Syslib Rm035 en P
Syslib Rm035 en P
IMPORTANT This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.
For Rockwell Automation Library of Process Objects version 5.0, see
• PROCES-RM200
For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:
• PROCES-RM013 contains logic instructions
• PROCES-RM014 contains display elements
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface Software Compatibility and Content Revision. . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mix-proof Valve (P_ValveMP) Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Required Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mix-proof Valve Input Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mix-proof Valve Output Structure . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mix-proof Valve Local Configuration Tags . . . . . . . . . . . . . . . . . . 21
Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Programming Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
State Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Mode Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Using Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Quick Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Mix-proof Valve Faceplate Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Notes:
For the latest compatible software information and to download the Rockwell
Automation® Library of Process Objects, see the Product Compatibility and
Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
PlantPAx® Distributed Control System Selection Guide, Provides information to assist with equipment
publication PROCES-SG001 procurement for your PlantPAx system.
PlantPAx Distributed Control System Reference Manual, Provides characterized recommendations for
publication PROCES-RM001 implementing your PlantPAx system.
Rockwell Automation Library of Process Objects, Provides general considerations for the PlantPAx system
publication PROCES-RM002 library of process objects.
FactoryTalk® View Machine Edition User Manual, Provides details on how to use this software package for
publication VIEWME-UM004 creating an automation application.
FactoryTalk View Site Edition User Manual, Provides details on how to use this software package for
publication VIEWSE-UM006 developing and running human-machine interface
(HMI) applications that can involve multiple users and
servers, distributed over a network.
Logix5000™ Controllers Add-On Instructions Programming Provides information for designing, configuring, and
Manual, publication 1756-PM010 programming Add-On Instructions.
Rockwell Automation Library of Process Objects Common Details how to monitor an input condition to raise an
Alarm Block (P_Alarm) Reference Manual, publication alarm. Information includes acknowledging, resetting,
SYSLIB-RM002 inhibiting, and disabling an alarm.
Rockwell Automation Library of Process Objects: Interlocks Explains how to collect (sum up) the interlock
with First Out and Bypass (P_Intlk) Reference Manual, conditions that stop or de-energize a running or
publication SYSLIB-RM004 energized piece of equipment or prevent it from
starting or being energized.
Rockwell Automation Library of Process Objects Common Explains how to select the Mode (owner) of an
Mode Block (P_Mode) Reference Manual, publication instruction or control strategy. The Mode instruction is
SYSLIB-RM005 usually embedded within other instructions to extend
their functionality. It is possible to use a standalone
Mode instruction to enhance a program where modes
are wanted.
Rockwell Automation Library of Process Objects: Permissives Details how to collect permissive conditions to start a
with Bypass (P_Perm) Reference Manual, publication piece of equipment.
SYSLIB-RM007
Rockwell Automation Library of Process Objects: 2-state Explains how to monitor stroke times and stroke counts
Valve Statistics (P_ValveStats) Reference Manual, for a 2-state (open and close) valve.
publication SYSLIB-RM036
Global Objects
Guidelines Use this instruction if you want to operate a discrete mix-proof valve.
Functional Description The P_ValveMP Add-On Instruction provides the following capabilities:
• Operates a mix-proof valve with the following positions:
– Closed
– Opened
– Lift upper seat (optional)*
– Lift lower seat (optional)*
– CIP/SIP leakage cavity (optional)
– CIP/SIP upper seat (optional)*
– CIP/SIP lower seat (optional)*
The asterisk (*) indicates that the position has an option to pulse the seat
being cleaned or lifted opened and closed to provide enhanced cleaning.
(As the seat is popped open and closed, the flow velocity across the seat is
increased compared to the fully open seat position.) Pulse times are
configurable
• Operated by using a state model that makes sure that valve seats are
sequenced properly to avoid cross-contamination
See page 49 for the valve state diagram
• Provides six outputs and six inputs. The outputs in each valve state
(including intermediate states) are configurable for on and off states. The
inputs that verify each valve state are configurable for their required on,
required off, and don't care states. Provides feedback checking to make sure
the valve reaches each position, including intermediate positions before
moving to the next position. The time for feedback inputs to confirm each
state is configurable
• Graphic symbols are provided for mix-proof valves in 2-D layouts and
3-D (isometric) layouts for ease in building valve array and routing
manifold displays
• Provides inputs for Permissive conditions to enable moving the valve from
the closed state
• Provides inputs for Interlock conditions to drive the valve to the closed
state
• Monitors for I/O communication faults and closes the valve and alarms on
a fault
• Provides an ‘available’ status for Program mode logic so automation code
can know whether the valve can be controlled
• Provides a valve simulation capability. When the mix-proof valve is being
simulated, outputs are left de-energized, and the instruction behaves as if a
fully functioning valve were providing feedback
Required Files Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This lets you create your own
instruction set for programming logic as a supplement to the instruction set
provided natively in the ControlLogix® firmware. An Add-On Instruction is
defined once in each controller project, and can be instantiated multiple times in
your application code as needed.
Controller File
The P_ValveMP_3_5-00_AOI.L5X Add-On Instruction must be imported into
the controller project to be used in the controller configuration. The service
release number (boldfaced) can change as service revisions are created.
Visualization Files
This Add-On Instruction has associated visualization files that provide a
common user interface. These files can be downloaded from the Product
Compatibility and Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
IMPORTANT The visualization file dependencies require Process Library content imports to
occur in a specific order as reflected in the following tables:
• Images
• Global Objects
• Standard Displays
• HMI Tags
• Macros
Images are external graphic files that can be used in displays. They must be
imported for FactoryTalk View to make use of them.
When PNG files are imported, they are renamed by FactoryTalk View with
a .bmp file extension, but retain a .png format.
Table 2 - Visualization Files: Images (.png)
FactoryTalk View SE Software FactoryTalk View ME Software Description
All .png files in the images folder All .png files in the images folder These are the common icons used in the global objects and
standard displays for all Process Objects.
The Global Object files (.ggfx file type) in the following table are Process Library
display elements that are created once and referenced multiple times on multiple
displays in an application. When changes are made to a Global Object, all
instances in the application are automatically updated.
Table 3 - Visualization Files: Global Objects (.ggfx)
FactoryTalk View SE Software FactoryTalk View ME Software Description
(RA-BAS) Common Faceplate Objects (RA-BAS-ME) Common Faceplate Objects Global objects used on process object faceplates.
(RA-BAS) P_ValveMP Graphics Library (RA-BAS-ME) P_ValveMP Graphics Library P_ValveMP global object device symbols used to build
process graphics.
The Standard Display files (.gfx file type) in the following table are the Process
Library displays that you see at runtime.
Table 4 - Visualization Files: Standard Displays (.gfx)
FactoryTalk View SE Software FactoryTalk View ME Software Description
(RA-BAS) Common-AnalogEdit N/A Faceplate used for analog input data entry. The FactoryTalk
View ME faceplates use the native analog input data entry
so no file is required.
(RA-BAS) P_Alarm-Faceplate (RA-BAS-ME) P_Alarm-Faceplate The faceplate that is used for managing alarms for
the object.
(RA-BAS) P_Alarm-Help (RA-BAS-ME) P_Alarm-Help Alarm Help information that is accessed from the
P_AIarm faceplate.
(RA-BAS) P_Mode-Config (RA-BAS-ME) P_Mode-Config The Configuration Display used to configure the
P_Mode object.
(RA-BAS) P_Mode-Help (RA-BAS-ME) P_Mode-Help Mode Help information that is accessed from the
Help faceplate.
(RA-BAS) P_ValveMP-Config (RA-BAS-ME) P_ValveMP-Config The Configuration Display used to configure the
P_ValveMP object.
(RA-BAS) P_ValveMP-Faceplate (RA-BAS-ME) P_ValveMP-Faceplate The faceplate that is used for the object
(RA-BAS) P_ValveMP-Quick (RA-BAS-ME) P_ValveMP-Quick The Quick display that is used for the object
(RA-BAS) Process Valve Family-Help (RA-BAS-ME) Process Valve Family-Help The Help display for Valve objects
(RA-BAS) P_Intlk-Faceplate (RA-BAS-ME) P_Intlk-Faceplate Optional
The interlock faceplate used for the object.
Use this file if your Discrete Output has an associated
P_Intlk object and you enable navigation to its faceplate
from the Discrete Output faceplate.
(RA-BAS) P_Perm-Faceplate (RA-BAS-ME) P_Perm-Faceplate Optional
Permissive faceplate that is used for the object
Use this file if your object has an associated P_Perm object
and you enable navigation to the P_Perm faceplate from
the object faceplate.
(RA-BAS) P_ValveStats-Faceplate (RA-BAS-ME) P_ValveStats-Faceplate Optional
Valve statistics faceplate display that is used for the object
Use this file if your object has an associated P_ValveStats
object and you enable navigation to the P_ValveStats
faceplate from the object faceplate.
Controller Code This section describes the parameter references for this Add-On Instruction.
Configuration parameters that are arrayed, string, or structure data types cannot
be configured as parameters for Add-On Instructions. Configuration parameters
of these types appear as local tags to the Add-On Instruction. Local tags can be
configured through the HMI faceplates or in Studio 5000 Logix Designer®
application by opening the Instruction Logic of the Add-On Instruction instance
and then opening the Data Monitor on a local tag. These parameters cannot be
modified by using controller logic or Logix Designer application
export/import functionality.
Table 8 - Local Configuration Tags
Tag Name Data Type Default Description
Cfg_Desc STRING_40 'Mix Proof Valve' Description for display on HMI. This string is shown in the title bar of the faceplate.
Cfg_Label STRING_20 'Valve Control' Label for graphic symbol displayed on HMI. This string appears on the graphic symbol.
Cfg_Tag STRING_20 'P_ValveMP' Tagname for display on HMI. This string is shown in the title bar of the faceplate..
Cfg_OutStateTbl SINT [11] [0] 2#0000_0000 Valve state tables showing, respectively, output states in given valve state, feedback
[1] 2#0000_0001 inputs required (checked) to achieve valve state, and feedback input states to achieve
[2] 2#0010_0000 valve state.
[3] 2#0010_0010 The array index ([0]…[10]) indicates the device state as follows (per the state diagram
in the manual):
[4] 2#0000_0100
[5] 2#0000_1000 Index Function
[6] 2#0001_0000
[7] 2#0001_0100 [0] (intermediate state) De-energized
[8] 2#0011_0100 [1] Closed
[9] 2#0001_1000
[10] 2#0011_1000 [2] (intermediate state) Close cavity outlet
Operations This section describes the primary operations for Add-On Instructions.
Modes
This instruction uses the following standard modes, which are implemented by
using an embedded P_Mode Add-On Instruction.
Table 9 - Modes
Mode Description
Operator The Operator owns control of the device. Operator commands (OCmd_) and Operator settings
(OSet_) from the HMI are accepted.
Program Program logic owns control of the device. Program commands (PCmd_) and Program settings
(PSet_) are accepted.
Override Priority logic owns control of the device and supersedes Operator and Program control. Override
Inputs (Inp_OvrdCmd and other Inp_OvrdXxxx values) are accepted. If so configured,
bypassable interlocks and permissives are bypassed.
Maintenance Maintenance owns control of the device and supersedes Operator, Program, and Override
control. Operator commands and settings from the HMI are accepted. Bypassable interlocks and
permissives are bypassed, and device timeout checks are not processed.
Hand Hardwired logic or other logic outside the instruction owns control of the device. The instruction
tracks the state of the device for bumpless transfer back to one of the other modes.
No Mode The device is disabled and has no owner because the EnableIn input is false. The main
instruction Logic routine is not being scanned. See Execution section for more information on
EnableInFalse processing.
Alarms
This instruction uses the following alarms, which are implemented by using
embedded P_Alarm and P_Gate Add-On Instructions.
Simulation
Simulation in P_ValveMP disables the normal outputs and provides the feedback
of a working valve.
You must set the Inp_Sim parameter in the controller to ‘1’ to enable simulation.
When you have finished in simulation, set the Inp_Sim parameter in the
controller to ‘0’ to return to normal operation.
Execution
Condition Description
EnableIn False (false rung) Handled the same as if the device were Disabled by
Command. The device outputs are de-energized and the
device is shown as Disabled on the HMI. The mode is
shown as ‘NO MODE’. All alarms are cleared.
Powerup (prescan, first scan) On prescan, any commands received before first scan are
discarded. The device is de-energized. On first scan, the
device is commanded to the closed state.
Embedded P_Mode and P_Alarm instructions are
handled in accordance with their standard powerup
procedures.
See Rockwell Automation Library of Process Objects:
Common Mode Block (P_Mode), publication SYSLIB-
RM005, and Rockwell Automation Library of Process
Objects: Common Alarm Block (P_Alarm), publication
SYSLIB-RM002, for P_Mode and P_Alarm instructions,
respectively.
Postscan No SFC Postscan logic is provided.
Programming Example This example uses the P_ValveMP instruction to implement a mix-proof valve
feeding bulk material (safflower oil) from a storage silo into a mixer.
For this example, the mix-proof valve connects to the control system by using two
inputs and three outputs. The manufacturer's data sheet for the valve shows the
following information.
In the closed position (all outputs off ), flow is not directed anywhere and the
valve cavity is vented to waste recovery. In the open state, flow is directed from
the upper line to the lower line. In the Lower Lift position, flow is directed from
the lower line through the valve cavity to waste recovery. In the Upper Lift
position, flow is directed from the upper line through the valve cavity to waste
recovery.
The P_ValveMP instruction for this valve is configured as shown in the following
diagram.
The two limit switches from the field are connected into inputs Inp_LowerLS
and Inp_UpperLS. The three outputs to the field are connected to Out_Open,
Out_LiftLower, and Out_LiftUpper.
From the Engineering Tab Page 1 Description on page 45, the descriptive strings
and supported states are configured.
Parameter Description
Cfg_Desc Safflower Oil T-47 to Mixer M-5
Cfg_Label Safflower T-47 / M-5
Cfg_Tag XV-5047
Cfg_HasLiftLower, Cfg_HasLiftUpper 1 (checked)
Cfg_HasSIPCavity, Cfg_HasSIPLower, Cfg_HasSIPUpper 0 (unchecked)
From the Engineering Tab Page 4 Description on page 49, the state configuration
can be accessed and modified. For this example, we have to configure six states.
There are three outputs only, so for each state, the outputs for Close, Cavity In,
and Cavity Out can be ignored. We will also ignore feedback states for feedback
that is not required. The example uses parameters for all ignored values set to 0.
From the faceplate, you can open the state configuration for all valve states
simultaneously to compare and configure the states. For example, Figure 1 shows
the state configuration for the Closed state.
On this message box, you set the states of the outputs, as well as the states of
required feedback inputs, for the given valve state.
TIP You can open the state configuration message boxes for multiple states
simultaneously. This can make it easier for you to check your selections against
the documentation for your particular valve and actuator.
Display Elements A display element (global object) is created once and can be referenced multiple
times on multiple displays in an application. When changes are made to the
original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, in conjunction with tag structures
in the ControlLogix system, aid consistency and save engineering time.
Table 10 - P_ValveMP Display Elements Description
Display Element Name Display Element Description
GO_P_ValveMP2D This Mix-proof Valve graphic object
allows for numerous orientations on
displays.
Each display element includes a touch field that accesses the object’s faceplate.
In addition, there is a tooltip that displays the object’s configured tag and
description.
State Indicators
The state indicator text changes and the graphic symbol color changes depending
on the state of the valve.
Color State Text
Blue Transition: Commanded to a new position and not there
yet.
Light yellow Indicates the following states: CIP/SIP cavity inlet,
CIP/SIP lower seat, CIP/SIP upper seat.
Dark gray Closed.
White Open.
Cyan Indicates the following states: Lift lower, Lift upper.
Status/Quality Indicators
One of these symbols appears on the graphic symbol when the described
condition is true.
Graphic Symbol Description
Invalid configuration.
TIP When the Invalid Configuration Indicator appears, you can find what
configuration setting is invalid by following the indicators. Click the graphic
symbol to open the faceplate. The Invalid Configuration indicator appears next
to the appropriate tab at the top of the faceplate to guide you in finding the
configuration error. Once you navigate to the tab, this indicator or a magenta
box identifies the misconfigured item.
For the Mix-proof Valve instruction, the Invalid Configuration indicator appears
under the following conditions:
• An alarm minimum on time, a valve feedback time, pulse time, or the valve
failure time is set to a value less than zero or greater than 2,147,483
seconds.
• Alarm Severity is set to a value less than 1 or greater than 1000.
• Invalid Feedback Time or Pulse Time (use 0…2,147,483 sec).
• Invalid Failure Time (use 0…2,147,483).
TIP When the Not Ready indicator appears, you can find what condition is
preventing operation by following the indicators. Click the graphic symbol to
open the faceplate. The Not Ready indicator appears next to the appropriate
tab at the top of the faceplate to guide you in finding the condition. When you
navigate to the tab, the condition preventing operation is flagged.
For the Mix-proof Valve instruction, the Device Not Ready indicator appears
under the following conditions:
• Device has been disabled by Maintenance.
• There is a configuration error.
• Interlock or Permissive is not OK.
• There is a device failure and shed requires a reset.
• There is an I/O Fault and shed requires a reset.
Mode Indicators
One of these symbols appears on the right side of the graphic symbol to indicate
the mode of the object instruction.
Transparent Program mode (if the default mode is Program and the current mode is Program, the mode
indicator is transparent).
Program mode (if the default mode is Operator).
Override mode
Hand mode
No mode.
TIP The images provided for the Operator and Program default modes are
transparent; therefore, no mode indicators are visible if the device is in its
default mode. This behavior can be changed by replacing the image files for
these mode indicators with images that are not transparent.
Alarm Indicators
One of these symbols appears on the left side of the label to indicate the described
alarm condition and the alarm border and label background change color. The
alarm border and label background blink if acknowledgement of an alarm
condition is required. Once the alarm is acknowledged, the alarm border and
label background remain the color that corresponds to the severity of the alarm.
No symbol No change in color No alarm or alarm inhibit condition, and all alarms
are acknowledged.
This symbol appears to the right of the label to indicate that a maintenance
bypass has been activated.
TIP When the Maintenance Bypass Indicator appears, you can find what condition
was bypassed by following the indicators. Click the graphic symbol to open the
faceplate. The Maintenance Bypass Indicator appears next to the appropriate
tab at the top of the faceplate to guide you in finding the bypass. Once you
navigate to the tab, this indicator identifies the bypassed item.
For the Mix-proof Valve instruction, the Maintenance Bypass indicator appears
when bypassable interlocks and permissives have been bypassed.
The global objects for P_ValveMP can be found in the global object file
(RA-BAS) P_ValveMP Graphics Library.ggfx.
1. Copy it from the global object file and paste it in the display file.
2. In the display, right-click the global object and choose Global Object
Parameter Values.
3. Type the tag or value in the Value column as specified in the Description
column.
TIP You can click the ellipsis (. . .) to browse and select a tag.
Values for items marked ‘(optional)’ can be left blank.
4. Click OK.
Quick Display The Quick Display screen provides a means for operators to perform simple
interactions with the P_ValveMP instruction instance. From the Quick Display,
you can navigate to the faceplate for full access for operation, maintenance, and
configuration.
Faceplate The P_ValveMP faceplate consists of five tabs and each tab consists of one or
more pages.
The faceplate contains the value of local configuration tags Cfg_Tag and
Cfg_Desc in the title bar.
The Operator tab is displayed when the faceplate is initially opened. Click the
appropriate icon at the top of the faceplate to access a specific tab.
Maintenance Diagnostics Help
Operator Tab
The Faceplate initially opens to the Operator (‘Home’) tab. From here, an
operator can monitor the device status and manually operate the device when it is
in Operator mode.
Lift Valve Upper Seat Button SIP/CIP Valve Upper Seat Button
The following table shows the functions included on the Operator tab.
Table 11 - Operator Tab Description
Function Action Security
Click to release Operator mode lock. Manual Device
Operation
(Code B)
If the object is configured to have permissive and interlock objects (for example,
Cfg_HasPermObj is true), the permissive and interlock indication become
buttons that open the faceplates of the source objects used as a permissive or
interlock (often this is a P_Intlk interlock or P_Perm permissive object). If the
object is not configured in this way, the permissive or interlock are indicators
only.
The Operator tab also has a button to open the Valve Statistics faceplate if the
valve is configured to use the P_ValveStats object (Cfg_HasValveStats = 1).
When the object is not configured to have an P_ValveStats instruction, the Valve
Statistics button is not displayed.
Non-bypassed conditions OK
All conditions OK
Fail Alarm
The following table shows the alarm status on the Operator tab.
Table 12 - Operator Tab Alarm Status
Graphic Symbol Alarm Status
In Alarm (Active Alarm)
Maintenance Tab
Maintenance personnel use the information and controls on the Maintenance tab
to adjust device parameters, troubleshoot and temporarily work around device
problems, and disable the device for routine maintenance.
Engineering Tab
Page 1 of the Engineering tab lets you can enter descriptive strings and configure
valve options.
The following table lists the functions on page 1 of the Engineering tab.
Table 14 - Engineering Tab Page 1 Description
Function Action Security Configuration Parameters
Click to navigate to the Mode None See Mode Configuration Display on
Configuration display. page 45
This display lets you select the default mode for the object by selecting the
appropriate mode.
IMPORTANT If no mode is being requested, changing the default mode changes the mode
of the instruction.
You must have FactoryTalk View security code E to select the default mode on
this display.
The following table shows the functions on page 2 of the Engineering tab.
Table 15 - Engineering Tab Page 2 Description
Function Action Security Configuration Parameters
Pulse seat lift Check to enable pulsing in the lift Engineering Cfg_PulseLiftLower
output during Lift lower state. Configuration
Lower (Code E)
Pulse seat lift Check to enable pulsing in the lift Cfg_PulseLiftUpper
output during Lift upper state.
Upper
Pulse seat lift Check to enable pulsing in the SIP/CIP Cfg_PulseSIPLower
output during lower state.
SIP/CIP Lower
Pulse seat lift Check to enable pulsing in the SIP/CIP Cfg_PulseSIPUpper
output during upper state.
SIP/CIP Upper
The following table shows the functions on page 3 of the Engineering tab.
Table 16 - Engineering Tab Page 3 Description
Function Action Security Configuration Parameters
Close Valve: On I/O Check to close the valve when an I/O Engineering Cfg_ShedOnIOFault
Fault Fault occurs. A reset is required to Configuration
clear this latched shed condition. (Code E)
Clear this checkbox to show only the
I/O fault status/alarm and not trip
the valve if an I/O fault is detected.
Close Valve: On Check to close the valve when a Cfg_ShedOnFail
Position Fail Position Fail occurs. A reset is
required to clear this latched shed
condition.
Clear this checkbox to show only the
Position Fail status/alarm and not
trip the valve if a Position Fail is
detected.
Close Valve: On The device always sheds (closes) on None
Interlock Trip an interlock trip. This item cannot be
unchecked. It is displayed as a
reminder that the interlock trip
function always triggers a shed.
The following table shows the functions on page 4 of the Engineering tab.
Table 17 - Engineering Tab Page 4 Description
Function Action Security
State Configuration Click a state box to open the State Configuration display to None
access configuration parameters for the valve state. See
page 50.
Diagnostics Tab
The previous figure shows that the valve is not ready because the device has been
disabled by Maintenance.
Alarms Tab
The Alarms tab displays each configured alarm for the P_ValveMP instruction.
The icon on the tab for the alarms page changes color based on the current active
alarms. A blinking alarm icon indicates that one or more alarms must be
acknowledged or the device must be reset.
Alarm Acknowledge
Command Button
Alarm Severity
Indicators
Alarm Names
Click an alarm name to open the P_Alarm faceplate for that alarm. From the
P_Alarm faceplate, you can configure and perform additional operations on
the alarm.
If an alarm is active, the panel behind the alarm changes color to match the
severity of the alarm. The color of the bell icon at the top of the faceplate shows
the severity of the highest active alarm, and the icon blinks if any alarm is
unacknowledged or requires reset.
When the Reset and Acknowledge All Alarms button is enabled, the panel
behind the alarm blinks, indicating the alarm requires acknowledgement or reset.
The Alarm Acknowledge button is enabled if the alarm requires
acknowledgment. Click the button with the check mark to acknowledge the
alarm.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400