Technical specification document for procurement of
CPCBIV+ compliant DG sets for NS-CFS JNPT
Scope
Design, Engineering, Manufacturing, Inspection, Testing, Supply, Delivery,
Supervision of Installation and Commissioning of 02 No. 650 kVA CPCB IV+
Compliant Diesel Gensets at NS-CFS JNPT.
Schedule of quantities
ITEM NO ITEM DESCRIPTION QTY.
1 Supply of 01 No. 650 kVA CPCB IV+ Compliant 02
Diesel Genset (DG Set) with Acoustic Enclosure
along with TPI, complete as per attached
Technical Specifications. Scope includes
Unloading of the DG Set at Site. The supplied
DG Set (Complete Package) shall be covered
under OEM Warranty for a period of 02 Years
from the date of Commissioning.
MAX. OUTPUT VOLTAGE: 415 V; NUMBER OF
PHASES: 3 PHASE PLUS NEUTRAL;
Scope of supply & work
Scope of work covers the minimum requirements for the design, manufacturing,
procurement of materials and inspection, testing, supply, packing, shipment, and
delivery to site of CPCB IV+ Compliant Diesel Generator Package.
The scope of supply shall be in accordance with the latest revision of Data
sheets, Specifications along with documents specified herein and applicable
codes and standards. The Vendor shall be fully responsible for the design,
material, manufacturing, inspection, testing at works and site, delivery, and
supervision of installation and perform commissioning of the DG Set Package at
site.
Diesel Generator set rating shall be the Prime Rated Apparent Power output
(kVA), in accordance with ISO 8528, of the set at the design conditions specified
for the site. Vendor shall account for the temperature rise inside the acoustic
enclosure during full load operation. The enclosure ventilation system shall be
designed accordingly. Diesel Generator set shall be located outdoor in an
acoustic enclosure. Acoustic enclosure shall house the Diesel Generator set skid,
control panel, as well as the battery bank.
Exhaust piping bends etc. and necessary hardware and supporting material as
per CPCB norms shall be supplied by Vendor for safe and standard installation at
site. Height of building to be consider for sizing of exhaust stack.
This scope of work which includes Dismantling of existing DG set and
exhaust stack and related works for Both 600 KVA and 400 kVA DG sets.
Installation and commissioning
Vendor shall provide qualified personnel to supervise the installation and
carryout site testing and commissioning of equipment supplied under this
contract. Supervision personnel and equipment: The supplier shall provide, at
fixed cost, for qualified and experienced Supervision Personnel for the
supervision of installation, site testing, pre commissioning, commissioning, and
hook-up. The supervision shall include the provision of any special equipment/
tools required to carry out the above stated activities, all local costs including
accommodation, transportation, meals etc. and the cost for mobilization and
demobilization.
Data requirement list
Technical data sheets
Assembly drawings – GA, Cross-sectional views, cubical arrangement, installation
planning, cut-out, and mounting details
Electrical wiring details -SLD, schematic drawings,
Bill of materials
Calculation -Battery sizing, CT, PT, Relay setting
QA plan of vendor
Installation plan and testing procedure, TPI Testing reports.
Manuals
DG set technical specifications.
Genset data
Parameter DP world requirement
KVA RATING 650 KVA
DUTY Prime (As per ISO 8528)
VOLTAGE & FREQUENCY 415 V/ 240V, 50 Hz
NO. OF PHASES 3
. POWER FACTOR 0.8 (LAGGING)
SPEED 1500 RPM
OVERLOAD PERMITTED FOR PRIME 10% overload permitted for 1 hour in
RATING every 12 hours consecutive run.
CPCB COMPLIANCE CPCB IV+ & 75 dBA @ 1 m distance
from skid edge as per latest CPCB
Norms
Engine data
Parameter DP world requirement
Make Approved Makes: Cummins India Ltd.,
Kirloskar Oil Engines Ltd, Perkins
Starting system 24V DC Electrical Battery Approved
Makes: EXIDE AMARON Battery
Charger Approved Makes NHP
Meanwell Cummins, connect well
Specific fuel consumption (kg/kWhr): 10% Overload Full Load 75% Load
50% Load 25% Load
Alternator Specification
Parameter DP world requirement
Make Approved Makes: Stamford, Kirloskar,
LEROY‐SOMER
Enclosure IP23 MIN.
Voltage regulation +/- 0.5%
Class of insulation H
Waveform distortion/Total harmonic No load < 1.5%, Non distorting
distortion balanced linear load < 5 %
Maximum Unbalanced Load across less than or equal to 25%
phases
DG Synchronising panel
A DG INCOMER-650KVA 2
1000A TP 50KA EDO, ACB Microprocessor based
1 release for (O/L, S/C & E/F) Protection with U/V L&T U Power1G/ABB/Siemens
Release, CT
2 Breaker Control Switch,25A Kaycee
3 185 TP Power Contactor, 240V AC, AC3 Duty C&S
4 Digital Multifunction Meter with RS 485. SECURE
5 1000/1A CT 15VA, Accuracy CL-1.0 Saviour
5 ELR WITH CBCT PROK DVS
Restricted Earth fault Relay (numerical type)
6 ABB
REF615
7 1000/1A CT 15VA, Accuracy CL-PS Saviour
8 Indicating Light (R, Y, B, Trip, ON, OFF, DC) C&S
9 Toggle Switch C&S
1
Push Buttons C&S
0
1 Emergency Stop Push Button (Stay put Type) with
C&S
1 Lockout Tagout Arrangement
1
Auto/ Manual OFF Sel. Switch 3P, 3way Kaycee
2
1
Control MCB,10KA, C-Curve C&S
3
1
Aux. Contactor C&S
4
1
Aux. Relay Salzer
5
1
Hooter, 96Sq.mm., Electronic Type, 24V DC Reputed
6
1 4W Annunciator with T/A/R Push Button with Hooter
Minilec /GIC
7 Contact, 24V DC
1
Cranking Relay, 2 C/O, 24V DC PLA
8
1 CVCC Battery Charger I/P-230V AC, O/P-24V DC,12A
Jakson
9 DCA, DC V
2
On Delay Timer EAPL/GIC
0
2
Terminal Elmex
1
2
GCU WOODWARDS/DEEPSEA
2
2
Master Trip Relay Reputed
3
2 Reputed
Annunciation
4
2 Reputed
Ammeter Analog
5
2 Reputed
Voltmeter Analog
6
2 Reputed
Ampere Selector Switch -ASS
7
2 Reputed
Voltage Selector Switch -VSS
8
2
Panel LED Light & 16A Socket Reputed
9
B OUTGOING 2000A 1
2000A FP 50KA EDO, ACB Microprocessor based
1 L&T U Power1G/ABB/Siemens
release for (O/L, S/C & E/F) Protection
2 Breaker Control Switch,25A Kaycee
3 Digital Multifunction Meter with RS 485. SECURE
4 2000/1A CT 15VA, Accuracy CL-1.0 Saviour
5 Indicating Light (R, Y, B, Trip, ON, OFF) C&S
6 Auto/ Manual OFF Sel. Switch 3P, 3way Kaycee
7 Control MCB,10KA, C-Curve C&S
Restricted Earth fault Relay (numerical type)
8 ABB
REF615
9 Master Trip Relay Reputed
1
Ammeter Analog Reputed
0
1
Ampere Selector Switch -ASS Reputed
1
1
Panel LED Light & 16A Socket Reputed
2
C 3 Phase Voltage Monitoring Relay Minilec/Eqv
Fuel Day Tank.
Parameter DP world requirement
Fuel Day Tank. for 12 hours continuous operation at
full load subject to max. 990lts.
Level Transmitter Suitable make and model for
communicating with PLC-AMF Panel.
Supply of Fuel Pipe and Valve of Min. 15m Length to be supplied.
suitable size for connection of Day Bidder to Advise.
Tank with Internal Tank of DG Set.