a voluntary community with a hands-on
approach to residential building that focuses
on educating builders, designers, product
manufacturers and consumers about the
benefits of an environmentally responsible
approach to business.
CSR Gyprock® and Rondo® FNPW runs one of the largest
are proud to partner with environmental community-led restoration
The Foundation for National programs in Australia, the FNPWs
Landscape Resilience Program (LRP)
Parks & Wildlife
which targets fragmented ecosystems
The Foundation for National Parks & adjacent to protected areas, habitat
Wildlife (FNPW) was founded in 1970 and corridors, riparian zones, and wetlands to
is the charity partner of national parks and increase resilience and support biodiversity
wildlife services across Australia. Having on a national scale.
invested more than $65 million since The LRP will plant and grow 1 million+
2000, FNPW has the mission to combat native trees in flood and fire affected areas
biodiversity loss through the growth of by 2025 by establishing and supporting
national parks, the conservation of native community nurseries which propagate
flora and fauna, and the restoration of native seedlings that will be planted locally
disaster affected lands now and for future on public and private lands.
generations. Thanks to collaborations like the one
FNPW joins the dots between corporate Gyprock currently has with FNPW, we
partners, local communities, government, can have a positive environmental impact
environmental scientists, and First Nation on Australia’s biodiversity, creating a
peoples to restore and protect Australia’s sustainable and healthy country for all
unique natural beauty. future generations.

Photo Credit; Douglas Gimesy

Photo Credit; Rebecca Collins

The interconnectedness of FNPWs


projects to grow national parks, save Scan here to find out
threatened species, and restore more about FNPW’s
work and how to get
disaster-affected lands allows us involved.
to maximise the impact for the
environment and our ecosystems.

Photo Credit; Stacey Irving


INTRODUCTION
A
PRODUCTS & DESIGN
B
STEEL FRAMED WALL SYSTEMS
C
TIMBER FRAMED WALL SYSTEMS
D
CONCRETE AND MASONRY WALL SYSTEMS
E
EXTERNAL WALL SYSTEMS
F
CEILING SYSTEMS
G
SERVICES SYSTEMS
H
FLANKING PATH SYSTEMS
J
INDEX OF SYSTEM NUMBERS
IN
EPDs
NOW AVAILABLE
As part of our
commitment to
sustainable building
practices, CSR has
launched a series of
Environmental Product
Declarations (EPDs).

SCAN QR CODE TO SEE


ALL AVAILABLE EPDS
INTRODUCTION

A
SECTION CONTENTS
Three Red Books ������������������������������������������� A2
Introduction to The Red Book ����������������������������� A2
Using The Red Book ��������������������������������������� A3

QUICK SELECTION GUIDES


Multi-Residential Class 2������������������������������� A4
Hospitals������������������������������������������������� A6
Office����������������������������������������������������� A8
Aged Care ����������������������������������������������A10
Retail����������������������������������������������������A12
House Class 1������������������������������������������A14
Education������������������������������������������������A16
Brand & Product Overview��������������������������������A18
Technical Support����������������������������������������� A21

GYPROCK® THE RED BOOK™ 1 A1


THREE RED BOOKS INTRODUCTION TO
The Red Book now includes 3 parts: THE RED BOOK
• Book 1 Design Guide
Fire, Acoustics and Thermal The Red Book 1, Fire, Acoustic & Thermal Design Guide
showcases the performance of CSR Gyprock’s extensive
• Book 2 Residential Installation Guide range of building systems. Together with the associated
Class 1 & 10 Buildings Red Book installation manuals, it forms a suite of essential
• Book 3 Commercial & Multi-Residential Installation Guide reference documents for the building industry.
Class 2 – 9 Buildings Over the last 75 years, Gyprock has developed effective,
Over time, each version of the Red Book has grown practical and cost-effective systems for most applications.
significantly with the addition of new systems, sections Extensive testing has been carried out on the systems
and details. As a result of this, the Red Book has been and components in the Design Guide, including for fire,
extended to three books for enhanced navigation, acoustic, thermal, weather resistance and structural
functionality and efficiency. properties. To complement this program, Gyprock has
obtained assessments from appropriate authorities on the
likely performance of many details and system variations;
BOOK 1 DESIGN GUIDE
expert opinions based on test results.
FIRE, ACOUSTICS AND THERMAL
Systems in the Red Book Design Guide should be viewed
Dedicated to complete system solutions for walls, ceilings in conjunction with the relevant product or installation
and façades for all building classes. Book 1 provides fire, manual noted on system pages.
acoustic and thermal information on hundreds of wall
and ceiling systems and includes products from the CSR
companies Gyprock, Cemintel, Himmel, Bradford, Martini,
AFS and Hebel.
For current products/systems performance, visit CSR
online digital tools such as on CSR System Selector and
Thermal Calculator at https://apps.csr.com.au/

BOOK 2 RESIDENTIAL
INSTALLATION GUIDE
CLASS 1 & 10 BUILDINGS COMMERCIAL
MULTI- RESIDE&
INSTALLATION NTIAL
Book 2 provides comprehensive installation details for CLASS 2-9
GUIDE

BUILDINGS

Gyprock plasterboards fixed to walls and ceilings of timber,


steel and masonry construction in residential buildings. RESIDENTIA
L
INSTALLATION
Applications include internal wet areas, protected external GU IDE
CLASS 1 & 10

ceilings and eaves, curved surfaces, bushfire solutions, BUILDINGS

and fire rated boundary walls.


N
DESIG
GUIDEICS
BOOK 3 COMMERCIAL & MULTI-
OUST
FIRE, AC MAL 27/7/2023
11:26 am

ER
AND TH

RESIDENTIAL INSTALLATION Red Book


2023_Cover
s_Finals_07
23.indd
1

GUIDE CLASS 2 – 9 BUILDINGS


Book 3 provides comprehensive installation details for
Gyprock plasterboard in commercial style construction.
The details focus on slab-to-slab steel framed
construction that is common in offices, warehouses,
schools, hospitals, and medium to high-rise residential
construction. Applications include wall, ceiling, column,
beam and wet area linings that may be required to achieve
fire and acoustic ratings.

A2 GYPROCK® THE RED BOOK™ 1


USING THE RED BOOK
INTRODUCTION
A
Section Index: Use the Section Index to search for
walls by framing type, ceilings under roofs and floors,
PRODUCTS & DESIGN
B INDE
X–T
O PA

C
Section G ES

for services enclosures and acoustic junction systems. STEEL FRAMED WALL SYSTEMS
C – Ste
FOR
2023
el Fra
med
Wall Sys
System tems
SYST
CSR

1000
Page
Nº System
Page
EM Nº
C6 Nº
CSR System

Navigate quickly by colour or section letter – section letter


1002 CSR Nº

D
CSR C6 1075 Page
1005 C13 Nº
CSR System
CSR C6 1078 CSR Nº
1008 CSR C14 1224 Page
TIMBER FRAMED WALL SYSTEMS 1079 C24 Nº
CSR C6 CSR System
1009 CSR C14 1225 CSR Nº
1080 CSR C24 1348 Page
CSR C6 C14 1226 CSR C31 Nº
1011 CSR 1355 CSR Nº System
C6 1085 CSR C24 3043
CSR C15 1227 CSR C32 Nº Page
1025 CSR C24 1356 CSR C14
C7 1086 CSR C32 3044 CSR Nº

and page numbers are referenced at the bottom of each


CSR C15 1230 CSR C15 10022
1027 CSR C24 1357 CSR C34
CSR C7 1087 CSR C32 3062 CSR
1030 CSR C15 1250 CSR C17 10023
C25 136 CSR C34

E
C7 1105 CSR 0 C33 3072 CSR
CSR C16 1251 CSR C18 10024
1032 CSR C25 1361 CSR C34
CSR C8 1108 CSR C33 3073 CSR
1033 CSR C16 125 2 C25 CSR C19 10025
1362 CSR
CONCRETE AND MASONRY WALL SYSTEMS C8 1110 CSR C33 3082 CSR C36
CSR C16 1260 CSR C19 10026
1035 CSR C25 1382 CSR C36
CSR C8 112 0 CSR C34 309 5 C20 CSR
1037 CSR C16 1264 CSR 10027
C26 1383 CSR

page.
C8 1125 CSR C34 3132 CSR C36
CSR C17 1275 CSR C22 10028
1040 CSR C26 1385 CSR C35
CSR C8 1126 CSR C35 3162 CSR
1042 CSR C17 1280 CSR C25 10029
1127 CSR C26 1386 CSR C29
CSR C8 1281 CSR C35 3172 CSR
1044 CSR C17 1387 C27 10030
1128 C26 CSR C29

F
CSR C9 CSR C35 3222 CSR
1045 CSR C18 1282 CSR C30 10031
1129 CSR C26 1390 CSR C18
CSR C9 1285 CSR C37 3232 CSR
1048 CSR C18 1391 C31 10034
C27 CSR C20
EXTERNAL WALL SYSTEMS CSR C9 1130 CSR C37 3242 CSR
1050 CSR C18 1286 CSR C32 10037
113 CSR C27 1392 CSR C17
CSR C10 3 C19 1287 CSR C37 326 0 C33 CSR
1051 CSR 10095

Index to Systems – Section IN: An index of all


1135 CSR C27 1510 CSR C41
CSR C10 1290 CSR C38 3270 CSR
1052 CSR C19 1516 C35 10096
1140 CSR C28 CSR CSR C41
CSR C10 1291 CSR C38 3312 10097
1055 CSR C19 1523 CSR C39
C10 1142 CSR C28 3332 CSR C41
CSR C20 1292 CSR C38 10098
1058 CSR C28 1524 CSR C39
C11 1160 CSR 10000 CSR C41

G
CSR C21 1305 CSR C38 10099
1060 CSR C29 1525 CSR C9 C42
CSR C11 1161 CSR C38 10001 CSR
1061 CSR C21 1306 CSR C10 10100
1162 CSR C29 1530 CSR C42
10002
CEILING SYSTEMS
C11 C39 CSR

systems is provided in Section IN at the rear of the book.


CSR C21 1307 CSR C11 10101
1062 CSR C29 1535 CSR C42
CSR C12 116 5 C21 CSR C39 100 03 C11 CSR
1065 CSR 1320 CSR 10102
1166 CSR C29 1540 CSR C42
CSR C12 1321 C39 10004 CSR
1066 CSR C21 CSR CSR C12 10103
1167 CSR C30 1700 10005 C43
CSR C12 1322 CSR C40 CSR
1067 CSR C22 1710 CSR C14 10104
C12 1175 CSR C30 10006 CSR C43
CSR C22 1330 CSR C40 10138
1070 CSR C30 1720 CSR C17
C13 1176 CSR C40 10007 CSR C7

H
CSR C22 1333 CSR C18 10139
1071 CSR C30 3006 CSR

Here all systems are listed in numerical order using the


C13 1177 CSR C9 10008 CSR C7
CSR C22 1340 CSR C19 10140
1072 CSR C31 3011 CSR C7
C13 1220 CSR 10009 CSR
SERVICES SYSTEMS C23 1341 CSR C9 C22 10141
CSR C31 301 7 CSR C23
1223 CSR C10 10010 CSR
C23 1342 CSR C25 10142
CSR C31 3023 CSR C23
1345 C11 10011 CSR
CSR CSR C27 10143
C31 3033 10012 C23
CSR C12 CSR
3034 CSR C30 10144
C13 10013 C38

unique system numbers, alongside their location within


CSR C32
10014

J
C39

FLANKING PATH SYSTEMS

the book by section/page number INDEX OF SYSTEM NUMBERS


IN
IN2
GYPROC
K ® THE
RED
BOOK ™
1

Draft v7 12/03/20
GYPROCK® THE RED BOOK™ A1

SYSTEM SHORT CUTS


Many systems are on offer in The Red Book and finding Building Type Short list of systems
the right one can be time consuming. To make the task
easier, a set of systems is presented that may lead to
solutions for some common building types. The systems Office

available include walls, ceilings, façades and services


Corridor Wall
System No. Page No. System Feature
Services Shaft
CSR 1050 C10 FRL –/60/60
System No. Page No. System Feature CSR 10001 C7 Impact resistant
CSR 7665 H20 FRL –/90/90 CSR 3011 C9 Green building, Wet area, Rw 45
CSR 7217 H10 Wet area, sound insulating Rw 48

enclosures.
CSR 10019 H20 Impact resistant, FRL –/90/90

Services Duct Office Walls


System No. Page No. System Feature System No. Page No. System Feature
CSR 7020 H6 Sound insulating Rw 44 CSR 1030 C7 Low cost

The system sets are based on years of experience


CSR 1110 C16 Sound insulating Rw 51
CSR 3017 C10 Green building, sound insulating Rw 51

Meeting Room Junction Office Ceiling

in collaborating with designers and builders, and aim


System No. Page No. System Feature System No. Page No. System Feature
CSR 8269 J8 Sound insulating Rw 45 CSR 6811 G52 Sound absorptive NRC 0.70
CSR 10044 G52 NRC 0.9

to provide typical fire and acoustic values, properties


necessary for a space’s use, and other features such as Façade

cost, appearance and footprint.


System No. Page No. System Feature
CSR 5303 F11 Aesthetic feature
CSR 21347 F32 Impact resistant, FRL –/120/120

The recommendations will not be suitable in all cases,


but systems displayed on pages near to the highlighted System No. Page No.
CSR 1037

CSR 3017
C8

C10
Meeting Room Wall
System Feature
Sound insulating Rw 46
Green building, Rw 51,

solution have variations that are likely to suit.


damage resistant, water resistant
CSR 10031 C18 Rw 58, FRL –/90/90

Meeting Room Ceiling


System No. Page No. System Feature
CSR 6854 G54 Sound absorptive NRC 0.90
CSR 10043 G52 NRC 0.7

The Guide is intended as a shortcut to the right system A8 GYPROCK® THE RED BOOK™ 1 GYPROCK® THE RED BOOK™ 1 A9

and the user should ensure that any system selected


meets all performance requirements.

GYPROCK® THE RED BOOK™ 1 A3


Multi-Residential Class 2

Sole Occupancy Unit Floor/Ceiling


System No. Page No. System Feature
CSR 6311 G15 Floor, low cost
CSR 6360 G22 Floor with services cavity

Corridor Wall
System No. Page No. System Feature
CSR 1125 C19 Low cost, FRL –/60/60, Rw 50
Green Building, FRL –/60/60, Rw 50,
CSR 10006 C19
impact resistant

Services Bulkhead/Ceiling
System No. Page No. System Feature
Habitable & Non-Habitable systems,
CSR 7020 H6
Rw + Ctr 25 to 40 available

A4 GYPROCK® THE RED BOOK™ 1


Sole Occupancy Unit Ceilings
System No. Page No. System Feature
CSR 6615 G43 Roof, pitched, Rw 50, R 6.0
CSR 6620 G44 Roof, pitched with RISF 60
CSR 6644 G46 Roof, low slope with RISF 60

Sole Occupancy Unit Walls


System No. Page No. System Feature
CSR 1386 C37 FRL –/90/90, Rw + Ctr 50
CSR 1523 C40 FRL –/60/60, Rw + Ctr 50
Masonry + stud + furring
CSR 4269 E15
channel Rw + Ctr 50
Masonry + furring channel
CSR 4294 E18
two sides Rw + Ctr 50

Façade Wall
System No. Page No. System Feature
CSR 5303 F11 Pre-finished option, lightweight
CSR 5173 F10 FRL 90/90/90
CSR 10313 F58 Class 4 Permiance

Services Shafts
System No. Page No. System Feature
CSR 4065 E8 Concrete lift shaft, Rw 54
CSR 4070 E8 Concrete stair shaft, Rw 61, wet area
CSR 7670 H21 FRL –/90/90, wet area

GYPROCK® THE RED BOOK™ 1 A5


Hospitals

Service Shaft
System No. Page No. System Feature
FRL –/90/90,
CSR 10018 H20
water and mould resistant
CSR 7680 H21 FRL –/120/120, wet area
CSR 7220 H10 Non-fire rated, services in riser

Corridor Wall
System No. Page No. System Feature
CSR 10001 C12 Impact resistant
CSR 3033 C14 FRL –/90/90, Rw 51
FRL –/180/180, Rw 50,
CSR 3095 C22
impact resistant

Service Duct
System No. Page No. System Feature
CSR 7020 H6 Sound rated Rw 50

A6 GYPROCK® THE RED BOOK™ 1


Operating Room Ceilings
System No. Page No. System Feature
Global Greentag Level A Certified,
CSR 10041 G52
NRC 0.7
CSR 6811 G52 Sound absorptive NRC 0.70

Operating Room Wall


System No. Page No. System Feature
CSR 3017 C12 FRL –/60/60, mould resistant, low VOC

Ward Walls
System No. Page No. System Feature
CSR 10002 C13 Impact resistant, FRL –/60/60
CSR 1066 C14 FRL –/90/90, wet area
CSR 1030 C9 Low cost

Ward Ceilings
System No. Page No. System Feature
CSR 6816 G52 Sound resisting CAC 41
Global Greentag Level A Certified,
CSR 10041 G52
NRC 0.7

Façade
System No. Page No. System Feature
CSR 5327 F13 Impact resistant, lightweight
CSR 21347 F33 FRL –/120/120, Rw 50
CSR 5324 F12 Pre-finished, lightweight, FRL 90/90/90
CSR 10313 F58 Class 4 Permiance, FRL –/60/60

GYPROCK® THE RED BOOK™ 1 A7


Office
Services Shaft
System No. Page No. System Feature
CSR 7665 H20 FRL –/90/90
CSR 7217 H10 Wet area, sound insulating Rw 48
CSR 10019 H20 Impact resistant, FRL –/90/90

Services Duct
System No. Page No. System Feature
CSR 7020 H6 Sound insulating Rw 44

Meeting Room Junction


System No. Page No. System Feature
CSR 8269 J8 Sound insulating Rw 45

Façade
System No. Page No. System Feature
CSR 5303 F11 Aesthetic feature
CSR 21347 F33 Impact resistant, FRL –/120/120
CSR 10313 F58 Class 4 Permiance

Meeting Room Wall


System No. Page No. System Feature
CSR 1037 C10 Sound insulating Rw 46
Green building, Rw 51,
CSR 3017 C12
damage resistant, water resistant
CSR 10031 C20 Rw 58, FRL –/90/90

Meeting Room Ceiling


System No. Page No. System Feature
CSR 6854 G54 Sound absorptive NRC 0.90
CSR 10043 G52 NRC 0.7

A8 GYPROCK® THE RED BOOK™ 1


Corridor Wall
System No. Page No. System Feature
CSR 1050 C12 FRL –/60/60
CSR 10001 C12 Impact resistant
CSR 3011 C11 Green building, Wet area, Rw 45

Office Walls
System No. Page No. System Feature
CSR 1030 C9 Low cost
CSR 1110 C18 Sound insulating Rw 51
CSR 3017 C12 Green building, sound insulating Rw 51

Office Ceiling
System No. Page No. System Feature
CSR 6811 G52 Sound absorptive NRC 0.70
CSR 10044 G52 NRC 0.9

GYPROCK® THE RED BOOK™ 1 A9


Aged Care

Corridor Wall
System No. Page No. System Feature
Impact resistant,
CSR 2049 D8
sound insulating Rw 40
CSR 2045 D7 Timber frame, Smoke-proof
Steel frame, impact resistant,
CSR 3017 C12
FRL –/60/60
CSR 1030 C9 Steel frame, smoke proof

Façade
System No. Page No. System Feature
CSR 5520 F19 Lightweight, FRL 60/60/60
Cladding with cavity; lightweight,
CSR 5710 F24
timber frame, FRL 60/60/60
CSR 5828 F26 Timber frame, pre-finished, lightweight
CSR 5303 F11 Steel frame, pre-finished, lightweight
CSR 10333 F60 Timber frame, pre-finished, Class 4

A10 GYPROCK® THE RED BOOK™ 1


Ward Ceiling
System No. Page No. System Feature
CSR 6636 G46 Low cost
CSR 6463 G31 Sound insulating, Rw 51
CSR 6644 G46 Sound insulating, Rw 50, RSIF 60

Ward Wall (SOU)


System No. Page No. System Feature
CSR 1035 C10 Wet areas, Rw 47
CSR 2059 D8 Timber frame
CSR 2220 D16 Sound insulating Rw 48, wet area

Ward Floor
System No. Page No. System Feature
CSR 6170 G8 Rw 45, low cost
CSR 6338 G19 Rw 58, Ln,w 45
CSR 6940 G25 Services cavity

GYPROCK® THE RED BOOK™ 1 A11


Retail
Services Ceiling
System No. Page No. System Feature
CSR 7020 H6 Low cost
CSR 6722 G49 FRL 120/120/120 both directions

Services Wall
System No. Page No. System Feature
CSR 7410 H14 Low cost, lined one side

Services Shaft
System No. Page No. System Feature
CSR 7220 H10 Low cost
CSR 7675 H21 FRL –/120/120

Corridor Wall
System No. Page No. System Feature
CSR 10002 C13 Impact resistant
CSR 1065 C14 FRL –/90/90

Façade
System No. Page No. System Feature
CSR 5327 F13 Impact resistant, Rw 50, R2.6
CSR 5385 F16 FRL 90/90/90, steel clad

A12 GYPROCK® THE RED BOOK™ 1


Cinema Wall
System No. Page No. System Feature
CSR 1700 C45 Sound insulating for cinemas Rw 77

Commercial Unit Ceiling


System No. Page No. System Feature
CSR 6861 G54 Sound absorptive NRC 0.65

Commercial Unit Wall


System No. Page No. System Feature
CSR 1030 C9 Low cost
CSR 1037 C10 Sound insulating Rw 46
CSR 10002 C13 Impact resistant

GYPROCK® THE RED BOOK™ 1 A13


House Class 1

Floor/Ceiling
System No. Page No. System Feature
CSR 6153 G8 Low cost
CSR 10169 G10 Rw 55, impact sound resistant Ln,w 50

Façade
System No. Page No. System Feature
CSR 5502 F18 Low cost
CSR 5709 F24 BAL 29, water resistant
CSR 5828 F26 Aesthetic feature
Zero lot boundary wall, FRL 60/60/60,
CSR 10161 F23
Rw + Ctr 50
BAL FZ, FRL 60/60/60, Class 4
CSR 10325 F59
Permiance

A14 GYPROCK® THE RED BOOK™ 1


House Ceiling
System No. Page No. System Feature
CSR 6403 G29 Low cost
CSR 10185 G33 Impact resistant Rw 50
CSR 6644 G46 Sound insulating, Rw 50, RSIF 60

House Wall
System No. Page No. System Feature
CSR 10146 D7 Impact resistant
CSR 10154 D25 FRL 60/60/60, Rw + Ctr 51
CSR 10153 D15 Impact resistant, Rw 57
CSR 2000 D6 Wet area

GYPROCK® THE RED BOOK™ 1 A15


Education

Classroom Wall
System No. Page No. System Feature
CSR 1045 C11 Rw 51
CSR 3011 C11 impact resistant, Rw 45
CSR 3017 C12 Impact resistant from both sides

Gymnasium/Hall Ceiling
System No. Page No. System Feature
CSR 6525 G37 Moisture; Impact resistant
CSR 6940 G25 Low cost
CSR 3718 G25 Impact resistant

Corridor Wall
System No. Page No. System Feature
CSR 3017 C12 Green building, Rw 45, impact resistant
CSR 10002 C13 Impact resistant, Rw 45

Façade
System No. Page No. System Feature
CSR 5327 F13 Impact resistant, Rw 50, R2.6
CSR 5403 F17 Masonry, Rw 59
CSR 5303 F11 Pre-finished option, lightweight

A16 GYPROCK® THE RED BOOK™ 1


Classroom Ceiling
System No. Page No. System Feature
CSR 6854 G54 Plasterboard durability, NRC 0.90
CSR 6615 G43 Rain noise protection Rw 51

Library/Common Room Ceiling


System No. Page No. System Feature
CSR 6816 G52 NRC 0.7, light reflectance 87%
CSR 10043 G52 NRC 0.7
CSR 6525 G37 Moisture; Impact resistant

Gymnasiums/Halls Wall
System No. Page No. System Feature
CSR 10002 C13 Green building; Rw 47; Impact resistant

GYPROCK® THE RED BOOK™ 1 A17


BRAND & PRODUCT
OVERVIEW Cemintel is an Australian owned company and part of the
GYPROCK iconic CSR Building Materials group, manufacturing and
supplying cement panels and building systems used for
external façades, ceilings, internal linings, and flooring,
Since introducing paper-faced plasterboard to Australia suitable for use in commercial and residential applications.
in 1947, Gyprock has led the industry in innovation,
Cemintel fibre cement products are locally manufactured
service and product quality. Gyprock’s rich history of
at Wetherill Park NSW to AS/NZS 2908 Cellulose-cement
pioneering many of the plastering industry’s developments
products. Part 2: Flat sheets. The factory utilises a full-
includes the delivery of specialty plasterboards for fire,
steels process to produce a variety of products. This
moisture and impact applications, numerous advances
method provides a smoother and flatter sheet compared
in adhesives and compounds, and the introduction of
to non-steels or sheet-on-sheet manufacturing processes
Australia’s first GECA accredited plasterboard product.
and sets Cemintel products apart from others in the
Gyprock’s industry leadership continues today, with the
market.
introduction of Optimised Core technology, delivering
stronger, lighter plasterboard, and with development of Cemintel also has established global partnerships with
premium quality compounds, cornice and accessories. leading manufacturers to obtain new product technology
to meet our ever-changing market demands. Products
With products readily available from over 50 Gyprock
are made to perform to relevant Australian Standards
Trade plaster stores, through preferred specialist
and Building Code requirements, to meet fire, acoustic
distributors, and via national retail stockists, Gyprock
and thermal requirements to service all segments of the
maintains a key focus on ensuring every customer’s needs
construction industry, and are covered by a Cemintel
are fully realised. From over-the-phone assistance, to a
warranty.
complete supply and fix service, Gyprock’s experienced
and knowledgeable team are available to support all Fibre cement products are considered as non-combustible
projects. and have the highest reaction to fire rating, allowing the
material to be used as a wall or ceiling lining in all building
ACTU areas.
UF
MAN

RE

With only 20 years history, Cemintel has made some


D

FO innovative contributions to the building industry including


R LIFE
the introduction of CeminSeal water block technology
in 2010 which is still unmatched today. Australian made
Apart from a small number of specialty products, Barestone products, launched in 2012, have become
Gyprock manufactures products in Australia to meet the a favourite of the design community, and were quickly
requirements of AS/NZS 2588 – ‘Gypsum Plasterboard’ followed by other pre-finished product ranges such as
where applicable, and to exacting quality control standards. Territory panels and Surround façade.
These products are backed by a Manufactured for Life Products are available nationally through a significant
warranty (25 years). Gyprock has developed exclusive distribution chain, and technical support can be sought
relationships with leading manufacturers throughout the from the DesignLINK team. In addition, customers can
world for a small number of specialty products. CSR also access on-line technical resources such as BIM files,
warrants its International Alliance Gyprock products to white papers, and how-to videos.
remain free of defects in material and manufacture for 7
years.

A18 GYPROCK® THE RED BOOK™ 1


HIMMEL manufacturing technologies, combined with the research
and development expertise of CSR, Bradford is the most
BRADFORDtrusted name in insulation and energy efficiency. We
provide the high-performance building science solutions
for residential homes, commercial and industrial projects.
HEBEL
CSR Himmel brings together Australia’s widest range of Our products are specifically designed for the Australian
commercial interior system products and accessories market in order to improve the long-term sustainability and
under the one roof. Distributing high-qualityRONDO
products health of buildings.
that ensure the design and functionality needs of any
project are always met, Himmel offers a global product
portfolio to support any sized commercial project. Himmel
boasts some of the world’s leading brands as part of
their product portfolio, such as the CSR Martini dECO
Acoustic Collection, Gyprock, Rondo, OWA, Troldtekt
and Ecophon. Hebel is a strong, versatile building product made from
OWA produce a wide range of mineral fibre ceiling tiles, autoclaved aerated concrete (AAC), suitable for use in
from commodity ceilings to specialty and customised residential, commercial, industrial and civil applications.
tiles. OWA products are produced in Germany utilising AAC was developed in Scandinavia over 70 years ago
the most up-to-date technologies to ensure a premium and is now a mainstream building material used in Europe,
product offering. Asia and increasingly in Australia. In 2015, the Reinforced
AAC Standards (AS 5146 Parts 1-3) were approved and
Ecophon, part of Saint Gobain, one of the world’s largest published by Standards Australia, which will guide the use
building material companies, are a leading manufacturer of Reinforced AAC in design and construction in Australia.
worldwide. Focusing on the well-being of humans, CSR Hebel is the only organisation to manufacture AAC
Ecophon products enhance the everyday experience of in Australia and has over 25 years of experience. A focus
individuals in commercial environments. on knowledge, innovation, customer service and high
Both OWA and Ecophon products have been tested to standards of production has enabled Hebel to stand out
Australian standards and offer extensive warranties when as a supplier of AAC. This is evident in the fit-for-purpose
used with approved Rondo and Ecophon Grids. product formulas to suit specific applications, and in the
development of rigorously tested systems that ensure a
Himmel also distributes the iconic Australia Made and consistently high-quality product and makes building with
Owned Gyprock paper or vinyl faced plasterboard ceiling Hebel efficient and low-risk. CSR Hebel is a licensee of
tiles, Aluminium Partition Systems and Architectural Xella GmBH, the largest AAC producer in the world. This
Hardware. This diverse product offering enables Himmel affords CSR Hebel access to new AAC technologies and
to provide a solution for all projects. AAC specific testing facilities. An alliance with Asahi Japan,
the largest AAC producer in Japan, also provides access
to AAC panel manufacturing technology developments.
Hebel products and systems are designed, developed and
warranted in Australia by CSR, making Hebel the AAC
Bradford Insulation is a leading manufacturer of premium brand of choice amongst engineers, architects and builders.
energy saving insulation products.
CSR Hebel is Australia’s only manufacturer of high
Established in 1934, the Bradford Insulation business was performance Autoclaved Aerated Concrete (AAC) for
acquired by CSR Limited in the 1950’s. Due to strong façades and internal walls in residential, high rise, commercial
growth over the 60’s and 70’s, manufacturing of reflective and civil applications. Hebel panels are non-combustible
foil sarking was also added to the Bradford business in and contain anti-corrosion coated steel reinforcement for
the 1980’s. By 2006, Bradford acquired the Edmonds added strength. Lightweight compared to other masonry
ventilation business, further enhancing Bradford’s products, Hebel panels are eco-friendly, termite resistant
leadership position in Australian manufacturing and energy and can be finished to achieve the latest in building trends
efficient construction products. CSR Bradford is now a and design aesthetics. Quick and easy to build with, Hebel
market leading manufacturer of premium energy efficiency systems deliver safe solutions with the technical support
products including insulation, wraps and ventilation. and expertise to back them up.
Driven by extensive industry knowledge and the latest
research, Bradford continues to innovate and develop new
products to provide customers with meaningful, effective
and compliant solutions.
With over 90 years of insulation experience, world class

GYPROCK® THE RED BOOK™ 1 A19


For over two decades, AFS’s innovative permanent Fricker is a customizable modular Aluminium ceiling grid
formwork system has been instrumental in facilitating the system. The product has been installed in many of the
rapid construction of multi-residential, residential, and landmark Perth and Sydney high rise buildings, and can
commercial projects across Australia, New Zealand, the be modified to suit a range of architectural building styles.
USA, the UK, and Canada.
Fricker has been designed to work with our extensive
Manufactured in Australia, Rediwall® is fully compliant range of ceiling tiles, from mineral fibre and Ecophon tiles
with AS3600 standards and has attained CodeMark to acoustical metal pan and wood wool products. As a
Certification, ensuring its adherence to the National system, Fricker can be installed to be compliant to the
Construction Code (NCC) and affirming its suitability for most recent seismic building codes across Australia.
use in the design of concrete structures.
This advanced formwork system has been rigorously
tested by leading bodies within the Australian building
industry and certified for its ability to withstand various Rondo has been manufacturing and supplying a wide
stressors, including those related to heat, fire, water, wind, range of market leading wall and ceiling systems for over
and structural loading. 50 years. With highly flexible, versatile and innovative
As a lightweight, load-bearing, and compliant permanent manufacturing capabilities, not only can Rondo produce
formwork, Rediwall offers a versatile walling solution in a their standard range at fast rates, but they can also
variety of panel thicknesses, making it suitable for diverse customise products to suit individual project needs. In
applications both above and below ground, as well as in addition, Rondo offers in-depth customer services that
internal and external environments. Rediwall optimizes include technical design support, product training, and
floor space while providing a consistent, high-quality superior technical resources; all backed by a written
finish, making it the preferred choice for construction guarantee and leading environmental performance.
professionals seeking an efficient, durable, and cost- Rondo’s dedication to providing outstanding customer
effective alternative to traditional building methods. service leads to their contribution to the best buildings in
AFS is dedicated to the development of products and Australia and overseas.
manufacturing processes that prioritize both innovation
and environmental responsibility. This includes systems
aimed at recycling raw materials and maximizing the
thermal efficiency of its products. Rediwall has achieved
Silver status in the Vinyl Council of Australia’s PVC
Stewardship Program, an ongoing, voluntary initiative
that promotes environmental sustainability, health, and
safety throughout the PVC lifecycle. As a signatory to this
program, AFS is committed to producing and supplying
OTHER CSR BRANDS
sustainable solutions that meet the needs of the building CSR Building Products is one of Australia’s oldest and
industry while adhering to environmentally responsible most respected public companies. With one of Australia’s
practices. largest portfolios of building materials manufacturers,
each of CSR’s respected brands are different, yet they all
share the company’s vision and values with the common
goal being the provision of reliable and trusted products
and services.
Additional brands in the CSR building product group
include Monier Roofing, Martini insulation, PGH and
Potter Interior systems and Woven Image.

A20 GYPROCK® THE RED BOOK™ 1


TECHNICAL
SUPPORT DesignLINK is a team of professionals including,
engineers and building designers working to support
CSR brands continually invests in research and
the specification of CSR building products in projects
development to ensure that their products and systems
across Australia. With extensive knowledge of the building
are responsive to Australia’s ever-changing construction
industry, DesignLINK partners with clients to workshop
needs. Reach out for support on your next project, by
complex design issues, provide value engineering,
phone, in person or through digital tools – the choice is
rationalise system specifications and deliver improved
yours.
building performance while maintaining buildability for
Each brand website features multiple tools to help you both builders and contractors. The DesignLINK team
navigate product or construction system selection. is based at the CSR Technical Centre in Wetherill Park,
From system selectors to installation guides, aesthetic New South Wales, adjacent to the manufacturing sites
visualisers to CAD files – visit the sites to explore the tools for Gyprock and Cemintel products. The facility includes
available; a technical workshop housing an extensive range of
testing equipment as well as NATA accredited testing
www.gyprock.com.au
laboratories.
www.cemintel.com.au
What does DesignLINK offer?
www.himmel.com.au
The DesignLINK service is tailored to meet the demands
www.bradfordInsulation.com.au of the building professionals. From technical support
for architects and designers, to installation guidance for
www.hebel.com.au
builders and contractors, assistance is available via phone
www.rondo.com.au and email. DesignLINK can provide compliance support
www.afsformwork.com.au through the provision of complex test data, assistance
with major projects, and the supply of CAD and BIM files
With years of experience in the field, our national team of for increased productivity.
commercially or residentially focused Account Managers
provide personalised service by getting to know your Phone and email support
business and projects. Simply call 1300 306 556 to find All enquiries are handled professionally. Where possible,
your nearest representative. the service can provide an immediate response, and
otherwise will be escalated to the most qualified team
member.

Assistance with major projects


DesignLINK is available to support major projects, offering
system rationalisation to meet performance objectives.
This service is offered in conjunction with State Technical
Managers to ensure the very best local knowledge is
combined with DesignLINK’s technical expertise.

System performance data


Compliance reports are available for a wide variety of Red
Book systems, covering fire, acoustics, weatherproofing,
and structural properties. In addition, the CSR Acoustic
Predictor provides ratings for lightweight walls, delivering
custom solutions that save time and money.

How do I contact the DesignLINK team?


Call 1800 621 117 or email: [email protected].

GYPROCK® THE RED BOOK™ 1 A21


NOTES

A22 GYPROCK® THE RED BOOK™ 1


PRODUCTS &
DESIGN
B
SECTION CONTENTS
Introduction ������������������������������������������������� B2
Referenced Material����������������������������������������� B2
Gyprock Range & Selection ������������������������������� B3
Cemintel Range������������������������������������������� B10
Bradford Range������������������������������������������� B10
Himmel Range��������������������������������������������� B13
AFS Range������������������������������������������������� B13
Material Properties ��������������������������������������� B14
Design Considerations ����������������������������������� B16
Fire Resistant Design������������������������������������� B19
Building Acoustics����������������������������������������� B20
Thermal Performance������������������������������������� B24
Condensation & Moisture Control����������������������� B24
Levels of Finish��������������������������������������������� B26

GYPROCK® THE RED BOOK™ 1 B1


INTRODUCTION underlays – Materials.
• AS 4200.2 – Pliable building membranes and underlays
This section provides important background – Installation.
information necessary for the selection and • AS/NZS 4600 – Cold formed steel structures.
usage of CSR Gyprock fire, acoustic and
thermal systems and associated products. • AS/NZS 4858 – Wet area membranes.
• AS/NZS 4859.1 – Thermal insulation materials for
All performance information provided in this manual relies buildings – General criteria and technical provisions.
on the system linings, components and accessories being
• AS 5216 – Design of post-installed and cast-in
strictly as specified. Information on the performance of third
fastenings in concrete.
party materials should be sought from the relevant supplier.
• AS/NZS 5601.1 – Gas installations – General
installations.
REFERENCED • AS 5637.1 – Determination of fire hazard properties -

MATERIAL wall and ceiling linings.


• AS/ISO 13007 – Ceramic tiles – grouts and adhesives
The following Standards and handbooks are referenced - Terms, definitions and specifications for adhesives.
in this guide. • National Construction Code (NCC).
Manufacturing Standards: • ICANZ Insulation Handbook Part 1: Thermal
• AS/NZS 2588 – Gypsum plasterboard. Performance – Version 3.
• AS/NZS 2908.2 – Cellulose-cement products • NASH Standards – Residential and Low-rise Steel
– Flat sheets. Framing, Part 1: Design criteria and Part 2: Design
Solutions.
Other referenced Standards and handbooks:
• SAHB39 – Installation code for metal roof and wall
• AS/NZS 1170 series – Structural design actions.
cladding.
• AS 1530.4 – Methods for fire tests on building materials,
• AS 5164 series – Reinforced autoclaved aerated
components and structures - fire resistance tests for
concrete.
elements of constructions.
• ASTM C518 – Test method for steady-state thermal
• AS 1684 (series) – Residential timber framed
transmission properties by means of the heat flow
construction.
meter apparatus.
• AS 1720.1 – Timber structures – Design methods.
• ISO 11654 – Sound absorbers for use in buildings –
• AS/NZS 2311 – Guide to the painting of buildings. rating for sound absorption.
• AS/NZS 2358 – Adhesive – For fixing ceramic tiles. • AS 4312 – Atmospheric corrosivity zones in Australia.
• AS/NZS 2589 – Gypsum linings – Application and
finishing. RELATED GYPROCK
• AS/NZS 2785 – Suspended ceilings – Design and PUBLICATIONS
installation. • GYP949 Gyprock StrataWall Systems.
• AS/NZS 3000 – Electrical installations (known as the • GYP512 Gyprock Cinema Wall Systems.
Australian/New Zealand wiring rules).
• GYP513 Gyprock Party Wall Systems.
• AS 3600 – Concrete Structures.
• GYP514 Gyprock Boundary Wall Installation Guide.
• AS/NZS 3700 – Masonry structures.
• GYP546 Gyprock Shaft Wall Systems.
• AS 3740 – Waterproofing of domestic wet areas.
• Book 2 Residential Installation Guide –
• AS 3958.1 – Ceramic tiles – Part 1: Guide to the Buildings Class 1 & 10.
installation of ceramic tiles.
• Book 3 Commercial & Multi-Residential Installation
• AS 3959 – Construction of buildings in bushfire-prone Guide – Buildings Class 2 to 9.
areas.
• AS 4055 – Wind loads for housing.
• AS/NZS 4200.1 – Pliable building membranes and

B2 GYPROCK® THE RED BOOK™ 1


RELATED CEMINTEL PRODUCT & Plasterboard, or drywall as it is called in some parts of the
world, is a machine made sheet comprised of a gypsum
PUBLICATIONS core wrapped in a heavy-duty liner paper.
• Cemintel Rigid Air Barrier.
The core is made by first mixing gypsum, a non-toxic
• Cemintel Wallboard – Interior Steel Framed Walling. sedimentary rock, with a foaming agent to create a wet
plaster mix. This plaster is applied onto a sheet of thick
• Cemintel Wet Area Systems.
paper and the side edges of the paper are wrapped
• Cemintel External Cladding & Eaves Lining. around the plaster. Another sheet of linerboard paper is
• Cemintel Texture Base Sheet. applied over the top to create a plaster ‘sandwich’ which
is cut to length and oven dried, ready for use. The final
• Cemintel Headland Weatherboard. plasterboard sheet has two long edges that are paper-
• Cemintel Scarborough Weatherboard. wrapped and two cut edges.

• Cemintel Balmoral Weatherboard. Gyprock manufactures in Australia to AS 2588 – Gypsum


plasterboard, and is formally accredited to the standard
• Cemintel Plank. for Gyprock Plus, Supaceil and Standard Plasterboard
• Cemintel Commercial ExpressPanel. 13mm.
• Cemintel Barestone External. In addition to standard plasterboard, Gyprock has
developed technologies that deliver significant
• Cemintel Ceiling Systems.
performance benefits to meet our customers’ specific
• Cemintel Edge & SimpleLine. needs.
• Cemintel Surround External. Gyprock Optimised Core technology delivers an advanced
performance-to-weight ratio, providing greater breaking
• Cemintel Territory Vertical Installation.
strength in a substantially lighter board. Optimised Core
• Cemintel Territory Horizontal Installation. technology is currently available in Gyprock Plus and
• Cemintel Mosaic Façade Systems. Supaceil.

• Cemintel Aspect Cladding. While the majority of the plasterboard range is accredited
by Good Environment Choice Australia, Gyprock also
• Cemintel Constructafloor Interior Flooring. produces a handful of plasterboard products featuring
Also refer to relevant technical guides from AFS, Hebel, higher levels of recycled content. This includes the
Himmel and other product manufacturers for additional Gyprock EC08 boards and HD, making these products a
information. superior choice for Green Building projects.

GYPROCK RANGE & Good Environmental Choice Australia


(GECA)
SELECTION In 2008, Gyprock was the first Australian manufacturer
to deliver a plasterboard product certified by GECA.
With continual development in the green building space,
GYPROCK PLASTERBOARD Gyprock now presents a wide range of accredited
MANUFACTURING plasterboard products, and in 2014, was awarded GECA
certification covering the majority of compounds in the
Plasterboard is an internal wall and ceiling lining board, range.
used in residential and commercial lightweight framed
construction.
The Gyprock range of plasterboard closely follows
the plasterboard market split between Residential
and Commercial applications. Each sector has two
classifications:
• Select Range – Gyprock plasterboards products
recommended for use in the majority of non-specialist
wall and ceiling applications.
• Specialty Options – Gyprock plasterboards products
• GECA Panel Boards PBv3.0-2021
for use in wall and ceiling systems where higher levels
of performance are specified. • Adhesives, Fillers & Sealants AFSv4.0-2014

GYPROCK® THE RED BOOK™ 1 B3


GYPROCK PLASTERBOARD SELECTION
Gyprock plasterboard products are available in a large range of sheet lengths. Lengths vary by state, and a full list is
available at www.gyprock.com.au. Standard width is 1200mm. Some products are also available in 900, 1350 and
1400mm widths (lead times may apply). Shaft Liner Panel is supplied in 600mm width only. Colour shading behind each
product name approximates the colour of the product face liner sheet.

TABLE B1: GYPROCK PLASTERBOARD FEATURES, APPLICATIONS & SPECIFICATIONS


   APPLICATIONS – WALLS & CEILINGS
GYPROCK® THICK-
MASS
NESS
PLASTERBOARDS kg/m2
(mm)
  FEATURES

RESIDENTIAL – SELECT RANGE


• A 10mm thick sheet primarily designed for residential walls. Long
edges are recessed to assist in producing a smooth, even and
continuous surface once jointed.
• Made with Optimised Core technology that delivers an advanced
Plus™ performance-to-weight ratio, meaning greater breaking strength in a
substantially lighter board that continues to exceed the performance
requirements of AS/NZS2588.
10 5.7

• Optimised Core technology delivers improved handling and installed
performance, as well as crisper score and snap.
• A 10mm thick sheet designed to span up to 600mm in ceiling
applications. Can also be used for wall applications. Long edges
are recessed to assist in producing a smooth, even and continuous 6.1
surface once jointed.

Supaceil™
• Made with Optimised Core technology that delivers an advanced
performance-to-weight ratio, meaning greater breaking strength in a
substantially lighter board that continues to exceed the performance
10 6.2
WA

requirements of AS/NZS2588. only
• Optimised Core technology delivers improved handling and installed
performance, as well as crisper score and snap.
• Both the core and linerboard facing are treated in manufacture to
withstand the effects of moisture and high humidity.
Aquachek™
• Recessed long edges allow flush jointing to other Recessed Edge
plasterboard types.
10 7.1
✓ ✓
RESIDENTIAL – SPECIALTY OPTIONS
• Manufactured with a high density core and heavy duty liner paper to
provide enhanced impact and acoustic resistance.
• Will span 600mm in ceiling applications.
HD • 75% more impact resistant compared to standard plasterboard.
• Denser core to provide a reduction in sound transmission compared
10 8.5
✓✓ ✓
to standard 10mm thick plasterboard.
• Long edges are recessed for flush jointing.
COMMERCIAL – SELECT RANGE

RE – Recessed Edge
• Long edges are recessed to assist in producing a smooth, even and
continuous surface once jointed.
13 8.5

RE/SE – 1 Recessed Edge, 1 Square Edge
• Typically used on walls with a single horizontal joint. One long edge
Standard
Plasterboard
is recessed to assist in producing a smooth, even and continuous
surface once jointed.
• One long edge is square to enable easy fixing of skirting and cornice
13 8.5

at the top and bottom of walls.

SE – 2 Square Edges
• Long edges are square, and can be butted together without jointing,
or covered with aluminium, timber or vinyl mouldings.
13 8.5

• Both the core and linerboard facing are treated in manufacture to
withstand the effects of moisture and high humidity.
Aquachek™
• Recessed long edges allow flush jointing to other Recessed Edge
plasterboard types.
13 9.8
✓ ✓
• Designed to provide enhanced acoustic resistance.

Soundchek™
• A machine made sheet composed of a high density gypsum core
encased in a heavy duty linerboard.
• Long edges are recessed for flush jointing.
13 13.0
✓ ✓

B4 GYPROCK® THE RED BOOK™ 1


TABLE B1: GYPROCK PLASTERBOARD FEATURES, APPLICATIONS & SPECIFICATIONS
   APPLICATIONS – WALLS & CEILINGS
GYPROCK® THICK-
MASS
NESS
PLASTERBOARDS kg/m2
(mm)
  FEATURES

• Fire grade board reinforced with a woven fibreglass mesh to produce


a high strength plasterboard which resists hard and soft body impact

Impactchek™
damage.
• Ideal for high traffic areas such as hallways, stairways, playrooms
and garages.
13 10.5
✓ ✓
✓✓ ✓
• Long edges are recessed for flush jointing.

• Fire grade board composed of a specially processed glass fibre 13 10.8


reinforced gypsum core encased in a heavy duty linerboard.
Fyrchek™ • Ideal for high performance fire and acoustic rated walls and ceilings.
• Long edges are recessed for flush jointing. 16 12.9
✓ ✓ ✓
• Fire grade board with moisture resistant properties. 13 11.1
Fyrchek™ MR
• Both the core and the liner board are treated in manufacture to
withstand the effects of high humidity and moisture.
• Long edges are recessed for flush jointing. 16 13.3
✓✓ ✓ ✓
COMMERCIAL – SPECIALTY OPTIONS
• This product features higher levels of recycled content, making it a
superior choice for Green Building projects. 13 12.4
EC08™ • Gyprock EC08 Complete is an internal lining solution which
Complete
integrates an efficient mould inhibitor, scuff resistance, soft and hard
body impact resistance, moisture resistance, sound resistance and
fire resistance into a low VOC plasterboard. 16 14.8
✓✓✓✓✓✓
• Long edges are recessed for flush jointing.
• This product features higher levels of recycled content, making it a
superior choice for Green Building projects.
• Gyprock EC08 Extreme is a premium internal lining solution with a

✓✓✓
EC08™ focus on superior impact resistance for hard & soft body impact,
Extreme
and surface indentation. It also includes an efficient mould inhibitor,
moisture resistance, sound resistance and fire resistance in a low
VOC plasterboard to provide multifunction performance to a wide
13 12.5
✓✓✓✓
variety of commercial projects.
• Long edges are recessed for flush jointing.
• Fire grade board with antifungal additives to resist mould formation.
Shaft Liner
Panel MP
• A 25mm thick sheet composed of a glass fibre reinforced gypsum
core encased in a heavy duty ivory linerboard.
• 600mm wide square edge sheets.
25 19.8
✓ ✓✓✓
• A 6.5mm thick plasterboard with an enhanced core to allow bending
to small radii for curved walls and ceilings.
Flexible • Designed for installation as a two layer system.
• Long edges are recessed for flush jointing.
6.5 4.3

• A 30mm thick paperless gypsum board with glass fibre reinforced
core.
Glasroc F • Designed for single-layer installation, without jointing, to provide fire
protection to structural steel columns and beams.
30 25.5
✓ ✓
• 1200mm wide square edge boards.
• A 12.5mm thick paperless gypsum board with glass mat
reinforcement.
Glasroc X® • A class 4 vapour-permeable rigid air barrier suitable for use externally
in Climate Zones 2-8.
12.5 10.9
✓✓ ✓✓
• 1200mm wide recessed edge boards.

GYPROCK® THE RED BOOK™ 1 B5


GYPROCK PERFORATED PLASTERBOARD SELECTION
Excellence in design is achieved with a balance of aesthetics and functional performance. The Gyprock range of perforated
plasterboard and access panels allows architects and designers to create beautiful ceilings and walls that achieve high
levels of acoustic performance.
The perforations together with fleece linings and insulation where used, reduce echo and noise reverberation to create
more comfortable environments for work and leisure.

TABLE B2: GYPROCK PERFORATED PLASTERBOARD FEATURES, APPLICATIONS & SPECIFICATIONS


GYPROCK®
SIZE THICKNESS MASS SUITABLE SUITABLE
ACOUSTIC
PERFORATED   PRODUCT FEATURES FOR FOR
(mm) (mm) kg/m2 FABRIC
CEILINGS WALLS
PLASTERBOARDS

STANDARD RANGE
• Featuring six large rectangular groupings per sheet, each with 2,100 x
Standard
6mm diameter perforations at 15mm centres to provide an open area of 1200 x
Perforated 6mm
Round
8.3%.
• Long edges are recessed for flush jointing.
3600
13 8.5
✓ ✓ NIL

GYPTONE RANGE
• Featuring eight large square groupings per sheet, each with 576 x
12mm hexagonal perforations at 20mm centres, providing a 15% open
area.
• Supplied with a black acoustic fabric backing.
Gyptone 1200 x
12mm Hexagon
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
living in the space.
2400
12.5 8.0
✓ ✓ Black

• All four edges are recessed for flush jointing.


• Matching access panel available.
• Featuring 3 large square groupings per sheet, each with 1,521 x 12mm
hexagonal perforations at 20mm centres, providing a 17.6% open area.
Gyptone • Supplied with a white acoustic fabric backing. 900 x
12mm Hexagon
Longboard
• The Longboard provides a bigger perforation area than the standard
board which makes it ideal for creating a strong visual impact on
2700
12.5 8.0
✓ ✓ White

projects with a higher distance from floor to ceiling, as well as better


sound absorption.
• Featuring eight large square groupings per sheet, each with 400 x
12mm square perforations at 25mm centres, providing a 16% open
area.
• Supplied with a black acoustic fabric backing.
Gyptone 1200 x
12mm Square
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
living in the space.
2400
12.5 8.0
✓ ✓ Black

• All four edges are recessed for flush jointing.


• Matching access panel available.
• Featuring eight large square groupings per sheet, each with nine mini
grids of 16 x 12mm square perforations at 25mm centres. This subtle
pattern provides an open area of 6%.
Gyptone • Supplied with black acoustic fabric backing.
1200 x
12mm Square
Minigrid
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
living in the space.
2400
12.5 8.0
✓ ✓ Black

• All four edges are recessed for flush jointing.


• Matching access panel available.
• 32 small square groupings per sheet, each with 64 x 12mm square
perforations at 25mm centres, providing a 10% open area.
• Supplied with black acoustic fabric backing.
Gyptone
1200 x
12mm Square
Grid
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
living in the space.
2400
12.5 8.0
✓ ✓ Black

• All four edges are recessed for flush jointing.


• Matching access panel available.
• 3 large square groupings per sheet, each with 1,024 x 12mm square
perforations at 25mm centres, providing a 18% open area.
Gyptone • Supplied with a white acoustic fabric backing. 900 x
12mm Square
Grid Longboard
• The Long board provides a bigger perforation area than the standard
board which makes it ideal for creating a strong visual impact on
2700
12.5 8.0
✓ ✓ White

projects with a higher distance from floor to ceiling, as well as better


sound absorption.

B6 GYPROCK® THE RED BOOK™ 1


TABLE B2: GYPROCK PERFORATED PLASTERBOARD FEATURES, APPLICATIONS & SPECIFICATIONS
GYPROCK®
SIZE THICKNESS MASS SUITABLE SUITABLE
ACOUSTIC
PERFORATED   PRODUCT FEATURES FOR FOR
(mm) (mm) kg/m2 FABRIC
CEILINGS WALLS
PLASTERBOARDS

GYPTONE RANGE (continued)


• Featuring eight large square groupings per sheet, each with 16 mini
grids of six 6mm x 80mm slot perforations. This contemporary design
provides 13% open area.
• Supplied with black acoustic fabric backing.
Gyptone Slotted 1200 x
Minigrid
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
living in the space.
2400
12.5 8.0
✓ ✓ Black

• All four edges are recessed for flush jointing.


• Matching access panel available.
• 3 large square groupings per sheet, each with 49 mini grids of six 6mm
x 80mm slot perforations.
Gyptone Slotted • This contemporary design provides 18% open area and is supplied with
900 x
Minigrid
Longboard
a white acoustic fabric backing.
• The Longboard provides a bigger perforation area than the standard
board which makes it ideal for creating a strong visual impact on
2700
12.5 8.0
✓ ✓ White

projects with a higher distance from floor to ceiling, as well as better


sound absorption.
• Flexible board suitable for curving to 1.2m minimum radius.
• Perforated gypsum board with square holes
Gyptone Flexible 1200 x
12mm Square
of 12mm x 12mm.
• Total perforated area of 16%.
2400
6.5 6.5
✓ ✘ Black

• Supplied with black acoustic fabric backing.


• Flexible board suitable for curving to 1.2m minimum radius.
• Perforated gypsum board with rectangular holes
Gyptone Flexible 1200 x
Slotted Minigrid
of 6mm x 80mm.
• Total perforated area of 13%.
2400
6.5 6.5
✓ ✘ Black

• Supplied with black acoustic fabric backing.


RIGITONE RANGE
• Featuring a grid pattern of 8mm round perforations spaced at 18mm
centres, providing a 15.5% open area.
Rigitone • Supplied with black acoustic fabric backing.
1188 x
Matrix
8mm Round
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
1998
12.5 10.0
✓ ✓ Black

living in the space.


• Unique jointing method to provide a continuous pattern once finished.
• A pattern of 8mm square perforations spaced at 18mm centres,
providing a 19.8% open area. Supplied with a black acoustic fabric
backing.
Rigitone
• Manufactured with patented Activ’Air technology, which removes 1188 x
Matrix
8mm Square
formaldehyde and improves the environment for people working and
living in the space.
1998
12.5 10.0
✓ ✓ Black

• Supplied with black acoustic fabric backing.


• Unique jointing method to provide a continuous pattern once finished.
• Featuring a grid pattern of 12mm round perforations spaced at 25mm
centres, providing a 18.1% open area.
Rigitone • Manufactured with patented Activ’Air technology, which removes
1200 x
Matrix
12mm Round
formaldehyde and improves the environment for people working and
living in the space. 2000
12.5 9.5
✓ ✓ Black

• Supplied with black acoustic fabric backing.


• Unique jointing method to provide a continuous pattern once finished.
• Featuring a grid pattern of 12mm square perforations spaced at 25mm
centres, providing a 23% open area.
Rigitone • Supplied with black acoustic fabric backing.
1200 x
Matrix
12mm Square
• Manufactured with patented Activ’Air technology, which removes
formaldehyde and improves the environment for people working and
1200
12.5 9.5
✓ ✓ Black

living in the space.


• Unique jointing method to provide a continuous pattern once finished.
• A pattern of 10mm round perforations spaced at 23mm centres,
providing a 14.8% open area. Supplied with a black acoustic fabric
backing.
Rigitone
• Manufactured with patented Activ’Air technology, which removes 1196 x
Matrix
10mm Round
formaldehyde and improves the environment for people working and
living in the space.
2000
12.5 10
✓ ✓ Black

• Supplied with black acoustic fabric backing.


• Unique jointing method to provide a continuous pattern once finished.

GYPROCK® THE RED BOOK™ 1 B7


TABLE B2: GYPROCK PERFORATED PLASTERBOARD FEATURES, APPLICATIONS & SPECIFICATIONS
GYPROCK®
SIZE THICKNESS MASS SUITABLE SUITABLE
ACOUSTIC
PERFORATED   PRODUCT FEATURES FOR FOR
(mm) (mm) kg/m2 FABRIC
CEILINGS WALLS
PLASTERBOARDS

RIGITONE RANGE (continued


• Featuring a grid pattern of 15mm round perforations spaced at 30mm
centres, providing a 19.6% open area.
Rigitone • Manufactured with patented Activ’Air technology, which removes
1200 x
Matrix
15mm Round
formaldehyde and improves the environment for people working and
living in the space. 1980
12.5 9.5
✓ ✓ Black

• Supplied with black acoustic fabric backing.


• Unique jointing method to provide a continuous pattern once finished.
• Featuring a regularly staggered pattern consisting of 12mm and 20mm
round perforations spaced at 33mm centres, providing a 19.6% open
area.
Rigitone • Manufactured with patented Activ’Air technology, which removes 1188 x
Astral formaldehyde and improves the environment for people working and
living in the space.
1980
12.5 9.5
✓ ✓ Black

• Supplied with black acoustic fabric backing.


• Unique jointing method to provide a continuous pattern once finished.
• Featuring an irregular scattered pattern consisting of 8mm, 15mm and
20mm round perforations, providing a 10% open area.
• Manufactured with patented Activ’Air technology, which removes
Rigitone 1200 x
Galaxy
formaldehyde and improves the environment for people working and
living in the space. 1960
12.5 10.0
✓ ✓ Black

• Supplied with black acoustic fabric backing.


• Unique jointing method to provide a continuous pattern once finished.

GYPROCK PLASTERBOARD CEILING TILE SELECTION


TABLE B3: CEILING TILE FEATURES, APPLICATIONS & SPECIFICATIONS
GYPROCK®   APPLICATIONS – GRID CEILING SYSTEMS
THICKNESS MASS
PLASTERBOARD CEILING
(mm) kg/m2
TILES   FEATURES

• Gyprock Supatone Bright is a plasterboard tile with a ‘wipe clean’ smooth polycoated surface
paper laminate. Supatone Bright is available in ‘white’, and used in basic commercial ceiling
Supatone™ Bright applications. Supatone Bright’s core features the sag resistance properties of Supaceil. 1200 x
10 7.6
600mm nom.

• Freshtone is a Gyprock plasterboard tile finished with a finely textured vinyl laminate which resists
Freshtone™ fading and is easily wiped clean. Freshtone is available in ‘white’, and is ideal for shopping centres,
offices and industrial premises. Freshtone’s core features the sag resistance properties of Supaceil.
10 7.6
Diamond White
1200 x 600mm nom.

• Gyprock Arctic White Vinyl Face is a plasterboard panel finished with a finely textured vinyl laminate
which resists fading and mould growth. It is suitable for a wide range of commercial building
Arctic White applications such as shopping centres, offices and retail spaces. 1200 x 600mm nom.
10 7.6
Product ONLY available in WA.

B8 GYPROCK® THE RED BOOK™ 1


GYPROCK CORNICE SELECTION INSPIRATIONS RANGE
Gyprock Cornice is designed to provide an attractive Gyprock Presto Cornice
finish at the junction of the wall and ceiling. It can be used 10mm
on Gyprock plasterboard, fibrous plaster, fibre cement or 10mm

cement rendered surfaces. Gyprock cornice is composed


of gypsum plaster encased in a strong linerboard.

TABLE B4: GYPROCK CORNICE RANGE


   APPLICATIONS – CEILING SYSTEMS
GYPROCK
90mm
CORNICE
  FEATURES
Gyprock Alto Cornice
Standard
• Gyprock Cove has long been the standard cornice choice
Cove for Australian home builders. Its functional profile does not
detract from common décor styles and it is available in
three profile sizes (55, 75 & 90mm) to suit different ceiling
heights and applications.
Contemporary
Aria™ • If the property style calls for something more modern
and streamlined than Cove, the Gyprock Contemporary
Duo range offers minimalistic profiles that will add interest with
simple, fresh appeal.
Opera™ Gyprock Trio Cornice
Alto™ Inspirations
Trio • A Gyprock Inspirations cornice gives a new dimension of
style and detail. Whether traditional or modern in style,
Tempo™ each has a unique and distinctive look that can add
Concerto™ quality and value to the project.
Symphony

COVE RANGE
Gyprock Cove Cornice
Gyprock Tempo Cornice

CONTEMPORARY RANGE Gyprock Concerto Cornice


Reverse application shown
Gyprock Aria Cornice

Gyprock Symphony Cornice

Gyprock Duo Cornice

GYPROCK® THE RED BOOK™ 1 B9


CEMINTEL RANGE BRADFORD RANGE
CEMINTEL WALLBOARD INSULATION PRODUCTS
Cemintel CeminSeal Wallboard features an embedded The Red Book’s fire, acoustic and thermal systems are
micro water block technology that prevents water designed around a range of Bradford insulation products
penetrating into the sheet, repelling water and providing including, Bradford Gold, Soundscreen, Acoustigard and
a more stable sheet. Martini Polyester.
Wallboard is a superior lining for wet areas such as These products are specifically designed to achieve
bathrooms, laundries and semi-exposed ceilings, and high performance results in a wide range of applications
for the construction of impact resistant walls. throughout the Red Book.
Cemintel Wallboard has a recess on both long edges so Bradford Gold™ insulation for walls and
that sheets may be taped and set. Once jointed it may be ceilings is specifically designed to deliver
tiled, painted or wall papered as desired. optimal thermal performance for the
building envelope. Up to 25% of heat can
FAÇADES AND SOFFITS be lost through the walls and up to 35%
through the ceiling in winter. Essentially,
Cemintel has a selection of façades with classics such as Bradford Gold acts as a barrier to slow
weatherboards and profiled sheets, and contemporary down heat loss and make a substantial
products such as the pre-finished Territory ™ and difference to the energy efficiency and
Surround™ ranges. temperature inside the building. Bradford
Cemintel ceiling solutions that can be used in residential Gold Hi-Performance wall batts are
or commercial applications are also available. also available for even higher thermal
performance.
FLOORING & DECKING Bradford SoundScreen ™ is a high-
density acoustic insulation that is
Choose from our range of advanced lightweight fibre
designed for hollow internal walls to
cement flooring and high strength compressed sheet
provide exceptional noise reduction
solutions – suitable for both residential and commercial
benefits. SoundScreen fills the empty
applications
space inside internal walls, effectively
absorbing unwanted noise transfer
RIGID AIR BARRIER between rooms for greater acoustic
Cemintel Rigid Air Barrier is a 6mm fibre cement panel comfort.
consisting primarily of Portland Cement, cellulose fibres, Bradford Acoustigard™ is a glasswool
sand and water. It is sealed on the face and edges fibre insulation specifically engineered to
using Cemintel’s proven Ceminseal embedded micro reduce sound transmission in walls and
waterblock technology, which repels water, preventing ceilings. The product comes in a range of
water penetrating into the panel and hence providing densities and is also certified as a thermal
a durable sheet that will not rot, swell or warp when insulation for non-combustible external
correctly installed. By protecting against wind and rain, walls
it allows work to be carried on inside the building prior
to cladding being installed. Being fibre cement, Cemintel
Rigid Air Barrier may be used where a non-combustible
material is required by the NCC.

B10 GYPROCK® THE RED BOOK™ 1


WALL WRAP PRODUCTS ROOF SARKING PRODUCTS
The installation of wall wrap can greatly increase The installation of roof sarking can greatly increase
weather resistance of the building both during and after weather resistance of the building both during and after
construction. Wall wrap can assist in reducing the amount construction. Roof sarking assists in reducing the amount
of wind driven rain that can enter the internal wall and of wind driven rain that can enter the roof and protect the
protect the building from water damage. Additionally, building from water damage. Some roof sarking products
Class 4 vapour permeable wall wraps allow internally provide additional thermal performance while others help
generated water vapour to escape the inside of the minimise the risk of condensation.
building and minimise the risk of condensation formation.
Thermoseal™ Roof Tile Plus is an extra heavy duty,
Thermoseal™ Wall Wrap is a Class 1 vapour barrier reflective foil weather
wall wrap that provides additional weather protection barrier for use under
to the building frame tiled roofs. Thermoseal
and minimises the entry Roof Tile Plus can reflect
of outside moisture up to 97% of radiant
into the wall system. heat and minimises the
Thermoseal Wall Wrap entry of wind driven rain
i s re c o m m e n d e d f o r into the roof cavity.
use behind masonry
Enviroseal ™ HTS is
c o n s t r u c t i o n o n l y,
a highly durable, vapour permeable roof underlay for
however, may be used
use in residential or commercial tiled, slate and metal
behind lightweight clad in
roof applications.
humid, tropical regions.
Enviroseal™ HTS
Enviroseal ™ RW Plus is a Class 4 highly vapour provides an additional
permeable wall wrap that can greatly reduce this risk layer of protection under
of mould growth and tiles or metal roofs and
condensation formation minimises the risk of
in the wall envelope while condensation damage.
still providing exceptional
weather resistance.
Enviroseal ™ RW Plus is
suitable behind masonry
and light weight clad
TABLE B5: WALL WRAP/ROOF SARKING
construction in cold to PRODUCT SPECIFICATION
warm climates. It is not When used on
Vapour When used on
recommended in tropical or high humidity regions. walls – weather
Permeance roof – weather
Product exposure
Enviroseal ™ CW and CW-IT are a Class 4 vapour Class AS/NZS exposure limit
limit prior to
4200.1 prior to roofing
permeable wall wrap cladding
which protects against Thermoseal 733
Class 1 6 Weeks N/A
MD
water-related weather
Thermoseal
damage and mould Class 1 6 Weeks 2 Weeks
Resiwrap
or rot, while reducing
Thermoseal
airflow around insulation Class 1 6 Weeks N/A
Wall Wrap/XP
allowing it to work more Thermoseal
Class 2 6 Weeks N/A
efficiently. With a higher Firespec
burst strength & material Enviroseal HTS Class 4 6 weeks 2 Weeks
gsm weight than RW, Enviroseal RW
Class 4 6 weeks N/A
Enviroseal™ CW is suitable for use as a commercial grade PLUS
wrap with brick, timber, steel, fibre cements products & Thermoseal
Class 1 N/A 2 Weeks
Roof Tile Plus
Hebel construction.
Enviroseal CW/
Class 4 6 weeks N/A
CW-IT

GYPROCK® THE RED BOOK™ 1 B11


TABLE B6: SPECIFIED INSULATION AND ABBREVIATIONS
(Abbreviated names have been used in system tables).
R – Value
Product Abbreviation Non-Combustible
(m2 K/W)^
70mm Bradford Soundscreen R2.0 70 Soundscreen 2.0 2.0 ✔
88mm Bradford Soundscreen R2.5 88 Soundscreen 2.5 2.5 ✔
110mm Bradford Soundscreen R3.1 110 Soundscreen 3.1 3.1 ✔
25mm Bradford Acoustigard (24kg/m3) 25 Acoustigard 24kg 0.65 ✔
25mm Bradford Acoustigard (32kg/m3) 25 Acoustigard 32kg 0.7 ✔
50mm Bradford Acoustigard (14kg/m3) 50 Acoustigard 14kg 1.2 ✔
50mm Bradford Acoustigard (24kg/m3) 50 Acoustigard 24kg 1.4 ✔
75mm Bradford Acoustigard (11kg/m3) 75 Acoustigard 11kg 1.7 ✔
75mm Bradford Acoustigard (14kg/m3) 75 Acoustigard 14kg 1.8 ✔
75mm Bradford Acoustigard (24kg/m3) 75 Acoustigard 24kg 2.1 ✔
75mm Bradford Acoustigard (32kg/m3) 75 Acoustigard 32kg 2.2 ✔
100mm Bradford Acoustigard (14kg/m3) 100 Acoustigard 14kg 2.4 ✔
110mm Bradford Acoustigard (11kg/m3) 110 Acoustigard 11kg 2.5 ✔
165mm Bradford Acoustigard (11kg/m3) 165 Acoustigard 11kg 3.5 ✔
90mm Bradford Acoustigard (14kg/m3) 90 Acoustigard 14kg 2.2 ✔
90mm Bradford Acoustigard (24kg/m3) 90 Acoustigard R2.5 2.5 ✔
90mm Bradford Acoustigard (32kg/m3) 90 Acoustigard 32kg 2.7 ✔
75mm Bradford Gold Wall HP Batts R2.0 75 Gold Batts 2.0 2.0 ✔
90mm Bradford Gold Wall Batts R2.0 90 Gold Batts 2.0 2.0 ✔
90mm Bradford Gold Wall HP Batts R2.5 90 Gold Batts 2.5 2.5 ✔
90mm Bradford Gold Wall HP Batts R2.7 90 Gold Batts 2.7 2.7 ✔
140mm Bradford Gold Ceiling Batts R2.5 140 Gold Batts 2.5 2.5 ✔
165mm Bradford Gold Ceiling Batts R3.0 165 Gold Batts 3.0 3.0 ✔
185mm Bradford Gold Ceiling Batts R3.5 185 Gold Batts 3.5 3.5 ✔
215mm Bradford Gold Ceiling Batts R4.1 215 Gold Batts 4.1 4.1 ✔
50mm Martini MAB Polyester (11kg/m3) 50 MAB Polyester 11kg N/A –
75mm Martini MAB Polyester (11kg/m3) 75 MAB Polyester 11kg N/A –
100mm Martini MAB Polyester (11kg/m3) 100 MAB Polyester 11kg N/A –
25mm Martini MAB Polyester (20kg/m3) 25 MAB Polyester 20kg N/A –
75mm Martini MAB Polyester (20kg/m3) 75 MAB Polyester 14kg N/A –
90mm Bradford Polymax R2.0 90 Polymax 2.0 2.0 –
100mm Martini Absorb XHD Polyester 100mm Absorb XHD Polyester N/A –
25mm Bradford Fibertex 450 Rockwool (80kg/m3) 25mm Bradford Fibertex 450 0.72 ✔
110mm Bradford Glasswool Building Blanket R2.5 110 Glasswool Building Blanket 2.5 ✔
25mm Soundlag 4525C Acoustic Pipewrap# Soundlag# – –
60mm Bradford Anticon Medium Duty R1.3 Anticon 60 MD 1.3 ✔*

N/A: Product not tested for R-Value


^ R-Value are determined in accordance with AS/NZS 4859.1 and will remain the same unless the product is compressed or altered. The total
R-Value of the system is dependent on installation and environmental conditions.
* Bulk Glasswool insulation material only - excludes facing material.
# Supplied by others

B12 GYPROCK® THE RED BOOK™ 1


HIMMEL RANGE
HIMMEL CEILING TILE SELECTION
CSR Himmel offers a range of ceiling tiles for exposed grid ceiling systems, each with various surface finishes and different
properties to suit a variety of commercial applications. For more information please contact the Himmel team on 1300
374 253 or visit www.Himmel.com.au.

TABLE B7: CEILING TILE FEATURES, APPLICATIONS & SPECIFICATIONS


   APPLICATIONS – GRID CEILING SYSTEMS
OWA THICKNESS MASS

CEILING TILES (mm) kg/m2


  FEATURES

• A mineral fibre ceiling tile that offers good acoustic properties and a traditional fissured face pattern.
OWA Constellation A • Suitable for many commercial applications such as offices and education projects. 14 4.5
• Available in a variety of sizes and edge details.

• A mineral fibre ceiling tile that offers good acoustic properties and a pinhole face pattern.
OWA Finetta • Perfect for commercial projects where acoustics are essential to the environment. 15 4.5
• Available in a variety of sizes and edge details.

• A mineral fibre ceiling tile that offers good premium acoustic properties and durable face pattern.
OWA New Sandila • Ideal for commercial applications with large noisy areas such as classrooms, retail spaces and 15 4.5
hotels.

• A premium acoustic ceiling tile that offers high acoustic properties and a clean white face pattern.
OWA Brillianto A 15 4.2
• Perfect for general commercial spaces such as hallways and open plan office spaces.

• A mineral fibre ceiling tile that offers premium acoustic properties with a modern, clean face pattern.
OWA Sinfonia Privacy • Prevents the spread of bacteria, fungi, and germs, and effective in stopping the growth of MRSA
pathogens.
20 6.4
Humancare
• Achieves Hygiene Finish with Particle class ISO 4 (ISO 14644-1:1999)

• A mineral fibre ceiling tile that offers premium acoustic properties and a modern, clean face pattern.
• Perfect for commercial projects such as healthcare and retail where design and acoustics are
OWA Sinfonia Balance essential.
20 4.4
• Available in white and black and a variety of sizes and edge detail.

• Decorative acoustic woodwool panel made with responsibly-sourced spruce timber and cement.
Troldtekt Panel –
• Provides acoustic and aesthetic design in offices and retail projects and education spaces. 25 11.4
Ultrafine Natural
• Available in natural timber, grey, white, black and custom RAL colours.

• dECO Ceiling Tiles are durable acoustic ceiling tiles with square edges designed for standard drop-
in ceiling grid systems.
dECO Ceiling Tile • Available in 22 colours from our dECO Felt colour range. 25 2.85
• Suitable in a variety of spaces such as open plan offices, meeting rooms, boardrooms, break-out
spaces, classrooms and lecture theatres.

AFS RANGE
AFS rediwall®
AFS Rediwall is a PVC permanent formwork system and
a time-saving alternative to conventional masonry and
blockwork. Its precision-extruded components easily
interconnect for rapid installation. CodeMark Certified,
Rediwall panels are load bearing for multi-level structures,
is suitable design in accordance AS 3600, and provides
a consistently clean, even and water-resistant surface.
For more information on permanent formwork
systems contact AFS on 1300 727 237 or
visit afsformwork.com.au

GYPROCK® THE RED BOOK™ 1 B13


MATERIAL THERMAL PERFORMANCE
The R value, or thermal resistance of a material, expresses
PROPERTIES the ability of a particular material to resist heat flow.
Gyprock and Cemintel products have been tested to
ASTM C518 for thermal performance.
MANUFACTURING STANDARDS
The ‘R’ values for Gyprock plasterboards are:
CSR Gyprock and Cemintel products, as referenced in
this design guide, comply with the following manufacturing • 10mm plasterboard R = 0.04 – 0.05.
standards. (0.04 – 0.05 m2K/W).
Plasterboard • 12.5 – 13mm plasterboard R = 0.05 – 0.07.
(0.05 – 0.07 m2K/W).
• AS/NZS 2588 Gypsum Plasterboard.
• 16mm plasterboard R = 0.07 – 0.09.
CeminSeal Wallboard
(0.07 – 0.09 m2K/W).
• AS/NZS 2908.2 : 2000 Cellulose-cement products Part
The ‘R’ values for Cemintel products are:
2: Flat sheets. Type A, Category 3.
• 6mm fibre cement R = 0.02 (0.02 m2K/W).
THERMAL & MOISTURE • 7.5mm fibre cement R = 0.03 (0.03 m2K/W).
STABILITY • 9mm fibre cement R = 0.03 (0.03 m2K/W).
Gyprock plasterboard and Cemintel fibre cement products
are stable building materials when subjected to the normal RESISTANCE TO IMPACT
range of interior temperature and humidity conditions.
Wall lining materials may be selected for properties
Thermal coefficient of expansion (). delivering resistance to damage. These properties include
surface indentation (resistance to indentation from small,
• Plasterboard:  = 16.2 x 10 -6 mm/mm/°C in the
solid objects), soft body impact resistance (resistance to
temperature range 4°C to 38°C
damage from people impact, measured with a swung
• Fibre cement:  = 7.5 x 10 -6 mm/mm/°C in the sand bag) and hard body impact resistance (resistance
temperature range 0°C to 60°C to damage from solid object impact, measured with a
Hygrometric coefficient of expansion (). swung hammer). Refer to TABLE B8 to TABLE B10 for a
selection of linings and relative performance for the various
• Plasterboard:  =7.2 x 10-6 mm/mm/% (in the range properties.
5% to 90% R.H.)
Walls lined with Gyprock Fyrchek, Impactchek and
• Fibre cement:  = 6.6x10-6 mm/mm/% (in the range CeminSeal Wallboard can meet the requirements of
30% to 90% R.H.) NCC2022 Specification 6 [NCC2019: Spec C1.8]. This
• The value of total expansion from equilibrium to saturated clause specifies resistance to Uniform Distributed Loads
condition for fibre cement is 5.0x10-4 mm/mm. (UDLs), surface indentation and impact from a weighted
sand bag that is dropped from a specified height. For
Note that these values are approximate only and will vary
wall system deflection performance, please contact the
across the range of product formulations.
framing manufacturer for more information.
Gyprock plasterboard of 10mm and 13mm thickness
INTERNAL MOISTURE
provides adequate resistance to soft body impacts likely
Gyprock plasterboard must not be used where it will be in domestic or light commercial uses respectively. CSR
in contact with liquid water or an atmosphere of constant has tested these products to meet the requirements of
relative humidity above 90%. NCC2022 S6C11(b) [NCC2019: Spec C1.8:6b].
For wet area walls and ceilings (including external ceilings) In addition to the above requirements, CSR Shaft wall
subject to intermittent high humidity where plasterboard system has been tested to meet the addition requirements
is specified, any of the moisture resistant Gyprock for lift shafts of NCC2022 S6C5 [NCC2019: Spec
plasterboards are recommended. CeminSeal Wallboard C1.8:3.3].
products are highly suitable for wet areas and semi-
exposed ceilings. In all cases follow product installation
brochures.

B14 GYPROCK® THE RED BOOK™ 1


TABLE B8: Impact Properties - Surface Indentation TABLE B10: Impact Properties - Hard Body Impact
Lining Result Lining Rating¹
6mm Wallboard Pass 6mm Wallboard ✓

9mm Wallboard Pass 10mm HD ✓✓

10mm Plus Pass 10mm Plus ✓

10mm Supaceil Pass 13mm EC08 Extreme ✓✓✓

10mm HD Pass 13mm Impactchek ✓✓✓

10mm Aquachek Pass 13mm EC08 Complete ✓✓

13mm Standard Pass 13mm Fyrchek ✓✓

13mm Soundchek Pass 1 More ✓ indicates higher performance.


13mm Aquachek Pass

13mm Fyrchek Pass

13mm Fyrchek MR Pass

13mm EC08 Extreme Pass

13mm Impactchek Pass

13mm EC08 Complete Pass

16mm EC08 Complete Pass

16mm Fyrchek Pass

16mm Fyrchek MR Pass

30mm Glasroc F Pass


Note: test method as per NCC2022 Specification 6
[NCC2019: Spec C1.8].

TABLE B9: Impact Properties - Soft Body Impact


Drop Typical Wall
Lining Results
Height2 Application
6mm Wallboard Pass
Fire resisting
10mm HD1 100mm Pass
walls general
13mm Standard1 Pass

13mm Fyrchek Pass

13mm Fyrchek MR Pass


Fire resisting
13mm Impactchek walls of shafts Pass
150mm
and fire-isolated
13mm EC08 Extreme exits generally Pass
2 x 10mm Gyprock
Pass
Plus1
2 x 13mm EC08
Pass
Extreme
2 x 13mm EC08 Fire resisting
walls of certain Pass
Complete 350mm
Class 9b
16mm Fyrchek buildings Pass

16mm Fyrchek MR Pass


1 For PartyWall/StrataWall application.
2 Drop height requirement as per NCC2022 Specification 6
[NCC2019: Spec C1.8].

GYPROCK® THE RED BOOK™ 1 B15


FIRE HAZARD PROPERTIES COMBUSTIBILITY
The NCC limits the materials used in Class 2 to 9 buildings In accordance with NCC2022 Clause C2D10 [NCC2019:
by controlling the Fire Hazard properties of linings. These C1.9], plasterboard and fibre cement sheet may be used
properties are assessed using AS 5637.1. wherever a non-combustible material is required by the
Code.
Please refer to TABLE B11 for Gyprock plasterboard and
Cemintel product performance details. Contact Himmel Polyester insulation may NOT be selected where the
for properties of other acoustic ceiling products. system has non-combustible construction requirements.

TABLE B11: FIRE HAZARD PROPERTIES

Gyprock Plasterboard SMOGRARC


Group
Number
DESIGN
10mm Plus
10mm Supaceil
<100
<100
1
1
CONSIDERATIONS
10mm HD <100 1
13mm Standard <100 1 DESIGN RESPONSIBILITY
10 – 13mm Aquachek <100 1 This guide represents good practice, though it is not
13mm Soundchek <100 1 intended as an exhaustive statement of all relevant
information. It remains the responsibility of the customer
13mm Impactchek <100 1
(in conjunction with their designer or engineer, when
13 – 16mm Fyrchek <100 1
applicable) to ensure that CSR’s products/systems are
13 – 16mm Fyrchek MR <100 1 suitable for their chosen application for any given project.
13 – 16mm EC08 Complete <100 1 CSR recommends that a comprehensive assessment
13mm EC08 Extreme <100 1 of the performance requirements be undertaken prior
to selection, including in respect of project-specific
25mm Shaft Liner Panel MP <100 1
matters such as, but not limited structural adequacy,
6.5mm Flexible <100 1
seismic, acoustic, fire resistance/combustibility, thermal,
13mm Perforated Panel <100 1 condensation and weatherproofing requirements. For
12.5mm Gyptone Perforated
<100 1
further information refer to the relevant sections of this
Ceiling Panels guide, and to the specific system design & installation
12.5mm Rigitone Perforated guides.
<100 1
Ceiling Panels
Cemintel Fibre Cement CSR offers online digital tools for the most updated
CeminSeal Wallboard <100 1 information, including but not limited to update of
Gyprock Ceiling Tiles
products/components, inclusion of new and modified
10mm Freshtone Diamond White <100 1
systems, to meet the requirements of the National
Construction Code of Australia (NCC) and any relevant
10mm Supatone <100 1
Australian Standards.
10mm Arctic White <100 1
NOTES: For the most up-to-date product & system performance
SMOGRARC = Smoke Growth Rate Index information, visit:
Report: WF 45759
CSR System Selector: https://apps.csr.com.au/
Scan QR CODE for
Gyprock Fire Hazard Report systemselector/search-option
CSR Thermal Calculator: https://apps.csr.com.au/
thermalcalculator

WIND LOADS
All linings and framing are to be designed for the
appropriate wind loads. Contact CSR DesignLink for
loads higher than those stated in this guide.
Wind pressure can occur on walls and ceilings that
form part of the building perimeter enclosure due to air
infiltration through the façade and lining elements. It can
also occur on any wall and ceiling when openings are
present in the building façade such as doors and windows
that are left open or are damaged in a wind event. The
spacing of framing for these elements is dependent on

B16 GYPROCK® THE RED BOOK™ 1


the plasterboard lining span limits. Refer to TABLE B12 TABLE B13: MAXIMUM FRAMING CENTRES FOR
and TABLE B13 for maximum framing centres. PLASTERBOARD AND WALLBOARD LININGS ON
CEILINGS
Gyprock plasterboard and CeminSeal wallboard linings Wind Load (kPa) Ult.
Room
for all systems may be fixed with fasteners alone, using Linings 0.25 0.50 0.75 1.00
Conditions
nails or screws as appropriate. Linings for some walls and Max. Framing Centres (mm)
ceilings may be fixed with a combination of fasteners and Low humidity 450 450 450 450
10mm Plus
adhesive, for example, non-fire rated systems. Refer to High humidity 450 450 300 N/A
specific framing sections for more information. Other 10mm Low humidity 600 600 600 450
Gyprock
plasterboards High humidity 450 450 450 450
SEISMIC LOADS
13mm Gyprock Low humidity 600 600 600 600
Seismic actions must be considered for building plasterboards High humidity 600 450 450 450
elements in accordance with the NCC. The loads and
16mm Gyprock Low humidity 600 600 600 600
effects of earthquakes may be determined in accordance
plasterboards High humidity 600 600 600 600
with AS 1170.4 ‘Earthquake Actions in Australia’. The
Standard has design procedures for houses (Class 1), 6mm Low humidity 600 450 450 450
CeminSeal
and to buildings (Classes 2 to 9) with importance levels Wallboard High humidity 450 450 450 450
2, 3 or 4 as defined in the NCC. 9mm Low humidity 600 600 600 600
CeminSeal
Framed walls and ceilings lined with plasterboard and Wallboard High humidity 600 600 450 450
fibre cement products are subject to inertial forces and • For Gyptone and Rigitone products, please refer to the appropriate
the effect of movement such as inter-storey drift. The installation guide.
• Includes an allowance for up to 5kg/m2 insulation
calculated seismic forces may be equated to pressures
• Low humidity includes air conditioned spaces
as is done for wind loads and are resisted by the lining • High humidity includes non-air conditioned spaces
product’s strength properties and by the fastening
methods that attach them to the framing.
CONTROL JOINTS
Design pressures for linings are given in TABLE B12 &
TABLE B13. Values for the design of framing elements Movement and stresses created by temperature and
may be calculated by standard engineering practices or humidity fluctuation can result in deformation and damage
may be provided by product manufacturers. to internal linings and partitions.

The effects of both building movement and the inertial Control joints must be installed to allow for structural
forces require specific design of the connection of wall movement. Allowance for movement must be made
and ceiling framing to the structure. This is part of the through the frame, lining and any tiles.
wall framing manufactures design and information may Door frames extending from floor to ceiling constitute
be available from the frame supplier. control joints. For doors less than ceiling height, a control
TABLE B12: MAXIMUM FRAMING CENTRES FOR joint extending from one corner of the frame may be used.
PLASTERBOARD AND WALLBOARD LININGS ON
Control joints must be installed at all construction joints in
WALLS
Linings Wind Load (kPa) Ult. the building and at the following locations:
(horizontal or vertical
sheet orientation)
0.25 0.50 0.75 1.00 • Non-tiled internal walls with plasterboard outer layer –
10mm Plus 600 600 450 450 at 12m maximum centres.
Other 10mm Gyprock • Non-tiled internal walls with fibre cement outer layer –
600 600 600 450
plasterboards
12.5mm Glasroc X 600 600 600 600
at 7.2m maximum centres.
13 and 16mm Gyprock • Tiled internal walls – at 4.8m maximum centres.
600 600 600 600
plasterboards
6mm CeminSeal
600 600 450 450
• Internal Gyprock ceilings – at 12m maximum centres.
Wallboard
9mm CeminSeal • External Gyprock ceilings – at 6m maximum centres.
600 600 600 600
Wallboard
• Horizontal control joint at internal mid-floor position.
• For ceilings lined with CeminSeal Wallboard, refer to
Cemintel Ceiling Systems.
• At junctions with other building elements.
• At changes of lining material.
• At changes of structural support systems.
• At each storey or rise of studs.

GYPROCK® THE RED BOOK™ 1 B17


HEATING SEQUENCE OF WORKS
The following situations may give rise to localised high The sequence of works should be considered on a
temperature conditions (≥52°) which may be detrimental situation-by-situation basis, but generally will follow the
to wall and ceiling linings: following order:
• Radiant heaters, Internal construction for Class 2-9 buildings:
• Halogen lighting, 1. Building made weathertight.
• Heat pumps, 2. Framing installation.
• Reverse cycle air conditioners, 3. Installation of in wall services (roughing in).
• Solid fuel stoves. 4. Installation of insulation in fire rated walls.
Recessed lights must be installed in a way which prevents 5. Fire rated plasterboard installation and jointing.
damage from temperature rise and to prevent the risk of 6. Fire rated penetrations (elec, mech etc).
fire. Refer to AS/NZS 3000.
7. Installation of insulation in ceilings and walls.
Refer to heating unit manufacturer for more information.
8. Remaining plasterboard installation on ceilings then
walls.
GAS SERVICES & APPLIANCES
9. Jointing of plasterboard.
Where a gas stove in a residential or commercial
application is required to be installed to AS/NZ S5601.1 10. Finishing of services.
Gas Installations, there are requirements stipulated for
11. Decorative finishing.
the protection of surrounding construction. In this case
a fire resistant material must be used that meets the Internal construction for Class 1a buildings:
specification provided in the code. 1. Framing installation.
In residential applications, where a burner is within 200mm of 2. Building made weathertight.
a wall, protection methods include:
3. Mechanical, electrical services and penetrations.
• A splashback attached to the stove intended to protect
the rear wall. 4. Installation of insulation in ceilings and walls.

• 12mm fibre cement lining covered with 0.4mm steel 5. Plasterboard installation on ceilings then walls.
sheet. 6. Jointing of plasterboard.
• 5mm ceramic tiles attached to 10mm plasterboard or 7. Finishing of services.
6mm fibre cement lining.
8. Decorative finishing.
• 5mm toughened glass attached to 10mm plasterboard
or 6mm fibre cement lining.
Note that Gyprock plasterboards and Cemintel fibre
cement products do not meet the code definition of fire
resistant material.

ATTACHING FIXTURES
For non-fire rated plasterboard walls, lightweight fixtures such
as picture frames may be attached with proprietary fixings.
Check with the fixing manufacturer for allowable loadings.
Heavier loads such as shelves and appliances must be fixed
through the linings to the framing, such as studs or noggings.
For fire rated plasterboard walls, fixtures such as handrails
and other lightweight items may be attached to framing,
such as studs or noggings with maximum 10g screws.
Refer to details in Book 3. For the use of proprietary fixings
in fire rated walls, refer to the manufacturers’ details.

B18 GYPROCK® THE RED BOOK™ 1


FIRE RESISTANT unexposed surface of the specimen increases by
more than 140°C above the initial temperature, or the

DESIGN temperature at any point of the unexposed surface


increases by more than 180°C above the reference
temperature.
CSR Gyprock has developed systems with ‘Fire
Resistance Levels’ (FRL) up to – /180/180. The systems The test performance of the specimen is expressed as
and performance specifications detailed in this manual are a Fire Resistance Level, which indicates the number of
guaranteed only for the construction specified. Any variation minutes for which the specimen fulfils the requirements
or substitution of materials or assembly requirements, or of the three fire test criteria. These numbers are then
any compromise in assembly may result in failure under rounded down to the nearest regulatory requirement.
critical conditions. It is recommended that only accredited The common regulatory FRL requirements are:
plasterboard fixers install fire rated systems.
Non-Loadbearing Loadbearing
– /30/30 30/30/30
FIRE TESTING – /60/60 60/60/60
CSR Gyprock fire rated systems have been tested or – /90/90 90/90/90
assessed to AS 1530. 4 – Fire Resistance Tests of – /120/120 120/120/120
Elements of Building Construction, at approved testing – /180/180 180/180/180
laboratories.
For Example: – /120/120.
This standard gives the test method and criteria of failure
for the various elements of construction such as partition The dash indicates no requirement for Structural
walls, floor/ceilings and roof/ceilings. Adequacy, which applies to all non-loadbearing systems.

The specimen assemblies are built into the test furnace The first 120 indicates Integrity for 120 minutes.
and subjected to furnace temperatures in accordance The second 120 indicates Insulation for 120 minutes.
with AS 1530.4 Standard Time vs Temperature Curve.
TABLE B14: STANDARD TIME vs TEMPERATURE CURVE Resistance to the Incipient Spread of Fire
1200
Ceiling systems may be required to achieve a Resistance
1100
to the Incipient Spread of Fire. This requires the ceiling
1000 to provide adequate thermal insulation to prevent
TEMPERATURE (°C)

combustibles in a roof/ceiling or floor/ceiling cavity from


900
igniting for the specified time.
800
The National Construction Code (NCC) requirement for
700 some ceilings is to provide Resistance to the Incipient
600 Spread of Fire (RISF), into the space above it, for not less
than 60 minutes.
500

0 30 60 90 120 150 180 210 240 270 300 330 360


TIME (minutes)
Fire Hazard Properties
Fire hazard properties of wall and ceiling linings in some
classes of building are specified by the NCC. Refer to
FIRE RESISTANCE LEVEL (FRL) TABLE B11.
The fire rating of systems is determined by laboratory
testing to determine the time to failure of three performance Smoke Proof Walls
measurements, which combine to give a Fire Resistance
Smoke proof walls are required in some Class 9a buildings,
Level (FRL). They are:
and, where they do not require an FRL, must be built from
Structural Adequacy non-combustible materials. Steel framed wall systems clad to
full height with Gyprock Standard Plasterboard may be used.
Failure occurs when the specimen collapses under load.
Fire rated smoke proof walls should be selected from the steel
Integrity framed systems with an appropriate FRL.
Failure occurs when the specimen develops cracks or Smoke proof walls required for Class 9c buildings may use
openings through which flames or hot gases can pass. steel or timber framing with linings of 13mm Gyprock Standard
Plasterboard, continued full height on a minimum of one side.
Insulation
Failure occurs when the average temperature of the

GYPROCK® THE RED BOOK™ 1 B19


Penetrations and ductwork. Practical methods for addressing common
situations within buildings can be seen in Section J.
Service penetrations in fire rated walls and ceilings
that can be effectively rated include electrical and data
cables, switches and GPOs, hydraulic pipes, vents and SOUND IMPACT RATINGS
mechanical ducts. Access panels and control joints can The NCC has performance requirements relating to sound
also be installed with appropriate fire resistance levels. impact for floors and some walls.
Power outlets and light switches can be installed in fire For floors, this is specified as a maximum value such as:
rated walls using fire rated switch boxes. When installed Lnw = 62. Note that lower values of Lnw indicate better
correctly, these maintain the FRL of the wall system in acoustic impact performance.
which they are installed.
Walls may be required to meet the definition of
Where fire and acoustic rated switch boxes are specified, Discontinuous Construction. This means that wall leaves
refer to the manufacturer for appropriate products and must be separated by at least 20mm and no mechanical
installation details. connection is permitted, except that masonry may have
resilient ties.

BUILDING ACOUSTICS Systems that meet this specification are noted in the
appropriate system specifications.
Building acoustics can be separated into sound FIG B1: COMMON FLANKING TRANSMISSION PATHS
absorption and sound transmission. 1. Ceiling plenums, floors, walls. 4. Heating and ventilation ducting.
2. Poor seals between structural 5. Rigid plumbing connections
Sound absorption relates to control of sound that is elements and around service and penetrations.
penetrations. 6. Back-to-back cabinets and
generated within a room and how it affects people in
3. External air-borne paths. switches/power outlets.
that room.
Sound transmission relates to sound that passes through
1
a dividing element (direct sound, controlled by the
element’s sound insulation), and through the surrounding 4 1
3
2 2
structure (indirect or flanking transmission).
Methods of controlling noise in buildings can be based 2

on systems, structure and lining materials and their 2


3 6
absorption and transmission properties.
4 2
CSR Gyprock recommends that an acoustic engineer be 3
6
consulted for all projects where acoustics are important. 5
1
FLANKING TRANSMISSION
Flanking sounds reach adjoining areas by indirect paths,
rather than through the dividing element. The perimeter SYSTEM PERFORMANCE
junction of walls, floors and ceilings that surround The Rw, Rw + Ctr and Ln,w values in this manual refer to
the dividing element are the main paths for flanking expected results of a laboratory test on an element. Text
transmission. Other paths include open windows, ducts, has been bolded with Rw + Ctr value greater than 50dB
doorways and suspended ceilings. Common flanking for common building code requirement.
paths are shown in FIG B1.
Extensive testing over many years has been carried out
Noise sources that have a high degree of low frequency by CSR at laboratories including the Commonwealth
noise such as traffic, aircraft and surround sound systems Experimental Building Station (later CSIRO) at North
have potential for transmission through the building Ryde NSW, National Acoustic Laboratory at Lindfield
structure. Transmission of this type of noise follows NSW, CSIRO Laboratories at Highett, and Clayton, VIC,
structural load paths and can be controlled by breaking RMIT acoustic laboratories, VIC and even, up to 1978,
these load paths or providing complete separation of the at the Gyprock NATA registered laboratory. Extensive
structure. development testing has been carried out at Resolute
Noise sources that generate a high amount of mid and (formally kilargo) Acoustic Laboratories, QLD and Rintoul
high frequency noise, such as services and speech, Laboratories, NSW.
tend to transmit via air paths and direct transmission in Performance values provided by PKA Acoustic Consulting
lightweight construction. use a prediction system based on these tests, and the
Typical problem areas for this type of transmission include system has been updated to include the most current
doors and door frames, glazing, suspended ceiling cavities CSR sponsored testing. The prediction system has

B20 GYPROCK® THE RED BOOK™ 1


been calibrated against the round robin European The likelihood and effect of defects occurring with typical
test of a standard plasterboard wall in 24 European systems is shown in TABLE B15.
acoustic laboratories, and has successfully predicted the
TABLE B15: ACOUSTIC INTEGRITY
performance of a calibration wall for the Resolute Acoustic
Chance of Gaps Effect of
Laboratory. Wall System Being Left Defects on
As testing from different laboratories can vary (the Unsealed Performance

European 24 laboratory test of the standard plasterboard


wall was Rw47 to Rw52), it is possible that laboratory
tests may be 1 to 2 Rw points above a prediction. High High Degradation

All care has been taken with preparation of these


predictions and it is assumed that construction is strictly Single skin masonry wall
in accordance with this manual and relevant Gyprock and
Cemintel installation guides.
The PKA Predictor was used in The Red Book 01 to High High Degradation
calculate acoustic values for specified systems. The
PKA Predictor formulas are based on PKA’s extensive Masonry with stud,
experience calculating the acoustic properties of uninsulated
lightweight wall systems. PKA certifies that the PKA
Acoustic Predictor is an accurate tool for the acoustic
prediction of lightweight wall systems. These acoustic Low High Degradation
predictions result in tolerances within ±2 Rw points
when validated against acoustic laboratory test results
Single stud, uninsulated
and other supporting information, which have their own
inherent variability.

Moderate
SITE PERFORMANCE vs Low
Degradation
LABORATORY PERFORMANCE
Single stud, insulated
As houses are not built like laboratories, it is unlikely that
performance measured in ideal test conditions will be
achieved in a building. Designers should take care to
select systems compatible with the support structure to Low Low Degradation
provide the desired level of insulation.
The NCC specifies deemed to satisfy acoustic values Double stud, insulated
that are laboratory results, and in some cases allows
lower values when site tested. For example, in a Class BACKGROUND NOISE
2 building the separating wall can have Rw + Ctr = 50
Low levels of noise transmitted from other areas can be
(a laboratory result), or DnT,w + Ctr = 45 (tested on site).
partially obscured by background noise.
The difference of 5 is that expected between site and
laboratory, although it might not always be the case. Where the background noise level is low, such as in
CSR Gyprock recommends that where designers are remote areas, consideration should be given to providing
selecting systems based on expected site performance, a higher than standard level of sound insulation.
an acoustic engineer be consulted.
VARIATION IN OCCUPANT
ACOUSTIC INTEGRITY PERCEPTION OF NOISE
The acoustic integrity of a system can be influenced by Tolerance for noise varies greatly between people,
the combination of elements that make up the system. and variations of up to 15dB can be considered
Single leaf and uninsulated systems are more dependent acceptable. This means consideration should be given
on high quality installation, as relatively minor defects can to the occupant’s expectation of the internal acoustic
cause major degradation of the system performance. environment. Users of concert halls and practice rooms
Building systems that allow defects to be hidden from view may have higher acoustic expectations than guests of
have a higher chance of gaps being left unsealed, making inner city hotels.
them more vulnerable to performance degradation.

GYPROCK® THE RED BOOK™ 1 B21


MINIMUM PERFORMANCE LEVELS • Background noise levels are low.

FOR INTERNAL WALLS & CEILINGS • Flanking transmission of the surrounding structure,
particularly at windows and doors.
The NCC sets out minimum performance levels for
internal walls and ceilings based on acceptable standards • The lack of simplicity in construction could reduce
for affordable housing. The performance requirements are actual performance.
in terms of Rw, Rw+Ctr and Ln,w.
These levels may need to be increased for: PENETRATIONS
• Variation in occupant perceptions of noise, e.g. high, The acoustic performance of walls and ceilings can be
medium or low cost housing. reduced by penetrations for plumbing, electrical switches,
light fittings, etc. For construction that is acoustically
• Local authorities have higher or additional requirements. sensitive, it is recommended that, wherever possible,
• Background noise levels are low. such penetrations are avoided. In other cases, rated
proprietary sealants and products should be used.
• Flanking transmission of the surrounding structure.
Lightweight structures can be more prone to low There is a wide range of services and materials that may
frequency flanking. be required to penetrate sound rated walls and ceilings,
and in varied configurations and concentrations. CSR
• The presence of services will vary which NCC provisions Gyprock recommends that an acoustic engineer be
are applicable, and could mean separate construction consulted for advice on all details for projects with specific
is required. acoustic objectives.
• The lack of simplicity in construction could reduce The patented Gyprock SilencerF has been developed for
actual performance. use in Gyprock walls to provide fire and acoustic ratings
for various penetrations. It can maintain fire rating up
MINIMUM PERFORMANCE to FRL –/120/120 and maintain the system acoustic
LEVELS FOR SERVICES rating. Taps, pipes, power outlets, light switches and
similar services can be installed in systems incorporating
The NCC sets out minimum performance levels for SilencerF sections.
isolation of noise from services based on acceptable
standards for affordable housing. The performance levels Fire and acoustic rated switch boxes are available from
are in terms of Rw and Rw+Ctr. manufacturers such as CLIPSAL and HPM to assist in
maintaining the acoustic integrity of wall systems.
These levels may need to be increased for:
FIG B2: TYPICAL POWER OUTLET/LIGHT SWITCH
• The nature of the noise source and adjacent occupant INSTALLATION USING FIRE RATED SWITCH BOX
activity. Some noises are particularly annoying to
occupants.
Stud Gyprock fire grade
• Variation in occupant perceptions of noise, e.g. high, plasterboard (number of
layers and thickness in
medium or low cost housing. accordance with wall
system specifications)
• Background noise levels may be very low.
Fire Rated Switchbox
• The lack of simplicity in construction could reduce
actual performance. Seal around cutout and
cable penetration as
per switch box
manufacturer’s
MINIMUM PERFORMANCE requirements

LEVELS FOR EXTERNAL WALLS


The NCC does not set minimum performance levels of
transmission for external walls, although some State
and local government rules apply, for example Qld
Development Code MP4.4 for Noise Corridors. Guidance
should be sought from an acoustic consultant or local
authority for setting the design requirements of these
elements, as they may be affected by road or aircraft
noise.
Issues that may affect the design levels for external walls are:
• Variation in occupant perceptions of noise,
e.g. high, medium or low cost housing.

B22 GYPROCK® THE RED BOOK™ 1


GAPS, CRACKS & HOLES A number of noise criteria refer to, and are measured in
dB(A). The larger the dB(A) level the louder the noise.
Small openings allow airborne sound to pass through
an element and can significantly reduce sound insulation Ln,w – Weighted Normalised Impact Sound Pressure
performance. For optimum sound insulation, the element Level. A measure of the noise impact performance of a
must be airtight. floor/ceiling. It is measured in very controlled conditions
in a laboratory and is characterised by how much impact
Perimeters and penetrations for services must be sealed sound reaches the receiving room via the ceiling/floor
with an acoustic sealant that is capable of accommodating from a standard tapping machine test.
the expected building movement.
The lower the number the better the performance.
For systems that are multi-layered, such as masonry
composite systems, each layer must be air tight, as services L’ nT,w – Weighted Standardised Field Impact
such as power points and switches can act as airborne Sound Pressure Level. A measure of the noise impact
flanking paths. To remedy this, consider using acoustic performance of a floor/ceiling. It is similar to Ln,w except
rated power boxes, the Gyprock SilencerF, and insulation it is measured in the field and is therefore subject to the
in the cavity. inherent inaccuracies involved in such a measurement.
The lower the number the better the performance.
ACOUSTIC TERMINOLOGY NRC – Noise Reduction Coefficient. A measure of the
DEFINITIONS ability of a material to absorb sound.
Rw – Weighted Sound Reduction Index. A measure of NRC is generally a number between 0 and 1. A material
the sound insulation performance of a building element. with an NRC rating of 1 absorbs 100 % of incoming sound,
Rw is a laboratory measurement similar to STC. that is, no sound is reflected back from the material.
Rw is measured and calculated using the procedures from STC – Sound Transmission Class. A measure of the
the relevant Australian and International Standards. The sound insulation performance of a building element used
related field measurement is abbreviated as DnT,w. in the BCA prior to 2000. It is measured in very controlled
conditions in a laboratory.
The higher the number the better the insulation
performance. CAC – Ceiling Attenuation Class. A single number
rating from a laboratory test to measure sound reduction
D nT,w – Weighted Standardised Field Level
between rooms via the ceiling.
Difference. A measurement of the sound insulation
performance of a building element. It describes the Dnc,w – Weighted Suspended Ceiling Normalised
difference in noise level on each side of a wall or floor, Level Difference. Similar to CAC.
and indicates the level of speech privacy between spaces.
Source: National Construction Code, Sound Insulation
It is measured in the field and is therefore subject to the
Guideline.
inherent inaccuracies involved in such a measurement.
αw – Weighted Sound Absorption Coefficient
The higher the number the better the insulation
performance. Calculated According to AS ISO 11654-2002

Ctr – A spectrum adaptation value used to modify the A Weighted reference curve from 250Hz to 4000Hz is
sound insulation performance of a wall or floor. Sound shifted until an octave band result exhibits deviation.
insulation performance can be described by R w or Shape indicators mean that one or more frequencies is
the D nT,w but these are not accurate for all noises, considerably higher than the weighted reference curve.
especially for low frequency bass noise from modern
stereo systems. Ctr values are negative values which are (L) denotes excess performance at 250Hz
added to either the Rw or DnT,w. The standards set out (M) denotes excess performance at 500Hz, 1000Hz
testing methodologies for the sound insulation properties
of building elements and incorporates these factors and (H) denotes excess performance at 2000Hz, 4000Hz
explains their use.
Smaller negative Ctr values are more favourable than large
negative values.
dB(A) – The ‘A’-scale and dB(A) noise level are used
to degrade the performance of a sound level meter to
simulate what humans hear. The human ear is not a
perfect listening device, it is poor at hearing low frequency
noise. dB(A) is used to compare measured sound with
perceived sound.

GYPROCK® THE RED BOOK™ 1 B23


THERMAL NCC2016 Amdt. 1 Volume 1 and NCC2016 Amdt. 1
Volume 2 (and earlier).

PERFORMANCE Class1 and Class 10 only for NCC2019 (incl. Amdt. 1)


Volume 2.
External wall and roof systems in this manual have thermal For product information, refer to section B of this
Total R-Values expressed as Rt (WIN) and Rt (SUM). These guide. Note, the insulation also improves the acoustic
are intended for use in various Climate Zones to suit the performance of the wall against outside noise.
direction of heat flow, that is, Winter (WIN) for upward
heat flow through roofs, outward for walls, and Summer
(SUM) for downward heat flow through roofs and inward
for walls.
CONDENSATION
The Total R-Values presented have been calculated using & MOISTURE
Bradford’s Thermal Calculation software version 1.6 and
are in accordance with the methods of AS/NZS 4859.1 CONTROL
– Materials for thermal insulation of buildings – General
criteria and technical provisions. Any included bulk
insulation is a CSR Bradford product that has a material CONDENSATION CONTROL
R-Value compliant with the standard, and building Gyprock plasterboard will give many years of satisfactory
elements have thermal values sourced from the ICANZ performance under a wide range of climatic conditions,
Technical Handbook. Wall cavities provided behind light but to ensure long term performance to both lining material
weight claddings are assumed to be ventilated in line with and paint finishes, care should be taken in design of the
weather resistance details, while masonry veneer walls external envelope to ensure that damaging condensation
and roofs are treated as non-ventilated in accordance does not occur.
with guidance in the ICANZ handbook.
Condensation within a building is the result of a
Thermal performance values quoted are based on an temperature difference from one side of a building element
assessment through the insulation path. This method to the other. The temperature differential forces water
is consistent with the definition of Total R-Value given in vapour contained in the warmer air to flow towards the
Volume Two of the NCC and excludes thermal bridging cooler region where it condenses on any surface below
effects. The calculation for Total R-Value in accordance the dew point temperature of the air.
with NCC Volume One requires consideration of an
For walls and ceilings, vapour barriers are incorporated
element’s framing components and arrangement and,
into the structure to prevent the flow of water vapour from
for walls, any glazing areas. CSR recommends that an
the warm to the cool regions. As a general rule, locate the
energy consultant is used for project specific calculations.
vapour barrier as close as possible to the surface which
NCC 2022 will include changes to energy efficiency will normally be at the higher temperature at the time of
requirements. These requirements will express the the condensation hazard.
R-Value of the building fabric as the Total R-Value. The
For ceilings, unheated roof spaces should be adequately
Total R-Value will consider the project specific external wall
ventilated. Comprehensive ventilation solutions are
configuration and materials used, so that the impact of
available from Bradford Ventilation, part of the Bradford
the thermal bridging on the added insulation is captured.
Insulation Group. In rooms such as bathrooms, kitchens,
Additional to the effects of thermal bridging through the and laundries, moisture laden air should be exhausted to
framing paths of the structure, the designer will need the outside of the building, not to the roof or floor space.
to allow for gaps in the bulk insulation layer in the wall
Condensation is a complex problem and can occur
system due to structural framing (i.e., studs, noggings,
under a variety of conditions, not just in cold and
perimeter of wall openings) and services obstructing or
tropical climates. There are a large number of factors
limiting wall insulation coverage, slab edge insulation,
that need to be considered in assessing and managing
wall cavity ventilation, and the effects of air leakage
condensation risk. Such factors include the local climate,
due to unsealed architraves, unsealed door jambs,
building use, orientation, material R-Value of the insulation
unsealed gaps between windows and the masonry wall
and the type of bulk insulation, position and integrity of
or services penetrating the inner leaf. These effects are
vapour barriers/vapour permeable membranes, and the
to be compensated for as outlined in NCC Volume One
degree and location of ventilation. As a result, it is highly
Section J.
recommended that designers undertake a condensation
For projects conforming to BCA versions prior to the NCC risk analysis as part of the building design.
2022, thermal bridging consideration is not required in the
Additional literature on this subject is available from
Total R-Value calculation for all building classes, such as:
CSIRO, BRANZ, ASHRAE and ABCB, and should be
Class 1 to Class 10 buildings (all building classes) for consulted.

B24 GYPROCK® THE RED BOOK™ 1


MOISTURE CONTROL WITHIN Methods to control moisture within buildings include:

BUILDINGS • Providing adequate ventilation of the building sub-floor.

Moisture can be evident within a building for varied • Ensuring the roof space is adequately ventilated, as
reasons and may include: failure to do so may result in the plasterboard sagging,
or the excessive moisture movement of the timber
• Failure of the building fabric to protect the building
framing causing nail popping or joint deformation.
from the ingress of external water, such as defective
Attics or similar unheated spaces above ceilings can
roofs, external claddings, flashings, etc. Wind loads
be adequately ventilated to provide effective cross-
can produce lower air pressures within buildings than
ventilation by screened louvres or other approved and
on the outside, forcing water through small gaps in the
acceptable means. The ratio of total net free ventilating
building envelope around penetrations and joints, even
area to area of ceiling shall not be less than 1/150.
at low wind speeds.
• In rooms such as bathrooms, kitchens, and laundries,
• Dampness within the building sub-floor due to poor
moisture laden air should be exhausted to the outside
sub-soil drainage and ponding of water under the
of the building, not into the roof space.
building.
• Installing wall wraps/sarking into the structure to
• Excess moisture from within the building including due
control the flow of water vapour from the warm to
to the condensation of water vapour, including from
the cool regions to prevent condensation within the
sources including cooking, bathing, and the vapour
structure. This is a complex problem and can occur
expelled in the breath of its occupants. Condensation
under a variety of conditions (not just in cold and
within a building is the result of a temperature difference
tropical climates) so selection of the right wall wrap/
from one side of a building element to the other. The
sarking needs to consider the local climate, building
temperature differential forces water vapour contained
use and orientation, material R-Value of the insulation,
in the warmer air to flow towards the cooler region
as well as the degree and location of ventilation.
where it condenses on any surface below the dew
point temperature of the air. Additional literature on condensation is available from
sources including the CSIRO, BRANZ, ASHRAE, and
• Failure of appliances within the building and the leakage
the ABCB.
of water, including from Hot Water Systems, plumbing
fittings and drains, etc. The control of moisture within a building is a requirement
of the Building Code of Australia and is the responsibility
of the designer.

TABLE B16: RECOMMENDED PRODUCTS FOR MOISTURE MANAGEMENT OF WALLS


Climate (NCC Zone) Guidance on Vapour Control Performance and Category Recommended CSR Products
Bradford Thermoseal membranes
Warm-Humid, or Where vapour flow is typically inward, such as
Bradford Thermoseal Firespec
Tropical climates where the building is air-conditioned for cooling, Vapour Barrier - Class1 or 2
Cemintel Rigid Air Barrier with a
(Zone 1) the membrane should function as a vapour barrier
Vapour Barrier Membrane
These climates have varying diurnal and seasonal
temperature changes that can affect the direction
of the water vapour flow. In most cases a vapour
Bradford Enviroseal™ membranes
permeable membrane outside the insulation is
Bradford Thermoseal membranes
Temperate or Hot- recommended to avoid creating a moisture trap,
Vapour Permeable or Vapour Cemintel Rigid Air Barrier
Dry (inland) climates allowing drying in either direction. Where a high
Barrier Class 2, 3 or 4 as required Cemintel Rigid Air Barrier with a
(Zones 2, 3, 4, 5) level of thermal insulation is used, a high degree
Vapour Barrier Membrane
of permeability may be required, and in some
Gyprock Glasroc X
locations a vapour barrier is required. Expert
guidance based on local experience should be
sought.
Where there is a strong tendency for outward
migration of vapour and a high risk of
Cold climates(1) Vapour Permeable Bradford Enviroseal™ membranes.
condensation, vapour permeable membranes
(Zones 6, 7, 8) Class 3 or 4 Gyprock Glasroc X
should be installed on the cold, external side of the
insulation.(1)

(1) The use of a Class 3 membrane such as Cemintel Rigid Air Barrier may not be sufficient in some cold climates. If a Class 4 membrane cannot be
used, a solution may include the use of a material to the interior side of the insulation that acts as a vapour barrier, e.g. a Class 1 or 2 membrane or
a vapour sealed plasterboard lining coupled with a mechanical ventilation solution. Seek expert advice prior specifying systems for these regions.

GYPROCK® THE RED BOOK™ 1 B25


LEVELS OF FINISH applied, and the fitting and finishing of stopping beads.
Refer to FIG B3.

Levels of finish are defined in the Australian/New Zealand It should be noted that, generally, residential applications
Standard AS/NZS 2589 Gypsum linings – Application and should be prepared to a minimum Level 4 Finish unless
Finishing for non-fire rated applications. This standard is specifically a higher or lower level of finish is agreed to
intended to provide builders, plasterboard installers and by all contracting parties. Other commercial applications
finishers, and their customers with the various defined should be specified in contract documents.
methods and practices necessary to meet the customer’s
expectations in terms of the ‘Level of Finish’. SELECTION OF LEVEL OF FINISH
Three Levels of Finish (3, 4 and 5) are defined, and Factors affecting the level of finish include the surface’s
minimum specifications to achieve each level of finish visibility, the texture and gloss level of the final decoration
are detailed in the standard for each of the installation and the lighting conditions. Critical or glancing light is that
processes from framing preparation to finishing. All details projected across the surface at low angles of incidence,
may not be suitable for fire rated systems or multilayer as opposed to diffused lighting or light striking the surface
systems. at close to right angles. Refer to the following section
It is essential to determine the level of finish required before “Surface Finishing & Lighting” on page B28.
the frame construction begins, as specific tolerances are A good method to overcome differences in opinions of
required for frame alignment as well as for plasterboard quality is to prepare a sample area in a suitable position
fixing and finishing for each of the levels of finish. Unless and for all parties to agree on the finish. The flow chart
these requirements are met throughout construction, FIG B3 and TABLE B17 will assist in selecting the most
it may not be possible to attain the desired finish level appropriate Level of Finish for each area.
without extensive corrective measures.
For further information on levels of finish, refer to
The level of finish specified also affects the methods Plasterboard Expectations, available from the Association
of jointing, particularly butt joints and back-blocking of Wall & Ceiling Industries.
requirements, the number of coats of joint compound

FIG B3: SELECTING A LEVEL OF FINISH

Decoration

Finish Not Important Wall Covering,


Paint
or Undecorated Wallpaper or Texture

Flat/Matt/Satin/ Semi-gloss/Gloss
Low Sheen

Pastel/ Dark Tones


Mid-tones

Critical and Non-critical Critical Critical and


Non-critical Lighting Lighting Lighting Non-critical Lighting

Level 3 Finish Level 4 Finish Level 5 Finish

B26 GYPROCK® THE RED BOOK™ 1


Level 3 Level 5
For use in areas that do not require a finish, such as above This level of finish should be used wherever gloss or semi-
ceilings and inside service shafts and other inaccessible gloss paints are to be used, where paint is mid or dark
spaces. All joints are to be taped with two applications coloured, or where critical light conditions occur such as
of compound and all fastener heads are to be covered. from windows, skylights, or silhouette and spot lighting.
Compound is to be finished smooth, such as by scraping
A three coat jointing system is required as for level four.
ridges etc with a trowel.
All joint compound should be sanded to a smooth finish
free of tool marks and ridges. This should be followed
Level 4 by the application of proprietary surface preparations by
This is generally the accepted level of finish for residential skim coating to remove differential surface textures and
construction. Joints are to have a tape coat, and two porosity.
separate coats are to be applied over the tape coat and Skim coating is a term used to describe a thin finish coat,
fastener heads. All joint compound should be sanded to rolled, trowelled or airless sprayed and then possibly
a smooth finish free of tool marks and ridges. Refer to sanded, to achieve a smooth and even finish. It is
Gyprock Installation guides for details. normally less than 1mm in thickness and is applied over
Gyprock One Finish is a pre-mixed acrylic compound the entire surface to fill imperfections in the joint work,
designed to create a uniform surface on interior walls smooth the paper texture and provide a uniform surface
and ceilings affected by critical lighting conditions. The for decorating.
application of One Finish over a standard level 4 finish
will improve the final surface and minimise the effects of
critical light, however it will not automatically upgrade the
work to a level 5 finish.

TABLE B17: SUMMARY OF GYPROCK ‘LEVEL OF FINISH’ DEPENDENT REQUIREMENTS – NON-FIRE RATED
CONSTRUCTION

It should be noted that, generally, residential applications should be prepared to a minimum level 4 finish unless
specifically a higher or lower level of finish is agreed to by all parties.
Key to Symbols:   – = Not Applicable.   ✓ = Required.   Other symbols, see notes.

Max. Frame Joint Between Frame Members * Adhesive * Fastener Jointing and Finishing (minimum)
Level and Back-block
Alignment + Only
of Ceilings Walls OR
Deviation Fastener Fixing Butt and Recessed Joints
Finish
mm Butt Recessed Butt Recessed Fixing ➃ ➃ Internal and External Corners

3 4 – – – – ✓ OR ✓➄ Tape Coat + Second Coat

4 4 ✓ ✓➁➂ ✓➀ – ✓ OR ✓➄ Tape Coat + Second Coat + Finish Coat

Tape Coat + Second Coat + Finish Coat


5 3 ✓ ✓ ✓➀ – ✓ OR 3➄
+ Skim Coat to the entire surface
NOTES
➀ Where a butt joint in a wall is less than 400mm long and is located more than 2 metres from the floor, there may be no need to provide back-
blocking.
➁ Back-blocking required only where 3 or more recessed joints occur in a continuous ceiling area.
➂ Back-blocking is not required in suspended ceilings with no rigid connection between ceiling and walls.
➃ Tiled and/or fire rated installations MUST be all fastener fixed, adhesive is not permitted. All butt-joints to be on-stud.
➄ Not permitted for unseasoned timber.
* Tiled installations MUST be all fastener fixed, adhesive is not permitted.

GYPROCK® THE RED BOOK™ 1 B27


SURFACE FINISHING & LIGHTING • Wall lights and downlights close to walls.

Builders, plasterers and painters work hard to achieve • Windows at the end of long corridors.
the appearance of a flat surface when installing walls and • Brightly lit rooms.
ceilings. However, some surface variation is inevitable due
to the following factors: • Lights installed just below skillion/raked ceilings.

• Natural variations in the framing. • Reflections of light from water features.

• The hand-finished nature of a plasterboard wall or


ceiling.
CONSIDERATIONS TO MINIMISE
GLANCING LIGHT
• Subtle differences between the textures of plasterboard
and the jointing compounds. The best time to consider potential glancing light issues
is during the design phase, which allows choices to be
Under the majority of lighting conditions a plasterboard
made that can greatly reduce the impact of glancing light.
surface finished to a Level 4 standard, as defined in
AS/NZS 2589 ‘Gypsum Linings - Application and Large window areas are a popular feature of modern
finishing’, will appear flat. In critical lighting conditions, design and the preference for open plan living and
an effect referred to as ‘glancing light’, will highlight any working often results in ceilings and walls that extend
surface variations. through a number of different spaces. These features
can lead to challenging lighting conditions for wall and
This section will assist in minimising glancing light issues
ceilings surfaces.
and enhance the occupant’s enjoyment of their premises.
When designing a project it is important to consider the
effects of both natural and artificial light and how it will fall
What is Glancing Light? on the walls and ceilings across the whole day.
Glancing light (or critical light) is a condition which exists In particular, attention should be given to light entering the
when light hits the plasterboard surface at an acute angle building in mornings and evenings when the sun is lower
and casts shadows that highlight any surface irregularities. in the sky and casts elongated shadows that can highlight
On plasterboard walls and ceilings this can make the any surface variations in walls and ceilings.
surface look uneven and highlight the appearance of
joints.
Shading
This is most commonly found in situations where there
are: For windows that are positioned where glancing light can
be an issue, the use of external shading or vertical louvres
• Floor to ceiling windows.
may help to mitigate any problems. Curtains or interior
• Windows directly adjacent to walls. blinds are also helpful in this situation.
• Unshaded batten holder ceiling lights.
• Ceiling mounted fluorescent lights. Window Placement and Orientation
Ideally windows should not abut walls or ceilings and
FIG B4: WHAT IS GLANCING LIGHT
should be oriented away from the east and west. External
reflective surfaces, such as pools or neighbouring
buildings, can reflect light into the space, should also be
Direct Light
considered as they can exacerbate the problem.
Rooms with windows in two orientations provide a more
uniform natural light, and can reduce the effects of critical
light.

Joint Orientation
The installation of plasterboard walls and ceilings should
also be considered as there are a number of design and
Glancing Light
installation choices which can significantly impact the
appearance of the surface.
Running the plasterboard so that the long joints are parallel
to the direction of the light will help reduce the effects of
glancing light. The use of longer sheets to reduce the
number of butt joints is also beneficial.

B28 GYPROCK® THE RED BOOK™ 1


FIG B5: JOINT ORIENTATION • Do not use uplights, wall-washers and spotlights in
areas with a smooth wall finish to eliminate light being
emitted at a glancing angle to the surface.
• Preferably, locate fluorescent lights about 450mm below
the ceiling as this will give a more even distribution of
light.
• When installing ceiling mounted fluorescent lights it is

SUNLIT WINDOW
PLASTERBOARD JOINTS
recommended to position the light fittings over the long
edge joints. Refer to the following illustration.
FIG B6: INSTALLATION OF CEILING MOUNTED
FLUORESCENT LIGHT

LIGHT LIGHT

PLASTERBOARD
PLASTERB
PLASTERBOARD
OARD JOI
JOINTS
NTS

Artificial & Natural Lighting


Any imperfection in a completed lining installation will be
made obvious by a condition called critical lighting or
glancing light, where the incident light from an artificial
or natural light source is nearly parallel to the surface.
PLASTERBOARD
PLASTERB
PLASTERBOARD
OARD JOI
JOINTS
NTS
Glancing light also greatly exaggerates the size of
imperfections making them glaringly obvious.
The worst result is achieved by an unshaded light source
LIGHT LIGHT
located directly on a ceiling or wall where the light shines
parallel to the surface.
Cases where this situation may exist include:
• Unshaded batten holder light fittings.

• Fluorescent lights mounted on the ceiling.
• Wall mounted up lights and downlights.

Methods to minimise glancing/critical lighting


LIGHT

LIGHT

effects from artificial lighting sources


PLASTERBOARD JOINTS
The following lighting solutions will provide diffused light
and reduce the appearance of surface variations:
• Shaded batten holder light fittings.
• Ceiling mounted pendant lights.
• Recessed ceiling lights such as downlights and
PLASTERBOARD JOINTS
LIGHT

LIGHT

recessed fluorescents (although recessed lights are


more likely to be associated with glare problems).
• Consider the use of more lights of lower intensity at
regular spacings, ensuring lit areas overlap. This will
improve ambiance and reduce the visible effects of
glancing light, and minimise shadows that can occur
from a single row or single light source.

• Allow a generous angle of incidence to the surface
for feature lighting such as spotlights, to minimise the
highlighting of imperfections.
• Do not locate a single or isolated unshaded light source
close to a wall or ceiling in a space which has generally
low levels of light.

GYPROCK® THE RED BOOK™ 1 B29


Methods to minimise glancing/critical lighting Colour Selection
effects from natural lighting sources
Light colours diffuse light more effectively than dark shades
• Do not take window glazing right up to the ceiling level.
and reduce the effects of glancing light. In rooms where a
• Avoid placing windows or glass doors immediately dark colour is to be used a level 5 finish is recommended.
adjacent to the end of a wall.
• Provide sun shades over the windows and glass doors. Wall Paper Finishes
• Recess the window to stop the sunlight reaching the Gyprock plasterboard walls may be finished with wall
wall. paper. A Level 4 Finish is recommended. A primer sealer
should be applied to the surface prior to wall paper
APPLIED FINISH SELECTION application. This will also assist with future removal.

The chosen finish selected for walls and ceilings plays a Thin wall papers may still highlight imperfections in the
very important role in determining the effects of glancing wall surface. Textured or heavy patterned finishes tend
light. to hide imperfections.

A Level 4 finish presents the painter with a surface


comprised of two different materials, namely the INSPECTION OF PLASTERBOARD
plasterboard paper surface and the jointing compound, The Guide to Standards and Tolerances (Victorian
which have different textures and porosity. Building Authority 2015) outlines the following standard
In order to achieve a consistent finish across these for inspection of vertical and horizontal surfaces.
materials it is vital that a plasterboard primer sealer is “Generally, variations in the surface colour, texture and
applied. finish of walls, ceilings, floors and roofs, and variations in
AS/NZS 2311, ’Guide to the painting of buildings’, glass and similar transparent materials are to be viewed
requires that a sealer plus two coats of water based where possible from a normal viewing position. A normal
paint must be applied as a minimum. Such a system viewing position is looking at a distance of 1.5 m or
will provide a surface with minimal difference in texture greater (600 mm for appliances and fixtures) with the
and porosity. surface or material being illuminated by ‘non-critical light’.
‘Non-critical light’ means the light that strikes the surface
Roller application for all coats is strongly recommended is diffused and is not glancing or parallel to that surface.
as it imparts a light texture to the surface and minimises
visible differences. If spray application is used, each paint Slight variations in the colour and finish of materials do
coat should be back rolled while still wet, to create a lightly not always constitute a defect”.
textured finish, and allowed to dry completely before FIG B7: INSPECTION OF PLASTERBOARD
applying the next coat. Paint applied with a longer pile CEILING

roller tends to mask imperfections better than those applied


with a short pile roller. 150
0m
m

A similar paint system is recommended for a level 5 finish


to ensure the best possible result. 1500mm

Paint Finishes
WALL

The choice of gloss level can also have a significant


impact on the perceived quality of the surface in glancing
light conditions.
A matt paint finish provides the highest level of light
diffusion and helps to disguise any surface irregularities. It
is recommended that a matt finish be used in areas where
a higher gloss is not required for functional reasons, such
as ceilings. Textured or heavy patterned finishes tend to
hide imperfections.
Higher gloss levels, such as satin, semi gloss and gloss,
can accentuate any minor variations in the surface and are
recommended only for use over a level 5 finish.

B30 GYPROCK® THE RED BOOK™ 1


STEEL FRAMED
WALL SYSTEMS
C
SECTION CONTENTS
Introduction C2
Design Considerations C2
System Selection Tables

Single Stud C8

Double Stud C31

Rondo Quiet Stud C18

Party Wall/StrataWall C40

Resilient Mount C23

Cinema Wall C45

Staggered Stud C25

Column/Beam Encasement C46

GYPROCK® THE RED BOOK™ 1 C1


INTRODUCTION CSR Thermal Calculator: https://apps.csr.com.au/
thermalcalculator

This section provides important design


information and detailed selection and STRUCTURAL DESIGN
specification tables necessary for the correct All walls must be designed for the applied loads.
use of CSR steel frame wall systems. Guidance is given for the selection of Rondo studs for
non-loadbearing internal walls only. For more information,
CSR Gyprock and Cemintel steel framed wall systems refer to the appropriate design standards or handbooks,
use zinc coated steel components with one or more or contact Rondo Building Services Pty Ltd for design
layers of Gyprock plasterboard and/or Cemintel fibre information.
cement linings fixed to one or both sides. A wide range
of systems is available for both fire rated and non-fire Loadbearing walls, and walls subject to wind or seismic
rated applications in non-loadbearing and loadbearing loads, shall be appropriately designed to meet the relevant
situations. Australian Standards or construction manuals.

These wall systems are most often used in internal Walls lined with Gyprock fire grade plasterboard meet
non-loadbearing applications, including commercial, the requirements of NCC2022 Clauses S6C6 [NCC2019:
industrial, institutional, residential and high-rise residential Spec C1.8: 3.4].
construction. For external wall systems, refer to Section
F, External Wall Systems in this guide. Seismic Loads
This guide should be read in conjunction with The Seismic actions must be considered for building elements
Red Book Book 2 Residential Installation Guide, in accordance with the NCC. The loads and effects of
Book 3 Commercial & Multi-Residential Installation earthquakes may be determined in accordance with AS
G u i d e , G y p ro c k S h a f t Wa l l G u i d e , P a r t y Wa l l 1170.4 ‘Earthquake Actions in Australia’. The Standard
Guide, Cinema Wall systems Guide and Cemintel has design procedures for houses (Class 1), and to
Wallboard installation Guide available for download buildings (Classes 2 to 9) with importance levels 2, 3 or 4
from www.gyprock.com.au and https://www.cemintel. as defined in the NCC.
com.au/

Non-Loadbearing Walls
DESIGN Internal wall studs are friction fitted into tracks with no
clearance at the bottom and an allowance for vertical
CONSIDERATIONS expansion at the top. Where vertical building movement
is expected, a suitable gap must be specified. In this case
deflection head tracks must be used.
DESIGNER RESPONSIBILITY
Staggered stud walls using Rondo C studs must use
It remains the responsibility of the customer (in conjunction an appropriate head and base to restrain the stud from
with their designer or engineer, when applicable) to ensure twisting. Insulation may need to be cut to fit between
that CSR’s products/systems are suitable for their chosen studs (50mm max. thickness glasswool or 70mm max.
application for any given project. CSR recommends thickness polyester batts).
that a comprehensive assessment of the performance
requirements be undertaken prior to selection, including A comprehensive set of height tables for Rondo steel
in respect of project-specific matters such as, but frame stud walls is available in Book 3 Commercial &
not limited structural adequacy, seismic, acoustic, fire Multi-Residential Installation Guide. The tables include
resistance/combustibility, thermal, condensation and allowances for interior wind pressures, for other linings,
weatherproofing requirements. for the addition of tile finishes, and for a greater range of
stud sizes and spacings.
CSR offers online digital tools for the most updated
information, including but not limited to update of
products/components, inclusion of new and modified Loadbearing Walls
systems, to meet the requirements of the National The building designer must ensure loadbearing walls have
Construction Code of Australia (NCC) and any relevant been designed:
Australian Standards.
• To resist all applied loads.
For the most up-to-date product & system performance
information, visit: • To be in accordance with AS/NZS 4600.

CSR System Selector: https://apps.csr.com.au/ • Assuming no contribution to axial strength is required


systemselector/search-option of the wall linings.

C2 GYPROCK® THE RED BOOK™ 1


Wind Loads Load-bearing steel elements such as columns that are
contained within the wall. Have an FRL equivalent to the
All linings and framing are to be designed for the
structural adequacy component of the wall.
appropriate wind loads. Contact CSR for loads higher
than stated in this manual.
Framing, Lining & Jointing
Tall residential buildings often have exterior operable doors
and windows, resulting in internal walls being subject to Steel framed walls required to have an FRL must comply
wind pressure. In these cases, walls must be designed with the following:
for the appropriate loads. • Framing must be made from steel of up to 2.4mm BMT.
Refer to framing selection information in Wind Loads in • Wall plates must be fixed to the fire rated support
Section B and TABLE B12 and TABLE B13 for maximum structure with steel fasteners such as expansion
framing centres. anchors and power driven fasteners. Fastener types
may also be limited by seismic requirements. For fire
CONTROL JOINTS rated wall, use anchor compliant to AS5216 such as
Control joints must be installed to allow for structural Rondo Cert-R-Fix.
movement. Allowance for movement must be made • In wet areas, Gyprock Fyrchek MR or other Gyprock
through the frame, lining and any tiles. moisture grade, fire resistant plasterboard must be
Vertical control joints in stud walls are to be constructed used in lieu of Gyprock Fyrchek.
using two studs with a 15-20mm gap between. • As a minimum, systems require jointing and finishing of
Door frames extending from floor to ceiling constitute the outer (plasterboard or fibre cement) layer. Gyprock
control joints. For doors less than ceiling height, a control paper tape and a single coat finish may be used.
joint extending from one corner of the frame may be used.
Control joints must be installed at all construction joints in Caulking
the building and at the following locations: To attain the specified FRL, all perimeter gaps must be filled
• Non-tiled internal walls with plasterboard outer layer – to the specified depth with appropriate caulking material
at 12m maximum centres. such as Gyprock Fire Mastic or CSR FireSeal. Penetrations
must be installed in accordance to a proprietary tested
• Non-tiled internal walls with fibre cement outer layer – system.
at 7.2m maximum centres.
Vermiculite plaster has no capacity to accommodate
• Tiled internal walls – at 4.8m maximum centres. building movement and may not be suitable for use as a
• At junctions with other building elements. general purpose fire rated caulking.

• At changes of lining material.


• At changes of structural support systems.
• At each storey or rise of studs.

FIRE RESISTANCE
The steel frame wall systems in this manual are suitable
for the stated FRL when designed in accordance with the
structural considerations above. Wall system fire ratings
apply in both directions unless noted otherwise.
CSR fire rated steel stud wall systems have been
designed with fire protection that limits the temperature
of the steel framing to a maximum of 450°C at the FRL
stated. Therefore, the structural design of the framing need
only provide for normal temperature conditions, and no
additional consideration of fire rating is required.
To protect structural steel beams and columns that are
entirely within the wall, the FRL of the wall system must
be at least equivalent to that required by the structural
member. For example, a wall system with FRL 90/90/90,
provides FRL 90/–/– for a steel column or beam within
the wall.

GYPROCK® THE RED BOOK™ 1 C3


ACCEPTABLE VARIATIONS TO STEEL BEAM & COLUMN
FIRE SYSTEMS ENCASEMENT
The Fire Resistance Level (FRL) of the systems detailed in Additional fire protection systems are available using
this section will not be detrimentally affected by: Gyprock Fyrchek or Glasroc F plasterboard linings. It
is recommended for multi-residential and commercial
• Increasing the thickness of the wall.
construction projects where a fire rated encasement
• Increasing the cross-sectional dimensions of the system is required for structural steel beams and columns
framing elements. to provide fire protection of up to 120/–/–. TABLE C2
• Decreasing the stud spacing. and TABLE C3 provides the maximum section factor for
• Decreasing the fixing centres of wall sheet materials. given limiting steel temperatures when using Glasroc F to
• The inclusion of cavity insulation materials such as protect structural steel members used for Columns and
glasswool , rockwool and polyester provided any non- Beams respectively. TABLE C4 provides the maximum
combustible requirements have been considered for section factor for given limiting steel temperatures when
the certain wall applications. using Fyrchek and other CSR linings to protect structural
steel members used for Columns and Beams. These
• The use of Fyrchek MR, Impactchek or EC08 range
values are required to calculate the FRL in accordance
plasterboard in lieu of Fyrchek plasterboard of the
with AS4100:2020 clause 12.5.
same thickness.
• The use of Shaft Liner Panel MP in lieu of Shaft Liner Where the lining method creates void spaces to the
Panel. columns, the spaces may be packed solid to a height
of 1.2m, to prevent indenting. Surface protection from
• Additional layers of plasterboard or Cemintel fibre
vehicle, materials or equipment damage with steel
cement.
cladding or other suitable material may also be required
• Walls curved in plan with a radius of curvature no less as per NCC2022 Clause C2D9 [NCC2019:C1.8].
than 3m.
It remains the responsibility of the project engineer and
• The attachment of light weight fixtures through to the
certifier to ensure that the CSR system is is suitable for the
framing with screws up to 10 gauge. Walls supporting
chosen application and steel section type and size for any
loads from fixtures must be considered structurally.
given project. Please note that the encasement systems
• The addition of timber sheet material fixed directly to in Redbook are only suitable for internal applications.
the studs may be used provided any non-combustible
requirements have been considered for the certain wall Refer to Redbook 3 Commercial & Multi-Residential
applications. Installation Guide and Glasroc F encasement Manual for
installation instructions on Fyrchek and Glasroc F linings
COMBUSTIBILITY respectively.

Polyester insulation may NOT be selected where the


system has non-combustible construction requirements.
In accordance with NCC2022 Clause C2D10 [NCC2019:
C1.9], plasterboard and fibre cement sheet may be used
wherever a non-combustible material is required by the
Code.

C4 GYPROCK® THE RED BOOK™ 1


TABLE C1: Gyprock Steel Beam/Column Protection - FRL Calculation Summary
Section Factor -
13mm or 16mm
Configuration Beam / Column Designation Commonly Used 30mm Glasroc F
Fyrchek
Steel Geometry (m-1)
4 sided protection Hollow section CHS 50-500 TABLE C2 or TABLE C3
Hollow section RHS/SHS 50-500 TABLE C2 or TABLE C3
4 or 3 sided
I-section UC/UB/WB/WC 50-260 TABLE C2 or TABLE C3
protection
C-section PFC 80-300 TABLE C4 N/A
Hollow section RHS/SHS 40-320 N/A
2 sided protection I-section UC/UB/WB/WC 30-170 N/A
C-section PFC 30-190 N/A

TABLE C2: Columns for Glasroc F TABLE C3: Beams for Glasroc F
Maximum Selection Factor Hp/A m-1 Maximum Selection Factor Hp/A m-1
750 260 260 260 750 260 260 163 62
700 260 260 260 700 260 260 141 58

limiting Temperature ºc
limiting Temperature ºc

650 260 260 260 650 260 260 123 54


620 260 260 215 620 260 260 112 53
600 260 260 191 600 260 260 110 52
550 260 260 164 550 260 260 110 52
500 260 260 134 500 260 260 82 N/A
450 260 260 117 450 260 156 58 N/A
400 260 242 91 400 260 127 N/A N/A
350 260 158 70 350 260 90 N/A N/A
60 90 120 30 60 90 120
Structural Adequacy min. Structural Adequacy min.

TABLE C4: Columns and Beams for Fyrchek


Maximum Selection Factor A/V or Hp/A m-1
750 240 260 260 240 260
700 240 260 260 240 260
650 240 260 260 240 260
limiting Temperature ºc

620 240 260 260 240 260


600 240 260 260 240 260
550 240 260 260 240 260
500 234 260 260 N/A 260
450 201 260 260 N/A 260
400 168 260 260 N/A 260
<300 N/A N/A N/A N/A N/A
30/–/– 60/–/– 90/–/– 120/–/– 120/–/–
1 x 13mm 2 x 13mm 2 x 16mm 3 x 13mm 3 x 16mm or 2
x 16mm + 1 x
13mm
Structural Adequacy min.

GYPROCK® THE RED BOOK™ 1 C5


ACOUSTIC PERFORMANCE PLASTERBOARD & WALLBOARD
The performance of the as-built system may be affected FIXING
by sound flanking, the effectiveness of workmanship and Interior walls may be built to achieve a particular Level
caulking, the presence and treatment of penetrations, and of Finish as defined in AS/NZS 2589. The Level of Finish
the inclusion of structural elements and bridging items. specified can have requirements for frame alignment,
Refer to appropriate information on addressing these jointing and back blocking methods, and sheet orientation.
issues detailed in Section B, Design Considerations and Gyprock plasterboard and Cemintel Wallboard may be
Section J, Flanking Paths in this guide. installed vertically or horizontally, although for some Levels
General Notes. of Finish horizontal sheeting must be used.
• The acoustic performance of systems may be Walls lined with Gyprock plasterboard or Cemintel
adversely affected by the use of studs with higher BMT Wallboard may be finished with tiles. Sheets used as
or closer spacings than those specified, or by the use a substrate for tiles must be fastened with screws only.
of additional linings fixed with battens. Adhesive/fastener fixing is not acceptable.
• In non-fire rated systems, to attain the stated acoustic For detailed jointing and finishing information, refer to The
performance, use Gyprock Wet Area Acrylic Sealant, Red Book Installation Guides and the Cemintel Wet Area
Gyprock Fire Mastic or CSR FireSeal. Linings Manual.
The acoustic performance of CSR wall systems is not
adversely affected by: CURVED WALLS
• The substitution of Gyprock Standard plasterboard by Gyprock Flexible Plasterboard has a thickness or
13mm Aquachek. 6.5mm, and has been specifically designed for curved
wall applications. Installed in two layers, it is particularly
• Changing the order of lining sheets that are fixed direct
effective for small radius situations (less than 900mm)
to framing.
which cannot be accomplished with other Gyprock
• The use of Fyrchek MR, Impactchek, EC08 Extreme/ plasterboards.
Complete plasterboard in lieu of Fyrchek plasterboard
Fire rated walls MUST NOT be curved to a radius of less
of the same thickness.
than 3000mm.
For additional information on curved walls, refer to The
INSTALLATION Red Book 2 Residential Installation Guide or Book 3
Commercial & Multi-Residential Installation Guide
FRAMING
CSR recommends steel framing elements manufactured STEEL COMPONENT SELECTION
by Rondo Building Services Pty Ltd. Other steel framing CSR Gyprock recommends steel components
elements of equivalent performance may be used, manufactured by Rondo Building Services Pty Ltd.
however, it is the responsibility of the manufacturer of
Additional information on steel building components can
the component to substantiate equivalent performance.
be obtained from Rondo, telephone 1300‑367‑663.
For detailed information on wall junctions, intersections,
Other steel components of equivalent performance
frame attachments and penetrations, refer to the Red
may be used, however it is the responsibility of the
Book Installation Guides.
manufacturer of the steel component to substantiate
Gyprock Shaft Wall, Party Wall and Cinema Wall equivalent performance to the recommended component.
systems have additional installation details. Refer to the
relevant installation guide, available for download from
www.gyprock.com.au.

C6 GYPROCK® THE RED BOOK™ 1


GYPROCK PARTY WALL SYSTEMS FIG C1: GYPROCK PARTY WALL HIGHT LIMITATIONS

Gyprock Party Wall comprises a double frame wall with a


25mm Shaft Liner central fire barrier between the frames.
The basis of the fire performance is the central fire barrier
that provides the primary fire resistance, with the frame
Floor
lining (or cavity insulations) on each side contributing to Clip to J-track
ceiling
zone
some extent. This allows the wall linings to be installed 600mm max.

as for normal decorative linings, and to incorporate


penetrations. Floor
ceiling
The basis of the acoustic performance is the double zone
cavity system that provides effective sound transmission
performance, as well as impact isolation. Insulation in
both cavities is used to deliver a range of performance
levels, including allowance for certain penetrations and
services that may occur. ‘H’

TABLE C5 and TABLE C6 provides the overall wall height


and lateral support (clip spacing) limitations for stud
frames lined with plasterboard or fibre cement linings.
‘H’
The targeted FRL in the system table has considered the
stated overall wall height and lateral support (clip spacing)
limitations determined in accordance with AS1530.4.

TABLE C5: Party Wall lateral support (clip spacing) Floor


locations for plasterboard linings on both sides Clip to J-track ceiling
600mm max. zone
Overall Wall Height ‘H’
Up to 14m Max. 2.6m
Up to 12m Max. 2.8m Floor
ceiling
Up to 10.8m Max. 3.0m zone

Up to 9m Max. 3.4m

TABLE C6: Party Wall lateral support (clip spacing)


locations for fibre cement linings on one side or both sides
Overall Wall Height ‘H’
‘H’
Up to 7m Max. 2.6m
Up to 6m Max. 2.8m
Up to 5m Max. 3.0m
‘H’

GYPROCK® THE RED BOOK™ 1 C7


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1000 (a) Nil 32/25 34/27 35/28 36/29 38/31
(c) 75 Acoustigard 11kg – 44/35 44/35 45/36 46/37
BOTH SIDES (f) 50 Acoustigard 14kg 41/32 43/34 44/35 45/36 46/37
–/–/– • 1 x 6mm CeminSeal
Wallboard. (g) 70 Soundscreen 2.0 – – 45/35 46/36 47/37
(h) 50 MAB Polyester 11kg 38/30 40/32 41/33 42/34 43/35
Wall Thickness mm 63 76 88 104 162
CSR 1002 (a) Nil 37/30 38/31 39/32 40/33 42/36
(c) 75 Acoustigard 11kg – 48/39 48/39 49/40 50/42
BOTH SIDES (f) 50 Acoustigard 14kg 46/37 47/38 48/39 49/40 50/42
–/–/– • 1 x 9mm CeminSeal
Wallboard. (g) 70 Soundscreen 2.0 – – 49/39 50/40 51/42
(h) 50 MAB Polyester 11kg 43/35 44/36 45/37 46/38 47/40
Wall Thickness mm 69 82 94 110 168
CSR 1005 (a) Nil 31/23 32/25 34/27 35/28 37/30
SIDE ONE
• 1 x 6mm CeminSeal (c) 75 Acoustigard 11kg – 42/33 43/34 44/35 45/36
Wallboard. (f) 50 Acoustigard 14kg 40/30 41/32 43/34 44/35 45/36
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 44/34 45/35 46/36
• 1 x 10mm Gyprock (h) 50 MAB Polyester 11kg 37/28 38/30 40/32 41/33 42/34
Aquachek Plasterboard.
Wall Thickness mm 67 80 92 108 166
CSR 1008 (a) Nil 28/20 29/21 30/22 30/23 33/26
(c) 75 Acoustigard 11kg – 39/29 39/29 39/30 41/32
BOTH SIDES (f) 50 Acoustigard 14kg 37/27 38/28 39/29 39/30 41/32
–/–/– • 1 x 10mm Gyprock Plus
Plasterboard. (g) 70 Soundscreen 2.0 – – 40/29 40/30 42/32
(h) 75 MAB Polyester 14kg – 39/29 39/29 39/30 41/32
Wall Thickness mm 71 84 96 112 170
CSR 1009 (a) Nil 29/21 30/22 31/23 32/25 35/28
SIDE ONE
• 1 x 10mm Gyprock Plus (c) 75 Acoustigard 11kg – 40/30 40/30 41/32 43/34
Plasterboard. (f) 50 Acoustigard 14kg 38/28 39/29 40/30 41/32 43/34
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 41/30 42/32 44/34
• 1 x 10mm Gyprock (h) 75 MAB Polyester 14kg – 40/30 40/30 41/32 43/34
Aquachek Plasterboard.
Wall Thickness mm 71 84 96 112 170
CSR 1011 (a) Nil 30/22 31/24 32/25 34/27 36/29
(c) 75 Acoustigard 11kg – 41/32 41/32 43/34 44/35
BOTH SIDES (f) 50 Acoustigard 14kg 39/29 40/31 41/32 43/34 44/35
–/–/– • 1 x 10mm Gyprock
Aquachek Plasterboard. (g) 70 Soundscreen 2.0 – – 42/32 44/34 45/35
(h) 75 MAB Polyester 14kg – 41/32 41/32 43/34 44/35
Wall Thickness mm 71 84 96 112 170

C8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10138 (a) Nil 32/24 33/26 34/27 35/28 37/30
(b) 75 Acoustigard 11kg – 43/34 43/34 44/35 45/36
BOTH SIDES (c) 50 MAB Polyester 11kg 38/29 39/31 40/32 41/33 42/34
–/–/– • 1 x 10mm Gyprock HD
Plasterboard. (d) 50 Acoustigard 14kg 41/31 42/33 43/34 44/35 45/36
(e) 70 Soundscreen 2.0 – – 44/34 45/35 46/36
Wall Thickness mm 71 84 96 112 170
CSR 10139 (a) Nil 41/34 43/36 43/36 45/39 46/40
(b) 75 Acoustigard 11kg – 51/42 50/41 52/44 52/44
BOTH SIDES (c) 50 MAB Polyester 11kg 46/38 48/40 49/41 50/43 51/44
–/–/– • 2 x 10mm Gyprock HD
Plasterboard. (d) 50 Acoustigard 14kg 48/39 50/41 50/41 52/44 52/44
(e) 70 Soundscreen 2.0 – – 51/41 53/44 53/44
Wall Thickness mm 91 104 116 132 190
CSR 10140 (a) Nil 42/35 43/36 44/37 46/40 47/41
SIDE ONE
• 2 x 13mm Gyprock (b) 75 Acoustigard 11kg – 51/42 51/42 53/45 53/45
Aquachek Plasterboard. (c) 50 MAB Polyester 11kg 46/38 47/39 48/40 50/43 50/43
–/–/–
SIDE TWO (d) 50 Acoustigard 14kg 49/40 50/41 51/42 53/45 53/45
• 2 x 10mm Gyprock HD (e) 70 Soundscreen 2.0 – – 52/42 54/45 54/45
Plasterboard.
Wall Thickness mm 97 110 122 138 196
CSR 1025 (a) Nil 32/24 33/26 35/28 35/28 38/31
SIDE ONE
• 1 x 6mm CeminSeal (c) 75 Acoustigard 11kg – 43/34 44/35 44/35 46/37
Wallboard. (f) 50 Acoustigard 14kg 41/31 42/33 44/35 44/35 46/37
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 45/35 45/35 47/37
• 1 x 13mm Gyprock (h) 75 MAB Polyester 14kg – 43/34 44/35 44/35 46/37
Standard Plasterboard.
Wall Thickness mm 70 83 95 111 169
CSR 1027 (a) Nil 34/26 36/29 37/30 38/31 41/34
SIDE ONE
• 1 x 9mm CeminSeal (c) 75 Acoustigard 11kg – 46/37 46/37 47/38 49/40
Wallboard. (f) 50 Acoustigard 14kg 43/33 45/36 46/37 47/38 49/40
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 47/37 48/38 50/40
• 1 x 13mm Gyprock (h) 75 MAB Polyester 14kg – 46/37 46/37 47/38 49/40
Standard Plasterboard.
Wall Thickness mm 73 86 98 114 172
CSR 1030 (a) Nil 32/24 33/26 34/27 35/28 37/30
(c) 75 Acoustigard 11kg – 43/34 43/34 44/35 45/36
BOTH SIDES (f) 50 Acoustigard 14kg 41/31 42/33 43/34 44/35 45/36
–/–/– • 1 x 13mm Gyprock
Standard Plasterboard. (g) 70 Soundscreen 2.0 – – 44/34 45/35 46/36
(h) 50 MAB Polyester 11kg 38/29 39/31 40/32 41/33 42/34
Wall Thickness mm 77 90 102 118 176

GYPROCK® THE RED BOOK™ 1 C9


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1032 (a) Nil 32/24 34/27 35/28 36/29 38/31
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 44/35 44/35 45/36 46/37
Aquachek Plasterboard. (f) 50 Acoustigard 14kg 41/31 43/34 44/35 45/36 46/37
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 45/35 46/36 47/37
• 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 38/29 40/32 41/33 42/34 43/35
Standard Plasterboard.
Wall Thickness mm 77 90 102 118 176
CSR 1033 (a) Nil 33/25 35/28 35/28 36/29 38/31
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 45/36 44/35 45/36 46/37
Impactchek Plasterboard. (f) 50 Acoustigard 14kg 42/32 44/35 44/35 45/36 46/37
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 45/35 46/36 47/37
• 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 39/30 41/33 41/33 42/34 43/35
Standard Plasterboard.
Wall Thickness mm 77 90 102 118 176
CSR 1035 (a) Nil 33/26 35/28 36/29 37/30 39/33
(c) 75 Acoustigard 11kg – 45/36 45/36 46/37 47/39
BOTH SIDES (f) 50 Acoustigard 14kg 42/33 44/35 45/36 46/37 47/39
–/–/– • 1 x 13mm Gyprock
Aquachek Plasterboard. (g) 70 Soundscreen 2.0 – – 46/36 47/37 48/39
(h) 50 MAB Polyester 11kg 39/31 41/33 42/34 43/35 44/37
Wall Thickness mm 77 90 102 118 176
CSR 1037 (a) Nil 35/28 36/29 38/31 39/32 41/35
(c) 75 Acoustigard 11kg – 46/37 47/38 48/39 49/41
BOTH SIDES (f) 50 Acoustigard 14kg 44/35 45/36 47/38 48/39 49/41
–/–/– • 1 x 13mm Gyprock
Soundchek Plasterboard. (g) 70 Soundscreen 2.0 – – 48/38 49/39 50/41
(h) 75 MAB Polyester 14kg 42/33 43/34 45/36 46/37 47/39
Wall Thickness mm 77 90 102 118 176
CSR 1040 (a) Nil 37/29 38/31 39/32 41/34 43/36
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 47/38 47/38 49/40 50/41
Standard Plasterboard. (f) 50 Acoustigard 14kg 45/35 46/37 47/38 49/40 50/41
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 48/38 50/40 51/41
• 2 x 13mm Gyprock (h) 75 MAB Polyester 14kg 43/33 44/35 45/36 47/38 48/39
Standard Plasterboard.
Wall Thickness mm 90 103 115 131 189
CSR 1042 (a) Nil 38/31 39/32 40/33 41/34 43/37
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 48/39 48/39 49/40 50/42
Aquachek Plasterboard. (f) 50 Acoustigard 14kg 46/37 47/38 48/39 49/40 50/42
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 49/39 50/40 51/42
• 2 x 13mm Gyprock (h) 75 MAB Polyester 14kg 44/35 45/36 46/37 47/38 48/40
Standard Plasterboard.
Wall Thickness mm 90 103 115 131 189

C10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1044 (a) Nil 38/31 39/32 41/34 42/35 44/38
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 48/39 49/40 50/41 51/43
Aquachek Plasterboard. (f) 50 Acoustigard 14kg 46/37 47/38 49/40 50/41 51/43
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 50/40 51/41 52/43
• 2 x 13mm Gyprock (h) 75 MAB Polyester 14kg 44/35 45/36 47/38 48/39 49/41
Aquachek Plasterboard.
Wall Thickness mm 90 103 115 131 189
CSR 1045 (a) Nil 40/33 42/35 43/36 44/37 46/40
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 51/42 51/42 52/43 54/46
Soundchek Plasterboard. (f) 50 Acoustigard 14kg 48/39 50/41 51/42 52/43 53/45
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 – – 52/42 53/43 54/45
• 2 x 13mm Gyprock (h) 50 MAB Polyester 11kg 45/37 47/39 48/40 49/41 50/43
Soundchek Plasterboard.
Wall Thickness mm 90 103 115 131 189
CSR 1048 (a) Nil 43/36 44/37 46/40 47/41 48/42
(c) 75 Acoustigard 11kg – 52/43 53/45 54/46 54/46
BOTH SIDES (f) 50 Acoustigard 14kg 50/41 51/42 53/45 54/46 54/46
–/–/– • 2 x 13mm Gyprock
Aquachek Plasterboard. (g) 70 Soundscreen 2.0 – – 54/45 55/46 55/46
(h) 50 MAB Polyester 11kg 47/39 48/40 50/43 51/44 51/44
Wall Thickness mm 103 116 128 144 202
CSR 3006 (a) Nil 34/27 36/29 36/29 38/31 40/33
SIDE ONE
• 1 x 6mm CeminSeal (c) 75 Acoustigard 11kg – 46/37 45/36 47/38 48/39
Wallboard. (e) 88 Soundscreen 2.5 – – 48/39 49/40 51/42
–/–/–
SIDE TWO (f) 50 Acoustigard 14kg 43/34 45/36 45/36 47/38 48/39
• 1 x 13mm Gyprock EC08 (h) 50 MAB Polyester 11kg 40/32 42/34 42/34 44/36 45/37
Complete.
Wall Thickness mm 70 83 95 111 169
CSR 10000 (a) Nil 34/27 36/29 36/29 38/31 40/33
SIDE ONE
• 1 x 6mm CeminSeal (b) 75 Acoustigard 11kg – 46/37 45/36 47/38 48/39
Wallboard. (d) 88 Soundscreen 2.5 – – 48/39 49/40 51/42
–/–/–
SIDE TWO (e) 50 Acoustigard 14kg 43/34 45/36 45/36 47/38 48/39
• 1 x 13mm Gyprock EC08 (f) 50 MAB Polyester 11kg 40/32 42/34 42/34 44/36 45/37
Extreme.
Wall Thickness mm 70 83 95 111 169
CSR 3011 (a) Nil 33/25 35/28 36/29 38/31 40/33
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 45/36 45/36 47/38 48/39
Standard Plasterboard. (e) 88 Soundscreen 2.5 – – 48/39 49/40 51/42
–/–/–
SIDE TWO (f) 50 Acoustigard 14kg 42/32 44/35 45/36 47/38 48/39
• 1 x 13mm Gyprock EC08 (h) 50 MAB Polyester 11kg 39/30 41/33 42/34 44/36 44/36
Complete.
Wall Thickness mm 77 90 102 118 176

GYPROCK® THE RED BOOK™ 1 C11


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10001 (a) Nil 33/25 35/28 36/29 38/31 40/33
SIDE ONE
• 1 x 13mm Gyprock (b) 75 Acoustigard 11kg – 45/36 45/36 47/38 48/39
Standard Plasterboard. (d) 88 Soundscreen 2.5 – – 48/39 49/40 51/42
–/–/–
SIDE TWO (e) 50 Acoustigard 14kg 42/32 44/35 45/36 47/38 48/39
• 1 x 13mm Gyprock EC08 (f) 50 MAB Polyester 11kg 39/30 41/33 42/34 44/36 44/36
Extreme.
Wall Thickness mm 77 90 102 118 176
CSR 1050 (a) Nil 34/27 36/29 36/29 38/31 40/34

– /60/60 (c) 75 Acoustigard 11kg – 46/37 45/36 47/38 48/40


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 43/34 45/36 45/36 47/38 48/40
(from both sides) • 1 x 13mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 – – 46/36 48/38 49/40
FC 12946 (h) 75 MAB Polyester 14kg – 46/37 45/36 47/38 48/40
Wall Thickness mm 77 90 102 118 176
CSR 1051 (a) Nil 34/27 36/29 36/29 38/31 40/34
SIDE ONE
– /60/60 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 46/37 45/36 47/38 48/40
30/30/30 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 43/34 45/36 45/36 47/38 48/40
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 46/36 48/38 49/40
FC 12946 • 1 x 13mm Gyprock (h) 75 MAB Polyester 14kg – 46/37 45/36 47/38 48/40
Fyrchek Plasterboard.
Wall Thickness mm 77 90 102 118 176
CSR 1052 (a) Nil 34/27 36/29 36/29 38/31 40/34

– /60/60 (c) 75 Acoustigard 11kg – 46/37 45/36 47/38 48/40


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 43/34 45/36 45/36 47/38 48/40
(from both sides) • 1 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 – – 46/36 48/38 49/40
FC 12946 (h) 75 MAB Polyester 14kg – 46/37 45/36 47/38 48/40
Wall Thickness mm 77 90 102 118 176
CSR 1055 (a) Nil 33/25 35/28 35/28 37/30 39/32
SIDE ONE
– /60/60 (c) 75 Acoustigard 11kg – 45/36 44/35 46/37 47/38
• 1 x 16mm Gyprock
30/30/30 Fyrchek Plasterboard.
(from Fyrchek lined
(f) 50 Acoustigard 14kg 42/32 44/35 44/35 46/37 47/38
side only) SIDE TWO (g) 70 Soundscreen 2.0 – – 45/35 47/37 48/38
• 1 x 13mm Gyprock (h) 75 MAB Polyester 14kg 39/30 41/33 41/33 43/35 44/36
FC 12946
Standard Plasterboard.
Wall Thickness mm 80 93 105 121 179
CSR 3017 (a) Nil 36/29 37/30 39/32 40/33 42/36

– /60/60 (c) 75 Acoustigard 11kg – 47/38 48/39 49/40 50/42


30/30/30 BOTH SIDES (e) 88 Soundscreen 2.5 – – 51/42 51/42 53/45
(from both sides) • 1 x 13mm Gyprock EC08
Complete. (f) 50 Acoustigard 14kg 45/36 46/37 48/39 49/40 50/42
FC 12946 (h) 50 MAB Polyester 11kg 42/34 43/35 45/37 46/38 47/40
Wall Thickness mm 77 90 102 118 176

C12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10002 (a) Nil 36/29 37/30 39/32 40/33 42/36

– /60/60 (b) 75 Acoustigard 11kg – 47/38 48/39 49/40 50/42


30/30/30 BOTH SIDES (d) 88 Soundscreen 2.5 – – 51/42 51/42 53/45
(from both sides) • 1 x 13mm Gyprock EC08
Extreme. (e) 50 Acoustigard 14kg 45/36 46/37 48/39 49/40 50/42
FC 12946 (f) 50 MAB Polyester 11kg 42/34 43/35 45/37 46/38 47/40
Wall Thickness mm 77 90 102 118 176
CSR 3023 SIDE ONE (ANY ORDER) (a) Nil 40/33 42/35 42/35 43/36 45/39
• 1 x 13mm Gyprock EC08
– /60/60 (c) 75 Acoustigard 11kg – 51/42 50/41 51/42 52/44
Complete.
30/30/30 • 1 x 6mm CeminSeal (e) 88 Soundscreen 2.5 – – 53/44 53/44 55/47
(from both sides)
Wallboard. (f) 50 Acoustigard 14kg 48/39 50/41 50/41 51/42 52/44
FC 12946 SIDE TWO (h) 50 MAB Polyester 11kg 45/37 47/39 47/39 48/40 49/42
• 1 x 13mm Gyprock EC08
Complete. Wall Thickness mm 83 96 108 124 182
CSR 10003 SIDE ONE (ANY ORDER) (a) Nil 40/33 42/35 42/35 43/36 45/39
• 1 x 13mm Gyprock EC08
– /60/60 Extreme. (b) 75 Acoustigard 11kg – 51/42 50/41 51/42 52/44
30/30/30 • 1 x 6mm CeminSeal (d) 88 Soundscreen 2.5 – – 53/44 53/44 55/47
(from both sides)
Wallboard. (e) 50 Acoustigard 14kg 48/39 50/41 50/41 51/42 52/44
FC 12946 SIDE TWO (f) 50 MAB Polyester 11kg 45/37 47/39 47/39 48/40 49/42
• 1 x 13mm Gyprock EC08
Extreme. Wall Thickness mm 83 96 108 124 182
CSR 1058 (a) Nil 43/36 44/37 46/40 46/40 48/42

– /90/90 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg – 52/43 53/45 53/45 54/46
• 1 x 6mm CeminSeal
30/30/30 (f) 50 Acoustigard 14kg 50/41 51/42 53/45 53/45 54/46
(from both sides) Wallboard.
• 1 x 13mm Gyprock (g) 70 Soundscreen 2.0 – – 54/45 54/45 55/46
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 47/39 48/40 50/43 50/43 51/44
Wall Thickness mm 89 102 114 130 188
CSR 1060 (a) Nil 39/32 41/34 42/35 43/36 45/39
SIDE ONE
– /90/90 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 50/41 50/41 51/42 52/44
30/30/30 Fyrchek Plasterboard. (f) 50 Acoustigard 14kg 47/38 49/40 50/41 51/42 52/44
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 51/41 52/42 53/44
FC 12946 • 2 x 13mm Gyprock (h) 75 MAB Polyester 14kg – 50/41 50/41 51/42 52/44
Fyrchek Plasterboard.
Wall Thickness mm 90 103 115 131 189
CSR 1061 (a) Nil 39/32 41/34 42/35 43/36 45/39
SIDE ONE
– /90/90 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 50/41 50/41 51/42 52/44
30/30/30 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 47/38 49/40 50/41 51/42 52/44
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 51/41 52/42 53/44
FC 12946 • 2 x 13mm Gyprock (h) 75 MAB Polyester 14kg – 50/41 50/41 51/42 52/44
Fyrchek Plasterboard.
Wall Thickness mm 90 103 115 131 189

GYPROCK® THE RED BOOK™ 1 C13


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1062 (a) Nil 39/32 41/34 42/35 43/36 45/39
SIDE ONE
– /90/90 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg – 50/41 50/41 51/42 52/44
30/30/30 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 47/38 49/40 50/41 51/42 52/44
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 51/41 52/42 53/44
FC 12946 • 2 x 13mm Gyprock (h) 75 MAB Polyester 14kg – 50/41 50/41 51/42 52/44
Fyrchek MR Plasterboard.
Wall Thickness mm 90 103 115 131 189
CSR 3033 (a) Nil 40/33 42/35 43/36 45/38 46/40
SIDE ONE
– /90/90 (c) 75 Acoustigard 11kg – 51/42 51/42 53/44 53/45
• 1 x 13mm Gyprock EC08
30/30/30 Complete.
(from both sides)
(e) 88 Soundscreen 2.5 – – 54/45 55/46 56/48
SIDE TWO (f) 50 Acoustigard 14kg 48/39 50/41 51/42 53/44 53/45
FC 12946 • 2 x 13mm Gyprock EC08
FAS 200002 (g) 50 MAB Polyester 11kg 45/37 47/39 48/40 50/42 50/43
Complete.
Wall Thickness mm 90 103 115 131 189
CSR 10004 (a) Nil 40/33 42/35 43/36 45/38 46/40
SIDE ONE
– /90/90 • 1 x 13mm Gyprock EC08 (c) 75 Acoustigard 11kg – 51/42 51/42 53/44 53/45
30/30/30 Extreme. (e) 88 Soundscreen 2.5 – – 54/45 55/46 56/48
(from both sides)
SIDE TWO (f) 50 Acoustigard 14kg 48/39 50/41 51/42 53/44 53/45
FC 12946 • 2 x 13mm Gyprock EC08 (g) 50 MAB Polyester 11kg 45/37 47/39 48/40 50/42 50/43
Extreme.
Wall Thickness mm 90 103 115 131 189
CSR 1065 (a) Nil 34/27 35/28 37/30 38/31 40/34

– /90/90 (c) 75 Acoustigard 11kg – 45/36 46/37 47/38 48/40


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 43/34 44/35 46/37 47/38 48/40
(from both sides) • 1 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 – – 47/37 48/38 49/40
FC 12946 (h) 50 MAB Polyester 11kg 40/32 41/33 43/35 44/36 45/38
Wall Thickness mm 83 96 108 124 182
CSR 1066 (a) Nil 35/28 36/29 38/31 39/32 41/35
SIDE ONE
– /90/90 • 1 x 16mm Gyprock (c) 75 Acoustigard 11kg – 46/37 47/38 48/39 49/41
60/60/60 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 44/35 45/36 47/38 48/39 49/41
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 48/38 49/39 50/41
FC 12946 • 1 x 16mm Gyprock (h) 50 MAB Polyester 11kg 41/33 42/34 44/36 45/37 46/39
Fyrchek Plasterboard.
Wall Thickness mm 83 96 108 124 182
CSR 1067 (a) Nil 36/29 37/30 39/32 40/33 42/36

– /90/90 (c) 75 Acoustigard 11kg – 47/38 48/39 49/40 50/42


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 45/36 46/37 48/39 49/40 50/42
(from both sides) • 1 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 – – 49/39 50/40 51/42
FC 12946 (h) 50 MAB Polyester 11kg 42/34 43/35 45/37 46/38 47/40
Wall Thickness mm 83 96 108 124 182

C14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 3034 (a) Nil 38/31 39/32 40/33 41/34 44/38

– /90/90 (c) 75 Acoustigard 11kg – 49/40 49/40 50/41 52/44


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 47/38 48/39 49/40 50/41 51/43
(from both sides) • 1 x 16mm Gyprock EC08
Complete. (g) 70 Soundscreen 2.0 – – 50/40 51/41 52/43
FC 12946 (h) 50 MAB Polyester 11kg 44/36 45/37 46/38 47/39 49/42
Wall Thickness mm 83 96 108 124 182
CSR 1070 SIDE ONE (a) Nil 39/32 41/34 41/34 42/35 44/38
• 1 x 16mm Gyprock
(c) 75 Acoustigard 11kg – 50/41 49/40 50/41 51/43
– /90/90 Fyrchek Plasterboard.
60/60/60 SIDE TWO (ANY ORDER)
(f) 50 Acoustigard 14kg 47/38 49/40 49/40 50/41 51/43
(from both sides)
• 1 x 16mm Gyprock (g) 70 Soundscreen 2.0 – – 50/40 51/41 52/43
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 44/36 46/38 46/38 47/39 48/41
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness mm 89 102 114 130 188
CSR 1071 (a) Nil 44/37 45/38 46/40 47/41 48/42
BOTH SIDES
– /90/90 (c) 75 Acoustigard 11kg – 53/44 53/45 54/46 54/46
• 1 x 16mm Gyprock
60/60/60 Fyrchek Plasterboard (f) 50 Acoustigard 14kg 51/42 52/43 53/45 54/46 54/46
(from both sides) (against studs). (g) 70 Soundscreen 2.0 – – 54/45 55/46 55/46
FC 12946 • 1 x 6mm CeminSeal
(h) 50 MAB Polyester 11kg 48/40 49/41 50/43 51/44 51/44
Wallboard.
Wall Thickness mm 95 108 120 136 194
CSR 1072 (a) Nil 44/37 45/38 46/40 47/41 48/42

– /120/120 BOTH SIDES (c) 75 Acoustigard 11kg – 53/44 53/45 54/46 54/46
• 1 x 6mm CeminSeal
60/60/60 (f) 50 Acoustigard 14kg 51/42 52/43 53/45 54/46 54/46
(from both sides) Wallboard (against studs).
• 1 x 16mm Gyprock (g) 70 Soundscreen 2.0 – – 54/45 55/46 55/46
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 48/40 49/41 50/43 51/44 51/44
Wall Thickness mm 95 108 120 136 194
CSR 1075 (a) Nil 45/38 47/41 48/42 49/43 50/44

– /120/120 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg – 55/47 55/47 56/48 56/48
• 1 x 9mm CeminSeal
90/90/90 (f) 50 Acoustigard 14kg 52/43 54/46 55/47 56/48 56/48
(from both sides) Wallboard.
• 1 x 16mm Gyprock (g) 70 Soundscreen 2.0 – – 56/47 57/48 57/48
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 49/41 51/44 52/45 53/46 53/46
Wall Thickness mm 101 114 126 142 200

GYPROCK® THE RED BOOK™ 1 C15


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.
‡ Unique height restrictions apply. Refer to
The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1078 (a) Nil 44/37 45/38 46/40 47/41 48/42

– /120/120 (c) 75 Acoustigard 11kg – 53/44 53/45 54/46 54/46


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 51/42 52/43 53/45 54/46 54/46
(from both sides) • 2 x 13mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 – – 54/45 55/46 55/46
FC 12946 (h) 50 MAB Polyester 11kg 48/40 49/41 50/43 51/44 51/44
Wall Thickness mm 103 116 128 144 202
CSR 1079 (a) Nil 44/37 45/38 46/40 47/41 48/42
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 75 Acoustigard 11kg – 53/44 53/45 54/46 54/46
90/90/90 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 51/42 52/43 53/45 54/46 54/46
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 54/45 55/46 55/46
FC 12946 • 2 x 13mm Gyprock (h) 50 MAB Polyester 11kg 48/40 49/41 50/43 51/44 51/44
Fyrchek Plasterboard.
Wall Thickness mm 103 116 128 144 202
CSR 1080 (a) Nil 44/37 45/38 47/41 47/41 48/42

– /120/120 (c) 75 Acoustigard 11kg – 53/44 54/46 54/46 54/46


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 51/42 52/43 54/46 54/46 54/46
(from both sides) • 2 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 – – 55/46 55/46 55/46
FC 12946 (h) 50 MAB Polyester 11kg 48/40 49/41 51/44 51/44 51/44
Wall Thickness mm 103 116 128 144 202
CSR 3043 (a) Nil 45/38 47/41 48/42 49/43 50/44
SIDE ONE
– /120/120 • 2 x 13mm Gyprock EC08 (c) 75 Acoustigard 11kg – 55/47 55/47 56/48 56/48
90/90/90 Complete. (e) 88 Soundscreen 2.5 – – 58/50 58/50 59/51
(from both sides)
SIDE TWO (f) 50 Acoustigard 14kg 52/43 54/46 55/47 56/48 56/48
FC 12946 • 2 x 13mm Gyprock EC08 (h) 50 MAB Polyester 11kg 49/41 51/44 52/45 53/46 53/46
Complete.
Wall Thickness mm 103 116 128 144 202
CSR 10005 (a) Nil 45/38 47/41 48/42 49/43 50/44
SIDE ONE
– /120/120 • 2 x 13mm Gyprock EC08 (b) 75 Acoustigard 11kg – 55/47 55/47 56/48 56/48
90/90/90 Extreme. (d) 88 Soundscreen 2.5 – – 58/50 58/50 59/51
(from both sides)
SIDE TWO (e) 50 Acoustigard 14kg 52/43 54/46 55/47 56/48 56/48
FC 12946 • 2 x 13mm Gyprock EC08 (f) 50 MAB Polyester 11kg 49/41 51/44 52/45 53/46 53/46
Extreme.
Wall Thickness mm 103 116 128 144 202

C16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.
‡ Unique height restrictions apply. Refer to
The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 51 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1085 (a) Nil 43/36 45/39 46/40 47/41 48/42

– /180/180‡ (c) 75 Acoustigard 11kg – 53/45 53/45 54/46 54/46


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 50/41 52/44 53/45 54/46 54/46
(from both sides) • 2 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 – – 54/45 55/46 55/46
FC 12946 (h) 50 MAB Polyester 11kg 47/39 49/42 50/43 51/44 51/44
Wall Thickness mm 115 128 140 156 214
CSR 1086 (a) Nil 44/37 46/40 47/41 48/42 49/43
SIDE ONE
– /180/180‡ • 2 x 16mm Gyprock (c) 75 Acoustigard 11kg – 54/46 54/46 55/47 55/47
120/120/120 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 51/42 53/45 54/46 55/47 55/47
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – – 55/46 56/47 56/47
FC 12946 • 2 x 16mm Gyprock (h) 50 MAB Polyester 11kg 48/40 50/43 51/44 52/45 52/45
Fyrchek Plasterboard.
Wall Thickness mm 115 128 140 156 214
CSR 1087 (a) Nil 45/38 47/41 48/42 49/43 50/44

– /180/180‡ (c) 75 Acoustigard 11kg – 55/47 55/47 56/48 56/48


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 52/43 54/46 55/47 56/48 56/48
(from both sides) • 2 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 – – 56/47 57/48 57/48
FC 12946 (h) 50 MAB Polyester 11kg 49/41 51/44 52/45 53/46 53/46
Wall Thickness mm 115 128 140 156 214
CSR 3044 (a) Nil 48/42 49/43 49/43 50/44 52/46

– /180/180‡ (c) 75 Acoustigard 11kg – 57/49 56/48 57/49 58/50


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 55/47 56/48 56/48 57/49 57/49
(from both sides) • 2 x 16mm Gyprock EC08
Complete. (g) 70 Soundscreen 2.0 – – 57/48 58/49 58/49
FC 12946 (h) 50 MAB Polyester 11kg 52/45 53/46 53/46 54/47 55/48
Wall Thickness mm 115 128 140 156 214

GYPROCK® THE RED BOOK™ 1 C17


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Rondo Quiet Stud

Lining material as per system table. Cavity insulation as per system table.

Rondo Quiet studs at 600mm maximum Lining material as per system table.
centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 92
FRL SYSTEM STUD BMT mm 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1105 (a) Nil 40/33 39/32
(c) 75 Acoustigard 14kg 49/41 48/40
BOTH SIDES (f) 50 Acoustigard 14kg 48/39 47/38
–/–/– • 1 x 13mm Gyprock Aquachek
Plasterboard. (g) 70 Soundscreen 2.0 50/42 49/41
(i) 90 Acoustigard 14kg 50/42 49/41
Wall Thickness mm 118
CSR 1108 (a) Nil 42/35 41/34
SIDE ONE
• 1 x 13mm Gyprock Soundchek (c) 75 Acoustigard 14kg 51/43 50/42
Plasterboard. (f) 50 Acoustigard 14kg 50/41 49/40
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 52/44 51/43
• 1 x 13mm Gyprock Aquachek (i) 90 Acoustigard 14kg 52/44 51/43
Plasterboard.
Wall Thickness mm 118
CSR 1110 (a) Nil 42/35 41/34
(c) 75 Acoustigard 14kg 51/43 50/42
BOTH SIDES (f) 50 Acoustigard 14kg 50/41 49/40
–/–/– • 1 x 13mm Gyprock Soundchek
Plasterboard. (g) 70 Soundscreen 2.0 52/44 51/43
(i) 90 Acoustigard 14kg 52/44 51/43
Wall Thickness mm 118
CSR 1120 (a) Nil 51/45 50/44
(c) 75 Acoustigard 14kg 58/51 57/50
BOTH SIDES (f) 50 Acoustigard 14kg 57/49 56/48
–/–/– • 2 x 13mm Gyprock Soundchek
Plasterboard. (g) 70 Soundscreen 2.0 59/52 58/51
(i) 90 Acoustigard 14kg 59/52 58/51
Wall Thickness mm 144

C18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Rondo Quiet Stud

Lining material as per system table. Cavity insulation as per system table.

Rondo Quiet studs at 600mm maximum Lining material as per system table.
centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 92
FRL SYSTEM STUD BMT mm 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1125 (a) Nil 41/34 40/33

– /60/60 (c) 75 Acoustigard 14kg 50/42 49/41


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 49/40 48/39
(from both sides) • 1 x 13mm Gyprock Fyrchek
Plasterboard. (g) 70 Soundscreen 2.0 51/43 50/42
FC 12946 (i) 90 Acoustigard 14kg 51/43 50/42
Wall Thickness mm 118
CSR 1126 (a) Nil 41/34 40/33
SIDE ONE
– /60/60 • 1 x 13mm Gyprock Fyrchek MR (c) 75 Acoustigard 14kg 50/42 49/41
30/30/30 Plasterboard. (f) 50 Acoustigard 14kg 49/40 48/39
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 51/43 50/42
FC 12946 • 1 x 13mm Gyprock Fyrchek (i) 90 Acoustigard 14kg 51/43 50/42
Plasterboard.
Wall Thickness mm 118
CSR 1127 (a) Nil 41/34 40/33

– /60/60 (c) 75 Acoustigard 14kg 50/42 49/41


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 49/40 48/39
(from both sides) • 1 x 13mm Gyprock Fyrchek MR
Plasterboard. (g) 70 Soundscreen 2.0 51/43 50/42
FC 12946 (i) 90 Acoustigard 14kg 51/43 50/42
Wall Thickness mm 118
CSR 10037 (a) Nil 41/34 40/33

– /60/60 (c) 75 Acoustigard 14kg 50/42 49/41


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 49/40 48/39
(from both sides) • 1 x 13mm Gyprock Impactchek
Plasterboard. (g) 70 Soundscreen 2.0 51/43 50/42
FC 12946 (i) 90 Acoustigard 14kg 51/42 50/42
Wall Thickness mm 118
CSR 3062 (a) Nil 43/36 42/35

– /60/60 (c) 75 Acoustigard 14kg 51/42 50/41


30/30/30 BOTH SIDES (e) 88 Soundscreen 2.5 54/46 53/45
(from both sides) • 1 x 13mm Gyprock EC08 Complete. (f) 50 Acoustigard 14kg 51/42 50/41
FC 12946 (i) 90 Acoustigard 14kg 53/45 52/44
Wall Thickness mm 118
CSR 10006 (a) Nil 43/36 42/35

– /60/60 (b) 75 Acoustigard 14kg 51/42 50/41


30/30/30 BOTH SIDES (d) 88 Soundscreen 2.5 54/46 53/45
(from both sides) • 1 x 13mm Gyprock EC08 Extreme. (e) 50 Acoustigard 14kg 51/42 50/41
FC 12946 (f) 50 MAB Polyester 11kg 53/45 52/44
Wall Thickness mm 118

GYPROCK® THE RED BOOK™ 1 C19


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Rondo Quiet Stud

Lining material as per system table. Cavity insulation as per system table.

Rondo Quiet studs at 600mm maximum Lining material as per system table.
centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 92
FRL SYSTEM STUD BMT mm 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1128 (a) Nil 46/39 45/38
SIDE ONE
– /90/90 • 2 x 13mm Gyprock Fyrchek (c) 75 Acoustigard 14kg 54/46 53/45
30/30/30 Plasterboard (e) 88 Soundscreen 2.5 56/48 55/47
(from both sides)
SIDE TWO (f) 50 Acoustigard 14kg 53/44 52/43
FC 12946 • 1 x 13mm Gyprock Fyrchek (i) 90 Acoustigard 14kg 55/47 54/46
Plasterboard.
Wall Thickness mm 131
CSR 1129 (a) Nil 46/39 45/38
SIDE ONE
– /90/90 • 2 x 13mm Gyprock Fyrchek (c) 75 Acoustigard 14kg 54/46 53/45
30/30/30 Plasterboard (e) 88 Soundscreen 2.5 56/48 55/47
(from both sides)
SIDE TWO (f) 50 Acoustigard 14kg 53/44 52/43
FC 12946 • 1 x 13mm Gyprock Fyrchek MR (i) 90 Acoustigard 14kg 55/47 54/46
Plasterboard.
Wall Thickness mm 131
CSR 1130 SIDE ONE (ANY ORDER) (a) Nil 50/44 49/43
• 1 x 13mm Gyprock Fyrchek
– /90/90 Plasterboard (c) 75 Acoustigard 14kg 57/50 56/49
30/30/30 • 1 x 13mm Gyprock Standard (f) 50 Acoustigard 14kg 56/48 55/47
(from both sides) Plasterboard. (g) 70 Soundscreen 2.0 58/51 57/50
FC 12946 SIDE TWO (i) 90 Acoustigard 14kg 58/51 57/50
• 2 x 13mm Gyprock Fyrchek
Plasterboard. Wall Thickness mm 144
CSR 3072 (a) Nil 50/44 49/43

– /90/90 (c) 75 Acoustigard 11kg 56/48 55/47


BOTH SIDES (ANY ORDER)
30/30/30 (e) 88 Soundscreen 2.5 59/52 58/51
(from both sides) • 1 x 13mm Gyprock EC08 Complete.
• 1 x 6mm CeminSeal Wallboard. (f) 50 Acoustigard 14kg 56/48 55/47
FC 12946 (i) 90 Acoustigard 14kg 58/51 57/50
Wall Thickness mm 130
CSR 10007 (a) Nil 50/44 49/43

– /90/90 (b) 75 Acoustigard 11kg 56/48 55/47


BOTH SIDES (ANY ORDER)
30/30/30 (d) 88 Soundscreen 2.5 59/52 58/51
(from both sides) • 1 x 13mm Gyprock EC08 Extreme.
• 1 x 6mm CeminSeal Wallboard. (e) 50 Acoustigard 14kg 56/48 55/47
FC 12946 (i) 90 Acoustigard 14kg 58/51 57/50
Wall Thickness mm 130
CSR 10031 (a) Nil 50/44 49/43

– /120/120 (b) 75 Acoustigard 14kg 57/50 56/49


90/90/90 BOTH SIDES (d) 50 Acoustigard 14kg 56/48 55/47
(from both sides) • 2 x 13mm Gyprock Fyrchek
Plasterboard. (e) 70 Soundscreen 2.0 58/51 57/50
FC 12946 (i) 90 Acoustigard 14kg 58/51 57/50
Wall Thickness mm 144

C20 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Rondo Quiet Stud

Lining material as per system table. Cavity insulation as per system table.

Rondo Quiet studs at 600mm maximum Lining material as per system table.
centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 92
FRL SYSTEM STUD BMT mm 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 3082 (a) Nil 52/46 51/45

– /120/120 (c) 75 Acoustigard 11kg 58/50 57/49


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 61/54 60/53
(from both sides) • 2 x 13mm Gyprock EC08 Complete. (f) 50 Acoustigard 14kg 58/50 57/49
FC 12946 (i) 90 Acoustigard 14kg 60/53 59/52
Wall Thickness mm 144
CSR 10008 (a) Nil 52/46 51/45
– /120/120 (c) 75 Acoustigard 11kg 58/50 57/49
90/90/90
(from both sides) BOTH SIDES (e) 88 Soundscreen 2.5 61/54 60/53
• 2 x 13mm Gyprock EC08 Extreme. (f) 50 Acoustigard 14kg 58/50 57/49
FC 12946
FAS 200002 (i) 90 Acoustigard 14kg 60/53 59/52
Wall Thickness mm 144
CSR 1133 (a) Nil 41/34 40/33

– /90/90 (c) 75 Acoustigard 14kg 50/42 49/41


BOTH SIDES
60/60/60 (f) 50 Acoustigard 14kg 49/40 48/39
(from both sides) • 1 x 16mm Gyprock Fyrchek
Plasterboard. (g) 70 Soundscreen 2.0 51/43 50/42
FC 12946 (i) 90 Acoustigard 14kg 51/43 50/42
Wall Thickness mm 124
CSR 1135 (a) Nil 42/35 41/34
SIDE ONE
– /90/90 • 1 x 16mm Gyprock Fyrchek (c) 75 Acoustigard 14kg 51/43 50/42
60/60/60 Plasterboard. (f) 50 Acoustigard 14kg 50/41 49/40
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 52/44 51/43
FC 12946 • 1 x 16mm Gyprock Fyrchek MR (i) 90 Acoustigard 14kg 52/44 51/43
Plasterboard.
Wall Thickness mm 124
CSR 3073 (a) Nil 44/37 43/36

– /90/90 (c) 75 Acoustigard 14kg 53/45 52/44


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 52/43 51/42
(from both sides)
• 1 x 16mm Gyprock EC08 Complete. (g) 70 Soundscreen 2.0 54/46 53/45
FC 12946 (i) 90 Acoustigard 14kg 54/46 53/45
Wall Thickness mm 124
CSR 1140 (a) Nil 46/39 45/38
SIDE ONE
– /90/90 • 1 x 16mm Gyprock Fyrchek (c) 75 Acoustigard 14kg 54/46 53/45
60/60/60 Plasterboard. (f) 50 Acoustigard 14kg 53/44 52/43
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 55/47 54/46
FC 12946 • 2 x 16mm Gyprock Fyrchek (i) 90 Acoustigard 14kg 55/47 54/46
Plasterboard.
Wall Thickness mm 140

GYPROCK® THE RED BOOK™ 1 C21


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Rondo Quiet Stud

Lining material as per system table. Cavity insulation as per system table.

Rondo Quiet studs at 600mm maximum Lining material as per system table.
centres.

‡ Unique height restrictions apply. Refer to


The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide

STUD DEPTH mm 92
FRL SYSTEM STUD BMT mm 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1142 (a) Nil 47/40 46/39
SIDE ONE
– /90/90 • 1 x 16mm Gyprock Fyrchek MR (c) 75 Acoustigard 14kg 55/47 54/46
60/60/60 Plasterboard. (f) 50 Acoustigard 14kg 54/45 53/44
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 56/48 55/47
FC 12946 • 2 x 16mm Gyprock Fyrchek (i) 90 Acoustigard 14kg 56/48 55/47
Plasterboard.
Wall Thickness mm 140
CSR 10034 (a) Nil 53/47 52/46

– /180/180‡ (c) 75 Acoustigard 11kg 59/51 58/50


120/120/120 BOTH SIDES (e) 88 Soundscreen 2.5 62/55 61/54
(from both sides) • 2 x 16mm Gyprock Fyrchek
Plasterboard. (f) 50 Acoustigard 14kg 59/51 58/50
FC 12946 (i) 90 Acoustigard 14kg 58/51 57/50
Wall Thickness mm 156
CSR 3095 (a) Nil 53/47 52/46

– /180/180‡ (c) 75 Acoustigard 11kg 59/51 58/50


120/120/120 BOTH SIDES (e) 88 Soundscreen 2.5 62/55 61/54
(from both sides) • 2 x 16mm Gyprock EC08 Complete. (f) 50 Acoustigard 14kg 59/51 58/50
FC 12946 (i) 90 Acoustigard 14kg 61/54 60/53
Wall Thickness mm 156

C22 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Resilient Mount

Lining material as per system table. Gyprock Resilient Mounts screw fixed to
one side of studs.
Steel studs at 600mm maximum centres.
Rondo Nº308 or Nº129 Furring Channel
Continuous nogging aligned with every clipped to resilient mounts.
Gyprock Resilient Mount.
Cavity insulation as per system table.

Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

STUD DEPTH mm 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1160 (a) Nil 46/39 46/39 48/41 49/43
SIDE ONE (FURRING SIDE)
– /90/90 • 2 x 13mm Gyprock (c) 75 Acoustigard 14kg 55/45 55/45 57/47 57/48
30/30/30 Fyrchek Plasterboard. (f) 50 Acoustigard 14kg 55/45 54/44 56/46 57/48
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – 56/46 58/48 58/49
FC 12946 • 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 51/43 51/43 53/45 53/46
Fyrchek Plasterboard.
Minimum Wall Thickness mm 131 143 159 217
CSR 1161 (a) Nil 46/39 47/40 48/41 50/44
SIDE ONE (FURRING SIDE)
– /90/90 • 2 x 13mm Gyprock (c) 75 Acoustigard 14kg 55/45 56/46 57/47 58/49
30/30/30 Fyrchek Plasterboard. (f) 50 Acoustigard 14kg 55/45 55/45 56/46 58/49
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – 57/47 58/48 59/50
FC 12946 • 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 51/43 52/44 53/45 54/47
Fyrchek MR Plasterboard.
Minimum Wall Thickness mm 131 143 159 217
CSR 1162 (a) Nil 46/39 47/40 48/41 50/44
SIDE ONE (FURRING SIDE)
– /90/90 • 2 x 13mm Gyprock (c) 75 Acoustigard 14kg 55/45 56/46 57/47 58/49
30/30/30 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 55/45 55/45 56/46 58/49
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – 57/47 58/48 59/50
FC 12946 • 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 51/43 52/44 53/45 54/47
Fyrchek MR Plasterboard.
Minimum Wall Thickness mm 131 143 159 217
CSR 1165 (a) Nil 50/44 51/45 51/45 53/47

– /120/120 (c) 75 Acoustigard 14kg 58/49 59/50 59/50 60/51


BOTH SIDES
90/90/90 (f) 50 Acoustigard 14kg 58/49 58/49 58/49 60/51
(from both sides) • 2 x 13mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 – 60/51 60/51 61/52
FC 12946 (h) 50 MAB Polyester 11kg 54/47 55/48 55/48 56/49
Minimum Wall Thickness mm 144 156 172 230
CSR 1166 (a) Nil 50/44 51/45 51/45 53/47
SIDE ONE (FURRING SIDE)
– /120/120 • 2 x 13mm Gyprock (c) 75 Acoustigard 14kg 58/49 59/50 59/50 60/51
90/90/90 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 58/49 58/49 58/49 60/51
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – 60/51 60/51 61/52
FC 12946 • 2 x 13mm Gyprock (h) 50 MAB Polyester 11kg 54/47 55/48 55/48 56/49
Fyrchek Plasterboard.
Minimum Wall Thickness mm 144 156 172 230

GYPROCK® THE RED BOOK™ 1 C23


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Resilient Mount

Lining material as per system table. Gyprock Resilient Mounts screw fixed to
one side of studs.
Steel studs at 600mm maximum centres.
Rondo Nº308 or Nº129 Furring Channel
Continuous nogging aligned with every clipped to resilient mounts.
Gyprock Resilient Mount.
Cavity insulation as per system table.

Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
‡ Unique height restrictions apply. Refer to
The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

STUD DEPTH mm 64 76 92 150


FRL SYSTEM STUD BMT mm 0.50 0.55 0.55 0.75
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1167 (a) Nil 50/44 51/45 52/46 53/47

– /120/120 (c) 75 Acoustigard 14kg 58/49 59/50 60/51 60/51


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 58/49 58/49 59/50 60/51
(from both sides) • 2 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 – 60/51 61/52 61/52
FC 12946 (h) 50 MAB Polyester 11kg 54/47 55/48 56/49 56/49
Minimum Wall Thickness mm 144 156 172 230
CSR 3132 (a) Nil 52/46 52/46 53/47 54/48

– /120/120 (c) 75 Acoustigard 11kg 60/51 60/51 61/52 61/52


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 62/53 62/53 63/54 63/54
(from both sides) • 2 x 13mm Gyprock EC08
Complete. (f) 50 Acoustigard 14kg 60/51 59/50 60/51 61/52
FC 12946 (g) 50 MAB Polyester 11kg 56/49 56/49 57/50 57/50
Minimum Wall Thickness mm 144 156 172 230
CSR 10009 (a) Nil 52/46 52/46 53/47 54/48

– /120/120 (c) 75 Acoustigard 11kg 60/51 60/51 61/52 61/52


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 62/53 62/53 63/54 63/54
(from both sides) • 2 x 13mm Gyprock EC08
Extreme. (f) 50 Acoustigard 14kg 60/51 59/50 60/51 61/52
FC 12946 (g) 50 MAB Polyester 11kg 56/49 56/49 57/50 57/50
Minimum Wall Thickness mm 144 156 172 230
CSR 1175 (a) Nil 50/44 50/44 51/45 52/46

– /180/180‡ (c) 75 Acoustigard 11kg 58/49 58/49 59/50 59/50


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 58/49 57/48 58/49 59/50
(from both sides) • 2 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 – 59/50 60/51 60/51
FC 12946 (h) 50 MAB Polyester 11kg 54/47 54/47 55/48 55/48
Minimum Wall Thickness mm 156 168 184 242
CSR 1176 (a) Nil 51/45 51/45 52/46 54/48
SIDE ONE (FURRING SIDE)
– /180/180‡ • 2 x 16mm Gyprock (c) 75 Acoustigard 11kg 59/50 59/50 60/51 61/52
120/120/120 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 59/50 58/49 59/50 61/52
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 – 60/51 61/52 62/53
FC 12946 • 2 x 16mm Gyprock (h) 50 MAB Polyester 11kg 55/48 55/48 56/49 57/50
Fyrchek Plasterboard.
Minimum Wall Thickness mm 156 168 184 242
CSR 1177 (a) Nil 52/46 52/46 53/47 55/49

– /180/180‡ (c) 75 Acoustigard 11kg 60/51 60/51 61/52 62/53


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 60/51 59/50 60/51 62/53
(from both sides) • 2 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 – 61/52 62/53 63/54
FC 12946 (h) 50 MAB Polyester 11kg 56/49 56/49 57/50 58/51
Minimum Wall Thickness mm 156 168 184 242

C24 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.

Staggered steel studs at 600mm Lining material as per system table.


maximum centres each side. Studs
restrained in track or angle at top and
bottom with minimum 28mm clearance
between stud and opposing lining.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

CAVITY DEPTH mm 92 150


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5 92/0.55
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10141 (a) Nil 38/31 41/34
(b) 75 Acoustigard 11kg 49/40 51/42
BOTH SIDES (c) 75 MAB Polyester 11kg 45/37 47/39
–/–/– • 1 x 10mm Gyprock HD
Plasterboard. (d) 50 Acoustigard 14kg 49/40 51/42
(e) 70 Soundscreen 2.0 51/40 53/42
Wall Thickness mm 112 170
CSR 10142 (a) Nil 44/37 47/40
SIDE ONE
• 2 x 10mm Gyprock HD (b) 75 Acoustigard 11kg 54/45 56/47
Plasterboard. (c) 75 MAB Polyester 11kg 50/42 52/44
–/–/–
SIDE TWO (d) 50 Acoustigard 14kg 54/45 56/47
• 1 x 6mm CeminSeal (e) 70 Soundscreen 2.0 56/45 58/47
Wallboard.
Wall Thickness mm 118 176
CSR 10143 (a) Nil 44/37 47/41
SIDE ONE
• 2 x 10mm Gyprock HD (b) 75 Acoustigard 11kg 54/45 56/48
Plasterboard. (c) 75 MAB Polyester 11kg 50/42 52/45
–/–/–
SIDE TWO (d) 50 Acoustigard 14kg 54/45 56/48
• 1 x 13mm Gyprock (e) 70 Soundscreen 2.0 56/45 58/48
Aquachek Plasterboard.
Wall Thickness mm 125 183
CSR 1220 (a) Nil 38/31 42/35
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 49/40 52/43
Standard Plasterboard. (f) 50 Acoustigard 14kg 49/40 52/43
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 51/40 54/43
• 1 x 6mm CeminSeal (h) 75 MAB Polyester 11kg 45/37 48/40
Wallboard.
Wall Thickness mm 111 169
CSR 1223 (a) Nil 38/31 41/34
(c) 75 Acoustigard 11kg 49/40 51/42
BOTH SIDES (f) 50 Acoustigard 14kg 49/40 51/42
–/–/– • 1 x 13mm Gyprock
Standard Plasterboard. (g) 70 Soundscreen 2.0 51/40 53/42
(h) 100 MAB Polyester 11kg 46/38 49/41
Wall Thickness mm 118 176

GYPROCK® THE RED BOOK™ 1 C25


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.

Staggered steel studs at 600mm Lining material as per system table.


maximum centres each side. Studs
restrained in track or angle at top and
bottom with minimum 28mm clearance
between stud and opposing lining.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

CAVITY DEPTH mm 92 150


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5 92/0.55
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1224 (a) Nil 39/32 42/35
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 50/41 52/43
Aquachek Plasterboard. (f) 50 Acoustigard 14kg 50/41 52/43
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 52/41 54/43
• 1 x 13mm Gyprock (h) 100 MAB Polyester 11kg 47/39 50/42
Standard Plasterboard.
Wall Thickness mm 118 176
CSR 1225 (a) Nil 39/32 42/35
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 50/41 52/43
Standard Plasterboard. (f) 50 Acoustigard 14kg 50/41 52/43
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 52/41 52/43
• 1 x 13mm Gyprock (h) 75 MAB Polyester 11kg 46/38 48/40
Impactchek Plasterboard.
Wall Thickness mm 118 176
CSR 1226 (a) Nil 40/33 43/37
(c) 75 Acoustigard 11kg 51/42 53/45
BOTH SIDES (f) 50 Acoustigard 14kg 51/42 53/45
–/–/– • 1 x 13mm Gyprock
Aquachek Plasterboard. (g) 70 Soundscreen 2.0 53/42 55/45
(h) 100 MAB Polyester 11kg 48/40 51/44
Wall Thickness mm 118 176
CSR 1227 (a) Nil 42/35 45/39

(c) 75 Acoustigard 11kg 53/44 55/47


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (f) 50 Acoustigard 14kg 53/44 55/47
Soundchek Plasterboard.
(g) 70 Soundscreen 2.0 55/44 57/47

Wall Thickness mm 118 176


CSR 1230 (a) Nil 51/45 53/47

(c) 75 Acoustigard 11kg 60/52 61/53


BOTH SIDES
–/–/– • 2 x 13mm Gyprock (f) 50 Acoustigard 14kg 60/52 61/53
Soundchek Plasterboard.
(g) 70 Soundscreen 2.0 62/52 63/53

Wall Thickness mm 144 202

C26 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.

Staggered steel studs at 600mm Lining material as per system table.


maximum centres each side. Studs
restrained in track or angle at top and
bottom with minimum 28mm clearance
between stud and opposing lining.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

CAVITY DEPTH mm 92 150


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5 92/0.55
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1250 (a) Nil 41/34 44/38

– /60/60 (c) 75 Acoustigard 11kg 52/43 54/46


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 52/43 54/46
(from both sides) • 1 x 13mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 54/43 56/46
FC 12946 (h) 75 MAB Polyester 11kg 48/40 50/43
Wall Thickness mm 118 176
CSR 1251 (a) Nil 41/34 44/38
SIDE ONE
– /60/60 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 52/43 54/46
30/30/30 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 52/43 54/46
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 54/43 56/46
FC 12946 • 1 x 13mm Gyprock (h) 75 MAB Polyester 11kg 48/40 50/43
Fyrchek Plasterboard.
Wall Thickness mm 118 176
CSR 1252 (a) Nil 41/34 44/38

– /60/60 (c) 75 Acoustigard 11kg 52/43 54/46


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 52/43 54/46
(from both sides) • 1 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 54/43 56/46
FC 12946 (h) 75 MAB Polyester 11kg 48/40 50/43
Wall Thickness mm 118 176
CSR 3162 (a) Nil 43/36 46/40

– /60/60 (c) 75 Acoustigard 11kg 54/45 56/48


30/30/30 BOTH SIDES (e) 88 Soundscreen 2.5 57/47 60/51
(from both sides) • 1 x 13mm Gyprock EC08
Complete. (f) 50 Acoustigard 14kg 54/45 56/48
FC 12946 (h) 50 MAB Polyester 11kg 49/41 51/44
Wall Thickness mm 118 176
CSR 10010 (a) Nil 43/36 46/40

– /60/60 (c) 75 Acoustigard 11kg 54/45 56/48


30/30/30 BOTH SIDES (e) 88 Soundscreen 2.5 57/47 60/51
(from both sides) • 1 x 13mm Gyprock EC08
Extreme. (f) 50 Acoustigard 14kg 54/45 56/48
FC 12946 (h) 50 MAB Polyester 11kg 49/41 51/44
Wall Thickness mm 118 176
CSR 1260 (a) Nil 46/39 49/43
SIDE ONE
– /90/90 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 56/47 58/50
30/30/30 Fyrchek Plasterboard. (f) 50 Acoustigard 14kg 56/47 58/50
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 58/47 60/50
FC 12946 • 2 x 13mm Gyprock (h) 75 MAB Polyester 11kg 52/44 54/47
Fyrchek Plasterboard.
Wall Thickness mm 131 189

GYPROCK® THE RED BOOK™ 1 C27


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.

Staggered steel studs at 600mm Lining material as per system table.


maximum centres each side. Studs
restrained in track or angle at top and
bottom with minimum 28mm clearance
between stud and opposing lining.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

CAVITY DEPTH mm 92 150


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5 92/0.55
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1264 (a) Nil 49/43 52/46

– /90/90 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg 58/50 60/52
• 1 x 6mm CeminSeal
30/30/30 (f) 50 Acoustigard 14kg 58/50 60/52
(from both sides) Wallboard.
• 1 x 13mm Gyprock (g) 70 Soundscreen 2.0 60/50 62/52
FC 12946 Fyrchek Plasterboard. (h) 75 MAB Polyester 14kg 56/49 58/51
Wall Thickness mm 130 188
CSR 1275 (a) Nil 52/46 54/48

– /90/90 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg 61/53 62/54
• 1 x 16mm Gyprock
60/60/60 (f) 50 Acoustigard 14kg 61/53 62/54
(from both sides) Fyrchek Plasterboard.
• 1 x 13mm Gyprock (g) 70 Soundscreen 2.0 63/53 64/54
FC 12946 Soundchek Plasterboard. (h) 75 MAB Polyester 14kg 59/52 60/53
Wall Thickness mm 150 208
CSR 1280 (a) Nil 41/34 44/38

– /90/90 (c) 75 Acoustigard 11kg 52/43 54/46


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 52/43 54/46
(from both sides) • 1 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 54/43 56/46
FC 12946 (h) 75 MAB Polyester 11kg 48/40 50/43
Wall Thickness mm 124 182
CSR 1281 (a) Nil 42/35 45/39
SIDE ONE
– /90/90 • 1 x 16mm Gyprock (c) 75 Acoustigard 11kg 53/44 55/47
60/60/60 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 53/44 55/47
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 55/44 57/47
FC 12946 • 1 x 16mm Gyprock (h) 75 MAB Polyester 11kg 49/41 51/44
Fyrchek Plasterboard.
Wall Thickness mm 124 182
CSR 1282 (a) Nil 43/36 46/40

– /90/90 (c) 75 Acoustigard 11kg 54/45 56/48


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 54/45 56/48
(from both sides) • 1 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 56/45 58/48
FC 12946 (h) 75 MAB Polyester 11kg 50/42 52/45
Wall Thickness mm 124 182

C28 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Staggered Stud

Lining material as per system table.

Staggered steel studs at 600mm Cavity insulation as per system table.


maximum centres each side. Studs
restrained in track or angle at top and Lining material as per system table.
bottom with minimum 28mm clearance
between stud and opposing lining.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

CAVITY DEPTH mm 92 150


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5 92/0.55
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1285 (a) Nil 50/44 52/46

– /120/120 (c) 75 Acoustigard 11kg 59/51 60/52


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 59/51 60/52
(from both sides) • 2 x 13mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 61/51 62/52
FC 12946 (h) 75 MAB Polyester 14kg 59/50 58/51
Wall Thickness mm 144 202
CSR 1286 (a) Nil 50/44 52/46
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 75 Acoustigard 11kg 59/51 60/52
90/90/90 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 59/51 60/52
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 61/51 62/52
FC 12946 • 2 x 13mm Gyprock (h) 75 MAB Polyester 11kg 55/48 56/49
Fyrchek Plasterboard.
Wall Thickness mm 144 202
CSR 1287 (a) Nil 50/44 52/46

– /120/120 (c) 75 Acoustigard 11kg 59/51 60/52


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 59/51 60/52
(from both sides) • 2 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 61/51 62/52
FC 12946 (h) 75 MAB Polyester 11kg 55/48 56/49
Wall Thickness mm 144 202
CSR 3172 (a) Nil 52/46 54/48

– /120/120 (c) 75 Acoustigard 11kg 61/53 62/54


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 64/55 66/57
(from both sides) • 2 x 13mm Gyprock EC08
Complete. (f) 50 Acoustigard 14kg 61/53 62/54
FC 12946 (g) 50 MAB Polyester 11kg 56/49 57/50
Wall Thickness mm 144 202
CSR 10011 (a) Nil 52/46 54/48

– /120/120 (c) 75 Acoustigard 11kg 61/53 62/54


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 64/55 66/57
(from both sides) • 2 x 13mm Gyprock EC08
Extreme. (f) 50 Acoustigard 14kg 61/53 62/54
FC 12946 (g) 50 MAB Polyester 11kg 56/49 57/50
Wall Thickness mm 144 202

GYPROCK® THE RED BOOK™ 1 C29


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Staggered Stud

Lining material as per system table.

Staggered steel studs at 600mm Cavity insulation as per system table.


maximum centres each side. Studs
restrained in track or angle at top and Lining material as per system table.
bottom with minimum 28mm clearance
between stud and opposing lining.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
‡ Unique height restrictions apply. Refer to
The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Not Deemed Discontinuous Construction

CAVITY DEPTH mm 92 150


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5 92/0.55
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1290 (a) Nil 50/44 52/46

– /180/180‡ (c) 75 Acoustigard 11kg 59/51 60/52


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 59/51 60/52
(from both sides) • 2 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 61/51 62/52
FC 12946 (h) 75 MAB Polyester 11kg 55/48 56/49
Wall Thickness mm 156 214
CSR 1291 (a) Nil 51/45 53/47
SIDE ONE
– /180/180‡ • 2 x 16mm Gyprock (c) 75 Acoustigard 11kg 60/52 61/53
120/120/120 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 60/52 61/53
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 62/52 63/53
FC 12946 • 2 x 16mm Gyprock (h) 75 MAB Polyester 11kg 56/49 57/50
Fyrchek Plasterboard.
Wall Thickness mm 156 214
CSR 1292 (a) Nil 52/46 54/48

– /180/180‡ (c) 75 Acoustigard 11kg 61/53 62/54


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 61/53 62/54
(from both sides) • 2 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 63/53 64/54
FC 12946 (h) 75 MAB Polyester 11kg 57/50 58/51
Wall Thickness mm 156 214

C30 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of steel studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MINIMUM STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10029 (a) Nil 39/32 42/36 43/37 43/37
(c) 75 Acoustigard 11kg 52/42 54/45 55/46 55/46
BOTH SIDES (f) 50 Acoustigard 14kg 50/40 53/44 54/45 54/45
–/–/– • 1 x 13mm Gyprock
Standard Plasterboard. (g) 70 Soundscreen 2.0 53/41 56/45 57/46 57/46
(h) 50 MAB Polyester 11kg 45/37 48/41 49/42 49/42
Wall Thickness mm 174 226 276 326
CSR 10030 (a) Nil 42/36 44/38 45/39 45/39
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 55/46 56/47 57/48 57/48
Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 53/44 55/46 56/47 56/47
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 56/45 58/47 59/48 59/48
• 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 48/41 50/43 51/44 51/44
Fyrchek Plasterboard.
Wall Thickness mm 174 226 276 326
CSR 1305 (a) Nil 41/34 43/37 44/38 45/39
(c) 75 Acoustigard 11kg 54/44 55/46 56/47 57/48
BOTH SIDES (f) 50 Acoustigard 14kg 52/42 54/45 55/46 56/47
–/–/– • 1 x 13mm Gyprock
Aquachek Plasterboard. (g) 70 Soundscreen 2.0 55/43 57/46 58/47 59/48
(h) 50 MAB Polyester 11kg 47/39 49/42 50/43 51/44
Wall Thickness mm 174 226 276 326
CSR 1306 (a) Nil 43/36 44/38 45/39 46/40
SIDE ONE
• 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 56/46 56/47 57/48 58/49
Soundchek Plasterboard. (f) 50 Acoustigard 14kg 54/44 55/46 56/47 57/48
–/–/–
SIDE TWO (g) 70 Soundscreen 2.0 57/45 58/47 59/48 60/49
• 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 49/41 50/43 51/44 52/45
Aquachek Plasterboard.
Wall Thickness mm 174 226 276 326
CSR 1307 (a) Nil 43/37 44/38 45/39 46/40
(c) 75 Acoustigard 11kg 56/47 56/47 57/48 58/49
BOTH SIDES (f) 50 Acoustigard 14kg 54/45 55/46 56/47 57/48
–/–/– • 1 x 13mm Gyprock
Soundchek Plasterboard. (g) 70 Soundscreen 2.0 57/46 58/47 59/48 60/49
(h) 50 MAB Polyester 11kg 49/42 50/43 51/44 52/45
Wall Thickness mm 174 226 276 326
CSR 1320 (a) Nil 42/36 43/37 44/38 45/39

– /60/60 (c) 75 Acoustigard 11kg 55/46 55/46 56/47 57/48


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 53/44 54/45 55/46 56/47
(from both sides) • 1 x 13mm Gyprock
Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 48/41 49/42 50/43 51/44
FC 12946 (g) 70 Soundscreen 2.0 56/45 57/46 58/47 59/48
Wall Thickness mm 174 226 276 326

GYPROCK® THE RED BOOK™ 1 C31


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.

2 rows of steel studs at 600mm Lining material as per system table.


maximum centres with 20mm
minimum gap.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MINIMUM STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1321 (a) Nil 42/36 44/38 45/39 45/39
SIDE ONE
– /60/60 • 1 x 13mm Gyprock (c) 75 Acoustigard 11kg 55/46 56/47 57/48 57/48
30/30/30 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 53/44 55/46 56/47 56/47
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 56/45 58/47 59/48 59/48
FC 12946 • 1 x 13mm Gyprock (h) 50 MAB Polyester 11kg 48/41 50/43 51/44 51/44
Fyrchek Plasterboard.
Wall Thickness mm 174 226 276 326
CSR 1322 (a) Nil 42/36 44/38 45/39 45/39

– /60/60 (c) 75 Acoustigard 11kg 55/46 56/47 57/48 57/48


30/30/30 BOTH SIDES (f) 50 Acoustigard 14kg 53/44 55/46 56/47 56/47
(from both sides) • 1 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 56/45 58/47 59/48 59/48
FC 12946 (h) 50 MAB Polyester 11kg 48/41 50/43 51/44 51/44
Wall Thickness mm 174 226 276 326
CSR 3222 (a) Nil 44/38 45/39 46/40 47/41

– /60/60 (c) 75 Acoustigard 11kg 57/48 57/48 58/49 59/50


30/30/30 BOTH SIDES (e) 88 Soundscreen 2.5 60/50 60/50 61/51 62/52
(from both sides) • 1 x 13mm Gyprock EC08
Complete. (f) 50 Acoustigard 14kg 55/46 56/47 57/48 58/49
FC 12946 (h) 50 MAB Polyester 11kg 50/43 51/44 52/45 53/46
Wall Thickness mm 174 226 276 326
CSR 10012 (a) Nil 44/38 45/39 46/40 47/41

– /60/60 (c) 75 Acoustigard 11kg 57/48 57/48 58/49 59/50


30/30/30 BOTH SIDES (e) 88 Soundscreen 2.5 60/50 60/50 61/51 62/52
(from both sides) • 1 x 13mm Gyprock EC08
Extreme. (f) 50 Acoustigard 14kg 55/46 56/47 57/48 58/49
FC 12946 (h) 50 MAB Polyester 11kg 50/43 51/44 52/45 53/46
Wall Thickness mm 174 226 276 326
CSR 1330 (a) Nil 50/44 51/45 52/46 53/47

– /90/90 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg 61/52 61/52 62/53 63/54
• 1 x 6mm CeminSeal
30/30/30 (f) 50 Acoustigard 14kg 59/50 60/51 61/52 62/53
(from both sides) Wallboard.
• 1 x 13mm Gyprock (g) 70 Soundscreen 2.0 62/51 63/52 64/53 65/54
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 54/47 55/48 56/49 57/50
Wall Thickness mm 186 238 288 338
CSR 1333 SIDE ONE (a) Nil 50/44 51/45 52/46 53/47
• 2 x 13mm Gyprock
– /90/90 (c) 75 Acoustigard 11kg 61/52 61/52 62/53 63/54
Fyrchek Plasterboard.
30/30/30 (f) 50 Acoustigard 14kg 59/50 60/51 61/52 62/53
(from both sides) SIDE TWO (ANY ORDER)
• 1 x 6mm CeminSeal (g) 70 Soundscreen 2.0 62/51 63/52 64/53 65/54
FC 12946 Wallboard. (h) 50 MAB Polyester 11kg 54/47 55/48 56/49 57/50
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness mm 193 245 295 345

C32 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of steel studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MINIMUM STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1340 (a) Nil 42/36 43/37 44/38 45/39

– /90/90 (c) 75 Acoustigard 11kg 55/46 55/46 56/47 57/48


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 53/44 54/45 55/46 56/47
(from both sides) • 1 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 56/45 57/46 58/47 59/48
FC 12946 (h) 50 MAB Polyester 11kg 48/41 49/42 50/43 51/44
Wall Thickness mm 180 232 282 332
CSR 1341 (a) Nil 43/37 44/38 45/39 46/40
SIDE ONE
– /90/90 • 1 x 16mm Gyprock (c) 75 Acoustigard 11kg 56/47 56/47 57/48 58/49
60/60/60 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 54/45 55/46 56/47 57/48
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 57/46 58/47 59/48 60/49
FC 12946 • 1 x 16mm Gyprock (h) 50 MAB Polyester 11kg 49/42 50/43 51/44 52/45
Fyrchek Plasterboard.
Wall Thickness mm 180 232 282 332
CSR 1342 (a) Nil 44/38 45/39 46/40 47/41

– /90/90 (c) 75 Acoustigard 11kg 57/48 57/48 58/49 59/50


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 55/46 56/47 57/48 58/49
(from both sides) • 1 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 58/47 59/48 60/49 61/50
FC 12946 (h) 50 MAB Polyester 11kg 50/43 51/44 52/45 53/46
Wall Thickness mm 180 232 282 332
CSR 3232 (a) Nil 45/39 46/40 47/41 48/42

– /90/90 (c) 75 Acoustigard 11kg 58/49 58/49 59/50 60/51


60/60/60 BOTH SIDES (f) 50 Acoustigard 14kg 56/47 57/48 58/49 59/50
(from both sides) • 1 x 16mm Gyprock EC08
Complete. (g) 70 Soundscreen 2.0 59/48 60/49 61/50 62/51
FC 12946 (h) 50 MAB Polyester 11kg 51/44 53/45 53/46 54/47
Wall Thickness mm 180 232 282 332
CSR 1345 (a) Nil 50/44 52/46 53/47 53/47

– /90/90 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg 61/52 62/53 63/54 63/54
• 1 x 6mm CeminSeal
60/60/60 (f) 50 Acoustigard 14kg 59/50 61/52 62/53 62/53
(from both sides) Wallboard.
• 1 x 16mm Gyprock (g) 70 Soundscreen 2.0 62/51 64/53 65/54 65/54
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 54/47 56/49 57/50 57/50
Wall Thickness mm 192 244 294 344
CSR 1348 (a) Nil 49/43 50/43 51/45 52/46

– /90/90 BOTH SIDES (ANY ORDER) (c) 75 Acoustigard 11kg 60/51 60/51 61/52 62/53
• 1 x 10mm Gyprock Plus
60/60/60 (f) 50 Acoustigard 14kg 58/49 59/50 60/51 61/52
(from both sides) Plasterboard.
• 1 x 16mm Gyprock (g) 70 Soundscreen 2.0 61/50 62/51 63/52 64/53
FC 12946 Fyrchek Plasterboard. (h) 50 MAB Polyester 11kg 53/46 54/47 55/48 56/49
Wall Thickness mm 200 252 302 352

GYPROCK® THE RED BOOK™ 1 C33


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of steel studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MINIMUM STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1355 (a) Nil 50/44 51/45 52/46 53/47

– /120/120 (c) 75 Acoustigard 11kg 61/52 61/52 62/53 63/54


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 59/50 60/51 61/52 62/53
(from both sides) • 2 x 13mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 62/51 63/52 64/53 65/54
FC 12946 (h) 50 MAB Polyester 11kg 54/47 55/48 56/49 57/50
Wall Thickness mm 200 252 302 352
CSR 1356 (a) Nil 50/44 52/46 53/47 53/47
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 75 Acoustigard 11kg 61/52 62/53 63/54 63/54
90/90/90 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 59/50 61/52 62/53 62/53
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 62/51 64/53 65/54 65/54
FC 12946 • 2 x 13mm Gyprock (h) 50 MAB Polyester 11kg 54/47 56/49 57/50 57/50
Fyrchek Plasterboard.
Wall Thickness mm 200 252 302 352
CSR 1357 (a) Nil 50/44 52/46 53/47 53/47

– /120/120 (c) 75 Acoustigard 11kg 61/52 62/53 63/54 63/54


90/90/90 BOTH SIDES (f) 50 Acoustigard 14kg 59/50 61/52 62/53 62/53
(from both sides) • 2 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 62/51 64/53 65/54 65/54
FC 12946 (h) 50 MAB Polyester 11kg 54/47 56/49 57/50 57/50
Wall Thickness mm 200 252 302 352
CSR 3242 (a) Nil 52/46 53/47 54/48 55/49

– /120/120 (c) 75 Acoustigard 11kg 63/54 63/54 64/55 65/56


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 66/56 66/56 67/57 68/58
(from both sides) • 2 x 13mm Gyprock EC08
Complete. (f) 50 Acoustigard 14kg 61/52 62/53 63/54 64/55
FC 12946 (h) 50 MAB Polyester 11kg 56/49 57/50 58/51 59/52
Wall Thickness mm 200 252 302 352
CSR 10013 (a) Nil 52/46 53/47 54/48 55/49

– /120/120 (c) 75 Acoustigard 11kg 63/54 63/54 64/55 65/56


90/90/90 BOTH SIDES (e) 88 Soundscreen 2.5 66/56 66/56 67/57 68/58
(from both sides) • 2 x 13mm Gyprock EC08
Extreme. (f) 50 Acoustigard 14kg 61/52 62/53 63/54 64/55
FC 12946 (h) 50 MAB Polyester 11kg 56/49 57/50 58/51 59/52
Wall Thickness mm 200 252 302 352

C34 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of steel studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
‡ Unique height restrictions apply. Refer to
The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MINIMUM STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1360 (a) Nil 50/44 51/45 52/46 53/47

– /180/180‡ (c) 75 Acoustigard 11kg 61/52 61/52 62/53 63/54


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 59/50 60/51 61/52 62/53
(from both sides) • 2 x 16mm Gyprock
Fyrchek Plasterboard. (g) 70 Soundscreen 2.0 62/51 63/52 64/53 65/54
FC 12946 (h) 75 MAB Polyester 14kg 57/50 57/50 58/51 59/52
Wall Thickness mm 212 264 314 364
CSR 1361 (a) Nil 51/45 52/46 53/47 54/48
SIDE ONE
– /180/180‡ • 2 x 16mm Gyprock (c) 75 Acoustigard 11kg 62/53 62/53 63/54 64/55
120/120/120 Fyrchek MR Plasterboard. (f) 50 Acoustigard 14kg 60/51 61/52 62/53 63/54
(from both sides)
SIDE TWO (g) 70 Soundscreen 2.0 63/52 64/53 65/54 66/55
FC 12946 • 2 x 16mm Gyprock (h) 75 MAB Polyester 14kg 58/51 58/51 59/52 60/53
Fyrchek Plasterboard.
Wall Thickness mm 212 264 314 364
CSR 1362 (a) Nil 52/46 53/47 54/48 55/49

– /180/180‡ (c) 75 Acoustigard 11kg 63/54 63/54 64/55 65/56


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 61/52 62/53 63/54 64/55
(from both sides) • 2 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 70 Soundscreen 2.0 64/53 65/54 66/55 67/56
FC 12946 (h) 75 MAB Polyester 14kg 59/52 59/52 60/53 61/54
Wall Thickness mm 212 264 314 364
CSR 3260 (a) Nil 53/47 54/48 55/49 56/50

– /180/180‡ (c) 75 Acoustigard 11kg 64/55 64/55 65/56 66/57


120/120/120 BOTH SIDES (f) 50 Acoustigard 14kg 62/53 63/54 64/55 65/56
(from both sides) • 2 x 16mm Gyprock EC08
Complete. (g) 70 Soundscreen 2.0 65/54 66/55 67/56 68/57
FC 12946 (h) 75 MAB Polyester 14kg 60/53 60/53 61/54 62/55
Wall Thickness mm 212 264 314 364

GYPROCK® THE RED BOOK™ 1 C35


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud with Two Rows Insulation

Lining material as per system table. Cavity insulation as per system table.
(Insulation in each stud row required).
2 rows of steel studs at 600mm
maximum centres with 20mm Lining material as per system table.
minimum gap.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MIN. STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1382 (a) Nil 47/41 48/42 49/43 50/44
SIDE ONE
– /90/90 • 2 x 13mm Gyprock (c) 2 x 75 Acoustigard 11kg 62/53 63/54 64/55 64/55
30/30/30 Fyrchek Plasterboard. (f) 2 x 50 Acoustigard 14kg 61/52 61/52 62/53 63/54
(from both sides)
SIDE TWO (g) 2 x 70 Soundscreen 2.0 63/53 64/54 65/55 65/55
FC 12946 • 1 x 13mm Gyprock (h) 2 x 50 MAB Polyester 11kg 57/48 57/49 58/50 58/50
Fyrchek Plasterboard.
Wall Thickness mm 187 239 289 339
CSR 1383 (a) Nil 47/41 48/42 49/43 50/44
SIDE ONE
– /90/90 • 2 x 13mm Gyprock (c) 2 x 75 Acoustigard 11kg 62/53 63/54 64/55 64/55
30/30/30 Fyrchek Plasterboard. (f) 2 x 50 Acoustigard 14kg 61/52 61/52 62/53 63/54
(from both sides)
SIDE TWO (g) 2 x 70 Soundscreen 2.0 63/53 64/54 65/55 65/55
FC 12946 • 1 x 13mm Gyprock (h) 2 x 50 MAB Polyester 11kg 56/48 57/49 58/50 58/50
Fyrchek MR Plasterboard.
Wall Thickness mm 187 239 289 339
CSR 10022 (a) Nil 50/44 51/45 52/46 53/47

– /120/120 (c) 2 x 75 Acoustigard 14kg 64/55 65/58 66/57 66/57


90/90/90 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 63/54 63/54 64/55 65/56
(from both sides) • 2 x 13mm Gyprock
Fyrchek Plasterboard. (g) 2 x 70 Soundscreen 2.0 65/55 66/56 67/57 67/57
FC 12946 (h) 2 x 50 MAB Polyester 11kg 58/50 59/51 60/52 60/52
Wall Thickness mm 200 252 302 352
CSR 10023 (a) Nil 50/44 52/46 53/47 53/47
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 2 x 75 Acoustigard 14kg 64/55 66/57 67/58 66/57
90/90/90 Fyrchek MR Plasterboard. (f) 2 x 50 Acoustigard 14kg 63/54 64/55 65/56 65/56
(from both sides)
SIDE TWO (g) 2 x 70 Soundscreen 2.0 65/55 67/57 68/58 67/57
FC 12946 • 2 x 13mm Gyprock (h) 2 x 50 MAB Polyester 11kg 58/50 60/52 61/53 60/52
Fyrchek Plasterboard.
Wall Thickness mm 200 252 302 352
CSR 10024 (a) Nil 50/44 52/46 53/47 53/47

– /120/120 (c) 2 x 75 Acoustigard 14kg 64/55 66/57 67/58 66/57


90/90/90 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 63/54 64/55 65/56 65/56
(from both sides) • 2 x 13mm Gyprock
Fyrchek MR Plasterboard. (g) 2 x 70 Soundscreen 2.0 65/55 67/57 68/58 67/57
FC 12946 (h) 2 x 50 MAB Polyester 11kg 58/50 60/52 61/53 60/52
Wall Thickness mm 200 252 302 352

C36 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud with Two Rows Insulation

Lining material as per system table. Cavity insulation as per system table.
(Insulation in each stud row required).
2 rows of steel studs at 600mm
maximum centres with 20mm Lining material as per system table.
minimum gap.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MIN. STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10028 (a) Nil 52/46 53/4 54/48 55/49

– /120/120 (c) 2 x 75 Acoustigard 14kg 66/57 67/58 68/59 68/59


90/90/90 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 65/56 65/56 66/57 67/58
(from both sides) • 2 x 13mm Gyprock EC08
Extreme. (g) 2 x 70 Soundscreen 2.0 67/57 68/58 69/59 69/59
FC 12946 (h) 2 x 50 MAB Polyester 11kg 60/52 61/53 62/54 62/54
Wall Thickness mm 200 252 302 352
CSR 1385 (a) Nil 42/36 43/37 44/38 45/39

– /90/90 (c) 2 x 75 Acoustigard 14kg 59/50 60/51 61/52 61/52


60/60/60 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 57/48 57/48 58/49 59/50
(from both sides) • 1 x 16mm Gyprock
Fyrchek Plasterboard. (g) 2 x 70 Soundscreen 2.0 59/49 60/50 61/51 61/51
FC 12946 (h) 2 x 50 MAB Polyester 11kg 52/44 53/45 54/46 54/46
Wall Thickness mm 180 232 282 332
CSR 1386 (a) Nil 43/37 44/38 45/39 46/40
SIDE ONE
– /90/90 • 1 x 16mm Gyprock (c) 2 x 75 Acoustigard 11kg 59/50 60/51 61/52 61/52
60/60/60 Fyrchek MR Plasterboard. (f) 2 x 50 Acoustigard 14kg 58/49 58/49 59/50 60/51
(from both sides)
SIDE TWO (g) 2 x 70 Soundscreen 2.0 60/50 61/51 62/52 62/52
FC 12946 • 1 x 16mm Gyprock (h) 2 x 50 MAB Polyester 11kg 53/45 54/46 55/47 55/47
Fyrchek Plasterboard.
Wall Thickness mm 180 232 282 332
CSR 1387 (a) Nil 44/38 45/39 46/40 47/41

– /90/90 (c) 2 x 75 Acoustigard 11kg 60/51 61/52 62/53 62/53


60/60/60 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 59/50 59/50 60/51 61/52
(from both sides) • 1 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 2 x 70 Soundscreen 2.0 61/51 62/52 63/53 63/53
FC 12946 (h) 2 x 50 MAB Polyester 11kg 54/46 55/47 56/48 56/48
Wall Thickness mm 180 232 282 332
CSR 3270 (a) Nil 45/39 46/40 47/41 48/42

– /90/90 (c) 2 x 75 Acoustigard 11kg 61/52 62/53 63/54 63/54


60/60/60 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 60/51 60/51 61/52 62/53
(from both sides) • 1 x 16mm Gyprock EC08
Complete. (g) 2 x 70 Soundscreen 2.0 62/52 63/53 64/54 64/54
FC 12946 (h) 2 x 50 MAB Polyester 11kg 55/47 56/48 57/49 57/49
Wall Thickness mm 180 232 282 332

GYPROCK® THE RED BOOK™ 1 C37


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud with Two Rows Insulation

Lining material as per system table. Cavity insulation as per system table.
(Insulation in each stud row required).
2 rows of steel studs at 600mm
maximum centres with 20mm Lining material as per system table.
minimum gap.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
‡ Unique height restrictions apply. Refer to
The Red Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 148 200 250 300


FRL SYSTEM MIN. STUD DEPTH/BMT mm 64/Any
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10025 (a) Nil 50/44 51/45 52/46 53/47

– /180/180‡ (c) 2 x 75 Acoustigard 11kg 64/55 65/56 66/57 66/57


120/120/120 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 63/54 63/54 64/55 65/56
(from both sides) • 2 x 16mm Gyprock
Fyrchek Plasterboard. (g) 2 x 70 Soundscreen 2.0 65/55 66/56 67/57 67/57
FC 12946 (h) 2 x 50 MAB Polyester 11kg 58/50 59/51 60/52 60/52
Wall Thickness mm 212 264 314 364
CSR 10026 (a) Nil 51/45 52/46 53/47 54/48
SIDE ONE
– /180/180‡ • 2 x 16mm Gyprock (c) 2 x 75 Acoustigard 11kg 65/56 66/57 67/58 67/58
120/120/120 Fyrchek MR Plasterboard. (f) 2 x 50 Acoustigard 14kg 64/55 64/55 65/56 65/57
(from both sides)
SIDE TWO (g) 2 x 70 Soundscreen 2.0 66/56 67/57 68/58 68/58
FC 12946 • 2 x 16mm Gyprock (h) 2 x 50 MAB Polyester 11kg 59/51 60/52 61/53 61/53
Fyrchek Plasterboard.
Wall Thickness mm 212 264 314 364
CSR 10027 (a) Nil 52/46 53/47 54/48 55/49

– /180/180‡ (c) 2 x 75 Acoustigard 11kg 66/57 67/58 68/59 68/59


120/120/120 BOTH SIDES (f) 2 x 50 Acoustigard 14kg 65/56 65/56 66/57 67/58
(from both sides) • 2 x 16mm Gyprock
Fyrchek MR Plasterboard. (g) 2 x 70 Soundscreen 2.0 67/57 68/58 69/59 69/59
FC 12946 (h) 2 x 50 MAB Polyester 11kg 60/52 61/53 62/54 62/54
Wall Thickness mm 212 264 314 364

C38 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Double Stud with Two Rows Insulation

Lining material as per system table. Cavity insulation as per system table.
(Insulation in each stud row required).
2 rows of steel studs at 600mm
maximum centres with 44mm Lining material as per system table.
minimum gap.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A128


Refer to Gyprock Red Book 3 & Cemintel Wallboard Guide Discontinuous Construction

CAVITY WIDTH mm 2x64 studs + 44 gap = 172


FRL SYSTEM STUD DEPTH/BMT mm 64/0.5
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1390
SIDE ONE
– /60/60 (b) 165 Acoustigard 11kg
• 1 x 13mm Gyprock
30/30/30 Fyrchek Plasterboard. + 55/50
(from both sides)
SIDE TWO 50 Acoustigard 14kg
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 201
CSR 1391
SIDE ONE
– /60/60 (b) 165 Acoustigard 11kg
• 1 x 13mm Gyprock
30/30/30 Fyrchek MR Plasterboard. + 55/50
(from both sides)
SIDE TWO 50 Acoustigard 14kg
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 201
CSR 1392
SIDE ONE
– /60/60 (b) 165 Acoustigard 11kg
• 1 x 13mm Gyprock
30/30/30 Fyrchek MR Plasterboard. + 56/51
(from both sides)
SIDE TWO 50 Acoustigard 14kg
FC 12946 • 1 x 16mm Gyprock
Fyrchek MR Plasterboard.
Wall Thickness mm 201

GYPROCK® THE RED BOOK™ 1 C39


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Party Wall

Lining material as per system table. Steel studs at 600mm maximum centres.

Steel studs at 600mm maximum centres. Gyprock aluminium wall clip

Gyprock aluminium wall clip Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in 20-40mm air gap.


H-studs at 600mm maximum centres.

20-40mm air gap.

NOTE: Acoustic performance valid for


20mm min. air gap each side.
#Wall height and clip spacings
restrictions apply, refer to page C7.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP513, Gyprock Party Wall Design Guide for further information Discontinuous Construction

STUD DEPTH mm 64 70 76 90/92


FRL SYSTEM STUD BMT mm 0.50 0.55 0.55 0.55
WALL LININGS
Report Nº
CAVITY INFILL BOTH SIDES Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1502
(b) 75 Acoustigard 14kg 62/49 62/49 63/50 64/52

60/60/60# BOTH SIDES (d) 110 Acoustigard 11kg 62/49 62/49 64/51 64/52
• 1 x 6mm CeminSeal
WF 45743 Wallboard (c) 88 Soundscreen 2.5 63/50 63/50 64/51 65/53

Minimum Wall Thickness mm 205 217 229 261

CSR 10144
(a) 50 Acoustigard 14kg 60/46 60/47 61/48 61/49

60/60/60# BOTH SIDES (b) 75 Acoustigard 14kg 62/48 62/49 63/50 63/51
• 1 x 10mm Gyprock HD
WF 45743 Plasterboard. (c) 88 Soundscreen 2.5 63/49 63/50 64/51 64/52

Minimum Wall Thickness mm 213 225 237 269

CSR 1507
SIDE ONE
(b) 75 Acoustigard 14kg 63/50 63/50 63/50 64/52
• 2 x 10mm Gyprock Plus
60/60/60# Plasterboard. (d) 110 Acoustigard 11kg 63/50 63/50 64/51 64/52

WF 45743 SIDE TWO (c) 88 Soundscreen 2.5 64/51 64/51 64/51 65/53
• 1 x 6mm CeminSeal
Wallboard
Minimum Wall Thickness mm 219 231 243 275

CSR 1510
(a) 75 Acoustigard 14kg 63/50 63/50 64/52 64/52

60/60/60# BOTH SIDES (b) 110 Acoustigard 11kg 63/50 63/50 65/53 64/52
• 2 x 10mm Gyprock Plus
WF 45743 Plasterboard. (c) 88 Soundscreen 2.5 64/51 64/51 65/53 65/53

Minimum Wall Thickness mm 233 245 257 289

CSR 1516
(a) 75 Acoustigard 14kg 64/52 65/53 65/53 66/54

60/60/60# BOTH SIDES (b) 110 Acoustigard 11kg 64/52 65/53 66/54 66/54
• 2 x 10mm Gyprock
WF 45743 Aquachek Plasterboard. (c) 88 Soundscreen 2.5 65/53 66/54 66/54 67/55

Minimum Wall Thickness mm 233 245 257 289

CSR 1523
(a) 50 Acoustigard 14kg 60/46 60/47 61/48 61/49

60/60/60# BOTH SIDES (b) 75 Acoustigard 14kg 62/48 62/49 63/50 63/51
• 1 x 13mm Gyprock
WF 45743 Standard Plasterboard. (c) 88 Soundscreen 2.5 63/49 63/50 64/51 64/52

Minimum Wall Thickness mm 219 231 243 275

C40 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Party Wall

Lining material as per system table. Steel studs at 600mm maximum centres.

Steel studs at 600mm maximum centres. Gyprock aluminium wall clip

Gyprock aluminium wall clip Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in 20-40mm air gap.


H-studs at 600mm maximum centres.

20-40mm air gap.

NOTE: Acoustic performance valid for


20mm min. air gap each side.
#Wall height and clip spacings
restrictions apply, refer to page C7.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP513, Gyprock Party Wall Design Guide for further information Discontinuous Construction

STUD DEPTH mm 64 70 76 90/92


FRL SYSTEM STUD BMT mm 0.50 0.55 0.55 0.55
WALL LININGS
Report Nº
CAVITY INFILL BOTH SIDES Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 1524
SIDE ONE
(a) 50 Acoustigard 14kg 60/46 61/48 61/48 62/50
• 1 x 13mm Gyprock
60/60/60# Standard Plasterboard. (b) 75 Acoustigard 14kg 62/48 63/50 63/50 64/52

WF 45743 SIDE TWO (c) 88 Soundscreen 2.5 63/49 64/51 64/51 65/53
• 1 x 13mm Gyprock
Aquachek Plasterboard.
Minimum Wall Thickness mm 219 231 243 275

CSR 1525
(a) 75 Acoustigard 14kg 63/50 63/50 63/50 64/52

60/60/60# BOTH SIDES (b) 110 Acoustigard 11kg 63/50 63/50 64/51 64/52
• 1 x 13mm Gyprock
WF 45743 Aquachek Plasterboard. (c) 88 Soundscreen 2.5 64/51 64/51 64/51 65/53

Minimum Wall Thickness mm 219 231 243 275

CSR 1530
SIDE ONE
(a) 75 Acoustigard 14kg 63/50 64/51 64/51 65/53
• 1 x 13mm Gyprock
60/60/60# Soundchek Plasterboard. (b) 110 Acoustigard 11kg 63/50 64/51 65/52 65/53

WF 45743 SIDE TWO (c) 88 Soundscreen 2.5 64/51 65/52 65/52 66/54
• 1 x 13mm Gyprock
Aquachek Plasterboard.
Minimum Wall Thickness mm 219 231 243 275

CSR 1535
(a) 75 Acoustigard 14kg 64/52 64/52 64/52 65/53

60/60/60# BOTH SIDES (b) 110 Acoustigard 11kg 64/52 64/52 65/53 65/53
• 1 x 13mm Gyprock
WF 45743 Soundchek Plasterboard. (c) 88 Soundscreen 2.5 65/53 65/53 65/53 66/54

Minimum Wall Thickness mm 219 231 243 275

CSR 1540
(a) 75 Acoustigard 14kg 65/53 65/53 66/54 66/54

60/60/60# BOTH SIDES (b) 110 Acoustigard 11kg 65/53 65/53 67/55 66/54
• 2 x 13mm Gyprock
WF 45743 Standard Plasterboard. (c) 88 Soundscreen 2.5 66/54 66/54 67/55 67/55

Minimum Wall Thickness mm 245 257 269 301

GYPROCK® THE RED BOOK™ 1 C41


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Party Wall

Lining material as per system table. Steel studs at 600mm maximum centres.

Steel studs at 600mm maximum centres. Gyprock aluminium wall clip

Gyprock aluminium wall clip Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in 20-40mm air gap.


H-studs at 600mm maximum centres.

20-40mm air gap.

NOTE: Acoustic performance valid for


20mm min. air gap each side.
#Wall height and clip spacings
restrictions apply, refer to page C7.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP513, Gyprock Party Wall Design Guide for further information Discontinuous Construction

STUD DEPTH mm 64 70 76 90/92


FRL SYSTEM STUD BMT mm 0.50 0.55 0.55 0.55
WALL LININGS
Report Nº
CAVITY INFILL BOTH SIDES Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 3312
(a) 75 Acoustigard 11kg 63/50 63/51 63/51 64/52

60/60/60# BOTH SIDES (b) 88 Soundscreen 2.5 65/52 65/53 65/53 66/54
• 1 x 13mm Gyprock EC08
WF 45743 Complete. (c) 110 Acoustigard 11kg 64/51 64/52 65/53 65/53

Minimum Wall Thickness mm 219 231 243 275

CSR 10014
(a) 75 Acoustigard 11kg 63/50 63/51 63/51 64/52

60/60/60# BOTH SIDES (b) 88 Soundscreen 2.5 65/52 65/53 65/53 66/54
• 1 x 13mm Gyprock EC08
WF 45743 Extreme. (c) 110 Acoustigard 11kg 64/51 64/52 65/53 65/53

Minimum Wall Thickness mm 219 231 243 275

CSR 3332
(a) 75 Acoustigard 11kg 63/51 64/52 64/52 65/53

60/60/60# BOTH SIDES (b) 88 Soundscreen 2.5 65/53 66/54 66/54 67/55
• 1 x 16mm Gyprock EC08
WF 45743 Complete. (c) 110 Acoustigard 11kg 64/52 65/53 66/54 66/54

Minimum Wall Thickness mm 225 237 249 281

C42 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – StrataWall

Lining material as per system table. Steel studs at 600mm maximum centres.

Steel studs at 600mm maximum centres. Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in Min. 20mm air gap.


H-studs at 600mm maximum centres.

Min. 20mm air gap.

NOTE: Acoustic performance valid for air


gap each side as noted
System wall height limited to the height of a
single Shaft Liner Panel

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP949, Gyprock StrataWall Design Guide for further information Discontinuous Construction

STUD DEPTH mm Min. 64 70 76 90/92


FRL SYSTEM STUD BMT mm Air 0.50 0.55 0.55 0.55
WALL LININGS
Report Nº Gap
CAVITY INFILL BOTH SIDES Rw / Rw+Ctr
(Refer to TABLE B6) (mm)
CSR 10250 20 61/48 62/49 62/49 63/51
(a) 75 Acoustigard 11kg
40 62/49 62/50 63/51 63/51
–/60/60 BOTH SIDES 20 62/49 63/50 64/51 64/52
(b) 110 Acoustigard 11kg
• 1 x 6mm CeminSeal 40 63/50 63/51 64/52 64/52
FAS 230119 Wallboard. (c) 88 Soundscreen 2.5 20 63/50 64/51 64/51 65/53
20 205 217 229 261
Minimum Wall Thickness mm
40 245 257 269 301
CSR 10251 20 61/47 62/48 62/49 62/50
(a) 75 Acoustigard 11kg
40 62/49 62/50 62/50 63/51
– /60/60 BOTH SIDES 20 62/48 62/49 64/51 63/51
(b) 110 Acoustigard 11kg
• 1 x 10mm Gyprock HD 40 63/50 63/51 63/51 64/52
FAS 230119 Plasterboard. (c) 88 Soundscreen 2.5 20 63/49 63/50 64/51 64/52
20 213 225 237 269
Minimum Wall Thickness mm
40 253 265 277 309
CSR 10252 20 62/49 62/49 62/49 63/51
SIDE ONE (a) 75 Acoustigard 11kg
40 63/50 63/51 63/51 64/52
• 2 x 10mm Gyprock Plus
–/60/60 Plasterboard. 20 63/50 63/50 64/51 64/52
(b) 110 Acoustigard 11kg
40 64/51 64/52 64/52 65/53
FAS 230119 SIDE TWO
(c) 88 Soundscreen 2.5 20 64/51 64/51 64/51 65/53
• 1 x 6mm CeminSeal
Wallboard. 20 219 231 243 275
Minimum Wall Thickness mm
40 259 271 283 315
CSR 10253 20 62/49 62/49 63/51 63/51
(a) 75 Acoustigard 11kg
40 63/51 63/51 64/52 64/52
– /60/60 BOTH SIDES 20 63/50 63/50 65/53 64/52
(b) 110 Acoustigard 11kg
• 2 x 10mm Gyprock Plus 40 64/52 64/52 65/53 65/53
FAS 230119 Plasterboard. (c) 88 Soundscreen 2.5 20 64/51 64/51 65/53 65/53
20 233 245 257 289
Minimum Wall Thickness mm
40 273 285 297 329
CSR 10254 20 63/51 64/52 64/52 65/53
(a) 75 Acoustigard 11kg
40 64/52 64/52 65/53 65/54
– /60/60 BOTH SIDES 20 64/52 65/53 66/54 66/54
(b) 110 Acoustigard 11kg
• 2 x 10mm Gyprock 40 65/53 65/53 65/54 66/55
FAS 230119 Aquachek Plasterboard. (c) 88 Soundscreen 2.5 20 65/53 66/54 66/54 67/55
20 233 245 257 289
Minimum Wall Thickness mm
40 273 285 297 329
CSR 10255 20 61/47 61/48 62/49 62/50
(a) 75 Acoustigard 11kg
40 62/49 62/50 62/50 63/51
– /60/60 BOTH SIDES 20 62/48 62/49 64/51 63/51
(b) 110 Acoustigard 11kg
• 1 x 13mm Gyprock 40 63/50 63/51 63/51 64/52
FAS 230119 Standard Plasterboard. (c) 88 Soundscreen 2.5 20 63/49 63/50 64/51 64/52
20 219 231 243 275
Minimum Wall Thickness mm
40 259 271 283 315

GYPROCK® THE RED BOOK™ 1 C43


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – StrataWall

Lining material as per system table. Steel studs at 600mm maximum centres.

Steel studs at 600mm maximum centres. Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in Min. 20mm air gap.


H-studs at 600mm maximum centres.

Min. 20mm air gap.

NOTE: Acoustic performance valid for air


gap each side as noted
System wall height limited to the height of a
single Shaft Liner Panel

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP949, Gyprock StrataWall Design Guide for further information Discontinuous Construction

STUD DEPTH mm Min. 64 70 76 90/92


FRL SYSTEM STUD BMT mm Air 0.50 0.55 0.55 0.55
WALL LININGS
Report Nº Gap
CAVITY INFILL BOTH SIDES Rw / Rw+Ctr
(Refer to TABLE B6) (mm)
CSR 10256 20 61/47 62/49 62/49 63/51
SIDE ONE (a) 75 Acoustigard 11kg
40 62/49 63/51 63/51 63/51
• 1 x 13mm Gyprock
– /60/60 Standard Plasterboard. 20 62/48 63/50 64/52 64/52
(b) 110 Acoustigard 11kg
40 63/50 64/52 64/52 64/52
FAS 230119 SIDE TWO
(c) 88 Soundscreen 2.5 20 63/49 64/51 64/51 65/53
• 1 x 13mm Gyprock
Aquachek Plasterboard. 20 219 231 243 275
Minimum Wall Thickness mm
40 259 271 283 315
CSR 10257 20 62/49 62/49 62/49 63/51
(a) 75 Acoustigard 11kg
40 63/51 63/51 63/51 64/52
– /60/60 BOTH SIDES 20 63/50 63/50 64/51 64/52
(b) 110 Acoustigard 11kg
• 1 x 13mm Gyprock 40 64/52 64/52 64/52 65/53
FAS 230119 Aquachek Plasterboard. (c) 88 Soundscreen 2.5 20 64/51 64/51 64/51 65/53
20 219 231 243 275
Minimum Wall Thickness mm
40 259 271 283 315
CSR 10258 20 62/49 63/50 63/50 64/52
SIDE ONE (a) 75 Acoustigard 11kg
40 63/51 64/52 64/52 64/52
• 1 x 13mm Gyprock
– /60/60 Soundchek Plasterboard. 20 63/50 64/51 65/52 65/53
(b) 110 Acoustigard 11kg
40 64/52 65/53 65/53 65/53
FAS 230119 SIDE TWO
(c) 88 Soundscreen 2.5 20 64/51 65/52 65/52 66/54
• 1 x 13mm Gyprock
Aquachek Plasterboard. 20 219 231 243 275
Minimum Wall Thickness mm
40 259 271 283 315
CSR 10259 20 63/51 63/51 63/51 64/52
(a) 75 Acoustigard 11kg
40 64/52 64/52 64/52 65/54
– /60/60 BOTH SIDES 20 64/52 64/52 65/53 65/53
(b) 110 Acoustigard 11kg
• 1 x 13mm Gyprock 40 65/53 65/53 65/53 66/55
FAS 230119 Soundchek Plasterboard. (c) 88 Soundscreen 2.5 20 65/53 65/53 65/53 66/54
20 219 231 243 275
Minimum Wall Thickness mm
40 259 271 283 315
CSR 10260 20 64/52 64/52 65/53 65/54
(a) 75 Acoustigard 11kg
40 65/53 65/53 65/54 66/55
– /60/60 BOTH SIDES 20 64/52 64/52 65/53 65/54
(b) 110 Acoustigard 11kg
• 2 x 13mm Gyprock 40 66/54 66/54 66/55 67/56
FAS 230119 Standard Plasterboard. (c) 88 Soundscreen 2.5 20 65/53 65/53 67/55 66/55
20 245 257 269 301
Minimum Wall Thickness mm
40 285 297 309 341

C44 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Frame Internal Wall Systems – Cinema Wall

Lining material as per system table. Top hat sections at 900mm maximum
centres to each side of girts to engineer’s
Steel columns to engineer’s design design.
(not shown).
2 x layers of glasswool or polyester
Girts fixed to columns with Gyprock insulation as per system table.
Cinema Wall Mounts.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A117 (Test ATF428 ➊)


Refer to GYP512, Gyprock Cinema Wall Installation Guide for further information Not Deemed Discontinuous Construction

FRL SYSTEM CAVITY INFILL


WALL LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)

CSR 1700 (a) 2 x 110 Glasswool Building Blanket 77/71➊

120/120/120 BOTH SIDES


• 3 x 16mm Gyprock (d) 2 x 100mm Absorb XHD Polyester 77/71
FC 12946 Fyrchek Plasterboard.

Minimum Wall Thickness mm 471

CSR 1710 (a) 2 x 110 Glasswool Building Blanket 79/73


SIDE ONE
• 3 x 16mm Gyprock
120/120/120 Fyrchek Plasterboard.
(d) 2 x 100mm Absorb XHD Polyester 79/73
FC 12946 SIDE TWO
• 4 x 16mm Gyprock
Fyrchek Plasterboard.
Minimum Wall Thickness mm 487

CSR 1720 (a) 2 x 110 Glasswool Building Blanket 81/75

120/120/120 BOTH SIDES


• 4 x 16mm Gyprock (d) 2 x 100mm Absorb XHD Polyester 81/75
FC 12946 Fyrchek Plasterboard.

Minimum Wall Thickness mm 503

GYPROCK® THE RED BOOK™ 1 C45


SYSTEM SPECIFICATIONS Steel Column Systems with I-Beam/Universal Beam or RHS

Steel Angle fixed to soffit


Gyprock Universal Encasement
Clips and/or Rondo Wall Track
fixed to steel column
External Angle Bead to all
corners and plaster set

Lining material as per NOTE: FRL shall be determined based on


system table fixed to calculation method in accordance with
framing AS4100:2020, refer to table C1.
#
indicative image does not represent the
system configuration.

SYSTEM SPECIFICATION
Refer to Book 3 Commercial & Multi-Residential Installation Guide

SYSTEM PLASTERBOARD
FRL PROTECTION STEEL SECTION
Nº LININGS

CSR 10095

• 1 x 13mm Gyprock Fyrchek


plasterboard.

CSR 10096

• 2 x 13mm Gyprock Fyrchek


plasterboard.

Hollow section
CSR 10400 • CHS
• RHS
• 1 x 13mm Gyprock Fyrchek
plasterboard. • SHS
• 1 x 16mm Gyprock Fyrchek
plasterboard. (any order) I-section
Refer to • UB
TABLE C4 2,3 or 4 sides • UC
CSR 10097
FC 16125 • WB
• WC
• 2 x 16mm Gyprock Fyrchek
plasterboard. C-section
• PFC

CSR 10098 Refer to TABLE C1

• 3 x 13mm Gyprock Fyrchek


plasterboard.

CSR 10401

• 3 x 16mm Gyprock Fyrchek


plasterboard.

C46 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Steel Beam Systems with I-Beam/Universal Beam or RHS

Noggings at each end of the


beam and behind plasterboard
Steel RHS Beam or
Universal Beam butt joints in single layer systems

Rondo steel track fixed to


RHS beam Lining material as per system
or table fixed to steel track
Track held by Rondo
Universal Encasement
Clip with Universal Beam
NOTE: FRL shall be determined based on
calculation method in accordance with
AS4100:2020, refer to table C1.
#
indicative image does not represent the
system configuration.

SYSTEM SPECIFICATION
Refer to Book 3 Commercial & Multi-Residential Installation Guide

FRL SYSTEM PLASTERBOARD


PROTECTION STEEL SECTION
Report Nº LININGS

CSR 10099

• 1 x 13mm Gyprock Fyrchek


plasterboard.

CSR 10100

• 2 x 13mm Gyprock Fyrchek


plasterboard.

Hollow section
CSR 10402 • CHS
• RHS
• 1 x 13mm Gyprock Fyrchek
plasterboard. • SHS
• 1 x 16mm Gyprock Fyrchek
plasterboard. (any order) I-section
Refer to • UB
TABLE C4 2,3 or 4 sides • UC
CSR 10101
FC 16125 • WB
• WC
• 2 x 16mm Gyprock Fyrchek
plasterboard. C-section
• PFC

CSR 10102 Refer to TABLE C1

• 3 x 13mm Gyprock Fyrchek


plasterboard.

CSR 10403

• 3 x 16mm Gyprock Fyrchek


plasterboard.

GYPROCK® THE RED BOOK™ 1 C47


SYSTEM SPECIFICATIONS Steel Column Systems with I-Beam/Universal Beam or RHS

30mm Gyprock Glasroc F


Steel column as as per system table
per system table

Steel angle fixed


to steel column

NOTE: FRL shall be determined based on


calculation method in accordance with
AS4100:2020, refer to table C1.
#
indicative image does not represent the
system configuration.

SYSTEM SPECIFICATION
Refer to Book 3 Commercial & Multi-Residential Installation Guide

FRL SYSTEM PLASTERBOARD


PROTECTION STEEL SECTION
Report Nº LININGS

CSR 10103 • RHS


• SHS
Refer to • CHS
TABLE C2 • 30mm Gyprock Glasroc F. 3 or 4 sides • PFC
FAR 4876 • I Section (i.e. UB, UC,WB,
WC)
Refer to TABLE C1

SYSTEM SPECIFICATIONS Steel Beam Systems with I-Beam/Universal Beam or RHS

Steel Beam as per


system table

Steel angle fixed


to RHS beam 30mm Gyprock Glasroc F
as per system table

NOTE: FRL shall be determined based on


calculation method in accordance with
AS4100:2020, refer to table C1.
#
indicative image does not represent the
system configuration.

SYSTEM SPECIFICATION
Refer to Book 3 Commercial & Multi-Residential Installation Guide

FRL SYSTEM PLASTERBOARD


PROTECTION STEEL SECTION
Report Nº LININGS

CSR 10104 • RHS


• SHS
Refer to • CHS
TABLE C3 • 30mm Gyprock Glasroc F. 3 or 4 sides • PFC
FAR 4876 • I Section (i.e. UB, UC,WB,
WC)
Refer to TABLE C1

C48 GYPROCK® THE RED BOOK™ 1


TIMBER FRAMED
WALL SYSTEMS
D
SECTION CONTENTS
Introduction D2
Design Considerations D2
Installation D4
System Selection Tables

Single Stud D6

Resilient Mount D12

Staggered Stud D15

Double Stud D20

Party Wall D25

GYPROCK® THE RED BOOK™ 1 D1


INTRODUCTION STRUCTURAL DESIGN
All walls must be designed for the applied loads. For
This section provides important design loadbearing walls and walls subject to wind pressures,
information and detailed selection tables walls shall be designed to the appropriate Australian
necessary for the correct use of CSR timber Standards or construction manuals.
frame wall systems.
Seismic Loads
CSR Gyprock & Cemintel timber frame wall systems
Seismic actions must be considered for building elements
are assemblies constructed from timber components
in accordance with the NCC. The loads and effects of
with one or more layers of Gyprock plasterboard and/or
earthquakes may be determined in accordance with AS
Cemintel linings fixed to one or both sides.
1170.4 ‘Earthquake Actions in Australia’. The Standard
Timber frame wall systems are typically used in single has design procedures for houses (Class 1), and to
dwellings and multi-residential applications. buildings (Classes 2 to 9) with importance levels 2, 3 or 4
A wide range of systems are available including fire rated as defined in the NCC.
walls for non-loadbearing and loadbearing applications,
as well as acoustic walls and party wall applications. Non-Loadbearing Walls
For external timber framed walls, refer to Section F It is recommended that non-loadbearing walls are
External Wall Systems in this guide. designed for a minimum design pressure of 0.25kPa and a
This Design Guide should be read in conjunction with maximum deflection of (height ÷ 240) or 30mm maximum.
the relevant Gyprock Installation Guide, available from (Based on NCC2022 Clause S6C6(b) [NCC2019: Spec
www.gyprock.com.au. C1.8: 3.4(b)]).

Loadbearing Walls
DESIGN Walls designed as loadbearing, with studs at 600mm
CONSIDERATIONS maximum centres and lined with Gyprock Fyrchek, meet
the requirements of NCC2022 Clause S6C6 [NCC2019:
Spec C1.8: 3.4] – Walls generally.
DESIGNER RESPONSIBILITY The building designer must ensure loadbearing walls have
It remains the responsibility of the customer (in conjunction been designed:
with their designer or engineer, when applicable) to ensure • To resist all applied loads.
that CSR’s products/systems are suitable for their chosen
• To be in accordance with AS 1720.1 or AS 1684 Series.
application for any given project. CSR recommends
that a comprehensive assessment of the performance • Assuming no contribution to axial strength is required
requirements be undertaken prior to selection, including of the wall linings.
in respect of project-specific matters such as, but
not limited structural adequacy, seismic, acoustic, fire Wind Loads
resistance/combustibility, thermal, condensation and
All linings and framing are to be designed for the
weatherproofing requirements.
appropriate wind loads. Contact CSR for loads higher
CSR offers online digital tools for the most updated than stated in this manual.
information, including but not limited to update of
Buildings often have exterior operable doors and
products/components, inclusion of new and modified
windows, resulting in internal walls being subject to wind
systems, to meet the requirements of the National
pressure. In these cases, walls must be designed for
Construction Code of Australia (NCC) and any relevant
the appropriate loads in accordance to AS4055 or AS/
Australian Standards.
NZS1170.2.
For the most up-to-date product & system performance
Refer to framing selection information in Section B, TABLE
information, visit:
B12 and TABLE B13 for maximum framing centres.
CSR System Selector: https://apps.csr.com.au/
systemselector/search-option
CSR Thermal Calculator: https://apps.csr.com.au/
thermalcalculator

D2 GYPROCK® THE RED BOOK™ 1


CONTROL JOINTS Framing & Lining
Control joints must be installed to allow for structural Timber stud walls required to have an FRL must comply
movement. Allowance for movement must be made with the following:
through the frame, lining and any tiles. • Studs must be minimum 70 x 35mm and spaced at
Vertical control joints in stud walls are to be constructed 600mm maximum centres, with minimum loads in
using two studs with a 15-20mm gap between. accordance with NCC2022 Specification 6 [NCC2019:
Spec C1.8].
Door frames extending from floor to ceiling constitute
control joints. For doors less than ceiling height, a control • Fire walls in Class 2 to 9 buildings and Class 1a
joint extending from one corner of the frame may be used. buildings outside the scope of AS4055 (over 8.5m
high) require wall plates be fixed to fire rated supporting
Control joints must be installed at all construction joints in
structure, using engineered steel fasteners to timber
the building and at the following locations:
or steel supporting elements and AS5216 compliant
• Non-tiled internal walls with plasterboard outer layer – anchors to concrete elements.
at 12m maximum centres.
• In wet areas, Gyprock Fyrchek MR (or other approved
• Non-tiled internal walls with fibre cement outer layer – Gyprock moisture grade and fire resistant plasterboard)
at 7.2m maximum centres. should be used in lieu of Gyprock Fyrchek.
• Tiled internal walls – at 4.8m maximum centres. • Joints in the outer layer of all systems lined with
• Horizontal control joint at internal mid-floor position. plasterboard or Wallboard must be set with Gyprock
paper tape. As a minimum, a single coat finish may be
• At junctions with other building elements. used.
• At changes of lining material. For additional information on frame design and detailing,
• At changes of structural support systems. including treatment at junctions, sub floor and roof areas,
cavity barriers and penetrations, refer to Forest and Wood
• At each storey or rise of studs. Products publication Timber Framed Construction for
Refer to the relevant installation guides for appropriate Multi-Residential Buildings.
details.
ACCEPTABLE VARIATIONS TO
FIRE RESISTANCE
FIRE SYSTEMS
The timber frame wall systems in this manual are suitable
for the stated FRL when designed in accordance with the The Fire Resistance Level (FRL) of the systems detailed in
structural considerations above. Wall system ratings apply this section will not be detrimentally affected by;
in either direction unless noted otherwise. • Increasing the thickness of the wall.
To protect structural beams and columns within a wall, • Increasing the cross-sectional dimensions of the
the FRL of the wall system must be at least equivalent to framing elements.
that required by the structural member. For example, a
• Decreasing the stud spacing.
wall system with FRL 90/90/90 provides FRL 90/–/– for
a timber column within the wall. • Decreasing the fixing centres of wall sheet materials.
The fire design of timber framing is based on the principle • The inclusion of bulk cavity insulation materials such as
that a level of char is acceptable without compromising glasswool, rockwool and polyester.
the performance of the wall. CSR has carried out testing
• The use of Fyrchek MR, Impactchek, the EC08 range
to verify the char limit, and where it is exceeded, the
of plasterboards in lieu of Fyrchek plasterboard of the
allowable axial capacity of the stud is reduced to account
same thickness.
for the loss of section. The systems are noted with an
Axial Capacity Reduction (ACR) Group number in TABLE • Additional layers of plasterboard or fibre cement.
D1. In these systems, the designer must increase the • Curved walls (in plan) with a radius of curvature no less
applied vertical loads by the ACR to compensate for the than 3m.
axial capacity reduction.
• The attachment of light weight fixtures through to the
framing.
TABLE D1: AXIAL CAPACITY REDUCTION (%) DUE TO
THE EFFECT OF TIMBER CHAR • The use of Shaft Liner Panel MP in lieu of Shaft Liner
Timber Size Group 1 Group 2 Group 3 Panel.
90 x 45 0% 0% 25%
90 x 35 0% 10% 30% • The addition of steel or timber sheeting against the stud
70 x 45 3% 25% 40% and behind the lining.
70 x 35 8% 35% 45%

GYPROCK® THE RED BOOK™ 1 D3


Perimeters & Penetrations
INSTALLATION
All perimeters, control joints and penetrations must be
treated appropriately to maintain the fire rating. Treatment
may include caulking with approved fire rated sealants, or FRAMING
by the use of fire collars, dampers, etc, to an approved Timber sizes indicated are nominal. For kiln-dried
detail. timber, protect frames from wetting prior to and during
construction by wrapping exposed sections as soon
COMBUSTIBILITY as practicable after erection. The timber should have a
Polyester insulation may NOT be selected where the system maximum of 15% moisture content at the time of lining.
has non-combustible construction requirements.
Accurate setting-out is required where 35mm wide
In accordance with NCC2022 Clause C2D10 [NCC2019: framing is used as the narrower member width is less
C1.9], plasterboard and fibre cement sheet may be used able to accommodate misalignment.
wherever a non-combustible material is required by the Code.
For detailed information on non-fire rated timber wall
junctions, intersections, frame attachments and curved
ACOUSTIC PERFORMANCE walls refer to Book 2 Residential Installation Guide.
The acoustic performance of wall systems is expressed For detailed information on fire rated wall junctions,
in terms of R w and R w +C tr where appropriate. The intersections, frame attachments and curved walls, refer
performance of the as-built system may be affected by: to Forest and Wood Products publication Timber Framed
sound flanking, the effectiveness of workmanship and Construction for Multi-Residential Buildings.
caulking, the presence and treatment of penetrations,
and the inclusion of structural elements and bridging
items. Refer to appropriate information on addressing PLASTERBOARD & WALLBOARD
these issues detailed in Section B, Products & Design and FIXING
Section J, Flanking Path Systems in this guide.
Interior walls may be built to achieve a particular ‘Level
General Notes of Finish’ as defined in AS/NZS 2589. The Level of Finish
• The acoustic performance of systems may be specified can have requirements for frame alignment,
adversely affected by the use of wider studs or closer jointing and back blocking methods, and sheet orientation.
stud spacings than that specified. CeminSeal Wallboard and Gyprock plasterboard may be
installed vertically or horizontally, although for some Levels
• In non-fire rated systems, to attain the stated acoustic of Finish, horizontal sheeting must be used.
performance, use Gyprock Wet Area Acrylic Sealant,
Gyprock Fire Mastic, CSR FireSeal or other tested Interior walls lined with Gyprock plasterboard or
acoustic rated material of equivalent or better CeminSeal Wallboard may be finished with tiles. Sheets
performance. used as a substrate for tiles must be fastener fixed only.
Adhesive/fastener fixing is not acceptable.
The acoustic performance of CSR wall systems is not
adversely affected by changing the order of lining sheets
that are fixed direct to framing.

D4 GYPROCK® THE RED BOOK™ 1


GYPROCK PARTY WALL SYSTEMS FIG D1: GYPROCK PARTY WALL HIGHT LIMITATIONS

Gyprock Party Wall comprises a double frame wall with a


25mm Shaft Liner central fire barrier between the frames.
The basis of the fire performance is the central fire barrier
that provides the primary fire resistance, with the frame
lining (or cavity insulations) on each side contributing to
Floor
some extent. This allows the wall linings to be installed ceiling
Clip to J-track zone
as for normal decorative linings, and to incorporate 600mm max.
penetrations.
The basis of the acoustic performance is the double Floor
cavity system that provides effective sound transmission ceiling
zone
performance, as well as impact isolation. Insulation in
both cavities is used to deliver a range of performance
levels, including allowance for certain penetrations and
services that may occur.
TABLE D2 and TABLE D3 provides the overall wall height ‘H’

and lateral support (clip spacing) limitations for stud


frames lined with plasterboard or fibre cement linings.
The targeted FRL in the system table has considered the
stated overall wall height and lateral support (clip spacing) ‘H’

limitations determined in accordance with AS1530.4.

TABLE D2: Party Wall lateral support (clip spacing)


locations for plasterboard linings on both sides
Floor
Overall Wall Height ‘H’ Clip to J-track ceiling
600mm max. zone
Up to 14m Max. 2.6m
Up to 12m Max. 2.8m
Up to 10.8m Max. 3.0m Floor
ceiling
Up to 9m Max. 3.4m zone

TABLE D3: Party Wall lateral support (clip spacing)


locations for fibre cement linings on one side or both sides
Overall Wall Height ‘H’
Up to 7m Max. 2.6m
‘H’
Up to 6m Max. 2.8m
Up to 5m Max. 3.0m

‘H’

GYPROCK® THE RED BOOK™ 1 D5


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Timber studs at 600mm maximum Lining material as per system table.


centres.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM OPTIONS ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2000 (a) Nil 33/26 34/27 36/29 37/30

(c) 70 Soundscreen 2.0 39/30 40/31 42/33 42/33


BOTH SIDES
–/–/– • 1 x 6mm CeminSeal (e) 75 Gold Batts R2.0 38/29 39/30 41/42 42/33
Wallboard.
(f) 50 MAB Polyester 11kg 36/28 37/29 39/31 39/31

Wall Thickness mm 82 102 132 152


CSR 2007 (a) Nil 31/24 33/26 35/28 36/29
SIDE ONE
• 1 x 6mm CeminSeal (c) 70 Soundscreen 2.0 37/28 39/30 41/32 41/32
Wallboard.
–/–/– (e) 75 Gold Batts R2.0 36/27 38/29 40/31 41/32
SIDE TWO
• 1 x 10mm Gyprock (f) 50 MAB Polyester 11kg 34/26 36/28 38/30 38/30
Aquachek Plasterboard.
Wall Thickness mm 86 106 136 156
CSR 2009
(a) Nil 27/19 28/21 31/24 31/24

BOTH SIDES (c) 70 Soundscreen 2.0 33/23 34/25 37/28 36/27


–/–/– • 1 x 10mm Gyprock Plus
Plasterboard. (e) 75 Gold Batts R2.0 32/22 33/24 36/27 36/27

Wall Thickness mm 90 110 140 160

CSR 2011 (a) Nil 28/20 30/23 32/25 32/25


SIDE ONE
• 1 x 10mm Gyprock Plus (c) 70 Soundscreen 2.0 34/24 36/27 38/29 37/28
Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 33/23 35/26 37/28 37/28
SIDE TWO
• 1 x 10mm Gyprock (f) 50 MAB Polyester 11kg 31/22 33/25 35/27 34/26
Aquachek Plasterboard.
Wall Thickness mm 90 110 140 160
CSR 2017 (a) Nil 29/22 32/25 33/26 35/28

(c) 70 Soundscreen 2.0 35/26 38/29 39/30 40/31


BOTH SIDES
–/–/– • 1 x 10mm Gyprock (e) 75 Gold Batts R2.0 34/25 37/28 38/29 40/31
Aquachek Plasterboard.
(f) 50 MAB Polyester 11kg 32/24 35/27 36/28 37/29

Wall Thickness mm 90 110 140 160


CSR 10145 (a) Nil 30/23 32/25 35/28 35/28
SIDE ONE
• 1 x 10mm Gyprock (b) 70 Soundscreen 2.0 36/27 38/29 41/32 40/31
Aquachek Plasterboard.
–/–/– (c) 50 MAB Polyester 11kg 33/25 36/28 38/30 38/30
SIDE TWO
• 1 x 10mm Gyprock HD (d) 75 Gold Batts R2.0 35/26 37/28 40/31 40/31
Plasterboard.
Wall Thickness mm 90 110 140 160

D6 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Timber studs at 600mm maximum Lining material as per system table.


centres.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM OPTIONS ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10146 (a) Nil 32/25 33/26 35/28 36/29

(b) 70 Soundscreen 2.0 38/29 39/30 41/32 41/32


BOTH SIDES
–/–/– • 1 x 10mm Gyprock HD (c) 50 MAB Polyester 11kg 35/27 36/28 38/30 38/30
Plasterboard.
(d) 75 Gold Batts R2.0 37/28 38/29 40/31 41/32

Wall Thickness mm 90 110 140 160


CSR 2026 (a) Nil 34/27 36/29 38/31 39/33

(c) 70 Soundscreen 2.0 40/31 42/33 44/35 44/36


BOTH SIDES
–/–/– • 2 x 10mm Gyprock Plus (e) 75 Gold Batts R2.0 39/30 41/32 43/34 44/36
Plasterboard.
(f) 50 MAB Polyester 11kg 37/29 39/31 41/33 41/34

Wall Thickness mm 110 130 160 180


CSR 10147 (a) Nil 39/32 41/35 42/36 43/37

(b) 70 Soundscreen 2.0 45/36 47/39 48/40 48/40


BOTH SIDES
–/–/– • 2 x 10mm Gyprock HD (c) 50 MAB Polyester 11kg 42/34 42/37 45/38 45/38
Plasterboard.
(d) 75 Gold Batts R2.0 44/35 46/38 47/39 48/40

Wall Thickness mm 110 130 160 180


CSR 2040 (a) Nil 32/25 33/26 36/29 36/29
SIDE ONE
• 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 38/29 39/30 42/33 41/32
Standard Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 37/28 38/29 41/32 41/32
SIDE TWO
• 1 x 6mm CeminSeal (f) 50 MAB Polyester 11kg 35/27 36/28 39/31 38/30
Wallboard.
Wall Thickness mm 89 109 139 159
CSR 2042
SIDE ONE
(a) Nil 34/27 36/29 38/31 38/31
• 1 x 13mm Gyprock
Standard Plasterboard. (c) 70 Soundscreen 2.0 40/31 42/33 44/35 43/34
–/–/–
SIDE TWO (e) 75 Gold Batts R2.0 39/30 41/32 43/34 43/34
• 1 x 9mm CeminSeal
Wallboard.
Wall Thickness mm 92 112 142 162

CSR 2045
(a) Nil 32/25 33/26 35/28 36/29

BOTH SIDES (c) 70 Soundscreen 2.0 38/29 39/30 41/32 41/32


–/–/– • 1 x 13mm Gyprock
Standard Plasterboard. (e) 75 Gold Batts R2.0 37/28 38/29 40/31 41/32

Wall Thickness mm 96 116 146 166

GYPROCK® THE RED BOOK™ 1 D7


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Timber studs at 600mm maximum Lining material as per system table.


centres.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM OPTIONS ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2047 (a) Nil 33/26 34/27 36/29 37/30
SIDE ONE
• 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 39/30 40/31 42/33 42/33
Standard Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 38/29 39/30 41/32 42/33
SIDE TWO
• 1 x 13mm Gyprock (f) 50 MAB Polyester 11kg 36/28 37/29 39/31 39/31
Aquachek Plasterboard.
Wall Thickness mm 96 116 146 166
CSR 2049
SIDE ONE
(a) Nil 33/26 34/27 36/29 37/30
• 1 x 13mm Gyprock
Impactchek Plasterboard. (c) 70 Soundscreen 2.0 39/30 40/31 42/33 42/33
–/–/–
SIDE TWO (e) 75 Gold Batts R2.0 38/29 39/30 41/32 42/33
• 1 x 13mm Gyprock
Standard Plasterboard.
Wall Thickness mm 96 116 146 166

CSR 2053 (a) Nil 33/26 34/27 37/30 37/30

(c) 70 Soundscreen 2.0 39/30 40/31 43/34 42/33


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 38/29 39/30 42/33 42/33
Aquachek Plasterboard.
(f) 50 MAB Polyester 11kg 36/28 37/29 40/32 39/31

Wall Thickness mm 96 116 146 166


CSR 2055 (a) Nil 36/29 37/30 39/33 40/34

(c) 70 Soundscreen 2.0 42/33 43/34 45/37 45/37


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (d) Polymax 2.0 42/33 43/34 45/37 46/38
Soundchek Plasterboard.
(e) 75 Gold Batts R2.0 41/32 42/33 44/36 45/37

Wall Thickness mm 96 116 146 166


CSR 2059 (a) Nil 39/32 41/35 42/36 43/37

(c) 70 Soundscreen 2.0 45/36 47/39 48/40 48/40


BOTH SIDES
–/–/– • 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 44/37 46/38 47/39 48/40
Standard Plasterboard.
(f) 50 MAB Polyester 11kg 42/34 44/37 45/38 45/38

Wall Thickness mm 122 142 172 192

D8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Timber studs at 600mm maximum Lining material as per system table.


centres.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM OPTIONS ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2060 (a) Nil 34/27 36/29 37/30 38/32
– /60/60 (c) 70 Soundscreen 2.0 40/31 42/33 43/34 43/35
30/30/30 BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 39/30 41/32 42/33 43/35
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 37/29 39/31 40/32 40/33

Wall Thickness mm 96 116 146 166


CSR 2061 (a) Nil 34/27 36/29 37/30 39/33
SIDE ONE
– /60/60 • 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 40/31 42/33 43/34 44/36
30/30/30 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 39/30 41/32 42/33 44/36
SIDE TWO
FC 12969 • 1 x 13mm Gyprock (f) 50 MAB Polyester 11kg 37/29 39/31 40/32 41/34
Fyrchek Plasterboard.
Wall Thickness mm 96 116 146 166
CSR 2062 (a) Nil 34/27 36/29 37/30 39/33
– /60/60 (c) 70 Soundscreen 2.0 40/31 42/33 43/34 44/36
30/30/30 BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 39/30 41/32 42/33 44/36
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 37/29 39/31 40/32 41/34

Wall Thickness mm 96 116 146 166

CSR 2065 SIDE ONE (ANY ORDER) (a) Nil 36/29 38/31 40/33 41/35
• 1 x 10mm Gyprock Plus
– /60/60 Plasterboard. (c) 70 Soundscreen 2.0 42/33 44/35 46/37 46/38
30/30/30 • 1 x 13mm Gyprock
Fyrchek Plasterboard. (e) 75 Gold Batts R2.0 41/32 42/33 44/36 45/37

FC 12969 SIDE TWO (f) 50 MAB Polyester 11kg 39/31 41/33 43/35 43/36
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness mm 106 126 156 176
CSR 2067 (a) Nil 40/33 42/36 44/38 44/38
– /60/60 BOTH SIDES
(c) 70 Soundscreen 2.0 46/37 48/40 50/42 49/41
• 1 x 6mm CeminSeal
60/60/60
Wallboard (against studs). (e) 75 Gold Batts R2.0 45/36 47/39 49/41 49/41
• 1 x 13mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 43/35 45/38 47/40 46/39
Fyrchek Plasterboard.
Wall Thickness mm 108 128 158 178

GYPROCK® THE RED BOOK™ 1 D9


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Timber studs at 600mm maximum Lining material as per system table.


centres.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.
*ACR = Axial Capacity Reduction.

SYSTEM OPTIONS ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2070 (a) Nil 33/26 36/29 38/32 38/32
– /60/60 (c) 70 Soundscreen 2.0 39/30 42/33 44/36 43/35
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 38/29 41/32 42/35 43/35
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 36/28 39/31 41/34 40/33

Wall Thickness mm 102 122 152 172


CSR 2071 (a) Nil 35/28 37/30 39/33 40/34
SIDE ONE
– /60/60 • 1 x 16mm Gyprock (c) 70 Soundscreen 2.0 41/32 43/34 45/37 45/37
60/60/60 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 40/31 42/33 44/36 45/37
SIDE TWO
FC 12969 • 1 x 16mm Gyprock (f) 50 MAB Polyester 11kg 38/30 40/32 42/35 42/35
Fyrchek Plasterboard.
Wall Thickness mm 102 122 152 172
CSR 2072 (a) Nil 37/30 38/31 40/34 41/35
– /60/60 (c) 70 Soundscreen 2.0 43/34 44/35 46/38 46/38
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 42/33 43/34 45/37 46/38
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 40/32 41/33 43/36 43/36

Wall Thickness mm 102 122 152 172


CSR 2075 SIDE ONE (a) Nil 38/31 40/33 41/35 42/36
• 1 x 16mm Gyprock
– /90/90 Fyrchek Plasterboard. (c) 70 Soundscreen 2.0 44/35 46/37 47/39 47/39
60/60/60
SIDE TWO (e) 75 Gold Batts R2.0 43/34 45/36 46/38 47/38
• 2 x 16mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 41/33 43/35 44/37 44/37
Fyrchek Plasterboard.
Wall Thickness mm 118 138 168 188
CSR 2080 (a) Nil 42/36 43/37 44/38 45/39
– /90/90 BOTH SIDES
(c) 70 Soundscreen 2.0 48/40 49/41 50/42 50/42
• 1 x 6mm CeminSeal
90/90/90*
*ACR Group 3 Wallboard (against studs). (e) 75 Gold Batts R2.0 47/39 48/40 49/41 50/42
• 1 x 16mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 45/38 46/39 47/40 47/40
Fyrchek Plasterboard.
Wall Thickness mm 114 134 164 184

D10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud

Lining material as per system table. Cavity insulation as per system table.

Timber studs at 600mm maximum Lining material as per system table.


centres.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM OPTIONS ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2090 (a) Nil 41/35 43/37 44/38 45/39
– /120/120 (c) 70 Soundscreen 2.0 47/39 49/41 50/42 50/42
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 46/38 48/40 49/41 50/42
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 44/37 46/39 47/40 47/40

Wall Thickness mm 122 142 172 192


CSR 2091 (a) Nil 42/36 43/37 44/38 45/39
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 70 Soundscreen 2.0 48/40 49/41 50/42 50/42
90/90/90 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 47/39 48/40 49/41 50/42
SIDE TWO
FC 12969 • 2 x 13mm Gyprock (f) 50 MAB Polyester 11kg 45/38 46/39 47/40 47/40
Fyrchek Plasterboard.
Wall Thickness mm 122 142 172 192
CSR 2092 (a) Nil 42/36 43/37 45/39 45/39
– /120/120 (c) 70 Soundscreen 2.0 48/40 49/41 51/43 50/42
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 47/39 48/40 50/42 50/42
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 45/38 46/39 48/41 47/40

Wall Thickness mm 122 142 172 192


CSR 2095 (a) Nil 41/35 43/37 44/38 44/38
– /120/120 (c) 70 Soundscreen 2.0 47/39 49/41 50/42 49/41
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 46/38 48/40 49/41 49/41
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 44/37 46/39 47/40 46/39

Wall Thickness mm 134 154 184 204


CSR 2096 (a) Nil 43/37 44/38 45/39 46/40
SIDE ONE
– /120/120 • 2 x 16mm Gyprock (c) 70 Soundscreen 2.0 49/41 50/42 51/43 51/43
120/120/120 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 48/40 49/41 50/42 51/43
SIDE TWO
FC 12969 • 2 x 16mm Gyprock (f) 50 MAB Polyester 11kg 46/39 47/40 48/41 48/41
Fyrchek Plasterboard.
Wall Thickness mm 134 154 184 204
CSR 2097 (a) Nil 44/38 45/39 46/40 47/41
– /120/120 (c) 70 Soundscreen 2.0 50/42 51/43 52/44 52/44
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 49/41 50/42 51/43 52/44
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 47/40 48/41 49/42 49/42

Wall Thickness mm 134 154 184 204

GYPROCK® THE RED BOOK™ 1 D11


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud with Resilient Mount

Side one – Lining material to Rondo Nº308 or Nº129 Furring Channel


furring side as per system table. clipped to resilient mounts.

Timber studs at 600mm maximum Cavity insulation as per system table.


centres.
Side two – Lining material as
Gyprock Resilient Mounts screw fixed to per system table.
one side of studs.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10148 (a) Nil 43/36 44/37 46/39 47/41
SIDE ONE
• 2 x 10mm Gyprock HD (b) 70 Soundscreen 2.0 53/43 54/44 55/45 56/47
Plasterboard.
–/–/– (c) 50 MAB Polyester 11kg 47/39 48/40 49/41 50/43
SIDE TWO
• 1 x 6mm CeminSeal (d) 75 Gold Batts R2.0 51/42 52/43 54/45 54/46
Wallboard.
Minimum Wall Thickness mm 124 144 174 194
CSR 2110 (a) Nil 41/34 42/35 43/36 45/38
SIDE ONE
• 2 x 10mm Gyprock (c) 70 Soundscreen 2.0 51/41 52/42 52/42 54/44
Aquachek Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 49/40 50/41 51/42 52/43
SIDE TWO
• 1 x 10mm Gyprock (f) 50 MAB Polyester 11kg 45/37 46/38 46/38 48/40
Aquachek Plasterboard.
Minimum Wall Thickness mm 128 148 178 198
CSR 10149 (a) Nil 43/36 43/36 45/38 46/39
SIDE ONE
• 2 x 10mm Gyprock HD (b) 70 Soundscreen 2.0 53/43 53/43 54/44 55/45
Plasterboard.
–/–/– (c) 50 MAB Polyester 11kg 4739 47/39 48/40 49/41
SIDE TWO
• 1 x 10mm Gyprock (d) 75 Gold Batts R2.0 51/42 51/42 53/44 53/44
Aquachek Plasterboard.
Minimum Wall Thickness mm 128 148 178 198
CSR 10150 (a) Nil 43/36 43/36 45/38 46/39
SIDE ONE
• 2 x 10mm Gyprock HD (b) 70 Soundscreen 2.0 53/43 53/43 54/44 55/45
Plasterboard.
–/–/– (c) 50 MAB Polyester 11kg 47/39 48/40 49/41 49/41
SIDE TWO
• 1 x 10mm Gyprock HD (d) 75 Gold Batts R2.0 51/42 51/42 53/44 53/44
Plasterboard.
Minimum Wall Thickness mm 128 148 178 198
CSR 2130 (a) Nil 42/35 43/36 45/38 45/39
SIDE ONE
• 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 52/42 53/43 54/44 54/45
Soundchek Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 50/41 51/42 53/44 52/44
SIDE TWO
• 1 x 6mm CeminSeal (f) 50 MAB Polyester 11kg 46/38 47/39 48/40 48/41
Wallboard.
Minimum Wall Thickness mm 117 137 167 187

D12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud with Resilient Mount

Side one – Lining material to Rondo Nº308 or Nº129 Furring Channel


furring side as per system table. clipped to resilient mounts.

Timber studs at 600mm maximum Cavity insulation as per system table.


centres.
Side two – Lining material as
Gyprock Resilient Mounts screw fixed to per system table.
one side of studs.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2135 (a) Nil 42/35 44/38 45/39 46/40

(c) 70 Soundscreen 2.0 52/42 54/45 54/45 55/46


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 50/41 52/44 53/45 53/45
Soundchek Plasterboard.
(f) 50 MAB Polyester 11kg 46/38 48/41 48/41 49/42

Minimum Wall Thickness mm 124 144 174 194


CSR 2150 (a) Nil 41/34 43/37 44/38 44/38
– /60/60 (c) 70 Soundscreen 2.0 51/41 53/44 53/44 53/44
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 49/40 51/43 52/44 51/43
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 45/37 47/40 47/40 47/40

Minimum Wall Thickness mm 130 150 180 200


CSR 2151 (a) Nil 42/35 44/38 45/39 45/39
SIDE ONE
– /60/60 • 1 x 16mm Gyprock (c) 70 Soundscreen 2.0 52/42 54/45 54/45 54/45
60/60/60 Fyrchek Plasterboard.
(e) 75 Gold Batts R2.0 50/41 52/44 53/45 52/44
SIDE TWO
FC 12969 • 1 x 16mm Gyprock (f) 50 MAB Polyester 11kg 46/38 48/41 48/41 48/41
Fyrchek MR Plasterboard.
Minimum Wall Thickness mm 130 150 180 200
CSR 2152 (a) Nil 43/36 45/39 46/40 46/40
– /60/60 (c) 70 Soundscreen 2.0 53/43 55/46 55/46 55/46
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 51/42 53/45 54/46 53/45
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 47/39 49/42 49/42 49/42

Minimum Wall Thickness mm 130 150 180 200


CSR 2160 (a) Nil 48/42 49/43 50/44 51/45
– /120/120 (c) 70 Soundscreen 2.0 58/49 59/50 59/50 60/51
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 56/48 57/49 58/50 58/50
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 52/45 53/46 53/46 54/47

Minimum Wall Thickness mm 150 170 200 220

GYPROCK® THE RED BOOK™ 1 D13


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Single Stud with Resilient Mount

Side one – Lining material to Rondo Nº308 or Nº129 Furring Channel


furring side as per system table. clipped to resilient mounts.

Timber studs at 600mm maximum Cavity insulation as per system table.


centres.
Side two – Lining material as
Gyprock Resilient Mounts screw fixed to per system table.
one side of studs.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2161 (a) Nil 49/43 49/43 50/44 51/45
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 70 Soundscreen 2.0 59/50 59/50 59/50 60/51
90/90/90 Fyrchek Plasterboard.
(e) 75 Gold Batts R2.0 57/49 57/49 58/50 58/50
SIDE TWO
FC 12969 • 2 x 13mm Gyprock (f) 50 MAB Polyester 11kg 53/46 53/46 53/46 54/47
Fyrchek MR Plasterboard.
Minimum Wall Thickness mm 150 170 200 220
CSR 2162 (a) Nil 49/43 49/43 50/44 51/45
– /120/120 (c) 70 Soundscreen 2.0 59/50 59/50 59/50 60/51
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 57/49 57/49 58/50 58/50
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 53/46 53/46 53/46 54/47

Minimum Wall Thickness mm 150 170 200 220


CSR 2170 (a) Nil 48/42 49/43 50/44 50/44
– /120/120 (c) 70 Soundscreen 2.0 58/49 59/50 59/50 59/50
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 56/48 57/49 58/50 57/49
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 52/45 53/46 53/46 53/46

Minimum Wall Thickness mm 162 182 212 232


CSR 2171 (a) Nil 49/43 50/44 51/45 51/45
SIDE ONE
– /120/120 • 2 x 16mm Gyprock (c) 70 Soundscreen 2.0 59/50 60/51 60/51 60/51
120/120/120 Fyrchek Plasterboard.
(e) 75 Gold Batts R2.0 57/49 58/50 59/51 58/50
SIDE TWO
FC 12969 • 2 x 16mm Gyprock (f) 50 MAB Polyester 11kg 53/46 54/47 54/47 54/47
Fyrchek MR Plasterboard.
Minimum Wall Thickness mm 162 182 212 232
CSR 2172 (a) Nil 50/44 51/45 52/46 53/47
– /120/120 (c) 70 Soundscreen 2.0 60/51 61/52 61/52 62/53
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 58/50 59/51 60/52 60/52
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 54/47 55/48 55/48 56/49

Minimum Wall Thickness mm 162 182 212 232

D14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.
(Insulation may be cut and fitted between
Staggered timber studs at 600mm studs).
maximum centres each side.
Lining material as per system table.
Minimum 20mm clearance between
stud and opposing lining.

No Noggings or any connection


between studs.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

PLATE WIDTH mm 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2200 (a) Nil 37/30 39/32 40/33

(c) 70 Soundscreen 2.0 48/38 50/40 50/40


BOTH SIDES
–/–/– • 1 x 6mm CeminSeal (e) 75 Gold Batts R2.0 46/37 48/39 50/41
Wallboard.
(f) 50 MAB Polyester 11kg 42/35 44/37 44/37

Wall Thickness mm 102 132 152


CSR 2202 (a) Nil 41/34 42/36 44/38

(c) 70 Soundscreen 2.0 52/42 53/44 54/45


BOTH SIDES
–/–/– • 1 x 9mm CeminSeal (e) 75 Gold Batts R2.0 50/41 52/44 54/46
Wallboard.
(f) 50 MAB Polyester 11kg 46/39 47/41 48/42

Wall Thickness mm 108 138 158


CSR 2205 (a) Nil 35/28 37/30 37/30
SIDE ONE
• 1 x 10mm Gyprock Plus (c) 70 Soundscreen 2.0 46/36 48/38 47/37
Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 44/35 46/37 48/39
SIDE TWO
• 1 x 6mm CeminSeal (f) 50 MAB Polyester 11kg 40/33 42/35 41/34
Wallboard.
Wall Thickness mm 106 136 156
CSR 10151 (a) Nil 39/32 41/34 42/35
SIDE ONE
• 1 x 10mm Gyprock HD (b) 70 Soundscreen 2.0 50/40 51/41 52/42
Plasterboard.
–/–/– (c) 50 MAB Polyester 11kg 44/37 45/38 46/39
SIDE TWO
• 1 x 6mm CeminSeal (d) 75 Gold Batts R2.0 48/39 50/41 50/41
Wallboard.
Wall Thickness mm 106 136 156
CSR 10152 (a) Nil 38/31 41/34 42/35

(b) 70 Soundscreen 2.0 49/39 51/41 52/42


BOTH SIDES
–/–/– • 1 x 10mm Gyprock HD (c) 50 MAB Polyester 11kg 46/36 45/38 46/39
Plasterboard.
(d) 75 Gold Batts R2.0 47/38 50/41 50/41

Wall Thickness mm 110 140 160


CSR 10153 (a) Nil 45/39 46/40 47/41

(b) 70 Soundscreen 2.0 56/47 56/47 57/48


BOTH SIDES
– /–/– • 2 x 10mm Gyprock HD (c) 50 MAB Polyester 11kg 50/44 50/44 51/45
Plasterboard.
(d) 75 Gold Batts R2.0 54/46 55/47 55/47

Wall Thickness mm 130 160 180

GYPROCK® THE RED BOOK™ 1 D15


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.
(Insulation may be cut and fitted between
Staggered timber studs at 600mm studs).
maximum centres each side.
Lining material as per system table.
Minimum 20mm clearance between
stud and opposing lining.

No Noggings or any connection


between studs.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

PLATE WIDTH mm 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2220 (a) Nil 37/30 38/31 40/33
SIDE ONE
• 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 48/38 49/39 50/40
Standard Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 46/37 48/39 50/41
SIDE TWO
• 1 x 6mm CeminSeal (f) 50 MAB Polyester 11kg 42/35 43/36 44/37
Wallboard.
Wall Thickness mm 109 139 159
CSR 2225 (a) Nil 37/30 38/31 40/33

(c) 70 Soundscreen 2.0 48/38 49/39 50/40


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 46/37 47/38 50/41
Standard Plasterboard.
(f) 50 MAB Polyester 11kg 42/35 43/36 44/37

Wall Thickness mm 116 146 166


CSR 2226 (a) Nil 37/30 39/32 40/33
SIDE ONE
• 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 48/38 50/40 50/40
Aquachek Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 46/37 48/39 50/41
SIDE TWO
• 1 x 13mm Gyprock (f) 50 MAB Polyester 11kg 42/35 44/37 44/37
Standard Plasterboard.
Wall Thickness mm 116 146 166
CSR 2227 (a) Nil 38/31 40/33 41/34

(c) 70 Soundscreen 2.0 49/39 51/41 51/41


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 47/38 49/40 50/41
Aquachek Plasterboard.
(f) 50 MAB Polyester 11kg 43/36 45/38 45/38

Wall Thickness mm 116 146 166

D16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.
(Insulation may be cut and fitted between
Staggered timber studs at 600mm studs).
maximum centres each side.
Lining material as per system table.
Minimum 20mm clearance between
stud and opposing lining.

No Noggings or any connection


between studs.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

PLATE WIDTH mm 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2240 (a) Nil 38/31 41/34 41/35
– /60/60 (c) 70 Soundscreen 2.0 49/39 52/42 51/42
30/30/30 BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 47/38 50/41 51/43
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 43/36 46/39 45/39

Wall Thickness mm 116 146 166


CSR 2241 (a) Nil 38/31 41/34 41/35
SIDE ONE
– /60/60 • 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 49/39 52/42 51/42
30/30/30 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 47/38 50/41 51/43
SIDE TWO
FC 12969 • 1 x 13mm Gyprock (f) 50 MAB Polyester 11kg 43/36 46/39 45/39
Fyrchek Plasterboard.
Wall Thickness mm 116 146 166
CSR 2242 (a) Nil 38/31 41/34 41/35
– /60/60 (c) 70 Soundscreen 2.0 49/39 52/42 51/42
30/30/30 BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 47/38 50/41 51/43
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 43/36 46/39 45/39

Wall Thickness mm 116 146 166


CSR 2245 (a) Nil 47/41 47/41 48/42
BOTH SIDES
– /60/60 • 1 x 6mm CeminSeal (c) 70 Soundscreen 2.0 58/49 57/48 58/49
60/60/60 Wallboard (against studs).
(d) Polymax 2.0 56/50 56/50 57/51
• 1 x 13mm Gyprock
Fyrchek Plasterboard. (e) 75 Gold Batts R2.0 56/48 56/48 56/48
FC 12969

Wall Thickness mm 128 158 178


CSR 2255 (a) Nil 39/32 40/34 41/35
– /60/60 (c) 70 Soundscreen 2.0 50/40 51/42 51/42
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 48/39 49/41 50/42
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 44/37 45/39 45/39

Wall Thickness mm 122 152 172


CSR 2256 (a) Nil 40/33 41/35 43/37
SIDE ONE
– /60/60 • 1 x 16mm Gyprock (c) 70 Soundscreen 2.0 51/41 52/43 53/44
60/60/60 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 49/40 50/42 51/43
SIDE TWO
FC 12969 • 1 x 16mm Gyprock (f) 50 MAB Polyester 11kg 45/38 46/40 47/41
Fyrchek Plasterboard.
Wall Thickness mm 122 152 172

GYPROCK® THE RED BOOK™ 1 D17


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.
(Insulation may be cut and fitted between
Staggered timber studs at 600mm studs).
maximum centres each side.
Lining material as per system table.
Minimum 20mm clearance between
stud and opposing lining.

No Noggings or any connection


between studs. NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

PLATE WIDTH mm 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2257 (a) Nil 40/33 41/35 43/37
– /60/60 (c) 70 Soundscreen 2.0 51/41 52/43 53/44
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 49/40 51/42 52/44
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 45/38 46/40 47/41

Wall Thickness mm 122 152 172


CSR 2265 (a) Nil 46/40 47/41 48/42
BOTH SIDES
– /60/60 • 1 x 16mm Gyprock (c) 70 Soundscreen 2.0 57/48 58/49 58/49
60/60/60 Fyrchek Plasterboard
(against studs). (e) 75 Gold Batts R2.0 55/47 56/48 57/49

FC 12969 • 1 x 6mm CeminSeal (f) 50 MAB Polyester 11kg 51/45 52/46 52/46
Wallboard.
Wall Thickness mm 134 164 184
CSR 2266 (a) Nil 46/40 47/41 48/42
– /90/90 BOTH SIDES
(c) 70 Soundscreen 2.0 57/48 58/49 58/49
• 1 x 6mm CeminSeal
90/90/90*
*ACR Group 3 Wallboard (against studs). (e) 75 Gold Batts R2.0 55/47 56/48 57/49
• 1 x 16mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 51/45 52/46 52/46
Fyrchek Plasterboard.
Wall Thickness mm 134 164 184
CSR 2275 (a) Nil 46/40 47/41 48/42
– /120/120 (c) 70 Soundscreen 2.0 57/48 58/49 58/49
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (d) Polymax 2.0 55/49 56/50 57/51
Fyrchek Plasterboard.
FC 12969 (e) 75 Gold Batts R2.0 55/47 56/48 57/49

Wall Thickness mm 142 172 192


CSR 2276 (a) Nil 46/40 47/41 48/42
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 70 Soundscreen 2.0 57/48 58/49 58/49
90/90/90 Fyrchek Plasterboard.
(e) 75 Gold Batts R2.0 55/47 56/48 57/49
SIDE TWO
FC 12969 • 2 x 13mm Gyprock (f) 50 MAB Polyester 11kg 51/45 52/46 52/46
Fyrchek MR Plasterboard.
Wall Thickness mm 142 172 192

D18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Staggered Stud

Lining material as per system table. Cavity insulation as per system table.
(Insulation may be cut and fitted between
Staggered timber studs at 600mm studs).
maximum centres each side.
Lining material as per system table.
Minimum 20mm clearance between
stud and opposing lining.

No Noggings or any connection


between studs.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Not Deemed Discontinuous Construction

PLATE WIDTH mm 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2277 (a) Nil 46/40 47/41 48/42
– /120/120 (c) 70 Soundscreen 2.0 57/48 58/49 58/49
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 55/47 56/48 57/49
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 51/45 52/46 52/46

Wall Thickness mm 142 172 192


CSR 2285 (a) Nil 45/39 46/40 47/41
– /120/120 (c) 70 Soundscreen 2.0 56/47 57/48 57/48
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 54/46 55/47 56/48
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 50/44 51/45 51/45

Wall Thickness mm 154 184 204


CSR 2286 (a) Nil 46/40 47/41 48/42
SIDE ONE
– /120/120 • 2 x 16mm Gyprock (c) 70 Soundscreen 2.0 57/48 58/49 58/49
120/120/120 Fyrchek Plasterboard.
(e) 75 Gold Batts R2.0 55/47 57/49 57/49
SIDE TWO
FC 12969 • 2 x 16mm Gyprock (f) 50 MAB Polyester 11kg 51/45 52/46 52/46
Fyrchek MR Plasterboard.
Wall Thickness mm 154 184 204
CSR 2287 (a) Nil 47/41 49/43 49/43
– /120/120 (c) 70 Soundscreen 2.0 58/49 60/51 59/50
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 56/48 58/50 59/51
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 52/46 54/48 53/47

Wall Thickness mm 154 184 204

GYPROCK® THE RED BOOK™ 1 D19


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of timber studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2300 (a) Nil 42/35 43/37 46/40 47/41

(c) 70 Soundscreen 2.0 56/45 57/47 60/50 61/51


BOTH SIDES
–/–/– • 1 x 6mm CeminSeal (e) 75 Gold Batts R2.0 54/44 55/46 58/49 59/50
Wallboard.
(f) 50 MAB Polyester 11kg 48/41 49/43 52/46 53/47

Minimum Wall Thickness mm 172 212 272 312


CSR 2302 (a) Nil 46/40 47/41 48/42 49/43

(c) 70 Soundscreen 2.0 60/50 61/51 62/52 63/53


BOTH SIDES
–/–/– • 1 x 9mm CeminSeal (e) 75 Gold Batts R2.0 58/49 59/50 60/51 61/52
Wallboard.
(f) 50 MAB Polyester 11kg 52/46 53/47 54/48 55/49

Minimum Wall Thickness mm 178 218 278 318


CSR 2310 (a) Nil 41/34 43/37 45/39 46/40

(c) 70 Soundscreen 2.0 55/44 57/47 59/49 60/50


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 53/43 55/46 57/48 58/49
Standard Plasterboard.
(f) 50 MAB Polyester 11kg 47/40 49/43 51/45 52/46

Minimum Wall Thickness mm 186 226 286 326


CSR 2312 (a) Nil 42/35 44/38 46/40 47/41
SIDE ONE
• 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 56/45 58/48 60/50 61/51
Standard Plasterboard.
–/–/– (e) 75 Gold Batts R2.0 54/44 56/47 58/49 59/50
SIDE TWO
• 1 x 13mm Gyprock (f) 50 MAB Polyester 11kg 48/41 50/44 52/46 53/47
Aquachek Plasterboard.
Minimum Wall Thickness mm 186 226 286 326
CSR 2314 (a) Nil 42/36 45/39 46/40 47/41

(c) 70 Soundscreen 2.0 56/46 59/49 60/50 61/51


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 54/45 57/48 58/49 59/50
Aquachek Plasterboard.
(f) 50 MAB Polyester 11kg 48/42 51/45 52/46 53/47

Minimum Wall Thickness mm 186 226 286 326


CSR 2316 (a) Nil 44/38 46/40 47/41 48/42

(c) 70 Soundscreen 2.0 58/48 60/50 61/51 62/52


BOTH SIDES
–/–/– • 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 56/47 58/49 59/50 60/51
Soundchek Plasterboard.
(f) 50 MAB Polyester 11kg 50/44 52/46 53/47 54/48

Minimum Wall Thickness mm 186 226 286 326

D20 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of timber studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2330 (a) Nil 43/37 45/39 47/41 48/42
– /60/60 (c) 70 Soundscreen 2.0 57/47 59/49 61/51 62/52
30/30/30 BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 55/46 57/48 59/50 60/51
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 49/43 51/45 53/47 54/48

Minimum Wall Thickness mm 186 226 286 326


CSR 2331 (a) Nil 44/38 45/39 47/41 48/42
SIDE ONE
– /60/60 • 1 x 13mm Gyprock (c) 70 Soundscreen 2.0 58/48 59/49 61/51 62/52
30/30/30 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 56/47 57/48 59/50 60/51
SIDE TWO
FC 12969 • 1 x 13mm Gyprock (f) 50 MAB Polyester 11kg 50/44 51/45 53/47 54/48
Fyrchek Plasterboard.
Minimum Wall Thickness mm 186 226 286 326
CSR 2332 (a) Nil 44/38 45/39 47/41 48/42
– /60/60 (c) 70 Soundscreen 2.0 58/48 59/49 61/51 62/52
30/30/30 BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Gold Batts R2.0 56/47 57/48 59/50 60/51
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 50/44 51/44 53/47 54/48

Minimum Wall Thickness mm 186 226 286 326


CSR 2336 (a) Nil 48/42 50/44 51/45 52/46
– /60/60 BOTH SIDES
(c) 70 Soundscreen 2.0 62/52 64/54 65/55 66/56
• 1 x 13mm Gyprock
30/30/30
Fyrchek Plasterboard. (e) 75 Gold Batts R2.0 60/51 62/53 63/54 64/55
• 1 x 13mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 54/48 56/50 57/51 58/52
Standard Plasterboard.
Minimum Wall Thickness mm 212 252 312 352
CSR 2340 (a) Nil 49/43 50/44 51/45 52/46
– /60/60 BOTH SIDES
(c) 70 Soundscreen 2.0 63/53 64/54 65/55 66/56
• 1 x 6mm CeminSeal
60/60/60
Wallboard (against studs). (e) 75 Gold Batts R2.0 61/52 62/53 63/54 64/55
• 1 x 13mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 55/49 56/50 57/51 58/52
Fyrchek plasterboard.
Minimum Wall Thickness mm 198 238 298 338

GYPROCK® THE RED BOOK™ 1 D21


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of timber studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2350 (a) Nil 43/37 44/38 46/40 47/41
– /60/60 (c) 70 Soundscreen 2.0 57/47 58/48 60/50 61/51
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 55/46 56/47 58/49 59/50
Fyrchek Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 49/43 50/44 52/46 53/47

Minimum Wall Thickness mm 192 232 292 332


CSR 2355 (a) Nil 43/37 44/38 46/40 47/41
– /60/60 (c) 2 x 70 Soundscreen 2.0 60/51 61/52 63/54 63/54
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 2 x 75 Gold Batts R2.0 58/49 59/50 61/52 61/52
Fyrchek Plasterboard.
FC 12969 (f) 2 x 50 MAB Polyester 11kg 53/46 54/47 55/48 56/49

Minimum Wall Thickness mm 192 232 292 332


CSR 2356 (a) Nil 44/38 45/39 47/41 48/42
SIDE ONE
– /60/60 • 1 x 16mm Gyprock (c) 70 Soundscreen 2.0 58/48 59/49 61/51 62/52
60/60/60 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 56/47 57/48 59/50 60/51
SIDE TWO
FC 12969 • 1 x 16mm Gyprock (f) 50 MAB Polyester 11kg 50/44 51/45 53/47 54/48
Fyrchek Plasterboard.
Minimum Wall Thickness mm 192 232 292 332
CSR 2357 (a) Nil 45/39 47/41 48/42 49/43
– /60/60 (c) 70 Soundscreen 2.0 59/49 61/51 62/52 63/53
60/60/60 BOTH SIDES
• 1 x 16mm Gyprock (e) 75 Gold Batts R2.0 57/48 59/50 60/51 61/52
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 51/45 53/47 54/48 55/49

Minimum Wall Thickness mm 192 232 292 332

CSR 2360 SIDE ONE (a) Nil 46/40 48/42 49/43 50/44
• 1 x 16mm Gyprock
– /60/60 Fyrchek Plasterboard. (c) 70 Soundscreen 2.0 60/50 62/52 63/53 64/54
60/60/60 SIDE TWO (ANY ORDER)
(e) 75 Gold Batts R2.0 58/49 60/51 61/52 62/53
• 1 x 16mm Gyprock
FC 12969 Fyrchek Plasterboard. (f) 50 MAB Polyester 11kg 52/46 54/48 55/49 56/50
• 1 x 6mm CeminSeal
Wallboard. Minimum Wall Thickness mm 198 238 298 338
CSR 2365 (a) Nil 48/42 49/43 51/45 51/45
– /60/60 BOTH SIDES
(c) 70 Soundscreen 2.0 62/52 63/53 65/55 65/55
• 1 x 16mm Gyprock
60/60/60
Fyrchek plasterboard. (e) 75 Gold Batts R2.0 60/51 61/52 63/54 63/54
• 1 x 10mm Gyprock Plus
FC 12969 (f) 50 MAB Polyester 11kg 54/48 55/49 57/51 57/51
Plasterboard.
Minimum Wall Thickness mm 212 252 312 352

D22 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of timber studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2367 (a) Nil 49/43 50/44 52/46 53/47
BOTH SIDES
– /60/60 • 1 x 16mm Gyprock (c) 70 Soundscreen 2.0 63/53 64/54 66/56 67/57
60/60/60 Fyrchek plasterboard
(against studs). (e) 75 Gold Batts R2.0 61/52 62/53 64/55 65/56

FC 12969 • 1 x 6mm CeminSeal (f) 50 MAB Polyester 11kg 55/49 56/50 58/52 59/53
Wallboard.
Minimum Wall Thickness mm 204 244 304 344
CSR 2368 (a) Nil 49/43 50/44 52/46 53/47
– /90/90 BOTH SIDES
(c) 70 Soundscreen 2.0 63/53 64/54 66/56 67/57
• 1 x 6mm CeminSeal
90/90/90*
*ACR Group 3 Wallboard (against studs). (e) 75 Gold Batts R2.0 61/52 62/53 64/55 65/56
• 1 x 16mm Gyprock
FC 12969 (f) 50 MAB Polyester 11kg 55/49 56/50 58/52 59/53
Fyrchek plasterboard.
Minimum Wall Thickness mm 204 244 304 344
CSR 2375 (a) Nil 49/43 50/44 52/46 52/46
– /120/120 (c) 70 Soundscreen 2.0 63/53 64/54 66/56 66/56
90/90/90 Both Sides
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 61/52 62/53 64/55 64/55
Fyrchek plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 55/49 56/50 58/52 58/52

Minimum Wall Thickness mm 212 252 312 352


CSR 2376 (a) Nil 49/43 50/44 52/46 53/47
SIDE ONE
– /120/120 • 2 x 13mm Gyprock (c) 70 Soundscreen 2.0 63/53 64/54 66/56 67/57
90/90/90 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 61/52 62/53 64/55 65/56
SIDE TWO
FC 12969 • 2 x 13mm Gyprock (f) 50 MAB Polyester 11kg 55/49 56/50 58/52 59/53
Fyrchek Plasterboard.
Minimum Wall Thickness mm 212 252 312 352
CSR 2377 (a) Nil 49/43 51/45 52/46 53/47
– /120/120 (c) 70 Soundscreen 2.0 63/53 65/55 66/56 67/57
90/90/90 BOTH SIDES
• 2 x 13mm Gyprock (e) 75 Gold Batts R2.0 61/52 63/54 64/55 65/56
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 55/49 57/51 58/52 59/53

Minimum Wall Thickness mm 212 252 312 352


CSR 2385 (a) Nil 49/43 50/44 51/45 52/46
– /120/120 (c) 70 Soundscreen 2.0 63/53 64/54 65/55 66/56
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 61/52 62/53 63/54 64/55
Fyrchek plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 55/49 56/50 57/51 58/52

Minimum Wall Thickness mm 224 264 324 364

GYPROCK® THE RED BOOK™ 1 D23


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Double Stud

Lining material as per system table. Cavity insulation as per system table.
(Unless otherwise specified, cavity
2 rows of timber studs at 600mm insulation is required in one stud row
maximum centres with 20mm only).
minimum gap.
Lining material as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.
Acoustic performance valid for 35mm wide
studs at 600mm centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 2 Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 70 90 120 140


FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2386 (a) Nil 50/44 51/45 52/46 53/47
SIDE ONE
– /120/120 • 2 x 16mm Gyprock (c) 70 Soundscreen 2.0 64/54 65/55 66/56 67/57
120/120/120 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 62/53 63/54 64/55 65/56
SIDE TWO
FC 12969 • 2 x 16mm Gyprock (f) 50 MAB Polyester 11kg 56/50 57/51 58/52 59/53
Fyrchek Plasterboard.
Minimum Wall Thickness mm 224 264 324 364
CSR 2387 (a) Nil 51/45 52/46 53/47 54/48
– /120/120 (c) 70 Soundscreen 2.0 65/55 66/56 67/57 68/58
120/120/120 BOTH SIDES
• 2 x 16mm Gyprock (e) 75 Gold Batts R2.0 63/54 64/55 65/56 66/57
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 57/51 58/52 59/53 60/54

Minimum Wall Thickness mm 224 264 324 364


CSR 2392 (a) Nil 52/46 53/47 54/48 55/49
– /120/120 (c) 70 Soundscreen 2.0 66/56 67/57 68/58 69/59
120/120/120 BOTH SIDES
• 3 x 16mm Gyprock (e) 75 Gold Batts R2.0 64/55 65/56 66/57 67/58
Fyrchek plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 58/52 59/53 60/54 61/55

Minimum Wall Thickness mm 256 296 356 396


CSR 2393 (a) Nil 53/47 54/48 55/49 56/50
SIDE ONE
– /120/120 • 3 x 16mm Gyprock (c) 70 Soundscreen 2.0 67/57 68/58 69/59 70/60
120/120/120 Fyrchek MR Plasterboard.
(e) 75 Gold Batts R2.0 65/56 66/57 67/58 68/59
SIDE TWO
FC 12969 • 3 x 16mm Gyprock (f) 50 MAB Polyester 11kg 59/53 60/54 61/55 62/56
Fyrchek Plasterboard.
Minimum Wall Thickness mm 256 296 356 396
CSR 2394 (a) Nil 54/48 55/49 57/51 57/51
– /120/120 (c) 70 Soundscreen 2.0 68/58 69/59 71/61 71/61
120/120/120 BOTH SIDES
• 3 x 16mm Gyprock (e) 75 Gold Batts R2.0 66/57 67/58 69/60 69/60
Fyrchek MR Plasterboard.
FC 12969 (f) 50 MAB Polyester 11kg 60/54 61/55 63/57 63/57

Minimum Wall Thickness mm 256 296 356 396

D24 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Party Wall with 25mm Fire Barrier

Lining material as per system table. Timber studs at 600mm maximum


centres.
Gyprock aluminium wall clips
Gyprock aluminium wall clips
Timber studs at 600mm maximum
centres. Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in 20-40mm air gap (30mm typical).
H-studs at 600mm maximum centres.

20-40mm air gap (30mm typical). NOTE: Acoustic performance valid for 35mm
wide studs at 600mm cts. with 20mm air gaps.
Wall height and clip spacings
restrictions apply, refer to page D5.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP513 Gyprock Party Wall Installation Guide for further information Discontinuous Construction

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL (Both Sides)
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2402 (a) 75 Gold Batts 2.0 61/48 62/50

(b) 90 Gold Batts 2.7 63/50 64/52


60/60/60 BOTH SIDES
• 1 x 6mm CeminSeal (c) 88 Soundscreen 2.5 64/51 65/53
WF 45743 Wallboard.
(d) 110 GW Acoustigard 11kg 63/50 64/52

Typical Wall Thickness mm 237 277


CSR 2459 (a) 75 Gold Batts 2.0 62/49 63/51

(b) 90 Gold Batts 2.7 64/51 65/53


60/60/60 BOTH SIDES
• 7.5mm Cemintel Texture (c) 88 Soundscreen 2.5 65/52 66/54
WF 45743 Base Sheet.
(d) 110 GW Acoustigard 11kg 64/51 65/53

Typical Wall Thickness mm 240 280


CSR 10154 (a) 75 Gold Batts 2.0 61/48 62/50

(b) 90 Gold Batts 2.7 63/50 64/52


60/60/60 BOTH SIDES
• 1 x 10mm Gyprock HD (c) 88 Soundscreen 2.5 64/51 65/53
WF 45743 Plasterboard.
(d) 110 Acoustigard 11kg 63/50 64/52

Typical Wall Thickness mm 245 285


CSR 2415 (a) 75 Gold Batts 2.0 62/49 63/51

(b) 90 Gold Batts 2.7 64/51 65/53


60/60/60 BOTH SIDES
• 2 x 10mm Gyprock Plus (c) 88 Soundscreen 2.5 65/52 66/54
WF 45743 Plasterboard.
(d) 110 Acoustigard 11kg 64/51 65/53

Typical Wall Thickness mm 265 305


CSR 2421 (a) 75 Gold Batts 2.0 63/51 64/52

(b) 90 Gold Batts 2.7 65/53 66/54


60/60/60 BOTH SIDES
• 2 x 10mm Gyprock (c) 88 Soundscreen 2.5 66/54 67/55
WF 45743 Aquachek Plasterboard.
(d) 110 Acoustigard 11kg 65/53 66/54

Typical Wall Thickness mm 265 305


CSR 10038 (a) 75 Gold Batts 2.0 62/49 63/51
SIDE ONE
• 2 x 10mm Gyprock HD (b) 90 Gold Batts 2.7 64/51 65/53
60/60/60 Plasterboard.
(c) 88 Soundscreen 2.5 65/52 66/54
WF 45743 SIDE TWO
• 2 x 10mm Gyprock (d) 110 Acoustigard 11kg 64/51 65/53
Aquachek Plasterboard.
Typical Wall Thickness mm 265 305

GYPROCK® THE RED BOOK™ 1 D25


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Party Wall with 25mm Fire Barrier

Lining material as per system table. Timber studs at 600mm maximum


centres.
Gyprock aluminium wall clips
Gyprock aluminium wall clips
Timber studs at 600mm maximum
centres. Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in 20-40mm air gap (30mm typical).
H-studs at 600mm maximum centres.

20-40mm air gap (30mm typical). NOTE: Acoustic performance valid for 35mm
wide studs at 600mm cts. with 20mm air gaps.
Wall height and clip spacings
restrictions apply, refer to page D5.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP513 Gyprock Party Wall Installation Guide for further information Discontinuous Construction

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL (Both Sides)
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10039 (a) 75 Gold Batts 2.0 62/49 63/51
SIDE ONE
• 1 x 10mm Gyprock HD (b) 90 Gold Batts 2.7 64/51 65/53
60/60/60 Plasterboard.
(c) 88 Soundscreen 2.5 65/52 66/54
WF 45743 SIDE TWO
• 1 x 13mm Gyprock (d) 110 Acoustigard 11kg 64/51 65/53
Soundchek Plasterboard.
Typical Wall Thickness mm 248 288
CSR 2441 (a) 75 Gold Batts 2.0 61/48 62/50

(b) 90 Gold Batts 2.7 63/50 64/52


60/60/60 BOTH SIDES
• 1 x 13mm Gyprock (c) 88 Soundscreen 2.5 64/51 65/53
WF 45743 Standard Plasterboard.
(d) 110 Acoustigard 11kg 63/50 64/52

Typical Wall Thickness mm 251 291


CSR 2443 (a) 75 Gold Batts 2.0 61/48 62/50
SIDE ONE
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.7 63/50 64/52
60/60/60 Standard Plasterboard.
(c) 88 Soundscreen 2.5 64/51 65/53
WF 45743 SIDE TWO
• 1 x 13mm Gyprock (d) 110 Acoustigard 11kg 63/50 64/52
Aquachek Plasterboard.
Typical Wall Thickness mm 251 291
CSR 2445 (a) 75 Gold Batts 2.0 62/49 63/51

(b) 90 Gold Batts 2.7 64/51 65/53


60/60/60 BOTH SIDES
• 1 x 13mm Gyprock (c) 88 Soundscreen 2.5 65/52 66/54
WF 45743 Aquachek Plasterboard.
(d) 110 Acoustigard 11kg 64/51 65/53

Typical Wall Thickness mm 251 291


CSR 2450 (a) 75 Gold Batts 2.0 62/49 63/51
SIDE ONE
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.7 64/51 65/53
60/60/60 Aquachek Plasterboard.
(c) 88 Soundscreen 2.5 65/52 66/54
WF 45743 SIDE TWO
• 1 x 13mm Gyprock (d) 110 Acoustigard 11kg 64/51 65/53
Soundchek Plasterboard.
Typical Wall Thickness mm 251 291

D26 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Timber Frame Internal Wall Systems – Party Wall with 25mm Fire Barrier

Lining material as per system table. Timber studs at 600mm maximum


centres.
Gyprock aluminium wall clips
Gyprock aluminium wall clips
Timber studs at 600mm maximum
centres. Cavity insulation as per system table.

Cavity insulation as per system table. Lining material as per system table.

25mm Gyprock Shaft Liner Range in 20-40mm air gap (30mm typical).
H-studs at 600mm maximum centres.

20-40mm air gap (30mm typical). NOTE: Acoustic performance valid for 35mm
wide studs at 600mm cts. with 20mm air gaps.
Wall height and clip spacings
restrictions apply, refer to page D5.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP513 Gyprock Party Wall Installation Guide for further information Discontinuous Construction

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL (Both Sides)
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 2455 (a) 75 Gold Batts 2.0 63/51 64/52

(b) 90 Gold Batts 2.7 65/53 66/54


60/60/60 BOTH SIDES
• 1 x 13mm Gyprock (c) 88 Soundscreen 2.5 66/54 67/55
WF 45743 Soundchek Plasterboard.
(d) 110 Acoustigard 11kg 65/53 66/54

Typical Wall Thickness mm 251 291


CSR 3372 (a) 75 Gold Batts 2.0 63/51 64/52

(b) 90 Gold Batts 2.7 65/53 66/54


60/60/60 BOTH SIDES
• 1 x 13mm Gyprock EC08 (c) 88 Soundscreen 2.5 66/54 67/55
WF 45743 Complete.
(d) 110 Acoustigard 11kg 65/53 66/54

Typical Wall Thickness mm 251 291


CSR 10016 (a) 75 Gold Batts 2.0 63/51 64/52

(b) 90 Gold Batts 2.7 65/53 66/54


60/60/60 BOTH SIDES
• 1 x 13mm Gyprock EC08 (c) 88 Soundscreen 2.5 66/54 67/55
WF 45743 Extreme.
(d) 110 Acoustigard 11kg 65/53 66/54

Typical Wall Thickness mm 251 291

GYPROCK® THE RED BOOK™ 1 D27


NOTES

D28 GYPROCK® THE RED BOOK™ 1


CONCRETE &
MASONRY
WALL SYSTEMS E
SECTION CONTENTS
Introduction E2
Design Considerations E2
Installation E5
System Selection Tables

Stud One Side E6


PowerPanel
E23
with Steel Stud/Furring

Stud Both Sides E9


PowerPanel Intertenancy
System with E24
Timber Studs Both Sides

Stud Side One &


E12
Furring Side Two
AFS Rediwall® E25

Furring Both Sides E17

Blade Columns E27

Furring One Side E19

GYPROCK® THE RED BOOK™ 1 E1


INTRODUCTION systems, to meet the requirements of the National
Construction Code of Australia (NCC) and any relevant
Australian Standards.
This section provides important design
information for the selection and specification For the most up-to-date product & system performance
of concrete and masonry wall systems that information, visit:
incorporate Gyprock and Cemintel linings. CSR System Selector: https://apps.csr.com.au/
The linings may be fixed directly, to timber, systemselector/search-option
or to steel framing.
CSR Thermal Calculator: https://apps.csr.com.au/
thermalcalculator
Gyprock plasterboard and CeminSeal Wallboard can be
used with masonry walls for effective fire and acoustic Systems in this section are suitable for a wide range of
solutions. These linings can eliminate the need for render, masonry products. These are typically clay and concrete
increase the fire rating of the masonry, or provide an blocks, autoclaved aerated concrete blocks and panels.
acoustic performance to meet sound transmission and Concrete elements can be pre-cast or formed in-situ.
sound impact ratings. Minimum performance conditions apply to the substrates
to achieve some system performance values, and these
Systems incorporating an insulated cavity are generally
are stated in the system specifications. Specific fixing
used where there is a requirement for excellent acoustic
details apply to each type of substrate.
performance and discontinuous construction. The
provision of a cavity also allows for the inclusion of These wall systems are generally used in internal
services. applications in commercial, industrial, institutional,
domestic and high-rise domestic construction, or in the
Gyprock plasterboard may be directly applied to the
renovation of older buildings. For external masonry veneer
masonry substrate, screw fixed to metal furring channels
walls, please refer to Section F, External Wall Systems.
that are fixed to the masonry or may be fixed to separate
stud framing. CeminSeal Wallboard may be fixed to furring
channels or to studs. STRUCTURAL DESIGN
All wall elements must be designed for the applied loads.

DESIGN Vertical loads may be supported by the masonry element


of the wall, or for non-fire rated walls, by the stud framing.

CONSIDERATIONS Lateral loads should be considered separately for framed


and masonry parts of a wall. To achieve the specified
sound performance, ties from masonry to the stud framing
must not be used.
DESIGNER RESPONSIBILITY
It remains the responsibility of the customer (in conjunction
with their designer or engineer, when applicable) to ensure TABLE E4: RONDO FRAMING SPACING & SPAN FOR
that CSR’s products/systems are suitable for their chosen BLADE COLUMN ENCASEMENT
Rondo Maximum Span (mm)
application for any given project. CSR recommends Spacing
Framing Wind Pressure kPa (Ult.)
that a comprehensive assessment of the performance Section
(mm)
0.375 0.5 1.0
requirements be undertaken prior to selection, including 600 1400 1350 1070
Nº129
in respect of project-specific matters such as, but Furring 400 1600 1550 1230
not limited structural adequacy, seismic, acoustic, fire Channel 300 1760 1710 1360
resistance/combustibility, thermal, condensation and 600 1090 1050 830
M515
weatherproofing requirements. 400 1250 1200 950
Top Hat
300 1370 1320 1050
CSR offers online digital tools for the most updated 600 1220 1180 930
H515
information, including but not limited to update of Top Hat
400 1400 1350 1070
products/components, inclusion of new and modified 300 1540 1480 1180

TABLE E3: MAXIMUM WALL HEIGHTS FOR RONDO LIPPED WALL STUDS – NON-LOADBEARING INTERNAL WALLS
Lining Configuration 64mm Stud 76mm Stud 92mm Stud
0.50BMT 0.75BMT 0.55BMT 0.75BMT 0.55BMT 0.75BMT
600mm max. cts
2720 3130 3200 3580 3610 4130

NOTES:
• 600mm maximum stud spacing • Minimum linings 6mm fibre cement sheet or 10mm plasterboard
• Pressures Pultimate = 0.375kPa, Pservice = 0.25kPa • No allowance for wall tiles or shelf loads

E2 GYPROCK® THE RED BOOK™ 1


Framed Wall Elements For masonry with any direct fixed lining or lining fixed to
furring channels:
TABLE E3 shows maximum wall heights for Rondo steel
studs to suit most applications. For other brands of • At control joints in masonry (refer to masonry
studs, studs that are required to be loadbearing, and manufacturer.)
for studs subject to higher lateral pressures, contact the • At 12m maximum centres.
manufacturer for design information. For timber stud
framing, walls should be designed to the appropriate • At change of substrate material.
Australian standards. For stud framed wall elements:
Tall multi-residential buildings often have exterior operable • Non-tiled internal walls with plasterboard outer layer –
doors and windows, resulting in internal walls being at 12m maximum centres.
subject to wind pressure. In these cases, walls must be
• Non-tiled internal walls with fibre cement outer layer –
designed for the appropriate loads.
at 7.2m maximum centres.
Stud frames that are part of a masonry wall system may
• Tiled internal walls – at 4.8m maximum centres.
be loadbearing. A qualified person must complete the
structural design of loadbearing wall systems. Walls with • At junctions with other building elements.
shelving attached also require specific design.
• At changes of lining material.
Steel framing utilising horizontal furring channels or top
• At changes of structural support systems.
hats has been designed to allow wall linings to encase
short blade columns of concrete, including those formed • At each storey or rise of studs.
with AFS formwork, and masonry. There is no connection For AFS wall systems:
between the framing and the column for effective
acoustic performance, and the column length that can • Refer to AFS manuals for guidelines and
be accommodated is given as the span of the framing recommendations.
in TABLE E4. • Engineer to review spacing greater than 16m.

Concrete & Masonry Wall Elements FIRE RESISTANCE


All brick and block wall elements are to be designed in For blade column encasement systems, the plasterboard
accordance with AS 3700 Masonry Structures. Concrete linings are not intended to act as fire protection to the
walls must be designed to AS 3600: Concrete Structures, column. Systems with fire grade plasterboard provide the
and Hebel PowerPanel must be designed in accordance fire separation rating (FRL) as for double stud framed wall
with CSR Hebel literature. systems with the same linings.
For wall systems without a stated Fire Resistance Level
Seismic Loads (FRL), the system FRL is equal to the FRL of the masonry
or concrete wall element. The FRL of masonry walls is
Seismic actions must be considered for building elements
dependent on the height and width of the wall. Contact
in accordance with the NCC. The loads and effects of
the manufacturer or appropriate design standard for more
earthquakes may be determined in accordance with
information. The fire rating of concrete elements may
AS1170.4 ‘Earthquake Actions in Australia’. The Standard
be determined in accordance with AS 3600 Concrete
has design procedures for houses (Class 1), and to
Structures.
buildings (Classes 2 to 9) with importance levels 2, 3 or 4
as defined in the NCC. To achieve the required fire performance of a wall, it
is essential that installation is in accordance with the
CONTROL JOINTS masonry manufacturer’s details and relevant installation
standards. This should include fire sealing at the wall head
Control joints must be installed to allow for structural and perimeters, and filling of mortar joints. All gaps and
movement. Allowance for movement must be made penetrations should be effectively fire sealed.
through the frame, lining and any tiles. Door frames
extending from floor to ceiling constitute control joints. The Fire Resistance Level (FRL) of the systems detailed in
For doors less than ceiling height, a control joint extending this section will not be detrimentally affected by the use of
from one corner of the frame may be used. Control joints Fyrchek MR, Impactchek or EC08 range plasterboard in
must be installed at all construction joints in the building, lieu of Fyrchek plasterboard of the same thickness.
and at the following locations:

GYPROCK® THE RED BOOK™ 1 E3


ACCEPTABLE VARIATIONS TO COMBUSTIBILITY
FIRE SYSTEMS Polyester insulation may NOT be used where the system
has non-combustible construction requirements
The Fire Resistance Level (FRL) of the systems detailed in
this section will not be detrimentally affected by:
ACOUSTIC PERFORMANCE
• Increasing the thickness of the wall.
The acoustic performance of some systems is dependent
• Increasing the cross-sectional dimensions of the
on a minimum R w of the concrete or masonry wall
framing elements.
element. For masonry, this is to be the tested performance
• Decreasing the stud spacing. of the element without render or sheet linings and must be
verified by the masonry unit manufacturer. Alternatively, a
• The inclusion of cavity insulation materials such as
masonry wall may be chosen from TABLE E1. Installation
glasswool , rockwool and polyester provided any
of the masonry element of the wall must be in accordance
noncombustible requirements have been considered
with the manufacturer’s details for the tested product.
for the certain wall applications.
The performance of concrete elements may be selected
• The use of Fyrchek MR, Impactchek or EC08 range
from TABLE E1 or be verified by an acoustic engineer.
plasterboard in lieu of Fyrchek plasterboard of the
same thickness. For blade column encasement systems, the concrete and
masonry elements must have properties as specified in
• Additional layers of plasterboard or Cemintel fibre
TABLE E2.
cement.
Uninsulated cavities formed by fixing linings directly to
TABLE E1: MASONRY/CONCRETE GROUPS FOR USE
masonry or concrete walls can have a deleterious effect
WITH SYSTEM TABLES
Min. Thickness Min. Mass on the rating of the unlined wall due to resonance effects.
Groups Masonry Type
(mm) (kg/m2) Systems in this section that have linings adhesive fixed
A
90 Brick 140 to masonry may have a gap of up to 8mm maximum
140 Blockwork (Hollow) 140 between the masonry surface and lining. If larger gaps
90 Blockwork (Core-Filled) 150
are required it is recommended that a furring channel
90 Blockwork (Solid) 150
B system is used, with insulation as noted in the relevant
110 Brick 170
140 Blockwork (Hollow) 170 system table. Systems that meet the NCC requirements
140 Blockwork (Hollow) 200 for discontinuous construction are noted in the system
C
190 Blockwork (Hollow) 210 specifications. These have studs that are separated from
140 Blockwork (Core-Filled) 260 the masonry by at least 20mm. Ties between masonry
290 Blockwork (Hollow) 290 and stud framing must not be used.
D
220 Brick (Double) 260
120 Concrete 270 Systems that use Gyprock Resilient Mounts with furring
150 Concrete 360 channels to create a cavity do not meet the requirements
E
190 Blockwork (Core-Filled) 360 of discontinuous construction. The installation of services
Note: in these systems is not recommended as they can bridge
Walls from subsequent groups may be used to achieve the ratings
the gap between the masonry and the linings.
in the system tables. For example where Group D is specified, walls
in Group E may also be used. The acoustic performance of wall systems may be
affected by:

TABLE E2: MATERIAL PROPERTIES FOR BLADE • Sound flanking.


COLUMN SYSTEMS
• The effectiveness of workmanship and caulking.
Blade Column Nominal thickness Minimum mass
(mm) (kg/m2) • The presence and treatment of penetrations.
Concrete 120 270
• The inclusion of structural elements and bridging items
150 360
such as ties for external brick wall.
200 460
Core-filled blockwork 140 260
• Reducing the stated or implied cavity sizes.
190 360 The acoustic performance of wall systems will not be
reduced by:
• The addition of Gyprock plasterboard or Cemintel
linings.
• The use of deeper studs or larger cavities.
• The use of timber studs of at least equal depth in lieu
of steel studs.

E4 GYPROCK® THE RED BOOK™ 1


• Omitting the lining direct fixed to the concrete or
masonry (except in Hebel systems).
• The use EC08 Extreme plasterboard in lieu of EC08
Complete plasterboard of the same thickness.

ACOUSTIC SEALING
To attain the stated acoustic rating the perimeters should
be effectively sealed. In systems that do not rely on
plasterboard for the fire rating, use Gyprock Wet Area
Acrylic Sealant, CSR FireSeal, Gyprock Fire Mastic or
other tested acoustic rated material of equivalent or better
performance.

INSTALLATION
MASONRY
All brick and block walls are to be installed in accordance
with AS 3700 Masonry Structures. CSR Hebel PowerPanel
must be installed in accordance with CSR Hebel literature.
AFS Rediwall™ systems must be installed in accordance
with relevant manufacturers specifications.
For systems in this section, masonry may include clay or
concrete blocks, and autoclaved aerated concrete blocks
and panels. Brick and block substrates shall comply with
AS 3700.

FRAMING
CSR recommends steel components manufactured by
Rondo Building Services Pty Ltd. Additional information
on the steel components can be obtained from the Rondo
Building Services Pty Ltd.
Fixing clips include Gyprock Resilient Mount, Rondo direct
fixing clips and BETAGRIP clips.
For systems using furring channels and fixing clips, furring
channels are to be fitted into top and bottom tracks.
Refer to Book 3 Commercial & Multi-Residential Installation
Guide for additional information.

PLASTERBOARD & WALLBOARD


FIXING
Walls may be built to achieve a particular ‘Level of
Finish’ as defined in AS/NZS 2589.1. The Level of Finish
specified can have requirements for frame alignment,
jointing, back blocking methods and sheet orientation.
CeminSeal Wallboard and Gyprock plasterboard may be
installed vertically or horizontally, although for some Levels
of Finish horizontal sheeting must be used.
A nominal 5mm has been allowed for adhesive thickness.

GYPROCK® THE RED BOOK™ 1 E5


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud One Side

Lining material as per system table, Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm Optional lining material as per system


maximum centres. table, direct fixed to masonry.

Cavity insulation as per system table.

20mm minimum cavity between


framing and masonry wall.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 4005 (a) 75 Acoustigard 11kg 55/45 56/46
STUD SIDE
• 1 x 6mm CeminSeal (b) 90 Gold Batts 2.0 56/46 57/47
Wallboard.
(d) Nil 46/35 47/36
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 54/44 55/45
Standard Plasterboard.
Additional Wall Thickness mm 103 131
CSR 4010 (a) 75 Acoustigard 11kg 55/47 57/49
STUD SIDE
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 56/48 58/50
Standard Plasterboard.
(d) Nil 46/37 48/39
MASONRY SIDE
Tested
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 54/46 56/48
Brick, Standard Plasterboard.
Block or Additional Wall Thickness mm 110 138
Concrete CSR 4015 (a) 75 Acoustigard 11kg 56/48 58/50
Wall STUD SIDE
with • 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 57/49 59/51
Rw ≥ 45 Aquachek Plasterboard.
(d) Nil 47/38 49/40
MASONRY SIDE
Wall from • 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 55/47 57/49
TABLE E1 Standard Plasterboard.
Group B Additional Wall Thickness mm 110 138
CSR 4020 (a) 75 Acoustigard 11kg 56/48 58/50
Refer to Wall STUD SIDE
Manufacturer for • 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 57/49 59/51
FRL Details Aquachek Plasterboard.
(d) Nil 49/40 50/41
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 55/47 57/49
Aquachek Plasterboard.
Additional Wall Thickness mm 110 138
CSR 4025 (a) 75 Acoustigard 11kg 58/50 59/51
STUD SIDE
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 59/51 60/52
Soundchek Plasterboard.
(d) Nil 48/37 49/38
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 57/49 58/50
Standard Plasterboard.
Additional Wall Thickness mm 110 138

E6 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud One Side

Lining material as per system table, Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm Optional lining material as per system


maximum centres. table,direct fixed to masonry.

Cavity insulation as per system table.

20mm minimum cavity between


framing and masonry wall.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 4030 (a) 75 Acoustigard 11kg 57/47 58/48
STUD SIDE
• 1 x 6mm CeminSeal (b) 90 Gold Batts 2.0 58/48 59/49
Wallboard.
(d) Nil 48/37 49/38
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 56/46 57/47
Standard Plasterboard.
Additional Wall Thickness mm 103 131
CSR 4035 (a) 75 Acoustigard 11kg 57/49 59/51
STUD SIDE
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 58/50 60/52
Standard Plasterboard.
(d) Nil 48/39 50/41
MASONRY SIDE
Tested
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 56/48 58/50
Brick,
Standard Plasterboard.
Block or Additional Wall Thickness mm 110 138
Concrete CSR 4040 (a) 75 Acoustigard 11kg 58/50 60/52
Wall STUD SIDE
with • 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 59/51 61/53
Rw ≥ 47 Aquachek Plasterboard.
(d) Nil 49/40 51/42
MASONRY SIDE
Wall from • 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 57/49 59/51
TABLE E1 Standard Plasterboard.
Group C Additional Wall Thickness mm 110 138
CSR 4045 (a) 75 Acoustigard 11kg 58/50 60/52
Refer to Wall STUD SIDE
Manufacturer for • 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 59/51 61/53
FRL Details Aquachek Plasterboard.
(d) Nil 49/40 51/42
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 57/49 59/51
Aquachek Plasterboard.
Additional Wall Thickness mm 110 138
CSR 4050 (a) 75 Acoustigard 11kg 60/52 61/53
STUD SIDE
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 61/53 62/54
Soundchek Plasterboard.
(d) Nil 51/42 52/43
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 59/51 60/52
Standard Plasterboard.
Additional Wall Thickness mm 110 138

GYPROCK® THE RED BOOK™ 1 E7


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud One Side

Lining material as per system table, Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm Optional lining material as per system


maximum centres. table,direct fixed to masonry.

Cavity insulation as per system table.

20mm minimum cavity between


framing and masonry wall.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 4055 (a) Nil 51/41 52/42
STUD SIDE
• 1 x 6mm CeminSeal (b) 75 Acoustigard 11kg 60/51 61/52
Wallboard.
(c) 90 Gold Batts 2.0 61/52 62/53
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 59/50 60/51
Standard Plasterboard.
Additional Wall Thickness mm 103 131
CSR 4060 (a) Nil 49/39 51/41
STUD SIDE
• 1 x 10mm Gyprock Plus (b) 75 Acoustigard 11kg 58/49 60/51
Plasterboard.
(c) 90 Gold Batts 2.0 59/50 61/52
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 57/48 59/50
Standard Plasterboard.
Additional Wall Thickness mm 107 135
CSR 4065 (a) Nil 51/42 53/44
Tested STUD SIDE
Brick, • 1 x 13mm Gyprock (b) 75 Acoustigard 11kg 60/52 62/54
Block or Standard Plasterboard.
Concrete (c) 90 Gold Batts 2.0 61/53 63/55
MASONRY SIDE
Wall (e) 75 MAB Polyester 11kg 59/51 61/53
• 1 x 13mm Gyprock
with Standard Plasterboard.
Rw ≥ 50 Additional Wall Thickness mm 110 138
CSR 4070 (a) Nil 52/43 54/45
Wall from STUD SIDE
TABLE E1 • 1 x 13mm Gyprock (b) 75 Acoustigard 11kg 61/53 63/55
Group D Aquachek Plasterboard.
(c) 90 Gold Batts 2.0 62/54 64/56
MASONRY SIDE
Refer to Wall (e) 75 MAB Polyester 11kg 60/52 62/54
• 1 x 13mm Gyprock
Manufacturer for
Standard Plasterboard.
FRL Details Additional Wall Thickness mm 110 138
CSR 4075 (a) Nil 52/43 54/45
STUD SIDE
• 1 x 13mm Gyprock (b) 75 Acoustigard 11kg 61/53 63/55
Aquachek Plasterboard.
(c) 90 Gold Batts 2.0 62/54 64/56
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 60/52 62/54
Aquachek Plasterboard.
Additional Wall Thickness mm 110 138
CSR 4080 (a) Nil 54/45 55/46
STUD SIDE
• 1 x 13mm Gyprock (b) 75 Acoustigard 11kg 63/55 64/56
Soundchek Plasterboard.
(c) 90 Gold Batts 2.0 64/56 65/57
MASONRY SIDE
• 1 x 13mm Gyprock (e) 75 MAB Polyester 11kg 62/54 63/55
Standard Plasterboard.
Additional Wall Thickness mm 110 138

E8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Both Sides

Single Brick, Block or Concrete Wall


Lining material as per system table, with Rw as stated.
fixed to studs.
Steel stud framing at 600mm
Steel stud framing at 600mm maximum centres.
maximum centres.
Lining material as per system table,
Cavity insulation as per system table. fixed to studs.

20mm minimum cavity between Cavity insulation as per system table.


framing and masonry wall.
20mm minimum cavity between
framing and masonry wall.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
CAVITY INFILL (Both Sides) Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 4105
(a) 75 Acoustigard 11kg 60/46 61/47

BOTH SIDES (b) 90 Gold Batts 2.0 61/47 62/48


• 1 x 6mm CeminSeal
Wallboard. (d) 75 MAB Polyester 11kg 58/44 59/45

Additional Wall Thickness mm 180 236

CSR 4110
(a) 75 Acoustigard 11kg 59/46 60/47

BOTH SIDES (b) 90 Gold Batts 2.0 60/47 61/48


• 1 x 10mm Gyprock Plus
Plasterboard. (d) 75 MAB Polyester 11kg 57/44 58/45

Additional Wall Thickness mm 188 244

CSR 4115
Tested (a) 75 Acoustigard 11kg 60/48 61/49
Brick,
Block or BOTH SIDES (b) 90 Gold Batts 2.0 61/49 62/50
Concrete • 1 x 13mm Gyprock
Wall Standard Plasterboard. (d) 75 MAB Polyester 11kg 58/46 59/47
with
Rw ≥ 42 Additional Wall Thickness mm 194 250

CSR 4120
Wall from (a) 75 Acoustigard 11kg 61/49 62/50
TABLE E1
BOTH SIDES (b) 90 Gold Batts 2.0 62/50 63/51
Group A
• 1 x 13mm Gyprock
Aquachek Plasterboard. (d) 75 MAB Polyester 11kg 59/47 60/48
Refer to Wall
Manufacturer for
FRL Details Additional Wall Thickness mm 194 250

CSR 4125
SIDE ONE
(a) 75 Acoustigard 11kg 62/50 63/51
• 1 x 13mm Gyprock
Aquachek Plasterboard. (b) 90 Gold Batts 2.0 63/51 64/52

SIDE TWO (d) 75 MAB Polyester 11kg 60/43 61/49


• 1 x 13mm Gyprock
Soundchek Plasterboard.
Additional Wall Thickness mm 194 250

CSR 4130
(a) 75 Acoustigard 11kg 63/51 64/52
BOTH SIDES
• 1 x 13mm Gyprock (b) 90 Gold Batts 2.0 64/52 65/53
Soundchek Plasterboard.
(d) 75 MAB Polyester 11kg 61/49 62/50

Additional Wall Thickness mm 194 250

GYPROCK® THE RED BOOK™ 1 E9


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Both Sides

Single Brick, Block or Concrete Wall


Lining material as per system table, with Rw as stated.
fixed to studs.
Steel stud framing at 600mm
Steel stud framing at 600mm maximum centres.
maximum centres.
Lining material as per system table,
Cavity insulation as per system table. fixed to studs.

20mm minimum cavity between Cavity insulation as per system table.


framing and masonry wall.
20mm minimum cavity between
framing and masonry wall.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
CAVITY INFILL (Both Sides) Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 4135
(a) 75 Acoustigard 11kg 62/48 63/49

BOTH SIDES (b) 90 Gold Batts 2.0 63/49 64/50


• 1 x 6mm CeminSeal
Wallboard. (d) 75 MAB Polyester 11kg 60/46 61/47

Additional Wall Thickness mm 180 236

CSR 4140
(a) 75 Acoustigard 11kg 62/49 63/50

BOTH SIDES (b) 90 Gold Batts 2.0 63/50 64/51


• 1 x 10mm Gyprock Plus
Plasterboard. (d) 75 MAB Polyester 11kg 60/47 61/48

Additional Wall Thickness mm 188 244

CSR 4145
Tested (a) 75 Acoustigard 11kg 63/51 64/52
Brick,
Block or BOTH SIDES (b) 90 Gold Batts 2.0 64/52 65/53
Concrete • 1 x 13mm Gyprock
Wall Standard Plasterboard. (d) 75 MAB Polyester 11kg 61/49 62/50
with
Rw ≥ 45 Additional Wall Thickness mm 194 250

CSR 4150
Wall from (a) 75 Acoustigard 11kg 63/51 64/52
TABLE E1
BOTH SIDES (b) 90 Gold Batts 2.0 64/52 65/53
Group B
• 1 x 13mm Gyprock
Aquachek Plasterboard. (d) 75 MAB Polyester 11kg 61/49 62/50
Refer to Wall
Manufacturer for
FRL Details Additional Wall Thickness mm 194 250

CSR 4155
SIDE ONE
(a) 75 Acoustigard 11kg 64/52 65/53
• 1 x 13mm Gyprock
Aquachek Plasterboard. (b) 90 Gold Batts 2.0 65/53 66/54

SIDE TWO (d) 75 MAB Polyester 11kg 62/50 63/51


• 1 x 13mm Gyprock
Soundchek Plasterboard.
Additional Wall Thickness mm 194 250

CSR 4160
(a) 75 Acoustigard 11kg 65/53 66/54

BOTH SIDES (b) 90 Gold Batts 2.0 66/54 67/55


• 1 x 13mm Gyprock
Soundchek Plasterboard. (d) 75 MAB Polyester 11kg 63/51 64/52

Additional Wall Thickness mm 194 250

E10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Both Sides

Single Brick, Block or Concrete Wall


Lining material as per system table, with Rw as stated.
fixed to studs.
Steel stud framing at 600mm
Steel stud framing at 600mm maximum centres.
maximum centres.
Lining material as per system table,
Cavity insulation as per system table. fixed to studs.

20mm minimum cavity between Cavity insulation as per system table.


framing and masonry wall.
20mm minimum cavity between
framing and masonry wall.
NOTE: Polyester insulation may NOT be
used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
CAVITY INFILL (Both Sides) Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 4165
(a) 75 Acoustigard 11kg 65/51 66/52

BOTH SIDES (b) 90 Gold Batts 2.0 66/52 67/53


• 1 x 6mm CeminSeal
Wallboard. (d) 75 MAB Polyester 11kg 63/49 64/50

Additional Wall Thickness mm 180 236

CSR 4170
(a) 75 Acoustigard 11kg 64/51 65/52

BOTH SIDES (b) 90 Gold Batts 2.0 65/52 66/53


• 1 x 10mm Gyprock Plus
Plasterboard. (d) 75 MAB Polyester 11kg 62/49 63/50

Additional Wall Thickness mm 188 244

CSR 4175
Tested (a) 75 Acoustigard 11kg 65/53 66/54
Brick,
Block or BOTH SIDES (b) 90 Gold Batts 2.0 66/54 67/55
Concrete • 1 x 13mm Gyprock
Wall Standard Plasterboard. (d) 75 MAB Polyester 11kg 63/51 64/52
with
Rw ≥ 47 Additional Wall Thickness mm 194 250

CSR 4180
Wall from (a) 75 Acoustigard 11kg 65/53 66/54
TABLE E1
BOTH SIDES (b) 90 Gold Batts 2.0 66/54 67/55
Group C
• 1 x 13mm Gyprock
Aquachek Plasterboard. (d) 75 MAB Polyester 11kg 63/51 64/52
Refer to Wall
Manufacturer for
FRL Details Additional Wall Thickness mm 194 250

CSR 4185
SIDE ONE
(a) 75 Acoustigard 11kg 66/54 67/55
• 1 x 13mm Gyprock
Aquachek Plasterboard. (b) 90 Gold Batts 2.0 67/55 68/56

SIDE TWO (d) 75 MAB Polyester 11kg 64/52 65/53


• 1 x 13mm Gyprock
Soundchek Plasterboard.
Additional Wall Thickness mm 194 250

CSR 4190
(a) 75 Acoustigard 11kg 67/55 68/56

BOTH SIDES (b) 90 Gold Batts 2.0 68/56 69/57


• 1 x 13mm Gyprock
Soundchek Plasterboard. (d) 75 MAB Polyester 11kg 65/53 66/54

Additional Wall Thickness mm 194 250

GYPROCK® THE RED BOOK™ 1 E11


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Side One + Furring Side Two

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm 28mm furring channel, clip fixed to


maximum centres. masonry with 40mm cavity.

Cavity insulation as per system table. Furring cavity insulation as per table.

20mm minimum cavity between Lining material as per system table


framing and masonry wall. fixed to furring.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
STUD CAVITY INFILL FURRING CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6) (Refer to TABLE B6)
CSR 4205
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 57/45 59/47

BOTH SIDES
(e) 75 Acoustigard 11kg 50 Acoustigard 14kg 59/47 61/49
• 1 x 13mm
Gyprock Standard
(f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 56/44 58/46
Plasterboard.

Additional Wall Thickness mm 150 178

CSR 4210 SIDE ONE


Tested • 1 x 13mm (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 58/46 59/47
Brick, Gyprock Aquachek
Block or Plasterboard. (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 60/48 61/49
Concrete
SIDE TWO (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 57/45 58/46
Wall
• 1 x 13mm
with Gyprock Standard
Rw ≥ 42 Additional Wall Thickness mm 150 178
Plasterboard.
CSR 4215
Wall from (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 58/46 59/47
TABLE E1 BOTH SIDES
(e) 75 Acoustigard 11kg 50 Acoustigard 14kg 60/48 61/49
Group A • 1 x 13mm
Gyprock Aquachek
(f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 57/45 58/46
Refer to Wall Plasterboard.
Manufacturer for
FRL Details Additional Wall Thickness mm 150 178

CSR 4220
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 59/47 60/49
BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 61/49 62/51
Soundchek
Plasterboard. (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 58/46 59/48

Additional Wall Thickness mm 150 178

E12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Side One + Furring Side Two

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm 28mm furring channel, clip fixed to


maximum centres. masonry with 40mm cavity.

Cavity insulation as per system table. Furring cavity insulation as per table.

20mm minimum cavity between Lining material as per system table


framing and masonry wall. fixed to furring.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
STUD CAVITY INFILL FURRING CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6) (Refer to TABLE B6)
CSR 4225 STUD SIDE (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 60/47 62/49
• 1 x 13mm
Gyprock Standard (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 62/49 64/51
Plasterboard.
FURRING SIDE (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 59/46 61/48
• 1 x 6mm CeminSeal
Wallboard. Additional Wall Thickness mm 143 171

CSR 4230
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 61/49 63/51

BOTH SIDES
(e) 75 Acoustigard 11kg 50 Acoustigard 14kg 63/51 65/53
• 1 x 13mm
Gyprock Standard
Tested Plasterboard.
(f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 59/47 61/49
Brick,
Block or Additional Wall Thickness mm 150 178
Concrete CSR 4235 STUD SIDE
Wall • 1 x 13mm (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 61/49 62/50
with Gyprock Aquachek
Rw ≥ 45 Plasterboard. (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 63/51 64/52

FURRING SIDE (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 60/48 61/49
Wall from • 1 x 13mm
TABLE E1 Gyprock Standard
Additional Wall Thickness mm 150 178
Group B Plasterboard.
CSR 4240
Refer to Wall (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 61/49 62/50
Manufacturer for
BOTH SIDES
FRL Details (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 63/51 64/52
• 1 x 13mm
Gyprock Aquachek
(f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 60/48 61/49
Plasterboard.

Additional Wall Thickness mm 150 178

CSR 4245
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 62/50 63/52
BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 64/52 65/54
Soundchek
Plasterboard. (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 61/49 62/51

Additional Wall Thickness mm 150 178

GYPROCK® THE RED BOOK™ 1 E13


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Side One + Furring Side Two

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm 28mm furring channel, clip fixed to


maximum centres. masonry with 40mm cavity.

Cavity insulation as per system table. Furring cavity insulation as per table.

20mm minimum cavity between Lining material as per system table


framing and masonry wall. fixed to furring.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64 92
WALL SYSTEM STUD BMT mm 0.50 0.55
WALL LININGS
REQUIREMENTS Nº
STUD CAVITY INFILL FURRING CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6) (Refer to TABLE B6)
CSR 4250 STUD SIDE (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 62/49 64/51
• 1 x 13mm
Gyprock Standard (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 64/51 66/53
Plasterboard.
FURRING SIDE (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 61/48 63/50
• 1 x 6mm CeminSeal
Wallboard. Additional Wall Thickness mm 143 171

CSR 4255
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 61/47 63/50

BOTH SIDES (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 63/49 65/52


• 1 x 10mm Gyprock
Plus Plasterboard. (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 59/45 61/48

Additional Wall Thickness mm 144 172

CSR 4260
Tested (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 62/50 64/52
Brick,
BOTH SIDES
Block or (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 64/52 66/54
• 1 x 13mm
Concrete Gyprock Standard
Wall (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 61/49 63/51
Plasterboard.
with
Rw ≥ 47 Additional Wall Thickness mm 150 178

CSR 4265 STUD SIDE


Wall from • 1 x 13mm (d) 50 Acoustigard 14kg 50 Acoustigard 14kg 63/51 64/52
TABLE E1 Gyprock Aquachek
Plasterboard. (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 65/53 66/54
Group C
FURRING SIDE (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 62/50 63/51
Refer to Wall
• 1 x 13mm
Manufacturer for
Gyprock Standard
FRL Details Additional Wall Thickness mm 150 178
Plasterboard.
CSR 4270
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 63/51 64/52

BOTH SIDES
(e) 75 Acoustigard 11kg 50 Acoustigard 14kg 65/53 66/54
• 1 x 13mm
Gyprock Aquachek
(f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 62/50 63/51
Plasterboard.

Additional Wall Thickness mm 150 178

CSR 4275
(d) 50 Acoustigard 14kg 50 Acoustigard 14kg 64/52 65/54
BOTH SIDES
• 1 x 13mm Gyprock (e) 75 Acoustigard 11kg 50 Acoustigard 14kg 66/54 67/56
Soundchek
Plasterboard. (f) 75 MAB Polyester 14kg 25 MAB Polyester 20kg 63/51 64/53

Additional Wall Thickness mm 150 178

E14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Side One + Furring Side Two

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm 28mm furring channel, clip fixed to


maximum centres. masonry with 40mm cavity.

Cavity insulation as per system table. Lining material as per system table
fixed to furring.
20mm minimum cavity between
framing and masonry wall.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64
WALL SYSTEM STUD BMT mm 0.50
WALL LININGS
REQUIREMENTS Nº
STUD CAVITY INFILL FURRING CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6) (Refer to TABLE B6)
CSR 4259
(b) 75 Acoustigard 11kg Nil 62/51

BOTH SIDES
(d) 50 Acoustigard 14kg Nil 61/50
• 1 x 13mm Gyprock
Soundchek
(e) 75 MAB Polyester 14kg Nil 60/49
Plasterboard.

Additional Wall Thickness mm 150

CSR 4264
(b) 75 Acoustigard 11kg Nil 62/51

BOTH SIDES (d) 50 Acoustigard 14kg Nil 61/50


• 1 x 13mm Gyprock
Tested EC08 Complete. (e) 75 MAB Polyester 14kg Nil 60/49
Brick,
Block or Additional Wall Thickness mm 150
Concrete CSR 10049
Wall (b) 75 Acoustigard 11kg Nil 62/51
with
Rw ≥ 50 BOTH SIDES (d) 50 Acoustigard 14kg Nil 61/50
• 1 x 13mm Gyprock
EC08 Extreme. (e) 75 MAB Polyester 14kg Nil 60/49
Wall from
TABLE E1
Additional Wall Thickness mm 150
Group D
CSR 4269
Refer to Wall (b) 75 Acoustigard 11kg Nil 62/51
Manufacturer for
BOTH SIDES
FRL Details (d) 50 Acoustigard 14kg Nil 61/50
• 1 x 16mm
Gyprock Fyrchek
(e) 75 MAB Polyester 14kg Nil 60/49
Plasterboard.

Additional Wall Thickness mm 150

CSR 4274
(b) 75 Acoustigard 11kg Nil 62/51

BOTH SIDES
(d) 50 Acoustigard 14kg Nil 61/50
• 1 x 16mm Gyprock
Fyrchek MR
(e) 75 MAB Polyester 14kg Nil 60/49
Plasterboard.

Additional Wall Thickness mm 150

GYPROCK® THE RED BOOK™ 1 E15


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Stud Side One + Furring Side Two

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Steel stud framing at 600mm 28mm furring channel, clip fixed to


maximum centres. masonry with 40mm cavity.

Cavity insulation as per system table. Lining material as per system table
fixed to furring.
20mm minimum cavity between
framing and masonry wall.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide Discontinuous Construction

STUD DEPTH mm 64
WALL SYSTEM STUD BMT mm 0.50
WALL LININGS
REQUIREMENTS Nº
STUD CAVITY INFILL FURRING CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6) (Refer to TABLE B6)
CSR 4276
(b) 75 Acoustigard 11kg Nil 63/52

BOTH SIDES
(d) 50 Acoustigard 14kg Nil 62/51
• 1 x 13mm
Gyprock Standard
(e) 75 MAB Polyester 14kg Nil 61/50
Plasterboard.

Additional Wall Thickness mm 150

CSR 4277 STUD SIDE


• 1 x 13mm (b) 75 Acoustigard 11kg Nil 64/53
Gyprock Aquachek
Plasterboard. (d) 50 Acoustigard 14kg Nil 63/52

FURRING SIDE (e) 75 MAB Polyester 14kg Nil 62/51


• 1 x 13mm
Gyprock Standard
Additional Wall Thickness mm 150
Plasterboard.
CSR 4278
Tested (b) 75 Acoustigard 11kg Nil 64/53
Brick,
BOTH SIDES
Block or (d) 50 Acoustigard 14kg Nil 63/52
• 1 x 13mm
Concrete Gyprock Aquachek
Wall (e) 75 MAB Polyester 14kg Nil 62/51
Plasterboard.
with
Rw ≥ 55 Additional Wall Thickness mm 150

CSR 10050
Wall from (a) 75 Acoustigard 11kg Nil 65/54
TABLE E1 BOTH SIDES
(c) 50 Acoustigard 14kg Nil 64/53
Group E • 1 x 13mm
Gyprock Fyrchek
(d) 75 MAB Polyester 14kg Nil 63/52
Refer to Wall Plasterboard.
Manufacturer for
FRL Details Additional Wall Thickness mm 150

CSR 10051
(a) 75 Acoustigard 11kg Nil 66/55

BOTH SIDES (c) 50 Acoustigard 14kg Nil 65/54


• 1 x 13mm Gyprock
EC08 Complete. (d) 75 MAB Polyester 14kg Nil 64/53

Additional Wall Thickness mm 150

CSR 10052
(a) 75 Acoustigard 11kg Nil 66/55

BOTH SIDES (c) 50 Acoustigard 14kg Nil 65/54


• 1 x 13mm Gyprock
EC08 Extreme. (d) 75 MAB Polyester 14kg Nil 64/53

Additional Wall Thickness mm 150

E16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Furring Channel Both Sides

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to studs. with Rw as stated.

Rondo Nº129 furring channel fixed to Rondo Nº129 furring channel fixed to
masonry at 600mm maximum centres masonry at 600mm maximum centres
with a 40mm cavity. with a 40mm cavity.

Cavity insulation as per system table. Lining material as per system table
fixed to furring.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide NOT Deemed Discontinuous Construction

WALL SYSTEM CAVITY INFILL SIDE 1 CAVITY INFILL SIDE 2 Rw /


WALL LININGS
REQUIREMENTS Nº (Refer to TABLE B6) (Refer to TABLE B6) Rw+Ctr

CSR 4280
(b) 50 Acoustigard 14kg Nil 51/37
BOTH SIDES
• 1 x 13mm
(d) 50 MAB Polyester 11kg Nil 48/34
Gyprock Standard
Plasterboard
Additional Wall Thickness mm 84

CSR 4281 SIDE ONE


Tested • 1 x 13mm (b) 50 Acoustigard 14kg Nil 52/38
Brick, Gyprock Aquachek
Block or Plasterboard.
Concrete (d) 50 MAB Polyester 11kg Nil 49/35
SIDE TWO
Wall • 1 x 13mm
with Gyprock Standard Additional Wall Thickness mm 84
Rw ≥ 42 Plasterboard.
CSR 4282
Wall from (b) 50 Acoustigard 14kg Nil 52/38
TABLE E1 BOTH SIDES
Group A • 1 x 13mm
(d) 50 MAB Polyester 11kg Nil 49/35
Gyprock Aquachek
Refer to Wall Plasterboard.
Manufacturer for
FRL Details Additional Wall Thickness mm 84

CSR 4283
(b) 50 Acoustigard 14kg Nil 53/40
BOTH SIDES
• 1 x 13mm Gyprock
(d) 50 MAB Polyester 11kg Nil 50/37
Soundchek
Plasterboard
Additional Wall Thickness mm 84

GYPROCK® THE RED BOOK™ 1 E17


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Furring Channel Both Sides

Lining material as per system table Single Brick, Block or Concrete Wall
fixed to furring. with Rw as stated.

Rondo Nº129 furring channel fixed to Rondo Nº129 furring channel fixed to
masonry at 600mm maximum centres masonry at 600mm maximum centres
with a 40mm cavity. with a 40mm cavity.

Cavity insulation as per system table. Lining material as per system table
fixed to furring.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide NOT Deemed Discontinuous Construction

WALL SYSTEM CAVITY INFILL SIDE 1 CAVITY INFILL SIDE 2 Rw /


WALL LININGS
REQUIREMENTS Nº (Refer to TABLE B6) (Refer to TABLE B6) Rw+Ctr

CSR 4290
(b) 50 Acoustigard 14kg Nil 53/41
BOTH SIDES
• 1 x 13mm
(c) 25 Acoustigard 24kg Nil 54/42
Gyprock Standard
Plasterboard
Additional Wall Thickness mm 106

CSR 4291 SIDE ONE


• 1 x 13mm (b) 50 Acoustigard 14kg Nil 54/42
Gyprock Aquachek
Plasterboard.
(c) 25 Acoustigard 24kg Nil 55/43
SIDE TWO
• 1 x 13mm
Gyprock Standard Additional Wall Thickness mm 106
Plasterboard.
CSR 4292
Tested (b) 50 Acoustigard 14kg 50 Acoustigard 14kg 64/50
Brick, BOTH SIDES
Block or • 1 x 13mm Gyprock
Concrete (c) 25 Acoustigard 24kg 25 Acoustigard 24kg 64/50
Soundchek
Wall Plasterboard.
with Additional Wall Thickness mm 106
Rw ≥ 55
CSR 4293
Wall from (b) 50 Acoustigard 14kg 50 Acoustigard 14kg 64/50
TABLE E1
Group E BOTH SIDES
• 1 x 13mm Gyprock (c) 25 Acoustigard 24kg 25 Acoustigard 24kg 64/50
Refer to Wall EC08 Complete.
Manufacturer for
FRL Details Additional Wall Thickness mm 106

CSR 4294
(b) 50 Acoustigard 14kg 50 Acoustigard 14kg 64/50

BOTH SIDES
• 1 x 16mm Gyprock (c) 25 Acoustigard 24kg 25 Acoustigard 24kg 64/50
Fyrchek Plasterboard

Additional Wall Thickness mm 112

CSR 4295
(b) 50 Acoustigard 14kg 50 Acoustigard 14kg 64/50
BOTH SIDES
• 1 x 16mm Gyprock
(c) 25 Acoustigard 24kg 25 Acoustigard 24kg 64/50
Fyrchek MR
Plasterboard
Additional Wall Thickness mm 112

E18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Furring + Direct Fixed

Lining material as per system table, Single Brick, Block or Concrete Wall
direct fixed to furring. with Rw as stated.

28mm furring channel at 600mm Optional lining material as per system


maximum centres, fixed to masonry with table, direct fixed to masonry.
40mm cavity.

Cavity insulation as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide NOT Deemed Discontinuous Construction
WALL SYSTEM CAVITY INFILL
WALL LININGS Rw / Rw+Ctr
REQUIREMENTS Nº (Refer to TABLE B6)

CSR 4400
MASONRY SIDE (b) 50 Acoustigard 14kg 53/43
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 50/40
FURRING SIDE
• 1 x 9mm CeminSeal
Wallboard. Additional Wall Thickness mm 67

CSR 4401
MASONRY SIDE (b) 50 Acoustigard 14kg 50/40
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 47/37
FURRING SIDE
• 1 x 13mm Gyprock
Standard Plasterboard. Additional Wall Thickness mm 71

CSR 10058
Tested MASONRY SIDE (a) 50 Acoustigard 14kg 54/44
Brick, • 1 x 13mm Gyprock EC08
Block or Extreme.
Concrete (c) 50 MAB Polyester 11kg 51/41
FURRING SIDE
Wall • 1 x 13mm Gyprock EC08
with Extreme. Additional Wall Thickness mm 71
Rw ≥ 45
CSR 4405
Wall from MASONRY SIDE (b) 50 Acoustigard 14kg 51/41
TABLE E1 • 1 x 13mm Gyprock
Group B Aquachek Plasterboard.
(d) 50 MAB Polyester 11kg 48/38
FURRING SIDE
Refer to Wall
• 1 x 13mm Gyprock
Manufacturer for
FRL Details Aquachek Plasterboard. Additional Wall Thickness mm 71

CSR 4406
MASONRY SIDE (b) 50 Acoustigard 14kg 53/43
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 50/40
FURRING SIDE
• 1 x 13mm Gyprock
Soundchek Plasterboard. Additional Wall Thickness mm 71

CSR 4407
MASONRY SIDE (b) 50 Acoustigard 14kg 54/45
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 51/42
FURRING SIDE
• 2 x 13mm Gyprock
Aquachek Plasterboard. Additional Wall Thickness mm 84

GYPROCK® THE RED BOOK™ 1 E19


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Furring + Direct Fixed

Lining material as per system table, Single Brick, Block or Concrete Wall
direct fixed to furring. with Rw as stated.

28mm furring channel at 600mm Optional lining material as per system


maximum centres, fixed to masonry with table, direct fixed to masonry.
40mm cavity.

Cavity insulation as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide NOT Deemed Discontinuous Construction
WALL SYSTEM CAVITY INFILL
WALL LININGS Rw / Rw+Ctr
REQUIREMENTS Nº (Refer to TABLE B6)

CSR 4412
MASONRY SIDE (b) 50 Acoustigard 14kg 55/45
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 52/42
FURRING SIDE
• 1 x 9mm CeminSeal
Wallboard. Additional Wall Thickness mm 67

CSR 4413
MASONRY SIDE (b) 50 Acoustigard 14kg 52/42
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 49/39
FURRING SIDE
• 1 x 13mm Gyprock
Standard Plasterboard. Additional Wall Thickness mm 71

CSR 10063
Tested MASONRY SIDE (a) 50 Acoustigard 14kg 56/46
Brick, • 1 x 13mm Gyprock EC08
Block or Extreme.
Concrete (c) 50 MAB Polyester 11kg 53/43
FURRING SIDE
Wall • 1 x 13mm Gyprock EC08
with Extreme. Additional Wall Thickness mm 71
Rw ≥ 47
CSR 4415
Wall from MASONRY SIDE (b) 50 Acoustigard 14kg 53/43
TABLE E1 • 1 x 13mm Gyprock
Group C Aquachek Plasterboard.
(d) 50 MAB Polyester 11kg 50/40
FURRING SIDE
Refer to Wall
• 1 x 13mm Gyprock
Manufacturer for
FRL Details Aquachek Plasterboard. Additional Wall Thickness mm 71

CSR 4418
MASONRY SIDE (b) 50 Acoustigard 14kg 55/45
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 52/42
FURRING SIDE
• 1 x 13mm Gyprock
Soundchek Plasterboard. Additional Wall Thickness mm 71

CSR 4419
MASONRY SIDE (b) 50 Acoustigard 14kg 56/47
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 53/44
FURRING SIDE
• 2 x 13mm Gyprock
Aquachek Plasterboard. Additional Wall Thickness mm 84

E20 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Furring + Direct Fixed

Lining material as per system table, Single Brick, Block or Concrete Wall
direct fixed to furring. with Rw as stated.

28mm furring channel at 600mm Optional lining material as per system


maximum centres, fixed to masonry with table, direct fixed to masonry.
40mm cavity.

Cavity insulation as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide NOT Deemed Discontinuous Construction
WALL SYSTEM CAVITY INFILL
WALL LININGS Rw / Rw+Ctr
REQUIREMENTS Nº (Refer to TABLE B6)

CSR 4422
MASONRY SIDE (b) 50 Acoustigard 14kg 58/49
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 55/46
FURRING SIDE
• 1 x 9mm CeminSeal
Wallboard. Additional Wall Thickness mm 67

CSR 4423
MASONRY SIDE (b) 50 Acoustigard 14kg 55/46
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 52/43
FURRING SIDE
• 1 x 13mm Gyprock
Standard Plasterboard. Additional Wall Thickness mm 71

CSR 10068
Tested MASONRY SIDE (a) 50 Acoustigard 14kg 59/50
Brick, • 1 x 13mm Gyprock EC08
Block or Extreme.
Concrete (c) 50 MAB Polyester 11kg 56/47
FURRING SIDE
Wall • 1 x 13mm Gyprock EC08
with Extreme. Additional Wall Thickness mm 71
Rw ≥ 50
CSR 4427
Wall from MASONRY SIDE (b) 50 Acoustigard 14kg 56/47
TABLE E1 • 1 x 13mm Gyprock
Group D Aquachek Plasterboard.
(d) 50 MAB Polyester 11kg 53/44
FURRING SIDE
Refer to Wall
• 1 x 13mm Gyprock
Manufacturer for
FRL Details Aquachek Plasterboard. Additional Wall Thickness mm 71

CSR 4428
MASONRY SIDE (b) 50 Acoustigard 14kg 58/49
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 55/46
FURRING SIDE
• 1 x 13mm Gyprock
Soundchek Plasterboard. Additional Wall Thickness mm 71

CSR 4429
MASONRY SIDE (b) 50 Acoustigard 14kg 59/51
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 56/48
FURRING SIDE
• 2 x 13mm Gyprock
Aquachek Plasterboard. Additional Wall Thickness mm 84

GYPROCK® THE RED BOOK™ 1 E21


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Furring + Direct Fixed

Lining material as per system table, Single Brick, Block or Concrete Wall
direct fixed to furring. with Rw as stated.

28mm furring channel at 600mm Optional lining material as per system


maximum centres, fixed to masonry with table, direct fixed to masonry.
40mm cavity.

Cavity insulation as per system table.

NOTE: Polyester insulation may NOT be


used where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A118


Refer to Book 3 Commercial & Multi-Residential Installation Guide NOT Deemed Discontinuous Construction
WALL SYSTEM CAVITY INFILL
WALL LININGS Rw / Rw+Ctr
REQUIREMENTS Nº (Refer to TABLE B6)

CSR 4432 (a) Nil 55/46


MASONRY SIDE
• 1 x 13mm Gyprock
Standard Plasterboard. (c) 50 Acoustigard 14kg 62/53

FURRING SIDE (e) 50 MAB Polyester 11kg 59/50


• 1 x 9mm CeminSeal
Wallboard.
Additional Wall Thickness mm 67

CSR 4433 (a) Nil 52/43


MASONRY SIDE
• 1 x 13mm Gyprock
Standard Plasterboard. (c) 50 Acoustigard 14kg 59/50

FURRING SIDE (e) 50 MAB Polyester 11kg 56/47


• 1 x 13mm Gyprock
Standard Plasterboard.
Additional Wall Thickness mm 71

CSR 10073 (a) Nil 56/47


Tested MASONRY SIDE
Brick, • 1 x 13mm Gyprock EC08
Block or Extreme. (b) 50 Acoustigard 14kg 63/54
Concrete FURRING SIDE
Wall (d) 50 MAB Polyester 11kg 60/51
• 1 x 13mm Gyprock EC08
with Extreme.
Rw ≥ 55 Additional Wall Thickness mm 71

CSR 4437 (a) Nil 53/44


Wall from MASONRY SIDE
TABLE E1 • 1 x 13mm Gyprock
Group E Aquachek Plasterboard. (c) 50 Acoustigard 14kg 60/51

FURRING SIDE (e) 50 MAB Polyester 11kg 57/48


Refer to Wall
• 1 x 13mm Gyprock
Manufacturer for
FRL Details Aquachek Plasterboard.
Additional Wall Thickness mm 71

CSR 4438 (a) Nil 55/46


MASONRY SIDE
• 1 x 13mm Gyprock
Standard Plasterboard. (c) 50 Acoustigard 14kg 62/53

FURRING SIDE (e) 50 MAB Polyester 11kg 59/50


• 1 x 13mm Gyprock
Soundchek Plasterboard.
Additional Wall Thickness mm 71

CSR 4439
MASONRY SIDE (b) 50 Acoustigard 14kg 65/57
• 1 x 13mm Gyprock
Standard Plasterboard.
(d) 50 MAB Polyester 11kg 62/54
FURRING SIDE
• 2 x 13mm Gyprock
Soundchek Plasterboard. Additional Wall Thickness mm 84

E22 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS CSR Hebel Internal Wall Systems – Steel Stud + PowerPanel

Lining material as per system table, CSR Hebel PowerPanel


fixed to steel framing. (tongue and groove).

64mm steel studs at 600mm centres. Lining material as per system table,
direct fixed to Hebel panels.
Cavity insulation as per system table.

Minimum 20mm gap.

NOTE: *For wall heights up to 3.3m.


Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

ACOUSTIC LOGIC REPORT:


SYSTEM SPECIFICATION
Refer to Hebel for further information 20210103.7/1608A/R2/TB
Discontinuous Construction

FRL SYSTEM CAVITY INFILL


WALL LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)

CSR 21070
(a) 75 Acoustigard 11kg 61/50
Up to
– /90/90* BOTH SIDES
• 1 x 13mm Gyprock (c) 75 MAB Polyester 14kg 61/50
(from both sides)
Standard Plasterboard.
FCO 3035
Wall Thickness mm 185

SYSTEM SPECIFICATIONS CSR Hebel Internal Wall Systems – Steel Furring + PowerPanel + Steel Stud

Lining material as per system table, Cavity insulation as per system table.
fixed to furring.
64mm steel studs at 600mm centres.
Rondo Nº129 furring channel at
600mm maximum centres. Lining material as per system table,
direct fixed to framing.
Cavity insulation as per system table
in a 43mm cavity. 75mm CSR Hebel PowerPanel
(tongue and groove).

Minimum 35mm air gap.


NOTE: *For wall heights up to 3.3m.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

ACOUSTIC LOGIC REPORT:


SYSTEM SPECIFICATION
Refer to Hebel for further information 20210103.7/1608A/R2/TB
Discontinuous Construction

FRL SYSTEM FURRING CAVITY INFILL STUD CAVITY INFILL


WALL LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6) (Refer to TABLE B6)

CSR 21072

Up to (a) 50 Acoustigard 14kg 75 Acoustigard 11kg 64/50


– /90/90* BOTH SIDES
(from both sides) • 1 x 13mm Gyprock
Standard Plasterboard. (b) 50 Acoustigard 14kg 75 MAB Polyester 14kg 64/50
FCO 3035

Wall Thickness mm 243

GYPROCK® THE RED BOOK™ 1 E23


SYSTEM SPECIFICATIONS CSR Hebel Internal Wall Systems – PowerPanel50 Intertenancy Systems

Lining material as per system table, Timber or steel framing.


fixed to framing.
Cavity infill as per system table.
Timber or steel framing.
Lining material as per system table,
Cavity infill as per system table. fixed to framing.

Hebel PowerPanel50. Air gap between PowerPanel50 and


framing.
Air gap between PowerPanel50 and
NOTE: Polyester insulation may NOT be
framing.
used where the system has non-combustible
construction requirements.
NOTE: *Acoustic values in the table are
based on a 10mm air gap between the
#
Applicable only to walls supporting non-fire
PowerPanel50 and framing. rated structures such as floors and roofs.

SYSTEM SPECIFICATION ACOUSTIC LOGIC REPORT: 20140366.35/0202A/R6/GW


Refer to CSR for further information Discontinuous Construction

STUD DEPTH mm 70 90
FRL System
WALL LININGS SYSTEM CAVITY INFILL (sides)
Report Icon Rw / Rw+Ctr* Rw / Rw+Ctr*
Nº (Refer to TABLE B6)

CSR 21245 Nil 38/29 –

CSR 21246 90 Gold Batts 2.0 – both sides 61/47 –


–/90/90 BOTH SIDES
90/90/90# • 1 x 13mm
CSR 21269 Nil – 40/31
Gyprock Standard
FCO 3255 Plasterboard.
CSR 21270 90 Gold Batts 2.0 – both sides – 64/50

Wall Thickness mm 236 276

CSR 21251 Nil 39/30 –

CSR 21252 90 Gold Batts 2.0 – both sides 64/50 –


–/90/90 BOTH SIDES
90/90/90# • 1 x 9mm CeminSeal CSR 21275 Nil – 40/31
Wallboard.
FCO 3255
CSR 21276 90 Gold Batts 2.0 – both sides – 67/52

Wall Thickness mm 228 268

E24 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS AFS Internal Wall Systems – Rediwall® System

AFS Rediwall® System

ACOUSTIC LOGIC REPORT:


SYSTEM SPECIFICATION
Refer to AFS Rediwall® Design Guide for further information Refer to AFS
NOT Deemed Discontinuous Construction

FRL SYSTEM
SYSTEM DESCRIPTION Rw / Rw+Ctr
Report Nº

CSR 36001

AFS FORMWORK 50/45


90/90/90 • RW110C Wall

Refer to AFS CONCRETE CORE


• 105mm nominal Wall Thickness mm 110

CSR 37001

AFS FORMWORK 54/50


240/240/240 • RW156C Wall

Refer to AFS CONCRETE CORE


• 151mm nominal Wall Thickness mm 156

CSR 38001

AFS FORMWORK 58/53


240/240/240 • RW200C Wall

Refer to AFS CONCRETE CORE


• 195mm nominal Wall Thickness mm 200

CSR 39001

AFS FORMWORK 60/55


240/240/240 • RW256C Wall

Refer to AFS CONCRETE CORE


• 251mm nominal Wall Thickness mm 256

GYPROCK® THE RED BOOK™ 1 E25


SYSTEM SPECIFICATIONS AFS Internal Wall Systems – Rediwall® + Steel Stud

Lining material as per system table, AFS Rediwall® System


fixed to stud framing.
Cavity insulation as per system table.
64mm steel studs at 600mm centres.
20mm gap.

ACOUSTIC LOGIC REPORT:


SYSTEM SPECIFICATION
Refer to AFS Rediwall® Design Guide for further information Refer to AFS
Discontinuous Construction

FRL SYSTEM SYSTEM CAVITY INFILL


WALL LININGS Rw / Rw+Ctr
Report Nº DESCRIPTION (Refer to TABLE B6)

CSR 36101
EXTERNAL SIDE
AFS FORMWORK
• Nil 75 Acoustigard 14kg 62/52
90/90/90 • RW110C Wall
INTERNAL (STUD) SIDE
Refer to AFS CONCRETE CORE
• 1 x 6mm Cemintel
• 105mm nominal
Wallboard.
Min. Wall Thickness mm 200

CSR 37101
EXTERNAL SIDE
AFS FORMWORK
• Nil 75 Acoustigard 14kg 65/55
240/240/240 • RW156C Wall
INTERNAL (STUD) SIDE
Refer to AFS CONCRETE CORE
• 1 x 6mm Cemintel
• 151mm nominal
Wallboard.
Min. Wall Thickness mm 246

CSR 37302 SIDE ONE


• 1 x 13mm
AFS FORMWORK Gyprock Standard 75 Acoustigard 14kg 65/55
240/240/240 • RW156C Wall Plasterboard.

Refer to AFS CONCRETE CORE SIDE TWO


• 151mm nominal • 1 x 13mm
Gyprock Standard Min. Wall Thickness mm 266
Plasterboard.
CSR 37503 SIDE ONE
• 1 x 13mm
AFS FORMWORK
Gyprock Standard 75 Acoustigard 14kg 65/55
240/240/240 • RW156C Wall
Plasterboard.
Refer to AFS CONCRETE CORE
SIDE TWO
• 151mm nominal
• 1 x 6mm Cemintel
Min. Wall Thickness mm 259
Wallboard.

E26 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Blade Columns – Rw

Boxed or double studs Single Block or Concrete Column


64mm x 0.5BMT min. as per system table.

Rondo M515/H515 top hat framing to Rondo M515/H515 top hat framing to
system specifications in 20mm min. cavity. system specifications in 20mm min. cavity.
OR OR
Rondo Nº129 furring channel framing to Rondo Nº129 furring channel framing to
system specifications in 33mm min. cavity. system specifications in 33mm min. cavity.

Lining material as per system table Lining material as per system table fixed to
fixed to furring. steel framing.

Cavity insulation one side or both sides


as per system table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A127


Refer to Book 3 Commercial & Multi-Residential Installation Guide Deemed Discontinuous Construction

CAVITY INFILL
CAVITY ADDITIONAL
COLUMN SYSTEM WALL LININGS (a) ONE SIDE
WIDTH WIDTH Rw
(Refer to TABLE E2) Nº BOTH SIDES (b) BOTH SIDES
MIN. MIN.
(Refer to TABLE B6)

CSR 4850
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock Standard


20/33 66/92
Plasterboard.

(b) 25 Acoustigard 32kg ≥55

CSR 4852
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock Aquachek


20/33 66/92
Plasterboard.

(b) 25 Acoustigard 32kg ≥55


200mm
Concrete CSR 4854
OR
(a) 25 Acoustigard 32kg ≥50
190mm
Core Filled • 1 x 13mm Gyprock Fyrchek
20/33 66/92
Blockwork Plasterboard.

For wall FRL refer (b) 25 Acoustigard 32kg ≥55


to Section C
Steel Framed Wall
Systems CSR 4856
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock Fyrchek


20/33 66/92
MR Plasterboard.

(b) 25 Acoustigard 32kg ≥55

CSR 4858
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock EC08


20/33 66/92
Complete Plasterboard.

(b) 25 Acoustigard 32kg ≥55

GYPROCK® THE RED BOOK™ 1 E27


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Blade Columns – Rw

Boxed or double studs Single Block or Concrete Column


64mm x 0.5BMT min. as per system table.

Rondo M515/H515 top hat framing to Rondo M515/H515 top hat framing to
system specifications in 20mm min. cavity. system specifications in 20mm min. cavity.
OR OR
Rondo Nº129 furring channel framing to Rondo Nº129 furring channel framing to
system specifications in 33mm min. cavity. system specifications in 33mm min. cavity.

Lining material as per system table Lining material as per system table fixed to
fixed to furring. steel framing.

Cavity insulation one side or both sides


as per system table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A127


Refer to Book 3 Commercial & Multi-Residential Installation Guide Deemed Discontinuous Construction

CAVITY INFILL
CAVITY ADDITIONAL
COLUMN SYSTEM WALL LININGS (a) ONE SIDE
WIDTH WIDTH Rw
(Refer to TABLE E2) Nº BOTH SIDES (b) BOTH SIDES
MIN. MIN.
(Refer to TABLE B6)

CSR 4859
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock Standard


20/33 66/92
Plasterboard.

(b) 25 Acoustigard 32kg ≥55

CSR 4860
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock Soundchek


20/33 66/92
Plasterboard.

(b) 25 Acoustigard 32kg ≥55

CSR 4862
150mm
(a) 25 Acoustigard 32kg ≥50
Concrete
• 1 x 13mm Gyprock Fyrchek
For wall FRL refer 20/33 66/92
Plasterboard.
to Section C
Steel Framed Wall (b) 25 Acoustigard 32kg ≥55
Systems

CSR 4864
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock Fyrchek


20/33 66/92
MR Plasterboard.

(b) 25 Acoustigard 32kg ≥55

CSR 4866
(a) 25 Acoustigard 32kg ≥50

• 1 x 13mm Gyprock EC08


20/33 66/92
Complete Plasterboard.

(b) 25 Acoustigard 32kg ≥55

E28 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Blade Columns – Rw+Ctr

Boxed or double studs Single Block or Concrete Column


64mm x 0.5BMT min. as per system table.

Rondo M515/H515 top hat framing to Rondo M515/H515 top hat framing to
system specifications in 30mm min. cavity. system specifications in 30mm min. cavity.
OR OR
Rondo Nº129 furring channel framing to Rondo Nº129 furring channel framing to
system specifications in 33mm min. cavity. system specifications in 33mm min. cavity.

Lining material as per system table Lining material as per system table fixed to
fixed to framing. steel framing.

Cavity insulation both sides as per


system table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A127


Refer to Book 3 Commercial & Multi-Residential Installation Guide Deemed Discontinuous Construction
CAVITY ADDITIONAL CAVITY INFILL
COLUMN SYSTEM WALL LININGS
WIDTH WIDTH BOTH SIDES Rw+Ctr
(Refer to TABLE E2) Nº BOTH SIDES
MIN. MIN. (Refer to TABLE B6)

CSR 4870

• 1 x 13mm Gyprock EC08


30/33 86/92 (b) 25 Acoustigard 24kg ≥50
Complete Plasterboard.

CSR 4872
200mm
Concrete
• 1 x 16mm Gyprock Fyrchek
For wall FRL refer 30/33 92/98 (b) 25 Acoustigard 24kg ≥50
Plasterboard.
to Section C
Steel Framed Wall
Systems

CSR 4874

• 1 x 16mm Gyprock Fyrchek MR


30/33 92/98 (b) 25 Acoustigard 24kg ≥50
Plasterboard.

GYPROCK® THE RED BOOK™ 1 E29


SYSTEM SPECIFICATIONS Masonry/Concrete Internal Wall Systems – Blade Columns – Rw+Ctr

Boxed or double studs Single Block or Concrete Column


64mm x 0.5BMT min. as per system table.

Rondo M515/H515 top hat framing to Rondo M515/H515 top hat framing to
system specifications in 50mm min. cavity. system specifications in 50mm min. cavity.
OR OR
Rondo Nº129 furring channel framing to Rondo Nº129 furring channel framing to
system specifications in 50mm min. cavity. system specifications in 50mm min. cavity.

Lining material as per system table Lining material as per system table fixed to
fixed to framing. steel framing.

Cavity insulation both sides as per


system table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A127


Refer to Book 3 Commercial & Multi-Residential Installation Guide Deemed Discontinuous Construction
CAVITY ADDITIONAL CAVITY INFILL
COLUMN SYSTEM WALL LININGS
WIDTH WIDTH BOTH SIDES Rw+Ctr
(Refer to TABLE E2) Nº BOTH SIDES
MIN. MIN. (Refer to TABLE B6)

CSR 4876

• 1 x 13mm Gyprock EC08


50 126 (b) 25 Acoustigard 24kg ≥50
Complete Plasterboard.

150mm
Concrete CSR 4878
OR
190mm
Core Filled • 1 x 16mm Gyprock Fyrchek
50 132 (b) 25 Acoustigard 24kg ≥50
Blockwork Plasterboard.

For wall FRL refer


to Section C
Steel Framed Wall
Systems CSR 4880

• 1 x 16mm Gyprock Fyrchek MR


50 132 (b) 25 Acoustigard 24kg ≥50
Plasterboard.

CSR 4882

• 2 x 13mm Gyprock EC08


50 152 (b) 25 Acoustigard 24kg ≥50
Complete Plasterboard.

120mm
Concrete CSR 4884
OR
140mm
Core Filled • 2 x 16mm Gyprock Fyrchek
50 164 (b) 25 Acoustigard 24kg ≥50
Blockwork Plasterboard.

For wall FRL refer


to Section C
Steel Framed Wall
Systems CSR 4886

• 2 x 16mm Gyprock Fyrchek MR


50 164 (b) 25 Acoustigard 24kg ≥50
Plasterboard.

E30 GYPROCK® THE RED BOOK™ 1


EXTERNAL
WALL SYSTEMS
F
SECTION CONTENTS
Introduction F2
Design Considerations F2
System Selection Tables

Direct Fix Steel Frame F7


Boundary Wall F22

Cavity Steel Frame F9


Cavity Timber Frame F24

Cavity Steel Girt F15


Masonry with
F30
Timber Frame

Masonry with Steel Frame F17


Hebel PowerPanel F32

Direct Fix Timber Frame F18


Thermally Enhanced
Systems Including Thermal F34
Bridging Considerations

Glasroc X Systems F55

GYPROCK® THE RED BOOK™ 1 F1


INTRODUCTION DESIGN
This section provides important design
information and detailed selection and
CONSIDERATIONS
specification tables necessary for the correct
use of CSR external wall systems. DESIGN RESPONSIBILITY
This guide represents good practice, though it is not
CSR Gyprock and Cemintel steel and timber framed intended as an exhaustive statement of all relevant
external wall systems use Cemintel fibre cement exterior information. It remains the responsibility of the building
linings and may include one or more layers of Gyprock designer to verify that the chosen cladding system is
plasterboard fixed to one or both sides of the framing. A suitable for the requirements of any given project. CSR
selection of masonry, concrete and steel sheet systems recommends that a comprehensive assessment of the
are also included. A wide range of systems is available performance requirements for the external walls be
for both fire rated and non-fire rated applications in non- undertaken prior to selection of the external wall and
loadbearing and loadbearing walls. Fire rating can apply cladding system, including for:
from the outside only or in both directions.
• Structural design
These wall systems are suitable for many building types
including commercial, industrial, institutional, and low, • Weatherproofing
medium and high-rise residential construction. • Fire resistance
This Guide should be read in conjunction with the • Energy efficiency
relevant Cemintel system installation manual (available
• Acoustic performance
for download from www.cemintel.com.au), with Book 2
Residential Installation Guide and Book 3 Commercial & • Condensation management
Multi-Residential Installation Guide (available for download
CSR offers online digital tools for the most updated
from www.gyprock.com.au).
information, including but not limited to update of
This section is divided into two parts: products/components, inclusion of new and modified
systems, to meet the requirements of the National
• Total R-Values calculated in the first part on page F7
Construction Code of Australia (NCC) and any relevant
to page F33 DO NOT INCLUDE consideration of the
Australian Standards. For the most up-to-date product &
effects of thermal bridging.
system performance information, visit:
• Total R-Values calculated in the second part on page
CSR System Selector: https://apps.csr.com.au/
F34 to page F54 INCLUDE consideration of the
systemselector/search-option
effect of thermal bridging.
CSR Thermal Calculator: https://apps.csr.com.au/
thermalcalculator

STRUCTURAL DESIGN
All walls must be designed for the applied loads.
Loadbearing walls and walls subject to wind pressures
shall be appropriately designed to meet the relevant
Australian Standards or construction manuals. Walls
lined with Gyprock fire grade plasterboard meet the
requirements of NCC2022 Clause S6C6 [NCC2019: Spec
C1.8: 3.4] Walls generally

Cladding
Cladding must be designed for the applicable wind loads.
To determine the maximum framing spacing, any batten
requirements, and the cladding fixing specifications, refer
to the relevant Cemintel system installation guide. It is the
responsibility of the building designer to determine the
wind loads or classifications of the building and to assess
the suitability of the system.

F2 GYPROCK® THE RED BOOK™ 1


Internal Linings equalisation. Any water which does enter can drain
away or can evaporate due to airflow throughout the
Internal linings are to be designed for the applicable wind
cavity. An effective air seal to the building frame must
pressures calculated in accordance with AS/NZS 1170
be provided behind the cavity and CSR recommends
series. For Gyprock plasterboard linings, the sheet fixing
the use of Cemintel Rigid Air Barrier.
details are to be in accordance with Book 2 and 3. For
other lining materials, consult the manufacturer. • Direct Fix System with Face Sealing: In many Australian
residential applications, cladding is fixed directly to the
frame. A degree of sealing is required at joints and gaps
Structural Bracing to prevent water ingress. Although not as effective
External cladding materials, including Cemintel cladding, as ventilated and drained cavity systems, direct fix
are not intended to provide wall bracing. Bracing must be systems can be an effective means of weatherproofing
provided in the structural framing in the normal manner by low risk buildings, i.e., in low rise buildings in low wind
using methods such as strap bracing or sheet bracing. pressure areas.
• Unique System: A unique system uses methods or a
Control Joints combination of methods of achieving weatherproofing
other than described above.
Control joints for interior linings may be required to allow
for structural movement, and allowance for movement
must be made through the frame, linings and all elements WALL WRAP/SARKING
within the wall. Control joints are also required for some SELECTION
cladding types. For further information refer to Book 2
To ensure occupant comfort and protection of the building
and 3 and the relevant cladding installation manual for
frame, the following factors should be considered during
detailed information.
the selection of the correct wall wrap/sarking.
• Condensation Risk: This is a complex problem and can
Seismic Loads occur under a variety of conditions (not just in cold and
Seismic actions must be considered for building tropical climates) so selection of the right wall wrap/
elements in accordance with the NCC. The loads and sarking should consider the local climate, building use
effects of earthquakes may be determined in accordance and orientation, material R-Value of the insulation, and
with AS 1170.4 ‘Earthquake Actions in Australia’. The the use of ventilation methods.
Standard has design procedures for houses (Class 1),
• Weather Barrier: Wind loads can produce lower air
and to buildings (Classes 2 to 9) with importance levels
pressures within buildings than on the outside, forcing
2, 3 or 4 as defined in the NCC.
water through small gaps in the building envelope
around penetrations and joints, even at low wind
WEATHERPROOFING speeds.
The control of water ingress to a building is the Key selection characteristics for a suitable wall wrap/
responsibility of the building designer. CSR recommends sarking are:
that a comprehensive risk assessment of the building be
conducted prior to selection of the cladding system. It • The wall wrap/sarking must have a ‘high’ water barrier
should be noted that cavity systems are the best method classification – an ‘unclassified’ rating is not suitable.
for weather proofing walls and should be considered for • Wall wrap/sarking must meet the requirements of
complex and high-risk building designs. AS/NZS 4200.1: Pliable building membranes and
All framing, sarking, flashings, damp proof courses and underlays – Materials, and be installed in accordance
sealants must be installed in accordance with the relevant with AS/NZS 4200.2: Pliable building membranes and
product manufacturer’s instructions, applicable standards underlays – Installation requirements.
and building codes. CSR recommends sealing the external wall wrap/sarking
to maintain vapour performance and draught proofing
effectiveness, as well as to ensure water barrier integrity.
Cladding System Types
An air barrier such as Cemintel Rigid Air Barrier can
Typical cladding systems used to achieve the objectives also be installed as part of an effective cavity system.
of the NCC in relation to weatherproofing include: Additional literature on condensation control is available
• Ventilated and Drained Cavity: A ventilated and from CSIRO/BRANZ/ASHRAE/ABCB, and CSR Bradford
drained cavity or “Rainscreen” is an open jointed, can help with product and system selection.
rear-ventilated (vented primarily at the head and base)
cladding system. These systems reduce the risk of
moisture entering the cavity by means of pressure

GYPROCK® THE RED BOOK™ 1 F3


CORROSIVITY CATEGORIES/ of the steel framing to a maximum of 450°C at the FRL
stated. Therefore, the structural design of the framing
COASTAL AREAS need only provide for normal temperature conditions,
Corrosivity categories are as described in AS 4312 - and no additional consideration of fire rating is required.
Atmospheric corrosivity zones in Australia. The code has
The fire design of timber framing is based on the principle
methods for determining categories as well as maps and
that a level of char is acceptable without compromising
tables of major population centres. It is recommended
the performance of the wall. CSR has carried out testing
that the building designer assess the site in accordance
to verify the char limit, and where it is exceeded, the
with the standard and local conditions, and to specify
allowable axial capacity of the stud is reduced to account
appropriate components, protective coatings, and
for the loss of section. The systems are noted with an
maintenance procedures and schedules.
Axial Capacity Reduction (ACR) Group number in TABLE
The Standard describes six atmospheric corrosivity F1. In these systems, the designer must increase the
categories: applied vertical loads by the ACR to compensate for the
axial capacity reduction.
• C1 – Very Low: Generally inside buildings, semi-
sheltered locations away from marine or industrial The stated FRL for a system is dependent on the linings
influence, and some alpine regions. extending for the full extent of the wall. Where linings
are omitted, for example at intersecting wall, floor and
• C2 – Low: Dry, rural areas, away from the coast or
roof junctions, the rating is reduced. For walls rated
sources of pollution. Most areas of Australia at least 50
from outside only it may be possible to use a system
kilometres from the coast, or over one kilometre from
with the required rating independent of the interior lining,
quiet, sheltered seas. Most inland towns that are more
and this typically involves additional layers of fire grade
than one kilometre from the sea.
linings. Contact CSR DesignLINK for more information.
• C3 – Medium: Coastal areas with low salinity. Sheltered In the case of timber framed construction rated up to
areas such as Port Philip Bay, 50 metres from the 60/60/60 FRL there are options available to replace the
shoreline to about one kilometre inland. Around interior linings with extra timber members. Details are
less sheltered bays to about 0.5 to between 5 and available from Forest and Wood Products Australia at
15 kilometres inland. Along ocean front areas with woodsolutions.com.au. In any case it is recommended
breaking surf and significant salt spray, extending that a fire engineer be consulted to achieve an acceptable
from about one kilometre inland to between 10 and 50 solution.
kilometres inland. Urban and industrial areas with low
External walls in some building types are required by the
pollution levels, and for several kilometres around large
NCC to be non-combustible. This may exclude the use
industries such as steelworks and smelters.
of timber framing, some insulation products, and some
• C4 – High: Around sheltered bays up to 50 metres accessories such as thermal breaks.
inland from the shoreline. Areas with rough seas and
To protect structural steel beams and columns that are
surf, extending from several hundred metres in and
entirely within a wall, the FRL of the wall system must
to about one kilometre inland. Up to 1.5 kilometres
be at least equivalent to that required by the structural
downwind of large industrial plants. Damp interior
member. For example, a wall system with FRL 90/90/90
environments such as for swimming pools and
provides FRL 90/–/– for a steel column within the wall.
factories.
TABLE F1: AXIAL CAPACITY REDUCTION (%) DUE TO
• C5 – Very High: around 50 to 500 m from shorelines THE EFFECT OF TIMBER CHAR
with surf or very rough seas. Some aggressive industrial Timber Size Group 1 Group 2 Group 3
areas. 90 x 45 0% 0% 25%
90 x 35 0% 10% 30%
• CX – Extreme: Offshore and on the beach front in 70 x 45 3% 25% 40%
regions of rough seas and surf beaches, and inland for 70 x 35 8% 35% 45%
several hundred metres, Interior areas with permanent
condensation or high pollution.
ACCEPTABLE VARIATIONS TO
FIRE RESISTANCE FIRE SYSTEMS
The wall systems in this manual are suitable for the stated The Fire Resistance Level (FRL) of the systems detailed in
FRL when designed in accordance with the structural this section will not be detrimentally affected by:
design considerations above. Wall system fire ratings • The use of alternative claddings in systems with cavities
apply in either direction unless noted otherwise. formed on battens or top hats.
Most CSR fire rated steel stud wall systems have been • Increasing the thickness of the wall.
designed with fire protection that limits the temperature

F4 GYPROCK® THE RED BOOK™ 1


• Increasing the cross-sectional dimensions of the configuration and materials used, so that the impact of
framing elements. the thermal bridging on the added insulation is captured.
• Decreasing the stud spacing. Additional to the effects of thermal bridging through the
framing paths of the structure, the designer will need
• Decreasing the fixing centres of wall sheet materials.
to allow for gaps in the bulk insulation layer in the wall
• The inclusion of bulk cavity insulation materials such as system due to structural framing (i.e., studs, noggings,
Glasswool, Rockwool and Polyester. perimeter of wall openings) and services obstructing or
• Additional layers of plasterboard or Cemintel fibre limiting wall insulation coverage, slab edge insulation,
cement. wall cavity ventilation, and the effects of air leakage
due to unsealed architraves, unsealed door jambs,
• Wall curved in plan with a radius of curvature no less unsealed gaps between windows and the masonry wall
than 3m. or services penetrating the inner leaf. These effects are
• The attachment of light weight fixtures through to the to be compensated for as outlined in NCC Volume One
framing. Section J.

• The addition of timber sheeting or fibre cement sheets.


THERMAL BRIDGING
COMBUSTIBILITY For projects conforming to BCA versions prior to the NCC
2022, thermal bridging consideration is not required in the
Polyester insulation may NOT be selected where the Total R-Value calculation for all building classes, such as:
system has non-combustible construction requirements.
• Class 2 to Class 9 buildings for NCC2016 Amdt.
In accordance with NCC2022 Clause C2D10 [NCC2019: 1 Volume 1 and NCC2016 Amdt. 1 Volume 2 (and
C1.9], plasterboard and fibre cement sheet may be used earlier).
wherever a non-combustible material is required by the
Code. • Class1 and Class 10 only for NCC2019 (incl. Amdt. 1)
Volume 2.
THERMAL PERFORMANCE For product information, refer to section B of this
guide. Note, the insulation also improves the acoustic
Energy efficiency requirements for buildings are set out
performance of the wall against noise transmission. Refer
in the NCC as performance requirements dependent on
to page F34 for further information on systems where
geographical climate zones. To meet the requirements,
total R-Values include consideration of the effects of
it is recommended that CSR Bradford batts be installed
thermal bridging.
in the wall framing, with insulation values chosen with
consideration for energy conservation and occupant
comfort. Insulation also improves the acoustic ACOUSTIC PERFORMANCE
performance of the wall against noise transmission. The performance of the as-built system may be affected
The level of insulation provided in a wall is described by its by sound flanking, the effectiveness of workmanship and
R-Value, the higher the R-Value the greater the insulation caulking, the presence and treatment of penetrations, and
provided. The system values provided have been the inclusion of structural elements and bridging items.
calculated based on a thermal transmission path through Refer to appropriate information on addressing these
the wall cavity and does not allow for any thermal bridging issues detailed in Section B and Section J in this guide.
This method is in accordance with the requirements of General Notes:
NCC Volume 2, Class 1 and 10 buildings and may not be
applicable for other building classes. Rt(SUM) and Rt(WIN) • The acoustic performance of systems may be adversely
represent the system total R-Value calculated for heat flow affected by the use of studs with closer spacings than
inwards and heat flow outwards respectively. those specified, studs with a different BMT, timber
studs of greater width, or by the use of additional
A thermal break may be required where Cemintel cladding linings fixed on battens.
is fixed directly to steel framing of walls enclosing
habitable or usable spaces. For detailed information refer • The acoustic performance of CSR wall systems is not
to the NCC. The thermal break is used to ensure that the adversely affected by the order of lining sheets that
thermal performance of the wall is comparable to that of are fixed direct to framing or by the use of deeper stud
a timber framed wall. For systems with timber battens sections.
20mm or thicker, no additional thermal break is required.
NCC 2022 includes changes to energy efficiency
requirements. These requirements will express the
R-Value of the building fabric as the Total R-Value. The
Total R-Value will consider the project specific external wall

GYPROCK® THE RED BOOK™ 1 F5


CEMINTEL CLADDING
Lightweight cladding materials have been selected from
the Cemintel range.

Weatherboard products
• Headland
• Scarborough
• Balmoral
• Aspect Cemintel Mosaic
• Plank

Sheet products
• Cladding Sheet
• Texture Base Sheet
• SimpleLine
• Edge
• Mosaic

Wood particle fibre cement panels


Cemintel Commercial ExpressWall
• Territory

ExpressWall products
• ExpressPanel
• Barestone
• Surround

Cemintel Scarborough Weatherboard

Cemintel Edge Cladding

Cemintel Barestone Cemintel Territory - Urban Grey

F6 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Weatherboards – Direct Fixed – Steel Frame

Cemintel weatherboard cladding. DCT VulcanWool Thermal Break if required.

Wall wrap. Steel studs at 600mm maximum centres.

Lining material as per system Cavity insulation as per system table.


table to external side.
Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been calculated
based on a thermal transmission path through the wall cavity
and does not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
CSR 5010
(b) 90 Gold Batts R2.0 – – 41/32 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 42/33 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 10mm Gyprock Plus (d) 75 Gold Batts R2.0 40/31 2.1/2.2 41/32 2.3/2.5
Plasterboard.
Wall Thickness 80 100
Excluding Cladding mm
CSR 10087
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 44/35 2.1/2.3
• 1 x 16mm Gyprock
60/60/60 (c) 90 Gold Batts R2.5 – – 45/36 2.6/2.8
Fyrchek MR Plasterboard
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/34 2.2/2.3 44/35 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 96 116
Excluding Cladding mm
CSR 10088
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 48/40 2.1/2.3
60/60/60 • 1 x 16mm Gyprock
– /90/90 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 49/41 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 47/39 2.2/2.4 48/40 2.4/2.6
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness
Excluding Cladding mm 102 122

CSR 10089
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/38 2.1/2.3
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/39 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/37 2.2/2.4 47/38 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 106 126
Excluding Cladding mm
CSR 10090
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 51/43 2.1/2.3
90/90/90 • 2 x 13mm Gyprock
– /120/120 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 52/44 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 50/42 2.3/2.5 51/43 2.5/2.7
FC 12946 • 2 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 122 142
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F7


SYSTEM SPECIFICATIONS Cemintel Sheets – Direct Fixed – Steel Frame

DCT VulcanWool Thermal Break if required.

Cemintel sheet cladding. Steel studs at 600mm maximum centres.

Wall wrap. Cavity insulation as per system table.

Lining material as per system Lining material as per system


table to external side. table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been calculated
based on a thermal transmission path through the wall cavity
and does not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5030
(b) 90 Gold Batts R2.0 – – 41/32 2.1/2.3
EXTERNAL WALL SIDE
• Nil. (c) 90 Gold Batts R2.5 – – 42/33 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 10mm Gyprock Plus (d) 75 Gold Batts R2.0 41/32 2.1/2.2 41/32 2.3/2.4
Plasterboard.
Wall Thickness 80 100
Excluding Cladding mm
CSR 10091
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/36 2.1/2.3
• 1 x 13mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/37 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/36 2.1/2.3 45/36 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 93 113
Excluding Cladding mm
CSR 10092
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 50/42 2.1/2.3
60/60/60 • 1 x 16mm Gyprock
– /90/90 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 51/43 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 50/42 2.2/2.3 50/42 2.4/2.6
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 102 122
Excluding Cladding mm
CSR 10093
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 49/40 2.1/2.3
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 50/41 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 49/40 2.2/2.4 49/40 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 106 126
Excluding Cladding mm
CSR 10094
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 53/45 2.1/2.3
90/90/90 • 2 x 13mm Gyprock
– /120/120 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 54/46 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 53/45 2.3/2.5 53/45 2.5/2.7
FC 12946 • 2 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 122 142
Excluding Cladding mm

F8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboards – With Cavity – Steel Frame

Cemintel sheet or weatherboard Steel studs at 600mm maximum centres.


cladding.
Cavity insulation as per system table.
19 to 35mm depth battens.
Lining material as per system
Wall wrap or 6mm Cemintel table to internal side.
Rigid Air Barrier.

Lining material as per system


table to external side. NOTE: Acoustic performance valid for studs with 0.75 BMT.
The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5152
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 41/30 2.2/2.4
• 1 x 13mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 42/31 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 40/29 2.1/2.3 41/30 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 112 132
Excluding Cladding mm
CSR 5160
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/35 2.2/2.4
• 1 x 16mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/36 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/34 2.1/2.2 45/35 2.3/2.5
FC 12946
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness 111 131
Excluding Cladding mm
CSR 5161
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 42/31 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 43/32 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 41/30 2.1/2.3 42/31 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 115 135
Excluding Cladding mm
CSR 5163
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 43/32 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 44/33 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 42/31 2.1/2.3 43/32 2.3/2.5
FC 12946
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 115 135
Excluding Cladding mm
CSR 10155
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 44/34 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (b) 90 Gold Batts R2.5 – – 45/35 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 43/32 2.1/2.3 44/34 2.3/2.5
FC 12946
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 115 135
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F9


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboards – With Cavity – Steel Frame

Cemintel sheet or weatherboard Steel studs at 600mm maximum centres.


cladding.
Cavity insulation as per system table.
19 to 35mm depth battens.
Lining material as per system
Wall wrap or 6mm Cemintel table to internal side.
Rigid Air Barrier.
NOTE: Acoustic performance valid for studs with 0.75 BMT.
Lining material as per system
The system thermal R-values provided have been
table to external side. calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5168
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/37 2.2/2.4
60/60/60 • 1 x 16mm Gyprock
– /90/90 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/38 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/36 2.2/2.3 46/37 2.4/2.6
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 121 141
Excluding Cladding mm
CSR 5170
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/34 2.2/2.4
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/35 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/33 2.2/2.3 45/34 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 125 145
Excluding Cladding mm
CSR 5172
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 46/35 2.2/2.4
• 2 x 16mm Gyprock
120/120/120
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 47/36 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/34 2.2/2.4 46/35 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 131 151
Excluding Cladding mm
CSR 5173
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 50/41 2.2/2.4
90/90/90 • 2 x 13mm Gyprock
– /120/120 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 51/41 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 49/40 2.3/2.4 50/41 2.5/2.7
FC 12946 • 2 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 141 161
Excluding Cladding mm
CSR 5174
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 52/43 2.2/2.4
120/120/120 • 2 x 16mm Gyprock
– /180/180‡ Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 53/44 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 51/42 2.3/2.5 52/43 2.6/2.7
FC 12946 • 2 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 153 173
Excluding Cladding mm

F10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Territory – With Cavity – Steel Frame

Cemintel Territory cladding system Steel studs at 600mm maximum centres.


clip-fixed to studs.
Cavity insulation as per system table.
Wall wrap or 6mm Cemintel
Rigid Air Barrier Lining material as per system
table to internal side.
Lining material as per system
table to external side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5302
(b) 90 Gold Batts R2.0 – – 46/37 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 47/38 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 10mm Gyprock Plus (d) 75 Gold Batts R2.0 44/35 2.0/2.2 46/37 2.2/2.4
Plasterboard.
Wall Thickness mm 111 131

CSR 5303
(b) 90 Gold Batts R2.0 – – 46/37 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 47/38 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 13mm Standard (d) 75 Gold Batts R2.0 47/38 2.1/2.2 48/39 2.3/2.4
Plasterboard.
Wall Thickness mm 113 134

CSR 5305
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 44/33 2.1/2.3
• 1 x 13mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 45/34 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/32 2.1/2.3 44/33 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard.
Wall Thickness mm 124 144

CSR 5308
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/36 2.1/2.3
30/30/30 • 1 x 13mm Gyprock
– /60/60 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/37 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/35 2.1/2.3 47/36 2.3/2.5
FC 12946 • 1 x 13mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 127 147

CSR 5315
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/34 2.1/2.3
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/35 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/33 2.1/2.3 45/34 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard.
Wall Thickness mm 127 147

GYPROCK® THE RED BOOK™ 1 F11


SYSTEM SPECIFICATIONS Cemintel Territory – With Cavity – Steel Frame

Cemintel Territory cladding system Steel studs at 600mm maximum centres.


clip-fixed to studs.
Cavity insulation as per system table.
Wall wrap or 6mm Cemintel
Rigid Air Barrier. Lining material as per system
table to internal side.
Lining material as per system
table to external side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10156
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 47/37 2.1/2.3
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (b) 90 Gold Batts R2.5 – – 48/38 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 46/36 2.1/2.3 47/37 2.3/2.5
FC 12946
• 1 x 10mm Gyprock HD
Plasterboard.
Wall Thickness mm 127 147

CSR 5320
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 46/35 2.1/2.3
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 47/36 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/34 2.1/2.3 46/35 2.3/2.5
FC 12946
• 1 x 10mm Gyprock
Aquachek Plasterboard.
Wall Thickness mm 127 147

CSR 5321
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 50/40 2.1/2.3
60/60/60 • 1 x 16mm Gyprock
– /90/90 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 51/41 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 49/39 2.2/2.3 50/40 2.4/2.6
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 133 153

CSR 5324
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/37 2.1/2.3
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/38 2.6/2.8
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/36 2.2/2.3 47/37 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard.
Wall Thickness mm 137 157

F12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Steel Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Steel studs at 600mm maximum centres.
cladding support system.
Cavity insulation as per system table.
Wall wrap or 6mm Cemintel
Rigid Air Barrier. Lining material as per system
table to internal side.
15mm top hat.

Lining material as per system


table to external side. NOTE: Acoustic performance valid for studs with 0.75 BMT.
The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5327
(b) 90 Gold Batts R2.0 – – 49/40 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 50/41 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 13mm Gyprock (d) 75 Gold Batts R2.0 48/39 2.1/2.2 49/40 2.3/2.4
Standard Plasterboard.
Wall Thickness 133 153
Excluding Cladding mm
CSR 5332
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 43/32 2.2/2.4
• 1 x 13mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 44/33 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 42/31 2.1/2.3 43/32 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 143 163
Excluding Cladding mm
CSR 5340
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 48/38 2.2/2.4
• 1 x 16mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 49/39 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 47/37 2.1/2.2 48/38 2.3/2.5
FC 12946
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness 142 162
Excluding Cladding mm
CSR 5342
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 44/33 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 45/34 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/32 2.1/2.3 44/33 2.3/2.5
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 146 166
Excluding Cladding mm
CSR 5343
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 46/35 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 47/36 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/34 2.1/2.3 46/35 2.3/2.5
FC 12946
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 146 166
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F13


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Steel Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Steel studs at 600mm maximum centres.
cladding support system.
Cavity insulation as per system table.
Wall wrap or 6mm Cemintel
Rigid Air Barrier. Lining material as per system
table to internal side.
15mm top hat.
NOTE: Acoustic performance valid for studs with 0.75 BMT.
Lining material as per system The system thermal R-values provided have been
table to external side. calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5345
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 50/40 2.2/2.4
60/60/60 • 1 x 16mm Gyprock
– /90/90 Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 51/41 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 49/39 2.2/2.3 50/40 2.4/2.6
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 152 172
Excluding Cladding mm
CSR 5346
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 48/37 2.2/2.4
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 49/38 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 47/36 2.2/2.3 48/37 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 156 176
Excluding Cladding mm
CSR 5347
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 49/38 2.2/2.4
• 2 x 16mm Gyprock
120/120/120
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 50/39 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 48/37 2.2/2.4 49/38 2.4/2.6
FC 12946
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 162 182
Excluding Cladding mm
CSR 5349
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 55/46 2.2/2.4
120/120/120 • 2 x 16mm Gyprock
– /180/180‡ Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 56/47 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 54/45 2.3/2.5 55/46 2.6/2.7
FC 12946 • 2 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 184 204
Excluding Cladding mm

F14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Steel Girt Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Steel girt framing to engineer’s details.
cladding support system.

Wall wrap.

Lining material as per system


table to external side.

NOTE: *Additional limits apply for wind


pressures

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

FRL SYSTEM *Maximum Girt


WALL LININGS Rw / Rw+Ctr
Report Nº Spacing (mm)
CSR 5360

EXTERNAL WALL SIDE


– /– / – • Nil – 33/30

CSR 5365

60/60/60 EXTERNAL WALL SIDE


(from outside only)
• 2 x 16mm Gyprock 600 38/28
Fyrchek MR Plasterboard.
FC 12946

CSR 5368

90/90/90 EXTERNAL WALL SIDE


(from outside only)
• 3 x 13mm Gyprock 900 41/31
Fyrchek MR Plasterboard.
FC 12946

CSR 5371

120/120/120 EXTERNAL WALL SIDE


(from outside only)
• 3 x 16mm Gyprock 1200 42/32
Fyrchek MR Plasterboard.
FC 12946

GYPROCK® THE RED BOOK™ 1 F15


SYSTEM SPECIFICATIONS Metal Cladding – With Cavity – Steel Girt Frame

External metal cladding. Lining material as per system


table to external side.
Wall wrap.
Steel girts to engineer’s detail.
Galvanised steel battens
(20mm depth min.) fixed through
plasterboard to steel girts.

NOTE: *Additional limits apply for wind


pressures

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119


FRL SYSTEM
WALL LININGS *MAXIMUM GIRT SPACING (mm) Rw / Rw+Ctr
Report Nº
CSR 5380

60/60/60 EXTERNAL WALL SIDE


(from outside only)
• 2 x 16mm Gyprock 600 33/25
Fyrchek MR Plasterboard.
FC 12946

CSR 5385

90/90/90 EXTERNAL WALL SIDE


(from outside only)
• 3 x 13mm Gyprock 900 35/27
Fyrchek MR Plasterboard.
FC 12946

CSR 5390

120/120/120 EXTERNAL WALL SIDE


(from outside only)
• 3 x 16mm Gyprock 1200 36/28
Fyrchek MR Plasterboard.
FC 12946

F16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry Veneer – With Cavity – Steel Frame

Fire rated masonry veneer wall. Steel studs at 600mm maximum centres.

Wall wrap. Cavity insulation as per system table.

40mm minimum cavity. Lining material as per system


table to internal side.

NOTE: To achieve stated acoustic performance


masonry must be a minimum of 90mm thick and
170kg/m2.
The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A120

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5403
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 59/51 2.3/2.6
• Masonry veneer wall with
60/60/60 (c) 90 Gold Batts R2.5 – – 59/51 2.8/3.1
FRL 60/60/60.
(from outside only)
refer to Masonry INTERNAL WALL SIDE
Manufacturer (d) 75 Gold Batts R2.0 57/48 2.3/2.5 58/50 2.5/2.7
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness Excluding 80 100
Masonry & Cavity mm
CSR 5405
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 60/52 2.3/2.6
• Masonry veneer wall with
60/60/60 (c) 90 Gold Batts R2.5 – – 60/52 2.8/3.1
FRL 60/60/60.
(from outside only)
refer to Masonry INTERNAL WALL SIDE
Manufacturer (d) 75 Gold Batts R2.0 58/49 2.3/2.5 59/51 2.5/2.7
• 1 x 10mm Gyprock
Aquachek Plasterboard Wall Thickness Excluding 80 100
Masonry & Cavity mm
CSR 10157
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 60/52 2.3/2.6
• Masonry veneer wall with
60/60/60 (b) 90 Gold Batts R2.5 – – 60/52 2.8/3.1
FRL 60/60/60.
(from outside only)
refer to Masonry INTERNAL WALL SIDE
Manufacturer (c) 75 Gold Batts R2.0 58/49 2.3/2.5 59/51 2.5/2.7
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness Excluding 80 100
Masonry & Cavity mm
CSR 5410
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 62/55 2.3/2.6
60/60/60 • Masonry veneer wall with
(from both sides) (c) 90 Gold Batts R2.5 – – 62/55 2.8/3.1
FRL 60/60/60.
FC 12946
and refer INTERNAL WALL SIDE
to Masonry (d) 75 Gold Batts R2.0 60/52 2.4/2.5 61/54 2.6/2.8
• 1 x 16mm Gyprock
Manufacturer
Fyrchek Plasterboard. Wall Thickness Excluding 86 106
Masonry & Cavity mm
CSR 5415
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 63/56 2.3/2.6
90/90/90 • Masonry veneer wall with
(from both sides) (c) 90 Gold Batts R2.5 – – 63/56 2.8/3.1
FRL 90/90/90.
FC 12946
and refer INTERNAL WALL SIDE
to Masonry (d) 75 Gold Batts R2.0 61/53 2.4/2.6 62/55 2.6/2.8
• 2 x 13mm Gyprock
Manufacturer
Fyrchek Plasterboard. Wall Thickness Excluding 96 116
Masonry & Cavity mm
CSR 5420
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 64/57 2.3/2.6
120/120/120 • Masonry veneer wall with
(from both sides) (c) 90 Gold Batts R2.5 – – 64/57 2.8/3.1
FRL 120/120/120.
FC 12946
and refer INTERNAL WALL SIDE
to Masonry (d) 75 Gold Batts R2.0 62/54 2.5/2.6 63/56 2.7/2.9
• 2 x 16mm Gyprock
Manufacturer
Fyrchek Plasterboard. Wall Thickness Excluding 102 122
Masonry & Cavity mm

GYPROCK® THE RED BOOK™ 1 F17


SYSTEM SPECIFICATIONS Cemintel Weatherboards – Direct Fixed – Timber Frame

Cemintel weatherboard cladding. Timber studs at 600mm maximum


centres.
Wall wrap.
Cavity insulation as per system table.
Lining material as per system
table to external side. Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been calculated
based on a thermal transmission path through the wall cavity
and does not allow for the effects of thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5502
(b) 90 Gold Batts R2.0 – – 38/29 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 39/30 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 10mm Gyprock Plus (d) 75 Gold Batts R2.0 37/28 2.1/2.2 38/29 2.3/2.5
Plasterboard.
Wall Thickness 80 100
Excluding Cladding mm
CSR 5505
EXTERNAL WALL SIDE (b) 90 Gold Batts R2.0 – – 44/35 2.2/2.4
• 1 x 13mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 45/36 2.7/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/34 2.2/2.3 44/35 2.4/2.6
FC 12969
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 96 116
Excluding Cladding mm
CSR 5510
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 41/32 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 42/33 2.7/2.9
*ACR Group 2
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 40/31 2.2/2.3 41/32 2.4/2.6
FC 12969 • 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 96 116
Excluding Cladding mm

F18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Weatherboards – Direct Fixed – Timber Frame

Cemintel weatherboard cladding. Timber studs at 600mm maximum


centres.
Wall wrap.
Cavity insulation as per system table.
Lining material as per system
table to external side. Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been calculated
based on a thermal transmission path through the wall cavity
and does not allow for the effects of thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5512
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 42/33 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 43/34 2.7/2.9
*ACR Group 2
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 41/32 2.2/2.3 42/33 2.4/2.6
FC 12969 • 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 96 116
Excluding Cladding mm
CSR 10158
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 43/34 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (b) 90 Gold Batts R2.5 – – 44/35 2.7/2.9
*ACR Group 2
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 42/33 2.2/2.3 43/34 2.4/2.6
FC 12969 • 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 96 116
Excluding Cladding mm
CSR 5520
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/37 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/38 2.7/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/36 2.2/2.4 45/37 2.4/2.6
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 102 122
Excluding Cladding mm
CSR 5527 EXTERNAL WALL SIDE
• 1 x 6mm CeminSeal (b) 90 Gold Batts R2.0 – – 49/41 2.2/2.4
60/60/60 Wallboard (against frame)
90/90/90* (c) 90 Gold Batts R2.5 – – 50/42 2.7/2.9
(from both sides)
• 1 x 16mm Gyprock
*ACR Group 3 Fyrchek MR Plasterboard.
(d) 75 Gold Batts R2.0 48/40 2.3/2.4 49/41 2.5/2.7
INTERNAL WALL SIDE
FC 12969
• 2 x 13mm Gyprock Wall Thickness 118 138
Fyrchek Plasterboard. Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F19


SYSTEM SPECIFICATIONS Cemintel Sheet – Direct Fixed – Timber Frame

Cemintel sheet cladding. Timber studs at 600mm maximum


centres.
Wall wrap.
Cavity insulation as per system table.
Lining material as per system
table to external side. Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been calculated
based on a thermal transmission path through the wall cavity
and does not allow for the effects of thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5603
(b) 90 Gold Batts R2.0 – – 38/29 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 39/30 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 10mm Gyprock Plus (d) 75 Gold Batts R2.0 37/28 2.1/2.2 38/29 2.3/2.4
Plasterboard.
Wall Thickness 80 100
Excluding Cladding mm
CSR 5605
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 42/33 2.2/2.4
60/60/60* • 1 x 13mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 43/34 2.7/2.9
*ACR Group 1
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 41/32 2.1/2.3 42/33 2.3/2.5
FC 12969 • 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 93 113
Excluding Cladding mm
CSR 5608
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/36 2.2/2.4
60/60/60* • 1 x 13mm Gyprock
(from both sides) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/37 2.7/2.9
*ACR Group 1
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/34 2.2/2.3 44/35 2.4/2.6
FC 12969 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 99 119
Excluding Cladding mm
CSR 5613
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 43/34 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 44/35 2.7/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 42/33 2.1/2.3 43/34 2.3/2.5
FC 12969
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 96 116
Excluding Cladding mm
CSR 10159
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 44/35 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (b) 90 Gold Batts R2.5 – – 45/36 2.7/2.9
(from outside only)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 43/34 2.1/2.3 44/35 2.3/2.5
FC 12969
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 96 116
Excluding Cladding mm

F20 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Sheet – Direct Fixed – Timber Frame

Cemintel sheet cladding. Timber studs at 600mm maximum


centres.
Wall wrap.
Cavity insulation as per system table.
Lining material as per system
table to external side. Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been calculated
based on a thermal transmission path through the wall cavity
and does not allow for the effects of thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5618 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock (b) 90 Gold Batts R2.0 – – 49/41 2.2/2.4
60/60/60 Fyrchek MR Plasterboard.
90/90/90* (c) 90 Gold Batts R2.5 – – 50/42 2.7/2.9
(from both sides) INTERNAL WALL SIDE
*ACR Group 3 • 1 x 6mm CeminSeal
(d) 75 Gold Batts R2.0 48/40 2.2/2.4 49/41 2.4/2.6
Wallboard (against frame)
FC 12969
• 1 x 16mm Gyprock Wall Thickness 108 128
Fyrchek Plasterboard. Excluding Cladding mm
CSR 5623
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 49/41 2.2/2.4
60/60/60
• 1 x 16mm Gyprock
90/90/90* Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 50/42 2.7/2.9
(from both sides)
*ACR Group 3 INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 48/40 2.2/2.4 49/41 2.4/2.6
• 2 x 13mm Gyprock
FC 12969
Fyrchek Plasterboard. Wall Thickness 112 132
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F21


SYSTEM SPECIFICATIONS Gyprock Boundary Wall System – Timber Frame – Single Wall

Cemintel 6mm Cladding Sheet. Timber studs at 600mm centres.

Bradford Enviroseal RW Plus. Cavity insulation as per system table.

1 x 16mm Gyprock Fyrchek MR to Lining material as per system


external side. table to internal side.

NOTE: The system thermal R-values provided have


been calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-100CSR

STUD DEPTH mm 90
FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr Rt(sum) / Rt(win)
(Refer to TABLE B6)

CSR 10160 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock Fyrchek (a) 90 Gold Batts 2.0 49/41 2.2
MR Plasterboard (against
60/60/60 studs)
(from outside) • 1 x 6mm Cemintel Cladding (b) 90 Gold Batts 2.5 50/43 2.7
Sheet.
FC 12969
INTERNAL WALL SIDE
• 1 x 10mm Gyprock HD Wall Thickness mm 122
Plasterboard.
CSR 5915 EXTERNAL WALL SIDE
• 1 x 16mm Gyprock Fyrchek (a) 90 Gold Batts 2.0 53/45 2.3
MR Plasterboard (against
60/60/60 studs)
(from outside) • 1 x 6mm Cemintel Cladding (b) 90 Gold Batts 2.5 54/47 2.7
Sheet.
FC 12969
INTERNAL WALL SIDE
• 2 x 10mm Gyprock Aquachek Wall Thickness mm 132
Plasterboard.
CSR 5920 EXTERNAL WALL SIDE
• 1 x 16mm Gyprock Fyrchek (a) 90 Gold Batts 2.0 50/42 2.2
MR Plasterboard (against
60/60/60 studs)
(from outside) • 1 x 6mm Cemintel Cladding (b) 90 Gold Batts 2.5 51/44 2.7
Sheet.
FC 12969
INTERNAL WALL SIDE
• 1 x 13mm Gyprock Aquachek Wall Thickness mm 125
Plasterboard.
CSR 5925 EXTERNAL WALL SIDE
• 1 x 16mm Gyprock Fyrchek (a) 90 Gold Batts 2.0 50/43 2.2
MR Plasterboard (against
60/60/60 studs)
(from outside) • 1 x 6mm Cemintel Cladding (b) 90 Gold Batts 2.5 51/45 2.7
Sheet.
FC 12969
INTERNAL WALL SIDE
• 1 x 13mm Gyprock Fyrchek Wall Thickness mm 125
Plasterboard.
CSR 5930 EXTERNAL WALL SIDE
• 1 x 16mm Gyprock Fyrchek (a) 90 Gold Batts 2.0 50/43 2.2
MR Plasterboard (against
60/60/60 studs)
(from outside) • 1 x 6mm Cemintel Cladding (b) 90 Gold Batts 2.5 51/45 2.7
Sheet.
FC 12969
INTERNAL WALL SIDE
• 1 x 13mm Gyprock Fyrchek Wall Thickness mm 125
MR Plasterboard.

F22 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Gyprock Boundary Wall System – Timber Frame - Double Wall

Lining material as per system Lining material as per system


table to internal side. table to internal side.

Timber studs at 600mm centres. Timber studs at 600mm centres.

Cavity insulation as per system table. Cavity insulation as per system table.

1 x 16mm Gyprock Fyrchek MR 1 x 16mm Gyprock Fyrchek MR


plasterboard to external side. plasterboard to external side.

Bradford Enviroseal RW Plus. Bradford Enviroseal RW Plus.

Cemintel 6mm Cladding Sheet Cemintel 6mm Cladding Sheet to external side.
to external side.

Building gap as per system table.

ACOUSTIC REPORT: PKA-100CSR


SYSTEM SPECIFICATION
Discontinuous Construction
STUD DEPTH mm 90
FRL SYSTEM BUILDING GAP mm
WALL LININGS 20 40 60 80
Report Nº
CAVITY INFILL Rw / Rw+Ctr Rw / Rw+Ctr
(Refer to TABLE B6)

CSR 10161 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock Fyrchek MR (a) 90 Gold Batts 2.0 63/40 65/43 66/44 67/45
60/60/60 Plasterboard (against studs)
(from centre • 1 x 6mm Cemintel Cladding
inwards) Sheet. (b) 90 Gold Batts 2.5 67/45 69/48 70/49 71/50

FAR 4840 INTERNAL WALL SIDE


• 1 x 10mm Gyprock HD
Wall Thickness mm 264 284 304 324
Plasterboard.

CSR 5940 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock Fyrchek MR (a) 90 Gold Batts 2.0 69/52 69/53 69/53 69/53
60/60/60 Plasterboard (against studs)
(from centre • 1 x 6mm Cemintel Cladding
inwards) Sheet. (b) 90 Gold Batts 2.5 72/57 73/58 73/58 73/58

FAR 4840 INTERNAL WALL SIDE


• 2 x 10mm Gyprock Aquachek
Wall Thickness mm 284 304 324 344
Plasterboard.

CSR 5945 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock Fyrchek MR (a) 90 Gold Batts 2.0 64/43 65/44 67/48 68/49
60/60/60 Plasterboard (against studs)
(from centre • 1 x 6mm Cemintel Cladding
inwards) Sheet. (b) 90 Gold Batts 2.5 68/48 69/49 71/53 71/54

FAR 4840 INTERNAL WALL SIDE


• 1 x 13mm Gyprock Aquachek
Wall Thickness mm 270 290 310 330
Plasterboard.

CSR 5950 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock Fyrchek MR (a) 90 Gold Batts 2.0 66/49 67/51 68/52 69/53
60/60/60 Plasterboard (against studs)
(from centre • 1 x 6mm Cemintel Cladding
inwards) Sheet. (b) 90 Gold Batts 2.5 70/54 71/56 72/57 73/58

FAR 4840 INTERNAL WALL SIDE


• 1 x 13mm Gyprock Fyrchek
Wall Thickness mm 270 290 310 330
Plasterboard.

CSR 5951 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock Fyrchek MR (a) 90 Gold Batts 2.0 66/49 67/51 68/52 69/53
60/60/60 Plasterboard (against studs)
(from centre • 1 x 6mm Cemintel Cladding
inwards) Sheet. (b) 90 Gold Batts 2.5 70/54 71/56 72/57 73/58

FAR 4840 INTERNAL WALL SIDE


• 1 x 13mm Gyprock Fyrchek MR
Wall Thickness mm 270 290 310 330
Plasterboard.

GYPROCK® THE RED BOOK™ 1 F23


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboard – With Cavity – Timber Frame

Cemintel weatherboard or Timber studs at 600mm maximum centres.


sheet cladding.
Cavity insulation as per system table.
19 to 35mm depth timber battens.
Lining material as per system
Wall wrap. table to internal side.

Lining material as per system


table to external side. NOTE: Acoustic performance valid for 35mm wide
studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10280
(b) 90 Gold Batts R2.0 – – 39/31 2.2/2.4
EXTERNAL WALL SIDE
• Nill. (c) 90 Gold Batts R2.5 – – 40/32 2.6/2.9
–/–/–
INTERNAL WALL SIDE
FC 12969 • 1 x 10mm Gyprock HD (d) 75 Gold Batts R2.0 38/30 2.1/2.3 39/31 2.3/2.5
Plasterboard.
Min. Wall Thickness 102 122
Excluding Cladding mm
CSR 5703
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 42/32 2.2/2.4
• 1 x 13mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 43/33 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 41/31 2.1/2.3 42/32 2.3/2.5
FC 12969
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Min. Wall Thickness 115 135
Excluding Cladding mm
CSR 5706
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 42/31 2.2/2.4
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 43/32 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 41/30 2.2/2.3 42/31 2.4/2.6
FC 12969
• 1 x 10mm Gyprock Plus
Plasterboard. Min. Wall Thickness 125 145
Excluding Cladding mm
CSR 5709
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 42/32 2.2/2.4
• 1 x 16mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 43/33 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 41/31 2.1/2.2 42/32 2.3/2.5
FC 12969
• 1 x 6mm CeminSeal
Wallboard. Min. Wall Thickness 111 131
Excluding Cladding mm
CSR 5710
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 41/30 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 42/31 2.6/2.9
*ACR Group 2
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 40/29 2.1/2.3 41/30 2.3/2.5
FC 12969 • 1 x 10mm Gyprock
Aquachek Plasterboard. Min. Wall Thickness 115 135
Excluding Cladding mm
CSR 5711
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 40/29 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 41/30 2.6/2.9
*ACR Group 2
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 39/28 2.1/2.3 40/29 2.3/2.5
FC 12969 • 1 x 10mm Gyprock Plus
Plasterboard. Min. Wall Thickness 115 135
Excluding Cladding mm

F24 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboard – With Cavity – Timber Frame

Cemintel weatherboard or Timber studs at 600mm maximum centres.


sheet cladding.
Cavity insulation as per system table.
19 to 35mm depth timber battens.
Lining material as per system
Wall wrap. table to internal side.

Lining material as per system


table to external side. NOTE: Acoustic performance valid for 35mm wide
studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10162
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 41/31 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (b) 90 Gold Batts R2.5 – – 42/32 2.6/2.9
*ACR Group 2
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 40/30 2.1/2.3 41/31 2.3/2.5
FC 12969 • 1 x 10mm Gyprock HD
Plasterboard. Min. Wall Thickness 115 135
Excluding Cladding mm
CSR 5716
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 43/33 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 44/34 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 42/32 2.2/2.3 43/33 2.4/2.6
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard. Min. Wall Thickness 121 141
Excluding Cladding mm
CSR 5718 EXTERNAL WALL SIDE
• 1 x 6mm CeminSeal (b) 90 Gold Batts R2.0 – – 45/35 2.2/2.4
60/60/60
(from both sides) Wallboard, (against studs).
90/90/90* (c) 90 Gold Batts R2.5 – – 46/36 2.6/2.9
• 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard.
*ACR Group 3 (d) 75 Gold Batts R2.0 44/34 2.2/2.3 45/35 2.4/2.6
INTERNAL WALL SIDE
FC 12969 • 1 x 16mm Gyprock Min. Wall Thickness 127 147
Fyrchek Plasterboard. Excluding Cladding mm
CSR 5721
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/38 2.2/2.4
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/39 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/37 2.3/2.4 47/38 2.5/2.7
FC 12969
• 2 x 13mm Gyprock
Fyrchek Plasterboard. Min. Wall Thickness 141 161
Excluding Cladding mm
CSR 5722
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 43/32 2.2/2.4
• 2 x 16mm Gyprock
120/120/120
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 44/33 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 42/31 2.2/2.4 43/32 2.4/2.6
FC 12969
• 1 x 10mm Gyprock Plus
Plasterboard. Min. Wall Thickness 131 151
Excluding Cladding mm
CSR 5724
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 48/39 2.2/2.4
• 2 x 16mm Gyprock
120/120/120
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 49/40 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 47/38 2.3/2.5 48/39 2.6/27
FC 12969
• 2 x 16mm Gyprock
Fyrchek Plasterboard. Min. Wall Thickness 153 173
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F25


SYSTEM SPECIFICATIONS Cemintel Territory – With Cavity – Timber Frame

Cemintel Territory cladding system Timber studs at 600mm maximum


clip-fixed to studs. centres.

Wall wrap. Cavity insulation as per system table.

Lining material as per system Lining material as per system


table to external side. table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5828
(b) 90 Gold Batts R2.0 – – 43/34 2.1/2.3
EXTERNAL WALL SIDE
• Nil (c) 90 Gold Batts R2.5 – – 44/35 2.6/2.8
– /– / – INTERNAL WALL SIDE
• 1 x 10mm Gyprock Plus (d) 75 Gold Batts R2.0 42/33 2.0/2.2 43/34 2.2/2.4
Plasterboard.
Wall Thickness mm 111 131

CSR 5832
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/35 2.2/2.4
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/36 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/34 2.2/2.3 45/35 2.4/2.6
FC 12969
• 1 x 10mm Gyprock Plus
Plasterboard.
Wall Thickness mm 137 157

CSR 5835
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 46/35 2.2/2.4
• 1 x 16mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 47/36 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/34 2.1/2.2 46/35 2.3/2.5
FC 12969
• 1 x 6mm CeminSeal
Wallboard.
Wall Thickness mm 123 143

CSR 5837
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 44/33 2.2/2.4
30/30/30
• 1 x 16mm Gyprock
60/60/60* Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 45/34 2.6/2.9
(from outside only)
*ACR Group 2 INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/32 2.1/2.3 44/33 2.3/2.5
• 1 x 10mm Gyprock Plus
FC 12969
Plasterboard.
Wall Thickness mm 127 147

CSR 5839
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/34 2.2/2.4
30/30/30
• 1 x 16mm Gyprock
60/60/60* Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/35 2.6/2.9
(from outside only)
*ACR Group 2 INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/33 2.1/2.3 45/34 2.3/2.5
• 1 x 10mm Gyprock
FC 12969
Aquachek Plasterboard.
Wall Thickness mm 127 147

F26 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Territory – With Cavity – Timber Frame

Cemintel Territory cladding system Timber studs at 600mm maximum


clip-fixed to studs. centres.

Wall wrap. Cavity insulation as per system table.

Lining material as per system Lining material as per system


table to external side. table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10163
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/35 2.2/2.4
30/30/30
• 1 x 16mm Gyprock
60/60/60* Fyrchek MR Plasterboard. (b) 90 Gold Batts R2.5 – – 46/36 2.6/2.9
(from outside only)
*ACR Group 2 INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/34 2.1/2.3 45/35 2.3/2.5
• 1 x 10mm Gyprock HD
FC 12969
Plasterboard.
Wall Thickness mm 127 147

CSR 5844
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/37 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/38 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/36 2.2/2.3 47/37 2.4/2.6
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 133 153

CSR 5848 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock (b) 90 Gold Batts R2.0 – – 51/42 2.2/2.4
60/60/60 Fyrchek MR Plasterboard.
90/90/90* (c) 90 Gold Batts R2.5 – – 52/43 2.6/2.9
(from both sides)
• 1 x 6mm CeminSeal
*ACR Group 3 Wallboard. (against frame)
(d) 75 Gold Batts R2.0 50/41 2.2/2.4 51/42 2.4/2.6
INTERNAL WALL SIDE
FC 12969
• 2 x 13mm Gyprock
Wall Thickness mm 149 169
Fyrchek Plasterboard.

GYPROCK® THE RED BOOK™ 1 F27


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Timber Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Timber studs at 600mm maximum
cladding support system. centres.

Wall wrap. Cavity insulation as per system table.

Lining material as per system Lining material as per system


table to external side. table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119


STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5851
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 46/36 2.2/2.4
• 1 x 16mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 47/37 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/35 2.1/2.2 46/36 2.3/2.5
FC 12969
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness 127 147
Excluding Cladding mm
CSR 5854
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 45/34 2.2/2.4
• 1 x 13mm Gyprock
30/30/30
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 46/35 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 44/33 2.1/2.3 45/34 2.3/2.5
FC 12969
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 131 151
Excluding Cladding mm
CSR 5857
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 46/35 2.2/2.4
• 2 x 13mm Gyprock
90/90/90
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 47/36 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 45/34 2.2/2.3 46/35 2.4/2.6
FC 12969
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 141 161
Excluding Cladding mm
CSR 5860
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 43/32 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 44/33 2.6/2.9
*ACR Group 2
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 42/31 2.1/2.3 43/32 2.3/2.5
FC 12969 • 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 131 151
Excluding Cladding mm
CSR 5862
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 44/33 2.2/2.4
60/60/60* • 1 x 16mm Gyprock
(from outside only) Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 45/34 2.6/2.9
*ACR Group 2
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 43/32 2.1/2.3 44/33 2.3/2.5
FC 12969 • 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 131 151
Excluding Cladding mm

F28 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Timber Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Timber studs at 600mm maximum
cladding support system. centres.

Wall Wrap. Cavity insulation as per system table.

Lining material as per system Lining material as per system


table to external side. table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119


STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5865
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/37 2.2/2.4
• 1 x 16mm Gyprock
60/60/60
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/38 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/36 2.2/2.3 47/37 2.4/2.6
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 137 157
Excluding Cladding mm
CSR 5868 EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 49/39 2.2/2.4
60/60/60 • 1 x 16mm Gyprock
(from both sides) Fyrchek MR Plasterboard.
(c) 90 Gold Batts R2.5 – – 50/40 2.6/2.9
90/90/90* • 1 x 6mm CeminSeal
(from outside only) Wallboard. (against frame)
*ACR Group 2 (d) 75 Gold Batts R2.0 48/38 2.2/2.3 49/39 2.4/2.6
INTERNAL WALL SIDE
FC 12969 • 1 x 16mm Gyprock Wall Thickness 143 163
Fyrchek Plasterboard. Excluding Cladding mm
CSR 5870 EXTERNAL WALL SIDE
• 1 x 16mm Gyprock (b) 90 Gold Batts R2.0 – – 51/42 2.2/2.4
90/90/90* Fyrchek MR Plasterboard.
(from both sides) (c) 90 Gold Batts R2.5 – – 52/43 2.6/2.9
• 1 x 6mm CeminSeal
*ACR Group 3 Wallboard. (against frame)
(d) 75 Gold Batts R2.0 50/41 2.2/2.4 51/42 2.4/2.6
FC 12969 INTERNAL WALL SIDE
• 2 x 13mm Gyprock Wall Thickness 153 173
Fyrchek Plasterboard. Excluding Cladding mm
CSR 5872
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 47/36 2.2/2.4
• 2 x 16mm Gyprock
120/120/120
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 48/37 2.6/2.9
(from outside only)
INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 46/35 2.2/2.4 47/36 2.4/2.6
FC 12969
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 147 167
Excluding Cladding mm
CSR 5874 EXTERNAL WALL SIDE (b) 90 Gold Batts R2.0 – – 52/43 2.2/2.4
• 2 x 16mm Gyprock
Fyrchek MR Plasterboard. (c) 90 Gold Batts R2.5 – – 53/44 2.6/2.9
120/120/120
(from both sides) INTERNAL WALL SIDE
FC 12969 • 2 x 16mm Gyprock (d) 75 Gold Batts R2.0 51/42 2.3/2.5 52/43 2.6/2.7
Fyrchek Plasterboard.
Wall Thickness 169 189
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F29


SYSTEM SPECIFICATIONS Masonry Veneer – With Cavity – Timber Frame

Fire rated masonry veneer wall. Timber studs at 600mm maximum


centres.
Wall wrap.
Cavity insulation as per system table.
40mm minimum gap to timber framing.
Lining material as per system
table to internal side.

NOTE: To achieve stated acoustic performance masonry


must be a minimum of 90mm thick and 170kg/m2.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A120


STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5877
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 59/51 2.3/2.6
60/60/60 • Masonry veneer wall with
(from outside only) FRL 60/60/60. (c) 90 Gold Batts R2.5 – – 59/51 2.8/3.1
refer to Masonry
Manufacturer INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 57/48 2.3/2.5 58/50 2.5/2.7
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness Excluding 80 100
Masonry & Cavity mm
CSR 5879
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 60/52 2.3/2.6
60/60/60 • Masonry veneer wall with
(from outside only) FRL 60/60/60. (c) 90 Gold Batts R2.5 – – 60/52 2.8/3.1
refer to Masonry
Manufacturer INTERNAL WALL SIDE (d) 75 Gold Batts R2.0 58/49 2.3/2.5 59/51 2.5/2.7
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness Excluding 80 100
Masonry & Cavity mm
CSR 10164
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 60/52 2.3/2.6
60/60/60 • Masonry veneer wall with
(from outside only) FRL 60/60/60. (b) 90 Gold Batts R2.5 – – 60/52 2.8/3.1
refer to Masonry
Manufacturer INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 58/49 2.3/2.5 59/51 2.5/2.7
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness Excluding 80 100
Masonry & Cavity mm
CSR 10165
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 62/55 2.3/2.6
• Masonry veneer wall with
60/60/60 (b) 90 Gold Batts R2.5 – – 62/55 2.8/3.1
FRL 60/60/60.
(from outside only)
refer to Masonry INTERNAL WALL SIDE
Manufacturer (c) 75 Gold Batts R2.0 60/52 2.4/2.6 61/54 2.6/2.8
• 2 x 10mm Gyprock HD
Plasterboard. Wall Thickness Excluding 90 110
Masonry & Cavity mm
CSR 5885 EXTERNAL WALL SIDE
• Masonry veneer wall with (b) 90 Gold Batts R2.0 – – 63/56 2.3/2.6
60/60/60*
(from both sides) FRL 60/60/60.
*ACR Group 1 (c) 90 Gold Batts R2.5 – – 63/56 2.8/3.1
INTERNAL WALL SIDE
FC 12969
and refer • 1 x 13mm Gyprock
(d) 75 Gold Batts R2.0 61/53 2.4/2.5 62/55 2.6/2.8
to Masonry Fyrchek Plasterboard.
Manufacturer •1 x 6mm CeminSeal Wall Thickness Excluding 89 109
Wallboard. (against frame) Masonry & Cavity mm

F30 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Masonry Veneer – With Cavity – Timber Frame

Fire rated masonry veneer wall. Timber studs at 600mm maximum


centres.
Wall wrap.
Cavity insulation as per system table.
40mm minimum gap to timber framing.
Lining material as per system
table to internal side.

NOTE: To achieve stated acoustic performance masonry


must be a minimum of 90mm thick and 170kg/m2.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.
*ACR = Axial Capacity Reduction.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A120


STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 5888
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 63/56 2.3/2.6
90/90/90 • Masonry veneer wall with
(from both sides) (c) 90 Gold Batts R2.5 – – 63/56 2.8/3.1
FRL 90/90/90.
FC 12969
and refer INTERNAL WALL SIDE
to Masonry (d) 75 Gold Batts R2.0 60/52 2.4/2.6 61/54 2.6/2.8
• 2 x 13mm Gyprock
Manufacturer
Fyrchek Plasterboard. Wall Thickness Excluding 96 116
Masonry & Cavity mm
CSR 5891
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.0 – – 62/55 2.3/2.6
60/60/60 • Masonry veneer wall with
(from both sides) (c) 90 Gold Batts R2.5 – – 62/55 2.8/3.1
FRL 60/60/60.
FC 12969
and refer INTERNAL WALL SIDE
to Masonry (d) 75 Gold Batts R2.0 61/53 2.4/2.5 62/55 2.6/2.8
• 1 x 16mm Gyprock
Manufacturer
Fyrchek Plasterboard. Wall Thickness Excluding 86 106
Masonry & Cavity mm
CSR 5893 EXTERNAL WALL SIDE
• Masonry veneer wall with (b) 90 Gold Batts R2.0 – – 64/57 2.3/2.6
90/90/90*
(from both sides) FRL 90/90/90.
*ACR Group 3 (c) 90 Gold Batts R2.5 – – 64/57 2.8/3.1
INTERNAL WALL SIDE
FC 12969
and refer • 1 x 16mm Gyprock
(d) 75 Gold Batts R2.0 62/54 2.4/2.6 63/56 2.6/2.8
to Masonry Fyrchek Plasterboard.
Manufacturer •1 x 6mm CeminSeal Wall Thickness Excluding 89 109
Wallboard. (against frame) Masonry & Cavity mm

GYPROCK® THE RED BOOK™ 1 F31


SYSTEM SPECIFICATIONS Hebel PowerPanelXL Wall – Timber Frame

24 or 35mm depth top hats at 900mm Timber or steel studs at 600mm


centres fixed to framing. maximum centres.

CSR Hebel PowerPanel XL screw fixed Cavity insulation as per system table.
to top hats.
Lining material as per system
Wall Wrap as per system table. table to internal side.

NOTE: Values in table are only valid for


24mm top hats and 90mm timber frame.
Stated R-values are based upon AS/NZS
4859:2018, including thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC LOGIC REPORT: 20140366.34/1909A/R3/GW

STUD DEPTH mm 90

Standard Reflective
FRL SYSTEM SYSTEM Wall Warp Wall Warp
WALL LININGS CAVITY INFILL Rw /
Report ICON Nº (Enviroseal RW (Thermoseal
(Refer to TABLE B6) Rw+Ctr Plus) Wall Wrap XP)

Rt(sum) / Rt(win) Rt(sum) / Rt(win)

CSR 21727 90 Gold Batts 2.0 41/26 – 2.99/3.15

180/180/180 INTERNAL WALL SIDE CSR 21728 90 Gold Batts 2.5 41/26 3.0/3.15 –
(from outside only)
• 1 x 10mm Gyprock
Plus Plasterboard. CSR 21730 90 Gold Batts 2.7 41/26 3.15/3.29 –
FCO 3003

Minimum Wall Thickness mm 199

F32 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Hebel PowerPanel Wall – Steel Frame

CSR Hebel PowerPanel screw fixed to Steel studs at 600mm maximum centres.
50mm top hats at 900mm centres.
Cavity insulation as per system table.
Wall Wrap as per system table.
Lining material as per system
table to internal side.

NOTE: Stated R-values are based upon


AS/NZS 4859:2018, including thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC LOGIC REPORT: 20171728.19/1603A/R1/GW

STUD DEPTH mm 92

FRL SYSTEM Enviroseal RW Plus


WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
Rt(sum) Rt(win)

CSR 21347

– /120/120 INTERNAL WALL SIDE 90 Acoustigard 14kg 50/41 2.62 2.78


(from outside only)
• 1 x 13mm Gyprock
Standard Plasterboard.
FCO 2532

Wall Thickness mm 230

CSR 21536
– /60/60
(from inside only) INTERNAL WALL SIDE
• 1 x 16mm Gyprock 90 Acoustigard 14kg 50/42 2.55 2.69
– /180/180 Fyrchek Plasterboard.
(from outside only) • Studs at 450mm
maximum centres.
FCO 2532 Wall Thickness mm 233

CSR 21537
– /90/90
(from inside only) INTERNAL WALL SIDE
• 2 x 13mm Gyprock 90 Acoustigard 14kg 53/45 2.62 2.77
– /180/180 Fyrchek Plasterboard.
(from outside only) • Studs at 450mm
maximum centres.
FCO 2532 Wall Thickness mm 243

CSR 21538
– /120/120 INTERNAL WALL SIDE
(from outside only) • 2 x 16mm Gyprock 90 Acoustigard 14kg 54/47 2.67 2.82
Fyrchek Plasterboard.
– /180/180
• Studs at 450mm
(from outside only)
maximum centres.
FCO 2532 Wall Thickness mm 249

GYPROCK® THE RED BOOK™ 1 F33


THERMALLY ENHANCED SYSTEMS INCLUDING
THERMAL BRIDGING CONSIDERATIONS
INTRODUCTION R-VALUE
Energy efficiency requirements for buildings are set The R-Value is a measure of the resistance to heat flow,
out in the NCC as performance requirements and also known as thermal resistance. The greater the R-Value
acceptable construction practices, and are dependent (m2 k/W), the greater the resistance to heat transfer, and
on geographical climate zones. To meet the requirements, the greater the insulating effect and subsequent energy
it is recommended that insulation be installed in the savings.
wall framing and provision of appropriate sealing of the
building envelope. Check with local building authorities for
minimum insulation requirements. The level of insulation
Product/Material R-Value
provided by a wall is described by its Total R-Value. The The product/material R-Values represents the thermal
determination of the total R-Value requirement should resistance performance of a specific product/building
be considered on a situation-by-situation basis, but element. Refer to TABLE B6 for the R-Values of the
generally will follow the order as shown in FIG F1. In this insulations recommended in the CSR Redbook. Note that
section, thermally enhanced systems are introduced: the insulation also improves the acoustic performance of
double stud system, continuous internal insulation system the wall against noise transmission.
& continuous external insulation system.
Total R-Value
FIG F1: GENERAL STEPS FOR DETERMINATION OF The Total R-Value is the sum of the R-Values of the
ENERGY EFFICIENCY REQUIREMENTS individual component layers in a composite element
including any building material, insulating material,
Determine building class
airspace, thermal bridging and associated surface
resistances. NCC 2022 volume 1 defines the total R-Value
Class 2 to Class 9 Class 1 & Class 10
as a metric of compliance, refer to FIG F1 for the general
steps for determination of energy efficiency requirements.
The total R-Value (including thermal bridging of the wall
Determine: Determine: systems detailed in this section) will not be detrimentally
• Climate Zone • Climate Zone affected by:
• Floor Area • Floor Area
• Opaque external wall area • Opaque external wall area
• Wall-glazing construction • Wall-glazing construction • Increasing the wall thickness
• Increasing the frame spacings
Identify requirements from: Identify requirements from:
• NCC 2022 Volume One Section • NCC 2022 Volume Two Section
• Decreasing the number of noggings
J – Energy efficiency J – Energy efficiency
performance requirement, and performance requirement, and • Decreasing the BMT of the steel framing
• Local building authorities • Local building authorities
requirements requirements
System R-Value Solution
The project energy efficiency The project energy efficiency The system R-Value represents the thermal resistance
opaque wall requirements can opaque wall requirements can performance of a system. For systems on page F38 to
include: include:
• Minimum wall insulation R value • Total R value including thermal page F54, systems R-Values including thermal bridging
requirement bridging, and are modeled in accordance with AS/NZS4859.2:2018
• Mandatory thermal break • Thermal break when required
• Total R value including thermal which includes thermal bridging in accordance with
bridging assessment, or
• Thermal bridging mitigation
NZS4214 and NCC requirements. The system R-Values
provision are based on product/material R-Values in service
conditions, including the alteration of insulation product/
material R-Value for temperature, and air space for
Choose the appropriate system:
• Select the appropriate CSR temperature and infrared emittance.
system to suit project specific
requirements, including While the total R-Value in The Red Book is based on
structural, thermal, fire and
acoustic values. specific modelling with the following general modelling
assumptions, it is recommended to consult with qualified
engineers for specific thermal design.

F34 GYPROCK® THE RED BOOK™ 1


The influence on the R-vlaue of the insulation has been 7. Façade cavity: The cavity is assumed to be well-
considered such that higher temperature results in lower ventilated and the thermal resistance of a well-
R-Value and lower temperature results in higher R-Value. ventilated air space and no thermal resistance for
The R-Value for the thermally enhanced external wall the CSR cladding and external air film have been
systems include thermal ratings expressed as Rt(WIN) adopted.
and Rt(SUM) to represent Total R-Values for the winter
8. Wall cavities: Still air space thermal resistance was not
and summer design conditions as required by AS/NZS
considered.
4859.1, which is called upon in the NCC.
9. Wall Insulation: Although the specified wall insulation
Broadly the calculation involves determining the unique
must be installed within the steel sections (i.e., studs,
pathways through the wall with different arrangements of
tracks, noggings) and provides 100% coverage of
components and then using a weighted area approach to
the wall area, it is assumed no insulation in the steel
calculate an equivalent Total R-Value of the bridged layers
sections for the thermal calculations.
and then combined with the uniform layers to calculate
the Total R-Value. 10. Compression of insulation: Insulation is assumed to
recover to its nominal thickness unless the cavity
GENERAL MODELING dimension is less than the nominal thickness of the
selected insulation. The influence of compression on
ASSUMPTIONS the thermal resistance was considered.
The modelings of the thermally enhanced systems include 11. Solar absorptance, air leakage, emissivity have not
the assumptions listed below: been considered in the calculation.
1. Calculation methodology: Calculated in accordance 12. When wall wrap is specified as an air barrier, the use
with ASNZS4859.2:2018 which includes thermal of Cemintel Rigid Air Barrier will not detrimentally
bridging in accordance with NZS4214 and the affect the thermal performance stated.
National Construction Code versions NCC2019
Amendment 1 and NCC2022. Note the calculation
and model may not be representative of actual in-situ
THERMAL BRIDGING
performance and construction. Thermal bridging is a path of least resistance for heat to
travel, which can significantly reduce the effectiveness
2. Changes to the system components and configuration
of insulation. An example is where a steel stud with high
described may result in changes to Total R-Value
thermal conductivity interrupts the insulation layer. This
thermal performance.
can result in internal heat loss on a cold day and internal
3. Thermal resistance: Where specified, CSR insulation heat gain on a hot day. At thermal bridging locations,
products are tested in accordance with ASNZS4859:1 condensation may occur where warm, moist air contacts
in a NATA certified laboratory. Where available, NATA a colder surface. The detrimental impact of a thermal
tested supporting data for thermal resistance is used bridge can be diminished with the installation of a thermal
for other products or when test data is unavailable, break, which increases the resistance for heat to travel at
AIRAH, ASHRAE or NCC reference data for generic the thermal bridging locations. Typically, the thermal break
materials is used. has low thermal conductivity.
4. In accordance with AS4859:2018, the System
Total R-Value includes mean temperature condition THERMAL BREAK
adjustments of material R-Value to Australia-Only For some situations, e.g. Class 2 buildings or Class 4
conditions. For wall insulation, an iterative approach parts of a building, an envelope consisting of a metal
determined the insulation temperature from the framed wall with an external fibre-cement cladding and an
temperature profile (based on Australian seasonal internal lining directly fixed to the frame, NCC2022 J3D6
temperature differences) and adjusted the R-Value of (1) [2019: J0.5] requires a thermal break to be installed
insulation. between all points of contact between the external fibre-
- WINTER: air temperature difference of 12°C to 18°C; cement cladding and the metal frame.

- SUMMER: air temperature difference of 24°C to The thermal break shall have a minimum R-Value of
36°C. R0.2. The Australian Building and Construction Board
(ABCB), “Energy efficiency NCC Volume One Handbook”,
5. Material properties: Unless stated otherwise, all
June 2019, advises a thermal break is not needed if a
materials are assumed to be a constant thickness.
secondary framing member, orientated perpendicular to
6. Packers: Thermal bridging due to the incorporation the metal frame, is installed between the metal frame and
of packers has been included in this calculation. lightweight external cladding.

GYPROCK® THE RED BOOK™ 1 F35


NCC REQUIREMENTS
NCC 2019 for Volume 1 and NCC 2022 for Volume 2
includes changes to energy efficiency requirements. These
requirements will express the R-Value of the building fabric
system as the Total R-Value inclusive of thermal bridging.
The Total R-Value will consider the project specific
external wall configuration and materials used, so that the
detrimental impact of the thermal bridging on the added
insulation is captured. Additional to the effects of thermal
bridging through the framing paths of the structure, the
designer will need to allow for the following:
• Gaps in the bulk insulation layer in the wall system due
to structural framing (i.e., studs, noggings, perimeter of
wall openings) and services obstructing or limiting wall
insulation coverage;
• Slab edge insulation;
• Wall cavity ventilation; and
• The effects of air leakage due to unsealed architraves,
unsealed door jambs, unsealed gaps between windows
and the masonry wall or services penetrating the inner
leaf.
These effects are to be compensated for as outlined in
Section J of the NCC.
For projects conforming to NCC versions prior to the NCC
2022, thermal bridging consideration is not required in the
Total R-Value calculation for all building classes, such as:
• Class 2 to Class 9 buildings for NCC 2016 Amdt. 1
Volume One and NCC 2016 Amdt. 1 Volume Two (and
earlier).
• Class 1 and Class 10 only for NCC 2019 (incl. Amdt. 1)
Volume Two.

ADDITIONAL DESIGN
CONSIDERATIONS FOR
THERMALLY BRIDGED SYSTEMS
The calculations provided in this section only assess and
provide a system's thermal performance. Other factors
which are not considered and should be independently
assessed, include but are not limited to:
• Structural adequacy
• Weatherproofing
• Fire resistance
• Condensation management
• The suitability of the wall system and products for a
project should be independently verified by the specifier
or purchaser prior to use.

F36 GYPROCK® THE RED BOOK™ 1


Thermally Bridged Systems and Thermal Pathways – Double Stud
FIG F2: THERMALLY ENHANCED WALL SYSTEM – DOUBLE STUD

Approved fire rated sealant


76mm steel studs
(0.75BMT) at 450mm
centres
Wall Wrap as moisture
75mm cavity insulation as barrier, taped at top and
per system table bottom, overlap and tape
all joins
Lining material as per
system table to internal Rondo H515 horizontal
side of stud framing Top Hats at 400mm
centres fixed to studs

92mm steel studs


(1.15BMT) at 450mm
centres

90mm cavity insulation as Cemintel ExpressPanel,


per system table Barestone or Surround
Panel on ventilated cavity
cladding support system,
(does not contribute to
Lining material as per thermal calculations)
system table to external
side of stud framing,
horizontal sheeting, butt
joints offset by one stud,
tape and set all joints in
outer layer

30mm air gap filled with


NOTE: Images are for representation purposes only
25mm insulation as per
and may not accurately represent actual products,
system table
Approved fire rated sealant construction and/or installation methods. For general
calculation assumptions, refer to page F35

The wall model used in the calculation has four (4) unique • Internal side stud framing: 76mm x 0.75mm BMT steel
thermal resistance pathways from exterior to interior. sections (i.e., studs, tracks and noggings).
The following specific assumptions were used for this
• 100% alignment between the external side and internal
calculation:
side steel stud sections.
• External side stud framing: 92mm x 1.15mm BMT steel
• No alignment between the horizontal top hats and
sections (i.e., studs, tracks and noggings).
noggings of the external side stud framing.

TABLE F2: THERMAL PATHWAYS THROUGH DOUBLE STUD SYSTEM


Pathway Thermal Pathway Through Wall Weighted Area (%)
Lining materials + cavity insulation materials
1 77.70
NOT ALIGNED with stud framing or horizontal top hats.
Stud framing + aligned materials
2 15.63
but EXCLUDING areas intersecting with horizontal top hats.
Horizontal top hats + aligned materials
3 5.55
but EXCLUDING areas intersecting with stud framing.
Wall materials
4 1.12
SIMULTANEOUSLY ALIGNED with stud framing and horizontal top hats.
NOTES: 'Stud framing' includes studs, tracks and noggings.

GYPROCK® THE RED BOOK™ 1 F37


SYSTEM SPECIFICATIONS Cemintel Panel Cladding – Thermally Enhanced – Double Stud

92mm steel studs (1.15BMT) at Lining material as per system


450mm centres. table to internal side.

Lining material as per system 76mm steel studs (0.75BMT) at 450mm


table to external side. centres.

Wall Wrap. 75mm cavity insulation as per


system table.
90mm cavity insulation as per
system table. 30mm air gap filled with 25mm insulation
as per system table.
Cemintel ExpressPanel, Barestone
or Surround panel on ventilated NOTE: Acoustic performance valid for studs noted.
cavity cladding support system. The system thermal R-Values provided have been
calculated based on the specified wall configuration only,
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119


SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB3-01.01

FRL SYSTEM CAVITY INFILL Rt(sum) /


WALL LININGS EXTERNAL/AIR GAP/INTERNAL Rw / Rw+Ctr
Report Nº Rt(win)
(Refer to TABLE B6)

CSR 10108 90 Acoustigard 24kg


EXTERNAL WALL SIDE
(a) 25 Acoustigard 24kg 53/44 2.84/3.03
75 Acoustigard 24kg
• Nil.
–/–/– 90 Acoustigard 32kg
INTERNAL WALL SIDE
(b) 25 Acoustigard 32kg 53/44 3.01/3.21
• 1 x 13mm Gyprock 75 Acoustigard 32kg
Standard Plasterboard.
Wall Thickness 261
Excluding Cladding mm
CSR 10109 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 54/43 2.84/3.03
• 1 x 13mm Gyprock 75 Acoustigard 24kg
30/30/30
Fyrchek MR Plasterboard.
(from outside only) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 54/43 3.01/3.21
FC 12946 75 Acoustigard 32kg
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 271
Excluding Cladding mm
CSR 10110 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 57/46 2.84/3.03
• 1 x 13mm Gyprock 75 Acoustigard 24kg
30/30/30
Fyrchek MR Plasterboard.
(from outside only) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 57/46 3.01/3.21
FC 12946 75 Acoustigard 32kg
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 271
Excluding Cladding mm
CSR 10111 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 59/49 2.84/3.03
30/30/30 • 1 x 13mm Gyprock 75 Acoustigard 24kg
–/60/60 Fyrchek MR Plasterboard.
(from both sides) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 59/49 3.01/3.21
FC 12946 • 1 x 13mm Gyprock EC08 75 Acoustigard 32kg
Extreme Plasterboard. Wall Thickness 274
Excluding Cladding mm
CSR 10112 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 57/47 2.84/3.03
• 2 x 13mm Gyprock 75 Acoustigard 24kg
90/90/90
Fyrchek MR Plasterboard.
(from outside only) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 57/47 3.01/3.21
FC 12946 75 Acoustigard 32kg
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 284
Excluding Cladding mm

F38 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Panel Cladding – Thermally Enhanced – Double Stud
Lining material as per system
92mm steel studs (1.15BMT) at
table to internal side.
450mm centres.
76mm steel studs (0.75BMT) at 450mm
Lining material as per system
centres.
table to external side.
75mm cavity insulation as per
Wall Wrap.
system table.
90mm cavity insulation as per
30mm air gap filled with 25mm insulation
system table.
as per system table.
Cemintel ExpressPanel, Barestone NOTE: Acoustic performance valid for studs noted.
or Surround panel on ventilated The system thermal R-Values provided have been
cavity cladding support system. calculated based the specified wall configuration only,
and allow for the effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

ACOUSTIC REPORT: PKA-A119


SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB3-01.01

FRL SYSTEM CAVITY INFILL Rt(sum) /


WALL LININGS EXTERNAL/AIR GAP/INTERNAL Rw / Rw+Ctr
Report Nº Rt(win)
(Refer to TABLE B6)

CSR 10113 90 Acoustigard 24kg


EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 58/47 2.84/3.03
• 1 x 16mm Gyprock 75 Acoustigard 24kg
30/30/30
Fyrchek MR Plasterboard.
(from outside only) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 58/47 3.01/3.21
FC 12946 75 Acoustigard 32kg
• 1 x 6mm Cemintel
Wallboard. Wall Thickness 270
Excluding Cladding mm
CSR 10114 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 57/46 2.84/3.03
• 1 x 16mm Gyprock 75 Acoustigard 24kg
60/60/60
Fyrchek MR Plasterboard.
(from outside only) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 57/46 3.01/3.21
FC 12946 75 Acoustigard 32kg
• 1 x 10mm Gyprock
Aquachek Plasterboard . Wall Thickness 274
Excluding Cladding mm
CSR 10115 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 59/49 2.84/3.03
60/60/60 • 1 x 16mm Gyprock 75 Acoustigard 24kg
–/90/90 Fyrchek MR Plasterboard.
(from both sides) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 59/49 3.01/3.21
FC 12946 • 1 x 16mm Gyprock 75 Acoustigard 32kg
Fyrchek Plasterboard. Wall Thickness 280
Excluding Cladding mm
CSR 10116 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 58/48 2.84/3.03
• 2 x 16mm Gyprock 75 Acoustigard 24kg
120/120/120
Fyrchek MR Plasterboard.
(from outside only) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 58/48 3.01/3.21
FC 12946 75 Acoustigard 32kg
• 1 x 10mm Gyprock Plus
Plasterboard. Wall Thickness 290
Excluding Cladding mm
CSR 10117 90 Acoustigard 24kg
EXTERNAL WALL SIDE (a) 25 Acoustigard 24kg 63/54 2.84/3.03
120/120/120 • 2 x 16mm Gyprock 75 Acoustigard 24kg
–/180/180‡ Fyrchek MR Plasterboard.
(from both sides) 90 Acoustigard 32kg
INTERNAL WALL SIDE (b) 25 Acoustigard 32kg 63/54 3.01/3.21
FC 12946 • 2 x 16mm Gyprock 75 Acoustigard 32kg
Fyrchek Plasterboard. Wall Thickness 312
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F39


Thermally Bridged Systems and Thermal Pathways – Internal Furring + Insulation
FIG F3: THERMALLY ENHANCED WALL SYSTEM – INTERNAL FURRING + INSULATION SYSTEM

RONDO BG01 clip with


308 furring channel Approved fire rated sealant
OR,
RONDO BG05 clip with
129 furring channel
Wall Wrap as moisture
barrier, taped at top and
BG01 BG05
bottom, overlap and tape
all joins

Rondo H515 horizontal


Top Hats at 400mm
31mm 76mm centres fixed to studs
nom nom

Lining material as per


system table to internal side
Cemintel ExpressPanel,
25mm or 75mm cavity insulation Barestone or Surround
as per system table Panel on ventilated cavity
cladding support system,
(does not contribute to
thermal calculations)‘ ‘
92mm steel studs
(1.15BMT) at 450mm
centres

90mm cavity insulation


as per system table

Lining material as per


system table to external
side of stud framing,
horizontal sheeting, butt
joints offset by one stud,
tape and set all joints in
outer layer NOTE: Images are for representation purposes only
and may not accurately represent actual products,
Approved fire rated sealant construction and/or installation methods. For general
calculation assumptions, refer to page F35

The wall model used in the calculation has four (4) unique • Internal side framing: Rondo BG01 clip (31mm cavity)
thermal resistance pathways from exterior to interior. with No.308 furring channel, or Rondo BG05 clip
The following specific assumptions were used for this (76mm cavity) with No.129 furring channel.
calculation:
• 100% alignment between the studs and internal furring
• External side stud framing: 92mm x 1.15mm BMT steel channels.
sections (i.e., studs, tracks, noggings).
• No alignment between the horizontal top hats and
noggings of the stud framing.

TABLE F3: THERMAL PATHWAYS THROUGH INTERNAL FURRING AND INSULATION SYSTEM
Pathway Thermal Pathway Through Wall Weighted Area (%)
Lining materials + cavity insulation materials
1 79.03
NOT ALIGNED with stud framing or horizontal top hats or furring or clips.
Stud framing + aligned materials
2 15.88
but EXCLUDING areas intersecting with horizontal top hats or furring or clips.
Horizontal top hats + aligned materials
3 4.22
but EXCLUDING areas intersecting with stud framing or furring or clips.
Wall materials
4 0.87
SIMULTANEOUSLY ALIGNED with stud framing and horizontal top hats
NOTES: 'Stud framing' includes studs, tracks and noggings.

F40 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Panel Cladding – Thermally Enhanced – Internal Furring + Insulation

92mm steel studs (1.15BMT) at Lining material as per system


450mm centres. table to internal side.

Lining material as per system Rondo BG01 Clip + 308 Furring channel
table to external side. OR
Rondo BG05 Clip + 129 Furring Channel.
Wall Wrap.
25mm or 75mm cavity insulation as per
Cemintel ExpressPanel, Barestone system table.
or Surround panel on ventilated
cavity cladding support system.

90mm cavity insulation as per


NOTE: Acoustic performance valid for studs noted.
system table.
The system thermal R-Values provided have been
calculated based the specified wall configuration only,
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

FRAMING
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB3-02.01
FRL SYSTEM STUD CAVITY INFILL CLIP + FURRING Rw / Rt(sum)
WALL LININGS WITH INFILL
Report Nº (Refer to TABLE B6)
(Refer to TABLE B6) Rw+Ctr / Rt(win)
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 48/38 2.03/2.17

RONDO 308
CSR 10118

BG01 +
EXTERNAL WALL SIDE (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 48/38 2.16/2.30
• Nil.
Wall Thickness Excluding Cladding mm 186
–/–/– INTERNAL WALL SIDE
• 1 x 13mm Gyprock
RONDO 129 (c) 90 Acoustigard 24kg 75 Acoustigard 24kg 50/40 3.71/4.02
BG05 +

Standard Plasterboard.
(d) 90 Acoustigard 32kg 75 Acoustigard 32kg 50/40 3.92/4.24
Wall Thickness Excluding Cladding mm 231
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 49/38 2.03/2.17
RONDO 308

CSR 10119 EXTERNAL WALL SIDE


BG01 +

• 1 x 13mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/38 2.16/2.30


30/30/30 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 196
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 51/40 3.71/4.02
RONDO 129

FC 12946 INTERNAL WALL SIDE


BG05 +

• 1 x 10mm Gyprock Plus (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 51/40 3.92/4.24
Plasterboard.
Wall Thickness Excluding Cladding mm 241
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 51/40 2.03/2.17
RONDO 308

CSR 10120 EXTERNAL WALL SIDE


BG01 +

• 1 x 13mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/40 2.16/2.30


30/30/30 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 196
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 52/41 3.71/4.02
RONDO 129

FC 12946 INTERNAL WALL SIDE


BG05 +

• 1 x 10mm Gyprock HD (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 52/41 3.92/4.24


Plasterboard.
Wall Thickness Excluding Cladding mm 241
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 53/43 2.03/2.17
RONDO 308

CSR 10121 EXTERNAL WALL SIDE


BG01 +

• 1 x 13mm Gyprock
(b) 90 Acoustigard 32kg 25 Acoustigard 32kg 53/43 2.16/2.30
30/30/30 Fyrchek MR
–/60/60 Plasterboard. Wall Thickness Excluding Cladding mm 199
(from both sides)
INTERNAL WALL SIDE (c) 90 Acoustigard 24kg 75 Acoustigard 24kg 54/44 3.71/4.02
RONDO 129
BG05 +

FC 12946 • 1 x 13mm Gyprock


EC08 Extreme (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 54/44 3.92/4.24
Plasterboard. Wall Thickness Excluding Cladding mm 244
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 51/41 2.03/2.17
RONDO 308

CSR 10122 EXTERNAL WALL SIDE


BG01 +

• 2 x 13mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 2.16/2.30


90/90/90 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 209
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 52/42 3.71/4.02
RONDO 129

FC 12946 INTERNAL WALL SIDE


BG05 +

• 1 x 10mm Gyprock Plus (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 52/42 3.92/4.24
Plasterboard.
Wall Thickness Excluding Cladding mm 254

GYPROCK® THE RED BOOK™ 1 F41


SYSTEM SPECIFICATIONS Cemintel Panel Cladding – Thermally Enhanced – Internal Furring + Insulation

92mm steel studs (1.15BMT) at Lining material as per system


450mm centres. table to internal side.

Lining material as per system Rondo BG01 Clip + 308 Furring channel
table to external side. OR
Rondo BG05 Clip + 129 Furring Channel.
Wall Wrap.
25mm or 75mm cavity insulation as per
Cemintel ExpressPanel, Barestone system table.
or Surround panel on ventilated
cavity cladding support system.
NOTE: Acoustic performance valid for studs noted.
90mm cavity insulation as per The system thermal R-Values provided have been
system table. calculated based the specified wall configuration only,
and allow for the effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

ACOUSTIC REPORT: PKA-A119

FRAMING
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB3-02.01
FRL SYSTEM STUD CAVITY INFILL CLIP + FURRING Rw / Rt(sum)
WALL LININGS WITH INFILL
Report Nº (Refer to TABLE B6)
(Refer to TABLE B6) Rw+Ctr / Rt(win)
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 52/41 2.03/2.17

RONDO 308
CSR 10123 EXTERNAL WALL SIDE

BG01 +
• 1 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 52/41 2.16/2.30
30/30/30 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 195
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 53/42 3.71/4.02
RONDO 129

FC 12946 INTERNAL WALL SIDE


BG05 +

• 1 x 6mm Cemintel (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 53/42 3.92/4.24


Wallboard.
Wall Thickness Excluding Cladding mm 240
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/39 2.03/2.17
RONDO 308

CSR 10124 EXTERNAL WALL SIDE


BG01 +

• 1 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 50/39 2.16/2.30


60/60/60 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 199
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 52/41 3.71/4.02
RONDO 129

FC 12946 INTERNAL WALL SIDE


BG05 +

• 1 x 10mm Gyprock (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 52/41 3.92/4.24


Aquachek Plasterboard .
Wall Thickness Excluding Cladding mm 244
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 53/43 2.03/2.17
RONDO 308

CSR 10125 EXTERNAL WALL SIDE


BG01 +

• 1 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 53/43 2.16/2.30


60/60/60
Fyrchek MR
–/90/90 Plasterboard. Wall Thickness Excluding Cladding mm 205
(from both sides)
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 54/44 3.71/4.02
RONDO 129

INTERNAL WALL SIDE


BG05 +

FC 12946 • 1 x 16mm Gyprock (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 54/44 3.92/4.24
Fyrchek Plasterboard.
Wall Thickness Excluding Cladding mm 250
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 52/42 2.03/2.17
RONDO 308

CSR 10126 EXTERNAL WALL SIDE


BG01 +

• 2 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 52/42 2.16/2.30


120/120/120 Fyrchek MR
(from outside only) Wall Thickness Excluding Cladding mm 215
Plasterboard.
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 53/43 3.71/4.02
RONDO 129

FC 12946 INTERNAL WALL SIDE


BG05 +

• 1 x 10mm Gyprock Plus (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 53/43 3.92/4.24
Plasterboard.
Wall Thickness Excluding Cladding mm 260
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 57/48 2.03/2.17
RONDO 308

CSR 10127 EXTERNAL WALL SIDE


BG01 +

• 2 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 57/48 2.16/2.30


120/120/120
Fyrchek MR
–/180/180‡ Plasterboard. Wall Thickness Excluding Cladding mm 237
(from both sides)
(c) 90 Acoustigard 24kg 75 Acoustigard 24kg 58/49 3.71/4.02
RONDO 129

INTERNAL WALL SIDE


BG05 +

FC 12946 • 2 x 16mm Gyprock (d) 90 Acoustigard 32kg 75 Acoustigard 32kg 58/49 3.92/4.24
Fyrchek Plasterboard.
Wall Thickness Excluding Cladding mm 282

F42 GYPROCK® THE RED BOOK™ 1


Thermally Bridged Systems and Thermal Pathways – External Batten + Insulation
FIG F4: THERMALLY ENHANCED WALL SYSTEM – EXTERNAL BATTEN + INSULATION

Approved fire rated sealant


J-track at top of wall
fixed to soffit
Lining material as per
system table to internal
Wall Wrap as air barrier,
side of stud framing
taped at top and bottom,
overlap and tape all joins

92mm steel studs (1.15BMT)


Rondo H525 Top Hat fixed to
at 450mm centres
studs
OR
Rondo H515 Top Hat on pads of
90mm cavity insulation 10mm thick, min. R0.2 thermal
as per system table break fixed to studs

Wall Wrap as moisture


Lining material as per barrier, taped at top and
system table to external side bottom, overlap and tape
of stud framing, horizontal all joins
sheeting, butt joints offset by
one stud, tape and set all
outer layer joints Cemintel ventilated
cavity framing system

25mm insulation Cemintel ExpressPanel,


continuous between Top Barestone or Surround
Hats, as per system table Panel on ventilated cavity
cladding support system.
(does not contribute to
thermal calculations)
Rondo Top Hats at 400mm
centres, fixed to studs
J-track at bottom of wall
fixed to floor

Approved fire rated sealant NOTE: Images are for representation purposes only
and may not accurately represent actual products,
construction and/or installation methods. For general
calculation assumptions, refer to page F35.

FIG F5: TOP HAT OPTIONS


Wall Wrap Wall Wrap The wall model used in the calculation has four (4) unique
H525 Top Hat Thermal Break H515 Top Hat thermal resistance pathways from exterior to interior.
The following specific assumptions were used for this
calculation:
• Horizontal top hats: Rondo H525 or Rondo H515 on
Cladding support

Cladding support

10mm thick thermal break pads.


Stud Stud • Internal side stud framing: 92mm x 1.15mm BMT steel
frame frame
sections (i.e., studs, tracks, nogging).
• No alignment between the horizontal top hats and
noggings of the internal stud framing.
Plasterboard as Insulation Plasterboard as Insulation
per system table per system table
Rondo H525 with 25mm Rondo H515 with pads of 10mm thick,
insulation continuous min. R0.2 thermal break at intersection
between Top Hats with studs, and 25mm insulation
continuous between Top Hats

TABLE F4: THERMAL PATHWAYS THROUGH DOUBLE STUD SYSTEM


Pathway Thermal Pathway Through Wall Weighted Area (%)
Lining materials + cavity insulation materials
1 73.54
NOT ALIGNED with stud framing or horizontal top hats.
Stud framing + aligned materials
2 14.80
but EXCLUDING areas intersecting with horizontal top hats.
Horizontal top hats + aligned materials
3 9.71
but EXCLUDING areas intersecting with stud framing.
Wall materials
4 1.95
SIMULTANEOUSLY ALIGNED with stud framing and horizontal top hats.
NOTES: 'Stud framing' includes studs, tracks and noggings.

GYPROCK® THE RED BOOK™ 1 F43


SYSTEM SPECIFICATIONS Cemintel Panel Cladding – Thermally Enhanced – External Batten + Insulation

92mm steel studs (1.15BMT) at Lining material as per system


450mm centres. table to internal side.

25mm cavity insulation as per 90mm cavity insulation as per


system table. system table.

Lining material as per system H525 Top Hat


table to external side. OR
H515 Top Hat with 10mm thick, min. R0.2
Cemintel ExpressPanel, Barestone thermal break at intersection with stud framing.
or Surround panel on ventilated
cavity cladding support system. Wall Wrap.

Wall Wrap. NOTE: Acoustic performance valid for studs noted.


The system thermal R-Values provided have been
calculated based the specified wall configuration only,
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

FRAMING
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB3-03.01
FRL SYSTEM STUD CAVITY INFILL EXTERNAL BATTEN Rw / Rt(sum)
WALL LININGS
Report Nº (Refer to TABLE B6) WITH INFILL Rw+Ctr / Rt(win)
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 47/37 1.76/1.85

Rondo H525
CSR 10128
EXTERNAL WALL SIDE (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 48/38 1.85/1.94
• Nil.
Wall Thickness Excluding Cladding mm 165
–/–/– INTERNAL WALL SIDE
Rondo H515 +
Thermal Break

• 1 x 13mm Gyprock (c) 90 Acoustigard 24kg 25 Acoustigard 24kg 48/38 2.06/2.18


Standard Plasterboard. (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/39 2.18/2.30
Wall Thickness Excluding Cladding mm 165
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 47/36 1.76/1.85
Rondo H525

CSR 10129 EXTERNAL WALL SIDE


• 1 x 13mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 48/37 1.85/1.94
30/30/30 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 175
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 48/37 2.06/2.18
FC 12946
• 1 x 10mm Gyprock Plus (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/38 2.18/2.30
Plasterboard.
Wall Thickness Excluding Cladding mm 175
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 48/37 1.76/1.85
Rondo H525

CSR 10130 EXTERNAL WALL SIDE


• 1 x 13mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/38 1.85/1.94
30/30/30 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 175
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 48/37 2.06/2.18
FC 12946
• 1 x 10mm Gyprock HD (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/38 2.18/2.30
Plasterboard.
Wall Thickness Excluding Cladding mm 175
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/40 1.76/1.85
Rondo H525

CSR 10131 EXTERNAL WALL SIDE


• 1 x 13mm Gyprock
(b) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 1.85/1.94
60/60/60 Fyrchek MR
–/90/90 Plasterboard. Wall Thickness Excluding Cladding mm 178
(from both sides)
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE (c) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/40 2.06/2.18
FC 12946 • 1 x 13mm Gyprock
EC08 Extreme (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 2.18/2.30
Plasterboard. Wall Thickness Excluding Cladding mm 178
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 49/39 1.76/1.85
Rondo H525

CSR 10132 EXTERNAL WALL SIDE


• 2 x 13mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 50/40 1.85/1.94
90/90/90 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 188
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 49/39 2.06/2.18
FC 12946
• 1 x 10mm Gyprock Plus (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 50/40 2.18/2.30
Plasterboard.
Wall Thickness Excluding Cladding mm 188

F44 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Panel Cladding – Thermally Enhanced – External Batten + Insulation
92mm steel studs (1.15BMT) at Lining material as per system
450mm centres. table to internal side.

25mm cavity insulation as per 90mm cavity insulation as per


system table. system table.

Lining material as per system H525 Top Hat


table to external side. OR
H515 Top Hat with 10mm thick, min. R0.2
Cemintel ExpressPanel, Barestone thermal break at intersection with stud framing.
or Surround panel on ventilated
cavity cladding support system.
NOTE: Acoustic performance valid for studs noted.
Wall Wrap. The system thermal R-Values provided have been
calculated based on the specified wall configuration
only, and allow for the effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

ACOUSTIC REPORT: PKA-A119

FRAMING
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB3-03.01
FRL SYSTEM STUD CAVITY INFILL EXTERNAL BATTEN Rw / Rt(sum)
WALL LININGS
Report Nº (Refer to TABLE B6) WITH INFILL Rw+Ctr / Rt(win)
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 49/38 1.76/1.85

Rondo H525
CSR 10133 EXTERNAL WALL SIDE
• 1 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 50/39 1.85/1.94
30/30/30 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 174
Rondo H515 +
INTERNAL WALL SIDE Thermal Break (c) 90 Acoustigard 24kg 25 Acoustigard 24kg 49/38 2.06/2.18
FC 12946
• 1 x 6mm Cemintel (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 50/39 2.18/2.30
Wallboard.
Wall Thickness Excluding Cladding mm 174
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 48/37 1.76/1.85
Rondo H525

CSR 10134 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/38 1.85/1.94
60/60/60 Fyrchek MR
(from outside only) Plasterboard. Wall Thickness Excluding Cladding mm 178
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 49/38 2.06/2.18
FC 12946
• 1 x 10mm Gyprock (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 49/38 2.18/2.30
Aquachek Plasterboard .
Wall Thickness Excluding Cladding mm 178
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/40 1.76/1.85
Rondo H525

CSR 10135 EXTERNAL WALL SIDE


• 1 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 1.85/1.94
60/60/60
Fyrchek MR
–/90/90 Plasterboard. Wall Thickness Excluding Cladding mm 184
(from both sides)
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/40 2.06/2.18
FC 12946 • 1 x 16mm Gyprock (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 2.18/2.30
Fyrchek Plasterboard.
Wall Thickness Excluding Cladding mm 184
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/40 1.76/1.85
Rondo H525

CSR 10136 EXTERNAL WALL SIDE


• 2 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 1.85/1.94
120/120/120 Fyrchek MR
(from outside only) Wall Thickness Excluding Cladding mm 194
Plasterboard.
Rondo H515 +
Thermal Break

FC 12946 INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 50/40 2.06/2.18
• 1 x 10mm Gyprock Plus (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 51/41 2.18/2.30
Plasterboard.
Wall Thickness Excluding Cladding mm 194
(a) 90 Acoustigard 24kg 25 Acoustigard 24kg 54/45 1.76/1.85
Rondo H525

CSR 10137 EXTERNAL WALL SIDE


• 2 x 16mm Gyprock (b) 90 Acoustigard 32kg 25 Acoustigard 32kg 55/46 1.85/1.94
120/120/120
Fyrchek MR
–/180/180‡ Plasterboard. Wall Thickness Excluding Cladding mm 216
(from both sides)
Rondo H515 +
Thermal Break

INTERNAL WALL SIDE


(c) 90 Acoustigard 24kg 25 Acoustigard 24kg 54/45 2.06/2.18
FC 12946 • 2 x 16mm Gyprock (d) 90 Acoustigard 32kg 25 Acoustigard 32kg 55/46 2.18/2.30
Fyrchek Plasterboard.
Wall Thickness Excluding Cladding mm 216

GYPROCK® THE RED BOOK™ 1 F45


THERMALLY BRIDGED SYSTEMS AND THERMAL PATHWAYS –
OTHER SYSTEMS

The wall model used in the calculation have considered the thermal resistance pathways from exterior to interior for the
following systems. A 10mm thick, R0.2 thermal break was included in the calculation when required as per the system
table. For general calculation assumptions, refer to page F35.

TABLE F5: THERMAL PATHWAYS FOR SYSTEMS ON page F47 & page F48
Pathway Thermal Pathway Through Wall Weighted Area (%)
Lining materials + cavity insulation materials
1 85.89
NOT ALIGNED with stud framing.
Wall materials
2 14.05
ALIGNED with stud framing.
NOTES: 'Stud framing' includes studs, tracks and noggings.

TABLE F6: THERMAL PATHWAYS FOR SYSTEMS ON page F49 to page F54
Pathway Thermal Pathway Through Wall Weighted Area (%)
Lining materials + cavity insulation materials
1 76.40
NOT ALIGNED with stud framing.
Stud framing + aligned materials
2 12.49
but EXCLUDING external framing and cladding.
Battens + aligned materials
3 9.55
but EXCLUDING areas intersecting with stud framing.
Wall materials
4 1.56
SIMULTANEOUSLY ALIGNED with stud framing and external framing.
NOTES:
'Stud framing' includes studs, tracks and noggings.
'External framing' includes battens, Territory clips and horizontal top hats.

F46 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Weatherboards – Direct Fixed – Steel Frame – Thermal Bridged

Cemintel weatherboard cladding. Thermal break, 10mm thick, min. R0.2 if


required, as per system table.
Wall wrap.
Steel studs at 600mm maximum centres.
Lining material as per system
table to external side. Cavity insulation as per system table.

Lining material as per system


table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been
calculated based on the specified wall configuration only,
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-01.03 / CSRRB2-02.04
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 41/32 1.30/1.35
CSR 10211

Break
WIth
(b) 90 Gold Batts R2.5 – – 42/33 1.41/1.45
EXTERNAL WALL SIDE
(c) 75 Gold Batts R2.0 40/31 1.28/1.32 41/32 1.34/1.38
• Nil
Thickness Excluding Cladding mm 90 110
– /– / – INTERNAL WALL SIDE
(d) 90 Gold Batts R2.0 – – 41/32 0.69/0.70
WIthout

• 1 x 10mm Gyprock Plus


Break

Plasterboard. (e) 90 Gold Batts R2.5 – – 42/33 0.71/0.72


(f) 75 Gold Batts R2.0 40/31 0.70/0.71 41/32 0.71/0.72
Thickness Excluding Cladding mm 80 100
(a) 90 Gold Batts R2.0 – – 44/35 1.45/1.51
CSR 10212
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 45/36 1.59/1.63

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 43/34 1.42/1.46 44/35 1.50/1.55
60/60/60
Fyrchek MR Plasterboard Thickness Excluding Cladding mm 106 126
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 44/35 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 45/36 1.02/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 43/34 0.98/0.99 44/35 0.99/1.01
Thickness Excluding Cladding mm 96 116
(a) 90 Gold Batts R2.0 – – 48/40 1.45/1.51
CSR 10213
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 49/41 1.59/1.63
60/60/60 • 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 47/39 1.42/1.46 48/40 1.50/1.55
– /90/90 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 112 132
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 48/40 0.97/0.99
WIthout
Break

FC 12946 • 1 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 49/41 1.02/1.04


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 47/39 0.98/0.99 48/40 0.99/1.01
Thickness Excluding Cladding mm 102 122
(a) 90 Gold Batts R2.0 – – 47/38 1.45/1.51
CSR 10214
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 48/39 1.59/1.63

• 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 46/37 1.42/1.46 47/38 1.50/1.55
90/90/90
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 116 136
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 47/38 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 48/39 1.02/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 46/37 0.98/0.99 47/38 0.99/1.01
Thickness Excluding Cladding mm 106 126
(a) 90 Gold Batts R2.0 – – 51/43 1.62/1.68
CSR 10215
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 52/44 1.77/1.82
90/90/90 • 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 50/42 1.58/1.63 51/43 1.67/1.72
– /120/120 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 132 152
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 51/43 1.20/1.23
WIthout
Break

FC 12946 • 2 x 13mm Gyprock (e) 90 Gold Batts R2.5 – – 52/44 1.27/1.29


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 50/42 1.19/1.22 51/43 1.22/1.25
Thickness Excluding Cladding mm 122 142

GYPROCK® THE RED BOOK™ 1 F47


SYSTEM SPECIFICATIONS Cemintel Sheets – Direct Fixed – Steel Frame – Thermal Bridged

Thermal break 10mm, min. R0.2 if


Cemintel sheet cladding. required, as per system table.

Wall wrap. Steel studs at 600mm maximum centres.

Lining material as per system Cavity insulation as per system table.


table to external side.
Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been calculated
based on the specified wall configuration only, and allow for
the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-01.03 / CSRRB2-02.04
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 41/32 1.30/1.35
CSR 10216

Break
WIth
(b) 90 Gold Batts R2.5 – – 42/33 1.41/1.45
EXTERNAL WALL SIDE
(c) 75 Gold Batts R2.0 41/32 1.28/1.32 41/32 1.34/1.38
• Nil
Thickness Excluding Cladding mm 100 120
– /– / – INTERNAL WALL SIDE
(d) 90 Gold Batts R2.0 – – 41/32 0.69/0.70
WIthout

• 1 x 10mm Gyprock Plus


Break

Plasterboard. (e) 90 Gold Batts R2.5 – – 42/33 0.71/0.72


(f) 75 Gold Batts R2.0 41/32 0.70/0.71 41/32 0.71/0.72
Thickness Excluding Cladding mm 90 110
(a) 90 Gold Batts R2.0 – – 45/36 1.45/1.51
CSR 10217
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 46/37 1.59/1.63

• 1 x 13mm Gyprock (c) 75 Gold Batts R2.0 45/36 1.42/1.46 45/36 1.50/1.55
30/30/30
Fyrchek MR Plasterboard Thickness Excluding Cladding mm 103 123
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 45/36 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 46/37 1.02/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 45/36 0.98/0.99 45/36 0.99/1.01
Thickness Excluding Cladding mm 93 113
(a) 90 Gold Batts R2.0 – – 50/42 1.45/1.51
CSR 10218
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 51/43 1.59/1.63
60/60/60 • 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 50/42 1.42/1.46 50/42 1.50/1.55
– /90/90 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 112 132
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 50/42 0.97/0.99
WIthout
Break

FC 12946 • 1 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 51/43 1.02/1.04


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 50/42 0.98/0.99 50/42 0.99/1.01
Thickness Excluding Cladding mm 102 122
(a) 90 Gold Batts R2.0 – – 49/40 –
CSR 10219
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 50/41 –

• 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 49/40 1.42/1.46 49/40 0.98/0.99
90/90/90
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 116 136
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 49/40 1.45/1.51
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 50/41 1.59/1.63


Plasterboard.
(f) 75 Gold Batts R2.0 49/40 0.98/0.99 49/40 1.50/1.55
Thickness Excluding Cladding mm 106 126
(a) 90 Gold Batts R2.0 – – 53/45 1.62/1.68
CSR 10220
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 54/46 1.77/1.82
90/90/90 • 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 53/45 1.58/1.63 53/45 1.67/1.72
– /120/120 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 132 152
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 53/45 1.20/1.23
WIthout
Break

FC 12946 • 2 x 13mm Gyprock (e) 90 Gold Batts R2.5 – – 54/46 1.27/1.29


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 53/45 1.19/1.22 53/45 1.22/1.25
Thickness Excluding Cladding mm 122 142

F48 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboards – Steel Frame With Cavity – Thermal Bridged

Thermal break, 10mm thick, min. R0.2,


if required, as per system table.
Cemintel sheet or weatherboard
cladding. Steel studs at 600mm maximum centres.

19 to 35mm depth battens. Cavity insulation as per system table.

Wall wrap. Lining material as per system


table to internal side.
Lining material as per system
table to external side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been
calculated based on the specified wall configuration
only, and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-05.03
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 41/30 1.41/1.47
CSR 10221

Break
WIth
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.5 – – 42/31 1.56/1.60

• 1 x 13mm Gyprock (c) 75 Gold Batts R2.0 40/29 1.38/1.43 41/30 1.46/1.51
30/30/30
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 122 142
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 41/30 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 42/31 1.03/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 40/29 0.97/0.99 41/30 0.99/1.01
Thickness Excluding Cladding mm 112 132
(a) 90 Gold Batts R2.0 – – 45/35 1.41/1.47
CSR 10222
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 46/36 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 44/34 1.38/1.43 45/35 1.46/1.51
30/30/30
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 121 141
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 45/35 0.97/0.99
WIthout

FC 12946
Break

• 1 x 6mm CeminSeal (e) 90 Gold Batts R2.5 – – 46/36 1.03/1.04


Wallboard.
(f) 75 Gold Batts R2.0 44/34 0.97/0.99 45/35 0.99/1.01
Thickness Excluding Cladding mm 111 131
(a) 90 Gold Batts R2.0 – – 42/31 1.41/1.47
CSR 10223
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 43/32 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 41/30 1.38/1.43 42/31 1.46/1.51
60/60/60
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 125 145
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 42/31 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 43/32 1.03/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 41/30 0.97/0.99 42/31 0.99/1.01
Thickness Excluding Cladding mm 115 135
(a) 90 Gold Batts R2.0 – – 44/33 1.41/1.47
CSR 10224
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 45/34 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 43/32 1.38/1.43 44/33 1.46/1.51
60/60/60
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 125 145
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 44/33 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock (e) 90 Gold Batts R2.5 – – 45/34 1.03/1.04


Aquachek Plasterboard.
(f) 75 Gold Batts R2.0 43/32 0.97/0.99 44/33 0.99/1.01
Thickness Excluding Cladding mm 115 135
(a) 90 Gold Batts R2.0 – – 45/35 1.41/1.47
CSR 10225
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 46/36 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 44/33 1.38/1.43 45/35 1.46/1.51
60/60/60
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 125 145
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 45/35 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock HD (e) 90 Gold Batts R2.5 – – 46/36 1.03/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 44/33 0.97/0.99 45/35 0.99/1.01
Thickness Excluding Cladding mm 115 135

GYPROCK® THE RED BOOK™ 1 F49


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboards – Steel Frame With Cavity – Thermal Bridged

Thermal break 10mm thick, min. R0.2


if required, as per system table.
Cemintel sheet or weatherboard
cladding. Steel studs at 600mm maximum centres.

19 to 35mm depth battens. Cavity insulation as per system table.

Wall wrap. Lining material as per system


table to internal side.
Lining material as per system
table to external side. NOTE: Acoustic performance valid for studs with 0.75 BMT.
The system thermal R-Values provided have been
calculated based on the specified wall configuration
only and allow for the effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-06.03
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 47/37 1.47/1.53
CSR 10226

Break
WIth
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.5 – – 48/38 1.62/1.66
60/60/60 • 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 46/36 1.43/1.48 46/37 1.51/1.57
– /90/90 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 131 151
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 47/37 1.04/1.07
WIthout
Break

FC 12946 • 1 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 48/38 1.10/1.12


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 46/36 1.03/1.06 46/37 1.06/1.08
Thickness Excluding Cladding mm 121 141
(a) 90 Gold Batts R2.0 – – 45/34 1.47/1.53
CSR 10227
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 46/35 1.62/1.66

• 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 44/33 1.43/1.48 45/34 1.51/1.57
90/90/90
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 135 155
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 45/34 1.04/1.07
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 46/35 1.10/1.12


Plasterboard.
(f) 75 Gold Batts R2.0 44/33 1.03/1.06 45/34 1.06/1.08
Thickness Excluding Cladding mm 125 145
(a) 90 Gold Batts R2.0 – – 46/35 1.47/1.53
CSR 10228
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 47/36 1.62/1.66

• 2 x 16mm Gyprock (c) 75 Gold Batts R2.0 45/34 1.43/1.48 46/35 1.51/1.57
120/120/120
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 141 161
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 46/35 1.04/1.07
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 47/36 1.10/1.12


Plasterboard.
(f) 75 Gold Batts R2.0 45/34 1.03/1.06 46/35 1.06/1.08
Thickness Excluding Cladding mm 131 151
(a) 90 Gold Batts R2.0 – – 50/41 1.47/1.53
CSR 10229
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 51/41 1.62/1.66
90/90/90 • 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 49/40 1.43/1.48 50/41 1.51/1.57
– /120/120 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 151 171
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 50/41 1.04/1.07
WIthout
Break

FC 12946 • 2 x 13mm Gyprock (e) 90 Gold Batts R2.5 – – 51/41 1.10/1.12


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 49/40 1.03/1.06 50/41 1.06/1.08
Thickness Excluding Cladding mm 141 161
(a) 90 Gold Batts R2.0 – – 52/43 1.47/1.53
CSR 10230
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 53/44 1.62/1.66
120/120/120 • 2 x 16mm Gyprock (c) 75 Gold Batts R2.0 51/42 1.43/1.48 52/43 1.51/1.57
– /180/180‡ Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 163 183
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 52/43 1.04/1.07
WIthout
Break

FC 12946 • 2 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 53/44 1.10/1.12


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 51/42 1.03/1.06 52/43 1.06/1.08
Thickness Excluding Cladding mm 153 173

F50 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Territory – Steel Frame With Cavity – Thermal Bridged

Cemintel Territory cladding system Steel studs at 600mm maximum centres.


clip-fixed to studs.
Thermal break 10mm thick, min. R0.2,
Wall wrap. if required, as per system table.

Lining material as per system Cavity insulation as per system table.


table to external side.
Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been
calculated based on the specified wall configuration only
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-08.03 / CSRRB2-09.03
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 46/37 1.30/1.35
CSR 10231

Break
WIth
(b) 90 Gold Batts R2.5 – – 47/38 1.42/1.46
EXTERNAL WALL SIDE
(c) 75 Gold Batts R2.0 44/35 1.27/1.31 46/37 1.34/1.39
• Nil
Wall Thickness mm 121 141
– /– / – INTERNAL WALL SIDE
(d) 90 Gold Batts R2.0 – – 46/37 0.76/0.78
WIthout
• 1 x 10mm Gyprock Plus
Break

Plasterboard. (e) 90 Gold Batts R2.5 – – 47/38 0.80/0.81


(f) 75 Gold Batts R2.0 44/35 0.77/0.79 46/37 0.78/0.79
Wall Thickness mm 111 131
(a) 90 Gold Batts R2.0 – – 46/37 1.30/1.35
CSR 10232
Break
WIth

(b) 90 Gold Batts R2.5 – – 47/38 1.42/1.46


EXTERNAL WALL SIDE
(c) 75 Gold Batts R2.0 47/38 1.27/1.31 48/39 1.34/1.39
• Nil
Wall Thickness mm 124 144
– /– / – INTERNAL WALL SIDE
(d) 90 Gold Batts R2.0 – – 46/37 0.76/0.78
WIthout

• 1 x 13mm Standard
Break

Plasterboard. (e) 90 Gold Batts R2.5 – – 47/38 0.80/0.81


(f) 75 Gold Batts R2.0 47/38 0.77/0.79 48/39 0.78/0.79
Wall Thickness mm 114 134
(a) 90 Gold Batts R2.0 – – 44/33 1.41/1.47
CSR 10233
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 45/34 1.56/1.60

• 1 x 13mm Gyprock (c) 75 Gold Batts R2.0 43/32 1.38/1.43 44/33 1.46/1.51
30/30/30
Fyrchek MR Plasterboard. Wall Thickness mm 134 154
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 44/33 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 45/34 1.03/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 43/32 0.97/0.99 44/33 0.99/1.01
Wall Thickness mm 124 144
(a) 90 Gold Batts R2.0 – – 47/36 1.41/1.47
CSR 10234
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 48/37 1.56/1.60
30/30/30 • 1 x 13mm Gyprock (c) 75 Gold Batts R2.0 46/35 1.38/1.43 47/36 1.46/1.51
– /60/60 Fyrchek MR Plasterboard. Wall Thickness mm 137 157
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 47/36 0.97/0.99
WIthout
Break

FC 12946 • 1 x 13mm Gyprock (e) 90 Gold Batts R2.5 – – 48/37 1.03/1.04


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 46/35 0.97/0.99 47/36 0.99/1.01
Wall Thickness mm 127 147
(a) 90 Gold Batts R2.0 – – 45/34 1.41/1.47
CSR 10235
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 46/35 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 44/33 1.38/1.43 45/34 1.46/1.51
60/60/60
Fyrchek MR Plasterboard. Wall Thickness mm 137 157
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 45/34 0.97/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 46/35 1.03/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 44/33 0.97/0.99 45/34 0.99/1.01
Wall Thickness mm 127 147

GYPROCK® THE RED BOOK™ 1 F51


SYSTEM SPECIFICATIONS Cemintel Territory – Steel Frame With Cavity – Thermal Bridged

Cemintel Territory cladding system Steel studs at 600mm maximum centres.


clip-fixed to studs.
Thermal break 10mm thick, min. R0.2,
Wall wrap. if required, as per system table.

Lining material as per system Cavity insulation as per system table.


table to external side.
Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been
calculated based on the specified wall configuration only
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-10.03 / CSRRB2-11.03
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 48/38 1.42/1.48
CSR 10236

Break
WIth
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.5 – – 49/39 1.57/1.61

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 47/37 1.38/1.43 48/38 1.47/1.52
60/60/60
Fyrchek MR Plasterboard. Wall Thickness mm 137 157
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 48/38 0.99/1.02
WIthout

FC 12946
Break

• 1 x 10mm Gyprock HD (e) 90 Gold Batts R2.5 – – 49/39 1.05/1.07


Plasterboard.
(f) 75 Gold Batts R2.0 47/37 1.19/1.22 48/38 1.01/1.04
Wall Thickness mm 127 147
(a) 90 Gold Batts R2.0 – – 47/36 1.42/1.48
CSR 10237
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 48/37 1.57/1.61

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 46/35 1.38/1.43 47/36 1.47/1.52
60/60/60
Fyrchek MR Plasterboard. Wall Thickness mm 137 157
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 47/36 0.99/1.02
WIthout

FC 12946
Break

• 1 x 10mm Gyprock (e) 90 Gold Batts R2.5 – – 48/37 1.05/1.07


Aquachek Plasterboard.
(f) 75 Gold Batts R2.0 46/35 1.19/1.22 47/36 1.01/1.04
Wall Thickness mm 127 147
CSR 10238 (a) 90 Gold Batts R2.0 – – 50/40 1.47/1.53
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 51/41 1.62/1.66
60/60/60 • 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 49/39 1.43/1.49 50/40 1.52/1.58
– /90/90 Fyrchek MR Plasterboard. Wall Thickness mm 143 163
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 50/40 1.04/1.07
WIthout
Break

FC 12946 • 1 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 51/41 1.10/1.12


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 49/39 1.03/1.06 50/40 1.06/1.09
Wall Thickness mm 133 153
(a) 90 Gold Batts R2.0 – – 47/37 1.47/1.53
CSR 10239
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 48/38 1.62/1.66

• 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 46/36 1.43/1.49 47/37 1.52/1.58
90/90/90
Fyrchek MR Plasterboard. Wall Thickness mm 147 167
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 47/37 1.04/1.07
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 48/38 1.10/1.12


Plasterboard.
(f) 75 Gold Batts R2.0 46/36 1.03/1.06 47/37 1.06/1.09
Wall Thickness mm 137 157

F52 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel ExpressWall – Steel Frame With Cavity – Thermal Bridged

Thermal break 10mm thick, min. R0.2,


Cemintel ExpressPanel, Barestone or if required, as per system table.
Surround panel on ventilated cavity
cladding support system. Steel studs at 600mm maximum centres.

Wall wrap. Cavity insulation as per system table.

15mm top hat. Lining material as per system


table to internal side.
Lining material as per system
table to external side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been
calculated based on the specified wall configuration only
and allow for the effects of thermal bridging.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-12.03 / CSRRB2-13.03
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 49/40 1.30/1.35
CSR 10240

Break
WIth
(b) 90 Gold Batts R2.5 – – 50/41 1.43/1.47
EXTERNAL WALL SIDE
(c) 75 Gold Batts R2.0 48/39 1.27/1.32 49/40 1.34/1.39
• Nil
Thickness Excluding Cladding mm 143 163
– /– / – INTERNAL WALL SIDE
(d) 90 Gold Batts R2.0 – – 49/40 0.76/0.78
WIthout

• 1 x 13mm Gyprock
Break

Standard Plasterboard. (e) 90 Gold Batts R2.5 – – 50/41 0.80/0.81


(f) 75 Gold Batts R2.0 48/39 0.77/0.79 49/40 0.77/0.79
Thickness Excluding Cladding mm 133 153
(a) 90 Gold Batts R2.0 – – 43/32 1.41/1.47
CSR 10241
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 44/33 1.56/1.60

• 1 x 13mm Gyprock (c) 75 Gold Batts R2.0 42/31 1.37/1.42 43/32 1.46/1.51
30/30/30
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 153 173
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 43/32 0.96/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 44/33 1.02/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 42/31 0.96/0.98 43/32 0.98/1.01
Thickness Excluding Cladding mm 143 163
(a) 90 Gold Batts R2.0 – – 48/38 1.41/1.47
CSR 10242
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 49/39 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 47/37 1.37/1.42 48/38 1.46/1.51
30/30/30
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 152 172
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 48/38 0.96/0.99
WIthout

FC 12946
Break

• 1 x 6mm CeminSeal (e) 90 Gold Batts R2.5 – – 49/39 1.02/1.04


Wallboard.
(f) 75 Gold Batts R2.0 47/37 0.96/0.98 48/38 0.98/1.01
Thickness Excluding Cladding mm 142 162
(a) 90 Gold Batts R2.0 – – 44/33 1.41/1.47
CSR 10243
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 45/34 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 43/32 1.37/1.42 44/33 1.46/1.51
60/60/60
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 156 176
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 44/33 0.96/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 45/34 1.02/1.04


Plasterboard.
(f) 75 Gold Batts R2.0 43/32 0.96/0.98 44/33 0.98/1.01
Thickness Excluding Cladding mm 146 166
(a) 90 Gold Batts R2.0 – – 47/36 1.41/1.47
CSR 10244
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 48/37 1.56/1.60

• 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 46/35 1.37/1.42 47/36 1.46/1.51
60/60/60
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 156 176
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 47/36 0.96/0.99
WIthout

FC 12946
Break

• 1 x 10mm Gyprock (e) 90 Gold Batts R2.5 – – 48/37 1.02/1.04


Aquachek Plasterboard.
(f) 75 Gold Batts R2.0 46/35 0.96/0.98 47/36 0.98/1.01
Thickness Excluding Cladding mm 146 166

GYPROCK® THE RED BOOK™ 1 F53


SYSTEM SPECIFICATIONS Cemintel ExpressWall – Steel Frame With Cavity – Thermal Bridged

Cemintel ExpressPanel, Barestone or Thermal break 10mm thick, min. R0.2,


Surround panel on ventilated cavity if required, as per system table.
cladding support system.
Steel studs at 600mm maximum centres.
Wall wrap.
Cavity insulation as per system table.
15mm top hat.
Lining material as per system
Lining material as per system table to internal side.
table to external side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-Values provided have been
calculated based on the specified wall configuration only
and allow for the effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red Book 3,
height selection tables.

ACOUSTIC REPORT: PKA-A119

Thermal Break
SYSTEM SPECIFICATION
THERMAL REPORT: CSRRB2-14.03
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum)/ Rw/ Rt(sum)/
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)
(a) 90 Gold Batts R2.0 – – 50/40 1.47/1.53
CSR 10245

Break
WIth
EXTERNAL WALL SIDE
(b) 90 Gold Batts R2.5 – – 51/41 1.62/1.66
60/60/60 • 1 x 16mm Gyprock (c) 75 Gold Batts R2.0 49/39 1.43/1.49 50/40 1.52/1.58
– /90/90 Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 162 182
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 50/40 1.04/1.07
WIthout
Break

FC 12946 • 1 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 51/41 1.10/1.12


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 49/39 1.03/1.06 50/40 1.06/1.09
Thickness Excluding Cladding mm 152 172
(a) 90 Gold Batts R2.0 – – 48/37 1.47/1.53
CSR 10246
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 49/38 1.62/1.66

• 2 x 13mm Gyprock (c) 75 Gold Batts R2.0 47/36 1.43/1.49 48/37 1.52/1.58
90/90/90
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 166 186
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 48/37 1.04/1.07
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 49/38 1.10/1.12


Plasterboard.
(f) 75 Gold Batts R2.0 47/36 1.03/1.06 48/37 1.06/1.09
Thickness Excluding Cladding mm 156 176
(a) 90 Gold Batts R2.0 – – 49/38 1.47/1.53
CSR 10247
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 50/39 1.62/1.66

• 2 x 16mm Gyprock (c) 75 Gold Batts R2.0 48/37 1.43/1.49 49/38 1.52/1.58
120/120/120
Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 172 192
(from outside only)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 49/38 1.04/1.07
WIthout

FC 12946
Break

• 1 x 10mm Gyprock Plus (e) 90 Gold Batts R2.5 – – 50/39 1.10/1.12


Plasterboard.
(f) 75 Gold Batts R2.0 48/37 1.03/1.06 49/38 1.06/1.09
Thickness Excluding Cladding mm 162 182
(a) 90 Gold Batts R2.0 – – 55/46 1.47/1.53
CSR 10248
Break
WIth

EXTERNAL WALL SIDE


(b) 90 Gold Batts R2.5 – – 56/47 1.62/1.66
120/120/120 • 2 x 16mm Gyprock (c) 75 Gold Batts R2.0 54/45 1.43/1.49 55/46 1.52/1.58
– /180/180‡ Fyrchek MR Plasterboard. Thickness Excluding Cladding mm 194 214
(from both sides)
INTERNAL WALL SIDE (d) 90 Gold Batts R2.0 – – 55/46 1.04/1.07
WIthout
Break

FC 12946 • 2 x 16mm Gyprock (e) 90 Gold Batts R2.5 – – 56/47 1.10/1.12


Fyrchek Plasterboard.
(f) 75 Gold Batts R2.0 54/45 1.03/1.06 55/46 1.06/1.09
Thickness Excluding Cladding mm 184 204

F54 GYPROCK® THE RED BOOK™ 1


GLASROC X SYSTEMS
INTRODUCTION Glasroc X can be used as part of a fire-rated wall system,
achieving an FRL of up to 60/60/60 on timber and steel
Glasroc ® X Sheathing Board (Glasroc ® X) is a high frames and an FRL of up to -90/90 on steel framing.
performance, Class 4 vapour-permeable rigid air barrier, Glasroc X is also suitable for use in bushfire zone BAL-FZ.
designed for use behind façade cladding systems, to
provide up to 6 months weather protection of the building Engineered for high-wind environments, Glasroc X can
interior prior to cladding. withstand wind pressures up to ±6kPa (ULS).

The 12.5mm thick board, reinforced with glass mat and Glasroc X is recommended for use in climate zones 2-8.
UV resistant coating delivers strength, durability and It’s class 4 vapour permeability allows moisture to easily
weather resistance. escape from the building structure, providing outstanding
performance in cold environments (climate zones 6, 7 &
8) where the condensation risk is increased.
FIG F6: CLIMATE ZONES
110° 115° 120° 125° 130° 135° 140° 145° 150° 155° 160°

Darwin Oenpelli Nhulunbuy


10°
Weipa 10°

Katherine

Wyndham
Timber Creek
Cooktown
Borroloola

Cairns
15° Elliot
Derby
15°
Burketown
Broome Halls Creek

Tennant Creek Townsville

Mount Isa

Port Hedland
Dampier
Mackay
Telfer
20°
20°
Exmouth
Alice Springs
Newman Longreach
Rockhampton

Yulara
Kulgera
Birdsville
Gascoyne
Carnarvon Junction Warburton Amata
Taroom
Maryborough
Charleville
Wiluna
Oodnadatta
25° Innamincka
Thargomindah 25°
Brisbane
Coober Pedy Goondiwindi
Yalgoo
Tibooburra
Geraldton
Leigh Creek Bourke

Kalgoorlie–Boulder Nullarbor
Coffs Harbour
Broken Hill
Eucla Tamworth
Merredin Ceduna
Norseman Whyalla Port Macquarie
Perth Ivanhoe Dubbo
30°
30°
Lord Howe Island
Newdegate Burra
Esperance Mildura Bathurst Newcastle
Bunbury
Adelaide
Renmark
Griffith Sydney
Margaret River Port Lincoln Wollongong
Albany Kingscote

Climate Zones Canberra


Albury–Wodonga
Horsham
Kingston SE
Zone 1 Zone 5 Shepparton

Mount Gambier Ballarat Melbourne


35° Zone 2 Zone 6
35°
Lakes Entrance
Zone 3 Zone 7

Zone 4 Zone 8

Devonport
Launceston
Local Government Area boundary Strahan www.abcb.gov.au
Swansea

Hobart Last amended: August 2015

40° Developed from a map produced


Southport 40°
VC00031.3
by the Bureau of Meteorology

105° 110° 115° 120° 125° 130° 135° 140° 145° 150° 155° 160° 165°

FIG F7: TYPICAL GLASROC X SYSTEM ARRANGEMENT

Steel studs
GlasrocX barrier

Cavity insulation as
per system table

Lining material as per


system table to internal
side of stud framing

All sheet joints sealed as


External Cladding as
per system specification
per system specification

GYPROCK® THE RED BOOK™ 1 F55


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboards – With Cavity – Steel Frame

Cemintel sheet or weatherboard Steel studs at 600mm maximum centres.


cladding.
Cavity insulation as per system table.
19 to 35mm depth battens.
Lining material as per system
12.5mm Gyprock Glasroc X. table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.
‡ Unique height restrictions apply. Refer to The Red
Book 3, height selection tables.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10290
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 44/34 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 45/35 2.6/2.9
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 43/33 2.1/2.2 44/34 2.3/2.5
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness 107.5 127.5
Excluding Cladding mm
CSR 10291
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 43/33 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 44/34 2.6/2.9
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 42/31 2.1/2.3 43/33 2.3/2.5
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 111.5 131.5
Excluding Cladding mm
CSR 10292
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 42/31 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 43/32 2.6/2.9
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 41/30 2.1/2.3 42/31 2.3/2.5
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 111.5 131.5
Excluding Cladding mm
CSR 10293
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 43/33 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 44/34 2.6/2.9
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 42/31 2.1/2.3 43/33 2.3/2.5
• 1 x 13mm Gyprock
Standard Plasterboard. Wall Thickness 114.5 134.5
Excluding Cladding mm
CSR 10294
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/35 2.2/2.4
– /60/60 • 1 x 12.5mm Gyprock
30/30/30 Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/36 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/34 2.1/2.3 45/35 2.3/2.5
FC 12946 • 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 114.5 134.5
Excluding Cladding mm
CSR 10295
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.2/2.4
– /90/90 • 1 x 12.5mm Gyprock
60/60/60 Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.9
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.1/2.3 46/36 2.3/2.5
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 117.5 137.5
Excluding Cladding mm

F56 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Territory – With Cavity – Steel Frame

Cemintel Territory cladding system Steel studs at 600mm maximum centres.


clip-fixed to studs.
Cavity insulation as per system table.
12.5mm Gyprock Glassroc X.
Lining material as per system
table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10300
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 47/37 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 48/38 2.8/2.8
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 46/36 2.1/2.2 47/37 2.3/2.4
• 1 x 6mm CeminSeal
Wallboard.
Wall Thickness mm 119.5 139.5

CSR 10301
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.8
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.1/2.3 46/36 2.3/2.5
• 1 x 10mm Gyprock HD
Plasterboard.
Wall Thickness mm 123.5 143.5

CSR 10302
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/34 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/35 2.6/2.8
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/33 2.1/2.3 45/34 2.3/2.5
• 1 x 10mm Gyprock
Aquachek Plasterboard.
Wall Thickness mm 123.5 143.5

CSR 10303
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.8
–/–/–
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.1/2.3 46/36 2.3/2.5
• 1 x 13mm Gyprock
Standard Plasterboard.
Wall Thickness mm 126.5 146.5

CSR 10304
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 48/38 2.1/2.3
– /60/60 • 1 x 12.5mm Gyprock
30/30/30 Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 49/39 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 47/37 2.1/2.3 48/38 2.3/2.5
FC 12946 • 1 x 13mm Gyprock
Frychek Plasterboard.
Wall Thickness mm 126.5 146.5

CSR 10305
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 49/39 2.1/2.3
– /90/90 • 1 x 12.5mm Gyprock
60/60/60 Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 50/40 2.6/2.8
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 48/38 2.1/2.3 49/39 2.3/2.5
FC 12946 • 1 x 16mm Gyprock
Frychek Plasterboard.
Wall Thickness mm 129.5 149.5

GYPROCK® THE RED BOOK™ 1 F57


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Steel Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Steel studs at 600mm maximum centres.
cladding support system.
Cavity insulation as per system table.
12.5 Gyprock Glassroc X.
Lining material as per system
15mm top hat. table to internal side.

NOTE: Acoustic performance valid for studs with 0.75 BMT.


The system thermal R-values provided have been
calculated based on a thermal transmission path
through the wall cavity and does not allow for the
effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10310
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 47/37 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 48/38 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 46/36 2.1/2.2 47/37 2.3/2.5
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness 138.5 158.5
Excluding Cladding mm
CSR 10311
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/35 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 47/36 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/34 2.1/2.2 46/35 2.3/2.5
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 142.5 162.5
Excluding Cladding mm
CSR 10312
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 44/33 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 45/34 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 43/32 2.1/2.2 44/33 2.3/2.5
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 142.5 162.5
Excluding Cladding mm
CSR 10313
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/35 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 47/36 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/34 2.1/2.2 46/35 2.3/2.5
• 1 x 13mm Gyprock
Standard Plasterboard. Wall Thickness 145.5 165.5
Excluding Cladding mm
CSR 10314
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 48/38 2.2/2.4
– /60/60 • 1 x 12.5mm Gyprock
30/30/30 Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 49/39 2.8/2.9
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 47/37 2.1/2.2 48/38 2.3/2.5
FC 12946 • 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 145.5 165.5
Excluding Cladding mm
CSR 10315
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 49/39 2.2/2.4
– /90/90 • 1 x 12.5mm Gyprock
60/60/60 Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 50/40 2.8/2.9
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 48/38 2.1/2.2 49/39 2.3/2.5
FC 12946 • 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 148.5 168.5
Excluding Cladding mm

F58 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel Sheet or Weatherboard – With Cavity – Timber Frame

Cemintel weatherboard or Timber studs at 600mm maximum centres.


sheet cladding.
Cavity insulation as per system table.
19 to 35mm depth timber battens.
Lining material as per system
12.5mm Gyprock Glassroc X. table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10320
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 42/32 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 43/33 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 41/31 2.1/2.3 42/32 2.3/2.5
• 1 x 6mm CeminSeal
Wallboard. Min. Wall Thickness 107.5 127.5
Excluding Cladding mm
CSR 10321
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 41/31 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 42./32 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 40/30 2.1/2.3 41/31 2.3/2.5
• 1 x 10mm Gyprock HD
Plasterboard. Min. Wall Thickness 111.5 131.5
Excluding Cladding mm
CSR 10322
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 40/29 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 41/30 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 39/28 2.1/2.3 40/29 2.3/2.5
• 1 x 10mm Gyprock
Aquachek Plasterboard. Min. Wall Thickness 111.5 131.5
Excluding Cladding mm
CSR 10323
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 41/31 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 42/32 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 40/30 2.1/2.3 41/31 2.3/2.5
• 1 x 13mm Gyprock
Standard Plasterboard. Min. Wall Thickness 114.5 134.5
Excluding Cladding mm
CSR 10324
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 42/32 2.2/2.4
• 1 x 12.5mm Gyprock
30/30/30 (b) 90 Gold Batts R2.5 – – 43/33 2.6/2.9
Glasroc X Plasterboard.
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 41/31 2.1/2.3 42/32 2.3/2.5
FC 12969
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Min. Wall Thickness 114.5 134.5
Excluding Cladding mm
CSR 10325
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 42/32 2.2/2.4
• 1 x 12.5mm Gyprock
60/60/60 (b) 90 Gold Batts R2.5 – – 43/33 2.6/2.9
Glasroc X Plasterboard.
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 41/31 2.1/2.3 42/32 2.3/2.5
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard. Min. Wall Thickness 117.5 137.5
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F59


SYSTEM SPECIFICATIONS Cemintel Territory – With Cavity – Timber Frame

Cemintel Territory cladding system Timber studs at 600mm maximum


clip-fixed to studs. centres.

12.5mm Gyprock Glasroc X Cavity insulation as per system table.

Lining material as per system


table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119

STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10330
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/35 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 47/36 2.6/2.8
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/34 2.0/2.2 46/35 2.2/2.4
• 1 x 6mm CeminSeal
Wallboard.
Wall Thickness mm 119.5 139.5

CSR 10331
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/35 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/36 2.6/2.8
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/34 2.0/2.2 45/35 2.2/2.4
• 1 x 10mm Gyprock HD
Plasterboard.
Wall Thickness mm 123.5 143.5

CSR 10332
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 44/33 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/36 2.6/2.8
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 43/32 2.0/2.2 45/35 2.2/2.4
• 1 x 10mm Gyprock
Aquachek Plasterboard.
Wall Thickness mm 123.5 143.5

CSR 10333
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/35 2.1/2.3
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/36 2.6/2.8
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/34 2.0/2.2 45/35 2.2/2.4
• 1 x 13mm Gyprock
Standard Plasterboard.
Wall Thickness mm 126.5 146.5

CSR 10334
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.1/2.3
• 1 x 12.5mm Gyprock
30/30/30 (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.8
Glasroc X Plasterboard.
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.0/2.2 46/36 2.2/2.4
FC 12969
• 1 x 13mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 126.5 146.5

CSR 10335
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.1/2.3
• 1 x 12.5mm Gyprock
60/60/60 (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.8
Glasroc X Plasterboard.
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.0/2.2 46/36 2.2/2.4
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 129.5 146.5

F60 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Cemintel ExpressWall – With Cavity – Timber Frame

Cemintel ExpressPanel, Barestone or


Surround panel on ventilated cavity Timber studs at 600mm maximum
cladding support system. centres.

12.5mm Gyprock Glasroc X Cavity insulation as per system table.

Lining material as per system


table to internal side.

NOTE: Acoustic performance valid for 35mm wide


studs at 600mm centres.
The system thermal R-values provided have been
calculated based on a thermal transmission path through
the wall cavity and does not allow for the effects of
thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A119


STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Rw / Rt(sum) / Rw / Rt(sum) /
Report Nº
(Refer to TABLE B6) Rw+Ctr Rt(win) Rw+Ctr Rt(win)

CSR 10340
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/35 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/36 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/34 2.1/2.2 45/35 2.3/2.5
• 1 x 6mm CeminSeal
Wallboard. Wall Thickness 123.5 143.5
Excluding Cladding mm
CSR 10341
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 42/31 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 43/32 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 41/30 2.1/2.2 42/31 2.3/2.5
• 1 x 10mm Gyprock HD
Plasterboard. Wall Thickness 127.5 147.5
Excluding Cladding mm
CSR 10342
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 44/33 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 45/34 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 43/32 2.1/2.2 44/33 2.3/2.5
• 1 x 10mm Gyprock
Aquachek Plasterboard. Wall Thickness 127.5 147.5
Excluding Cladding mm
CSR 10343
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 45/34 2.2/2.4
• 1 x 12.5mm Gyprock
Glasroc X Plasterboard. (b) 90 Gold Batts R2.5 – – 46/35 2.6/2.9
– /– / –
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 44/33 2.1/2.2 45/34 2.3/2.5
• 1 x 13mm Gyprock
Standard Plasterboard. Wall Thickness 130.5 150.5
Excluding Cladding mm
CSR 10344
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.2/2.4
• 1 x 12.5mm Gyprock
30/30/30 (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.9
Glasroc X Plasterboard.
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.1/2.2 46/36 2.3/2.5
FC 12969
• 1 x 13mm Gyprock
Fyrchek Plasterboard. Wall Thickness 130.5 150.5
Excluding Cladding mm
CSR 10345
EXTERNAL WALL SIDE
(a) 90 Gold Batts R2.0 – – 46/36 2.2/2.4
• 1 x 12.5mm Gyprock
60/60/60 (b) 90 Gold Batts R2.5 – – 47/37 2.6/2.9
Glasroc X Plasterboard.
(from both sides)
INTERNAL WALL SIDE (c) 75 Gold Batts R2.0 45/35 2.1/2.2 46/36 2.3/2.5
FC 12969
• 1 x 16mm Gyprock
Fyrchek Plasterboard. Wall Thickness 133.5 153.5
Excluding Cladding mm

GYPROCK® THE RED BOOK™ 1 F61


NOTES:

F62 GYPROCK® THE RED BOOK™ 1


CEILING SYSTEMS

G
SECTION CONTENTS
Introduction G2
Design Considerations G2
Installation G5
System Selection Tables

Floor/Ceiling
G6
Under Joists

Floor/Ceiling Under
G15
Concrete Structure

Ceilings Under Pitched


G29
Metal/Tiled Roofs

Ceilings Fire Rated


G48
from Above &/or Below

Hebel PowerFloor G51

Decorative and Sound


G52
Absorptive Ceilings

GYPROCK® THE RED BOOK™ 1 G1


INTRODUCTION resistance/combustibility, thermal, condensation and
weatherproofing requirements.

CSR Gyprock has developed an extensive CSR offers online digital tools for the most updated
range of flush jointed roof/ceiling and floor/ information, including but not limited to update of
ceiling systems to meet specific fire and products/components, inclusion of new and modified
acoustic requirements. CSR also offers a systems, to meet the requirements of the National
large selection of lay-in tile ceiling systems Construction Code of Australia (NCC) and any relevant
for non-fire rated decorative and acoustic Australian Standards.
applications. For the most up-to-date product & system performance
information, visit:
Systems in this section include ratings for
CSR System Selector: https://apps.csr.com.au/
sound transmission, sound impact and
systemselector/search-option
sound absorption, thermal resistance, fire
resistance up to FRL 120/120/120, and for up CSR Thermal Calculator: https://apps.csr.com.au/
to 60 minutes Resistance to Incipient Spread thermalcalculator
of Fire (RISF).
STRUCTURAL DESIGN
Gyprock flush jointed ceiling systems utilise Gyprock All floor, roof and ceiling framing must be designed for
plasterboard sheet which is fixed to appropriately the applied loads. It is recommended that the supporting
prepared framing. Plasterboard joints are taped and set structure be designed for maximum deflection of
to form a smooth flush jointed continuous ceiling suitable SPAN/240 under serviceability criteria.
for painting.
Gyprock tile ceiling systems offer lightweight, decorative Seismic Loads
and/or acoustic solutions for commercial applications.
The precoated face of the supporting grid or edge profile Seismic actions must be considered for building elements
of the tiles combine with various surface textures or in accordance with the NCC. The loads and effects of
perforations to form a decorative and functional ceiling. earthquakes may be determined in accordance with AS
Room-to-room acoustic performance details for tile 1170.4 ‘Earthquake Actions in Australia’. The Standard
ceilings are given in Section J in this guide. has design procedures for houses (Class 1), and to
buildings (Classes 2 to 9) with importance levels 2, 3 or 4
as defined in the NCC.
DESIGN
Wind Loads
CONSIDERATIONS All linings and framing are to be designed for the
Framing requirements detailed in this guide apply to both appropriate wind loads. CSR Gyprock recommends a
non-fire rated and fire rated installations, and for interior minimum design pressure of 0.25kPa (downward) for the
applications only. ceiling framing.

Information and guidance for the selection of Rondo Tall residential buildings often have exterior operable doors
suspension and grid components is given in Book and windows, resulting in internal areas being subject to
3 Commercial & Multi-Residential Installation Guide – wind pressure. In these cases, ceilings must be designed
Buildings Class 2 to 9. For other elements and additional for the appropriate loads.
information, refer to the appropriate design standards
or handbooks, or contact the manufacturer for design FRAMING
information. Steel framing for direct fixing of linings shall have a
maximum base metal thickness (BMT) 1.6mm and a
DESIGNER RESPONSIBILITY minimum face fixing width of 32mm. Framing may be
It remains the responsibility of the customer (in conjunction trusses, top hats, C sections, furring channels, or similar
with their designer or engineer, when applicable) to ensure members. In all cases they should be designed in
that CSR’s products/systems are suitable for their chosen accordance with AS/NZS 4600.
application for any given project. CSR recommends For steel components in corrosive environments,
that a comprehensive assessment of the performance additional coatings may be required. Refer to
requirements be undertaken prior to selection, including AS/NZS 2785 for guidance.
in respect of project-specific matters such as, but
Timber framing shall be solid timber or engineered floor
not limited structural adequacy, seismic, acoustic, fire
joist such as LVL Glulam, ply web joists, or trusses made

G2 GYPROCK® THE RED BOOK™ 1


from solid timber framing, and must be designed in Ceilings lined with CeminSeal Wallboard should have
accordance with AS 1720.1, or AS 1684 series. joints at 3.6m in most cases. For additional information,
refer to Cemintel Ceiling Systems.
Direct-Fix Framing Systems
Ceiling linings may be fixed directly to primary timber or FIRE RATED SYSTEMS
steel framing, or to secondary steel framing members Generally, the fire resistance of floor/ceiling and roof/
such as furring channels and battens. ceiling systems is assessed from below, in accordance
Timber members to which plasterboard will be fixed with the standard fire test of AS 1530.4:2014. This is a
must comply with AS 1684 series, Residential Timber – requirements of the NCC where lightweight construction
Framed Construction, or be designed in accordance with is used for compartmentation and separation.
AS 1720.1 Timber Structures – Design Methods. Gyprock fire rated floor/ceiling and roof/ceiling systems in
Steel framing to which plasterboard will be fixed must this guide have been designed with fire performance that
comply with AS/NZS 4600 Cold Formed Steel Structures. protects framing and provides an FRL rated performance.
The framed system must be designed by a professional
Suspended Ceiling Systems structural engineer and consider the impact of the exposed
heat of the fire. For systems exposed to fire from below,
Ceiling suspension systems must be designed to
where the horizontal elements are exposed to heat from
AS/NZS 2785 Suspended Ceilings – Design and
the underside only, to satisfy the following requirements:
Installation. Ceilings in this manual are non-trafficable.
• For steel framed floor/ceiling and roof/ceiling systems,
Strengthen suspension systems to support light fittings
the timber elements (joists, purlins, beams) must
and access panels as detailed in the appropriate
be designed to ensure that the maximum imposed
illustrations in this guide and/or other relevant Gyprock
flexural strength demand at the fire limit state does not
or Rondo technical literature.
exceed 25% of the design ultimate limit state strength
Any additional loads are not to be placed upon, or carried at ambient temperature.
by the suspension system.
• For timber framed floor/ceiling and roof/ceiling systems,
the timber elements (joists, purlins, beams) must
Ceilings Rated from Above
be designed to ensure that the maximum imposed
Ceiling systems with plasterboard linings on top of joists flexural strength demand at the fire limit state does not
are non-trafficable and should not be used for storage. exceed 50% of the design ultimate limit state strength
The joists should be designed for all imposed loads at ambient temperature.
including construction loads where fixing of sheets is
• In all cases, the suspension systems must be designed
required from above. Appropriate barriers and signage
by a professional structural engineer to support the
should be installed to prevent access.
imposed dead and live loads.
CONTROL JOINTS Some systems, such as fire-isolated passageways, have
horizontal elements exposed to heat from outside and are
Control joints are used to reduce the possibility of cracks
required to have a FRL rating when tested from outside.
forming from structural movement, thermal and moisture
movement and the like. Locations for joints should be
chosen by the designer with regard to building shape,
structural breaks, changes of substrate, and joint
appearance.
The continuity of lining sheets and support framework
should be broken at control joints.
Control joints may be positioned to intersect light fixtures,
heating vents and air diffusers.
Control joints are to be installed in both fire rated and
non-fire rated ceilings:
• To coincide with control joints in the supporting frame.
• At changes of framing type or framing direction.
• In continuous interior ceiling areas lined with
plasterboard, spaced at no more than 12m centres in
both directions.
• For external ceilings, at 6m maximum centres.

GYPROCK® THE RED BOOK™ 1 G3


ACCEPTABLE VARIATIONS TO that have:

FIRE SYSTEMS • No finish, or


• Are lined with tiles, timber, vinyl, or similar, without an
The Fire Resistance Level (FRL) of the systems detailed in acoustic underlay, or
this section will not be detrimentally affected by:
• Carpet without an underlay.
• The use of Fyrchek MR, Impactchek or EC08 Range
Timber/Tile + AQ (acoustic quality) Underlay values are
plasterboard in lieu of Fyrchek plasterboard of the
for slabs with:
same thickness.
• Additional layers of plasterboard or Cemintel fibre • Tiles, timber, engineered timber or laminate timber,
cement. or similar hard finishes, with an acoustic underlay of
at least 4.5mm thickness. Suitable products include
• Decreasing the framing spacings.
4.5mm Regupol 4515, 5mm Embleton Impactamat or
• Decreasing the fixing centers of ceiling sheet materials. composite products such as Acoustica AngelStep.
• Additional of M10 steel rods or 14g screws penetrating
Carpet + Underlay values are for concrete slabs or sheet
the exposed side plasterboard layers and into the
flooring that have:
ceiling cavity to facilitate the attachment of light weight
fixtures through to the main structural framing. • Carpet installed over standard chipfoam underlay
material.
Perimeters & Penetrations Systems acoustic performance are not affected by:
All perimeters, control joints and penetrations must be • The use of 13mm Aquachek in lieu of 13mm Gyprock
treated appropriately to maintain the fire rating. Treatment Standard
may include caulking with mastic sealants, or by the use
of fire collars, dampers, etc, to an approved detail. • The use of 10mm Aquachek in lieu of 10mm Gyprock
Plus

COMBUSTIBILITY
Perimeters & Penetrations
Non-combustible materials is determined by AS1530.1
- combustibility tests for materials, and in accordance In non-fire rated systems, to attain the stated sound
NCC2022 Clause C2D10 [NCC2019: C1.9]. NCC has transmission performance, use Gyprock Wet Area Acrylic
defined the construction requirement and restrictions of Sealant or other tested acoustic sealant. All penetrations
the application of combustible materials. should be treated to maintain the acoustic integrity of the
system.
Please note that polyester insulation may NOT be selected
where the system has non-combustible construction
requirements. THERMAL PERFORMANCE
Energy efficiency requirements for the building envelope
ACOUSTIC PERFORMANCE are set out in the NCC as performance requirements and
acceptable construction practices, and are dependent on
Sound Transmission geographical climate zones. To meet the requirements,
it is recommended that CSR Bradford insulation be
Sound flanking, the effectiveness of workmanship and
installed. Check with local building authorities for minimum
caulking, the presence and treatment of penetrations, and
insulation requirements.
the inclusion of structural elements and bridging items
may affect the acoustic performance of ceiling systems. The level of insulation provided in a wall is described by its
Refer to appropriate information on addressing these R-Value, the higher the R-Value the greater the insulation
issues detailed in Section B and Section J in this guide. provided.

Sound Impact The system values provided have been calculated based
on a thermal transmission path through the roof cavity
Sound impact ratings are given as L n,w for various and does not allow for any thermal bridging. This method
floor finishes. The ratings are given as a range due to is in accordance with the requirements of NCC Volume 2,
the effects of differing substrate stiffnesses and floor Class 1 and 10 buildings and may not be applicable for
types. It is recommended that to comply with the NCC other building classes. R(SUM) and R(WIN) represent the
maximum of Ln,w 62 (Class 2 or 3 buildings), systems be system total R-Value calculated for heat flow inwards and
chosen that have the entire range at Ln,w 62 or less. For heat flow outwards respectively.
systems that achieve Ln,w 60 – 65 it is recommended
that the proposed floor/ceiling be checked by an acoustic
consultant.
Bare Floor values are for concrete slabs or sheet flooring

G4 GYPROCK® THE RED BOOK™ 1


INSTALLATION
STEEL FRAMING & SUSPENSION
COMPONENTS
CSR Gyprock recommends components manufactured
by Rondo Building Services Pty Ltd. For detailed
information on installation and maintenance of
suspension systems, Refer to Book 3, Commercial
& Multi-Residential Installation Guide for further
information, or contact CSR Himmel on 1300 374 253 or
www.himmel.com.au.

PLASTERBOARD & FIBRE


CEMENT FIXING
Ceilings may be designed to achieve a particular ‘Level of
Finish’ as defined in AS/NZS 2589.1. The Level of Finish
specified can have requirements for frame alignment,
jointing and back blocking methods.
Lining sheets must be installed with the long edge at
right angles to the direction of the framing to which
they are fixed. Fixing information is provided in Book
2 Residential Installation Guide, Book 3 Commercial &
Multi-Residential Installation Guide, and Cemintel Ceiling
Systems - Soffitline & Ceminseal Wallboard, External &
Internal Ceiling Systems Design and Installation Guide.

INSULATION & SARKING


A range of insulation and sarking products have been
specified in some roof/ceiling systems to achieve the
acoustic and thermal values, refer to the Components &
Accessories in section B for further information.

JOINTING
Detailed plasterboard jointing and finishing information is
provided in relevant Gyprock installation guides. In multi-
layer systems, jointing and finishing is required on the
visible outer layer only.
For information on Cemintel fibre cement jointing, refer to
Cemintel Ceiling Systems.

GYPROCK® THE RED BOOK™ 1 G5


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Direct Fixed Plasterboard

Floor finished bare or with carpet and


underlay as per system table. Minimum 190mm cavity depth.

1 x 19mm or 22mm particleboard or Cavity infill as per system table.


timber flooring or fibre cement sheet
of at least 15kg/m2. Ceiling lining as per system table,
direct fixed to framing.
Timber or steel joists at 600mm
maximum centres.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw / Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6001
(a) Nil 37/30 80 – 85 65 – 70

• 1 x 10mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 40/32 75 – 80 60 – 65
Supaceil Plasterboard.

(c) 70 Soundscreen 2.0 40/32 75 – 80 60 – 65

CSR 10166
(a) Nil 38/32 80 – 85 65 – 70

• 1 x 10mm Gyprock HD
–/–/– (b) 90 Gold Batts 2.0 41/34 75 – 80 60 – 65
Plasterboard.

(c) 70 Soundscreen 2.0 41/34 75 – 80 60 – 65

CSR 10167
(a) Nil 41/35 80 – 85 60 – 65

• 2 x 10mm Gyprock HD
–/–/– (b) 90 Gold Batts 2.0 44/37 75 – 80 58 – 62
Plasterboard.

(c) 70 Soundscreen 2.0 44/37 75 – 80 58 – 62

CSR 6015
(a) Nil 39/32 80 – 85 65 – 70

• 1 x 13mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 42/34 75 – 80 60 – 65
Standard Plasterboard.

(c) 70 Soundscreen 2.0 42/34 75 – 80 60 – 65

CSR 6018
(a) Nil 40/34 80 – 85 65 – 70

• 1 x 13mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 43/36 75 – 80 60 – 65
Soundchek Plasterboard.

(c) 70 Soundscreen 2.0 43/36 75 – 80 60 – 65

G6 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Direct Fixed Plasterboard

Floor finished bare or with carpet and


underlay as per system table. Minimum 190mm cavity depth.

1 x 19mm or 22mm particleboard or Cavity infill as per system table.


timber flooring or fibre cement sheet
of at least 15kg/m2. Ceiling lining as per system table,
direct fixed to framing.
Timber or steel joists at 600mm
maximum centres.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw / Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6025
(a) Nil 38/32 80 – 85 65 – 70
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 90 Gold Batts 2.0 41/34 75 – 80 60 – 65
• Framing at 450mm
EWFA 26162
maximum centres.
(c) 70 Soundscreen 2.0 41/34 75 – 80 60 – 65

CSR 6026
60/60/60 (a) Nil 43/37 80 – 85 60 – 65
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 90 Gold Batts 2.0 46/39 75 – 80 58 – 62
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 46/39 75 – 80 58 – 62

CSR 6031
(a) Nil 38/32 80 – 85 65 – 70
30/30/30 • 1 x 16mm Gyprock
from below Fyrchek Plasterboard.
only (b) 90 Gold Batts 2.0 41/34 75 – 80 60 – 65
• Framing at 450mm
maximum centres.
EWFA 26162
(c) 70 Soundscreen 2.0 41/34 75 – 80 60 – 65

CSR 6132
60/60/60 (a) Nil 43/37 80 – 85 60 – 65
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 30 • 1 x 16mm Gyprock (b) 90 Gold Batts 2.0 46/39 75 – 80 58 – 62
minutes Fyrchek Plasterboard (any
order).
EWFA 26162 (c) 70 Soundscreen 2.0 46/39 75 – 80 58 – 62

CSR 6134
90/90/90 (a) Nil 42/36 80 – 85 60 – 65
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 90 Gold Batts 2.0 45/38 75 – 80 58 – 62
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 45/38 75 – 80 58 – 62

CSR 6140
120/120/120 (a) Nil 45/39 80 – 85 60 – 65
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 90 Gold Batts 2.0 48/41 75 – 80 58 – 62
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 48/41 75 – 80 58 – 62

GYPROCK® THE RED BOOK™ 1 G7


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Clip Fixed Furring

Floor finished bare or with carpet and


underlay as per system table. Cavity infill as per system table.

1 x 19mm or 22mm particleboard or Rondo Furring Channels at 600mm max.


timber flooring or fibre cement sheet centres except where noted in system
of at least 15kg/m2. table.

Timber or steel joists at 600mm Ceiling lining as per system table, fixed to
maximum centres. furring channel.

Minimum 205mm cavity depth.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw / Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6150
(a) Nil 41/34 80 – 85 60 – 65

• 1 x 6mm CeminSeal
–/–/– (b) 90 Gold Batts 2.0 46/39 70 – 75 55 – 60
Wallboard.

(c) 70 Soundscreen 2.0 47/40 70 – 75 55 – 60

CSR 6151
(a) Nil 39/32 80 – 85 60 – 65
• 1 x 10mm Gyprock Plus
Plasterboard.
–/–/– (b) 90 Gold Batts 2.0 44/37 70 – 75 55 – 60
• Furring channel at 450mm
maximum centres.
(c) 70 Soundscreen 2.0 45/38 70 – 75 55 – 60

CSR 6153
(a) Nil 39/32 80 – 85 60 – 65

• 1 x 10mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 44/37 70 – 75 55 – 60
Supaceil Plasterboard.

(c) 70 Soundscreen 2.0 45/38 70 – 75 55 – 60

CSR 10168
(a) Nil 40/34 80 – 85 60 – 65

• 1 x 10mm Gyprock HD
–/–/– (b) 90 Gold Batts 2.0 45/39 70 – 75 55 – 60
Plasterboard.

(c) 70 Soundscreen 2.0 46/40 70 – 75 55 – 60

CSR 6170
(a) Nil 40/34 80 – 85 60 – 65

• 1 x 13mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 45/39 70 – 75 55 – 60
Standard Plasterboard.

(c) 70 Soundscreen 2.0 46/40 70 – 75 55 – 60

CSR 6173
(a) Nil 43/37 80 – 85 60 – 65

• 1 x 13mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 48/42 70 – 75 55 – 60
Soundchek Plasterboard.

(c) 70 Soundscreen 2.0 49/43 70 – 75 55 – 60

G8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Clip Fixed Furring

Floor finished bare or with carpet and


underlay as per system table. Cavity infill as per system table.

1 x 19mm or 22mm particleboard or Rondo Furring Channels at 600mm max.


timber flooring or fibre cement sheet centres except where noted in system
of at least 15kg/m2. table.

Timber or steel joists at 600mm Ceiling lining as per system table, fixed to
maximum centres. furring channel.

Minimum 205mm cavity depth.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw / Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6180
(a) Nil 42/36 80 – 85 60 – 65
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 90 Gold Batts 2.0 47/41 70 – 75 55 – 60
• Furring channels at
450mm maximum centres.
EWFA 26162
(c) 70 Soundscreen 2.0 48/42 70 – 75 55 – 60

CSR 6183
60/60/60 (a) Nil 45/39 75 – 80 60 – 62
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 90 Gold Batts 2.0 50/44 65 – 70 50 – 55
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 51/45 65 – 70 50 – 55

CSR 6187
(a) Nil 42/36 80 – 85 60 – 65
30/30/30 • 1 x 16mm Gyprock
from below Fyrchek Plasterboard.
only (b) 90 Gold Batts 2.0 47/41 70 – 75 55 – 60
• Furring channels at
450mm maximum centres.
EWFA 26162
(c) 70 Soundscreen 2.0 48/42 70 – 75 55 – 60

CSR 6190
60/60/60 (a) Nil 45/39 75 – 80 60 – 62
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 60 • 1 x 16mm Gyprock (b) 90 Gold Batts 2.0 50/44 65 – 70 50 – 55
minutes Fyrchek Plasterboard (any
order).
EWFA 26162 (c) 70 Soundscreen 2.0 51/45 65 – 70 50 – 55

CSR 6193
90/90/90 (a) Nil 44/38 75 – 80 60 – 62
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 90 Gold Batts 2.0 49/43 65 – 70 50 – 55
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 50/44 65 – 70 50 – 55

CSR 6196
120/120/120 (a) Nil 47/41 75 – 80 60 – 62
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 90 Gold Batts 2.0 52/46 65 – 70 50 – 55
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 53/47 65 – 70 50 – 55

GYPROCK® THE RED BOOK™ 1 G9


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Resilient Mounted Furring

Floor finished bare or with carpet and


underlay as per system table. Cavity infill as per system table.

1 x 19mm or 22mm particleboard or Rondo Furring Channel clipped to


timber flooring or fibre cement sheet Gyprock Resilient Mounts.
of at least 15kg/m2.
Rondo Furring Channel at 600mm max
Timber or steel joists at 600mm centres except where noted in system
maximum centres. table.

Minimum 205mm cavity depth. Ceiling lining as per system table, fixed to
furring channel.
NOTE: RISF = Resistance to Incipient
Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw/Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 10169
(a) Nil 46/39 75 – 80 55 – 60

• 1 x 10mm Gyprock HD
–/–/– (b) 90 Gold Batts 2.0 55/46 65 – 70 50 – 55
Plasterboard.

(c) 70 Soundscreen 2.0 55/46 65 – 70 50 – 55

CSR 10170
(a) Nil 48/42 70 – 75 55 – 60

• 2 x 10mm Gyprock HD
–/–/– (b) 90 Gold Batts 2.0 57/49 60 – 65 45 – 50
Plasterboard.

(c) 70 Soundscreen 2.0 57/49 60 – 65 45 – 50

CSR 6209
(a) Nil 46/39 75 – 80 55 – 60

• 1 x 13mm Gyprock
–/–/– (b) 90 Gold Batts 2.0 55/46 65 – 70 50 – 55
Standard Plasterboard.

(c) 70 Soundscreen 2.0 55/46 65 – 70 50 – 55

CSR 6215
(a) Nil 47/41 75 – 80 55 – 60
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 90 Gold Batts 2.0 56/48 65 – 70 50 – 55
• Furring channels at
450mm maximum centres.
EWFA 26162
(c) 70 Soundscreen 2.0 56/48 65 – 70 50 – 55

CSR 6217
60/60/60 (a) Nil 50/44 70 – 75 55 – 60
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 90 Gold Batts 2.0 59/51 60 – 62 45 – 50
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 59/51 60 – 62 45 – 50

CSR 6219
(a) Nil 47/41 75 – 80 55 – 60
30/30/30 • 1 x 16mm Gyprock
from below Fyrchek Plasterboard.
only (b) 90 Gold Batts 2.0 56/48 65 – 70 50 – 55
• Furring channels at
450mm maximum centres.
EWFA 26162
(c) 70 Soundscreen 2.0 56/48 65 – 70 50 – 55

G10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Resilient Mounted Furring

Floor finished bare or with carpet and


underlay as per system table. Cavity infill as per system table.

1 x 19mm or 22mm particleboard or Rondo Furring Channel clipped to


timber flooring or fibre cement sheet Gyprock Resilient Mounts.
of at least 15kg/m2.
Rondo Furring Channel at 600mm max
Timber or steel joists at 600mm centres except where noted in system
maximum centres. table.

Minimum 205mm cavity depth. Ceiling lining as per system table, fixed to
furring channel.
NOTE: RISF = Resistance to Incipient
Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw/Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6221
60/60/60 (a) Nil 50/44 70 – 75 55 – 60
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 60 • 1 x 16mm Gyprock (b) 90 Gold Batts 2.0 59/51 60 – 62 45 – 50
minutes Fyrchek Plasterboard (any
order).
EWFA 26162 (c) 70 Soundscreen 2.0 59/51 60 – 62 45 – 50

CSR 6222
90/90/90 (a) Nil 50/44 70 – 75 55 – 60
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 90 Gold Batts 2.0 59/51 60 – 62 45 – 50
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 59/51 60 – 62 45 – 50

CSR 6223
120/120/120 (a) Nil 52/46 70 – 75 55 – 60
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 90 Gold Batts 2.0 60/52 60 – 62 45 – 50
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 70 Soundscreen 2.0 60/52 60 – 62 45 – 50

GYPROCK® THE RED BOOK™ 1 G11


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Suspended Grid & Furring

Floor finished bare or with carpet and Cavity infill as per system table.
underlay, as per system table.
Rondo Suspended Ceiling System.
1 x 19mm or 22mm particleboard or
timber flooring or fibre cement sheet Rondo Furring Channel at 600mm max
of at least 15kg/m2. centres except where noted in system
table.
Timber or steel joists.
Ceiling lining as per system table, fixed to
Minimum 340mm cavity depth. furring channel.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw/Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 10171
(a) Nil 45/38 75 – 80 60 – 65

(b) 90 Gold Batts 2.0 51/44 70 – 75 55 – 60


• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 70 Soundscreen 2.0 52/45 70 – 75 55 – 60

(d) 165 Acoustigard 11kg 53/46 70 – 75 55 – 60

CSR 6231
(a) Nil 45/38 75 – 80 60 – 65

(b) 90 Gold Batts 2.0 51/44 70 – 75 55 – 60


• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 70 Soundscreen 2.0 52/45 70 – 75 55 – 60

(d) 165 Acoustigard 11kg 53/46 70 – 75 55 – 60

CSR 6232
(a) Nil 47/41 75 – 80 60 – 65

(b) 90 Gold Batts 2.0 53/47 70 – 75 55 – 60


• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 70 Soundscreen 2.0 54/48 70 – 75 55 – 60

(d) 165 Acoustigard 11kg 55/49 70 – 75 55 – 60

CSR 6233
(a) Nil 48/42 75 – 80 60 – 65

(b) 90 Gold Batts 2.0 54/48 70 – 75 55 – 60


• 2 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 70 Soundscreen 2.0 55/49 70 – 75 55 – 60

(d) 165 Acoustigard 11kg 56/50 70 – 75 55 – 60

CSR 6240
(a) Nil 46/40 75 – 80 60 – 65
30/30/30 • 1 x 13mm Gyprock
from below (b) 90 Gold Batts 2.0 52/46 70 – 75 55 – 60
Fyrchek Plasterboard.
only
• Furring channels at
(c) 70 Soundscreen 2.0 53/47 70 – 75 55 – 60
450mm maximum centres.
EWFA 26162
(d) 165 Acoustigard 11kg 54/48 70 – 75 55 – 60

G12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Suspended Grid & Furring

Floor finished bare or with carpet and Cavity infill as per system table.
underlay, as per system table.
Rondo Suspended Ceiling System.
1 x 19mm or 22mm particleboard or
timber flooring or fibre cement sheet Rondo Furring Channel at 600mm max
of at least 15kg/m2. centres except where noted in system
table.
Timber or steel joists.
Ceiling lining as per system table, fixed to
Minimum 340mm cavity depth. furring channel.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw/Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6242
60/60/60 (a) Nil 49/43 75 – 80 58 – 62
from below
only (b) 90 Gold Batts 2.0 55/49 65 – 70 50 – 55
• 2 x 13mm Gyprock
+RISF 30 Fyrchek Plasterboard.
minutes (c) 70 Soundscreen 2.0 56/50 65 – 70 50 – 55

EWFA 26162 (d) 165 Acoustigard 11kg 57/51 65 – 70 50 – 55

CSR 6244
60/60/60 (a) Nil 50/44 75 – 80 58 – 62
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard. (b) 90 Gold Batts 2.0 56/50 65 – 70 50 – 55
only
+RISF 60 • 1 x 16mm Gyprock
minutes Fyrchek Plasterboard (any (c) 70 Soundscreen 2.0 57/51 65 – 70 50 – 55
order).
EWFA 26162 (d) 165 Acoustigard 11kg 58/52 65 – 70 50 – 55

CSR 6245
90/90/90 (a) Nil 49/43 75 – 80 58 – 62
from below
only (b) 90 Gold Batts 2.0 55/49 65 – 70 50 – 55
• 2 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 70 Soundscreen 2.0 56/50 65 – 70 50 – 55

EWFA 26162 (d) 165 Acoustigard 11kg 57/51 65 – 70 50 – 55

CSR 6247
120/120/120 (a) Nil 52/46 75 – 80 58 – 62
from below
only (b) 90 Gold Batts 2.0 58/52 65 – 70 50 – 55
• 3 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 70 Soundscreen 2.0 59/53 65 – 70 50 – 55

EWFA 26162 (d) 165 Acoustigard 11kg 60/54 65 – 70 50 – 55

GYPROCK® THE RED BOOK™ 1 G13


SYSTEM SPECIFICATIONS Floor/Ceiling – Joists with Suspended Grid & Resilient Mounted Furring

Floor finished bare or with carpet and Cavity infill as per system table.
underlay, as per system table.
Rondo Suspended Ceiling System with
1 x 19mm or 22mm particleboard or Gyprock Resilient Mounts.
timber flooring or fibre cement sheet
of at least 15kg/m2. Furring channels at 600mm max. centres
except where noted in system tables.
Timber or steel joists.
Ceiling lining as per system table, fixed to
Minimum 340mm cavity depth. furring channel.

NOTE: RISF = Resistance to Incipient


Spread of Fire

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A122


Refer to Book 2 and 3 for further information

Carpet +
FRL SYSTEM CAVITY INFILL Bare Floor
CEILING LININGS Rw/Rw+Ctr Underlay
Report Nº (Refer to TABLE B6) Ln,w
Ln,w
CSR 6255
(a) Nil 48/41 75 – 80 55 – 60

(b) 90 Gold Batts 2.0 54/47 65 – 70 45 – 50


• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 70 Soundscreen 2.0 55/48 65 – 70 45 – 50

(d) 165 Acoustigard 11kg 56/49 65 – 70 45 – 50

CSR 6265
(a) Nil 48/42 75 – 80 55 – 60
30/30/30 • 1 x 13mm Gyprock
from below (b) 90 Gold Batts 2.0 54/48 65 – 70 45 – 50
Fyrchek Plasterboard.
only • Furring channels at
(c) 70 Soundscreen 2.0 55/49 65 – 70 45 – 50
EWFA 26162
450mm maximum centres.
(d) 165 Acoustigard 11kg 56/50 65 – 70 45 – 50

CSR 6267
60/60/60 (a) Nil 51/45 70 – 75 55 – 60
from below
only (b) 90 Gold Batts 2.0 57/51 60 – 62 45 – 50
• 2 x 13mm Gyprock
+RISF 30 Fyrchek Plasterboard.
minutes (c) 70 Soundscreen 2.0 58/52 60 – 62 45 – 50

EWFA 26162 (d) 165 Acoustigard 11kg 59/53 60 – 62 45 – 50

CSR 6269
60/60/60 (a) Nil 52/46 70 – 75 55 – 60
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard. (b) 90 Gold Batts 2.0 58/52 60 – 62 45 – 50
only
+RISF 60 • 1 x 16mm Gyprock
minutes Fyrchek Plasterboard (any (c) 70 Soundscreen 2.0 59/53 60 – 62 45 – 50
order).
EWFA 26162 (d) 165 Acoustigard 11kg 60/54 60 – 62 45 – 50

CSR 6271
90/90/90 (a) Nil 51/45 70 – 75 55 – 60
from below
only (b) 90 Gold Batts 2.0 57/51 60 – 62 45 – 50
• 2 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 70 Soundscreen 2.0 58/52 60 – 62 45 – 50

EWFA 26162 (d) 165 Acoustigard 11kg 59/53 60 – 62 45 – 50

CSR 6273
120/120/120 (a) Nil 54/48 70 – 75 55 – 60
from below
only (b) 90 Gold Batts 2.0 60/54 60 – 62 40 – 45
• 3 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 70 Soundscreen 2.0 61/55 60 – 62 40 – 45

EWFA 26162 (d) 165 Acoustigard 11kg 62/56 60 – 62 40 – 45

G14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (150mm) with Clip Fixed Furring

Floor finished bare or with materials as


Rondo Furring Channel Nº129 at 600mm
per system table.
max. centres, except where noted in
system table.
150mm min. concrete slab.
Cavity infill as per system table.
Clips direct fixed to concrete slab at
1200mm centres.
Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: Polyester insulation may NOT


be used where the system has
NOTE: *AQ Underlay to be min 4.5mm non-combustible construction
acoustic quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 6303
(a) Nil 54/43 70 – 75 62 – 65 45 – 50
• 1 x 10mm Gyprock Plus
Refer to Plasterboard.
(d) 50 Acoustigard 14kg 59/48 65 – 70 58 – 62 40 – 45
AS3600 • Furring channel at 450mm
maximum centres.
(e) 50 MAB Polyester 14kg 56/45 65 – 70 58 – 62 40 – 45

CSR 6304
(a) Nil 55/44 70 – 75 63 – 68 45 – 50

Refer to • 1 x 10mm Gyprock


(d) 50 Acoustigard 14kg 60/49 65 – 70 55 – 60 40 – 45
AS3600 Supaceil Plasterboard.

(e) 50 MAB Polyester 14kg 57/46 65 – 70 58 – 62 40 – 45

CSR 10172
(a) Nil 56/46 70 – 75 60 – 65 45 – 50

Refer to • 1 x 10mm Gyprock HD


(b) 50 MAB Polyester 14kg 58/48 65 – 70 55 – 60 40 – 45
AS3600 Plasterboard.

(c) 50 Acoustigard 14kg 61/51 65 – 70 55 – 60 40 – 45

CSR 10173
(a) Nil 58/48 65 – 70 58 – 62 45 – 50

Refer to • 2 x 10mm Gyprock HD


(b) 50 MAB Polyester 14kg 60/51 65 – 70 53 – 58 40 – 45
AS3600 Plasterboard.

(c) 50 Acoustigard 14kg 63/54 65 – 70 53 – 58 40 – 45

CSR 6311
(a) Nil 56/46 70 – 75 60 – 65 45 – 50

Refer to • 1 x 13mm Gyprock


(d) 50 Acoustigard 14kg 61/51 65 – 70 55 – 60 40 – 45
AS3600 Standard Plasterboard.

(e) 50 MAB Polyester 14kg 58/48 65 – 70 55 – 60 40 – 45

CSR 6312
(a) Nil 58/48 70 – 75 60 – 65 45 – 50

Refer to • 1 x 13mm Gyprock


(d) 50 Acoustigard 14kg 63/53 65 – 70 55 – 60 40 – 45
AS3600 Soundchek Plasterboard.

(e) 50 MAB Polyester 14kg 60/50 65 – 70 55 – 60 40 – 45

GYPROCK® THE RED BOOK™ 1 G15


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (150mm) with Clip Fixed Furring

Floor finished bare or with materials as


Rondo Furring Channel Nº129 at 600mm
per system table.
max. centres, except where noted in
system table.
150mm min. concrete slab.
Cavity infill as per system table.
Clips direct fixed to concrete slab at
1200mm centres.
Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: RISF = Resistance to Incipient NOTE: Polyester insulation may NOT


Spread of Fire. be used where the system has
*AQ Underlay to be min 4.5mm acoustic non-combustible construction
quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 6315
(a) Nil 57/47 70 – 75 60 – 65 45 – 50
• 1 x 13mm Gyprock
30/30/30 Fyrchek Plasterboard.
(d) 50 Acoustigard 14kg 62/52 65 – 70 55 – 60 40 – 45
EWFA 26162 • Furring channels at
450mm maximum centres.
(e) 50 MAB Polyester 11kg 59/49 65 – 70 55 – 60 40 – 45

CSR 3614
(a) Nil 58/48 70 – 75 60 – 65 45 – 50
• 1 x 16mm Gyprock EC08
30/30/30 Complete.
(c) 50 Acoustigard 14kg 63/53 65 – 70 55 – 60 40 – 45
EWFA 26162 • Furring channels at
450mm maximum centres.
(d) 50 MAB Polyester 11kg 60/50 65 – 70 55 – 60 40 – 45

CSR 6318
(a) Nil 59/49 65 – 70 58 – 62 45 – 50

60/60/60 • 2 x 13mm Gyprock


(d) 50 Acoustigard 14kg 64/55 65 – 70 53 – 58 40 – 45
Fyrchek Plasterboard.
EWFA 26162

(e) 50 MAB Polyester 11kg 61/52 65 – 70 53 – 58 40 – 45

CSR 6321
(a) Nil 59/49 65 – 70 58 – 62 45 – 50
• 1 x 13mm Gyprock
60/60/60 Fyrchek Plasterboard.
• 1 x 16mm Gyprock (d) 50 Acoustigard 14kg 64/55 65 – 70 53 – 58 40 – 45
EWFA 26162 Fyrchek Plasterboard (any
order).
(e) 50 MAB Polyester 11kg 61/52 65 – 70 53 – 58 40 – 45

CSR 3631
(a) Nil 59/49 65 – 70 58 – 62 45 – 50
• 1 x 13mm Gyprock
60/60/60 EC08 Complete (against
framing). (d) 50 Acoustigard 14kg 64/55 65 – 70 53 – 58 40 – 45
EWFA 26162 • 1 x 16mm Gyprock EC08
Complete.
(e) 50 MAB Polyester 11kg 61/52 65 – 70 53 – 58 40 – 45

CSR 6322
(a) Nil 59/49 65 – 70 58 – 62 45 – 50

90/90/90 • 2 x 16mm Gyprock


(d) 50 Acoustigard 14kg 64/55 65 – 70 53 – 58 40 – 45
Fyrchek Plasterboard.
EWFA 26162

(e) 50 MAB Polyester 11kg 61/52 65 – 70 53 – 58 40 – 45

G16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (150mm) with Clip Fixed Furring

Floor finished bare or with materials as


Rondo Furring Channel Nº129 at 600mm
per system table.
max. centres, except where noted in
system table.
150mm min. concrete slab.
Cavity infill as per system table.
Clips direct fixed to concrete slab at
1200mm centres.
Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: RISF = Resistance to Incipient NOTE: Polyester insulation may NOT


Spread of Fire. be used where the system has
*AQ Underlay to be min 4.5mm acoustic non-combustible construction
quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 3635
(a) Nil 59/49 65 – 70 58 – 62 45 – 50

90/90/90 • 2 x 16mm Gyprock EC08


(d) 50 Acoustigard 14kg 64/55 65 – 70 53 – 58 40 – 45
Complete.
EWFA 26162

(e) 50 MAB Polyester 11kg 61/52 65 – 70 53 – 58 40 – 45

CSR 6324
(a) Nil 60/50 65 – 70 58 – 62 40 – 45

120/120/120 • 3 x 16mm Gyprock


(d) 50 Acoustigard 14kg 65/56 62 – 65 53 – 58 35 – 40
Fyrchek Plasterboard.
EWFA 26162

(e) 50 MAB Polyester 11kg 62/53 62 – 65 53 – 58 35 – 40

CSR 3645
(a) Nil 60/50 65 – 70 58 – 62 40 – 45

120/120/120 • 3 x 16mm Gyprock EC08


(d) 50 Acoustigard 14kg 65/56 62 – 65 53 – 58 35 – 40
Complete.
EWFA 26162

(e) 50 MAB Polyester 11kg 62/53 62 – 65 53 – 58 35 – 40

GYPROCK® THE RED BOOK™ 1 G17


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (200mm) with Clip Fixed Furring

Floor finished bare or with materials as


Rondo Furring Channel Nº129 at 600mm
per system table.
max. centres, except where noted in
system table.
200mm min. concrete slab.
Cavity infill as per system table.
Clips direct fixed to concrete slab at
1200mm centres.
Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: RISF = Resistance to Incipient NOTE: Polyester insulation may NOT


Spread of Fire. be used where the system has
*AQ Underlay to be min 4.5mm acoustic non-combustible construction
quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 6905
(a) Nil 58/48 70 – 75 63 – 68 45 – 50

Refer to • 1 x 10mm Gyprock


(d) 50 Acoustigard 14kg 63/53 63 – 68 53 – 58 40 – 45
AS3600 Supaceil Plasterboard.

(e) 50 MAB Polyester 11kg 60/50 63 – 68 55 – 60 40 – 45

CSR 6910
(a) Nil 59/50 70 – 75 60 – 65 45 – 50

Refer to • 1 x 13mm Gyprock


(d) 50 Acoustigard 14kg 64/55 63 – 68 53 – 58 40 – 45
AS3600 Standard Plasterboard.

(e) 50 MAB Polyester 11kg 61/52 63 – 68 53 – 58 40 – 45

CSR 6915
(a) Nil 61/52 70 – 75 60 – 65 45 – 50

Refer to • 1 x 13mm Gyprock


(d) 50 Acoustigard 14kg 66/57 63 – 68 53 – 58 40 – 45
AS3600 Soundchek Plasterboard.

(e) 50 MAB Polyester 11kg 63/54 63 – 68 53 – 58 40 – 45

CSR 6921
(a) Nil 60/51 70 – 75 60 – 65 45 – 50
• 1 x 16mm Gyprock
30/30/30 Fyrchek Plasterboard.
(c) 50 Acoustigard 14kg 65/56 63 – 68 55 – 58 40 – 45
EWFA 26162 • Furring channels at
450mm maximum centres.
(d) 50 MAB Polyester 11kg 62/53 63 – 68 53 – 58 40 – 45

CSR 3618
(a) Nil 61/52 70 – 75 60 – 65 45 – 50
• 1 x 16mm Gyprock EC08
30/30/30 Complete.
(c) 50 Acoustigard 14kg 66/58 63 – 68 53 – 58 40 – 45
EWFA 26162 • Furring channels at
450mm maximum centres.
(d) 50 MAB Polyester 11kg 63/55 63 – 68 53 – 58 40 – 45

CSR 6925
(a) Nil 61/52 65 – 70 58 – 62 45 – 50
• 1 x 13mm Gyprock
60/60/60 Fyrchek Plasterboard.
• 1 x 16mm Gyprock (d) 50 Acoustigard 14kg 65/58 63 – 68 50 – 55 40 – 45
EWFA 26162 Fyrchek Plasterboard (any
order).
(e) 50 MAB Polyester 14kg 63/55 63 – 68 50 – 55 40 – 45

G18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete with Resilient Mounted Furring

Floor finished bare or with materials as Rondo Furring Channel Nº129 at 600mm
per system table. max. centres, except where noted in
system table.
150mm min. concrete slab.
Cavity infill as per system table.
Gyprock Resilient Mounts direct fixed
to concrete slab at 1200mm centres. Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: Polyester insulation may NOT


be used where the system has
non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Floor Carpet +


FRL SYSTEM CAVITY INFILL or Tiles +
CEILING LININGS Rw/Rw+Ctr Adhesive Underlay
Report Nº (Refer to TABLE B6)
Ln,w Ln,w
CSR 6327
(a) Nil 56/45 65 – 70 40 – 45
• 1 x 10mm Gyprock Plus
Refer to Plasterboard.
(d) 50 Acoustigard 14kg 60/49 62 – 65 40 – 45
AS3600 • Furring channel at 450mm
maximum centres.
(e) 50 MAB Polyester 11kg 58/47 62 – 65 35 – 40

CSR 6328
(a) Nil 57/46 65 – 70 40 – 45

Refer to • 1 x 10mm Gyprock


(d) 50 Acoustigard 14kg 62/51 62 – 65 40 – 45
AS3600 Supaceil Plasterboard.

(e) 50 MAB Polyester 11kg 59/48 62 – 65 35 – 40

CSR 10174
(a) Nil 58/48 65 – 70 40 – 45

Refer to • 1 x 10mm Gyprock HD


(b) 50 MAB Polyester 11kg 60/50 62 – 65 35 – 40
AS3600 Plasterboard.

(c) 50 Acoustigard 14kg 63/53 62 – 65 40 – 45

CSR 10175
(a) Nil 61/52 65 – 70 40 – 45

Refer to • 2 x 10mm Gyprock HD


(b) 50 MAB Polyester 11kg 63/55 60 – 65 35 – 40
AS3600 Plasterboard.

(c) 50 Acoustigard 14kg 66/58 60 – 65 40 – 45

CSR 6338
(a) Nil 58/48 65 – 70 40 – 45

Refer to • 1 x 13mm Gyprock


(d) 50 Acoustigard 14kg 63/53 62 – 65 40 – 45
AS3600 Standard Plasterboard.

(e) 50 MAB Polyester 11kg 60/50 62 – 65 35 – 40

CSR 6339
(a) Nil 60/51 65 – 70 40 – 45

Refer to • 1 x 13mm Gyprock


(d) 50 Acoustigard 14kg 65/56 62 – 65 40 – 45
AS3600 Soundchek Plasterboard.

(e) 50 MAB Polyester 11kg 62/53 62 – 65 35 – 40

GYPROCK® THE RED BOOK™ 1 G19


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete with Resilient Mounted Furring

Floor finished bare or with materials as Rondo Furring Channel Nº129 at 600mm
per system table. max. centres, except where noted in
system table.
150mm min. concrete slab.
Cavity infill as per system table.
Gyprock Resilient Mounts direct fixed
to concrete slab at 1200mm centres. Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: Polyester insulation may NOT


NOTE: RISF = Resistance to Incipient be used where the system has
Spread of Fire non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Floor Carpet +


FRL SYSTEM CAVITY INFILL or Tiles +
CEILING LININGS Rw/Rw+Ctr Adhesive Underlay
Report Nº (Refer to TABLE B6)
Ln,w Ln,w
CSR 6343
(a) Nil 59/49 65 – 70 40 – 45
• 1 x 13mm Gyprock
30/30/30 Fyrchek Plasterboard.
(d) 50 Acoustigard 14kg 64/54 62 – 65 40 – 45
EWFA 26162 • Furring channels at
450mm maximum centres.
(e) 50 MAB Polyester 11kg 61/51 62 – 65 35 – 40

CSR 3666
(a) Nil 60/51 65 – 70 40 – 45
• 1 x 16mm Gyprock EC08
30/30/30 Complete.
(c) 50 Acoustigard 14kg 65/56 62 – 65 35 – 40
EWFA 26162 • Furring channels at
450mm maximum centres.
(d) 50 MAB Polyester 11kg 62/53 62 – 65 35 – 40

CSR 6344
(a) Nil 62/53 65 – 70 40 – 45
60/60/60
+RISF 30
• 2 x 13mm Gyprock
minutes (d) 50 Acoustigard 14kg 67/59 60 – 65 40 – 45
Fyrchek Plasterboard.
EWFA 26162
(e) 50 MAB Polyester 11kg 64/56 60 – 65 35 – 40

CSR 6345
(a) Nil 62/53 65 – 70 40 – 45
• 1 x 13mm Gyprock
60/60/60 Fyrchek Plasterboard.
• 1 x 16mm Gyprock (d) 50 Acoustigard 14kg 67/59 60 – 65 40 – 45
EWFA 26162 Fyrchek Plasterboard (any
order).
(e) 50 MAB Polyester 11kg 64/56 60 – 65 35 – 40

CSR 3681
(a) Nil 62/53 65 – 70 40 – 45
• 1 x 13mm Gyprock
60/60/60 EC08 Complete (against
framing). (d) 50 Acoustigard 14kg 67/59 60 – 65 35 – 40
EWFA 26162 • 1 x 16mm Gyprock EC08
Complete.
(e) 50 MAB Polyester 11kg 64/56 60 – 65 35 – 40

CSR 6346
(a) Nil 62/53 65 – 70 40 – 45

90/90/90 • 2 x 16mm Gyprock


(d) 50 Acoustigard 14kg 67/59 60 – 65 40 – 45
EWFA 26162 Fyrchek Plasterboard.

(e) 50 MAB Polyester 11kg 64/56 60 – 65 35 – 40

G20 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete with Resilient Mounted Furring

Floor finished bare or with materials as Rondo Furring Channel Nº129 at 600mm
per system table. max. centres, except where noted in
system table.
150mm min. concrete slab.
Cavity infill as per system table.
Gyprock Resilient Mounts direct fixed
to concrete slab at 1200mm centres. Ceiling lining as per system table, fixed to
furring channel.
Minimum 40mm cavity.

NOTE: Polyester insulation may NOT


be used where the system has
NOTE: RISF = Resistance to Incipient non-combustible construction
Spread of Fire requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Floor Carpet +


FRL SYSTEM CAVITY INFILL or Tiles +
CEILING LININGS Rw/Rw+Ctr Adhesive Underlay
Report Nº (Refer to TABLE B6)
Ln,w Ln,w
CSR 3685
(a) Nil 62/53 65 – 70 40 – 45

90/90/90 • 2 x 16mm Gyprock EC08


(d) 50 Acoustigard 14kg 67/59 60 – 65 35 – 40
Complete.
EWFA 26162

(e) 50 MAB Polyester 11kg 64/56 60 – 65 35 – 40

CSR 6348
(a) Nil 63/54 65 – 70 40 – 45

120/120/120 • 3 x 16mm Gyprock


(d) 50 Acoustigard 14kg 68/60 58 – 62 40 – 45
Fyrchek Plasterboard.
EWFA 26162

(e) 50 MAB Polyester 11kg 65/57 58 – 62 35 – 40

CSR 3695
(a) Nil 63/54 65 – 70 40 – 45

120/120/120 • 3 x 16mm Gyprock EC08


(d) 50 Acoustigard 14kg 68/60 58 – 62 35 – 40
Complete.
EWFA 26162

(e) 50 MAB Polyester 11kg 65/57 58 – 62 35 – 40

GYPROCK® THE RED BOOK™ 1 G21


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (150mm) with Suspension Grid

Floor finished bare or with materials as Minimum 150mm cavity.


per system table.
Cavity infill as per system table.
150mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system. furring channel.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.

NOTE: Polyester insulation may NOT


be used where the system has
NOTE: *AQ Underlay to be min 4.5mm non-combustible construction
acoustic quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 6352
(a) Nil 57/47 65 – 70 58 – 62 45 – 50
• 1 x 10mm Gyprock Plus
(c) 75 Acoustigard 11kg 61/52 60 – 65 53 – 58 40 – 45
Refer to Plasterboard.
AS3600 • Furring channel at 450mm
(e) 50 Acoustigard 14kg 60/51 60 – 65 53 – 58 40 – 45
maximum centres.
(f) 75 MAB Polyester 11kg 60/51 60 – 65 53 – 58 40 – 45

CSR 6353
(a) Nil 58/48 65 – 70 58 – 62 45 – 50

(c) 75 Acoustigard 11kg 62/53 60 – 65 53 – 58 40 – 45


Refer to • 1 x 10mm Gyprock
AS3600 Supaceil Plasterboard.
(e) 50 Acoustigard 14kg 61/52 60 – 65 53 – 58 40 – 45

(f) 75 MAB Polyester 11kg 61/52 60 – 65 53 – 58 40 – 45

CSR 10176
(a) Nil 59/50 65 – 70 58 – 62 45 – 50

(b) 75 Acoustigard 11kg 63/55 60 – 65 50 – 55 40 – 45


Refer to • 1 x 10mm Gyprock HD
AS3600 Plasterboard.
(c) 75 MAB Polyester 11kg 62/54 60 – 65 50 – 55 40 – 45

(d) 50 Acoustigard 14kg 62/54 60 – 65 50 – 55 40 – 45

CSR 10177
(a) Nil 61/53 65 – 70 55 – 60 45 – 50

(b) 75 Acoustigard 11kg 65/58 60 – 65 48 – 52 40 – 45


Refer to • 2 x 10mm Gyprock HD
AS3600 Plasterboard.
(c) 75 MAB Polyester 11kg 64/57 60 – 65 48 – 52 40 – 45

(d) 50 Acoustigard 14kg 64/57 60 – 65 48 – 52 40 – 45

CSR 6360
(a) Nil 59/50 65 – 70 58 – 62 45 – 50

(c) 75 Acoustigard 11kg 63/55 60 – 65 50 – 55 40 – 45


Refer to • 1 x 13mm Gyprock
AS3600 Standard Plasterboard.
(e) 50 Acoustigard 14kg 62/54 60 – 65 50 – 55 40 – 45

(f) 75 MAB Polyester 11kg 62/54 60 – 65 50 – 55 40 – 45

CSR 6361
(a) Nil 60/51 65 – 70 58 – 62 45 – 50

(c) 75 Acoustigard 11kg 64/56 60 – 65 50 – 55 40 – 45


Refer to • 1 x 13mm Gyprock
AS3600 Soundchek Plasterboard.
(e) 50 Acoustigard 14kg 63/55 60 – 65 50 – 55 40 – 45

(f) 75 MAB Polyester 11kg 63/55 60 – 65 50 – 55 40 – 45

G22 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (150mm) with Suspension Grid

Floor finished bare or with materials as Minimum 182mm cavity.


per system table.
Cavity infill as per system table.
150mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system. furring channel.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.

NOTE: RISF = Resistance to Incipient NOTE: Polyester insulation may NOT


Spread of Fire. be used where the system has
*AQ Underlay to be min 4.5mm acoustic non-combustible construction
quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 6365
(a) Nil 60/51 65 – 70 58 – 62 45 – 50
• 1 x 13mm Gyprock
30/30/30 (c) 75 Acoustigard 11kg 64/56 60 – 65 50 – 55 40 – 45
Fyrchek Plasterboard.
EWFA 26162 • Furring channels at
(e) 50 Acoustigard 14kg 63/55 60 – 65 50 – 55 40 – 45
450mm maximum centres.
(f) 75 MAB Polyester 11kg 63/55 60 – 65 50 – 55 40 – 45

CSR 3714
(a) Nil 60/51 65 – 70 58 – 62 45 – 50
• 1 x 16mm Gyprock EC08
30/30/30 (b) 75 Acoustigard 11kg 64/56 60 – 65 50 – 55 40 – 45
Complete.
EWFA 26162 • Furring channels at
(d) 50 Acoustigard 14kg 63/55 60 – 65 50 – 55 40 – 45
450mm maximum centres.
(e) 75 MAB Polyester 11kg 63/55 60 – 65 50 – 55 40 – 45

CSR 6367
(a) Nil 61/53 65 – 70 55 – 60 45 – 50
60/60/60
+RISF 30 (c) 75 Acoustigard 11kg 65/58 60 – 65 48 – 52 40 – 45
• 2 x 13mm Gyprock
minutes
Fyrchek Plasterboard.
(e) 50 Acoustigard 14kg 64/57 60 – 65 48 – 52 40 – 45
EWFA 26162
(f) 75 MAB Polyester 11kg 64/57 60 – 65 48 – 52 40 – 45

CSR 6370
(a) Nil 61/53 65 – 70 55 – 60 45 – 50
60/60/60 • 1 x 13mm Gyprock
+RISF 60 Fyrchek Plasterboard. (c) 75 Acoustigard 11kg 65/58 60 – 65 48 – 52 40 – 45
minutes • 1 x 16mm Gyprock
Fyrchek Plasterboard (any (e) 50 Acoustigard 14kg 64/57 60 – 65 48 – 52 40 – 45
EWFA 26162 order).
(f) 75 MAB Polyester 11kg 64/57 60 – 65 48 – 52 40 – 45

CSR 3731
(a) Nil 61/53 65 – 70 55 – 60 45 – 50
60/60/60 • 1 x 13mm Gyprock
+RISF 60 EC08 Complete (against (c) 75 Acoustigard 11kg 65/58 60 – 65 48 – 52 40 – 45
minutes framing).
• 1 x 16mm Gyprock EC08 (e) 50 Acoustigard 14kg 64/57 60 – 65 48 – 52 40 – 45
EWFA 26162 Complete.
(f) 75 MAB Polyester 11kg 64/57 60 – 65 48 – 52 40 – 45

CSR 6371
(a) Nil 61/53 65 – 70 55 – 60 45 – 50
90/90/90
+RISF 60 (c) 75 Acoustigard 11kg 65/58 60 – 65 48 – 52 40 – 45
• 2 x 16mm Gyprock
minutes
Fyrchek Plasterboard.
(e) 50 Acoustigard 14kg 64/57 60 – 65 48 – 52 40 – 45
EWFA 26162
(f) 75 MAB Polyester 11kg 64/57 60 – 65 48 – 52 40 – 45

GYPROCK® THE RED BOOK™ 1 G23


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (150mm) with Suspension Grid

Floor finished bare or with materials as Minimum 182mm cavity.


per system table.
Cavity infill as per system table.
150mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system. furring channel.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.

NOTE: RISF = Resistance to Incipient NOTE: Polyester insulation may NOT


Spread of Fire. be used where the system has
*AQ Underlay to be min 4.5mm acoustic non-combustible construction
quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information
Bare Timber/
FRL SYSTEM CAVITY INFILL Rw/ Floor or Tile + *AQ Carpet +
CEILING LININGS Tiles + Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Adhesive Underlay
Ln,w Ln,w Ln,w
CSR 3735
(a) Nil 61/53 65 – 70 55 – 60 45 – 50
90/90/90
+RISF 60 (c) 75 Acoustigard 11kg 65/58 60 – 65 48 – 52 40 – 45
• 2 x 16mm Gyprock EC08
minutes
Complete.
(e) 50 Acoustigard 14kg 64/57 60 – 65 48 – 52 40 – 45
EWFA 26162
(f) 75 MAB Polyester 11kg 64/57 60 – 65 48 – 52 40 – 45

CSR 6373
(a) Nil 62/54 60 – 65 55 – 60 40 – 45
120/120/120
+RISF 60 (c) 75 Acoustigard 11kg 66/59 58 – 62 48 – 52 35 – 40
• 3 x 16mm Gyprock
minutes
Fyrchek Plasterboard.
(e) 50 Acoustigard 14kg 65/58 58 – 62 48 – 52 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 65/58 58 – 62 48 – 52 35 – 40

CSR 3745
(a) Nil 62/54 60 – 65 55 – 60 40 – 45
120/120/120
+RISF 60 (c) 75 Acoustigard 11kg 66/59 58 – 62 48 – 52 35 – 40
• 3 x 16mm Gyprock EC08
minutes
Complete.
(e) 50 Acoustigard 14kg 65/58 58 – 62 48 – 52 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 65/58 58 – 62 48 – 52 35 – 40

G24 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete (200mm) with Suspension Grid

Floor finished bare or with materials as Minimum 182mm cavity.


per system table.
Cavity infill as per system table.
200mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system. furring channel.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.

NOTE: RISF = Resistance to Incipient NOTE: Polyester insulation may NOT


Spread of Fire. be used where the system has
*AQ Underlay to be min 4.5mm acoustic non-combustible construction
quality material requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Timber/ Carpet +


FRL SYSTEM CAVITY INFILL Rw/ Tile + *AQ
CEILING LININGS Floor Underlay
Report Nº (Refer to TABLE B6) Rw+Ctr Underlay
Ln,w Ln,w Ln,w
CSR 6935
(a) Nil 60/51 65 – 70 58 – 62 45 – 50

(c) 75 Acoustigard 11kg 64/56 60 – 65 53 – 58 40 – 45


Refer to • 1 x 10mm Gyprock
AS3600 Supaceil Plasterboard.
(e) 50 Acoustigard 14kg 63/55 60 – 65 53 – 58 40 – 45

(f) 75 MAB Polyester 11kg 63/55 60 – 65 53 – 58 40 – 45

CSR 6940
(a) Nil 61/53 63 – 68 58 – 62 45 – 50

(c) 75 Acoustigard 11kg 65/58 58 – 62 50 – 55 40 – 45


Refer to • 1 x 13mm Gyprock
AS3600 Standard Plasterboard.
(e) 50 Acoustigard 14kg 64/57 58 – 62 50 – 55 40 – 45

(f) 75 MAB Polyester 11kg 64/57 58 – 62 50 – 55 40 – 45

CSR 6945
(a) Nil 62/54 63 – 68 58 – 62 45 – 50

(c) 75 Acoustigard 11kg 66/59 58 – 62 50 – 55 40 – 45


Refer to • 1 x 13mm Gyprock
AS3600 Soundchek Plasterboard.
(e) 50 Acoustigard 14kg 65/58 58 – 62 50 – 55 40 – 45

(f) 75 MAB Polyester 11kg 65/58 58 – 62 50 – 55 40 – 45

CSR 6951
(a) Nil 62/54 63 – 68 58 – 62 45 – 50
• 1 x 16mm Gyprock
30/30/30 (b) 75 Acoustigard 11kg 66/59 58 – 62 50 – 55 40 – 45
Fyrchek Plasterboard.
EWFA 26162 • Furring channel at 450mm
(d) 50 Acoustigard 14kg 65/58 58 – 62 50 – 55 40 – 45
maximum centres.
(e) 75 MAB Polyester 11kg 65/58 58 – 62 50 – 55 40 – 45

CSR 3718
(a) Nil 63/55 63 – 68 58 – 62 45 – 50
• 1 x 16mm Gyprock EC08
30/30/30 (b) 75 Acoustigard 11kg 67/60 58 – 62 50 – 55 40 – 45
Complete.
EWFA 26162 • Furring channel at 450mm
(d) 50 Acoustigard 14kg 66/59 58 – 62 50 – 55 40 – 45
maximum centres.
(e) 75 MAB Polyester 11kg 66/59 58 – 62 50 – 55 40 – 45

CSR 6955
(a) Nil 64/56 63 – 68 55 – 60 45 – 50
60/60/60 • 1 x 13mm Gyprock
+RISF 60 Fyrchek Plasterboard. (c) 75 Acoustigard 11kg 68/61 58 – 62 48 – 52 40 – 45
minutes • 1 x 16mm Gyprock
Fyrchek Plasterboard (any (e) 50 Acoustigard 14kg 67/60 58 – 62 48 – 52 40 – 45
EWFA 26162 order).
(f) 75 MAB Polyester 11kg 67/60 58 – 62 48 – 52 40 – 45

GYPROCK® THE RED BOOK™ 1 G25


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete with Suspension Grid & Resilient Mounted Furring

Floor finished bare or with materials as Minimum 182mm cavity.


per system table.
Cavity infill as per system table.
150mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system with furring channel.
Gyprock Resilient Mounts.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.
NOTE: Polyester insulation may NOT
be used where the system has
non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Floor Carpet +


FRL SYSTEM CAVITY INFILL or Tiles +
CEILING LININGS Rw/Rw+Ctr Adhesive Underlay
Report Nº (Refer to TABLE B6)
Ln,w Ln,w
CSR 6377
(a) Nil 59/49 60 – 65 40 – 45
• 1 x 10mm Gyprock Plus
(c) 75 Acoustigard 11kg 63/54 58 – 62 35 – 40
Refer to Plasterboard.
AS3600 • Furring channel at 450mm
(e) 50 Acoustigard 14kg 62/53 58 – 62 35 – 40
maximum centres.
(f) 75 MAB Polyester 11kg 62/53 58 – 62 35 – 40

CSR 6378
(a) Nil 60/50 60 – 65 40 – 45

(c) 75 Acoustigard 11kg 64/55 58 – 62 35 – 40


Refer to • 1 x 10mm Gyprock
AS3600 Supaceil Plasterboard.
(e) 50 Acoustigard 14kg 63/54 58 – 62 35 – 40

(f) 75 MAB Polyester 11kg 63/54 58 – 62 35 – 40

CSR 10178
(a) Nil 61/52 60 – 65 40 – 45

(b) 75 Acoustigard 11kg 65/57 58 – 62 35 – 40


Refer to • 1 x 10mm Gyprock HD
AS3600 Plasterboard.
(c) 75 MAB Polyester 11kg 64/56 58 – 62 35 – 40

(d) 50 Acoustigard 14kg 64/56 58 – 62 35 – 40

CSR 10179
(a) Nil 63/55 60 – 65 40 – 45

(b) 75 Acoustigard 11kg 67/60 58 – 62 35 – 40


Refer to • 2 x 10mm Gyprock HD
AS3600 Plasterboard.
(c) 75 MAB Polyester 11kg 66/59 58 – 62 35 – 40

(d) 50 Acoustigard 14kg 66/59 58 – 62 35 – 40

CSR 6388
(a) Nil 61/52 60 – 65 40 – 45

(c) 75 Acoustigard 11kg 65/57 58 – 62 35 – 40


Refer to • 1 x 13mm Gyprock
AS3600 Standard Plasterboard.
(e) 50 Acoustigard 14kg 64/56 58 – 62 35 – 40

(f) 75 MAB Polyester 11kg 64/56 58 – 62 35 – 40

CSR 6389
(a) Nil 62/53 60 – 65 40 – 45

(c) 75 Acoustigard 11kg 66/58 58 – 62 35 – 40


Refer to • 1 x 13mm Gyprock
AS3600 Soundchek Plasterboard.
(e) 50 Acoustigard 14kg 65/57 58 – 62 35 – 40

(f) 75 MAB Polyester 11kg 65/57 58 – 62 35 – 40

G26 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete with Suspension Grid & Resilient Mounted Furring

Floor finished bare or with materials as Minimum 182mm cavity.


per system table.
Cavity infill as per system table.
150mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system with furring channel.
Gyprock Resilient Mounts.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.
NOTE: Polyester insulation may NOT
be used where the system has
NOTE: RISF = Resistance to Incipient non-combustible construction
Spread of Fire requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Floor Carpet +


FRL SYSTEM CAVITY INFILL or Tiles +
CEILING LININGS Rw/Rw+Ctr Adhesive Underlay
Report Nº (Refer to TABLE B6)
Ln,w Ln,w
CSR 6391
(a) Nil 62/53 60 – 65 40 – 45
• 1 x 13mm Gyprock
30/30/30 (c) 75 Acoustigard 11kg 66/58 58 – 62 35 – 40
Fyrchek Plasterboard.
EWFA 26162 • Furring channels at
(e) 50 Acoustigard 14kg 65/57 58 – 62 35 – 40
450mm maximum centres.
(f) 75 MAB Polyester 11kg 65/57 58 – 62 35 – 40

CSR 3766
(a) Nil 62/53 60 – 65 40 – 45
• 1 x 16mm Gyprock EC08
30/30/30 (b) 75 Acoustigard 11kg 66/58 58 – 62 35 – 40
Complete.
EWFA 26162 • Furring channel at 450mm
(d) 50 Acoustigard 14kg 65/57 58 – 62 35 – 40
maximum centres.
(e) 75 MAB Polyester 11kg 65/57 58 – 62 35 – 40

CSR 6393
(a) Nil 63/55 60 – 65 40 – 45
60/60/60
+RISF 30 (c) 75 Acoustigard 11kg 67/60 58 – 62 35 – 40
• 2 x 13mm Gyprock
minutes
Fyrchek Plasterboard.
(e) 50 Acoustigard 14kg 66/59 58 – 62 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 66/59 58 – 62 35 – 40

CSR 6395
(a) Nil 63/55 60 – 65 40 – 45
60/60/60 • 1 x 13mm Gyprock
+RISF 60 Fyrchek Plasterboard. (c) 75 Acoustigard 11kg 67/60 58 – 62 35 – 40
minutes • 1 x 16mm Gyprock
Fyrchek Plasterboard (any (e) 50 Acoustigard 14kg 66/59 58 – 62 35 – 40
EWFA 26162 order).
(f) 75 MAB Polyester 11kg 66/59 58 – 62 35 – 40

CSR 3781
(a) Nil 63/55 60 – 65 40 – 45
60/60/60 • 1 x 13mm Gyprock
+RISF 60 EC08 Complete (against (c) 75 Acoustigard 11kg 67/60 58 – 62 35 – 40
minutes framing).
• 1 x 16mm Gyprock EC08 (e) 50 Acoustigard 14kg 66/59 58 – 62 35 – 40
EWFA 26162 Complete.
(f) 75 MAB Polyester 11kg 66/59 58 – 62 35 – 40

CSR 6396
(a) Nil 63/55 60 – 65 40 – 45
90/90/90
+RISF 60 (c) 75 Acoustigard 11kg 67/60 58 – 62 35 – 40
• 2 x 16mm Gyprock
minutes
Fyrchek Plasterboard.
(e) 50 Acoustigard 14kg 66/59 58 – 62 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 66/59 58 – 62 35 – 40

GYPROCK® THE RED BOOK™ 1 G27


SYSTEM SPECIFICATIONS Floor/Ceiling – Concrete with Suspension Grid & Resilient Mounted Furring

Floor finished bare or with materials as Minimum 182mm cavity.


per system table.
Cavity infill as per system table.
150mm min. concrete slab.
Ceiling lining as per system table, fixed to
Rondo Suspended Ceiling system with furring channel.
Gyprock Resilient Mounts.

Rondo Furring Channel Nº129 at 600mm


max. centres, except where noted in
system table.
NOTE: Polyester insulation may NOT
be used where the system has
NOTE: RISF = Resistance to Incipient non-combustible construction
Spread of Fire requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A123


Refer to Book 2 and 3 for further information

Bare Floor Carpet +


FRL SYSTEM CAVITY INFILL or Tiles +
CEILING LININGS Rw/Rw+Ctr Adhesive Underlay
Report Nº (Refer to TABLE B6)
Ln,w Ln,w
CSR 3785
(a) Nil 63/55 60 – 65 40 – 45
90/90/90
+RISF 60 (c) 75 Acoustigard 11kg 67/60 58 – 62 35 – 40
• 2 x 16mm Gyprock EC08
minutes
Complete.
(e) 50 Acoustigard 14kg 66/59 58 – 62 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 66/59 58 – 62 35 – 40

CSR 6398
(a) Nil 64/56 58 – 62 40 – 45
120/120/120
+RISF 60 (c) 75 Acoustigard 11kg 68/61 55 – 60 35 – 40
• 3 x 16mm Gyprock
minutes
Fyrchek Plasterboard.
(e) 50 Acoustigard 14kg 67/60 55 – 60 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 67/60 55 – 60 35 – 40

CSR 3795
(a) Nil 64/56 58 – 62 40 – 45
120/120/120
+RISF 60 (c) 75 Acoustigard 11kg 68/61 55 – 60 35 – 40
• 3 x 16mm Gyprock EC08
minutes
Complete.
(e) 50 Acoustigard 14kg 67/60 55 – 60 35 – 40
EWFA 26162
(f) 75 MAB Polyester 11kg 67/60 55 – 60 35 – 40

G28 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Joist/Truss & Direct Fixed Plasterboard

A pitched steel sheet roof minimum Ceiling Joists or Trusses at 600mm


0.42mm. centres except where noted in system
table.
Bradford Anticon 60 MD insulation
over battens. Cavity infill as per system table.

40mm battens. Ceiling lining as per system table,


fixed to framing.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


Software Version – 1.6
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof Blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS
Report Nº (Refer to TABLE B6)
Rw / Rw+Ctr Rt(SUM) Rt(WIN)
CSR 6402
(a) 165 Gold Batts 3.0 41/31 5.5 5.3
• 1 x 10mm Gyprock Plus
(b) 185 Gold Batts 3.5 41/32 5.9 5.8
Plasterboard.
–/–/–
• Framing at 450mm
(c) 215 Gold Batts 4.1 42/33 6.5 6.4
maximum centres.
(d) 110 SoundScreen 3.1 41/32 5.6 5.4

CSR 6403
(a) 165 Gold Batts 3.0 42/32 5.4 5.3

(b) 185 Gold Batts 3.5 43/33 5.9 5.8


• 1 x 10mm Gyprock
–/–/–
Supaceil Plasterboard.
(c) 215 Gold Batts 4.1 43/34 6.5 6.4

(d) 110 SoundScreen 3.1 43/33 5.5 5.4

CSR 10180
(a) 165 Gold Batts 3.0 43/33 5.4 5.3

(b) 185 Gold Batts 3.5 43/34 5.9 5.8


• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 44/35 6.5 6.4

(d) 110 SoundScreen 3.1 43/34 5.5 5.4

CSR 10181
(a) 165 Gold Batts 3.0 48/39 5.5 5.3

(b) 185 Gold Batts 3.5 48/39 6.0 5.8


• 2 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 49/40 6.5 6.5

(d) 110 SoundScreen 3.1 48/39 5.6 5.4

CSR 6420
(a) 165 Gold Batts 3.0 43/33 5.5 5.3

(b) 185 Gold Batts 3.5 43/34 5.9 5.8


• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 215 Gold Batts 4.1 44/35 6.5 6.5

(d) 110 SoundScreen 3.1 43/34 5.6 5.4

CSR 6421
(a) 165 Gold Batts 3.0 47/38 5.4 5.3

(b) 185 Gold Batts 3.5 48/39 5.9 5.8


• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 215 Gold Batts 4.1 49/40 6.5 6.4

(d) 110 SoundScreen 3.1 48/39 5.5 5.4

GYPROCK® THE RED BOOK™ 1 G29


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Joist/Truss & Direct Fixed Plasterboard

A pitched steel sheet roof minimum Ceiling Joists or Trusses at 600mm


0.42mm. centres except where noted in system
table.
Bradford Anticon 60 MD insulation
over battens. Cavity infill as per system table.

40mm battens. Ceiling lining as per system table,


fixed to framing.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


Software Version – 1.6
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof Blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS
Report Nº (Refer to TABLE B6)
Rw / Rw+Ctr Rt(SUM) Rt(WIN)
CSR 6425
(a) 165 Gold Batts 3.0 44/35 5.5 5.3
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 185 Gold Batts 3.5 45/36 6.0 5.8
• Framing at 450mm
EWFA 26162
maximum centres.
(c) 215 Gold Batts 4.1 46/38 6.5 6.5

CSR 6427
60/60/60 (a) 165 Gold Batts 3.0 49/40 5.5 5.4
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 185 Gold Batts 3.5 50/41 6.0 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 51/42 6.6 6.5

CSR 6430
60/60/60 (a) 165 Gold Batts 3.0 49/40 5.6 5.4
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 30 • 1 x 16mm Gyprock (b) 185 Gold Batts 3.5 50/41 6.0 5.9
minutes Fyrchek Plasterboard
(any order).
EWFA 26162 (c) 215 Gold Batts 4.1 51/42 6.6 6.5

CSR 6440
90/90/90 (a) 165 Gold Batts 3.0 50/41 5.6 5.4
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 51/42 6.1 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 52/43 6.6 6.6

CSR 6445
120/120/120 (a) 165 Gold Batts 3.0 52/43 5.6 5.4
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 53/44 6.1 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 54/45 6.6 6.6

G30 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Joist/Truss & Clip Fixed Furring

A pitched steel sheet roof minimum Ceiling Joists or Trusses.


0.42mm.
Cavity infill as per system table.
Bradford Anticon 60 MD insulation
over battens. Rondo Furring Channel at 600mm
maximum centres except were noted.
40mm battens.
Ceiling lining as per system table,
fixed to framing.
Thermal Assumptions – Steel Sheet Roof/Ceiling Systems
Software Version – 1.6
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof Blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS
Report Nº (Refer to TABLE B6)
Rw / Rw+Ctr Rt(SUM) Rt(WIN)
CSR 6450
(a) 165 Gold Batts 3.0 45/35 5.4 5.3

(b) 185 Gold Batts 3.5 45/36 5.9 5.8


• 1 x 6mm CeminSeal
–/–/–
Wallboard.
(c) 215 Gold Batts 4.1 46/37 6.5 6.4

(d) 110 SoundScreen 3.1 45/36 5.5 5.4

CSR 10182
(a) 165 Gold Batts 3.0 45/35 5.4 5.3

(b) 185 Gold Batts 3.5 45/36 5.9 5.8


• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 46/37 6.5 6.4

(d) 110 SoundScreen 3.1 45/36 5.5 5.4

CSR 6456
(a) 165 Gold Batts 3.0 47/38 5.5 5.3
• 2 x 10mm Gyprock Plus
(b) 185 Gold Batts 3.5 48/39 6.0 5.8
Plasterboard.
–/–/–
• Furring channel at 450mm
(c) 215 Gold Batts 4.1 49/40 6.5 6.5
maximum centres.
(d) 110 SoundScreen 3.1 48/39 5.6 5.4

CSR 10183
(a) 165 Gold Batts 3.0 49/40 5.5 5.3

(b) 185 Gold Batts 3.5 50/41 6.0 5.8


• 2 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 51/42 6.5 6.5

(d) 110 SoundScreen 3.1 50/41 5.6 5.4

CSR 6462
(a) 165 Gold Batts 3.0 45/35 5.5 5.3

(b) 185 Gold Batts 3.5 45/36 5.9 5.8


• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 215 Gold Batts 4.1 46/37 6.5 6.5

(d) 110 SoundScreen 3.1 45/36 5.6 5.4

CSR 6463
(a) 165 Gold Batts 3.0 49/40 5.4 5.3

(b) 185 Gold Batts 3.5 50/41 5.9 5.8


• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 215 Gold Batts 4.1 51/42 6.5 6.4

(d) 110 SoundScreen 3.1 50/41 5.5 5.4

GYPROCK® THE RED BOOK™ 1 G31


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Joist/Truss & Clip Fixed Furring

A pitched steel sheet roof minimum Ceiling Joists or Trusses.


0.42mm.
Cavity infill as per system table.
Bradford Anticon 60 MD insulation
over battens. Rondo Furring Channel at 600mm
maximum centres except were noted.
40mm battens.
Ceiling lining as per system table,
fixed to framing.
Thermal Assumptions – Steel Sheet Roof/Ceiling Systems
Software Version – 1.6
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof Blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS
Report Nº (Refer to TABLE B6)
Rw / Rw+Ctr Rt(SUM) Rt(WIN)
CSR 6466
(a) 165 Gold Batts 3.0 46/37 5.5 5.3
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 185 Gold Batts 3.5 47/38 6.0 5.8
• Furring channel at 450mm
EWFA 26162
maximum centres.
(c) 215 Gold Batts 4.1 48/39 6.5 6.5

CSR 6468
60/60/60 (a) 165 Gold Batts 3.0 51/42 5.5 5.4
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 185 Gold Batts 3.5 52/43 6.0 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 53/44 6.6 6.5

CSR 6470
60/60/60 (a) 165 Gold Batts 3.0 51/42 5.6 5.4
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 60 • 1 x 16mm Gyprock (b) 185 Gold Batts 3.5 52/43 6.0 5.9
minutes Fyrchek Plasterboard
(any order).
EWFA 26162 (c) 215 Gold Batts 4.1 53/44 6.6 6.5

CSR 6471
90/90/90 (a) 165 Gold Batts 3.0 52/43 5.6 5.4
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 53/44 6.1 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 54/45 6.6 6.6

CSR 6473
120/120/120 (a) 165 Gold Batts 3.0 55/46 5.6 5.4
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 56/47 6.1 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 57/48 6.6 6.6

G32 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Joist/Truss & Resilient Mounted Furring

Ceiling Joists or Trusses.


A pitched steel sheet roof minimum
0.42mm. Cavity infill as per system table.

Bradford Anticon 60 MD insulation Rondo Furring Channel clipped to


over battens. Gyprock Resilient Mounts. Furring
channels at 600mm maximum
40mm battens. centres except were noted.

Ceiling lining as per system table,


fixed to furring channel.
Thermal Assumptions – Steel Sheet Roof/Ceiling Systems
Software Version – 1.6
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof Blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS
Report Nº (Refer to TABLE B6)
Rw / Rw+Ctr Rt(SUM) Rt(WIN)
CSR 6478
(a) 165 Gold Batts 3.0 46/36 5.4 5.3

(b) 185 Gold Batts 3.5 46/37 5.9 5.8


• 1 x 10mm Gyprock
–/–/–
Supaceil Plasterboard.
(c) 215 Gold Batts 4.1 47/38 6.5 6.4

(d) 110 SoundScreen 3.1 46/37 5.5 5.4

CSR 10184
(a) 165 Gold Batts 3.0 47/37 5.4 5.3

(b) 185 Gold Batts 3.5 47/38 5.9 5.8


• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 48/39 6.5 6.4

(d) 110 SoundScreen 3.1 47/38 5.5 5.4

CSR 10185
(a) 165 Gold Batts 3.0 52/43 5.5 5.3

(b) 185 Gold Batts 3.5 53/44 6.0 5.8


• 2 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 54/45 6.5 6.5

(d) 110 SoundScreen 3.1 53/44 5.6 5.4

CSR 6484
(a) 165 Gold Batts 3.0 47/37 5.5 5.3

(b) 185 Gold Batts 3.5 47/38 5.9 5.8


• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 215 Gold Batts 4.1 48/39 6.5 6.5

(d) 110 SoundScreen 3.1 47/38 5.6 5.4

CSR 6485
(a) 165 Gold Batts 3.0 51/42 5.4 5.3

(b) 185 Gold Batts 3.5 52/43 5.9 5.8


• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 215 Gold Batts 4.1 53/44 6.5 6.4

(d) 110 SoundScreen 3.1 52/43 5.5 5.4

GYPROCK® THE RED BOOK™ 1 G33


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Joist/Truss & Resilient Mounted Furring

Ceiling Joists or Trusses.


A pitched steel sheet roof minimum
0.42mm. Cavity infill as per system table.

Bradford Anticon 60 MD insulation Rondo Furring Channel clipped to


over battens. Gyprock Resilient Mounts. Furring
channels at 600mm maximum
40mm battens. centres except were noted.

Ceiling lining as per system table,


fixed to furring channel.
Thermal Assumptions – Steel Sheet Roof/Ceiling Systems
Software Version – 1.6
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof Blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS
Report Nº (Refer to TABLE B6)
Rw / Rw+Ctr Rt(SUM) Rt(WIN)
CSR 6491
(a) 165 Gold Batts 3.0 48/39 5.5 5.3
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 185 Gold Batts 3.5 49/40 6.0 5.8
• Furring channels at
EWFA 26162
450mm maximum centres.
(c) 215 Gold Batts 4.1 50/41 6.5 6.5

CSR 6492
60/60/60 (a) 165 Gold Batts 3.0 53/44 5.5 5.4
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 185 Gold Batts 3.5 54/45 6.0 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 55/46 6.6 6.5

CSR 6493
60/60/60 (a) 165 Gold Batts 3.0 53/44 5.6 5.4
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 60 • 1 x 16mm Gyprock (b) 185 Gold Batts 3.5 54/45 6.0 5.9
minutes Fyrchek Plasterboard
(any order).
EWFA 26162 (c) 215 Gold Batts 4.1 55/46 6.6 6.5

CSR 6495
90/90/90 (a) 165 Gold Batts 3.0 54/45 5.6 5.4
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 55/46 6.1 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 56/47 6.6 6.6

CSR 6497
120/120/120 (a) 165 Gold Batts 3.0 57/48 5.6 5.4
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 58/49 6.1 5.9
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 59/50 6.6 6.6

G34 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Tile Roof with Joist/Truss & Direct Fixed Plasterboard

A pitched tile roof. Ceiling Joists or Trusses at 600mm


centres except where noted in
40mm battens. system table.

Bradford Thermoseal Roof Tile Cavity infill as per system table.


sarking as per table, installed
under battens. Ceiling lining as per system table,
fixed to framing.

Thermal Assumptions – Tile Roof/Ceiling Systems


(Software version 1.6 )
System thermal R-values provided have been
Roof Pitch – 22.5 degrees nominal
calculated based on a thermal transmission
Roof space type – non-ventilated
path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire
not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information
Tile Roofing Tile Roofing
FRL SYSTEM CAVITY INFILL with Sarking without Sarking
CEILING LININGS
Report Nº (Refer to TABLE B6) Rw/ Rw/
Rt(SUM) Rt(WIN) Rt(SUM) Rt(WIN)
Rw+Ctr Rw+Ctr
CSR 6502
(a) 165 Gold Batts 3.0 41/34 4.4 4.1 39/33 3.6 3.8
• 1 x 10mm Gyprock Plus
(b) 185 Gold Batts 3.5 41/35 4.9 4.7 39/33 4.1 4.3
Plasterboard.
–/–/–
• Framing at 450mm
(c) 215 Gold Batts 4.1 42/36 5.5 5.3 40/34 4.6 4.9
maximum centres.
(d) 110 SoundScreen 3.1 41/35 4.5 4.3 39/33 3.7 3.9

CSR 6503
(a) 165 Gold Batts 3.0 42/36 4.4 4.1 40/35 3.6 3.7

(b) 185 Gold Batts 3.5 42/37 4.9 4.7 40/35 4.1 4.3
• 1 x 10mm Gyprock
–/–/–
Supaceil Plasterboard.
(c) 215 Gold Batts 4.1 43/38 5.5 5.3 41/36 4.6 4.9

(d) 110 SoundScreen 3.1 42/37 4.5 4.2 40/35 3.7 3.8

CSR 10186
(a) 165 Gold Batts 3.0 43/37 4.4 4.1 41/36 3.6 3.7

(b) 185 Gold Batts 3.5 43/38 4.9 4.7 41/36 4.1 4.3
• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 44/39 5.5 5.3 42/37 4.6 4.9

(d) 110 SoundScreen 3.1 43/38 4.5 4.2 41/36 3.7 3.8

CSR 10187
(a) 165 Gold Batts 3.0 48/42 4.4 4.1 46/42 3.6 3.8

(b) 185 Gold Batts 3.5 48/42 4.9 4.7 46/42 4.1 4.3
• 2 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 49/43 5.5 5.3 47/43 4.6 4.9

(d) 110 SoundScreen 3.1 48/42 4.5 4.2 46/42 3.7 3.9

CSR 6513
(a) 165 Gold Batts 3.0 43/37 4.4 4.2 41/36 3.6 3.8

(b) 185 Gold Batts 3.5 43/38 4.9 4.7 41/36 4.1 4.3
• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 215 Gold Batts 4.1 44/39 5.5 5.3 42/37 4.7 4.9

(d) 110 SoundScreen 3.1 43/38 4.5 4.3 41/36 3.7 3.9

CSR 6515
(a) 165 Gold Batts 3.0 48/42 4.4 4.1 46/41 3.6 3.7

(b) 185 Gold Batts 3.5 48/43 4.9 4.7 46/42 4.1 4.3
• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 215 Gold Batts 4.1 49/44 5.5 5.3 47/43 4.6 4.9

(d) 110 SoundScreen 3.1 48/43 4.5 4.2 46/42 3.7 3.9

GYPROCK® THE RED BOOK™ 1 G35


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Tile Roof with Joist/Truss & Direct Fixed Plasterboard

A pitched tile roof. Ceiling Joists or Trusses at 600mm


centres except where noted in
40mm battens. system table.

Bradford Thermoseal Roof Tile Cavity infill as per system table.


sarking as per table, installed
under battens. Ceiling lining as per system table,
fixed to framing.

Thermal Assumptions – Tile Roof/Ceiling Systems


(Software version 1.6 )
System thermal R-values provided have been
Roof Pitch – 22.5 degrees nominal
calculated based on a thermal transmission
Roof space type – non-ventilated
path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire
not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information
Tile Roofing Tile Roofing
FRL SYSTEM CAVITY INFILL with Sarking without Sarking
CEILING LININGS
Report Nº (Refer to TABLE B6) Rw/ Rw/
Rt(SUM) Rt(WIN) Rt(SUM) Rt(WIN)
Rw+Ctr Rw+Ctr
CSR 6519
(a) 165 Gold Batts 3.0 45/39 4.4 4.2 42/38 3.6 3.8
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 185 Gold Batts 3.5 45/39 4.9 4.7 42/38 4.1 4.3
• Framing at 450mm
EWFA 26162
maximum centres.
(c) 215 Gold Batts 4.1 46/40 5.5 5.3 43/39 4.7 4.9

CSR 6520
60/60/60 (a) 165 Gold Batts 3.0 50/44 4.4 4.2 47/43 3.6 3.8
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 185 Gold Batts 3.5 50/44 4.9 4.7 47/43 4.1 4.3
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 51/45 5.5 5.3 48/44 4.7 4.9

CSR 6521
60/60/60 (a) 165 Gold Batts 3.0 50/44 4.5 4.2 47/43 3.6 3.8
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 30 • 1 x 16mm Gyprock (b) 185 Gold Batts 3.5 50/44 4.9 4.7 47/43 4.1 4.3
minutes Fyrchek Plasterboard
(any order).
EWFA 26162 (c) 215 Gold Batts 4.1 51/45 5.5 5.3 48/44 4.7 4.9

CSR 6522
90/90/90 (a) 165 Gold Batts 3.0 51/45 4.5 4.2 48/44 3.6 3.8
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 51/45 4.9 4.7 48/44 4.1 4.3
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 52/46 5.5 5.3 49/45 4.7 4.9

CSR 6523
120/120/120 (a) 165 Gold Batts 3.0 53/47 4.5 4.2 50/46 3.7 3.8
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 53/47 5.0 4.7 50/46 4.1 4.4
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 54/48 5.6 5.4 51/47 4.7 5.0

G36 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Tile Roof with Joist/Truss & Clip Fixed Furring

A pitched tile roof. Ceiling Joists or Trusses.

40mm battens. Cavity infill as per system table.

Bradford Thermoseal Roof Tile Rondo Furring Channel at 600mm


sarking as per table. maximum centres except where noted.

Ceiling lining as per system table fixed


to furring channel.

Thermal Assumptions – Tile Roof/Ceiling Systems


(Software version 1.6 )
System thermal R-values provided have been
Roof Pitch – 22.5 degrees nominal
calculated based on a thermal transmission
Roof space type – non-ventilated
path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire
not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information
Tile Roofing Tile Roofing
FRL SYSTEM CAVITY INFILL with Sarking without Sarking
CEILING LININGS
Report Nº (Refer to TABLE B6) Rw / Rw /
Rt(SUM) Rt(WIN) Rt(SUM) Rt(WIN)
Rw+Ctr Rw+Ctr
CSR 6525
(a) 165 Gold Batts 3.0 45/39 4.4 4.1 43/38 3.6 3.7

(b) 185 Gold Batts 3.5 45/40 4.9 4.6 43/38 4.0 4.2
• 1 x 6mm CeminSeal
–/–/–
Wallboard.
(c) 215 Gold Batts 4.1 46/41 5.5 5.3 44/39 4.6 4.9

(d) 110 SoundScreen 3.1 45/40 4.5 4.2 43/38 3.7 3.8

CSR 6527
(a) 165 Gold Batts 3.0 43/36 4.4 4.1 41/36 3.6 3.8
• 1 x 10mm Gyprock Plus
(b) 185 Gold Batts 3.5 43/36 4.9 4.7 41/36 4.1 4.3
Plasterboard.
–/–/–
• Furring channels at
(c) 215 Gold Batts 4.1 44/37 5.5 5.3 42/37 4.6 4.9
450mm maximum centres.
(d) 110 SoundScreen 3.1 43/36 4.5 4.3 41/36 3.7 3.9

CSR 10188
(a) 165 Gold Batts 3.0 45/39 4.4 4.1 43/38 3.6 3.7

(b) 185 Gold Batts 3.5 45/40 4.9 4.7 43/38 4.1 4.3
• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 46/41 5.5 5.3 44/39 4.6 4.9

(d) 110 SoundScreen 3.1 45/40 4.5 4.2 43/38 3.7 3.8

CSR 6533
(a) 165 Gold Batts 3.0 48/42 4.4 4.1 45/41 3.6 3.8
• 2 x 10mm Gyprock Plus
(b) 185 Gold Batts 3.5 48/42 4.9 4.7 45/41 4.1 4.3
Plasterboard.
–/–/–
• Furring channels at
(c) 215 Gold Batts 4.1 49/43 5.5 5.3 46/42 4.7 4.9
450mm maximum centres.
(d) 110 SoundScreen 3.1 48/42 4.5 4.2 45/41 3.7 3.9

CSR 10189
(a) 165 Gold Batts 3.0 50/44 4.4 4.1 48/43 3.6 3.8

(b) 185 Gold Batts 3.5 50/45 4.9 4.7 48/44 4.1 4.3
• 2 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 51/46 5.5 5.3 49/45 4.6 4.9

(d) 110 SoundScreen 3.1 50/45 4.5 4.2 48/44 3.7 3.9

CSR 6537
(a) 165 Gold Batts 3.0 45/39 4.4 4.2 43/38 3.6 3.8

(b) 185 Gold Batts 3.5 45/40 4.9 4.7 43/38 4.1 4.3
• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 215 Gold Batts 4.1 46/41 5.5 5.3 44/39 4.7 4.9

(d) 110 SoundScreen 3.1 45/40 4.5 4.3 43/38 3.7 3.9

GYPROCK® THE RED BOOK™ 1 G37


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Tile Roof with Joist/Truss & Clip Fixed Furring

A pitched tile roof. Ceiling Joists or Trusses.

40mm battens. Cavity infill as per system table.

Bradford Thermoseal Roof Tile Rondo Furring Channel at 600mm


sarking as per table. maximum centres except where noted.

Ceiling lining as per system table fixed


to furring channel.

Thermal Assumptions – Tile Roof/Ceiling Systems


(Software version 1.6 )
System thermal R-values provided have been
Roof Pitch – 22.5 degrees nominal
calculated based on a thermal transmission
Roof space type – non-ventilated
path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire
not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information
Tile Roofing Tile Roofing
FRL SYSTEM CAVITY INFILL with Sarking without Sarking
CEILING LININGS
Report Nº (Refer to TABLE B6) Rw / Rw /
Rt(SUM) Rt(WIN) Rt(SUM) Rt(WIN)
Rw+Ctr Rw+Ctr
CSR 6538
(a) 165 Gold Batts 3.0 50/44 4.4 4.1 48/43 3.6 3.7

(b) 185 Gold Batts 3.5 50/45 4.9 4.7 48/44 4.1 4.3
• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 215 Gold Batts 4.1 51/46 5.5 5.3 49/45 4.6 4.9

(d) 110 SoundScreen 3.1 50/45 4.5 4.2 48/44 3.7 3.9

CSR 6542
(a) 165 Gold Batts 3.0 47/41 4.4 4.2 44/40 3.6 3.8
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 185 Gold Batts 3.5 47/41 4.9 4.7 44/40 4.1 4.3
• Furring channels at
EWFA 26162
450mm maximum centres.
(c) 215 Gold Batts 4.1 48/42 5.5 5.3 45/41 4.7 4.9

CSR 6543
60/60/60 (a) 165 Gold Batts 3.0 52/46 4.4 4.2 49/45 3.6 3.8
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 185 Gold Batts 3.5 52/46 4.9 4.7 49/45 4.1 4.3
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 53/47 5.5 5.3 50/46 4.7 4.9

CSR 6544
60/60/60 (a) 165 Gold Batts 3.0 52/46 4.5 4.2 49/45 3.6 3.8
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 60 • 1 x 16mm Gyprock (b) 185 Gold Batts 3.5 52/46 4.9 4.7 49/45 4.1 4.3
minutes Fyrchek Plasterboard
(any order).
EWFA 26162 (c) 215 Gold Batts 4.1 53/47 5.5 5.3 50/46 4.7 4.9

CSR 6545
90/90/90 (a) 165 Gold Batts 3.0 53/47 4.5 4.2 50/46 3.6 3.8
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 54/48 4.9 4.7 50/46 4.1 4.3
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 55/49 5.5 5.3 51/47 4.7 4.9

CSR 6548
120/120/120 (a) 165 Gold Batts 3.0 56/50 4.5 4.2 53/49 3.7 3.8
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 57/50 5.0 4.7 53/49 4.1 4.4
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 58/51 5.6 5.4 54/50 4.7 5.0

G38 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Tile Roof with Joist/Truss & Resilient Mounted Furring

Ceiling Joists or Trusses.


A pitched tile roof.
Cavity infill as per system table.
40mm battens.
Rondo Furring Channel clipped to
Bradford Thermoseal Roof Tile Gyprock Resilient Mounts. Furring
sarking as per table. channels at 600mm maximum
centres except where noted.

Ceiling lining as per system table,


fixed to furring channel.
Thermal Assumptions – Tile Roof/Ceiling Systems
(Software version 1.6 )
System thermal R-values provided have been
Roof Pitch – 22.5 degrees nominal
calculated based on a thermal transmission
Roof space type – non-ventilated
path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire
not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information
Tile Roofing Tile Roofing
FRL SYSTEM CAVITY INFILL with Sarking without Sarking
CEILING LININGS
Report Nº (Refer to TABLE B6) Rw / Rw /
Rt(SUM) Rt(WIN) Rt(SUM) Rt(WIN)
Rw+Ctr Rw+Ctr
CSR 6553
(a) 165 Gold Batts 3.0 46/40 4.4 4.1 44/39 3.6 3.7

(b) 185 Gold Batts 3.5 46/41 4.9 4.7 44/39 4.1 4.3
• 1 x 10mm Gyprock
–/–/–
Supaceil Plasterboard.
(c) 215 Gold Batts 4.1 47/42 5.5 5.3 45/40 4.6 4.9

(d) 110 SoundScreen 3.1 46/41 4.5 4.2 44/39 3.7 3.9

CSR 10190
(a) 165 Gold Batts 3.0 47/41 4.4 4.1 44/40 3.6 3.7

(b) 185 Gold Batts 3.5 47/42 4.9 4.7 45/40 4.1 4.3
• 1 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 48/43 5.5 5.3 46/41 4.6 4.9

(d) 110 SoundScreen 3.1 47/42 4.5 4.2 45/40 3.7 3.8

CSR 10191
(a) 165 Gold Batts 3.0 53/47 4.4 4.1 50/46 3.6 3.8

(b) 185 Gold Batts 3.5 53/47 4.9 4.7 50/46 4.1 4.3
• 2 x 10mm Gyprock HD
–/–/–
Plasterboard.
(c) 215 Gold Batts 4.1 54/48 5.5 5.3 51/47 4.6 4.9

(d) 110 SoundScreen 3.1 53/47 4.5 4.2 50/46 3.7 3.9

CSR 6560
(a) 165 Gold Batts 3.0 47/41 4.4 4.2 44/40 3.6 3.8

(b) 185 Gold Batts 3.5 47/42 4.9 4.7 45/40 4.1 4.3
• 1 x 13mm Gyprock
–/–/–
Standard Plasterboard.
(c) 215 Gold Batts 4.1 48/43 5.5 5.3 46/41 4.7 4.9

(d) 110 SoundScreen 3.1 47/42 4.5 4.3 45/40 3.7 3.9

CSR 6561
(a) 165 Gold Batts 3.0 52/46 4.4 4.1 50/45 3.6 3.7

(b) 185 Gold Batts 3.5 52/47 4.9 4.7 50/46 4.1 4.3
• 1 x 13mm Gyprock
–/–/–
Soundchek Plasterboard.
(c) 215 Gold Batts 4.1 53/48 5.5 5.3 51/47 4.6 4.9

(d) 110 SoundScreen 3.1 52/47 4.5 4.2 50/46 3.7 3.9

CSR 6568
(a) 165 Gold Batts 3.0 49/43 4.4 4.2 46/42 3.6 3.8
30/30/30 • 1 x 13mm Gyprock
from below Fyrchek Plasterboard.
only (b) 185 Gold Batts 3.5 49/43 4.9 4.7 46/42 4.1 4.3
• Furring channels at
EWFA 26162
450mm maximum centres.
(c) 215 Gold Batts 4.1 50/44 5.5 5.3 47/43 4.7 4.9

GYPROCK® THE RED BOOK™ 1 G39


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Tile Roof with Joist/Truss & Resilient Mounted Furring

Ceiling Joists or Trusses.


A pitched tile roof.
Cavity infill as per system table.
40mm battens.
Rondo Furring Channel clipped to
Bradford Thermoseal Roof Tile Gyprock Resilient Mounts. Furring
sarking as per table. channels at 600mm maximum
centres except where noted.

Ceiling lining as per system table,


fixed to furring channel.
Thermal Assumptions – Tile Roof/Ceiling Systems
(Software version 1.6 )
System thermal R-values provided have been
Roof Pitch – 22.5 degrees nominal
calculated based on a thermal transmission
Roof space type – non-ventilated
path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire
not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124


Refer to Book 2 Residential Installation Guide for further information
Tile Roofing Tile Roofing
FRL SYSTEM CAVITY INFILL with Sarking without Sarking
CEILING LININGS
Report Nº (Refer to TABLE B6) Rw / Rw /
Rt(SUM) Rt(WIN) Rt(SUM) Rt(WIN)
Rw+Ctr Rw+Ctr
CSR 6569
60/60/60 (a) 165 Gold Batts 3.0 54/48 4.4 4.2 51/47 3.6 3.8
from below
only • 2 x 13mm Gyprock
+RISF 30 (b) 185 Gold Batts 3.5 54/48 4.9 4.7 51/47 4.1 4.3
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 55/49 5.5 5.3 52/48 4.7 4.9

CSR 6570
60/60/60 (a) 165 Gold Batts 3.0 54/48 4.5 4.2 51/47 3.6 3.8
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard.
only
+RISF 60 • 1 x 16mm Gyprock (b) 185 Gold Batts 3.5 54/48 4.9 4.7 52/47 4.1 4.3
minutes Fyrchek Plasterboard
(any order).
EWFA 26162 (c) 215 Gold Batts 4.1 55/49 5.5 5.3 53/48 4.7 4.9

CSR 6571
90/90/90 (a) 165 Gold Batts 3.0 54/49 4.5 4.2 52/48 3.6 3.8
from below
only • 2 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 55/49 4.9 4.7 52/48 4.1 4.3
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 56/50 5.5 5.3 53/49 4.7 4.9

CSR 6573
120/120/120 (a) 165 Gold Batts 3.0 57/52 4.5 4.2 55/51 3.7 3.8
from below
only • 3 x 16mm Gyprock
+RISF 60 (b) 185 Gold Batts 3.5 58/52 5.0 4.7 55/51 4.1 4.4
Fyrchek Plasterboard.
minutes

EWFA 26162 (c) 215 Gold Batts 4.1 59/53 5.6 5.4 56/52 4.7 5.0

G40 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Suspended Grid & Clip Fixed Furring

Sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD Rondo Furring Channel at 600mm


over timber or steel purlins. max. centres except where noted in
system table.
Rondo Suspended Ceiling
system. Ceiling lining as per system table,
fixed to furring channel.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


(software version 1.6 )
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 6578 (a) 140 Gold Batts 2.5 45/35 5.0 4.8

• 1 x 10mm Gyprock Plus (b) 165 Gold Batts 3.0 45/35 5.5 5.3
Plasterboard.
–/–/– (c) 185 Gold Batts 3.5 46/36 5.9 5.8
• Furring channel at 450mm
maximum centres. (d) 215 Gold Batts 4.1 46/36 6.5 6.4

(e) 110 SoundScreen 3.1 45/35 5.5 5.4


CSR 6579 (a) 140 Gold Batts 2.5 45/35 5.0 4.8

(b) 165 Gold Batts 3.0 45/35 5.4 5.3


• 1 x 10mm Gyprock
–/–/– (c) 185 Gold Batts 3.5 46/36 5.9 5.8
Supaceil Plasterboard.
(d) 215 Gold Batts 4.1 46/36 6.5 6.4

(e) 110 SoundScreen 3.1 45/35 5.5 5.4


CSR 6590
(a) 140 Gold Batts 2.5 47/38 5.0 4.8
30/30/30 • 1 x 13mm Gyprock
from below (b) 165 Gold Batts 3.0 47/38 5.5 5.3
Fyrchek Plasterboard.
only • Furring channels at
(c) 185 Gold Batts 3.5 48/39 6.0 5.8
EWFA 26162
450mm maximum centres.
(d) 215 Gold Batts 4.1 48/39 6.5 6.5

CSR 3816
30/30/30 • 1 x 16mm Gyprock EC08
from below Complete.
only (a) 140 Gold Batts 2.5 49/40 5.0 4.8
• Furring channel at 450mm
EWFA 26162
maximum centres.

CSR 6593
60/60/60 (a) 140 Gold Batts 2.5 51/43 5.1 4.9
from below
only (b) 165 Gold Batts 3.0 51/43 5.5 5.4
• 2 x 13mm Gyprock
+RISF 30 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 52/44 6.0 5.9

EWFA 26162 (d) 215 Gold Batts 4.1 52/44 6.6 6.5

CSR 6595
60/60/60 (a) 140 Gold Batts 2.5 51/43 5.1 4.9
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard. (b) 165 Gold Batts 3.0 51/43 5.6 5.4
only
+RISF 60 • 1 x 16mm Gyprock
minutes Fyrchek Plasterboard (any (c) 185 Gold Batts 3.5 52/44 6.0 5.9
order).
EWFA 26162 (d) 215 Gold Batts 4.1 52/44 6.6 6.5

GYPROCK® THE RED BOOK™ 1 G41


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Suspended Grid & Clip Fixed Furring

Sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD Rondo Furring Channel at 600mm


over timber or steel purlins. max. centres except where noted in
system table.
Rondo Suspended Ceiling
system. Ceiling lining as per system table,
fixed to furring channel.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


(software version 1.6 )
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 3831
60/60/60
from below • 1 x 13mm Gyprock
EC08 Complete (against
only
+RISF 60
framing). (a) 140 Gold Batts 2.5 53/45 5.0 4.8
minutes • 1 x 16mm Gyprock EC08
Complete.
EWFA 26162

CSR 3835
90/90/90
from below
only • 2 x 16mm Gyprock EC08
+RISF 60 (a) 140 Gold Batts 2.5 53/45 5.0 4.8
Complete.
minutes

EWFA 26162

CSR 6598
120/120/120 (a) 140 Gold Batts 2.5 53/45 5.1 4.9
from below
only (b) 165 Gold Batts 3.0 53/45 5.6 5.4
• 3 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 54/46 6.1 5.9

EWFA 26162 (d) 215 Gold Batts 4.1 54/46 6.6 6.6

CSR 3845
120/120/120
from below
only • 3 x 16mm Gyprock EC08
+RISF 60 (a) 140 Gold Batts 2.5 54/46 5.1 4.9
Complete.
minutes

EWFA 26162

G42 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Suspended Grid & Resilient Mount

Sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD Rondo Furring Channel at 600mm


over timber or steel purlins. max. centres except where noted in
system table.
Rondo Suspended Ceiling
system with Gyprock Ceiling lining as per system table,
Resilient Mounts. fixed to furring channel.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


(software version 1.6 )
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 6604 (a) 140 Gold Batts 2.5 47/37 5.0 4.8

• 1 x 10mm Gyprock Plus (b) 165 Gold Batts 3.0 47/37 5.5 5.3
Plasterboard.
–/–/– (c) 185 Gold Batts 3.5 48/38 5.9 5.8
• Furring channel at 450mm
maximum centres. (d) 215 Gold Batts 4.1 48/38 6.5 6.5

(e) 110 SoundScreen 3.1 47/37 5.6 5.4


CSR 6605 (a) 140 Gold Batts 2.5 47/37 5.0 4.8

(b) 165 Gold Batts 3.0 47/37 5.4 5.3


• 1 x 10mm Gyprock
–/–/– (c) 185 Gold Batts 3.5 48/38 5.9 5.8
Supaceil Plasterboard.
(d) 215 Gold Batts 4.1 48/38 6.5 6.4

(e) 110 SoundScreen 3.1 47/37 5.5 5.4


CSR 10192 (a) 140 Gold Batts 2.5 48/39 5.0 4.7

(b) 165 Gold Batts 3.0 48/39 5.4 5.3


• 1 x 10mm Gyprock HD
–/–/– (c) 185 Gold Batts 3.5 49/40 5.9 5.8
Plasterboard.
(d) 215 Gold Batts 4.1 49/40 6.5 6.4

(e) 110 SoundScreen 3.1 48/39 5.5 5.4


CSR 10193 (a) 140 Gold Batts 2.5 51/43 5.0 4.8

(b) 165 Gold Batts 3.0 51/43 5.5 5.3


• 2 x 10mm Gyprock HD
–/–/– (c) 185 Gold Batts 3.5 52/44 6.0 5.8
Plasterboard.
(d) 215 Gold Batts 4.1 52/44 6.5 6.5

(e) 110 SoundScreen 3.1 51/43 5.6 5.4


CSR 6612 (a) 140 Gold Batts 2.5 48/39 5.0 4.8

(b) 165 Gold Batts 3.0 48/39 5.5 5.3


• 1 x 13mm Gyprock
–/–/– (c) 185 Gold Batts 3.5 49/40 5.9 5.8
Standard Plasterboard.
(d) 215 Gold Batts 4.1 49/40 6.5 6.5

(e) 110 SoundScreen 3.1 48/39 5.6 5.4


CSR 6615 (a) 140 Gold Batts 2.5 50/41 5.0 4.8

(b) 165 Gold Batts 3.0 50/41 5.4 5.3


• 1 x 13mm Gyprock
–/–/– (c) 185 Gold Batts 3.5 51/42 5.9 5.8
Soundchek Plasterboard.
(d) 215 Gold Batts 4.1 51/42 6.5 6.4

(e) 110 SoundScreen 3.1 50/41 5.5 5.4

GYPROCK® THE RED BOOK™ 1 G43


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Suspended Grid & Resilient Mount

Sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD Rondo Furring Channel at 600mm


over timber or steel purlins. max. centres except where noted in
system table.
Rondo Suspended Ceiling
system with Gyprock Ceiling lining as per system table,
Resilient Mounts. fixed to furring channel.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


(software version 1.6 )
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 6617
(a) 140 Gold Batts 2.5 49/40 5.0 4.8
30/30/30 • 1 x 13mm Gyprock
from below (b) 165 Gold Batts 3.0 49/40 5.5 5.3
Fyrchek Plasterboard.
only • Furring channels at
(c) 185 Gold Batts 3.5 50/41 6.0 5.8
EWFA 26162
450mm maximum centres.
(d) 215 Gold Batts 4.1 50/41 6.5 6.5

CSR 3866
30/30/30 • 1 x 16mm Gyprock EC08
from below Complete.
only (a) 140 Gold Batts 2.5 51/42 5.0 4.8
• Furring channel at 450mm
EWFA 26162
maximum centres.

CSR 6619
60/60/60 (a) 140 Gold Batts 2.5 53/45 5.1 4.9
from below
only (b) 165 Gold Batts 3.0 53/45 5.5 5.4
• 2 x 13mm Gyprock
+RISF 30 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 54/46 6.0 5.9

EWFA 26162 (d) 215 Gold Batts 4.1 54/46 6.6 6.5

CSR 6620
60/60/60 (a) 140 Gold Batts 2.5 54/46 5.1 4.9
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard. (b) 165 Gold Batts 3.0 54/46 5.6 5.4
only
+RISF 60 • 1 x 16mm Gyprock
minutes Fyrchek Plasterboard (any (c) 185 Gold Batts 3.5 55/47 6.0 5.9
order).
EWFA 26162 (d) 215 Gold Batts 4.1 55/47 6.6 6.5

CSR 3881
60/60/60
from below • 1 x 13mm Gyprock
EC08 Complete (against
only
+RISF 60
framing). (a) 140 Gold Batts 2.5 55/47 5.0 4.8
minutes • 1 x 16mm Gyprock EC08
Complete.
EWFA 26162

G44 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Pitched Steel Roof with Suspended Grid & Resilient Mount

Sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD Rondo Furring Channel at 600mm


over timber or steel purlins. max. centres except where noted in
system table.
Rondo Suspended Ceiling
system with Gyprock Ceiling lining as per system table,
Resilient Mounts. fixed to furring channel.

Thermal Assumptions – Steel Sheet Roof/Ceiling Systems


(software version 1.6 )
Roof Pitch – 22.5 degrees nominal System thermal R-values provided have been
Roof Space Type – non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 6621
90/90/90 (a) 140 Gold Batts 2.5 54/46 5.1 4.9
from below
only (b) 165 Gold Batts 3.0 54/46 5.6 5.4
• 2 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 55/47 6.1 5.9

EWFA 26162 (d) 215 Gold Batts 4.1 55/47 6.6 6.6

CSR 3885
90/90/90
from below
only • 2 x 16mm Gyprock EC08
+RISF 60 (a) 140 Gold Batts 2.5 55/48 5.0 4.8
Complete.
minutes

EWFA 26162

CSR 3895
120/120/120
from below
only • 3 x 16mm Gyprock EC08
+RISF 60 (a) 140 Gold Batts 2.5 57/50 5.1 4.9
Complete.
minutes

EWFA 26162

GYPROCK® THE RED BOOK™ 1 G45


SYSTEM SPECIFICATIONS Roof/Ceiling – Low Pitched Steel Roof with Purlins & Clip Fixed Furring

Low slope sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD over purlins. Rondo Furring Channel at 600mm


max. centres except where noted in
Minimum 150mm timber system table.
or steel purlins.
Ceiling lining as per system table, fixed
to furring channel.

Thermal Assumptions – Roof/Raked Ceiling Systems


(software version 1.6 )
Roof Pitch – 10 degrees nominal System thermal R-values provided have been
Framing air space – 180mm non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 10194 (a) 140 Gold Batts 2.5 45/36 5.8 4.7

(b) 165 Gold Batts 3.0 45/36 6.3 5.2


• 1 x 10mm Gyprock HD
–/–/– (c) 185 Gold Batts 3.5 46/37 6.8 5.7
Plasterboard.
(d) 215 Gold Batts 4.1 46/37 7.4 6.4

(e) 110 SoundScreen 3.1 45/36 6.4 5.3


CSR 6636 (a) 140 Gold Batts 2.5 45/36 5.9 4.7

(b) 165 Gold Batts 3.0 45/36 6.4 5.2


• 1 x 13mm Gyprock
–/–/– (c) 185 Gold Batts 3.5 46/37 6.8 5.8
Standard Plasterboard.
(d) 215 Gold Batts 4.1 46/37 7.4 6.4

(e) 110 SoundScreen 3.1 45/36 6.4 5.3


CSR 6640
(a) 140 Gold Batts 2.5 46/37 5.9 4.7
30/30/30 • 1 x 13mm Gyprock
from below (b) 165 Gold Batts 3.0 46/37 6.4 5.2
Fyrchek Plasterboard.
only • Furring channels at
(c) 185 Gold Batts 3.5 47/38 6.8 5.8
EWFA 26162
450mm maximum centres.
(d) 215 Gold Batts 4.1 47/38 7.4 6.4

CSR 3916
30/30/30 • 1 x 16mm Gyprock EC08
from below Complete.
only (a) 140 Gold Batts 2.5 48/39 4.3 4.6
• Furring channels at
EWFA 26162
450mm maximum centres.

CSR 6643
60/60/60 (a) 140 Gold Batts 2.5 49/40 5.9 4.8
from below
only (b) 165 Gold Batts 3.0 49/40 6.4 5.3
• 2 x 13mm Gyprock
+RISF 30 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 50/41 6.9 5.8

EWFA 26162 (d) 215 Gold Batts 4.1 50/41 7.5 6.5

CSR 6644
60/60/60 (a) 140 Gold Batts 2.5 50/41 6.0 4.8
from below • 1 x 13mm Gyprock
Fyrchek Plasterboard. (b) 165 Gold Batts 3.0 50/41 6.4 5.3
only
+RISF 60 • 1 x 16mm Gyprock
minutes Fyrchek Plasterboard (any (c) 185 Gold Batts 3.5 51/42 6.9 5.9
order).
EWFA 26162 (d) 215 Gold Batts 4.1 51/42 7.5 6.5

G46 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Roof/Ceiling – Low Pitched Steel Roof with Purlins & Clip Fixed Furring

Low slope sheet metal roof. Cavity infill as per system table.

Bradford Anticon 60 MD over purlins. Rondo Furring Channel at 600mm


max. centres except where noted in
Minimum150mm timber system table.
or steel purlins.
Ceiling lining as per system table, fixed
to furring channel.

Thermal Assumptions – Roof/Raked Ceiling Systems


(software version 1.6 )
Roof Pitch – 10 degrees nominal System thermal R-values provided have been
Framing air space – 180mm non-ventilated calculated based on a thermal transmission
Roof blanket – Bradford Anticon 60 MD R1.3 path through the roof/ceiling cavity and does
RISF = Resistance to Incipient Spread of Fire not allow for the effects of thermal bridging.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A124 Thermal


Refer to Book 2 and 3 for further information

Steel Roofing with Anticon


FRL SYSTEM CAVITY INFILL
CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)
Rt(SUM) Rt(WIN)
CSR 3931
60/60/60
from below • 1 x 13mm Gyprock
EC08 Complete (against
only
+RISF 60
framing). (a) 140 Gold Batts 2.5 52/43 4.3 4.6
minutes • 1 x 16mm Gyprock EC08
Complete.
EWFA 26162

CSR 6645
90/90/90 (a) 140 Gold Batts 2.5 50/41 6.0 4.8
from below
only (b) 165 Gold Batts 3.0 50/41 6.5 5.3
• 2 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 51/42 6.9 5.9

EWFA 26162 (d) 215 Gold Batts 4.1 51/42 7.5 6.5

CSR 3935
90/90/90
from below
only • 2 x 16mm Gyprock EC08
+RISF 60 (a) 140 Gold Batts 2.5 53/45 4.3 4.6
Complete.
minutes

EWFA 26162

CSR 6648
120/120/120 (a) 140 Gold Batts 2.5 52/44 6.0 4.8
from below
only (b) 165 Gold Batts 3.0 52/44 6.5 5.3
• 3 x 16mm Gyprock
+RISF 60 Fyrchek Plasterboard.
minutes (c) 185 Gold Batts 3.5 53/45 6.9 5.9

EWFA 26162 (d) 215 Gold Batts 4.1 53/45 7.5 6.5

CSR 3945
120/120/120
from below
only • 3 x 16mm Gyprock EC08
+RISF 60 (a) 140 Gold Batts 2.5 54/46 4.3 4.7
Complete.
minutes

EWFA 26162

GYPROCK® THE RED BOOK™ 1 G47


SYSTEM SPECIFICATIONS Ceiling – Steel Joists with Direct Fixed Plasterboard – Fire Rated from Above Only

Ceiling lining as per system table, Minimum cavity depth 150mm.


fixed to framing.
Cavity infill as per system table.
Steel framing maximum 1.6mm
BMT at 600mm maximum centres. Ceiling lining as per system table,
fixed to framing.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16 & PKA – A121
Refer to Book 3 Commercial & Multi-Residential Installation Guide

FRL SYSTEM CAVITY INFILL


CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)

CSR 6705 ABOVE


• 1 x 16mm Gyprock (a) Nil 36/29
– /60/60 Fyrchek Plasterboard.
from above
BELOW
only (c) 90 Gold Batts 2.0 46/36
• 1 x 10mm Gyprock Plus
Plasterboard.
FAR 2358
• Framing at 450mm (d) 50 Acoustigard 14kg 43/34
maximum centres.
CSR 6707
– /60/60 ABOVE
from above • 2 x 16mm Gyprock
Fyrchek Plasterboard. (a) Nil 34/32
only
BELOW
FAR 2358 • Nil.

CSR 6709
– /90/90 ABOVE
from above • 3 x 13mm Gyprock
Fyrchek Plasterboard. (a) Nil 37/34
only
BELOW
FAR 2358 • Nil.

CSR 6711 ABOVE


• 2 x 16mm Gyprock
– /120/120 Fyrchek Plasterboard. (a) Nil 41/34
from above
BELOW
only
• 1 x 10mm Gyprock Plus
Plasterboard.
FAR 2358 (b) 75 Acoustigard 11kg 48/39
• Framing at 450mm
maximum centres.
CSR 6713
– /120/120 ABOVE
from above • 3 x 16mm Gyprock
Fyrchek Plasterboard. (a) Nil 37/35
only
BELOW
FAR 2358 • Nil.

G48 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Ceiling – Steel Joists with Direct Fixed Plasterboard – Fire Rated from Above & Below

Ceiling lining as per system table, Minimum cavity depth 150mm.


fixed to framing.
Cavity infill as per system table.
Steel framing maximum 1.6mm
BMT at 600mm maximum centres. Ceiling lining as per system table,
fixed to framing.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to Book 3 Commercial & Multi-Residential Installation Guide

FRL SYSTEM CAVITY INFILL


CEILING LININGS Rw / Rw+Ctr
Report Nº (Refer to TABLE B6)

CSR 6717
ABOVE
– /60/60 • 1 x 16mm Gyprock (a) Nil 39/33
from above Fyrchek Plasterboard.
and below
BELOW
FAR 2358
• 1 x 16mm Gyprock (c) 50 Acoustigard 14kg 47/39
Fyrchek Plasterboard.

CSR 6720
– /120/120 ABOVE
• 2 x 16mm Gyprock (a) Nil 47/41
from above
Fyrchek Plasterboard.
– /90/90
from below BELOW
• 2 x 16mm Gyprock (c) 50 Acoustigard 14kg 53/45
FAR 2358 Fyrchek Plasterboard.

CSR 6722
ABOVE
– /120/120 • 2 x 16mm Gyprock (a) Nil 49/43
from above Fyrchek Plasterboard.
and below
BELOW
FAR 2358
• 3 x 16mm Gyprock (c) 50 Acoustigard 14kg 55/47
Fyrchek Plasterboard.

GYPROCK® THE RED BOOK™ 1 G49


SYSTEM SPECIFICATIONS Ceiling – C–H Stud with Direct Fixed Plasterboard – Fire Rated from Above &/or Below

Shaftwall C-H studs 0.55BMT Cavity infill as per system table.


at 600mm centres.
Ceiling lining as per system
Lining to top side as per table, fixed to framing.
system table in framing.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Book 3 Commercial & Multi-Residential Installation Guide

JOIST DEPTH mm 64 102


FRL SYSTEM
CEILING LININGS
Report Nº CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 6727
ABOVE
– /60/60 • 1 x 25mm Gyprock Shaft (a) Nil 36/29 40/33
from above Liner Panel MP.
only
BELOW
FAR 2358
• 1 x 16mm Gyprock (c) 50 Acoustigard 14kg 45/36 49/40
Fyrchek Plasterboard.

CSR 6730
ABOVE
– /90/90 • 1 x 25mm Gyprock Shaft (a) Nil 40/33 45/39
from above Liner Panel MP.
and below
BELOW
FAR 2358
• 2 x 16mm Gyprock (c) 50 Acoustigard 14kg 48/39 53/45
Fyrchek Plasterboard.

CSR 6735
ABOVE
– /120/120 • 1 x 25mm Gyprock Shaft (a) Nil 43/36 47/41
from above Liner Panel MP.
and below
BELOW
FAR 2358
• 3 x 16mm Gyprock (c) 50 Acoustigard 14kg 51/42 55/47
Fyrchek Plasterboard.

G50 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Ceiling – Hebel PowerFloor on Joists – Fire Rated from Above &/or Below

Carpet and medium duty underlay. Cavity infill as per system table.

CSR Hebel PowerFloor. Rondo Furring Channel at 600mm


centres fixed to joists with fixing clips.
Timber or steel joists at 600mm
maximum centres. Ceiling lining as per system table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A071


Refer to CSR Hebel for more information.

FRL SYSTEM CAVITY INFILL


CEILING LININGS Rw / Rw+Ctr Ln,w
Report Nº (Refer to TABLE B6)

CSR 21184
90/90/90
from above

SGA 2013/277.64 • Nil (a) Nil 37/33 45

–/–/–
from below
CSR 21188
90/90/90
from above
SGA 2013/277.64
• 2 x 16mm Gyprock
(a) 90 Gold Batts 2.0 59/53 30
Fyrchek Plasterboard.
90/90/90
+RISF 60 min.
EWFA 26162

GYPROCK® THE RED BOOK™ 1 G51


SYSTEM SPECIFICATIONS Ceiling – Tile Systems for Decorative & Sound Absorption Applications

Rondo Duo™ suspended ceiling


system.
Appropriate acoustic ceiling tiles,
as per system table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: Refer to Himmel


Refer to Book 3 Commercial & Multi-Residential Installation Guide

THICKNESS SUITABLE
LIGHT
SYSTEM (mm) MASS Plenum RELATIVE
CEILING TILES & kg/m2 Height mm
CAC1 dB NRC1 REFLECTANCE
HUMIDITY
Nº (%)
MATERIAL (%)

14mm
CSR 6808 • OWA Constellation A 4.5 200 35 0.70 88 99
Mineral Fibre

15mm
CSR 6811 • OWA Finetta 4.5 200 33 0.70 88 99
Mineral Fibre

15mm
CSR 6815 • OWA New Sandila 4.2 200 33 0.70 87 99
Mineral Fibre

20mm
CSR 6816 • OWA Sinfonia Privacy 6.1 200 41 0.70 87 99
Mineral Fibre

15mm
CSR 6817 • OWA Brillianto A 3.5 200 32 0.90 78 95
Mineral Fibre

20mm
CSR 10041 • OWA Sinfonia Privacy Humancare 6.4 200 41 0.7 87 99
Mineral Fibre

20mm
CSR 10042 • OWA Sinfonia Balance 4.4 200 37 0.8 87 99
Mineral Fibre

25mm
CSR 10043 • Troldtekt Panel – Ultrafine Natural 11.4 175 N/A 0.7 55.2 98
Woodwool
25mm
CSR 10044 • dECO Ceiling Tile Polyester fibre 2.75 400 N/A 0.9 91.1 90
(PET)

NOTES:
Refer to Himmel for insulation.
1

G52 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Ceiling – Gyprock & Gyptone Perforated Plasterboard

Concrete or steel support structure.

Rondo clip fixed or suspended ceiling Cavity infill as per system table.
grid system with 65mm minimum
cavity height. Gyptone Perforated Plasterboard
as per system table.

13mm Gyprock Standard


Plasterboard border (when
required).

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A167


Refer to Book 3 Commercial & Multi-Residential Installation Guide

CAVITY
SYSTEM CAVITY INFILL

CEILING LININGS HEIGHT (Refer to TABLE B6) αw NRC
(mm)
(a) Nil 0.15 0.1
CSR 6825 • Gyprock Standard 6mm Round 65
(b) 50Acoustigard 14kg 0.3 0.35
(a) Nil 0.15 0.15
CSR 6826 • Gyprock Standard 6mm Round 200
(b) 50Acoustigard 14kg 0.25 (LM) 0.4
(a) Nil 0.15 0.15
CSR 6827 • Gyprock Standard 6mm Round 600
(b) 50Acoustigard 14kg 0.30 (LM) 0.45

(a) Nil 0.55 0.55


CSR 6828 • Gyprock Gyptone 12mm Square 65
(b) 50Acoustigard 14kg 0.7 0.7
(a) Nil 0.60 (L) 0.65
CSR 6829 • Gyprock Gyptone 12mm Square 200
(b) 50Acoustigard 14kg 0.7 0.7
(a) Nil 0.65 (L) 0.65
CSR 6830 • Gyprock Gyptone 12mm Square 600
(b) 50Acoustigard 14kg 0.7 0.7

(a) Nil 0.35 0.35


CSR 6831 • Gyprock Gyptone 12mm Square Minigrid 65
(b) 50Acoustigard 14kg 0.35 (L) 0.4
(a) Nil 0.35 (L) 0.4
CSR 6832 • Gyprock Gyptone 12mm Square Minigrid 200
(b) 50Acoustigard 14kg 0.40 (L) 0.4
(a) Nil 0.40 (L) 0.4
CSR 6833 • Gyprock Gyptone 12mm Square Minigrid 600
(b) 50Acoustigard 14kg 0.45 0.45

(a) Nil 0.45 0.45


CSR 6834 • Gyprock Gyptone Slotted Minigrid 65
(b) 50Acoustigard 14kg 0.55 (L) 0.6
(a) Nil 0.50 (L) 0.6
CSR 6835 • Gyprock Gyptone Slotted Minigrid 200
(b) 50Acoustigard 14kg 0.55 (L) 0.6
(a) Nil 0.50 (L) 0.55
CSR 6836 • Gyprock Gyptone Slotted Minigrid 600
(b) 50Acoustigard 14kg 0.60 (L) 0.6

(a) Nil 0.60 0.55


CSR 10053 • Gyprock Gyptone 12mm Hexagon 65
(b) 50Acoustigard 14kg 0.65 0.65
(a) Nil 0.60 0.60
CSR 10054 • Gyprock Gyptone 12mm Hexagon 200
(b) 50Acoustigard 14kg 0.65 0.65
(a) Nil 0.60 0.60
CSR 10055 • Gyprock Gyptone 12mm Hexagon 600
(b) 50Acoustigard 14kg 0.70 0.70

NOTES:
• (L) denotes excess performance at 250Hz.
• (M) denotes excess performance at 500Hz, 1000Hz.
• (H) denotes excess performance at 2000Hz, 4000Hz.

GYPROCK® THE RED BOOK™ 1 G53


SYSTEM SPECIFICATIONS Ceiling – Gyprock Rigitone Perforated Plasterboard

Concrete or steel support structure. Cavity infill as per system table.

Rondo suspended ceiling grid system Rigitone Perforated Plasterboard


with 150mm minimum cavity height. as per system table.

13mm Gyprock Standard


Plasterboard border (when
required).

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA – A167


Refer to Book 3 Commercial & Multi-Residential Installation Guide

CAVITY
SYSTEM CAVITY INFILL

CEILING LININGS HEIGHT (Refer to TABLE B6) αw NRC
(mm)

• Gyprock Rigitone Matrix (a) Nil 0.60 (L) 0.65


CSR 6851 200
8mm Round (b) 50Acoustigard 14kg 0.75 (L) 0.75
• Gyprock Rigitone Matrix (a) Nil 0.65 (L) 0.65
CSR 6852 600
8mm Round (b) 50Acoustigard 14kg 0.75 0.75

• Gyprock Rigitone Matrix (a) Nil 0.65 (L) 0.70


CSR 6854 200
12mm Square (b) 50Acoustigard 14kg 0.85 (L) 0.90
• Gyprock Rigitone Matrix (a) Nil 0.65 (L) 0.70
CSR 6855 600
12mm Square (b) 50Acoustigard 14kg 0.90 0.85
(a) Nil 0.55 (LM) 0.65
CSR 6857 • Gyprock Rigitone Astral 200
(b) 50Acoustigard 14kg 0.80 (L) 0.85
(a) Nil 0.65 0.65
CSR 6858 • Gyprock Rigitone Astral 600
(b) 50Acoustigard 14kg 0.80 0.80
(a) Nil 0.45 (L) 0.55
CSR 6860 • Gyprock Rigitone Galaxy 200
(b) 50Acoustigard 14kg 0.55 (L) 0.60
(a) Nil 0.60 0.60
CSR 6861 • Gyprock Rigitone Galaxy 600
(b) 50Acoustigard 14kg 0.65 0.65
(a) Nil 0.60 (LM) 0.70
CSR 10056 • Gyprock Rigitone Matrix 12mm Round 200
(b) 50Acoustigard 14kg 0.70 (LM) 0.85
(a) Nil 0.65 (L) 0.70
CSR 10057 • Gyprock Rigitone Matrix 12mm Round 600
(b) 50Acoustigard 14kg 0.80 (L) 0.90
(a) Nil 0.50 (LM) 0.65
CSR 10106 • Gyprock Rigitone Matrix 15mm Round 200
(b) 50Acoustigard 14kg 0.70 (LM) 0.90
(a) Nil 0.55 (L) 0.65
CSR 10107 • Gyprock Rigitone Matrix 15mm Round 600
(b) 50Acoustigard 14kg 0.80 (L) 0.90

Note:
• (L) denotes excess performance at 250Hz.
• (M) denotes excess performance at 500Hz, 1000Hz.
• (H) denotes excess performance at 2000Hz, 4000Hz.

G54 GYPROCK® THE RED BOOK™ 1


SERVICES
SYSTEMS
H
SECTION CONTENTS
Introduction H2
Design Considerations H2
System Selection Tables

Services in Ceiling H6
Internal Service Wall Lined
H14
One Side

Services in Ceiling with


H8
Secondary Cavity
Shaft Wall System H20

Services in Riser H10

Services in Riser with


H12
Secondary Cavity

GYPROCK® THE RED BOOK™ 1 H1


INTRODUCTION rated should be designed for a static pressure of 0.35kPa,
and that there are additional requirements for lift shafts

Gyprock Services Systems are ducts,


Seismic Loads
risers, bulkheads and ceilings that provide
protection from noise generated by building Seismic actions must be considered for building elements
services, and may also be fire rated to provide in accordance with the NCC. The loads and effects of
fire separation or protection. These services earthquakes may be determined in accordance with AS
include water supply pipes, waste and 1170.4 ‘Earthquake Actions in Australia’. The Standard
storm water pipes, electrical services, and has design procedures for houses (Class 1), and to
mechanical services such as air conditioning buildings (Classes 2 to 9) with importance levels 2, 3 or 4
ducts. as defined in the NCC.

The NCC has deemed to satisfy performance acoustic


FIRE RESISTANCE
requirements for buildings that vary depending on the Service in Riser and Service in Ceiling systems in
room use adjacent to the service. The requirements are this section have no Fire Resistance Level. Shaftwall,
Rw + Ctr = 25 to a kitchen or non-habitable room, and Laminated systems, and stud walls lined one side have
Rw + Ctr = 40 for habitable rooms other than kitchens. fire resistances as stated in the System Specification
tables. Wall system fire ratings apply in both direction
unless noted otherwise.
DESIGN For additional information on frame design and detailing,

CONSIDERATIONS including treatment at junctions, sub floor and roof


areas, cavity barriers and penetrations, refer to Book 2
Residential Installation Guide, Book 3 Commercial & Multi-
DESIGNER RESPONSIBILITY Residential Installation Guide, and GYP546 Shaft Systems
Design an Installation Guide.
It remains the responsibility of the customer (in conjunction
with their designer or engineer, when applicable) to ensure ACCEPTABLE VARIATIONS TO
that CSR’s products/systems are suitable for their chosen
FIRE SYSTEMS
application for any given project. CSR recommends
that a comprehensive assessment of the performance The Fire Resistance Level (FRL) of the systems detailed in
requirements be undertaken prior to selection, including this section will not be detrimentally affected by:
in respect of project-specific matters such as, but • The use of Fyrchek MR, Impactchek or EC08 range
not limited structural adequacy, seismic, acoustic, fire plasterboard in lieu of Fyrchek plasterboard of the
resistance/combustibility, thermal, condensation and same thickness.
weatherproofing requirements. • The use of Shaft Liner Panel MP in lieu of Shaft Liner
CSR offers online digital tools for the most updated Panel.
information, including but not limited to update of • Additional layers of plasterboard or Cemintel fibre
products/components, inclusion of new and modified cement.
systems, to meet the requirements of the National
Construction Code of Australia (NCC) and any relevant
Australian Standards.
COMBUSTIBILITY
Polyester insulation may NOT be selected where the
For the most up-to-date product & system performance
system has non-combustible construction requirements.
information, visit:
In accordance with NCC2022 Clause C2D10 [NCC2019:
CSR System Selector: https://apps.csr.com.au/
C1.9], plasterboard and fibre cement sheet may be used
systemselector/search-option
wherever a non-combustible material is required by the
CSR Thermal Calculator: https://apps.csr.com.au/ Code.
thermalcalculator
ACOUSTIC PERFORMANCE
Structural Design The acoustic transmission performance of the services
systems is dependent on the type of support framing. In
All walls must be designed for the applied loads. All wall
some systems, higher ratings can be achieved with timber
systems in this section are considered as non-loadbearing,
framing compared to light steel framing. In cavity systems,
and guidance is given for the selection of timber studs and
this does not apply.
Rondo steel studs. Note that from NCC2022 Specification
6 [NCC2019: Spec C1.8], walls of shafts that are to be fire Services systems used as bulkheads or ceilings may
incorporate downlights. The distribution of downlights in

H2 GYPROCK® THE RED BOOK™ 1


a services system is specified as the maximum number INSTALLATION
permitted in a 5m 2 area. The lights shall be evenly
distributed and no closer than 900mm apart. Where Framing
higher concentrations of lights are required, an acoustic
engineer should be consulted. Framing shown in the system layout is indicative only. The
designer should ensure that framing elements are suitable
Penetrations for downlights must be neat and tight to the for the application. For systems specified with timber
fitting. No additional sealing is required. Ensure insulation framing, linings must be fixed directly to solid timber joist
material is kept clear of fittings and that transformers are or studs of minimum dimensions 70 x 35mm that are
supported separately from the plasterboard lining. spaced at 600mm maximum centres. For all other framing
The installation of exhaust grilles and ducting may reduce construction, select services systems that are specified
the performance of the systems. The building designer for steel framing.
should contact the exhaust system manufacturer for
performance details. Steel components selection
Similarly, access panels might be required. Contact the CSR recommends steel components manufactured by
panel manufacturer for suitable products. Rondo Building Services Pty Ltd. Refer to Section C in
Lagging of pipes or ducts is specified in some services this guide and relevant Gyprock installation guides for
systems. Lagging must provide complete coverage for steel framing product information. Additional information
the full extent of the pipe or duct. on the steel components can be obtained from the Rondo
Building Services Pty Ltd, telephone 1300 367 663.
FRAMING & LINING
Framing shown in the system layout is indicative only. Others
The designer should ensure that framing elements are
suitable for the application. For systems specified with Downlights may be of any non-gimbal type with glass
timber framing, linings must be fixed directly to solid cover, suitable for a circular cut-out of up to 80mm
timber joists or studs of minimum dimension 70 x 35mm diameter. Lights weighing more than 250g must be
that are spaced at 600mm maximum centres. For all other supported separately from the plasterboard lining.
framing construction, select services systems that are Lagging is to completely cover the service duct or pipe.
specified for steel framing. Remove a 50mm wide strip of glasswool and overlap the
CSR r vinyl at joins. Tape with a quality aluminium tape.

GYPROCK® THE RED BOOK™ 1 H3


FIG H1: FLOOR/CEILING OR ROOF/CEILING WITH DOWNLIGHTS
Cavity infill
insulation

Maximum Locally remove


number of insulation
downlights as
per system
specification

FIG H2: INSULATION CLEARANCE FIG H3: TYPICAL ACOUSTIC RATED DOWNLIGHT
NOTE: For walls and ceilings, insulation must not be compressed
between the lining and any lagging or the service being protected.
75mm 25mm
Insulation

Service

lagging

H4 GYPROCK® THE RED BOOK™ 1


SELECTION OF ACOUSTIC SEPARATION SYSTEMS FOR WASTE PIPE IN CEILING
FIG H4: WALL/CEILING SYSTEMS FOR WASTE PIPE IN CEILING – WITH WALL LINED BOTH SIDES
Fill all gaps with Gyprock Wet Area Acrylic
Sealant (or Gyprock fire rated sealant UNIT A
where required) for acoustic integrity

Steel or
timber
framing

Critical
Ceiling if acoustic
required area Waste
Pipe
Select wall Unlagged Lagged
system with
required
Waste
Pipe OR Waste
Pipe OR
sound rating
from
appropriate
tables in Linings as per
other 70mm min. system
sections of specifications
this guide

Wall linings Insulation as per chosen


and insulation system table, no
as per chosen compression allowed
wall system
specifications
Linings as per
chosen system
table
600mm min.
Select services Select services Select services in
in ceiling system in ceiling system ceiling system with
with required with required secondary cavity &
sound rating sound rating steel framing with
from the tables from the tables required sound
in this section in this section rating from the
tables in this section

UNIT B UNIT B

FIG H5: WALL/CEILING SYSTEMS FOR WASTE PIPE IN CEILING – WITH WALL LINED ONE SIDE

Fill all gaps with Gyprock Wet Area Acrylic


Sealant (or Gyprock fire rated sealant UNIT A
where required) for acoustic integrity

Steel or
timber
framing

Critical
Ceiling if acoustic
required area Waste
Pipe
Select wall Unlagged Lagged
system with
required
Waste
Pipe OR Waste
Pipe OR
sound rating
from
appropriate
lined-one-side Steel or Linings as per
or Services in timber 70mm min. system
Riser tables in framing specifications
this section

Wall linings Insulation as per chosen


and insulation system table, no
as per chosen compression allowed
wall system
specifications
Linings as per
chosen system
table
600mm min.
Select services Select services Select services
in ceiling system in ceiling system in ceiling system
with required with required with required
sound rating sound rating sound rating
from the tables from the tables from the tables
in this section in this section in this section

UNIT B UNIT B

GYPROCK® THE RED BOOK™ 1 H5


SYSTEM SPECIFICATIONS Services in Ceiling with Steel Framing

Steel joists or furring channel


Pipe with Pyrotek Soundlag as per
Direct fixed lining as per system table.
system table.
Cavity Insulation as per system
table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide
DOWNLIGHTS
SYSTEM SYSTEM INSULATION PIPE
CEILING LININGS Maximum Nº Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6) LAGGING
per 5m2

(a) 75 Acoustigard 11kg • Nil 0 29/26

• 1 x 10mm
CSR 7005 Gyprock Aquachek (d) 75 Acoustigard 11kg • Soundlag 5 49/39
Plasterboard.

(e) Nil • Soundlag 5 43/33

(a) 75 Acoustigard 11kg • Nil 5 30/27

• 1 x 10mm Gyprock
CSR 10195
HD Plasterboard.

(b) 75 Acoustigard 11kg • Soundlag 5 50/40

(a) Nil • Nil 0 26/23

• 2 x 10mm Gyprock
CSR 7015
Plus Plasterboard.

(c) 75 Acoustigard 11kg • Soundlag 5 51/41

(a) 75 Acoustigard 11kg • Nil 5 29/26

• 1 x 13mm
CSR 7020 Gyprock Standard (d) Nil • Soundlag 5 44/34
Plasterboard.

(e) 75 Acoustigard 11kg • Soundlag 5 50/40

(a) Nil • Nil 0 30/27

• 1 x 13mm Gyprock
CSR 7025 Soundchek (d) Nil • Soundlag 0 51/41
Plasterboard.

(e) 75 Acoustigard 11kg • Soundlag 5 53/43

(a) Nil • Nil 0 34/31


• 2 x 16mm
CSR 7030 Gyprock Fyrchek
Plasterboard.
(c) 75 Acoustigard 11kg • Soundlag 5 54/44

H6 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Services in Ceiling with Timber Framing

Timber joists or furring channel


Pipe with Pyrotek Soundlag as per
Direct fixed lining as per system table.
system table.
Cavity Insulation as per system
table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide
DOWNLIGHTS
SYSTEM SYSTEM INSULATION PIPE
CEILING LININGS Maximum Nº Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6) LAGGING
per 5m2

(a) 75 Acoustigard 11kg • Nil 0 33/30

• 1 x 6mm CeminSeal
CSR 7055
Wallboard.

(c) 75 Acoustigard 11kg • Soundlag 5 52/42

(a) 75 Acoustigard 11kg • Nil 5 29/26

• 1 x 10mm
CSR 7060 Gyprock Aquachek (d) 75 Acoustigard 11kg • Soundlag 5 50/40
Plasterboard.

(e) Nil • Soundlag 5 44/34

(a) Nil • Nil 0 28/25

• 1 x 10mm Gyprock (b) 75 Acoustigard 11kg • Soundlag 5 52/42


CSR 10196
HD Plasterboard.

(c) Nil • Soundlag 5 46/36

(a) 75 Acoustigard 11kg • Nil 5 31/28

• 2 x 10mm Gyprock
CSR 7070
Plus Plasterboard.

(c) 75 Acoustigard 11kg • Soundlag 5 52/42

(a) 75 Acoustigard 11kg • Nil 5 31/28

• 1 x 13mm
CSR 7075 Gyprock Standard (d) 75 Acoustigard 11kg • Soundlag 5 52/42
Plasterboard.

(e) Nil • Soundlag 5 46/36

(a) Nil • Nil 0 34/31

• 2 x 16mm
CSR 7080 Gyprock Fyrchek (d) Nil • Soundlag 0 55/45
Plasterboard.

(e) 75 Acoustigard 11kg • Soundlag 5 55/45

GYPROCK® THE RED BOOK™ 1 H7


SYSTEM SPECIFICATIONS Services in Ceiling with Secondary Cavity & Steel Framing

Inner layer steel framing. Outer layer steel framing with 12mm
minimum gap to inner lining.
Inner layer linings as per system table,
direct fixed to framing to encase Cavity insulation as per system
services. table, 1200mm minimum each side
of pipe or duct.
Cavity of 70mm minimum.
Outer layer lining as per system
NOTE: Polyester insulation may NOT table, direct fixed to framing.
be used where the system has
non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide
DOWNLIGHTS
SYSTEM SYSTEM INSULATION
CEILING LININGS Maximum Nº Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6)
per 5m2

INNER LAYER
• 1 x 13mm Gyprock (c) 50 Acoustigard 14kg • Nil 47/36
Soundchek
CSR 7110 Plasterboard.
CEILING
• 1 x 10mm Gyprock Plus (d) 75 MAB Polyester 11kg • Nil 43/34
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg • Nil 51/40
• 2 x 13mm Gyprock
Fyrchek Plasterboard.
CSR 7120
CEILING
• 1 x 10mm Gyprock Plus
(d) 75 MAB Polyester 11kg • Nil 47/38
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg • Nil 55/45
• 2 x 13mm Gyprock
Fyrchek Plasterboard.
CSR 7130
CEILING
• 2x 13mm Gyprock
(d) 75 MAB Polyester 11kg • Nil 51/43
Standard Plasterboard.

H8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Services in Ceiling with Secondary Cavity & Timber Framing

Inner layer timber framing. Outer layer timber framing with


12mm minimum gap to inner lining.
Inner layer linings as per system table,
direct fixed to framing to encase Cavity insulation as per system
services. table, 1200mm minimum each side
of pipe or duct.
Cavity of 70mm minimum.
Outer layer lining as per system
NOTE: Polyester insulation may NOT table, direct fixed to framing.
be used where the system has
non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide
DOWNLIGHTS
SYSTEM SYSTEM INSULATION
CEILING LININGS Maximum Nº Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6)
per 5m2

INNER LAYER
• 1 x 13mm Gyprock (c) 50 Acoustigard 14kg • Nil 48/38
Soundchek
CSR 7160 Plasterboard.
CEILING
• 1 x 10mm Gyprock Plus (d) 75 MAB Polyester 11kg • Nil 44/36
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg • Nil 51/41
• 2 x 13mm Gyprock
Fyrchek Plasterboard.
CSR 7170
CEILING
• 1 x 10mm Gyprock Plus
(d) 75 MAB Polyester 11kg • Nil 47/39
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg • Nil 56/47
• 2 x 13mm Gyprock
Fyrchek Plasterboard.
CSR 7180
CEILING
• 2x 13mm Gyprock
(d) 75 MAB Polyester 11kg • Nil 52/45
Standard Plasterboard.

GYPROCK® THE RED BOOK™ 1 H9


SYSTEM SPECIFICATIONS Services In Riser with Steel Framing

Steel studs or angle. Pipe with Pyrotek Soundlag as per


system table.
Linings as per system table, direct fixed
to framing to encase services. Cavity insulation as per system
table.

Lining as per system table, direct


fixed to framing.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide

SYSTEM SYSTEM INSULATION


WALL LININGS Pipe Lagging Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6)

(a) 75 Acoustigard 11kg • Nil 29/26


• 1 x 10mm
CSR 7205 Gyprock Aquachek
Plasterboard.
(c) 75 Acoustigard 11kg • Soundlag 50/40

(a) 75 Acoustigard 11kg • Nil 31/28

• 1 x 10mm Gyprock
CSR 10197
HD Plasterboard.

(b) 75 Acoustigard 11kg • Soundlag 52/42

(a) 75 Acoustigard 11kg • Nil 33/30

• 1 x 13mm
CSR 7217 Gyprock Aquachek (d) Nil • Soundlag 48/38
Plasterboard.

(e) 75 Acoustigard 11kg • Soundlag 54/44

(a) 75 Acoustigard 11kg • Nil 31/28

• 1 x 13mm
CSR 7220 Gyprock Standard (d) Nil • Soundlag 46/36
Plasterboard.

(e) 75 Acoustigard 11kg • Soundlag 52/42

(a) Nil • Nil 30/27

• 1 x 13mm Gyprock
CSR 7225 Soundchek (d) Nil • Soundlag 51/41
Plasterboard.

(e) 75 Acoustigard 11kg • Soundlag 57/47

(a) Nil • Nil 34/31


• 2 x 16mm
CSR 7230 Gyprock Fyrchek
Plasterboard.
(c) 75 Acoustigard 11kg • Soundlag 61/51

H10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Services In Riser with Timber Framing

Timber studs (min. 70 x 35mm) Pipe with Pyrotek Soundlag as per


system table.
Direct fixed lining as per system table.
Cavity Insulation as per system
table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide

SYSTEM SYSTEM INSULATION


WALL LININGS Pipe Lagging Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6)

(a) 75 Acoustigard 11kg • Nil 33/30

• 1 x 6mm CeminSeal
CSR 7255
Wallboard.

(c) 75 Acoustigard 11kg • Soundlag 54/44

(a) 75 Acoustigard 11kg • Nil 31/28

• 1 x 10mm
CSR 7260 Gyprock Aquachek (d) 75 Acoustigard 11kg • Soundlag 52/42
Plasterboard.

(e) Nil • Soundlag 44/34

(a) Nil • Nil 28/25

• 1 x 10mm Gyprock
CSR 10198
HD Plasterboard.

(b) 75 Acoustigard 11kg • Soundlag 54/44

(a) Nil • Nil 28/25

• 2 x 10mm Gyprock
CSR 7270
Plus Plasterboard.

(c) 75 Acoustigard 11kg • Soundlag 55/45

(a) 75 Acoustigard 11kg • Nil 33/30

• 1 x 13mm
CSR 7275 Gyprock Standard (d) 75 Acoustigard 11kg • Soundlag 54/44
Plasterboard.

(e) Nil • Soundlag 48/38

(a) Nil • Nil 34/31


• 2 x 16mm
CSR 7280 Gyprock Fyrchek
Plasterboard.
(c) Nil • Soundlag 55/45

GYPROCK® THE RED BOOK™ 1 H11


SYSTEM SPECIFICATIONS Services In Riser with Secondary Cavity & Steel Framing

Inner layer steel framing. Outer layer steel framing with 12mm
minimum gap to inner lining.
Inner layer linings as per system table,
direct fixed to framing to encase Cavity insulation as per system
services. table.

Cavity of 70mm minimum. Outer layer lining as per system


table, direct fixed to framing.
NOTE: Polyester insulation may NOT
be used where the system has
non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide

SYSTEM SYSTEM INSULATION


WALL LININGS Rw/ Rw+Ctr
Nº IMAGE (Refer to TABLE B6)

INNER LAYER
(c) 50 Acoustigard 14kg 47/36
• 1 x 13mm Gyprock Soundchek
Plasterboard.
CSR 7310
OUTER LAYER
• 1 x 10mm Gyprock Plus
(d) 75 MAB Polyester 11kg 43/34
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg 51/40
• 2 x 13mm Gyprock Fyrchek
Plasterboard.
CSR 7320
OUTER LAYER
• 1 x 10mm Gyprock Plus
(d) 75 MAB Polyester 11kg 47/38
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg 55/45
• 2 x 13mm Gyprock Fyrchek
Plasterboard.
CSR 7330
OUTER LAYER
• 2 x 13mm Gyprock Standard
(d) 75 MAB Polyester 11kg 51/43
Plasterboard.

H12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Services In Riser with Secondary Cavity & Timber Framing

Inner layer timber framing. Outer layer timber framing with


12mm minimum gap to inner lining.
Inner layer linings as per system table,
direct fixed to framing to encase Cavity insulation as per system
services. table.

Cavity of 70mm minimum. Outer layer lining as per system


table, direct fixed to framing.
NOTE: Polyester insulation may NOT
be used where the system has
non-combustible construction
requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A125


Refer to Book 3 Commercial & Multi-Residential Installation Guide

SYSTEM SYSTEM INSULATION Rw/


WALL LININGS Rw+Ctr
Nº IMAGE (Refer to TABLE B6) Rw+Ctr

INNER LAYER
(c) 50 Acoustigard 14kg 48/38 38
• 1 x 13mm Gyprock Soundchek
Plasterboard.
CSR 7360
OUTER LAYER
• 1 x 10mm Gyprock Plus
(d) 75 MAB Polyester 11kg 44/36 36
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg 51/41 41
• 2 x 13mm Gyprock Fyrchek
Plasterboard.
CSR 7370
OUTER LAYER
• 1 x 10mm Gyprock Plus
(d) 75 MAB Polyester 11kg 47/39 39
Plasterboard.

INNER LAYER
(c) 50 Acoustigard 14kg 56/47 47
• 2 x 13mm Gyprock Fyrchek
Plasterboard.
CSR 7380
OUTER LAYER
• 2 x 13mm Gyprock Standard
(d) 75 MAB Polyester 11kg 52/45 45
Plasterboard.

GYPROCK® THE RED BOOK™ 1 H13


SYSTEM SPECIFICATIONS Internal Services Wall – Steel Frame Lined One Side

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with any BMT .

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A121


Refer to Book 3 Commercial & Multi-Residential Installation Guide

STUD DEPTH mm ALL


FRL SYSTEM STUD BMT mm ALL
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 10199

ONE SIDE ONLY


–/–/– • 1 x 10mm Gyprock HD (a) Nil 25/22
Plasterboard.

CSR 7410

ONE SIDE ONLY


–/–/– • 1 x 13mm Gyprock (a) Nil 25/22
Standard Plasterboard.

CSR 7415

ONE SIDE ONLY


–/–/– • 1 x 13mm Gyprock (a) Nil 27/24
Aquachek Plasterboard.

CSR 10077

ONE SIDE ONLY


–/–/– • 1 x 13mm Gyprock (a) Nil 30/27
Extreme Plasterboard.

CSR 3512

ONE SIDE
–/–/– • 1 x 13mm Gyprock EC08 (a) Nil 30/27
Complete.

CSR 3522

ONE SIDE
–/–/– • 1 x 16mm Gyprock EC08 (a) Nil 31/28
Complete.

H14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Internal Services Wall – Steel Frame Lined One Side

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with any BMT .

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A121


Refer to Book 3 Commercial & Multi-Residential Installation Guide

STUD DEPTH mm ALL


FRL SYSTEM STUD BMT mm ALL
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7440
– /30/30
and
ONE SIDE ONLY
30/30/30
(Fire rated from • 2 x 13mm Gyprock (a) Nil 34/31
lined side only) Fyrchek Plasterboard.

FC 12946

CSR 7445
– /30/30
and
ONE SIDE ONLY
30/30/30
(Fire rated from • 2 x 13mm Gyprock (a) Nil 34/31
lined side only) Fyrchek MR Plasterboard.

FC 12946

CSR 3532
– /30/30
30/30/30
(Fire rated from ONE SIDE
lined side only) • 2 x 13mm Gyprock EC08 (a) Nil 35/32
Complete.
FC 12946
FAS 200002

CSR 7450
– /60/60
and
ONE SIDE ONLY
60/60/60
(Fire rated from • 2 x 16mm Gyprock (a) Nil 34/31
lined side only) Fyrchek Plasterboard.

FC 12946

CSR 7455
– /60/60
and
ONE SIDE ONLY
60/60/60
(Fire rated from • 2 x 16mm Gyprock (a) Nil 35/33
lined side only) Fyrchek MR Plasterboard.

FC 12946

CSR 3542
– /60/60
60/60/60
(Fire rated from ONE SIDE
lined side only) • 2 x 16mm Gyprock EC08 (a) Nil 36/33
Complete.
FC 12946
FAS 200002

GYPROCK® THE RED BOOK™ 1 H15


SYSTEM SPECIFICATIONS Internal Services Wall – Steel Frame Lined One Side

Steel studs at 600mm maximum centres. Lining material as per system table.

NOTE: Acoustic performance valid for


studs with any BMT .

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A121


Refer to Book 3 Commercial & Multi-Residential Installation Guide

STUD DEPTH mm ALL


FRL SYSTEM STUD BMT mm ALL
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7470
– /90/90
and
ONE SIDE ONLY
90/90/90
(Fire rated from • 3 x 13mm Gyprock (a) Nil 37/34
lined side only) Fyrchek Plasterboard.

FC 12946

CSR 7475
– /90/90
and
ONE SIDE ONLY
90/90/90
(Fire rated from • 3 x 13mm Gyprock (a) Nil 37/34
lined side only) Fyrchek MR Plasterboard.

FC 12946

CSR 3552
– /90/90
90/90/90
(Fire rated from ONE SIDE
lined side only) • 3 x 13mm Gyprock EC08 (a) Nil 38/35
Complete.
FC 12946
FAS 200002

CSR 7480
– /120/120
and
ONE SIDE ONLY
120/120/120
(Fire rated from • 3 x 16mm Gyprock (a) Nil 37/35
lined side only) Fyrchek Plasterboard.

FC 12946

CSR 7485
– /120/120
and
ONE SIDE ONLY
120/120/120
(Fire rated from • 3 x 16mm Gyprock (a) Nil 38/36
lined side only) Fyrchek MR Plasterboard.

FC 12946

CSR 3562
– /120/120
120/120/120
(Fire rated from ONE SIDE
lined side only) • 3 x 16mm Gyprock EC08 (a) Nil 40/37
Complete.
FC 12946
FAS 200002

H16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Internal Services Wall – Timber Frame Lined One Side

Timber studs at 600mm maximum Lining material as per system table.


centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A121


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70
FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7505
(a) Nil 25/22
ONE SIDE ONLY
–/–/– • 1 x 10mm Gyprock
Aquachek Plasterboard.
Wall Thickness mm 80

CSR 10200
(a) Nil 26/23
ONE SIDE ONLY
–/–/– • 1 x 10mm Gyprock HD
Plasterboard.
Wall Thickness mm 80

CSR 7515
(a) Nil 26/23
ONE SIDE ONLY
–/–/– • 1 x 13mm Gyprock
Standard Plasterboard.
Wall Thickness mm 83

CSR 7520
(a) Nil 28/25
ONE SIDE ONLY
–/–/– • 1 x 13mm Gyprock
Aquachek Plasterboard.
Wall Thickness mm 83

CSR 7525
(a) Nil 30/28
ONE SIDE ONLY
–/–/– • 1 x 13mm Gyprock
Soundchek Plasterboard.
Wall Thickness mm 83

GYPROCK® THE RED BOOK™ 1 H17


SYSTEM SPECIFICATIONS Internal Services Wall – Timber Frame Lined One Side

Timber studs at 600mm maximum Lining material as per system table.


centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A121


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70
FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7530
(a) Nil 29/26
ONE SIDE ONLY
–/–/– • 1 x 13mm Gyprock
Fyrchek Plasterboard.
Wall Thickness mm 83

CSR 7535
(a) Nil 29/26
ONE SIDE ONLY
–/–/– • 1 x 13mm Gyprock
Fyrchek MR Plasterboard.
Wall Thickness mm 83

CSR 7545

– /30/30 (a) Nil 34/31


30/30/30 ONE SIDE ONLY
(Fire rated from • 2 x 13mm Gyprock
lined side only) Fyrchek Plasterboard.
FC12969 Wall Thickness mm 96

CSR 7550
– /30/30 (a) Nil 34/31
30/30/30 ONE SIDE ONLY
(Fire rated from • 2 x 13mm Gyprock
lined side only)
Fyrchek MR Plasterboard.
FC12969 Wall Thickness mm 96

CSR 7555
– /60/60 (a) Nil 34/31
60/60/60 ONE SIDE ONLY
(Fire rated from • 2 x 16mm Gyprock
lined side only)
Fyrchek Plasterboard.
FC12969 Wall Thickness mm 102

CSR 7560
– /60/60 (a) Nil 35/33
60/60/60 ONE SIDE ONLY
(Fire rated from • 2 x 16mm Gyprock
lined side only)
Fyrchek MR Plasterboard.
FC12969 Wall Thickness mm 102

H18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Internal Services Wall – Timber Frame Lined One Side

Timber studs at 600mm maximum Lining material as per system table.


centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A121


Refer to Book 2 Residential Installation Guide

STUD DEPTH mm 70
FRL SYSTEM
WALL LININGS CAVITY INFILL
Report Nº Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7570
– /90/90 (a) Nil 37/34
90/90/90 ONE SIDE ONLY
(Fire rated from • 3 x 13mm Gyprock
lined side only)
Fyrchek Plasterboard.
FC12969 Wall Thickness mm 109

CSR 7575
– /90/90 (a) Nil 37/34
90/90/90 ONE SIDE ONLY
(Fire rated from • 3 x 13mm Gyprock
lined side only)
Fyrchek MR Plasterboard.
FC12969 Wall Thickness mm 109

CSR 7580
– /120/120 (a) Nil 37/35
120/120/120 ONE SIDE ONLY
(Fire rated from • 3 x 16mm Gyprock
lined side only)
Fyrchek Plasterboard.
FC12969 Wall Thickness mm 118

CSR 7585
– /120/120 (a) Nil 38/36
120/120/120 ONE SIDE ONLY
(Fire rated from • 3 x 16mm Gyprock
lined side only)
Fyrchek MR Plasterboard.
FC12969 Wall Thickness mm 118

GYPROCK® THE RED BOOK™ 1 H19


SYSTEM SPECIFICATIONS Internal Services Wall – Shaft Wall System

Lining material as per system table. Cavity insulation as per system table.

64mm or 102mm Gyprock C-H Steel Gyprock Shaft Liner Range in C-H Stud.
Studs at 600mm maximum centres.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP546, Gyprock Shaft Wall Installation Guide for further information

STUD DEPTH mm 64 102


FRL SYSTEM STUD BMT mm 0.5 0.5
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7655 (a) Nil 36/29 40/33
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 50/41
– /60/60 Liner Panel MP. (f) 50 Acoustigard 14kg 45/36 49/40

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 50/40


• 1 x 16mm Gyprock (h) 50 MAB Polyester 11kg – 46/38
Fyrchek Plasterboard.
Wall Thickness mm 80 118
CSR 10017 (a) Nil 36/29 40/33
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 50/41
– /60/60 Liner Panel MP. (f) 50 Acoustigard 14kg 45/36 49/40

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 50/40


• 1 x 16mm Gyprock EC08 (h) 50 MAB Polyester 11kg – 46/38
Complete.
Wall Thickness mm 80 118
CSR 7660 (a) Nil 37/30 41/34
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 50/41
– /60/60 Liner Panel MP. (f) 50 Acoustigard 14kg 46/37 50/41

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 51/41


• 1 x 16mm Gyprock (h) 50 MAB Polyester 11kg – 47/39
Fyrchek MR Plasterboard.
Wall Thickness mm 80 118
CSR 7665 (a) Nil 40/33 45/39
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 54/46
– /90/90 Liner Panel MP. (f) 50 Acoustigard 14kg 48/39 53/45

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 54/45


• 2 x 13mm Gyprock (h) 50 MAB Polyester 11kg – 50/43
Fyrchek Plasterboard.
Wall Thickness mm 90 128
CSR 10018 (a) Nil 40/33 45/39
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 54/46
– /90/90 Liner Panel MP. (f) 50 Acoustigard 14kg 48/39 53/45

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 54/45


• 2 x 13mm Gyprock EC08 (h) 50 MAB Polyester 11kg – 50/43
Complete.
Wall Thickness mm 90 128
CSR 10019 (a) Nil 40/33 45/39
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 54/46
– /90/90 Liner Panel MP. (f) 50 Acoustigard 14kg 48/39 53/45

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 54/45


• 2 x 13mm Gyprock EC08 (h) 50 MAB Polyester 11kg – 50/43
Extreme.
Wall Thickness mm 90 128

H20 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Internal Services Wall – Shaft Wall System

Lining material as per system table. Cavity insulation as per system table.

64mm or 102mm Gyprock C-H Steel Gyprock Shaft Liner Range in C-H Stud.
Studs at 600mm maximum centres.

NOTE: Acoustic performance valid for


studs with BMT stated in table.
Polyester insulation may NOT be used
where the system has non-combustible
construction requirements.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA Predictor V16


Refer to GYP546, Gyprock Shaft Wall Installation Guide for further information

STUD DEPTH mm 64 102


FRL SYSTEM STUD BMT mm 0.5 0.5
WALL LININGS
Report Nº
CAVITY INFILL Rw / Rw+Ctr
(Refer to TABLE B6)
CSR 7670 (a) Nil 40/33 45/39
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 53/45
– /90/90 Liner Panel MP. (f) 50 Acoustigard 14kg 48/39 53/45

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 54/45


• 2 x 13mm Gyprock (h) 50 MAB Polyester 11kg – 50/43
Fyrchek MR Plasterboard.
Wall Thickness mm 90 128
CSR 7675 (a) Nil 40/33 45/39
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 54/46
– /120/120 Liner Panel MP. (f) 50 Acoustigard 14kg 48/39 53/45

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 54/45


• 2 x 16mm Gyprock (h) 50 MAB Polyester 11kg – 50/43
Fyrchek Plasterboard.
Wall Thickness mm 96 134
CSR 7680 (a) Nil 41/34 46/40
BETWEEN STUDS
• 1 x 25mm Gyprock Shaft (c) 75 Acoustigard 11kg – 54/46
– /120/120 Liner Panel MP. (f) 50 Acoustigard 14kg 49/40 54/46

FCO 3063 SIDE ONE (g) 70 Soundscreen 2.0 – 55/46


• 2 x 16mm Gyprock (h) 50 MAB Polyester 11kg – 51/44
Fyrchek MR Plasterboard.
Wall Thickness mm 96 134

GYPROCK® THE RED BOOK™ 1 H21


NOTES

H22 GYPROCK® THE RED BOOK™ 1


FLANKING PATH
SYSTEMS
J
SECTION CONTENTS
Introduction J2
Design Considerations J2
System Selection Tables

Flanking Via Ceiling J3

Flanking Via Floor J14

Flanking Via Wall J15

GYPROCK® THE RED BOOK™ 1 J1


INTRODUCTION FLANKING PATHS & ACOUSTIC
PERFORMANCE
This section provides detailed performance
Flanking sounds reach adjoining areas by indirect
information for the correct selection and
paths, rather than through the dividing element. The
application of flanking path treatments. components and cavities of the walls, floors and ceilings
that surround the dividing element are the main paths for
Building systems and construction methods can vary
flanking transmission. When designing for room-to-room
greatly from site to site. CSR recommends that where
performance, all flanking paths should be considered, as
acoustic performance is important, an acoustic engineer
well as the dividing element itself, which may be found in
be consulted to assess the suitability of the flanking
other sections of this guide.
system values detailed in this section.
The flanking path values in this section are a guide to
the maximum sound transmission values that would
be achieved in a laboratory test. The rating assumes
DESIGN that the dividing wall that is being flanked has an
equivalent or higher sound transmission performance
CONSIDERATIONS (Rw or Rw + Ctr) than the flanking value. Where a flanking
system has a rating higher than that of the dividing wall,
the room-to-room transmission should be taken as the
DESIGNER RESPONSIBILITY wall value.
It remains the responsibility of the customer (in conjunction Each flanking path system is represented by a typical
with their designer or engineer, when applicable) to ensure layout, and is associated with one or more options. The
that CSR’s products/systems are suitable for their chosen details show an example of the construction required,
application for any given project. CSR recommends but must be amended to suit the system specification
that a comprehensive assessment of the performance and lining. Dividing walls shown as single studs may be
requirements be undertaken prior to selection, including substituted with other construction such as staggered
in respect of project-specific matters such as, but studs, double studs and masonry walls to achieve the
not limited structural adequacy, seismic, acoustic, fire same results, and Fyrchek MR of the same thickness may
resistance/combustibility, thermal, condensation and be used in lieu of Fyrchek without reducing the acoustic
weatherproofing requirements. values.
CSR offers online digital tools for the most updated Suspended grid tile ceiling systems must have no lights
information, including but not limited to update of or penetrations within 600mm of a dividing wall, and
products/components, inclusion of new and modified plasterboard ceilings must have no acoustically untreated
systems, to meet the requirements of the National penetrations in rooms adjacent to a dividing wall.
Construction Code of Australia (NCC) and any relevant For the example shown in FIG J1, performance values are
Australian Standards. given in the tables for various options of the critical linings
For the most up-to-date product & system performance with the specified insulation.
information, visit:
CSR System Selector: https://apps.csr.com.au/
systemselector/search-option FIG J1: FLANKING PATH GUIDE
Critical lining
CSR Thermal Calculator: https://apps.csr.com.au/ chosen from
thermalcalculator flanking table
Critical
Dividing wall with flanking path
acoustic rating
Seismic Loads
Lining to
Seismic actions must be considered for building elements system
specification
in accordance with the NCC. The loads and effects of
earthquakes may be determined in accordance with AS
Critical insulation
1170.4 ‘Earthquake Actions in Australia’. The Standard as detailed in
flanking system
has design procedures for houses (Class 1), and to specification
buildings (Classes 2 to 9) with importance levels 2, 3 or 4
as defined in the NCC.

Critical lining
chosen from
flanking table

J2 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure. Steel angle to support ceiling grid.

150mm minimum cavity. Suspended steel grid ceiling system.


Structural bracing to 100mm
manufacturer's detail, insulation min Ceiling tiles as per system table.
wrapped tightly around bracing
elements 75mm Bradford Acoustigard Partition –
11kg/m3 to extent specified in system
Wall with required sound rating
to 100mm min. above ceiling. table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

EXTENT OF INSULATION
(b) 1200mm each (c)
SYSTEM Nº CEILING LININGS (a) Nil
side of the wall Entire Ceiling
Rw
CSR 8005 1 x 10mm Gyprock plasterboard tiles. 38 44 45

CSR 8009 OWA Brillianto A. 33 35 37

CSR 8016 OWA New Sandila. 35 37 39

CSR 8019 OWA Finetta. 35 37 39

CSR 8020 OWA Sinfonia Privacy. 37 41 42

CSR 8022 OWA Constellation A. 35 37 39

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

Floor or roof structure. Ceiling framing.

150mm minimum cavity. 100mm Flush jointed ceiling linings as per


min
system table.
Structural bracing to
manufacturer's detail, insulation 75mm Bradford Acoustigard Partition
wrapped tightly around bracing – 11kg/m3 to extent specified in
elements system table.

Wall with required sound rating Tape and set or cornice finish.
to 100mm min. above ceiling.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

EXTENT OF INSULATION
(b) 1200mm each (c)
SYSTEM Nº CEILING LININGS (a) Nil
side of the wall Entire Ceiling
Rw / Rw+Ctr
CSR 8030 1 x 10mm Gyprock Supaceil plasterboard. 41/32 47/38 48/39

CSR 8032 1 x 13mm Gyprock Standard plasterboard. 43/34 49/40 50/41

CSR 8034 1 x 13mm Gyprock Fyrchek plasterboard. 46/38 52/44 53/45

CSR 8036 2 x 13mm Gyprock Fyrchek plasterboard. 54/46 58/50 59/51

CSR 8038 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 55/47 59/51 60/52

CSR 8040 2 x 16mm Gyprock Fyrchek plasterboard. 55/47 59/51 60/52

GYPROCK® THE RED BOOK™ 1 J3


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure. Fix wall track to ceiling to project


requirements.
150mm minimum cavity.
Suspended steel grid ceiling system.
75mm Bradford Acoustigard Partition –
11kg/m3 to extent specified in system Continuous bead of Gyprock approved
table. acoustic sealant or a closed cell foam
tape above wall track.
Wall with required sound rating to
underside of ceiling, with required Ceiling tile system as per table
structural bracing. continuous over wall.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

EXTENT OF INSULATION
(b) 1200mm each (c)
SYSTEM Nº CEILING LININGS (a) Nil
side of the wall Entire Ceiling
Rw
CSR 8055 1 x 10mm Gyprock plasterboard tile. 35 40 42

CSR 8056 OWA Brillianto A. 31 34 37

CSR 8062 OWA New Sandila. 33 36 39

CSR 8065 OWA Finetta. 33 36 39

CSR 8066 OWA Sinfonia Privacy. 34 39 41

CSR 8067 OWA Constellation A. 33 36 39

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

Floor or roof structure. Fix wall track to ceiling to project


requirements.
150mm minimum cavity.
Flush jointed ceiling linings as per
Wall with required sound system table continuous over wall.
rating to underside of ceiling,
with required structural 75mm Bradford Acoustigard Partition
bracing. – 11kg/m3 to extent specified in
system table.

Tape and set or cornice finish.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

EXTENT OF INSULATION
(b) 1200mm each (c)
SYSTEM Nº CEILING LININGS (a) Nil
side of the wall Entire Ceiling
Rw
CSR 8080 1 x 10mm Gyprock Supaceil plasterboard. 37 42 42

CSR 8082 1 x 13mm Gyprock Standard plasterboard. 39 45 45

CSR 8084 2 x 13mm Gyprock Fyrchek plasterboard. 47 48 50

CSR 8086 1 x 16mm Gyprock Fyrchek plasterboard. 43 48 50

CSR 8088 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 47 48 50

CSR 8090 2 x 16mm Gyprock Fyrchek plasterboard. 48 48 50

J4 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure. Fix wall track to ceiling to project


requirements.
150mm minimum cavity.
600mm Suspended steel grid ceiling system.
75mm Bradford Acoustigard
Partition – 11kg/m3 x 600mm Continuous bead of Gyprock approved
width, centred over wall and acoustic sealant or a closed cell foam
compressed by 30%. tape above wall track.

Wall with required sound Ceiling tile system as per table


rating to underside of ceiling, continuous over wall.
with required structural
bracing.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8105 1 x 10mm Gyprock plasterboard tile. 45

CSR 8106 OWA Brillianto A. 40

CSR 8116 OWA New Sandila. 42

CSR 8119 OWA Finetta. 42

CSR 8120 OWA Sinfonia Privacy. 43

CSR 8121 OWA Constellation A. 42

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

600mm
Floor or roof structure. Fix wall track to ceiling to project
requirements.
150mm minimum cavity.
Flush jointed ceiling linings as per
Wall with required sound system table continuous over wall.
rating to underside of ceiling,
with required structural 50mm Bradford Acoustigard Partition
bracing. – 14kg/m3 x 600mm width, centred
over wall and compressed by 30%.

Tape and set or cornice finish.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8130 1 x 10mm Gyprock Supaceil plasterboard. 50

CSR 8132 1 x 13mm Gyprock Standard plasterboard. 50

CSR 8134 2 x 13mm Gyprock Fyrchek plasterboard. 50

CSR 8136 1 x 16mm Gyprock Fyrchek plasterboard. 50

CSR 8138 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 50

CSR 8140 2 x 16mm Gyprock Fyrchek plasterboard. 50

GYPROCK® THE RED BOOK™ 1 J5


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure.


Fix wall track to ceiling to project
150mm minimum cavity. requirements.

13mm Gyprock Standard Suspended steel grid ceiling system.


plasterboard minimum, continuous
over wall and fixed to soffit. Continuous bead of Gyprock approved
acoustic sealant or a closed cell foam
75mm Bradford Acoustigard tape above wall track.
Partition – 11kg/m3 continuous
over wall, compressed and held in Ceiling tile system as per table
place with track or angle. continuous over wall.

Wall with required sound rating to Finish bead as required.


underside of ceiling.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8155 1 x 10mm Gyprock plasterboard tile. 48

CSR 8156 OWA Brillianto A. 43

CSR 8166 OWA New Sandila. 45

CSR 8169 OWA Finetta. 45

CSR 8170 OWA Sinfonia Privacy. 46

CSR 8171 OWA Constellation A. 45

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

Floor or roof structure.

150mm minimum cavity.

13mm Gyprock Standard


plasterboard minimum, continuous Ceiling framing.
over wall and fixed to soffit.
Flush jointed ceiling linings as per system
75mm Bradford Acoustigard table continuous over wall.
Partition – 11kg/m3 continuous
over wall, compressed and held in Tape and set or cornice finish.
place with track or angle.
Fix wall track to ceiling to project
requirements.

Wall with required sound rating to


underside of ceiling.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8180 1 x 10mm Gyprock Supaceil plasterboard. 50

CSR 8182 1 x 13mm Gyprock Standard plasterboard. 50

CSR 8184 2 x 13mm Gyprock Fyrchek plasterboard. 50

CSR 8186 1 x 16mm Gyprock Fyrchek plasterboard. 50

CSR 8188 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 50

CSR 8190 2 x 16mm Gyprock Fyrchek plasterboard. 50

J6 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure.


Fix wall track to ceiling to project
150mm minimum cavity. requirements.

Pyrotek Wavebar® (4.0kg/m2) Suspended steel grid ceiling system.


300mm min.
continuous over wall and fixed to
soffit Continuous bead of Gyprock approved
600mm min. acoustic sealant or a closed cell foam
50mm Bradford Acoustigard tape above wall track.
Partition – 14kg/m3 x 600mm
min. width, continuous over wall. Ceiling tile system as per table
continuous over wall.
Wall with required sound rating to
underside of ceiling. Finish bead as required.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8205 1 x 10mm Gyprock plasterboard tile. 48

CSR 8206 OWA Brillianto A. 43

CSR 8216 OWA New Sandila. 45

CSR 8219 OWA Finetta. 45

CSR 8220 OWA Sinfonia Privacy. 46

CSR 8221 OWA Constellation A. 45

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

Floor or roof structure.

150mm minimum cavity.

Pyrotek Wavebar® (4.0kg/m2) 300mm min. Ceiling framing.


continuous over wall and fixed to
soffit Flush jointed ceiling linings as per system
600mm min.
table continuous over wall.
50mm Bradford Acoustigard
Partition – 14kg/m3 x 600mm Tape and set or cornice finish.
min. width, continuous over wall.
Fix wall track to ceiling to project
requirements.

Wall with required sound rating to


underside of ceiling.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw / Rw+Ctr


CSR 8230 1 x 10mm Gyprock Supaceil plasterboard. 50/40

CSR 8232 1 x 13mm Gyprock Standard plasterboard. 50/40

CSR 8234 2 x 13mm Gyprock Fyrchek plasterboard. 50/42

CSR 8236 1 x 16mm Gyprock Fyrchek plasterboard. 50/41

CSR 8238 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 50/42

CSR 8240 2 x 16mm Gyprock Fyrchek plasterboard. 50/42

GYPROCK® THE RED BOOK™ 1 J7


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure. Steel angle to support ceiling grid.

Wall with required sound Suspended steel grid ceiling system.


rating.
Ceiling tiles as per system table.

50mm Bradford Acoustigard Partition –


14kg/m3 to 1200mm min. each side of
wall.

Finish bead as required.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8255 1 x 10mm Gyprock plasterboard tile. 48

CSR 8256 OWA Brillianto A. 43

CSR 8266 OWA New Sandila. 45

CSR 8269 OWA Finetta. 45

CSR 8270 OWA Sinfonia Privacy. 46

CSR 8271 OWA Constellation A. 45

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

Floor or roof structure.


Ceiling framing.
Wall with required sound
rating. Flush jointed ceiling linings as per
system table.

50mm Bradford Acoustigard Partition


– 14kg/m3 to 1200mm min. each side
of wall.

Tape and set, cornice finish or


shadowline bead.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CEILING LININGS Rw


CSR 8280 1 x 10mm Gyprock Supaceil plasterboard. 50

CSR 10201 1 x 10mm Gyprock HD plasterboard. 52

CSR 8288 1 x 13mm Gyprock Standard plasterboard. 52

CSR 8292 1 x 13mm Gyprock Soundchek plasterboard. 55

J8 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Suspended Grid Tile Ceiling – Over Stud Wall

Floor or roof structure. Steel angle to support ceiling grid.

Wall with required sound Suspended steel grid ceiling system.


rating.
Ceiling tiles as per system table.

50mm Bradford Acoustigard Partition –


14kg/m3 to the extent specified in the
table.

Finish bead as required.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

EXTENT OF INSULATION
(b) 1200mm each (c)
SYSTEM Nº CEILING LININGS (a) Nil
side of the wall Entire Ceiling
Rw
CSR 8273 1 x 10mm Gyprock plasterboard tile. 35 39 41

CSR 8274 OWA Brillianto A. 30 34 37

CSR 8276 OWA New Sandila. 33 35 38

CSR 8277 OWA Finetta. 33 35 38

CSR 8278 OWA Sinfonia Privacy. 34 38 40

CSR 8279 OWA Constellation A. 33 36 39

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Stud Wall

Floor or roof structure.


Ceiling framing.
Wall with required sound
rating. Flush jointed ceiling linings as per
system table.

50mm Bradford Acoustigard Partition


– 14kg/m3 to the extent specified in
the table.

Tape and set, cornice finish or


shadowline bead.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

EXTENT OF INSULATION
(b) 1200mm each (c)
SYSTEM Nº CEILING LININGS (a) Nil
side of the wall Entire Ceiling
Rw
CSR 8293 1 x 10mm Gyprock Supaceil plasterboard. 37 41 41

CSR 8295 2 x 13mm Gyprock Fyrchek plasterboard. 47 47 49

CSR 8296 1 x 16mm Gyprock Fyrchek plasterboard. 43 47 49

CSR 8297 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 47 47 49

CSR 8298 2 x 16mm Gyprock Fyrchek plasterboard. 48 47 49

GYPROCK® THE RED BOOK™ 1 J9


SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Party Wall

Roof structure with sheet metal or


tile roofing and 500mm minimum
average cavity height.

Bradford 90mm Gold Batts R2.5


to entire ceiling area.

Upper Ceiling – 1 x 13mm +


1 x 16mm Gyprock Fyrchek
plasterboard.

Cavity 150mm minimum height. 50mm Bradford Acoustigard


Partition – 14kg/m3 to entire
ceiling area.

Lower Ceiling – Lining as per


system table.

Tape and set or cornice finish.

Wall with required sound rating, to


underside of upper ceiling.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº LOWER CEILING LININGS Rw / Rw+Ctr


CSR 8305 1 x 10mm Gyprock Supaceil plasterboard. 65/53

CSR 10202 1 x 10mm Gyprock HD plasterboard. 66/54

CSR 8313 1 x 13mm Gyprock Standard plasterboard. 66/54

CSR 8317 1 x 13mm Gyprock Soundchek plasterboard. 67/55

J10 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Wall

Roof structure with sheet metal or


tile roofing and 500mm minimum
average cavity height.

Insulation for entire ceiling area,


refer to table.

40mm min.cavity height. Furring channel (Rondo 129,


28mm) fixed with clips to ceiling
joists.

Ceiling lining as per system table.

Tape and set or cornice finish.

Wall with required sound rating.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126


CAVITY INFILL
SYSTEM Nº CEILING LININGS Rw / Rw+Ctr
(Refer to TABLE B6)

(a) 50 GW Acoustigard 14kg 46/38

CSR 8331 1 x 10mm Gyprock Supaceil plasterboard. (b) 90 Gold Batts 2.5 47/39

(c) 165 Gold Batts 3.0 47/39

(a) 50 GW Acoustigard 14kg 50/42

CSR 10203 1 x 10mm Gyprock HD plasterboard. (b) 90 Gold Batts 2.5 51/43

(c) 165 Gold Batts 3.0 51/43

(a) 50 GW Acoustigard 14kg 50/42

CSR 8335 1 x 13mm Gyprock Standard plasterboard. (b) 90 Gold Batts 2.5 51/43

(c) 165 Gold Batts 3.0 51/43

(a) 50 GW Acoustigard 14kg 51/43

CSR 8337 1 x 13mm Gyprock Fyrchek plasterboard. (b) 90 Gold Batts 2.5 53/45

(c) 165 Gold Batts 3.0 53/45

(a) 50 GW Acoustigard 14kg 57/49

CSR 8339 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. (b) 90 Gold Batts 2.5 59/51

(c) 165 Gold Batts 3.0 59/51

GYPROCK® THE RED BOOK™ 1 J11


SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Party Wall

Roof structure with sheet


metal or tile roofing.
Bradford Fireseal insulation
200mm minimum average continuous and compressed
cavity height. between battens and masonry
wall.
Insulation for entire ceiling
area, refer to table. Ceiling lining as per system
table fixed to framing. (No
acoustically untreated lights,
vents or similar penetrations).

Wall with required sound


rating. Masonry wall 110mm
min. thickness, extending to
underside of roof battens.

Tape and set or cornice finish.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126


CAVITY INFILL
SYSTEM Nº CEILING LININGS Rw / Rw+Ctr
(Refer to TABLE B6)

(a) 50 GW Acoustigard 14kg 63/53

CSR 8356 1 x 10mm Gyprock Plus plasterboard. (b) 90 Gold Batts 2.5 65/55

(c) 165 Gold Batts 3.0 65/55

(a) 50 GW Acoustigard 14kg 63/53

CSR 8361 1 x 10mm Gyprock Supaceil plasterboard. (b) 90 Gold Batts 2.5 65/55

(c) 165 Gold Batts 3.0 65/55

SYSTEM SPECIFICATIONS Flanking Path via Concrete Soffit – Over Stud Wall

Deflection Head Track


fastened at 600mm centres
max.

Concrete soffit with thickness 20mm clearance to stud and


as per system table. Gyprock plasterboard.

100mm max. to first fastener Gaps filled with Gyprock


(Do not fix through track). Sealant for acoustic integrity.

Gyprock plasterboard.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CONCRETE SOFFIT THICKNESS Rw / Rw+Ctr


CSR 8380 100mm 55/50

CSR 8382 125mm 55/52

CSR 8384 150mm 56/53

CSR 8386 175mm 57/54

CSR 8388 200mm 58/55

CSR 8390 225mm 58/56

CSR 8392 250mm 58/56

J12 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Party Wall

Bradford Fireseal insulation


Roof structure with (300mm min. width)
non-combustible roofing. continuous and compressed
between battens over party
250mm minimum wall.
cavity height.
Ceiling lining as per system
Bradford 75mm Gold Batts table fixed to framing.
R2.0 1200mm min. on both
sides of the wall. Tape and set or cornice finish.

Gyprock Party Wall system


with required sound rating.
Central barrier extending to
underside of roof battens.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126


CAVITY INFILL
SYSTEM Nº CEILING LININGS Rw / Rw+Ctr
(Refer to TABLE B6)

(a) 50 GW Acoustigard 14kg 61/49

(b) 75 Gold Batts 2.0 62/50


CSR 8406 1 x 10mm Gyprock Plus plasterboard.
(c) 75 GW Acoustigard 11kg 62/50

(d) 165 Gold Batts 3.0 63/51

(a) 50 GW Acoustigard 14kg 61/49

(b) 75 Gold Batts 2.0 62/50


CSR 8411 1 x 10mm Gyprock Supaceil plasterboard.
(c) 75 GW Acoustigard 11kg 62/50

(d) 165 Gold Batts 3.0 63/51

SYSTEM SPECIFICATIONS Flanking Path via Flush Jointed Ceiling – Over Party Wall

Gyprock wall system with


required sound rating.

Continuously fill gap with


appropriate Gyprock sealant.

Timber framed floor/ceiling.


Gyprock plasterboard ceiling
Bradford 75mm Gold Batts as per system table, direct
R2.0 to entire ceiling area. fixed to joists or to
furring/battens.
Gyprock wall system with
required sound rating. Continuously fill gap with
appropriate Gyprock sealant.

Tape and set or cornice finish.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

CEILING PLASTERBOARD FIXING SYSTEM


(a) DIRECT FIXED TO (b) DIRECT FIXED TO
SYSTEM Nº CEILING LININGS
TRUSS OR JOIST FURRING OR BATTEN
Rw / Rw+Ctr
CSR 8430 1 x 13mm Gyprock Standard plasterboard. 53/47 53/47

CSR 8432 2 x 13mm Gyprock Fyrchek plasterboard. 57/51 57/51

CSR 8434 1 x 13mm + 1 x 16mm Gyprock Fyrchek plasterboard. 58/52 58/52

CSR 8436 1 x 16mm Gyprock Fyrchek plasterboard. 55/49 55/49

CSR 8438 2 x 16mm Gyprock Fyrchek plasterboard. 58/52 58/52

GYPROCK® THE RED BOOK™ 1 J13


SYSTEM SPECIFICATIONS Flanking Path via Timber Floor – Under Single Stud Wall

Gyprock single stud wall system


with required sound rating.

Continuously fill gap with


appropriate Gyprock sealant. Continuously fill gap with
appropriate Gyprock sealant.
Timber framed floor with
separate joists and Seal skirting with 3mm
discontinuous flooring. polyethylene tape.

Discontinuous flooring.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº FLOOR SHEETING Rw / Rw+Ctr


CSR 8455 Particleboard Flooring. 48/42

CSR 8460 15mm Cemintel Compressed Sheet. 50/44

CSR 8465 18mm Cemintel Compressed Sheet. 50/45

CSR 8470 19mm Cemintel Constructafloor Sheet. 50/46

SYSTEM SPECIFICATIONS Flanking Path via Timber Floor – Under Double Stud Wall

Gyprock double stud wall system


with required sound rating.

Continuously fill gap with


appropriate Gyprock sealant. Continuously fill gap with
appropriate Gyprock sealant.
Timber framed floor with common
joists. Continuous flooring.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº FLOOR SHEETING Rw / Rw+Ctr


CSR 8480 Particleboard Flooring. 45/39

CSR 8485 15mm Cemintel Compressed Sheet. 47/41

CSR 8490 18mm Cemintel Compressed Sheet. 47/41

CSR 8495 19mm Cemintel Constructafloor Sheet. 47/41

J14 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Concrete Floor – Under Single Stud Wall

Gyprock single stud wall


system with required sound
rating. Gyprock plasterboard.

Stud bottomed in track. Continuously fill gap with


appropriate Gyprock sealant.
Concrete slab floor with
thickness as per system table. 10mm max. gap at bottom of
sheet

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº CONCRETE SLAB THICKNESS Rw / Rw+Ctr


CSR 8505 100mm 55/50

CSR 8507 125mm 55/52

CSR 8509 150mm 56/53

CSR 8511 175mm 57/54

CSR 8513 200mm 58/55

CSR 8515 225mm 58/56

CSR 8517 250mm 58/56

SYSTEM SPECIFICATIONS Flanking Path via Wall – Double Stud to Single Stud Wall Junction

Timber or steel stud continuous


wall system with 75mm Bradford
Gold Batts R2.0
Fix end studs at 500mm
maximum vertical centres.
Gyprock plasterboard lining to
flanking path side, as per system
table.

Intersecting stud wall system,


with required sound rating.

Tape and
set corners

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº WALL LININGS Rw / Rw+Ctr

CSR 10204 2 x 10mm Gyprock HD plasterboard. 50/45

CSR 8532 1 x 13mm Gyprock Soundchek plasterboard. 50/45

CSR 8534 2 x 13mm Gyprock Standard plasterboard. 50/45

CSR 8536 1 x 13mm Gyprock Fyrchek plasterboard. 50/45

CSR 8538 1 x 16mm Gyprock Fyrchek plasterboard. 50/45

GYPROCK® THE RED BOOK™ 1 J15


SYSTEM SPECIFICATIONS Flanking Path via Wall – Staggered Stud to Staggered Stud Wall Junction

Timber or steel stud continuous


wall system with 75mm Bradford
Gold Batts R2.0
Steel Angle (75 x 75 x 0.7mm
BMT) fixed to stud with
Gyprock plasterboard lining to
panhead screw at 600mm
flanking path side, as per system
max. cts.
table.

Intersecting stud wall system,


with required sound rating.

Gyprock Staggered Studs and


Staggered Stud Clips.

Tape and set corners.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº WALL LININGS Rw / Rw+Ctr

CSR 10205 2 x 10mm Gyprock HD plasterboard. 54/46

CSR 8557 1 x 13mm Gyprock Soundchek plasterboard. 54/46

CSR 8559 2 x 13mm Gyprock Standard plasterboard. 53/45

CSR 8561 1 x 13mm Gyprock Fyrchek plasterboard. 53/45

CSR 8563 1 x 16mm Gyprock Fyrchek plasterboard. 54/46

SYSTEM SPECIFICATIONS Flanking Path via Wall – Stud and Masonry Wall to Stud Wall Junction

Timber or steel stud wall


system with 75mm Bradford
Gold Batts R2.0
Fix end stud at 500mm
maximum vertical centres.
Gyprock plasterboard lining to
flanking path side, as per
Caulk gaps with
system table.
appropriate Gyprock
sealant.
Intersecting wall system of
masonry and separate stud
Fix end stud to masonry at
framing, with required sound
500mm maximum vertical
rating.
centres.
Tape and set corners.
Continuous bead of
sealant.

10mm nom. gap from


masonry to lining.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº WALL LININGS Rw / Rw+Ctr


CSR 8580 1 x 10mm Gyprock Plus plasterboard. 50/42

CSR 10206 1 x 10mm Gyprock HD plasterboard. 51/43

CSR 8584 1 x 13mm Gyprock Soundchek plasterboard. 54/46

CSR 8586 1 x 13mm Gyprock Fyrchek plasterboard. 53/45

CSR 8588 1 x 16mm Gyprock Fyrchek plasterboard. 54/46

J16 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Wall – Double Stud Wall to Single Stud Wall Junction

Timber or steel stud continuous


wall system with 75mm Bradford
Acoustigard 11kg/m3.
Fix end studs at 500mm
maximum vertical centres.
Gyprock plasterboard lining to
flanking path side, as per system
Fill gaps with appropriate
table.
Gyprock Sealant.
Intersecting stud wall system,
with required sound rating.

Tape and set corners.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº WALL LININGS Rw / Rw+Ctr

CSR 10207 2 x 10mm Gyprock HD plasterboard. 58/50

CSR 8607 1 x 13mm Gyprock Soundchek plasterboard. 58/50

CSR 8609 2 x 13mm Gyprock Standard plasterboard. 58/50

CSR 8611 1 x 13mm Gyprock Fyrchek plasterboard. 58/50

CSR 8613 1 x 16mm Gyprock Fyrchek plasterboard. 58/50

SYSTEM SPECIFICATIONS Flanking Path via Wall – Staggered Stud Wall to Masonry Wall Junction

Continuous masonry wall, with


mass as per system table.

Finish corners as required.


Intersecting stud wall system,
with required sound rating. Gyprock fire rated sealant to
depth of first layer (minimum).
Gyprock Staggered Studs and Fix wall track to masonry wall
Staggered Stud Clips. at 600mm maximum vertical
centres.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº MASONRY WALL MASS Rw / Rw+Ctr


CSR 8630 90kg/m2 53/48

CSR 8632 150kg/m2 55/50

CSR 8634 200kg/m2 56/51

GYPROCK® THE RED BOOK™ 1 J17


SYSTEM SPECIFICATIONS Flanking Path via Wall – Single Stud Wall to Masonry & Stud Wall Junction

External masonry veneer and


continuous stud wall system
with 75mm Bradford Gold
6mm Cemintel Wallboard
Batts R2.0
barrier full height of wall
and fixed to stud.
Plasterboard lining to flanking
path side, as per system
Dampcourse.
table.

Intersecting stud wall system,


with required sound rating.

Tape and set corners.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

BARRIER
(b) 6mm Cemintel
SYSTEM Nº WALL LININGS (a) Nil
Wallboard
Rw / Rw+Ctr
CSR 8655 1 x 10mm Gyprock Supaceil plasterboard. 39/30 59/50

CSR 10208 1 x 10mm Gyprock HD plasterboard. 41/32 60/51

CSR 8659 1 x 13mm Gyprock Soundchek plasterboard. 45/37 60/52

CSR 8661 1 x 13mm Gyprock Fyrchek plasterboard. 43/35 60/52

CSR 8663 1 x 16mm Gyprock Fyrchek plasterboard. 45/37 60/52

SYSTEM SPECIFICATIONS Flanking Path via Wall – Blade Wall Junction

Concrete Blade wall encasement


system. Wall linings as per system table.

75mm Bradford Acoustigard


Partition – 11kg/m3.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº WALL LININGS Rw / Rw+Ctr


CSR 10209 2 x 10mm Gyprock HD plasterboard. 58/50

CSR 8682 1 x 13mm Gyprock Soundchek plasterboard. 58/50

CSR 8684 2 x 13mm Gyprock Standard plasterboard. 58/50

CSR 8686 1 x 13mm Gyprock Fyrchek plasterboard. 58/50

CSR 8688 1 x 16mm Gyprock Fyrchek plasterboard. 58/50

J18 GYPROCK® THE RED BOOK™ 1


SYSTEM SPECIFICATIONS Flanking Path via Wall – Party Wall to Quiet Stud Wall

Gyprock Party Wall or Quiet Stud wall system with


StrataWall System. 75mm Bradford Acoustigard
11kg/m3.
Gyprock plasterboard lining to
flanking path side, as per system
table.

SYSTEM SPECIFICATION ACOUSTIC REPORT: PKA-A126

SYSTEM Nº WALL LININGS Rw / Rw+Ctr

CSR 10210 2 x 10mm Gyprock HD plasterboard. 58/50

CSR 8707 1 x 13mm Gyprock Soundchek plasterboard. 58/50

CSR 8709 2 x 13mm Gyprock Standard plasterboard. 58/50

CSR 8711 1 x 13mm Gyprock Fyrchek plasterboard. 58/50

CSR 8713 1 x 16mm Gyprock Fyrchek plasterboard. 58/50

GYPROCK® THE RED BOOK™ 1 J19


NOTES

J20 GYPROCK® THE RED BOOK™ 1


INDEX OF
SYSTEM NUMBERS
IN
SECTION CONTENTS
Section C – Steel Framed Wall Systems������������������ IN2
Section D – Timber Framed Wall Systems ��������������� IN3
Section E – Concrete and Masonry Wall Systems������� IN4
Section F – External Wall Systems������������������������� IN5
Section G – Ceiling Systems������������������������������� IN6
Section H – Services Systems����������������������������� IN7
Section J – Flanking Path Systems ����������������������� IN7
Health & Safety, Warranty & Contact Details������������� IN8

GYPROCK® THE RED BOOK™ 1 IN1


INDEX – TO PAGES FOR 2023 SYSTEM Nº
Section C – Steel Framed Wall Systems

System Page System Page System Page System Page System Page System Page
Nº Nº Nº Nº Nº Nº Nº Nº Nº Nº Nº Nº
CSR 1000 C8 CSR 1061 C13 CSR 10007 C20 CSR 3162 C27 CSR 1356 C34 CSR 3312 C42
CSR 1002 C8 CSR 1062 C14 CSR 10031 C20 CSR 10010 C27 CSR 1357 C34 CSR 10014 C42
CSR 1005 C8 CSR 3033 C14 CSR 3082 C21 CSR 1260 C27 CSR 3242 C34 CSR 3332 C42
CSR 1008 C8 CSR 10004 C14 CSR 10008 C21 CSR 1264 C28 CSR 10013 C34 CSR 10250 C43
CSR 1009 C8 CSR 1065 C14 CSR 1133 C21 CSR 1275 C28 CSR 1360 C35 CSR 10251 C43
CSR 1011 C8 CSR 1066 C14 CSR 1135 C21 CSR 1280 C28 CSR 1361 C35 CSR 10252 C43
CSR 10138 C9 CSR 1067 C14 CSR 3073 C21 CSR 1281 C28 CSR 1362 C35 CSR 10253 C43
CSR 10139 C9 CSR 3034 C15 CSR 1140 C21 CSR 1282 C28 CSR 3260 C35 CSR 10254 C43
CSR 10140 C9 CSR 1070 C15 CSR 1142 C22 CSR 1285 C29 CSR 1382 C36 CSR 10255 C43
CSR 1025 C9 CSR 1071 C15 CSR 10034 C22 CSR 1286 C29 CSR 1383 C36 CSR 10256 C44
CSR 1027 C9 CSR 1072 C15 CSR 3095 C22 CSR 1287 C29 CSR 10022 C36 CSR 10257 C44
CSR 1030 C9 CSR 1075 C15 CSR 1160 C23 CSR 3172 C29 CSR 10023 C36 CSR 10258 C44
CSR 1032 C10 CSR 1078 C16 CSR 1161 C23 CSR 10011 C29 CSR 10024 C36 CSR 10259 C44
CSR 1033 C10 CSR 1079 C16 CSR 1162 C23 CSR 1290 C30 CSR 10028 C37 CSR 10260 C44
CSR 1035 C10 CSR 1080 C16 CSR 1165 C23 CSR 1291 C30 CSR 1385 C37 CSR 1700 C45
CSR 1037 C10 CSR 3043 C16 CSR 1166 C23 CSR 1292 C30 CSR 1386 C37 CSR 1710 C45
CSR 1040 C10 CSR 10005 C16 CSR 1167 C24 CSR 10029 C31 CSR 1387 C37 CSR 1720 C45
CSR 1042 C10 CSR 1085 C17 CSR 3132 C24 CSR 10030 C31 CSR 3270 C37 CSR 10095 C46
CSR 1044 C11 CSR 1086 C17 CSR 10009 C24 CSR 1305 C31 CSR 10025 C38 CSR 10096 C46
CSR 1045 C11 CSR 1087 C17 CSR 1175 C24 CSR 1306 C31 CSR 10026 C38 CSR 10400 C46
CSR 1048 C11 CSR 3044 C17 CSR 1176 C24 CSR 1307 C31 CSR 10027 C38 CSR 10097 C46
CSR 3006 C11 CSR 1105 C18 CSR 1177 C24 CSR 1320 C31 CSR 1390 C39 CSR 10098 C46
CSR 10000 C11 CSR 1108 C18 CSR 10141 C25 CSR 1321 C32 CSR 1391 C39 CSR 10401 C46
CSR 3011 C11 CSR 1110 C18 CSR 10142 C25 CSR 1322 C32 CSR 1392 C39 CSR 10099 C47
CSR 10001 C12 CSR 1120 C18 CSR 10143 C25 CSR 3222 C32 CSR 1502 C40 CSR 10100 C47
CSR 1050 C12 CSR 1125 C19 CSR 1220 C25 CSR 10012 C32 CSR 10144 C40 CSR 10402 C47
CSR 1051 C12 CSR 1126 C19 CSR 1223 C25 CSR 1330 C32 CSR 1507 C40 CSR 10101 C47
CSR 1052 C12 CSR 1127 C19 CSR 1224 C26 CSR 1333 C32 CSR 1510 C40 CSR 10102 C47
CSR 1055 C12 CSR 10037 C19 CSR 1225 C26 CSR 1340 C33 CSR 1516 C40 CSR 10403 C47
CSR 3017 C12 CSR 3062 C19 CSR 1226 C26 CSR 1341 C33 CSR 1523 C40 CSR 10103 C48
CSR 10002 C13 CSR 10006 C19 CSR 1227 C26 CSR 1342 C33 CSR 1524 C41 CSR 10104 C48
CSR 3023 C13 CSR 1128 C20 CSR 1230 C26 CSR 3232 C33 CSR 1525 C41
CSR 10003 C13 CSR 1129 C20 CSR 1250 C27 CSR 1345 C33 CSR 1530 C41
CSR 1058 C13 CSR 1130 C20 CSR 1251 C27 CSR 1348 C33 CSR 1535 C41
CSR 1060 C13 CSR 3072 C20 CSR 1252 C27 CSR 1355 C34 CSR 1540 C41

IN2 GYPROCK® THE RED BOOK™ 1


Section D – Timber Framed Wall Systems

System Page System Page System Page System Page System Page System Page
Nº Nº Nº Nº Nº Nº Nº Nº Nº Nº Nº Nº
CSR 2000 D6 CSR 2065 D9 CSR 2151 D13 CSR 2242 D17 CSR 2331 D21 CSR 2394 D24
CSR 2007 D6 CSR 2067 D9 CSR 2152 D13 CSR 2245 D17 CSR 2332 D21 CSR 2402 D25
CSR 2009 D6 CSR 2070 D10 CSR 2160 D13 CSR 2255 D17 CSR 2336 D21 CSR 2459 D25
CSR 2011 D6 CSR 2071 D10 CSR 2161 D14 CSR 2256 D17 CSR 2340 D21 CSR 10154 D25
CSR 2017 D6 CSR 2072 D10 CSR 2162 D14 CSR 2257 D18 CSR 2350 D22 CSR 2415 D25
CSR 10145 D6 CSR 2075 D10 CSR 2170 D14 CSR 2265 D18 CSR 2355 D22 CSR 2421 D25
CSR 10146 D7 CSR 2080 D10 CSR 2171 D14 CSR 2266 D18 CSR 2356 D22 CSR 10038 D25
CSR 2026 D7 CSR 2090 D11 CSR 2172 D14 CSR 2275 D18 CSR 2357 D22 CSR 10039 D26
CSR 10147 D7 CSR 2091 D11 CSR 2200 D15 CSR 2276 D18 CSR 2360 D22 CSR 2441 D26
CSR 2040 D7 CSR 2092 D11 CSR 2202 D15 CSR 2277 D19 CSR 2365 D22 CSR 2443 D26
CSR 2042 D7 CSR 2095 D11 CSR 2205 D15 CSR 2285 D19 CSR 2367 D23 CSR 2445 D26
CSR 2045 D7 CSR 2096 D11 CSR 10151 D15 CSR 2286 D19 CSR 2368 D23 CSR 2450 D26
CSR 2047 D8 CSR 2097 D11 CSR 10152 D15 CSR 2287 D19 CSR 2375 D23 CSR 2455 D27
CSR 2049 D8 CSR 10148 D12 CSR 10153 D15 CSR 2300 D20 CSR 2376 D23 CSR 3372 D27
CSR 2053 D8 CSR 2110 D12 CSR 2220 D16 CSR 2302 D20 CSR 2377 D23 CSR 10016 D27
CSR 2055 D8 CSR 10149 D12 CSR 2225 D16 CSR 2310 D20 CSR 2385 D23
CSR 2059 D8 CSR 10150 D12 CSR 2226 D16 CSR 2312 D20 CSR 2386 D24
CSR 2060 D9 CSR 2130 D12 CSR 2227 D16 CSR 2314 D20 CSR 2387 D24
CSR 2061 D9 CSR 2135 D13 CSR 2240 D17 CSR 2316 D20 CSR 2392 D24
CSR 2062 D9 CSR 2150 D13 CSR 2241 D17 CSR 2330 D21 CSR 2393 D24

GYPROCK® THE RED BOOK™ 1 IN3


Section E – Concrete and Masonry Wall Systems
2023 Page 2023 Page 2023 Page 2023 Page 2023 Page 2023 Page
System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº
CSR 4005 E6 CSR 4135 E10 CSR 4255 E14 CSR 4292 E18 CSR 4432 E22 CSR 37503 E26
CSR 4010 E6 CSR 4140 E10 CSR 4260 E14 CSR 4293 E18 CSR 4433 E22 CSR 4850 E27
CSR 4015 E6 CSR 4145 E10 CSR 4265 E14 CSR 4294 E18 CSR 10073 E22 CSR 4852 E27
CSR 4020 E6 CSR 4150 E10 CSR 4270 E14 CSR 4295 E18 CSR 4437 E22 CSR 4854 E27
CSR 4025 E6 CSR 4155 E10 CSR 4275 E14 CSR 4400 E19 CSR 4438 E22 CSR 4856 E27
CSR 4030 E7 CSR 4160 E10 CSR 4259 E15 CSR 4401 E19 CSR 4439 E22 CSR 4858 E27
CSR 4035 E7 CSR 4165 E11 CSR 4264 E15 CSR 10058 E19 CSR 21070 E23 CSR 4859 E28
CSR 4040 E7 CSR 4170 E11 CSR 10049 E15 CSR 4405 E19 CSR 21072 E23 CSR 4860 E28
CSR 4045 E7 CSR 4175 E11 CSR 4269 E15 CSR 4406 E19 CSR 21245 E24 CSR 4862 E28
CSR 4050 E7 CSR 4180 E11 CSR 4274 E15 CSR 4407 E19 CSR 21246 E24 CSR 4864 E28
CSR 4055 E8 CSR 4185 E11 CSR 4276 E16 CSR 4412 E20 CSR 21269 E24 CSR 4866 E28
CSR 4060 E8 CSR 4190 E11 CSR 4277 E16 CSR 4413 E20 CSR 21270 E24 CSR 4870 E29
CSR 4065 E8 CSR 4205 E12 CSR 4278 E16 CSR 10063 E20 CSR 21251 E24 CSR 4872 E29
CSR 4070 E8 CSR 4210 E12 CSR 10050 E16 CSR 4415 E20 CSR 21252 E24 CSR 4874 E29
CSR 4075 E8 CSR 4215 E12 CSR 10051 E16 CSR 4418 E20 CSR 21275 E24 CSR 4876 E30
CSR 4080 E8 CSR 4220 E12 CSR 10052 E16 CSR 4419 E20 CSR 21276 E24 CSR 4878 E30
CSR 4105 E9 CSR 4225 E13 CSR 4280 E17 CSR 4422 E21 CSR 36001 E25 CSR 4880 E30
CSR 4110 E9 CSR 4230 E13 CSR 4281 E17 CSR 4423 E21 CSR 38001 E25 CSR 4882 E30
CSR 4115 E9 CSR 4235 E13 CSR 4282 E17 CSR 10068 E21 CSR 39001 E25 CSR 4884 E30
CSR 4120 E9 CSR 4240 E13 CSR 4283 E17 CSR 4427 E21 CSR 36101 E26 CSR 4886 E30
CSR 4125 E9 CSR 4245 E13 CSR 4290 E18 CSR 4428 E21 CSR 37101 E26
CSR 4130 E9 CSR 4250 E14 CSR 4291 E18 CSR 4429 E21 CSR 37302 E26

IN4 GYPROCK® THE RED BOOK™ 1


Section F – External Wall Systems
2023 Page 2023 Page 2023 Page 2023 Page 2023 Page 2023 Page
System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº
CSR 5010 F7 CSR 5360 F15 CSR 5703 F24 CSR 21728 F32 CSR 10213 F47 CSR 10292 F56
CSR 10087 F7 CSR 5365 F15 CSR 5706 F24 CSR 21730 F32 CSR 10214 F47 CSR 10293 F56
CSR 10088 F7 CSR 5368 F15 CSR 5709 F24 CSR 21347 F33 CSR 10215 F47 CSR 10294 F56
CSR 10089 F7 CSR 5371 F15 CSR 5710 F24 CSR 21536 F33 CSR 10216 F48 CSR 10295 F56
CSR 10090 F7 CSR 5380 F16 CSR 5711 F24 CSR 21537 F33 CSR 10217 F48 CSR 10300 F57
CSR 5030 F8 CSR 5385 F16 CSR 10162 F25 CSR 21538 F33 CSR 10218 F48 CSR 10301 F57
CSR 10091 F8 CSR 5390 F16 CSR 5716 F25 CSR 10108 F38 CSR 10219 F48 CSR 10302 F57
CSR 10092 F8 CSR 5403 F17 CSR 5718 F25 CSR 10109 F38 CSR 10220 F48 CSR 10303 F57
CSR 10093 F8 CSR 5405 F17 CSR 5721 F25 CSR 10110 F38 CSR 10221 F49 CSR 10304 F57
CSR 10094 F8 CSR 10157 F17 CSR 5722 F25 CSR 10111 F38 CSR 10222 F49 CSR 10305 F57
CSR 5152 F9 CSR 5410 F17 CSR 5724 F25 CSR 10112 F38 CSR 10223 F49 CSR 10310 F58
CSR 5160 F9 CSR 5415 F17 CSR 5828 F26 CSR 10113 F39 CSR 10224 F49 CSR 10311 F58
CSR 5161 F9 CSR 5420 F17 CSR 5832 F26 CSR 10114 F39 CSR 10225 F49 CSR 10312 F58
CSR 5163 F9 CSR 5502 F18 CSR 5835 F26 CSR 10115 F39 CSR 10226 F50 CSR 10313 F58
CSR 10155 F9 CSR 5505 F18 CSR 5837 F26 CSR 10116 F39 CSR 10227 F50 CSR 10314 F58
CSR 5168 F10 CSR 5510 F18 CSR 5839 F26 CSR 10117 F39 CSR 10228 F50 CSR 10315 F58
CSR 5170 F10 CSR 5512 F19 CSR 10163 F27 CSR 10118 F41 CSR 10229 F50 CSR 10320 F59
CSR 5172 F10 CSR 10158 F19 CSR 5844 F27 CSR 10119 F41 CSR 10230 F50 CSR 10321 F59
CSR 5173 F10 CSR 5520 F19 CSR 5848 F27 CSR 10120 F41 CSR 10231 F51 CSR 10322 F59
CSR 5174 F10 CSR 5527 F19 CSR 5851 F28 CSR 10121 F41 CSR 10232 F51 CSR 10323 F59
CSR 5302 F11 CSR 5603 F20 CSR 5854 F28 CSR 10122 F41 CSR 10233 F51 CSR 10324 F59
CSR 5303 F11 CSR 5605 F20 CSR 5857 F28 CSR 10123 F42 CSR 10234 F51 CSR 10325 F59
CSR 5305 F11 CSR 5608 F20 CSR 5860 F28 CSR 10124 F42 CSR 10235 F51 CSR 10330 F60
CSR 5308 F11 CSR 5613 F20 CSR 5862 F28 CSR 10125 F42 CSR 10236 F52 CSR 10331 F60
CSR 5315 F11 CSR 10159 F20 CSR 5865 F29 CSR 10126 F42 CSR 10237 F52 CSR 10332 F60
CSR 10156 F12 CSR 5618 F21 CSR 5868 F29 CSR 10127 F42 CSR 10238 F52 CSR 10333 F60
CSR 5320 F12 CSR 5623 F21 CSR 5870 F29 CSR 10128 F44 CSR 10239 F52 CSR 10334 F60
CSR 5321 F12 CSR 10160 F22 CSR 5872 F29 CSR 10129 F44 CSR 10240 F53 CSR 10335 F60
CSR 5324 F12 CSR 5915 F22 CSR 5874 F29 CSR 10130 F44 CSR 10241 F53 CSR 10340 F61
CSR 5327 F13 CSR 5920 F22 CSR 5877 F30 CSR 10131 F44 CSR 10242 F53 CSR 10341 F61
CSR 5332 F13 CSR 5925 F22 CSR 5879 F30 CSR 10132 F44 CSR 10243 F53 CSR 10342 F61
CSR 5340 F13 CSR 5930 F22 CSR 10164 F30 CSR 10133 F45 CSR 10244 F53 CSR 10343 F61
CSR 5342 F13 CSR 10161 F23 CSR 10165 F30 CSR 10134 F45 CSR 10245 F54 CSR 10344 F61
CSR 5343 F13 CSR 5940 F23 CSR 5885 F30 CSR 10135 F45 CSR 10246 F54 CSR 10345 F61
CSR 5345 F14 CSR 5945 F23 CSR 5888 F31 CSR 10136 F45 CSR 10247 F54
CSR 5346 F14 CSR 5950 F23 CSR 5891 F31 CSR 10137 F45 CSR 10248 F54
CSR 5347 F14 CSR 5951 F23 CSR 5893 F31 CSR 10211 F47 CSR 10290 F56
CSR 5349 F14 CSR 10280 F24 CSR 21727 F32 CSR 10212 F47 CSR 10291 F56

GYPROCK® THE RED BOOK™ 1 IN5


Section G – Ceiling Systems
2023 Page 2023 Page 2023 Page 2023 Page 2023 Page 2023 Page
System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº
CSR 6001 G6 CSR 6271 G14 CSR 3714 G23 CSR 6463 G31 CSR 6569 G40 CSR 6720 G49
CSR 10166 G6 CSR 6273 G14 CSR 6367 G23 CSR 6466 G32 CSR 6570 G40 CSR 6722 G49
CSR 10167 G6 CSR 6303 G15 CSR 6370 G23 CSR 6468 G32 CSR 6571 G40 CSR 6727 G50
CSR 6015 G6 CSR 6304 G15 CSR 3731 G23 CSR 6470 G32 CSR 6573 G40 CSR 6730 G50
CSR 6018 G6 CSR 10172 G15 CSR 6371 G23 CSR 6471 G32 CSR 6578 G41 CSR 6735 G50
CSR 6025 G7 CSR 10173 G15 CSR 3735 G24 CSR 6473 G32 CSR 6579 G41 CSR 21184 G51
CSR 6026 G7 CSR 6311 G15 CSR 6373 G24 CSR 6478 G33 CSR 6590 G41 CSR 21188 G51
CSR 6031 G7 CSR 6312 G15 CSR 3745 G24 CSR 10184 G33 CSR 3816 G41 CSR 6808 G52
CSR 6132 G7 CSR 6315 G16 CSR 6935 G25 CSR 10185 G33 CSR 6593 G41 CSR 6811 G52
CSR 6134 G7 CSR 3614 G16 CSR 6940 G25 CSR 6484 G33 CSR 6595 G41 CSR 6815 G52
CSR 6140 G7 CSR 6318 G16 CSR 6945 G25 CSR 6485 G33 CSR 3831 G42 CSR 6816 G52
CSR 6150 G8 CSR 6321 G16 CSR 6951 G25 CSR 6491 G34 CSR 3835 G42 CSR 6817 G52
CSR 6151 G8 CSR 3631 G16 CSR 3718 G25 CSR 6492 G34 CSR 6598 G42 CSR 10041 G52
CSR 6153 G8 CSR 6322 G16 CSR 6955 G25 CSR 6493 G34 CSR 3845 G42 CSR 10042 G52
CSR 10168 G8 CSR 3635 G17 CSR 6377 G26 CSR 6495 G34 CSR 6604 G43 CSR 10043 G52
CSR 6170 G8 CSR 6324 G17 CSR 6378 G26 CSR 6497 G34 CSR 6605 G43 CSR 10044 G52
CSR 6173 G8 CSR 3645 G17 CSR 10178 G26 CSR 6502 G35 CSR 10192 G43 CSR 6825 G53
CSR 6180 G9 CSR 6905 G18 CSR 10179 G26 CSR 6503 G35 CSR 10193 G43 CSR 6826 G53
CSR 6183 G9 CSR 6910 G18 CSR 6388 G26 CSR 10186 G35 CSR 6612 G43 CSR 6827 G53
CSR 6187 G9 CSR 6915 G18 CSR 6389 G26 CSR 10187 G35 CSR 6615 G43 CSR 6828 G53
CSR 6190 G9 CSR 6921 G18 CSR 6391 G27 CSR 6513 G35 CSR 6617 G44 CSR 6829 G53
CSR 6193 G9 CSR 3618 G18 CSR 3766 G27 CSR 6515 G35 CSR 3866 G44 CSR 6830 G53
CSR 6196 G9 CSR 6925 G18 CSR 6393 G27 CSR 6519 G36 CSR 6619 G44 CSR 6831 G53
CSR 10169 G10 CSR 6327 G19 CSR 6395 G27 CSR 6520 G36 CSR 6620 G44 CSR 6832 G53
CSR 10170 G10 CSR 6328 G19 CSR 3781 G27 CSR 6521 G36 CSR 3881 G44 CSR 6833 G53
CSR 6209 G10 CSR 10174 G19 CSR 6396 G27 CSR 6522 G36 CSR 6621 G45 CSR 6834 G53
CSR 6215 G10 CSR 10175 G19 CSR 3785 G28 CSR 6523 G36 CSR 3885 G45 CSR 6835 G53
CSR 6217 G10 CSR 6338 G19 CSR 6398 G28 CSR 6525 G37 CSR 3895 G45 CSR 6836 G53
CSR 6219 G10 CSR 6339 G19 CSR 3795 G28 CSR 6527 G37 CSR 10194 G46 CSR 10053 G53
CSR 6221 G11 CSR 6343 G20 CSR 6402 G29 CSR 10188 G37 CSR 6636 G46 CSR 10054 G53
CSR 6222 G11 CSR 3666 G20 CSR 6403 G29 CSR 6533 G37 CSR 6640 G46 CSR 10055 G53
CSR 6223 G11 CSR 6344 G20 CSR 10180 G29 CSR 10189 G37 CSR 3916 G46 CSR 6851 G54
CSR 10171 G12 CSR 6345 G20 CSR 10181 G29 CSR 6537 G37 CSR 6643 G46 CSR 6852 G54
CSR 6231 G12 CSR 3681 G20 CSR 6420 G29 CSR 6538 G38 CSR 6644 G46 CSR 6854 G54
CSR 6232 G12 CSR 6346 G20 CSR 6421 G29 CSR 6542 G38 CSR 3931 G47 CSR 6855 G54
CSR 6233 G12 CSR 3685 G21 CSR 6425 G30 CSR 6543 G38 CSR 6645 G47 CSR 6857 G54
CSR 6240 G12 CSR 6348 G21 CSR 6427 G30 CSR 6544 G38 CSR 3935 G47 CSR 6858 G54
CSR 6242 G13 CSR 3695 G21 CSR 6430 G30 CSR 6545 G38 CSR 6648 G47 CSR 6860 G54

CSR 6244 G13 CSR 6352 G22 CSR 6440 G30 CSR 6548 G38 CSR 3945 G47 CSR 6861 G54

CSR 6245 G13 CSR 6353 G22 CSR 6445 G30 CSR 6553 G39 CSR 6705 G48 CSR 10056 G54

CSR 6247 G13 CSR 10176 G22 CSR 6450 G31 CSR 10190 G39 CSR 6707 G48 CSR 10057 G54

CSR 6255 G14 CSR 10177 G22 CSR 10182 G31 CSR 10191 G39 CSR 6709 G48 CSR 10106 G54

CSR 6265 G14 CSR 6360 G22 CSR 6456 G31 CSR 6560 G39 CSR 6711 G48 CSR 10107 G54

CSR 6267 G14 CSR 6361 G22 CSR 10183 G31 CSR 6561 G39 CSR 6713 G48
CSR 6269 G14 CSR 6365 G23 CSR 6462 G31 CSR 6568 G39 CSR 6717 G49

IN6 GYPROCK® THE RED BOOK™ 1


Section H – Services Systems
2023 Page 2023 Page 2023 Page 2023 Page 2023 Page 2023 Page
System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº
CSR 7005 H6 CSR 7120 H8 CSR 10198 H11 CSR 10077 H14 CSR 7485 H16 CSR 7570 H19
CSR 10195 H6 CSR 7130 H8 CSR 7270 H11 CSR 3512 H14 CSR 3562 H16 CSR 7575 H19
CSR 7015 H6 CSR 7160 H9 CSR 7275 H11 CSR 3522 H14 CSR 7505 H17 CSR 7580 H19
CSR 7020 H6 CSR 7170 H9 CSR 7280 H11 CSR 7440 H15 CSR 10200 H17 CSR 7585 H19
CSR 7025 H6 CSR 7180 H9 CSR 7310 H12 CSR 7445 H15 CSR 7515 H17 CSR 7655 H20
CSR 7030 H6 CSR 7205 H10 CSR 7320 H12 CSR 3532 H15 CSR 7520 H17 CSR 10017 H20
CSR 7055 H7 CSR 10197 H10 CSR 7330 H12 CSR 7450 H15 CSR 7525 H17 CSR 7660 H20
CSR 7060 H7 CSR 7217 H10 CSR 7360 H13 CSR 7455 H15 CSR 7530 H18 CSR 7665 H20
CSR 10196 H7 CSR 7220 H10 CSR 7370 H13 CSR 3542 H15 CSR 7535 H18 CSR 10018 H20
CSR 7070 H7 CSR 7225 H10 CSR 7380 H13 CSR 7470 H16 CSR 7545 H18 CSR 10019 H20
CSR 7075 H7 CSR 7230 H10 CSR 10199 H14 CSR 7475 H16 CSR 7550 H18 CSR 7670 H21
CSR 7080 H7 CSR 7255 H11 CSR 7410 H14 CSR 3552 H16 CSR 7555 H18 CSR 7675 H21
CSR 7110 H8 CSR 7260 H11 CSR 7415 H14 CSR 7480 H16 CSR 7560 H18 CSR 7680 H21

Section J – Flanking Path Systems


2023 Page 2023 Page 2023 Page 2023 Page 2023 Page 2023 Page
System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº System Nº Nº
CSR 8005 J3 CSR 8119 J5 CSR 8230 J7 CSR 8305 J10 CSR 8465 J14 CSR 8588 J16
CSR 8009 J3 CSR 8120 J5 CSR 8232 J7 CSR 10202 J10 CSR 8470 J14 CSR 10207 J17
CSR 8016 J3 CSR 8121 J5 CSR 8234 J7 CSR 8313 J10 CSR 8480 J14 CSR 8607 J17
CSR 8019 J3 CSR 8130 J5 CSR 8236 J7 CSR 8317 J10 CSR 8485 J14 CSR 8609 J17
CSR 8020 J3 CSR 8132 J5 CSR 8238 J7 CSR 8331 J11 CSR 8490 J14 CSR 8611 J17
CSR 8022 J3 CSR 8134 J5 CSR 8240 J7 CSR 10203 J11 CSR 8495 J14 CSR 8613 J17
CSR 8030 J3 CSR 8136 J5 CSR 8255 J8 CSR 8335 J11 CSR 8505 J15 CSR 8630 J17
CSR 8032 J3 CSR 8138 J5 CSR 8256 J8 CSR 8337 J11 CSR 8507 J15 CSR 8632 J17
CSR 8034 J3 CSR 8140 J5 CSR 8266 J8 CSR 8339 J11 CSR 8509 J15 CSR 8634 J17
CSR 8036 J3 CSR 8155 J6 CSR 8269 J8 CSR 8356 J12 CSR 8511 J15 CSR 8655 J18
CSR 8038 J3 CSR 8156 J6 CSR 8270 J8 CSR 8361 J12 CSR 8513 J15 CSR 10208 J18
CSR 8040 J3 CSR 8166 J6 CSR 8271 J8 CSR 8380 J12 CSR 8515 J15 CSR 8659 J18
CSR 8055 J4 CSR 8169 J6 CSR 8280 J8 CSR 8382 J12 CSR 8517 J15 CSR 8661 J18
CSR 8056 J4 CSR 8170 J6 CSR 10201 J8 CSR 8384 J12 CSR 10204 J15 CSR 8663 J18
CSR 8062 J4 CSR 8171 J6 CSR 8288 J8 CSR 8386 J12 CSR 8532 J15 CSR 10209 J18
CSR 8065 J4 CSR 8180 J6 CSR 8292 J8 CSR 8388 J12 CSR 8534 J15 CSR 8682 J18
CSR 8066 J4 CSR 8182 J6 CSR 8273 J9 CSR 8390 J12 CSR 8536 J15 CSR 8684 J18
CSR 8067 J4 CSR 8184 J6 CSR 8274 J9 CSR 8392 J12 CSR 8538 J15 CSR 8686 J18
CSR 8080 J4 CSR 8186 J6 CSR 8276 J9 CSR 8406 J13 CSR 10205 J16 CSR 8688 J18
CSR 8082 J4 CSR 8188 J6 CSR 8277 J9 CSR 8411 J13 CSR 8557 J16 CSR 10210 J19
CSR 8084 J4 CSR 8190 J6 CSR 8278 J9 CSR 8430 J13 CSR 8559 J16 CSR 8707 J19
CSR 8086 J4 CSR 8205 J7 CSR 8279 J9 CSR 8432 J13 CSR 8561 J16 CSR 8709 J19
CSR 8088 J4 CSR 8206 J7 CSR 8293 J9 CSR 8434 J13 CSR 8563 J16 CSR 8711 J19
CSR 8090 J4 CSR 8216 J7 CSR 8295 J9 CSR 8436 J13 CSR 8580 J16 CSR 8713 J19
CSR 8105 J5 CSR 8219 J7 CSR 8296 J9 CSR 8438 J13 CSR 10206 J16
CSR 8106 J5 CSR 8220 J7 CSR 8297 J9 CSR 8455 J14 CSR 8584 J16
CSR 8116 J5 CSR 8221 J7 CSR 8298 J9 CSR 8460 J14 CSR 8586 J16

GYPROCK® THE RED BOOK™ 1 IN7


Health & Safety Contact Details
Information on any known health risks of our products
and how to handle them safely is on their package and/ CSR Gyprock
or the documentation accompanying them. www.gyprock.com.au
Telephone: 1300 306 556
Additional information is listed in the Safety Data Sheet.
To obtain a copy, telephone 1300 306 556 or visit DesignLINK Technical Support Service
www.gyprock.com.au. Telephone: 1800 621 117
Email: [email protected]

Warranty New South Wales and ACT


376 Victoria Street,
Gyprock products are designed to achieve optimal Wetherill Park NSW 2164
performance when part of a CSR integrated system.
CSR Building Products Limited warrants its Australian
Queensland
768 Boundary Road,
made Gyprock products to remain free of defects in Coopers Plains QLD 4108
material and manufacture for the usual lifetime of the
product (25 years). CSR warrants its International Alliance Victoria
277 Whitehall Street,
Gyprock products to remain free of defects in material and
Yarraville VIC 3013
manufacture for 7 years.
For details on our product warranty, please visit South Australia
Lot 100 Sharp Court,
www.gyprock.com.au, or contact us on 1300 306 556. Mawson Lakes SA 5095

Western Australia
19 Sheffield Road,
Welshpool WA 6106

Tasmania
PO Box 61,
Glenorchy TAS 7010

Northern Territory
Cnr Stuart Hwy & Angliss St,
Berrimah NT 0828

Triniti 3, 39 Delhi Road, North Ryde, NSW 2113, Australia


CSR Building Products ABN 55 008 631 356

Disclaimer
The products/systems referred to in this document have been manufactured
by or on behalf of CSR Building Products Limited (“CSR”) to comply with the
The Red Book 01 Design Guide, National Construction Code of Australia (NCC) and any relevant Australian
Standards. While any design or usage guidelines set out in this document have
Fire, Acoustic & Thermal been prepared in good faith by CSR, they are of a general nature only and are
intended to be used in conjunction with project specific design and engineering
– April 2025 advice.
It is the responsibility of the customer to ensure that CSR’s products/systems
are suitable for their chosen application, including in respect of project-specific
CSR Gyprock, CSR Building Products A.B.N. 55 008 631 356. matters such as, but not limited structural adequacy, acoustic, fire resistance/
The following are trade marks of CSR Limited and are under license. CSR, combustibility, thermal, and weatherproofing requirements. All information
The Red Book™, Gyprock®, Soundchek™, Aquachek™, Impactchek™, relating to design/installation/application of these products is offered without
Fyrchek™, EC08™, Supaceil™, Bradford™, Martini™, DesignLINK™, Himmel™. warranty and no responsibility can be accepted by CSR for errors and
© CSR Limited 2025. Except as provided by the Copyright Act 1968, no part omissions, or for any use of the relevant products not in accordance with CSR’s
of this publication maybe reproduced in any form or by any means without the technical literature or any other relevant industry standards. For current technical
prior written permission of CSR Limited. and warranty documentation relating to CSR’s products, visit CSR’s website at
TRB01.BMS.0425 www.csr.com.au/.
CSR Martini manufactures high-performance acoustic
AFS is a leading provider of permanent formwork systems products that are specifically engineered to perform across
through Rediwall® a polymer based system for concrete walls. multiple environments within commercial interior spaces.
afsformwork.com.au csrmartini.com.au

ROOFING
CSR Bradford is Australia’s leading supplier of insulation, CSR Monier is Australia’s most experienced and diverse
acoustic control, ventilation and energy-saving products roofing companies, manufacturing quality concrete and
for homes and commercial buildings, offering a range of terracotta roof tiles in Australia.
environmentally sustainable solutions that can help you monier.com.au
improve comfort and energy efficiency.
bradfordinsulation.com.au

CSR Cemintel provides a complete range of lightweight fibre PGH bricks and pavers provide a broad range of quality clay
cement systems, including external facades, internal linings, brick and pavers across the east coast of Australia.
flooring and ceiling systems. pghbricks.com.au
cemintel.com.au

Potter interior systems is a leading supplier of building


Proudly Australian made CSR Gyprock is the leading brand materials in New Zealand including ceiling tiles and aluminium
of plasterboard in Australia with a comprehensive range of partitioning for commercial wall and ceiling industries.
plasterboard, compounds, cornices and associated finishing potters.co.nz
products.
gyprock.com.au

Woven Image are the design leaders in sustainable acoustic


CSR Hebel is Australia’s only manufacturer of high-
finishes and textiles for commercial interiors, including
performance autoclaved aerated concrete for residential
EchoPanel® acoustic panels, ceiling baffles and acoustic tiles.
commercial and civil applications.
wovenimage.com
hebel.com.au

Proud Partner

CSR Himmel offer a complete range of interior solutions Rondo is a highly focused business in the manufacturing and
through its global product portfolio, consisting of ceilings, supply of a wide range of light gauge rolled-formed, steel
wall, high performance, acoustic and aluminium options for products and systems, primarily for the construction industry
commercial buildings. in Australia and New Zealand.
himmel.com.au rondo.com.au
DesignLINK Technical Support
Gyprock.com.au
[email protected]
1800 621 117

er your Red Book for


s and digital copy

You might also like