Your professional electrical partner
Three Phase Smart Motor Soft Starter
With the single chip processor as the intelligence center, thyristor module for actuators for full automatic control motor.
It applies various squirrel-cage asynchronous motor control of load, the motor can smooth starting under any working
conditions, protect the drag system, reduce the starting current impact on power grid, ensure reliable motor starting.
Smoothly soft stopping function can effectively solve the inertial system surge problem, eliminate the drag system of
inertial impact, that is traditional equipment cannot be achieved. Intelligent digital motor soft start equipment system
with the complete protection function, extend the service life of the system, reduce the cost of system cost, improve
the reliability of system and compatible with all the functions of starting equipment; It is a new ideal alternative for
traditional star triangle starter and self-coupling decompression starter.
Features
The computer simulation design, SMT production process, Good EMC performance.
Perfect protection function: No voltage, less voltage, over voltage, over heating, starting time too long,
Input phase lost, output phase lost, 3phase unbalance, starting over current, running overload, load short circuit.
Fault self-diagnosis(short circuit, over voltage, less voltage, one phase grounded, motor overload, one phase lost,
motor blocked, and intelligent software can inspect drag system working state).
Combination of modular design, according to the fault display content, quick troubleshooting.
Independently software copyright.
Motor starting and protection proprietary technology.
Unique way to detect debug equipment and process.
Reliable performances lay the foundation of qualified service and quality.
Provide perfect system solution.
The timely and thoughtful Consulting Services.
Constantly improve the product performance according to user's opinion.
www.noker-inverter.com
Your professional electrical partner
Specification
Item Description
Power supply AC220V/380V/660V±15%, 50/60Hz
Adaptive Motor Squirrel-cage three-phase asynchronous motor
Starting times It is recommended not to exceed 20 times per hour
Control mode 1) Operation panel control;
2) Operation panel +external control;
3) External control ;
4) External control+ COM control ;
5) Operation panel +external+ COM control;
6) Operation panel + COM control;
7) COM control ;
8) No start or stop operation;
Start Mode 1) Current-limiting start;
2) Voltage ramp start;
3) Torque control +current-limiting to start;
4) Torque control +voltage ramp to start;
5) Current ramp to start;
6) Voltage current-limiting double closed-loop start;
Stop Mode 1) Soft stop; 2) Free stop;
1) Open loop protection for external instantaneous stop terminals;
2) Over-heat protection for soft starter;
3) Protection for too long starting time;
4) Input open phase protection;
5) Output open phase protection;
6) Unbalanced three-phase protection;
7) Starting over current protection;
Protective Function 8) Running overload protection;
9) Under voltage protection for power voltage;
10) Over-voltage protection for power voltage;
11) Protection for fault parameter setting;
12) Load short circuit protection;
13) Auto restart or incorrect wiring protection;
14) Incorrect wiring protection of external control stop terminals;
Protection Class IP00,IP20
Cooling Pattern Natural wind cooling
Place to be used Indoor location with good ventilation free from corrosive gas and conductive dust.
Environment Condition Below 2000M. Rise the rate power when the altitude is more than 2000M.
Ambient Temperature -25+45°C
Ambient Humidity 95%(20°C±5°C)
Vibration<0.5G
www.noker-inverter.com
Your professional electrical partner
Typical application
Terminals
Terminal No. Name of terminal Description
R、S、T Power Supply terminal Connect to Power supply
Main circuit L11、L12、L13 Bypass terminal Connect to Bypass contactor
U、V、W Motor terminal Connect to motor
1 Bypass output Bypass output
2
3 Time-delay output Time-delay output
4
5 Failure output Failure output
6
7 Instantaneous stop Instantaneous stop
8 Stop Stop disconnect to Public, then stop
Control circuit
9 Start-up Start-up connect to Public, then start
10 Public Public
11 Analog output - 4-20mA
12 Analog output +
www.noker-inverter.com
Your professional electrical partner
Three Phase Online Motor Soft Starter
Motor soft starter, the use of intelligent digital control; It used to various squirrel-cage asynchronous motor control of
load, the motor can smooth starting under any working conditions, protect the drag system, reduce the starting current
impact on power grid, ensure reliable motor starting.
Intelligent digital motor soft start equipment system with the complete protection function, extend the service life of the
system, reduce the cost of system cost, improve the reliability of system and compatible with all the functions of
starting equipment; It is a new ideal alternative for traditional star triangle starter and self-coupling decompression
starter.
Features
The computer simulation design, SMT production process, Good EMC performance.
Compact design, easy to install and use.
Fault self-diagnosis(short circuit, over voltage, less voltage, one phase grounded, motor overload, one phase lost,
motor blocked, and intelligent software can inspect drag system working state).
Combination of modular design, according to the fault display content, quick troubleshooting.
Humanized design, detachable operation panel, built-in Chinese and English display interface for flexible selection
Motor starting and protection proprietary technology.
Unique way to detect debug equipment and process.
Reliable performances lay the foundation of qualified service and quality.
Provide perfect system solution.
The timely and thoughtful Consulting Services.
Constantly improve the product performance according to user's opinion.
www.noker-inverter.com
Your professional electrical partner
Specification
Item Description
Power supply AC220V/380V±15%, 50/60Hz
Adaptive Motor Squirrel-cage three-phase asynchronous motor
Starting times It is recommended not to exceed 20 times per hour
External terminal 1) Remote control input
2) Relay output
3) Analog output
4) RS485 communication output
Start Mode 1) Start mode: voltage ramp start, current limit start, torque start
2) Stop mode: Soft stop, Free stop
3) Starting time: 1~120s
4) Stopping time: 0~60s
5) Starting current limiting multiplier: 0.5~6Ie
6) Starting voltage: 0.3~0.8Ue
7) Pump functions
Protection Class IP00,IP20
Cooling Pattern Natural wind cooling
Place to be used Indoor location with good ventilation free from corrosive gas and conductive dust.
Environment Condition Below 2000M. Rise the rate power when the altitude is more than 2000M.
Ambient Temperature -25+45°C
Ambient Humidity 95%(20°C±5°C)
Vibration<0.5G
Typical application
www.noker-inverter.com
Your professional electrical partner
Terminals
Special Application
In parallel the starting of the motors:
If the motors total power is less than 80% of soft starter, the motors can be parallel connection. But at this time should be
also provides for each motor thermal protection device.
Double speed motor:
Motor soft starter can cooperate with double speed motor starting, must go through demagnetization delay period before
change from low speed to high speed, to avoid anti-phase current generated between the lines and motor.
Too long cable:
If the cable is too long, the cable voltage drop will be high, and that will increase current loss and reduce starting torque, so
please use big KW soft starter and motor.
Soft starter parallel connected with one power-line:
If several soft starters parallel installed in the one power line, the input line reactor should be installed in the middle of the
transformer and the soft starter circuit. Reactor should be installed at each line input side between circuit breaker and soft
starter.
The application of surge protection device (SPD):
The surge protection device should be considered to installed in the application case, where is easily caused trouble by
lightning or other reasons, such as over voltage, over-current, surge interference. Please refer to SPD related documents
for details.
www.noker-inverter.com
Your professional electrical partner
Single/Three Phase Motor Soft Starter Built-in Bypass Contactor
NK series built-in bypass soft starter is a full digital product. Suitable for squirrel-cage asynchronous motors.
Rated voltage from 200V--525V, Rated power from 0.75--75kW. The soft starter can control the motor to
accelerate smoothly in the process of stopping, It also provides a comprehensive protection function for motors
and itself.
Features
Start/stop slope and initial voltage set by 3 different potentiometer built-in.
Bypass relay built-in, no need for extra contactor.
Voltage slope start-up mode.
The output torque can be maintained during the stop process, prevent water hammer effect.
Real-time data of communication.*1
Reading history fault records by communication.*1
The statistics data can be read by Modbus communication.*1
Protection:
1) 8xIn Over-current protection;
2) 5--8.5xIn Continued over-current protection;
3) Over-load protection with class 10A, 10, 20, 30;
4) Three phase current imbalance protection;
5) No voltage protection;
6) Phase missing protection;
7) Phase sequence protection;
8) SCR over-heating protection;
Note *1: Option, only if select the RS485 communication interface with the function.
www.noker-inverter.com
Your professional electrical partner
Specification
Item Description
Power supply AC220V/380V±15%
Power frequency 50/60Hz
Control source voltage 100-240VAC
Adaptive Motor Squirrel-cage three-phase asynchronous motor
Starting times It is recommended not to exceed 20 times per hour
Start Mode 1) Voltage slope start;
1) 8xIn Over-current protection;
2) 5--8.5xIn Continued over-current protection;
3) Over-load protection with class 10A, 10, 20, 30;
Protective Function 4) Three phase current imbalance protection;
5) No voltage protection;
6) Phase missing protection;
7) Phase sequence protection;
8) SCR over-heating protection;
Protection Class IP42
Cooling Pattern Natural wind cooling
Place to be used Indoor location with good ventilation free from corrosive gas and conductive dust.
Environment Condition Below 2000M. Rise the rate power when the altitude is more than 2000M.
Ambient Temperature 0--+50°C
Ambient Humidity 95%(20°C±5°C)
Vibration<0.5G
Internal Control diagram
www.noker-inverter.com
Your professional electrical partner
Rated main current
Three phase motor soft starter
Model Motor power rating Rated current
220V(kW) 400V(kW) 500 V(kW) Ie(A)
NKXX1T5-X-3P3 0.37 0.75 1.1 1.5
NKXX2T2-X-3P3 0.55 1.1 1.5 2.2
NKXX03-X-3P3 0.75 1.5 2.2 3
NKXX4T5-X-3P3 1.1 2.2 3 4.5
NKXX7T5-X-3P3 1.5 3.7 4.5 7.5
NKXX11-X-3P3 2.2 5.5 7.5 11
NKXX15-X-3P3 3.7 7.5 11 15
NKXX22-X-3P3 5.5 11 15 22
NKXX30-X-3P3 7.5 15 18.5 30
NKXX37-X-3P3 11 18.5 22 37
NKXX45-X-3P3 15 22 30 45
NKXX60-X-3P3 18.5 30 37 60
NKXX75-X-3P3 22 37 45 75
NKXX90-X-3P3 25 45 55 90
NKXX110-X-3P3 30 55 75 110
NKXX150-X-3P3 37 75 90 150
NKXX175-X-3P3 45 90 110 175
Single phase motor soft starter
Model Motor power rating Rated current
220V(kW) 400VkW) Ie(A)
NKXX02-X-1P1 0.37 0.55 2
NKXX03-X-1P1 0.55 0.75 3
NKXX04-X-1P1 0.75 1.1 4
NKXX06-X-1P1 1.1 1.5 6
NKXX09-X-1P1 1.5 2.2 9
NKXX12-X-1P1 2.2 3.7 12
NKXX20-X-1P1 3.7 5.5 20
NKXX30-X-1P1 5.5 7.5 30
NKXX37-X-1P1 7.5 11 45
Control terminal diagram
www.noker-inverter.com
Your professional electrical partner
Single/Three Phase Micro motor soft starter
This module is compatible with 220V, 380V, frequency 50-60Hz, soft starting time for 30s adjustable (time rise refers to 0-
220V), when the main power supply is 220V, The starting voltage can be adjusted from 0-110V to the rated voltage of 220V.
If the main power supply is 380V, the starting voltage can be adjusted from 0-180V to the rated voltage of 380V.
There are two software now: soft start without soft stop, with soft start with soft stop.
Note:1.Do not set the start time to the smallest.
2.Do not connect power supply to switch.
3.If not requirement, default R1.
4.Please choose the suitable radiator.
5.If need soft stop, must use the module switch, with soft stop R2 type.
6.Default 380v, if you need 220v, please inform when order.
Model
Model Phase No. Power Rated current
SSR-20WA-R1(1.0KW) Single phase 1.0kW 20A
SSR-40WA-R1(1.5KW) Single phase 1.5kW 40A
SSR-60WA-R1(2.0KW) Single phase 2.0kW 60A
SSR-100WA-R1(4.0KW) Single phase 4.0kW 100A
SSR-150WA-R1(6.0KW) Single phase 6.0kW 150A
SSR-200WA-R1(8.0KW) Single phase 8.0kW 200A
TSR-10WA-R1(1KW) Three phase 1kW 10A
TSR-20WA-R1(2KW) Three phase 2kW 20A
TSR-30WA-R1(3KW) Three phase 3kW 30A
TSR-40WA-R1(4KW) Three phase 4kW 40A
TSR-60WA-R1(6KW) Three phase 6kW 60A
TSR-80WA-R1(8KW) Three phase 8kW 80A
TSR-100WA-R1(10KW) Three phase 10kW 100A
TSR-120WA-R1(12KW) Three phase 12kW 120A
TSR-150WA-R1(15KW) Three phase 15kW 150A
TSR-200WA-R1(20KW) Three phase 20kW 200A
TSR-220WA-R1(22KW) Three phase 22kW 220A
www.noker-inverter.com
Your professional electrical partner
Application
Dimension
www.noker-inverter.com
Your professional electrical partner
Medium Voltage Motor Soft Starter
Medium Voltage Soft Starter is a high voltage motor soft starter designed with up-to date concept, mainly applicable to the
control of and protection for the starting and stopping of squirrel-cage type asynchronous and synchronous motors. The
starter is composed of several thyristors in series-parallel, and it can meet different current and voltage requirements.
The product is widely used in electric industry with rated voltage 3000 to 10000V,building materials chemical industry,
metallurgy, steel and paper-making industries etc., and can perform well if used together with various kinds of
electromechanical devices including water pumps, fans, compressors, crashers, agitators and conveyer belt etc., It is the
ideal device for starting and protecting high voltage motors.
Terminal Description
Terminal No. Definition of terminal Description
X1/1 Current output (+)
Analogue output Set by parameter items C06, C07
X1/2 Current output (-)
X1/3 COM COM
X1/4 Input terminal for remote run (RUN) Jump X1/3,X1/4 to run
Digital input X1/5 Input terminal for remote stop (STOP) Disconnect X1/3,X1/5 to stop
X1/6 Digital input signal D1 Set by parameter item C03
X1/7 Digital input signal D2 Set by parameter item C04
X2/1
L1 phase current sampling To sample phase current of L1
X2/2
Current sampling
X2/3
L3 phase current sampling To sample phase current of L3
X2/4
X2/5 PE for input signal Reference grounding for input current signal
Analogue input
X2/6 Analogue input Set by parameter item C06
RS 485-A X2/7 RS 485 communication (+)
RS 485-B X2/8 RS 485 communication (-)
X3/1
Output relay K1 Fault output) Contact capacity: AC250V/5A, DC30V/5A
X3/2
X3/3
Output relay K2 Output relay contact for bypass Contact capacity: AC250V/5A, DC30V/5A
X3/4
X3/5
Output relay K3 Programmable output relay contact Contact capacity: AC250V/5A, DC30V/5A
X3/6
X3/7 PE To earth
Control voltage
X3/8 Control voltage AC110V---AC220V+15% 50/60Hz
www.noker-inverter.com
Your professional electrical partner
Technical parameters
Basic parameters
Type of load Three-phase squirrel cage asynchronous and synchronous motors
AC voltage 3000---10000VAC
Service frequency 50HZ/60HZ±2HZ
Phase sequence Allowed to work with any phase sequence
Composition of major loop (12SCRS,18SCRS,30SCRS depend on model)
Bypass contactor Contactor with direct starting capacity
Control power supply AC220V±15%
Transient voltage overload
dv/dt snubber network
protection
Start times 1-3 times per hour
Ambient temperature: -20°C -+50°C
Ambient condition Relative humidity: 5%----95% no condensation
Altitude less than 1500m (derating when altitude is more than 1500m)
Protective functions
Open-phase protection Cut off any phase of primary power supply in the course of starting or operation.
Over-current protection in
Operational Over-current protection setting: 20~500%Ie
operation
Unbalanced phase current
Unbalanced phase current protection: 0~100%
protection
Overload protection 10A,10,15,20,25,30,OFF
Underload protection grade: 0~99%
Under-load protection
Action time of underload protection: 0~250S
Start timeout Start time limit: 0~120S
Over-voltage protection Primary power supply is 120% higher than rated value, over-voltage protection
Under-voltage protection Power supply is 70% lower than rated value, under-voltage protection
Phase protection Allow to work with any phase sequence (through setting parameter)
Ground protection Protection available when grounding current is higher than set value
Description of communication
Protocol Modbus RTU
Communication interface RS485
Network connection Each can communicate with 31 equipments in network.
Function Operation state and programming can be observed through communication interface
Operating interface
LCD display LCD display/touch screen display
Language Chinese and English
Keyboard 6 touch membrane keyboard
Meter display
Primary power supply Display voltage of three-phase primary power supply
Three-phase current Display current of three-phase major loop
Data record
Fault history Record recent 15 faults information
History of number of starts Record number of starts of this soft starter
www.noker-inverter.com
Your professional electrical partner
Features
1. Free of maintenance: Thyristor is an electric device without contacts. Different from other kinds of products that need
frequent maintenance on liquid and parts etc., it turns the mechanical lift into the service life of electronic components, so it
needs no maintenance after running for many years.
2. Easy installation and operation: A complete system for controlling and protecting the starting of motor. It can put into
operation only with the power line and motor line connected. The whole system can be tested electrically under low voltage
before operating with high voltage.
3. Backup: The starter comes equipped with a vacuum contactor which can be used to start the motor directly in the inside.
If fails, the vacuum contactor can be used to start the motor directly to ensure the continuity of the production.
4. High voltage thyristor is a component of major loop, equipped with voltage balancing protection system and over-voltage
protection system.
5. Comes equipped with an electromagnetic blocking device for fear of entering the high voltage device in the electrified
state.
6. Advanced optical fiber transmission technique realizes the triggering detection of high voltage thyristor and the isolation
between LV control loops.
7. 32-bit ARM-core microcontroller is used to perform central control which is real-time and high efficient with high reliability
and excellent stability.
8. LCD/touch screen display system in both Chinese and English with human-friendly operation interface.
9. RS-485 communication port can be used to communicate with the upper computer or centralized control center.
10. Aging experiments are made on all circuit boards.
Connection Diagram
www.noker-inverter.com