20.12.24 OW No. 9634 - TPC Bhingari Bays - 0001 2

The document outlines the requirement for two additional 22 KV feeder bays at the Tata Power Company's Panvel EHV substation to meet the increasing power demand due to rapid urbanization in the Raigad district. It highlights the existing infrastructure's capacity limitations and the necessity for upgrades to ensure reliable power supply. Recommendations for approval and compliance with relevant correspondence are included for further action.

Uploaded by

surendragj479
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views18 pages

20.12.24 OW No. 9634 - TPC Bhingari Bays - 0001 2

The document outlines the requirement for two additional 22 KV feeder bays at the Tata Power Company's Panvel EHV substation to meet the increasing power demand due to rapid urbanization in the Raigad district. It highlights the existing infrastructure's capacity limitations and the necessity for upgrades to ensure reliable power supply. Recommendations for approval and compliance with relevant correspondence are included for further action.

Uploaded by

surendragj479
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

b

&f,{thr$d[
"d\ t.$ Off ice of Superi ntending Engineer;
MSEIICI Vashi Circle, "Virt3'nt" Buiiding,
X* Flor:r, Flotoo" S5, Sector 17, Vashi,
{A G'lvt. of Maharashtra Undertaking} Navi Mumlrai.
Maharashtra State Electricity Distributiori Company l-td.
CIN : {.i40109MH20055GC153645
Fho:re no. OZZ-77894742
Enrail lD: [email protected]

sE I v c I r I EHv / B AY s I 2OZ 4,2s / DATE:


TO
THE CHIEF ENGINEER
${;. i.,, - 20 .JEC ZAZ1
MSEDCL [O&M) ZONE - BHANDUP URBAN ZONE
Br{ANDUP [W), MUMBAT.

SUBIECT : Requirement of 02 nos.22 KV Feeder Bays at


TATA Power Company's ITPCJ Panvel
[Bhingari) EHV Substation, at Panvel, Dist. Raigad.
Reference : 1J EE Panvel U itr no. EE/PNL-U12024-25/Tech/4073 dtd.27.09.2024.
2JToL No. SE/VCIT /EHV /Bays/202a-2518050 dtd. 04.11.2024.
L 3l EE Panvel U Ltr no. EE/PNL-tJ /2024-25/Tech/ 4425 dtd.0Z .1"1".2024.
4l EE Panvel U Ltr no. EEIPNL-U l2AZ4-25/Tech/4736 dtd.05.12.2A24.

With reference to above subject following brief facts are to bring your attention into;
Background:
Fanvel in Raigad district is undergoing significant residential and commercial development, enhancing
the area's infiastructure. This growth is expected to boost the local economy and provide modern amenities.
Howeve! it also increases the demand for reliable power supply, necessilatitrg upgrades and expansions in
the power distribution infrastructure to meel future needs. Presently 22 KV Bhingari Switching Station
catering the power supply demand from Palaspe, Nere, Pargaon, Akurli gaonthan wirich are experiencing
swift development as above^
11A/22 KV Tata Power Cotnpany's ITPCJ Panvel EHV substation is ]ocated at a distance of 0.1 KNIs from
existing 22 KV Switching Station Bhingari & the substation Management had upgraded the existing 110/22
KV Power Transformer 1 capacity to 30 MVA from existing 7.5 MVA. Subsequently M/s TPC informed it's
readiness vide ietter no. Trans/KYN Node/MSEDCL/24-25/34 dtd. 05.12.2024 to provide additional02 nos,
Z'ZKV Feeder Bays frotn Lrc/22 KV Tata Power Company's [TPC] Panvel EHV substation for MSEDCL.

t Existing Power Distribution Infrastructure :


Existing 22 KV Switching Station Bhingari {SS Code 223001) provided with 03 nos. 22 KV Incomer feeders.
The Loadings details of the same are as under;

SR FEEDER NAME SOURCE MAXIMUM I,OAII REMARK


No. SUBSTATION RECORDED

'22A/33/2ZtN
1 22 KV BHINGART i/C- 1 45a Amp I
{Feecier Cade 3A2) ONGC PANVEI, 17.14 MVA
Total maximum load recorded 36.58
EHV SUBSTATION
MVA
2 22 i{V BHINGART I/C -2 ISS No. 228013) 510 Amp /
[Feeder Code 303) 19.44 MVA

3 22 KV BHINGARI 1 1.10122 KV'rPC 0 Amp Stand-by feeder arcangement jbr 22


PANVEL EHV KV Karnala Feeder (308) [under
SUBSTATION jttrisdiction ofPonvel R dn ol Pen
Circle) from Bhingari Switching
Station in case af emergency

Page 1 of2
Necessity for Additional22 KV Incomer source :
1) Existing 22 KV Sr,vitching Station tshingari (SS Code 2n?A1) is utilised to its utmost capacity.
2J Rapid urbanization under Palaspe, Nere, Pargaon, Akurli gaonthan had resulted in a stiff rise in power
supply demand.
3l There is an urgent need for upgradation and strengthening of power distribution infrastructure to meet
the r,rpcoming power supply demand for reliable & uninterrupted power supply.
4)220/33/22 KV ONGC PANVEL EHV SUBSTATIOhI ISS No.228013J located at distance of 3.5 I(Ms from
existing 22 RV Switching Statiot-t Bhingari (SS Code 223001) & 02 nos. existing 22!<V Incomer feeders to
22KV Switching Station Bhingari {SS Code 2230A, are sourced from the same, Whereas the 1"10/22KV
Tata Power Company's (TPCJ Panvel EHV substation is located at distance of 0,1 KMs from existin gZZ KY
Swilching Station Bhingari {SS Cade 223001).
5) Reduced feeder length will ease for feeder maintenance and maintaining reliable uninteruupted power
supply.
6) 110/ZZ KV Tata Power Company's ITPCJ Panvel EHV substation uiell connected with Khopoli Hydro
power statiotr r,ryhich would act as an alternate source of power supply in case of emergency or shutdown
on existing MSETCL EHV substation / grid.
7) 1.1.0/22 KV Tata Power Company's [TPC] Panve] EHV substation Management had upgraded the existing
110 /ZZ KV Power TransFormer 1 capacity to 30 MVA from existing 7"5 MVA. Aiso the commissioning of 02
nos. additional 22 KV feeder bays are to be completed by MAY 2A25. M/s TPC informed it's readiness vide
letter no.'l'rans/KYN Node/MSEDCL/2+-ZS /34 dtd. 05.12 .2A24.

Recommendation:
As the utmost capacity utilization of existing power distribution infrastructure & strengthenlng &
upgradation in view to meet upcoming power sr-rpply demand vrrith reliable po.vver supply lt is recommended
to allocate 02 nos. 22KV feeder bay.s from 110/22 KVTata Power Compan_y's (TPC) PanvelEHVsubstation
as feasible & readily accessible additional 02 nos. 22 RV incomer source to existing 22 KV Switching Station
Bhingari {SS Code 223001) with provision of input meter reading.

Proposal:
In view of the above Jroposal for requirement of 02 nos. 22 KV Feeder Bays at TATA Power Company's
(TPC) Panvel [BhingariJ EHV Substation, at Panvel, Dist. Raigad as an additional 02 nas. 22 KV incomer
source to existing 22 KV Sr,r,itching Station Bl-ringari {SS Code 223001) is submitted herewith for further
needful approval please.

The Requiremetrt of Bay in prescribed format is enclosed herewith all relevant correspondence for your
reference please.
:@
{Sanjay S. Patil )
SU PERIN TEN D I N G EN G IN EER
MSEDCL, VASHI CIRCLE
Enclosure : Bay Requirement*Annexure A

Copy s.w.r.to;
1, The Chief Engineer [STU) MSETCL, Prakashganga, BKC Mumbai.
2. The Chief Enginee4 MSETCL, EHV PC O&M Zone - Vashi. at Vashi, Navi Mumbai.
3. The Chief Engineer [Dist), MSEDCL, Corporate Office "Prakashgad", Mumbai.
Copy s.wc.to;
1,. The Superintending Engineeq, MSETCL O&M Circle - Panvel, at Panvel, Dist. Raigad,
2. The Group Head - Kalyan Node, TATA Power Cornpany, I{alyan Receiving Station, Netivaii, Kalyan
- 421301
Copytor
1. The Executive Engineer [T), MSEDCL[Testingj Division- Vashi.
2. The Executive Enginee4 MSEDCL [O&MJ Division - Panvel U Dn, Panvel, Dist. Raigad
3. Add Executive Engineer; MSEDCL [O&M) Sub Division - Panvel l [BJ, Panvel, Dist. Raigad,

Page 2 of2
t i:.,
"*
-*'.
S.e.L. Vceht

D\{
t

,if tr ?---
.:1.1.i.; iiq:"
I
^/\ MAHARASHTRA STATE ErEc+. c tEi ?024-
e.r Lld.
DISTRIBUTION COMPANY LTb.
(Nlaharashtra State Undertaking) PANVEL URBAN DIVISION.
CIN : Office of the Executive Engineer, MSEDCL
(u40 I 09MH2005sGC 1 5 364s) Panvel Urban Division, MSEDCL, Employee
rer. No.27453787 I
27490299 Colony, Old Mumbai- pune Highway,
Bhingari. Tel. panvel 41206, Dist. Raigad
E-Mail id : [email protected],

EE/P NL -U/ 2024-25fi e ctt/


Date:
To.
Qe.ats16 0 5 0EC zoz4
L.rlGtrperinrendi ng Engineer
MSEDCL, O&M Circle Vashi.

Sub: Submission of compliance-of descripancies


! KV TATA power companry gp_c) purr;iiB;irguii;
in q:ol-1,-1l of requirement of 02 nos.
22 Ky Feeder Baysatr0/22
Ref:- I ) EEipNL U /2024_2s /T nnv srurt"ti"r-r, panver dist. Raigad.
+ot Z afi.ii-.ns.zozq.
2) SEty c/T tEHViBAys/2O""hi
24_25 I 80 50 Dt. 04. 1 1.2024.
3) EE/PNL U I 2024-25/T ech/ 459 I
dtd. 25.1 t .2024.
4) Email to TATA power for submission
of docurnents on dated 25.1r.2024.
5) Trans/KyN Node/MSED CLt24_25
/34 Dt. 05.12.2024.
6) EEipNL-Ui 2024 -25/T ecV 47 29
Dt. O S . I 2.2024.
This office is in receipt of letter u/r (2)
rcgarding DISCREPANCIES under
Requirement of 02 nos.22KV Feeder Bays
ii:l|i'.lfXffi .':ffi",,TJ:tt,ffi:i5:y6;iliffi ;'ii,f ,,",,",,tp;;;;ii[,i",*"a
l) Letter of readiness / interest received
from TATA Power co, for alotment
of 22KyFeeder bays to MSEDCL at 110/22
IJffi;l1Ti:?lj:f1?trvsuustationuipu,,"r,,.""r",.J,i.r,,r,.p."p1,"i,,r,"ri"u.,1;r,mitted.
110/22KV rPC',s Panver (Bhingari)
3],3:',J,::ti:;tlix1;ifffi,l"l'"t EFrv Substation at panver for arrangement
at
Compliance:- Enclosed
3) Requirement of Bavs to be submitted
in prescribed format enclosed herewith.
\ duly authenticated. The Bay Requirement submitted
shall be
Compliance:-Enclosed
latest SLD orMSEDCL's 22KY Switching Substation ar Brringari
3r'#ffi:::$T:[:.t shas be submitred.
5) Self explanatorv comm€nts
/ recommendations /justifications
shalr be subrnitted with proposar
emphasizing the necessity
MSEDCL zz iiv nr,i,gari Switching
suustation
Fl$iffiil;;H?tir'ff,",il:;;;;'#;;"J'to
Conrpliance:- Enclosed (u/r
rront ,0/22r(v rpc,s
6)
6) The connection Apprication
lAnnexure 2(A)) submitted sha, be dury
Comptiance:- Submitred ulong authe.ticated.
*iri ii. oi"ol.r, vide u/r I.
This is submitted for your information
and further needful action please.
,}
Encl: AA
I
ExecutiveiEngineer
Copy SWR To:- The Chief Panvel (U) Division
Engineer, MSEDCL, Bhandup
tJ Zone.
./\ MAHARASHTRA STATE EIECT.
Mrtrllltt)l$*ttu{ {hdddtf Dhldtjikn Se. Ltd.
DISTRIBUTION COM PANY LTD.
lrJahorathl.a State
PANVEL URBAN DIVISION.
(Maharashtra State Undertaking)
Office of the Executive Engineer, MSEDCL
CIN: Panvel Urban Division, MSEDCL, Employee
(u4o 1 09MH200s sGC 1 s 364s) Colony, Old Mumbai- Pune HighwaY,
re1. No.27453787 I 27490299 Bhingari. Tel. Panvel 4!206, Dist. Raigad
E-Mail id : [email protected],

E ryPNL-U/2 024-25lT ech/ gg J"2s Date


.0
L
5 Dtc ;,?4
To,
The Superintending Engi neer,
MSEDCL, O&M Circle Vashi'
L
Sub: Proposal for Requirement of 02 Nos. 22 KV Feeder Bays at Ll0l22 KV TATA Power Company's
(TPC) Panvel (Bhingari) EHV Substation, Panvel, Dist. Raigad'

Ref:

i. EE/PNL 3 dtd. 27 .09.2024.


rJ 12024-25lTechl 407

2. SE/VC/T/EHV/BAYS/2024-2s I 8050 dtd. 04. 1 1 .2024


3. EE/PNL U 12024-25necU4591 dtd. 25.11.2024.

In connection to the above subject, discrepancies raised vide reference 2 regarding the requirement of02 Nos. 22
KV Feeder Bays at the 1l0l22KV TATA Power Company's (TPC) Panvel (Bhingari) EHV Substation have been
noted. As per point no. 5 in reference 2, it is directed to provide self-explanatory comments, recommendations,
and justifi-ations highlighting the necessity of these additional bays for MSEDCL's 22122KY Bhingari
Switching Station.

Accordingly, a detailed survey and technical evaluation were conducted to assess the feasibility and necessity of
t establishing two additional incomer feeders from the 110122 KV TPC Panvel (Bhingari) EHV Substation, located
at Bhingari Village, Tal. Panvel, Dist. Raigad, Maharashtra410206. The findings are as follows:

1. Necessity:

a. The 22122KY Bhingari Switching Station is currently supported by a single source, with two incomer feeders
from the 220133122 KV ONGC Substation.
b. The length of these incomers is approximately 3.5 km, comprising both overhead lines (0.2 conductor) and
underground cables (double-run 300 sq mm HT cables).
c. Tlre existing HT cables pass under a railway track, creating maintenance challenges. Additionally,20
distribution transformers are connected to these feeders.
d. The peak load on Incomer-1 is 450 amps and on Incomer-2 is 510 amps, with a total load of 36.58 MVA on the
22 122 Ky Bhingari Switching Station.
e. Despite regular maintenance, the aging infrastructure leads to frequent interruptions, negatively irnpacting
consumers (details enclosed).
\

2. Justification Based on Standards:

As per Circular No. CE(Dist.yD-III/NSC/3001 1 dtd. 20.12.2018, if the


substation load exceeds 20 MVA,
additional incomer feeders must be proposed to maintain reliable
supply. Since the total load of 36.5g MVA
exceeds the capacity of the existing 02 incomer feeders,
02 additionai f:"ed".s are required to cater to
the demand
effectively.

3' As per existing position, the details of sources for 22/22 KV Bhingari
Srvitching Station is as below,

Sr. No Name of EHV Substation Name of Substation Number of 22KY


Sources
I
ll0l22 KV TPC's Panvel 22l22KY Bhingari
(Bhingari) EFIV Substation Switching Station 1

2 220122Ky ONGC Panvel 22/22KY Bhingari


Switching Station 2

4' The details of additional sources proposed for 22/22 KV Bhingari


switching Station are as follows,

Sr. No Name ofEHV Substation Name of Substation Number of 22KY


Sources

1
110122 KV TPC's panvel 22122KY Bhingari
(Bhingari) EI{V Substation Switching station 2

5' Distances of 22122 KV Bhingari switching station from 220/22Kv


ONGC panvet and 1l0l22KV Tpc,s
Panvel (Bhingari) EHV Substation

o Distance between 22122KY Bhingari Switching Station


and220l22KV ONGC panvel: 3.5 km
' Distance between 22122Kv Bhingari switchin! Station and
l10l22KV Tpc panvel (Bhingari): 0.1 km

3 5KftN O,1KM

6. Advantages of Proposed Incomers:

a' Reduced Feeder Length: Feeder length will reduce


voltage regulation and minimizing technlcal losses.
!
significantly
i from 3.5 km (existing) to 0.1 km, improving
b' Improved Reliability: Having-sources from two distinct EHV
stations enhances redundancy, ensuring fewer
interruptions due to shofter feeder lengths and undergro*o
*uhrg

I
c' connectivity to Hydro stations: The TATA Power
substation connects to hydro stations, enabling reliable
backup power during emergencies.
d' Future Expansion: Adequate space at the switching
station ensures seamless integration of new feeders
anticipated growth. for

7. Precedent in Other Areas:

Such affangements exist in nearby areas like Bhandup,


Kalyan, Ambarnath, and ulhasnagar, where supply
from
utilizid' In these cases, metering of incomer feeders is treateias
ffiffi?J!ffi3:*"'*lv drawal points and

"t ln lieht of the above, it is proposed to establish 02 additional


incomers from the 110122KV Tpc panvel
(Bhingari) EHV Substation to enhance
ihe reliabilir;J.;inuity of power supply for
22122Ky Bhingari Switching Station. The proposaiir the consumers of tlie
rru*iir"d for your r.ino uliiorar and fufiher necessary
action.

Encl:AA

Engineer
copy SWR To:- The chief Engineer, MSEDcL, Bhandup rJ Panvel (U) Division
Zone.
copy To:- Additional Executive Engineer, MSEDCL, panvel_I
Subdivision.

\
,/

I
I

of
lnstalled lcomissioned (Pt
NAME OF EHV Ievel
Capacity by
Comissioned of Bay status
IMVA)
bunching/Tap Scheme
of by EHV
ping/ttt o
date of

770/22 KV
1 Vashi Vashi Panvel tJ
TPC's panvel 22/22 KV Bhingari
(Bhingari) EHV Switching 2E+05 22/22 NA 1980 Tapping
Substation NA Commissioned NA 2 2 Permission Awaited

t
(l
vl

Ev.ectitive Engineer
Panvef Ur'*en Division
MSEDCL

t1 )

a, .
Ve-L
'--'-
Supcdntcndlng Engineer
il. S. E. D. Co. Ltd.
VASH|Ctrcto.

(
-
22/22 KV BH|NGAR| SW|TCH|NG STATTON SLD

22KCt/C NO. l FROM 220/33/22


22KCt/C NO.2 FROM 220/33/22
ONGC SUBSTATION
ONGC SUBSTATION

KV BUS
22 KV BUS COUPLER ISOLATOR
22 KV BUS

((l 22 KV 22 KV 22 KV SAI 22KV 22 KV 22KV 22KV


PANVEL 1 KOLKHA
22KV
NAGAR GAVHAN PANVEL 3 PARGAON KARNALA NERE

@
e,f:[:ggl*:llr" (V
VASHlOircle'
,*r/, Engineer
Pan'rel Urban Division
( q
MSEDCL
7

22122 KV BHINGARISWITCHING STATION SLD

22KCt/C NO.l FROM 220133122 22KCt/C NO.2 FROM 220/33122


ONGC SUBSTATION ONGC SUBSTATION

22 KV BUS COUPLER ISOLATOR 22 KV BUS


22 KV BUS

Ld

r$
\

22 KV 22KV 22 KV SAI 22KV 22KV 22KV 22KV 22KV


PANVEL 1. KOLKHA NAGAR GAVHAN PANVEL 3 PARGAON KARNALA NERE

nJ^ o
k *[nt
"l

)
e*e/,itt'n Ergineer
Panvef Urhan Division
MSEDCL
T )
TNTN
Trans /KyN Node /MSED CL/24_25/34
To Dt. 05-1.2_2024

The Executive Engineer,


Panvel Urban Division,
Maharashtra State Electricity
Distribution Company Ltd.,
Bhingari, panvel-pune Road,
Pa nve I

sub: Readiness of 2nos of 22kY


outlets for MSEDCL at rata power -
Ref: 1' Tata power Letter - Trans
Bhingari sub station.
/KyN Node /MSED CL/23-24/44 Dtd 1_L.09.2023
2' yo L EE / p NL-U / 2o2a-25
/T ech/04s9 1 Dtd 25.u..2024
.L

Dear Sir,

TataPowerTransmissionistransmissionlicenseeinMaharashtraandhasitsll0
in Bhingari area which feeds kv/zzkVpanvel substation
to MSEDCL's Bhingari switching
MW from this substation. The
station. There is continuous drawr of 4 Mw
Capacity of Transformer 1 is to 7
now upgraded to 30 MVA.
With reference to lettt
immediaterv *i,'
Xf,'fl:Hli;ff"1?llj;::::,o"1::,TJ;::;""1f#' 'ts can be rereased
',.*-li
llil"J,i k ffiilJffi;;: '""'"ion 02 nos or 22kV new bavs at Bhingari ror station rransrormers
This is for your information
and further necessary actions please.

Thanking you.

lr*

Yours Faithfu

ill.S.E,D.C.L, Panvel.U.Divi$on
(Surendra i)
EX. Eng.
Group Head- Ka n l@F i;r,
Dy EE (o)
Encl: Updated SLD for Tata power
22kV Bhingari SS
ir: (fl.C.)
A€-G:cr)-
AE {P}

2 AE HT
r.[ {0)
F (:!iore)
riE rr;iila)
ilv
riv. IJtr tif )
TNTN
The Tata power Company Limited
;ii i.r
Kalyan Receiving Station, Shil Road, Netivli,
Kalyan 42L 30L. District Thane.
Iel 91 22 67 17 4513 67 1,7 4s44
Registered Office : Bombay House, 24
Homi Mody Street, Mumbai 4OO 001.
CIN : L2890MH1919pLC0oo5G7 website :
www.tatapower.com Emair : [email protected]
Anne xure-2
application )
( ln resPonse to Sr No. 6 of the Connection

MSEDCL Construction
INTRA STATE No of
switching Schedule Outage schedu le of existing
TRANSMISSION Outlets Completion Target date for
stations Commencement system for energisation
CONNECTION POINT reqr.lired
date energisation of
Date
inte rconnection
6 7
4 5
2 3
Dec 24 ln consultation with M/s TPC
L
Nov-24 Dec-24
2 22 KV Bhingari
TPC Panvel SS 22 KV
Switching Station
BUS

ffii\
Executive Engineer
Superintending Engineer
Panvel Urban Jivision
l,r. S. e. D. Co. Ltd.
VASHlOircle.
MSEDGL
Annexure-2(A)
n n
n in

Sr. oeueRal Distribu tion


State ElectricitY
No. M aharas htra
I Name of Di stribution Licensee Co m pan v Limited (NnAHAD SC oM)

Sub Station
,'s EHV Sub-station Tata P ower's 110 kV Panvel
2 Name of Transm ission Licensee (Bhingari)
where connectiotn is ProPosed 22kv Outlets uired- 02 Nos
U rban Division
Executive Engineer, Panvel
Distributi o n L icen
co Officer tn ;harge fo co-
3 of
Dy E E a nd A E n charge
ordi nation of wo rk EE,
the D stri bution IN the atea I Single Line
Please R efer Annexure- 1 :TyPica
4 Dtagram

load demand in
ction and/o T U meet the ncrea sing
of the proPosed CO nne rea of the RSS and to imProve
(* 5 Pu rpo SE
ben eficia fles of SU rro und tn g
mod ification of CO nn e ction po int d nd q u ity an d re liabil ity of SU p ply
CO n nection m odificati o n
th e propo sed
o Con stru ction SC'hed u
C o mm nce men date Please refer Annexure-2
Com letion Date
U n of inter -con necti on
Ta et d ate for en ergls ati
-ystem, if any for
Outage sch edu le of existing
ene isation NA
D stri 0u tion L rce nsee
for
Any pro posals by the o b the
a') KV Grid Su bstati n v
creatio n of new 1
lon L nse o sh b furn sh ed n loss ES
T ta nsmis
q ity of SLI p ply d nd res u Itan
an d rm p rovem nt n u a
uen to creation of such
cost be nefit d naly sis con seq
GSS
B GON NECTI ON PO INT e
^+ Con necti o n bay ncl udi n g d etai
of Please Refer Annexure-3
1 Arrangem nt dL
existin g co n nection
/ LaYout at inter-
Substation Layout diagram
t 2
connection belY
a lta ng A ment required
in i) C.2 Class, ABT Com patible with
ioad profile
? D etail S of N/lete ring data
ndicati ng :wnershtP
com pli d nce of Meteri n g Code ii) OwnershiP : STU
of eter readi ngs meter
iiir g";Lrp - 0.2 class, ABT compatible
an d res ponsi b Iity m
owned bY Tata Power
irf' nu.pon.lbility of tt/eter Reading : STU'
IVISEDCL and Tata Power

22RV
4 Vo Itage of at poi nts of co n nection
SU p ply
i) P rotection fo 22 KV F eede
at conn ectio n
t^
p rotection prov id ed
E Protection Provt'ded Deta t5 of poin is n sco pe of T ata Power
both on pn mary an d e at R ece ivin I e nd
on 221 11 kV J ubstation S i) P rotection for 22 KV F eed
secondarY side) is n J co of N/l
v S E DC L
c LOADS na me Please Refer Annexure-4
gth No. of circu its, cond uctor
1 L ne Data-( Li ne len on
config urati
S 1Q
q
upp ort ty p A cond U cto i) 22 KV switch ln g statio
n
in g station op erated
S u b-statio n Data (22 122 KV switch i) The distrib ution system wl be
2 pacitY to be con n ected on
ca
Distri b uti o n Tran 5 former station S radiallY'
n a nd distance of sub
the feeder with lo catio ges tn
fro m starting poi nt)
The correslpondi ng chan
to n EW feed inter
other fee ders consequent
be furnished
co nn ecti n shall also

3 Load Data P lease refer Ann exu re-5


(a) Load drawn at po in
ts of co n nection Nil
D etail S of load fe d at
EHV if an v N.A.
(b
voltage of supp v contract
N ) me of CO NSU mer in e is
d Su bstation fro m wh ich
deman d and n a me of Gri S ubstatio n to
n e from G rid
d rawn length of EH
con SU m A r' J pre m ISES
profi A a n d
n EW co n nection load feeder 2 & 3
(c) Con tract dem and fo m pen sation sh un 22 kV Bhinagri Switching Stn
P F ran ge R A active P ower co
cap acito rS installed. NA
d uty cyc o State wh
ether fu nace
4 T ype of loa d with tn d ustrial lo ads
t^ loads, other
load q ro ln I nI l5 tra ction C o NS um rS a nd
vd 5tr of E HV
p um p ng lo ads etc in
Con SU m ers A XCCC d ng 5 tVIW dem a nd
NA
VCTS ity of load a nd
6 L oad p rofi la o n the fee der (D
col NC iden CE factor) NA
(lState n um b er and size
6 E le ctricao adt ng of eq u pme nt ,) in
an d con trol a rran g ments
A
of moto rS ty pes of d rive mers exceed ln g 5
A rS & Con SU
ca SE of E H Con SU m
tVIW demand NA
tn CAS o of E HV Con SU
mers and
7 L oad (. ha racteri stic
rQ exceed in g 5 NIW d em a nd
Co NS um NA
uen cy of S u
a) Sensiti of loa d to voltag a nd freq NA
nten of load
(b) lt/laximu m H a rm o nic co NA
Current Harmonrcs NA
e Harmon ics NA
hase u n balan CC of loa d
c) Averag o an d m AX m um
AN D c o NF RM ATION connection
B CERTI F h AS b een confirmed tn the
cond ition S utl ined n
that a (r) and
C o nfi rm atton to th effect Respon sibilitY agreemen betwee n T ata P owe
m nt Site outlin ed in the
the CO n nection Ag ree the tl 5tr a pply n g I\NSEDCL that all conditions
p with by Respo NS bi lity
Schedule shall be com ied of exi stin g connectiotn ag reem nt. Site
for new con n ectio n o mod fication schedule shall be com p ie d with by both the
connection parties.
a rd PI annin g data
We co nfi rm that the stand (Distribution) in
n to th o effect th
at the Sta nd rd P la nning detail plan n in g data
2
g0
a
D etail PI n ni ng
Data ( Distributio n n and
com iance to Grid
p code fo new modified i
Data con nection
com pli nce to Grid C ode for new/modified fu
con nection sh all be rn
ished
o in the con nection
shall be furn ish d in im um protecti o n
We have
P owe -T and
{ to the effect that m a g re ement between T ata
C time an d protecti o n
ta rg et fault cl arance that the m nl mu m
req ui re ment in clud ing hal be p rovid ed for NNSEDC L
lines an d
rati ng of SW itch gear requ irement on E HV
a nd H
S
S hort tim n
P owerrT'S Tra NSMISS
as Per Grid Code tra nsformer at Tata Systern sh al
stri bution
System and IVIS ED CL
Di
for AS Gird Co de.
be
Confirm ed
E rth ng h ave been
4 to the effe ct that
o EA SafetY
prov ided a S per E ru les I 56 and
sh a ll be abid e by
R ulations hall b o abide We con fi rm that VISEI) CL
effect th at the u SE S Gri d C ode, EGC
tr Confi rmatio NS to the Cod EGC the p rOVIS o NS of the State SM ission
c of the State G rid 1 956 an d Tran
by th 6 provi sion o T ransm iss on n di a n Electric ;it! Rules
les 56 a nd
ndian E ectric;it! Ru relevant Lines Performance'
Performan Stan n a rd S AS may be
Licen see
RE PO RT p letion report and
E c o MPL ETI o N furnish the We con fi rm that the com
and U ser sh a il be fu rn ish ed in the
I The transmtss io n Licensee n ln g d ata n the prescribed pla nn lng data shall co m pletion of work at
P lan prescribed form at afte
comp leti o n re p ort an d at S ite
p eti o n of works
fo rm ats afte com site

Sign ature
Date

a Fn inesr
$;[;1: 'ion
Parrvei '-

A,thJrfuth8fr,h,o,,
Licensee
On behalf of Distribution

Superlntendhg Enginoer
M. S. E. D. Co. Lrd.
VASHtCtrcto.
il

.-. DATE: JAN-2024 PREPARED BY: Darshan Patil


U'
TATA
THE TATA POWER COMPANY LITUITED CHECKED BY: Nitin Gawde APPROVED BY: Tushar Dhande

PANVEL RECEIVING STATION


MASTER SLD

110 KV BHOKARPADA KARNJADE LINE 1 1O KV KHOPOLI KARNJADE LINE

110 KV BUS

tr BUS II BUS I

7.5 MVA
30
!J MVA
POWER TRF-2 POWER IRF-1 ?O MvR Tlo$S. I

INCOMER-2
! INCOMER.l

L
B.S. BKR
22 kV BUS 2
22 kV BUS 1

PT2 PT1

STN TRF-I MSEB I MSEB 2


(TAIA PN\EL UNE cAuP)
SIN IRF-2
EHINGARI I

Mss,uc u
Bh
$"\- DcL
Bhrryoti.3
Engineer
Panvel Urban Bivision
&i
MSEDCL
E
I

DATE : JAN-2024 PREPARED BY: Darsharr Patil


.-,
flt THE TATA PowER cotvlPANY LlNxlrED
CHECKED BY: Nitin Gawde APPROVED BY: Tushar Dhande

TATA PANVEL RECEIVING STATION


N/ASTER SLD

i';i
(:i,
-:./

11il kV *t"JS

&)

:..1.
::1]]|:::. i: :

:i

@@ t7 )
ra
o

':l

Execrltive neef
Panvel Urban Division
- MSEDCL
An nex ure -4

Line Data-Sr. No' C-1 of


the Connection application

Proposed
Feeder details
No. of MSEDCL Connected
INTRA-STATE
outlets Receiving Load in
TRANSMISSION Distance
reqLrired Stations No. of Size MVA
CONNECTION (km)
POINT Feeders
from
TPC,S RS
(, 7
4 5
2 3
1.

0.2 20
22kV Bhingari 2 3 Core 300
2
TPC Panvel SS 2 7 Switching Sq.mm XLPE,
KV BUS Station AI

:s
$uperintending Englneer
M. s. E. D. Co. Ltd.
VASHlCircle.
Ann 5

application )
( ln response to Sr' No'
C-3-(a) of the Connection

LO AD IN MVA
Load
o
iNTRA-STA]E
TRANSMISSION Proposed ln 2024-25 2025-26 2026-27
2023'74
CONNECTION year 7024-
POINT 2025 5 6
3 4
L
2
22.5 23.4
20.8 21.6
20
TP C Panvel
TOTAL

2076-27 ?027-28
2074-25 z02s-26
OUT LETS REQ U R E D 2
N EWi EX ISTI N G RSS
F ORM E R
A n D tTl o N L T RANS Z
TOTAL
2
GR TOTAL

.g*,{.)
P:x;:.-$;;,:Hi'$:,;'

--\

3FSuoerlntending Englneer
U. S. e. D. Go' Lttl'
vASHlOlrcle'