Liquid Flow Switch

#N2-SF1K-US, C – 6/28/2024
Specification

Overview
Liquid Flow Switch
The liquid flow switch is a mechanical switch for the detection and verification of liquid
flow. The flow switch is designed to be used in 1 to 8” (25.4 to 203.2 mm) diameter pipe
sizes. The switch mounts into a 1” NPT pipe connection. The enclosure carries a IP65
rating with ½” conduit connection. The switch includes various 316 stainless steel
paddles. The paddle size to install is determined by the pipe size and flow rate. When
liquid pushes against the paddle, it triggers a SPDT micro switch that is controlled by a
manually adjustable set point.
Common application areas include heating and air conditioning systems, refrigeration
systems, heat pumps, water fire suppression, and others.

Applications: Monitoring flow in heating and air conditioning systems, refrigeration


systems, heat pumps, water fire suppression

Warranty: The SF1K Series Flow Switches are covered by a Two (2) Year Limited
Warranty.

Description: Liquid Flow Switch, SPDT, IP65, Paddle Kit, 1-8” Pipe Size

Part Numbers
N2-SF1K-US

Product Specifications
Contact Form: Form 1C (SPDT Contact)
Contact Rating: 15 (8) A, 24 to 250 VAC
Pipe Size: 1 to 8” (25.4 to 203.2 mm) Diameter
Maximum Pressure: 159.5 PSI (11 bar)
Flow Rate: See H2O Flow Rate table below
Connection: NPT 1"
Body Material: Brass
Paddle Material: Stainless steel AISI 316L
Housing Material: Base in ABS, transparent PC cover
Housing Operating Temperature | Humidity: -40 to 85ºC (-40 to 185ºF) | 10 to 90% RH, non-condensing
Maximum Liquid Temperature: -40 to 120ºC (-40 to 248ºF)
Recommended Storage Temperature |Humidity: -40 to 85ºC (-40 to 185ºF) | < 95% RH, Non-Condensing
Enclosure Ratings: IP65, Class 1
Product Dimensions (L x W x H): 5.51" (140 mm) x 2.44" (62 mm) x 2.56" (65 mm)
Approvals: CE
Product Weight: 2.1 lbs. (0.95 kg)

Specifications subject to change without notice.


Catalog No. 11-808-1129-01 Page 1 of 4
Liquid Flow Switch
#N2-SF1K-US, C – 6/28/2024
Specification
H2O Flow Rate
Qmax GPM (m3/h) Min. Adjustment GPM (m3/h) Max. Adjustment GPM (m3/h)
Pipe Connector Ø Recommended Cut-Off Cut-In Cut-Off Cut-In
1" 15.9 (3.6) 2.6 (0.6) 4.4 (1.0) 8.8 (2.0) 9.2 (2.1)
1 1/4” 26.4 (6.0) 3.5 (0.8) 5.7 (1.3) 12.3 (2.8) 13.2 (3.0)
1 1/2" 39.6 (9.0) 4.8 (1.1) 7.5 (1.7) 16.3 (3.7) 17.6 (4.0)
2" 66.0 (15.0) 9.7 (2.2) 13.6 (3.1) 25.1 (5.7) 26.9 (6.1)
2 1/2" 105.7 (24.0) 11.9 (2.7) 17.6 (4.0) 28.6 (6.5) 30.8 (7.0)
3" 158.5 (36.0) 18.9 (4.3) 27.3 (6.2) 47.1 (10.7) 50.2 (11.4)
4" 264.2 (60.0) 50.2 (11.4) 64.7 (14.7) 122.0 (27.7) 127.7 (29.0)
4" Z 264.2 (60.0) 26.9 (6.1) 35.2 (8.0) 76.2 (17.3) 81.0 (18.4)
5" 413.9 (94.0) 100.8 (22.9) 125.0 (28.4) 234.7 (53.3) 244.8 (55.6)
5"Z 413.9 (94.0) 40.9 (9.3) 56.8 (12.9) 111.0 (25.2) 118.0 (26.8)
6” 528.3 (120.0) 158.1 (35.9) 189.8 (43.1) 359.7 (81.7) 374.7 (85.1)
6" Z 528.3 (120.0) 54.2 (12.3) 74.0 (16.8) 134.7 (30.6) 144.0 (32.7)
8” 1,056.7 (240.0) 319.6 (72.6) 374.7 (85.1) 729.6 (165.7) 759.5 (172.5)
8" Z 1,056.7 (240.0) 170.0 (38.6) 204.7 (46.5) 399.8 (90.8) 414.8 (94.2)
For models with suffix “Z” the longest paddle must be used to obtain the values indicated on the table. Pressure drop at the
maximum flow (Qmax): 1.2 PSI (0.08 bar)

Product Drawings

Figure 1: Product Drawing (scale in mm)

Specifications subject to change without notice.


Catalog No. 11-808-1129-01 Page 2 of 4
Liquid Flow Switch
#SF1K-US-C – 6/28/2024
Installation and Operation

Mounting Instructions

• The cut-off value must be greater than or equal to of the minimum necessary flow to guarantee the
protection of the system.
• In case that the flow switch is used as a flow limiter, it is necessary to add another device
downstream for alarm condition activation. The controller must conform to the requirements of the
DIN EN 50156-1 :2016-03.
Caution
• Use gaskets and threads according to DIN EN 10242 only.
• If the flow switch is used as a minimum flow controller, you must add another device downstream
for alarm condition activation.

After the recalibration and the


verification of the switch point on
the site its recommended to seal the
Tips regulation screw and take note of
the value.

NOTE The device is delivered in the minimum cut off


condition.

1. The flow switch may be positioned with the casing


above in a horizontal or vertical position far from
elbows or narrowing. The arrow must be oriented
downstream.
2. If pipe is vertical, reset range to balance paddle
weight.
3. If the device is toward the bottom, look for slags, and
apply it in a straight pipe of least five times the tube diameter, both upstream and downstream, far from filters, valves,
etc.
4. After successful installation, ensure the paddle moves freely into
the tube. At the minimum necessary flow, set the regulation
screw until the electrical circuit turns off.
5. Ensure that the connector doesn't come out of the internal
circumference of the pipes.
6. With a screwdriver press lightly up to obtain the click of the micro
switch.
7. With the presence of flow to the admitted minimum range,
regulate the screw C up to obtain the opening of the red/ white
contact.

Specifications subject to change without notice.


Catalog No. 11-808-1129-01 Page 3 of 4
Liquid Flow Switch
#SF1K-US-C – 6/28/2024
Installation and Operation
Wiring Instructions

Connect the red and white contacts of the microswitch. The contact
red-white opens when the flow drops below the set level. When there
is no flow the contact red-blue closes and can be used as a signal or
alarm contact.

Appendix – Symbols Key

Potential for death, serious injury, or permanent damage to a system.


Warning

Potential for injury, damage to a system, or system failure.


Caution

Useful information not related to injury or system damage.


Tip

W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling center. Do not
dispose of with household waste. Do not burn.

Specifications subject to change without notice.


Catalog No. 11-808-1129-01 Page 4 of 4