MCCB - NDM5 400V 630V Products Specification

The document provides specifications and technical details for the NDM5-400V and NDM5-630V series of moulded case circuit breakers, which are designed for power distribution and protection against overload, short circuit, and under-voltage. It includes information on applicable voltage and current ratings, installation requirements, environmental conditions, and tripping characteristics. Compliance with international standards IEC 60947-2 and GB/T 14048.2 is also noted.

Uploaded by

bouaissi.yac98
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views17 pages

MCCB - NDM5 400V 630V Products Specification

The document provides specifications and technical details for the NDM5-400V and NDM5-630V series of moulded case circuit breakers, which are designed for power distribution and protection against overload, short circuit, and under-voltage. It includes information on applicable voltage and current ratings, installation requirements, environmental conditions, and tripping characteristics. Compliance with international standards IEC 60947-2 and GB/T 14048.2 is also noted.

Uploaded by

bouaissi.yac98
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

Document No.

: NDT2930384 Dcument Version: 5

1 、Applicable scope and purpose


The NDM5-400Vseries of moulded case circuit breakers have a rated insulation voltage of
1000V and apply to circuits with the AC 50Hz/60Hz, the rated working voltage (AC800V,AC1000V)
and rated working current (250A,320A,400A for 400 shell frame). The circuit breakers are used for
distributing power while protect the overload, short circuit and under-voltage (with a under-voltage
release) of lines and power units.
The NDM5-630V series of moulded case circuit breakers have a rated insulation voltage of
1000V and apply to circuits with the AC 50Hz/60Hz, the rated working voltage (AC800V,AC1000V)
and rated working current (400A,500A,630A for 630 shell frame). The circuit breakers are used for
distributing power while protect the overload, short circuit and under-voltage (with a under-voltage
release) of lines and power units.
The circuit breaker has an isolating function with the corresponding symbol of .
Comply with standards: IEC 60947-2, GB/T 14048.2.
2 、Picture of the Product

Product picture

Page 1/17
Document No.: NDT2930384 Dcument Version: 5

3、Specification and model description


ND M 5 - □ □ □ □ □ / □ / □ / □ □ □ □
1 2 3 4 5 6 7 8 9 10 11 12 13 14
S.N. Name of S.N. NDM5
1 Enterprise ND: Nader low-voltage apparatus
characteristic
2 Product type code M:Moulded case circuit breaker (MCCB)
3 Design S.N. 5
4 Current of the 400、630
Derived code of
5 V:High voltage
the series
6 Interrupting level M:medium-high
code
Reference Null: Normal temperature type
7
temperature T:High temperature type
8 Rated current See table 2

9 Pole 3:3 poles

TMF:Thermal magnetic fixed release


10 Trip release code
TMD: AC protection-thermo-magnetic distribution release
Installation code+
11 Null: Stationary connector + front panel wiring
Wiring method

Null: directly handle operation


Z1A150:rotary handle with round center hole and square axis
length 150
Z1A200:rotary handle with round center hole and square axis
length 200
Z1A300:rotary handle with round center hole and square axis
length 300
Z1A350:rotary handle with round center hole and square axis
12 Operation method length 350
Z1A650:rotary handle with round center hole and square axis
length 650
Z1F150:rotary handle with round square hole and square axis
length 150
Z1F200:rotary handle with round square hole and square axis
length 200
Z1F300:rotary handle with round square hole and square axis
length 300
Page 2/17
Document No.: NDT2930384 Dcument Version: 5

Z1F350:rotary handle with round square hole and square axis


length 350
Z1F650:rotary handle with round square hole and square axis
length 650
13 Accessory code See table 1
14 Application code EPT
Table 1 NDM5-400V/630V

Accessory Installation
Accessory name
code position

00 None

08 Alarm contact

10 Shunt release

30 Under-voltage release

21 Single auxiliary contact

61 Two sets of single auxiliary contacts

23 Three sets of single auxiliary contacts

18 Alarm contact+ shunt release

38 Alarm contact+ under-voltage release

22 Alarm contact+ single auxiliary contact

88 Alarm contact+ two sets of single auxiliary contacts

26 Alarm contact+ three sets of single auxiliary contacts

42 Alarm contact+ shunt release+ single auxiliary contact

44 Alarm contact+ shunt release+ two sets of single auxiliary contacts

46 Alarm contact+ shunt release+ three sets of single auxiliary contacts

75 Alarm contact+ under-voltage release+ single auxiliary contact

77 Alarm contact+ under-voltage release+ two sets of single auxiliary contacts

81 Alarm contact+ under-voltage release+ three sets of single auxiliary contacts

41 Shunt release+ single auxiliary contact

11 Shunt release+ two sets of single auxiliary contacts

12 Shunt release+ three sets of single auxiliary contacts

71 Under-voltage release+ single auxiliary contact

Page 3/17
Document No.: NDT2930384 Dcument Version: 5

72 Under-voltage release+ two sets of single auxiliary contacts

73 Under-voltage release+ three sets of single auxiliary contacts

50 Shunt release+ under-voltage release

31 Alarm contact+ shunt release+ under-voltage release

51 Shunt release+ under-voltage release+ single auxiliary contact

52 Shunt release+ under-voltage release+ two sets of single auxiliary contacts

53 Shunt release+ under-voltage release+ three sets of single auxiliary contacts

98 Two sets of single alarm contacts

63 Two sets of single alarm contacts+ single auxiliary contact

64 Two sets of single alarm contacts+ two sets of single auxiliary contacts

65 Two sets of single alarm contacts+ three sets of single auxiliary contacts

37 Two sets of single alarm contacts+ shunt release+ under-voltage release


Two sets of single alarm contacts+ shunt release+ under-voltage release+ single
39
auxiliary contact
Two sets of single alarm contacts+ shunt release+ under-voltage release+ two
55
sets of single auxiliary contacts
Two sets of single alarm contacts+ shunt release+ under-voltage release+ three
56
sets of single auxiliary contacts

32 Shunt release+ under-voltage release, single auxiliary contact

Alarm contact+ shunt release+ under-voltage release+ two sets of single


33
auxiliary contacts
Alarm contact+ shunt release+ under-voltage release+ three sets of single
34
auxiliary contacts
Note: Single auxiliary contact; □ Alarm contact; ●Shunt release; ○Under-voltage release.

Fig.2 Attachment installation diagram

4、Main Technical Parameters


Table 2

Page 4/17
Document No.: NDT2930384 Dcument Version: 5

Model NDM5-400V NDM5-630V


Frame current Inm (A) 400 630
Rated current In (A) 250, 320, 400 400, 500, 630
Rated voltage Ue (V) AC800, AC1000
Utilization category A
Rated impulse withstand voltage Uimp (V) 8000
Rated insulation voltage Ui (V) 1000
Power frequency withstand voltage (1min) (V) 4000
Rated frequency (Hz) 50/60
Rated Ultimate breaking AC800V 50
capacity Icu (kA) AC1000V 35
Rated Service breaking AC800V 50
capacity Ics (kA) AC1000V 18
Maintainable free life 15000
Mechanical life (times)
Maintainable life 30000
AC800V 1500
Electrical life (times)
AC1000V 1000
Boundary dimension L(mm) 250

W(mm) 140

H(mm) 130.5

Flashover distance(mm) ≤100

Note The overall dimension does not include the dimension of terminal cover.

4.1
Table 3-1 Wire parameters
Rated current (A) 250 320 400

Conductor area(mm²) 120 185 240


Table 3-2 Wire parameters
cable Copper bar
Rated current (A)
Conductor are(mm²) Quantity size(mm²) Quantity

500 150 2 30×5 2


630 185 2 32×6 2

4.2
Table 4 Derating factor table of temperature change for the circuit breaker
Page 5/17
Document No.: NDT2930384 Dcument Version: 5

Model Screw application Thread specification Torsional moment (N·m)

Wiring screw M10 50


NDM5-400V/630V
Set screw M5 2

4.3
Table 5 Derating factor table of temperature change for the circuit breaker
Model Derating factor of product temperature change

Temperatu(℃) 40 45 50 55 60 65 70

NDM5-400V 1 1 1 0.95 0.91 0.86 0.80

NDM5-630V 1 1 1 0.94 0.90 0.85 0.80


Note: 1)When the operating ambient temperature is below ﹢50℃,the product can be used normally
without derating capacity. and do not need to reduce capacity.
2)The above derating factors are measured under the rated current of the shell frame.
4.4
Table 6 Altitude drop correction factor
Working current Maximum working Power frequency Isolation voltage
Altitude
(m)
correction current correction withstand voltage correction
coefficient coefficient (V) (V) coefficient (V)
2000 1 1000 4000 1000
2500 1 1000 4000 1000
3000 0.98 900 3600 900
3500 0.97 850 3400 850
4000 0.95 810 3200 810
4500 0.94 770 3000 770
5000 0.93 730 2800 730

4.5
Table 7 NDM5-400V/630V Product current specification single phase power consumption able
Single phase power consumption (W)
Current
Model
specification
Front panel wiring

NDM5-400V 400A 19.8


NDM5-630V 630A 39.5
Note:The above data are the single-phase loss measured under the rated current of the circuit
breaker when the ring temperature is 40℃。

Page 6/17
Document No.: NDT2930384 Dcument Version: 5

5、Normal working environment of circuit breaker


1)The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude derating Factor
Table of Circuit Breaker” for the derating factor at the altitude;
2)The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be more than +35℃.
If the ambient temperature is higher than +40℃, the user needs to reduce the capacity. See the “derating Factor
Table of Temperature Change for the Circuit Breaker” for the derating factor;
3)Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higher relative
humidity is allowed at a lower temperature. For example, the relative humidity at 20℃ can reach 90%; for
frost due to temperature change, the corresponding measures should be taken;
4)The product can withstand the effects of wet air, salt mist, oil mist and mould;
5)The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power
distribution and control level), The installation category of the circuit breaker not connected to the main loop
is: Category Ⅱ (load level);
6)The pollution level is Level 3;
7) Degree of protection : IP 20;
8)The product should be installed in places that are free from explosive media, media corrosive to metal,
insulation damaging gas, and conductive dust, which should be also avoided from snow and rain;
9)In case of stricter user conditions than the above description, negotiate with the manufacturer.

6 Tripping characteristics
6.1 Tripping characteristics curve under normal environment (ambient air temperature: 40℃), see the
picture below:

Fig.2 NDM5-400V Fig.3 NDM5-630V

Page 7/17
Document No.: NDT2930384 Dcument Version: 5

6.2

Fig.4 NDM5-400V Current limiting Fig.5 NDM5-400V Permissive characteristic


characteristic curve chart curve chart

Fig.6 NDM5-630V Current limiting Fig.7 NDM5-630V Permissive characteristic


characteristic curve chart curve chart

Page 8/17
Document No.: NDT2930384 Dcument Version: 5

7、Products outline and installation dimensions

TMD TMF

Fig.8 Release adjustment gear chart


8
8.1

Page 9/17
Document No.: NDT2930384 Dcument Version: 5

Fig.9 Terminal cover size


Note: Unmarked tolerance level should follow GB/T 1804-c。

8.2
Manual operation-the schematic diagram of handle installation and opening and the outline dimension
diagram of manual operation are shown below respectively:
Installation drawing of rotary handle operating mechanism

Fig. 10 Installation drawing of rotary handle operating mechanism

Table 8 Installation drawing of rotary handle operating mechanism


Square shaft
Model W L L1 H H1 H2 specification

NDM5-400V/630V 22.5 19 214 223.5 144.5 18 10×10

Page 10/17
Document No.: NDT2930384 Dcument Version: 5

Installation opening diagram of rotary handle

Fig.11 Installation opening diagram of rotary handle


Note:1)During manual operation, it shall rotate 180°clockwise,and counterclockwise operation
is prohibited.
2) Unmarked tolerance level should follow GB/T 1804-c.。

8.3

Fig.12 Connection diagram of copper bar in front of board or copper cable with wiring terminal

Table 9 Connection size of copper bar in front of board or copper cable with wiring terminal
Model A(mm) B(mm) ΦC(mm) H(mm)
NDM5-400V ≤36 ≤14 11 26.6
NDM5-630V ≤36 ≤14 11 28.6

8.4

8.4.1

Page 11/17
Document No.: NDT2930384 Dcument Version: 5

a. Cable
Naked metal at cable lug must be insulated with interphase partition
b. Busbar (see picture below for size of insulated cover)
Stright bar:insulation covers all around
curved bar: Insulation covers to 100mm long to the curve.
Extended row:The thickness of NDM5-400V shell frame shall not be less than 6mm,the
thickness of NDM5-630V shell frame shall not be less than 6mm 10mm , and can also be
superimposed by multiple rows;
Stright bar: insulation covers all around
curved bar: Insulation covers to 100mm long to the curve.

Fig.13 Size of insulated cover


Page 12/17
Document No.: NDT2930384 Dcument Version: 5

Note: 1. Copper bar can be directly connected to the products. If aluminum bars are applied,
extended
Copper bars must be used to reach out of the terminal shell and then connect to the aluminum bar.
Plus, connection parts of the aluminum are suggested to plate with tin. Use partitions to insulate the
bars after connection. (If aluminum bars are intended to be applied, please contact us. we will
provide two more partitions for insulation.)
2. Partitions are not allowed to be pressed between bars.
The picture above is only for identifying the sizes of insulation cover. There is no requriement
of bar connection method here.
8.4.2
The minimum safety distance between the top, bottom, side and front panel when installing the
circuit breaker, see the figure below。

Distance requirement of installation in cabinet 前面板安全间距


Fig.14 Safety distance of front panel
Page 13/17
Document No.: NDT2930384 Dcument Version: 5

8.5

Fig.15 Main circuit wiring mode of AC products

9、Attachment function description

9.1

When the power voltage drops to the range (35%~70%) of the under-voltage release, the
release can break the circuit breaker reliably; when the power voltage is 35% lower than the rated
working voltage of the under-voltage release, the release can prevent closing of the circuit breaker;
when the power voltage is 85% higher than the rated working voltage of the under-voltage release,
the release can guarantee reliable closing of the circuit breaker.
Table 10 Rated parameters of the under-voltage release
Accessory name voltage release
Voltage Tightening torque
specifications (V) AC110/DC110 AC230/DC250 AC400
value of wiring screw
Maintain power
consumption (W) 0.5 1.0 2.2

Code name Q11 Q22 Q40 1.2N.m

Fig.16 Working diagram of under-voltage release

9.2

When the external voltage of the shunt release is between 70% and 110% of the rated control
power voltage, the release can break the circuit breaker reliably.
Table 11 Rated parameters of the shunt release
Voltage Tightening
specifications (V)
Shunt release
torque value
Maintain power of wiring
consumption (W) AC/DC24 AC/DC48 AC/DC110 AC230/DC250 screw
Voltage
specifications (V) 20 9.5 8 20
1.2N.m
Code name FT02 FT04 FT11 FT22

Page 14/17
Document No.: NDT2930384 Dcument Version: 5

Fig.17 Working diagram of shunt release

Working principle of the shunt release: a single pulse action. If another action is required, the
shunt release can only be operated after being off, reset and energized.

Fig.18 Working principle diagram of shunt tripper


If the circuit breaker cannot be closed normally due to long-term power on, an auxiliary contact can
be connected in series as shown in the figure.

Table 12 Parameter of auxiliary contact


Auxiliary contact(Low
Accessory name Auxiliary contact(conventional)
power consumption)
Voltage specifications(V)/ AC250V/10A、AC400V/3A、
DC30V/0.1A
conventional thermal current (Ith) DC220V/0.2A

Off
Wiring diagram
On

Internal resistance <30mΩ <50mΩ


Note 1: If need DC30V/0.1A auxiliary contact, please explain when ordering。
2: The first auxiliary harness is identified as F11 (red), F12 (white), F14 (yellow), and the
second auxiliary harness is identified as F21 (red), F22 (white), F24 (yellow), and so on. At most
three groups of auxiliary harness are installed.

Table 13 Rated parameters of the alarm contact

Page 15/17
Document No.: NDT2930384 Dcument Version: 5

Alarm contact(Low
Accessory name Alarm contact(conventional)
power consumption)
Voltage specifications(V)/ AC250V/10A、AC400V/3A、
DC30V/0.1A
conventional (Ith) DC220V/0.2A

On, off
Wiring diagram
Free tripping

Internal resistance <30mΩ <50mΩ


Note 1: If need DC30V/0.1A Alarm contact, please explain when ordering。
2:The first alarm harness is identified as B11 (red), B12 (white), B14 (yellow), and the
second auxiliary harness is identified as B21 (red), B22 (white), B24(yellow), and so on. At most
two groups of alarms are installed.

Under-voltage release、 shunt release、 auxiliary contact、 alarm


contact ,the standard wiring line is 0.7m long and can be customized
according to requirements。
10、Installation direction of circuit breaker

For vertical installation of the product, the gradient between the installation

surface and the vertical plane is no more than ±22.5°

Horizontal installation of the product.

Vertical installation Horizontal installation


Fig. 18 Mounting method of product

11、Packaging and storage of circuit breaker


Minimum packaging quantity: 1 piece/box. The packaged products should be stored in

a warehouse with the air ventilation and the relative humidity no more than 80% when

Page 16/17
Document No.: NDT2930384 Dcument Version: 5

the ambient temperature is -40℃~+75℃. No acidic alkaline or other corrosive gas

exists in the ambient air in the warehouse. Under the conditions above, the storage

period shall be no more than three years since the manufacturing date.

12、Environment

The environment that comply with RoHS instruction.

13、Packaging and Storage


S.N. Name Specification 3P Quantity/Set
Cross small pan-head
1 M5×130 4
screw
2 Plain washer M5 4
3 Spring washer 5 4
4 Hexagon nut 5 4
5 Phase partition —— 4
6 Insulating partition —— 1
7 Terminal cover —— 2
8 Terminal cover screw M4×12 4
9 Terminal screw M10×30 6

14、Circuit breaker notes


1) Various characteristics and accessories of the circuit breaker are set in the factory.

The circuit breaker, tripping unit or other accessories can only be adjusted, installed

and maintained by the trained or qualified professionals according to the parameter

requirements of the line design;

2) Ensure that the power supply is off before installing or removing any device;

3) The circuit breaker handle can be located in three positions, indicating three states:

on, off and free tripping. When the handle is in the free tripping position, pull the handle

in the off direction when the circuit breaker is connected and on.

Page 17/17