Belimo 22DTH-13.. Datasheet En-Gb

The 22DTH-13 is an active duct sensor designed to measure humidity and temperature in HVAC applications, with output options for enthalpy and dew point. It features a robust IP65/NEMA 4X rated housing, operates on a nominal voltage of DC 24 V, and provides multiple measuring ranges and high accuracy. The device is suitable for various environmental conditions and includes safety features and installation guidelines.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views5 pages

Belimo 22DTH-13.. Datasheet En-Gb

The 22DTH-13 is an active duct sensor designed to measure humidity and temperature in HVAC applications, with output options for enthalpy and dew point. It features a robust IP65/NEMA 4X rated housing, operates on a nominal voltage of DC 24 V, and provides multiple measuring ranges and high accuracy. The device is suitable for various environmental conditions and includes safety features and installation guidelines.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Technical data sheet 22DTH-13..

Duct sensor Humidity / Temperature

Active sensor (4...20 mA) for measuring the


relative or absolute humidity and temperature
in duct applications. Instead of the humidity
signal, the enthalpy or the dewpoint can be
selected as an output signal. IP65 / NEMA 4X
rated housing.

Type Overview

Type Output signal active temperature Output signal active humidity Probe length
22DTH-13M 4...20 mA 4...20 mA 140 mm
22DTH-13Q 4...20 mA 4...20 mA 270 mm

Technical data

Electrical data Nominal voltage DC 24 V


Nominal voltage range DC 13.5...26.4 V
Power consumption DC 1W
Electrical connection Pluggable spring loaded terminal block max.
2.5 mm²
Cable entry Cable gland with strain relief ø6...8 mm

Functional data Medium Air


Multirange 4 measuring ranges selectable
Current output 2x 4...20 mA, max. resistance 500 Ω

Measuring data Measured values Relative humidity


Absolute humidity
Dew point
Enthalpies
Temperature

Specification temperature active Sensing element technology Polymer-based capacitive sensor with stainless
steel wire mesh filter
Measuring range temperature settings Active sensor: range selectable
Attention: The maximum measuring range
listed does not indicate the allowable fluid
temperature for the sensor. Refer to safety
data for the maximum fluid temperature
limits.
Setting Range [°C] Range [°F] Factory setting
S0 -40...60 -40...160
S1 0...50 40...140
S2 -15...35 0...100
S3 -20...80 0...200
Accuracy temperature ±0.3°C @ 25°C [±0.5°F @ 77°F]
Long term stability ±0.05°C p.a. @ 21°C [±0.09°F p.a. @ 70°F]
Time constant τ (63%) in the air duct Typical 125 s @ 3 m/s

www.belimo.com 22DTH-13.. • en-gb • 2025-05-28 • Subject to change 1/5


Technical data sheet 22DTH-13..
Technical data

Specification Humidity Sensing element technology Polymer-based capacitive sensor with stainless
steel wire mesh filter
Measuring range 0...100% RH
Measuring range absolute humidity adjustable at the transducer:
0...50 g/m³ (default setting)
0...80 g/m³
Measuring range enthalpy 0...85 kJ/kg
Measuring range dew point adjustable at the transducer:
0...50°C [40...140°F] (default setting)
-20...80°C [0...200°F]
Accuracy ±2% between 0...80% RH @ 25°C
Long term stability ±0.3% RH p.a. @ 21°C @ 50% RH
Time constant τ (63%) in the air duct Typical 10 s @ 3 m/s

Safety data Protection class IEC/EN III, Safety Extra-Low Voltage (SELV)
Power source UL Class 2 Supply
Degree of protection IEC/EN IP65
Degree of protection NEMA/UL NEMA 4X
EU Conformity CE Marking
Certification IEC/EN IEC/EN 60730-1
Quality Standard ISO 9001
UL Approval cULus acc. to UL60730-1A/-2-9/-2-13, CAN/CSA
E60730-1/-2-9
Type of action Type 1
Rated impulse voltage supply 0.8 kV
Pollution degree 3
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature -35...50°C [-30...120°F]
Fluid humidity 0...100% RH, short-term condensation
permitted
Fluid temperature -40...80°C [-40...175°F]
Operating condition airflow max. 12 m/s

Materials Housing Cover: PC, orange


Bottom: PC, orange
Seal: NBR70, black
UV resistant
Cable gland PA6, black

Safety notes

This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application. Unauthorised
modifications are prohibited. The product must not be used in relation with any equipment
that in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.
Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied with during installation.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.

www.belimo.com 22DTH-13.. • en-gb • 2025-05-28 • Subject to change 2/5


Technical data sheet 22DTH-13..

Remarks

General remarks concerning sensors Sensing devices with a transducer should always be operated in the middle of the measuring
range to avoid deviations at the measuring end points. The ambient temperature of
transducer electronics should be kept constant. The transducers must be operated at a
constant supply voltage (±0.2 V). When switching the supply voltage on/off, onsite power
surges must be avoided.

Remark: Occurring draft leads to a better carrying-off of dissipative power at the sensor. Thus
temporally limited fluctuations might occur upon temperature measurement.

Build-up of self-heating by electrical Temperature sensors with electronic components always have a dissipative power which
dissipative power affects the temperature measurement of the ambient air. The dissipation in active
temperature sensors shows a linear increase with rising operating voltage. The dissipative
power should be taken into account when measuring temperature.
In case of a fixed operating voltage (±0.2 V), this is normally done by adding or reducing a
constant offset value. As Belimo transducers work with a variable operating voltage, for
reasons of production engineering only one operating voltage can be taken into
consideration. Transducers 0...10 V / 4...20 mA have a standard setting at an operating
voltage of DC 24 V. This means that at this voltage, the expected measuring error of the
output signal will be the least. For other operating voltages, the offset error will be increased
by a changing power loss of the sensor electronics.
If a readjustment directly at the active sensor should be necessary during later operation, this
can be done with the following adjustment methods.
- For sensors with NFC or dongle with the corresponding Belimo app
- For sensors with a trimming potentiometer on the sensor board
- For bus sensors via bus interface with a corresponding software variable

Application notice for humidity sensors The humidity sensor is extremely sensitive. Touching the sensor element or exposing it to
aggressive substances like chlorine, ozone, ammonia, hydrogen peroxide or ethanol (i.e. as a
cleaning agent) may affect the measurement accuracy.
Long term operation outside the recommended conditions (5…60°C and 20…80% RH) can
result in a temporary offset. After returning into the recommended range, this effect
disappears.

Parts included

Description Type
Mounting flange for duct sensor 19.5 mm, up to max. 120°C [248°F], A-22D-A35
Plastic

Accessories

Optional accessories Description Type


Replacement filter sensor probe tip, wire mesh, Stainless steel A-22D-A06
Connection adapter flex conduit, M20x1.5, for cable gland 1x 6 mm, A-22G-A01.1
Multipack 10 pcs.

www.belimo.com 22DTH-13.. • en-gb • 2025-05-28 • Subject to change 3/5


Technical data sheet 22DTH-13..

Wiring diagram

① Status LED
Slow blinking (0.5 Hz): Ok
Fast blinking (4 Hz): Failure

RH Relative humidity
absH Absolute humidity
EntH Enthalpy
TPkt/Dew Dew point
(Measured value available on output
AOI1)

Correct temperature values are only available, when the humidity output AOI1 and both
inputs UB + are connected.
The following measuring ranges can be adjusted through the jumper settings:
Setting Range [°C] Range [°F] Factory setting
S0 -40...60 -40...160
S1 0...50 40...140
S2 -15...35 0...100
S3 -20...80 0...200

www.belimo.com 22DTH-13.. • en-gb • 2025-05-28 • Subject to change 4/5


Technical data sheet 22DTH-13..

Dimensions

L = Probe length

Type Probe length Weight


22DTH-13M 140 mm 0.14 kg
22DTH-13Q 270 mm 0.20 kg

Further documentation

• Installation instructions

www.belimo.com 22DTH-13.. • en-gb • 2025-05-28 • Subject to change 5/5