AX260-30-11-80

AX260-30-11-80 Contactor


General Information
Extended Product Type AX260-30-11-80
Product ID 1SFL547074R8011
EAN 7320500514726
Catalog Description AX260-30-11-80 Contactor
Long Description AX260-30-11-80 Contactor


Classifications
Object Classification Code Q
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
UNSPSC 39121529
IDEA Granular Category Code (IGCC) 4755 >> Contactors


Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 175 mm
Package Level 1 Depth / Length 270 mm
Package Level 1 Height 223 mm
Package Level 1 Gross Weight 5.4 kg


Certificates and Declarations (Document Number)
Declaration of Conformity - CE 2CMT2015-005443
Instructions and Manuals N/A
RoHS Information 2CMT2015-005443


Environmental
Ambient Air Temperature Close to Contactor for Storage -40 ... +70 °C
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +55 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C
Maximum Operating Altitude Permissible 3000 m
AX260-30-11-80 2
RoHS Status Following EU Directive 2011/65/EU


Technical
Number of Main Contacts NO 3
Number of Main Contacts NC 0
Number of Auxiliary Contacts NO 1
Number of Auxiliary Contacts NC 1
Rated Operational Voltage Main Circuit 1000 V
Rated Frequency (f) Main Circuit 60 Hz
Conventional Free-air Thermal Current (I th ) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 250 A

Rated Operational Current AC-1 (I e ) (690 V) 40 °C 400 A


(690 V) 55 °C 350 A
(690 V) 70 °C 290 A
Rated Operational Current AC-3 (I e ) (220 / 230 / 240 V) 55 °C 265 A
(380 / 400 V) 55 °C 265 A
(415 V) 55 °C 265 A
(440 V) 55 °C 265 A
(500 V) 55 °C 250 A
(690 V) 55 °C 250 A
Rated Operational Power AC-3 (P e ) (220 / 230 / 240 V) 75 KWT
(380 / 400 V) 132 KWT
(415 V) 132 KWT
(440 V) 160 KWT
(500 V) 200 KWT
(690 V) 200 KWT
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1 10 x Ie AC-3
Rated Short-time Withstand Current (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2120 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 865 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2650 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1224 A
Maximum Electrical Switching Frequency 300 cycles per hour
Rated Insulation Voltage (U i ) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V

Rated Impulse Withstand Voltage (U imp ) 8 kV

Mechanical Durability 5 million


Maximum Mechanical Switching Frequency 300 cycles per hour
Coil Operating Limits (acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Rated Control Circuit Voltage (U c ) 50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Terminal Type Main Circuit: Bars


Dimensions
Product Net Width 140 mm
Product Net Depth / Length 180 mm
Product Net Height 225 mm
Product Net Weight 4.7 kg


Popular Downloads
Instructions and Manuals N/A
AX260-30-11-80 3


Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900


Categories
Low Voltage Products and Systems → Control Products → Contactors → Block Contactors