19427-Maly - Manua - L 2023 Tyco Fv411f Bez Kamery Plamenny - Hla - Sic
19427-Maly - Manua - L 2023 Tyco Fv411f Bez Kamery Plamenny - Hla - Sic
A clearance of 200 mm, in all directions, from the A drilling template is provided to allow optimum
fixing point will normally be sufficient to allow selection of the fixing centres.
the full range of adjustment as shown in Fig. 2. Interface Mode 4-20 mA Relay MODBUS MX Conventional
4 - 20 mA and 9 9 9 2 2
122 mm
Relay (Default)
Conventional 2 2 2 2 9
4-20 mA 9 2 9 2 2
MX 2 2 2 9 2
4-20 mA with 9 9 2 2 2
HART*
181 mm
Delay Settings
92 mm
Off On Medium 6s in 8s window 10s
94 mm
On Off Long 12s in 14s window 10s
Fig. 2: Adjustable Mounting Bracket and Surface Mounting Dimensions
On On Short 3s in 5s window 10s
1 To secure the mounting bracket onto the 2 To secure the detector onto the mounting Table 9: Delay Settings
chosen surface: bracket: The alarm hold time is configurable using the PC400. The default is 10s.
– Use four M8 bolts, studs or screws at the – Use M6 bolts, stud or screws at the fixing In the MX mode these options may be set in MX Consys and configured by the panel, see SW2-5.
fixing centres. (Refer to the orientation as centres shown in Fig 3.
shown in Fig 1). Range Settings MX Configuration
SW1-4 SW1-5 Range Set the MX Loop Address
1 Connect the detector to the 801AP (Address
Off Off Normal (33 m) Programming Tool)/ 850EMT (Engineering
Off On Half (0.5x) (15 m) Management Tool) via the ancillary
programming lead that plugs into the back of
On Off Close (0.25x) (6 m) the detector (see Fig. 15).
On On Extended (2x) (65 m) 2 Select the MX interface mode on the detector
and enable DIP switch settings (SW1-1, SW2-
Table 10: Range Settings 3 and, SW2-4 On).
In MX mode the normal, half, and extended options 3 Enable programming mode by switching DIP
may be set in MX Consys and configured remotely by switch SW2-7 On.
the panel, see SW2-5. The close option can only be set 4 Connect the programmer to the detector and
on the DIP switches. set the address as required.
5 Disconnect the programmer.
2/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 19/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
156 mm
139 mm
SW2-3 Interface See Table 8
99 mm
SW2-4 Interface See Table 8
4-20 mA Modes Band mode (Discrete) Continuous (Variable)
SW2-5 mode b
MX Mode MX Consys Options DIP Switch Options
FV411 RANGE : 2 x 20 mm GLAND HOLES
4-20 mA Modes HART Disabled HART Enabled
SW2-6 MX Mode Must be set to OFF Must be set to OFF 94 mm
155 mm
4-20 mA Modes Normal bands c Enhanced bands Fig. 3: FV400 Series of Detectors-Overall Dimensions
SW2-7 MX Mode Loop mode Programming mode
Temporary Weatherproof cover
SW2-8 Set to OFF (For future use)
The back-box is supplied with a cover that
Table 6: DIP Switch 2 Settings protects the wiring from the weather.
If the top-case is not fitted straight away then fit CAUTION
a – Optical Path Monitoring (OPM) - Check for window cleanliness
b – HART is not supported in Continuous (Variable) mode the Weatherproof cover to protect the wiring.
c – This mode is equivalent to the S241f+ discrete mode bands This cover does not make the back-box THE FITTING OF THIS TEMPORARY
flameproof. WEATHERPROOF COVER DOES NOT CONSTITUTE
COMPLETION OF THE CERTIFIED ASSEMBLY
18/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 3/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
4/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 17/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
Fitting the EMC clamp If it is not feasible to use a nylon gland washer or
Walk-Test Input and LED 1 Remove about 120 mm of outer sleeving at the where an anti-seizing union is required, the
end of the cable. threads of the flameproof glands or stopping plugs
may be sealed using any non-setting grease or
2 Fold the cable drain wire back over the end of
putty as described in BS EN 60079-14:1997.
the cable and shorten the length to 20 mm.
Fuchs Lubritech PBC/D is a metal-loaded, mineral
3 Wrap the copper tape around the end of the
oil-based grease suitable for sealing glands, which
cable over the drain wire.
can be purchased locally.
4 Pass the cable through the cable gland, sealing
washer, and the clamp with the copper tape Enclosure Sealing
resting over the clamp.
5 Slide the cable backwards to position wrapped NOTICE
drain wire in the clamp. The Front Cover must be fitted with the
6 Fit the loose part of the EMC clamp over the O-ring before fitting to the back box to
cable. ensure that the enclosure is properly
7 Tighten the cable gland and then, tighten the sealed against environment and dust.
screws on the EMC clamp (See Fig. 5).
IP66/67 Cable Entry Sealing Assembling the Detector to the Back Box
CAUTION CAUTION
Cable glands and stopping plugs MUST The safety chain MUST be used while
be certified to the required standard. assembling the detector to prevent the
They must be properly sealed to prevent Top Case from falling while it is
the ingress of moisture to meet the removed.
IP66/67 requirements.
Remote Ensure that the screw link is securely
Cable glands MUST be sealed to the closed to attach the Top Case to the
LED
4 K7Ω 1.8 KΩ 15 KΩ detector housing by fitting a sealing back-box.
washer between their flange and the
housing to meet the IP66/67
requirements.
How to fit the detector
Reset Alarm Window Fault
Test Test 1 If fitted, remove the Temporary Weatherproof
Test
cover from the backbox.
Only cable glands incorporating an inner cable seal
should be used. In exposed outdoor areas, it is 2 Check that the wiring is correct and that all the
Fig. 14: Walk-test input and remote LED wiring diagram recommended that a shroud be fitted over the pins on CON1 and CON2 (see the wiring
1. Do not use ancillary 0 V for wired input and remote LED. cable glands. diagrams from Fig. 7 to Fig. 14) on the terminal
2. LED drive current limited to 3 mA. No current-limit resistor is required. PCB in the base of the back-box are straight.
In applications where the ambient temperature is
3. LED voltage should be less than 3 V. expected to be 40oC or higher, cable glands with Ensure that the internal wiring will not be
the inner seal must be used and, when fitted, the trapped between the terminal blocks and the
Switch and Header Settings Configuration of DIP Switches shroud must be made of CR rubber. front assembly.
The unused cable gland entries must be fitted Ensure that no moisture will be trapped inside
The FV400 Series of detectors are very flexible The FV400 Series of detectors hardware has two
with a suitable stopping plug. One stopping plug is the housing.
and can be configured for a wide range of banks of eight DIP switches (SW1 and SW2) to
applications. For ease of installation the most configure basic detector options. If the switches supplied with the detector. The recommended 3 Split the safety chain into two parts by undoing
common, basic options are available on DIP are changed, the detector must be powered off types are those with a mushroom head and an the screw link (see Item 4 in Fig. 6).
switches located on the back of the detector. and switched on for the alterations to take integral ‘O-ring’. Fit part 1 of the safety chain to one of the M6
Advanced options, such as entering location effect. The detector is supplied in the default The glands/stopping plugs should be hand- bolts at the bottom of the back-box (see Item 2
information for the video display are set using tightened with the addition of, at least, a further 1/ in Fig. 6).
the PC400 configuration tool. 4 turn applied by spanner or other suitable tool.
16/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 5/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
Attach part 2 of the safety chain to the Top RS485 (Modbus) and Video
Case (see Fig. 6) using M6 washer between
the bolt head and the chain.
4 Hold the Top Case in two hands, one on each TO
RQ C
side, and then bring the unit up to be in front UE ABL TYCO TW16 5DB UK
CO E ENT T
of the back-box. VER
BOL
RIES: M
20 CABLE RA
TS (MIN. GRADE A4-7
5 Introduce the alignment pin into the barrel at
the top of the back-box and guide the detector
into position. 3
2
6 Push the Top Case firmly into the back-box 1
until it is fully in.
Do this slowly by pushing the Top Case down
in several stages to allow the air inside to
100R
escape.
7 Hand-tighten the four top-case M6 bolts Part 1 of 4
Safety Chain Part 2 of
seem 3 in Fig. 6).
Safety Chain
8 Then, use a a torque wrench (set to a
maximum force of 7 lb.ft (10 Nm)) to tighten
the M6 bolts to correct torque.
9 Join the two parts of the safety chain together Detail of M5 bolt
using the ‘L-shaped’ screw link (see Item 6 in Item 1
Fig. 6). 5
10 Adjust the angle of the detector to cover the
required field of view and then tighten the M8 6 RS485+
fixing nuts and bolts on the bracket. RS485+
RS485-
RS485-
Fig. 6: Safety Chain Connection
1– M5 bolt on the Underside of Top Case Video to Passive
2– M6 bolt on the Bottom of Back-box Or
3– Socket Cap Retaining M6 Top Case bolt Active Balun
4– Safety Chain
5– Washers Fig. 13: RS485 and video wiring diagram
6– L’-Shaped Screw Link 1. EOL Termination resistor (100R) to be fitted at each end of RS485 bus.
2. Dotted lines show the connections to the next detector on the RS485 network. If this is the last detector in the
network, then fit the EOL resistor as shown.
3. The RS485 and video must be powered from an ancillary supply or the main detector supply by fitting HDR3
and HDR4.
6/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 15/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
Main/Loop Main power input used to 4-20 mA -VE 4-20 mA Output -VE
operate the detector Alarm Relay Alarm relay contact - CON4
(DC/Zone/Loop) NC/NO selects NC/NO
Ancillary Power input used for options: Alarm Relay Alarm relay contact common
Power Window heater COM
RS485
Alarm Relay Alarm relay contact common
Camera/Video COM
HDR3
Table 1: Power Supplies Fault Relay Fault relay contact - CON5
0V 0V NC/NO selects NC/NO
HDR4
+24 V +24 V Fault Relay Fault relay contact common
COM
For Relay and 4-20mA interfaces fit HDR3 and HDR4 to use the Main Supply to provide Ancillary
Power. Do not fit HDR3 and HDR4 when using the MX Loop or Conventional Zone interfaces. Fault Relay Fault relay contact common
COM
Fig. 12: Ancillary Power Wiring Diagram Table 2: Left-hand Side Terminals
1. For relay and 4-20 mA modes the ancillary power must be provided from the main detector supply. Fit HDR3
and HDR4 to use the Main Supply only.
2. For MX and conventional interfaces a separate Ancillary Power Supply must be used. Do not fit HDR 3 or HDR 4.
3. Dotted lines show ancillary supply connections to next detector.
14/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 7/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
Conventional Zone
Terminals Description Terminals Description
WTEST/LED 0 V 0 V for Walk-test Input VIDEO -VE Video output -VE
and Remote Indicator (balanced line)
(LED) Output
Table 3: Right- hand Side Terminals (cont.)
WTEST Walk-test Input
RLED Remote indicator Links Description
(LED) output
HDR1 Fit to connect 4-20 mA -VE to 0 V in
Zone EOL
Network (RS485) Network (RS485) port - Sink mode
+VE twisted pair +VE
HDR2 Fit to connect 4-20 mA +VE to
Network (RS485) Network (RS485) port - +VE IN in Source mode
+VE twisted pair +VE
HDR3 Fit HDR3 and HDR4 to connect
Network (RS485) -VE Network (RS485) port - Detector and Ancillary power
twisted pair -VE HDR4 together to use a single power
source.
Network (RS485) -VE Network (RS485) port -
twisted pair -VE Do Not fit HDR3/HDR4 with the
Conventional Zone or MX Loop
Ancillary Supply +VE Ancillary supply output interfaces.
OUT to next detector
CON4 Select NC/NO contact for Alarm
Zone+
Ancillary Supply 0 V Ancillary supply output relay output Zone-
OUT to next detector
CON5 Select NC/NO contact for Fault Zone+
Ancillary Supply +VE Ancillary supply (DC) relay output Zone-
IN +VE
Table 4: Links
Ancillary Supply 0 V Ancillary supply (DC) Fig. 11: Conventional Zone Wiring Diagram
IN 0V
Wiring Diagrams 1. Zone end of line (EOL) resistor fitted in last detector. Otherwise connect to next detector as shown.
VIDEO +VE Video output +VE 2. If the window heater is required, then the ancillary power MUST be used, see Fig. 12.
For details on the wiring connections of the
(balanced line) 3. DO NOT FIT HDR3 OR HDR4 (the ancillary functions must not be connected to the zone circuit).
different interfaces of the FV400 Series of
4. Dotted lines show power connections to the next detector in the Conventional Zone. If this is the last detector on
detectors, see the wiring diagrams from Fig. 7 to
Table 3: Right- hand Side Terminals the zone, then fit the EOL resistor (as shown).
Fig. 14.
5. See Figs. 12 to 14 for wiring of ancillary power, walk-test input and remote indicator output
8/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 13/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
+24 V
+24 V 0V
0V
Monitor
Links
-VE
ALARM FAULT
CON4:NO CON5:NC
12/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 9/20
FV400 Triple IR Flame Detectors Triple IR Flame Detectors FV400
0V
+24 V
Monitor
Links
Loop Loop Loop Loop
-VE +VE -VE +VE HDR1
Select SINK
Fig. 8: MX Loop Wiring Diagram Mode
1. Ancillary power MUST be used for RS485, window heater or video options, see Fig. 12.
2. Do not fit links HDR3 or HDR4 (the ancillary functions must not be connected directly to the MX Loop). Fig. 9: 4-20mA Sink Wiring Diagram
3. Dotted lines show the loop connections to the next detector in the MX loop. 1. Fit link HDR1 to connect 4-20 mA- to 0 V.
4. Other options can be used at the same time as the MX loop. See Figs. 12 to 14 for wiring of ancillary power, 2. Monitor current from 24 V rail into 4-20 mA+.
walk-test input, remote indicator output, RS485, and video output. 3. If ancillary power is required for RS485, window heater, or video, use the main detector supply by fitting HDR3
and HDR4.(see Fig. 12).
4. Other options can be used at the same time as the 4-20 mA output. See Figs. 12 to 14 for wiring of ancillary
power, walk-test input, remote indicator output, RS485 and video output.
5. The 4-20 mA sink mode does not support HART.
10/20 Fixing Instructions Doc. version 9.0 Fixing Instructions Doc. version 9.0 11/20