KRRS-MG-BDA-V-DOC-228 (GA Drawing of MMS, Foundation, Part Details & Fabrication Drawing) - R5

This document contains detailed engineering drawings and specifications for a solar module assembly structure, including dimensions, materials, and construction guidelines. It emphasizes the importance of verifying all measurements on-site and obtaining necessary approvals before construction. Additionally, it outlines the responsibilities of the contractor and includes notes on compliance with various IS codes and standards.

Uploaded by

madurimahesh99
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
400 views8 pages

KRRS-MG-BDA-V-DOC-228 (GA Drawing of MMS, Foundation, Part Details & Fabrication Drawing) - R5

This document contains detailed engineering drawings and specifications for a solar module assembly structure, including dimensions, materials, and construction guidelines. It emphasizes the importance of verifying all measurements on-site and obtaining necessary approvals before construction. Additionally, it outlines the responsibilities of the contractor and includes notes on compliance with various IS codes and standards.

Uploaded by

madurimahesh99
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd.

it may not
32396 (PURLINS) be used or reproduced (in whole or in part) for purposes other than the project
named below without the express written consent of TEPSOL Projects Pvt.
32292 (MODULES ARRGT. LG.)
-This drawing is not to be used for construction until sealed by the engineer for
1134 20
GAP(TYP)
that express purpose.
RAFTER C-LIP: N -The Contractor is responsible for checking the drawing and verifying all levels
3 and dimensions at the project site. The Contractor shall report any

N
90x40x15x1.6 T

E
N
W E discrepancies to the engineer and shall obtain written clarification from the
B SW engineer to resolve all discrepancies prior to commencing any shop fabrication

SE
2P*28

or site work.

S
KEY PLAN:
CLEARANCE
GROUND

BRACINGS PURLIN- HAT:


8 4 80x40x25x7x0.9 75
1000

CONNECTING MEMBER

20
7
200

C-90x40x2 THK.
2

200
COLUMN POST-1
1
C-LIP 200x75x20x2T
1200

20
EXTENDED COLMN
C-90x40x2 THK.
2 NOTES:
C-LIP 200x75x20x2 THK.
B COLUMN POST-1 GENERAL INFORMATION
896 3050 3050 3050 3050 3050 3050 3050 3050 3050 3050 896 1:10
40 19.413, 76.073
DIA. 300 MM, LATITUDE LONGITUDE
1 16 2 3 4 5 6 7 8 9 10 11
M25 GRADE FDN.
VIEW A-A SITE AREA 37.77 Acres
1200mm DEEP PILE
1:50 MODULE RATING Wp 535, 540
ELEVATION OF 2Px28 MODULES ASSEMBLY STRUCTURE

2
4180.5 (PURLIN-1) 4 NO OF 535Wp MODULES 2520
1134 PURLIN- HAT: 6350 (PURLIN-2) 5 6350 (PURLIN-4) 7 4065.5 (PURLIN-6) 9
6350 (PURLIN-3) 6

90
80x40x25x7x0.9 6350 (PURLIN-5) 8 NO OF 540Wp MODULES 22512
1086 PURLIN- HAT:
20 250 80x40x25x7x0.9 250 250 250 250 25032
C/C NO OF MODULES
GAP(TYP) OVERLAP OVERLAP OVERLAP OVERLAP OVERLAP
TOTAL CAPACITY WITH 535Wp (MWp) 1.3482

TOTAL CAPACITY WITH 540Wp (MWp) 12.15648

EXTENDED COLUMN &


2274x1134

TOTAL CAPACITY (MWp) 13.50468


CONNECTING MEMBER MODULES TILT 15°
4412 (15° TILTED PLAN)

C-90x40x2 THK.
PITCH(Mtr's) 8.0
1:2.5
COULUMNS
L CENTER
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
40

15
COLUMN POST-1
1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08
C-LIP 200x75x20x2T
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
2274x1134

1.6 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40

90
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423

TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48

TOTAL NO OF SMB 44
896 3050 3050 3050 3050 3050 3050 3050 3050 3050 3050 896

15
A A RAFTER
TOTAL NO OF LA 8
1 2 3 4 5 6 7 8 9 10 11 C-LIP 90x40x15x1.6 THK. TOTAL NO OF CONVERTION STATIONS(5MVA) 2
1:2.5
PLAN OF 2Px28 MODULES ASSEMBLY STRUCTURE (15° TILTED)
1:50
40

10
32396 (PURLINS)
32292 (MODULES ARRGT. LG.)
4180.5 (PURLIN-1) 1.6

60
1134 6350 (PURLIN-2) 6350 (PURLIN-4) 4065.5 (PURLIN-6)
6350 (PURLIN-3) 6350 (PURLIN-5)
1086 PURLIN- HAT:
80x40x25x7x0.9 250 250 250 250 250
C/C OVERLAP OVERLAP OVERLAP OVERLAP OVERLAP

10
BRACING (BR1 & BR2)
587

C-LIP 60x40x10x1.6 THK.


1:2.5 R5 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED
2274x1134

IS CODES: DOCUMENT NUMBER CHANGED


R4 03.11.2021 D.V.S GHSV A.V D.V.S
1100

IS 12834-2013 Solar Photovoltaic energy systems AS PER NEW MDL


C/C

MS Structural Steel / Sheet (Hot Rolled) R3 25.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
Mechanical Properties
4568 (TRUE PLAN)

IS 2062 R2 22.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS


Chemical Properties
587

MS Structural Steel / Sheet (Cold Rolled) R1 18.10.2021 D.V.S GHSV A.V D.V.S ADDED IS CODES
Mechanical Properties
20

IS 1079 R0 11.10.2021 D.V.S GHSV A.V D.V.S -----------------------------


Chemical Properties
587

IS 513 (2008)
Cold Reduced Low Carbon Steel Rev. Date Designed Drawn Review Approval Description
Sheet & Strip
Cold Formed Light Gauge Steel
IS 801 (1975) OFFTAKER:
2274x1134

Structural members
COLUMN POST-1
MAHARASHTRA STATE POWER
1100

Zinc
C/C

C-LIP 200x75x20x2T
IS 209 Chemical Properties
1 IS 4759 HDG Structural Steel
In-Process
GENERATION COMPANY LTD.
587

IS 1852 Cutting
IS 7215 Punching
As per Specifications Bending
DEVELOPER:
896 3050 3050 3050 3050 3050 3050 3050 3050 3050 3050 896
IS 4759, IS 2629
Hot Dip Galvanizing
Defects & Surface Finish
KARNATAKA RESCO
1 2 3 4 5 6 7 8 9 10 11 IS 6745 Mass of Zinc Coating
ROOFTOP SOLAR PVT. LTD.
IS 2633 Uniformity in thickness
2197 2197 VIEW E-E IS 4759 Coating thickness
1:50 IS 875 Wind Speed loading, dead, live,
snow & wind loads CLIENT:
587 E PLAN OF 2Px28 MODULES ASSEMBLY STRUCTURE MODULE FIXING
IS 1893 Part -1
Criteria of Earthquake Resistant

13 2274
*113
4 HOLE 40 IS 12269
Design of Structures
Ordinary Port Land Cement,
53 Grade - Specification TEPSOL
NOTES: IS 10262 Concrete Mix Proportioning - Guidelines
1100
1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S PROJECTS PVT. LTD.
20 250 2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED.
H 587
SOUT HARDWARE OVERLAP 3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350).
HARDWARE RAFTER 14 0.9 PMC:

80
15 3 50 7575 50 4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE
587 3600
13
MODULE-JINKO
*113
4 14
HARDWARE
PURLIN-B
PURLIN-A PURLIN-B SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF
5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759. BUREAU VERITAS INDUSTRIAL
2274x1134x30H 2 274 HARDWARE
14
5
1182

45°

7
1100 280 6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED
(535Wp)
TO MINIMUM 80 MICRON. SERVICES (INDIA) PVT. LTD.
BRACING 103 7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.
587 14 RAFTER FIXING 25 25 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED
RAFTER C-LIP: RAFTER C-LIP:
3600 3 HOLES BY '"TORQUE WRENCH METHOD". EPC CONTRACTOR:
15°

105 90x40x15x1.6 T 90x40x15x1.6 T


30

9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE


250 AP ARDRA POWER
PURLIN-A
E 3 4 DETAIL-A PURLIN SECTION
G)

2182

L WITH IS:800 AND IS:802.


ER
BR R1)

14 1:20
IN

O V HAT 80x40x25x7x0.9 10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE SUIT #202,NISHAN-E-IQBAL
AC
B

ROAD NO.11,BANJARA HILLS


EA 44 (

PURLINS OVERLAP ARRANGEMENT IN 3D 1:2.5 BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
1410

1:20 DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL. HYDERABAD-500034,TELANGANA
19
GROUND CLEARANCE

PURLIN- HAT:
R

80x40x25x7x0.9 264 11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS.
(R

EARTHING Designed: Drawn:


4 to 9 BRACING-BR2 186 HOLE BRACING-BR1
FR 5
C-LIP 60x40x10x1.6T ONT (BR2 450
1000

58

C-LIP 60x40x10x1.6T
BR )
°
26°

12 A CIN
G 11
D.V.S 11.10.2021 GHSV 11.10.2021
CONNECTING MEMBER Reviewed: Approved:
10
300

C-90x40x2 THK.
200

F.G.L

14 COLUMN POST-1 A.V 11.10.2021 D.V.S 11.10.2021


57.5

2024 1453 C-LIP 200x75x20x2T 1


Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
850

℄ OF OVERLAP
COLUMN POST-1 PHOTOVOLTAIC PROJECT
C-LIP 200x75x20x2T 1 RAFTER C-LIP: AT BHENDALA ,MAHARASHTRA.
3
1200

90x40x15x1.6 T
2460.4 LG. SECTION D-D
1:20 Drawing Title: MODULES MOUNTING STRUCTURE
14 2Px28 ECCENTRIC GA DRAWING
20 20
400

EXTENDED COLMN
2 EXTENDED COLMN
2
100

C-90x40x2 THK. C-90x40x2 THK. Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:


Ø300
75

DIA. 300 MM, Date: 11.10.2021 01 of 08 R5


50

M25 GRADE FDN. 16 COLUMN POST-1


1
1200mm DEEP PILE
C-LIP 200x75x20x2T Scale: AS SHOWN
200
VIEW B-B Graphic Scale: 0
Original Size: A1
- -
1:20 SECTION C-C
1:20
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
48.3 1155.9 29.5
40 be used or reproduced (in whole or in part) for purposes other than the project
263.6 30.3 90 SLOT-24x12
1792.2 SLOT-24x12 280.2 SLOT-24x12 named below without the express written consent of TEPSOL Projects Pvt.

30
SLOT-24x12 2 NOS. 4 NOS. 200 -This drawing is not to be used for construction until sealed by the engineer for
SLOT-24x12 PURLINS 4 NOS.
2 NOS.

15
2 NOS. FIXING SLOTS 75 50 75 that express purpose.
TOP FLANGE -The Contractor is responsible for checking the drawing and verifying all levels

40

49.4
4 1.6 and dimensions at the project site. The Contractor shall report any

90

35
90
4 discrepancies to the engineer and shall obtain written clarification from the
BOT FLANGE

400
48 engineer to resolve all discrepancies prior to commencing any shop fabrication

30.2
56.8

30.7

28.7

15.7

57.3
62.5

49.5
or site work.

15
294.0 1783.2 1165.1 309.6 2 2
3600 KEY PLAN:
VIEW 4-4
PART-3 - RAFTER 1:2.5
C-LIP: 90x40x15x1.6 T PART-2
3600.0
EXTENDED COLMN
104.7 1100 1194 1100
C-90x40x2 THK.
1:10

20.0

1208.4
SLOT-24x12 SLOT-24x12 SLOT-24x12 SLOT-24x12
2 NOS. 2 NOS. 2 NOS. 2 NOS. 2 NOTES:
GENERAL INFORMATION

40
40.0
53.2 103 103 103 103 LATITUDE LONGITUDE 19.413, 76.073
== == == == 90
RAFTER TOP FLANGE 49.8 SITE AREA 37.77 Acres
PURLINS FIXING SLOTS
40
SECTION 2-2 MODULE RATING Wp 535, 540

10
30 SLOT-24x12 SLOT-24x12 30 1:5 SLOT-24x12
NO OF 535Wp MODULES 2520
2 NOS. 2 NOS. 1 NO. FOR
40 1804.2 40 EARTHING NO OF 540Wp MODULES 22512

2460.4
35
1.6
3 NO OF MODULES 25032

85
60
32.1 36.0 130.9 21.5 NOTES:
60

40
3 SLOT-24x12 TOTAL CAPACITY WITH 535Wp (MWp) 1.3482
131.9 50 1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S
1944.2 (BR1) 8 NOS. 2 2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED. 75 50 75 TOTAL CAPACITY WITH 540Wp (MWp) 12.15648
3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350). SLOT-24x12
PART-11

90.0
10

90
TOTAL CAPACITY (MWp) 13.50468
4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE 4 NOS.

2
BRACING-BR1 (REAR) SECTION 3-3 2 SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF MODULES TILT 15°
5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759.
C-LIP 60x40x10x1.6T

64.0
46.7

27.5
62.5

30.9
64.6
1:5

==
6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED PITCH(Mtr's) 8.0
1:10 TO MINIMUM 80 MICRON.
30 SLOT-24x12 SLOT-24x12 30 450.0 SECTION 2-2 7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM. 20 20 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
2 NOS. 2 NOS.
40 1725.3 40 1:5 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED
PART-10 BY '"TORQUE WRENCH METHOD". TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08
3 CONNECTING MEMBER 9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE

1062.5

2
60

75
WITH IS:800 AND IS:802. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
3 C-90x40x2 THK. 10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE
1865.3 (BR2) BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40
1:10 DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL.
200
PART-12 11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS. 1 1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423

BRACING-BR2 (FRONT) SECTION 1-1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48


1:5
C-LIP 60x40x10x1.6T TOTAL NO OF SMB 44
1:10 24.0 SLOT-24x12
SLOT-24x12 TOTAL NO OF LA 8
4180.5 6 NOS.
2 NOS.

12.0
76 1086 68 1086 68 1086 68 642.5 TOTAL NO OF CONVERTION STATIONS(5MVA) 2

51.5
51.5

40
SLOT-18x9 75 75 50

103.0

30
7 NOS.
5 18

PART-1
103

103

9
COLUMN POST-1
75.0 75.0 50.0
1006 3050 5 C-LIP 200x75x20x2T
SLOT-24x12
PART-4 - PURLIN-1 SLOT-24x12
ENLARGED DETAIL-A SLOT-18x9 (TYP) 1:10
2 NOS. 6 NOS. MODULES FIXING
TYPICAL DETAIL 40
HAT: 80x40x25x7x0.9
6350.0
SLOT-18x9
693.5 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 972.5

51.5
A 5 0.9

80
R5 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED

103
R4 03.11.2021 D.V.S GHSV A.V D.V.S CHANGED THE PURLIN MODULE

7
45°
FIXING SLOTS ORIENTATION
R3 25.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
SLOT-24x12 SLOT-24x12 SLOT-24x12 5 103
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 R2 22.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
25 25
3050.0 3050.0 R1 18.10.2021 D.V.S GHSV A.V D.V.S ADDED IS CODES
PART-5 - PURLIN- 2 VIEW 5-5 R0 11.10.2021 D.V.S GHSV A.V D.V.S -----------------------------
1:2.5
HAT: 80x40x25x7x0.9 Rev. Date Designed Drawn Review Approval Description
6350.0
SLOT-18x9 OFFTAKER:
363.5 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 148.5
MAHARASHTRA STATE POWER

51.5
5
GENERATION COMPANY LTD.
103

103
DEVELOPER:
SLOT-24x12 SLOT-24x12 SLOT-24x12 5
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 KARNATAKA RESCO
3050.0
PART-6 - PURLIN- 3 ROOFTOP SOLAR PVT. LTD.
HAT: 80x40x25x7x0.9
IS CODES:
6350.0 CLIENT:
IS 12834-2013 Solar Photovoltaic energy systems
SLOT-18x9
33.5 68.0 1086.0 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 478.5
MS Structural Steel / Sheet (Hot Rolled)
TEPSOL

51.5
Mechanical Properties
IS 2062
5 Chemical Properties
MS Structural Steel / Sheet (Cold Rolled)
PROJECTS PVT. LTD.
103

103
Mechanical Properties
IS 1079
Chemical Properties
PMC:
SLOT-24x12 SLOT-24x12 SLOT-24x12 5 IS 513 (2008)
Cold Reduced Low Carbon Steel
Sheet & Strip BUREAU VERITAS INDUSTRIAL
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 Cold Formed Light Gauge Steel
IS 801 (1975)
3050.0 3050.0 Structural members
Zinc
SERVICES (INDIA) PVT. LTD.
PART-7 -PURLIN- 4 IS 209 Chemical Properties

IS 4759 HDG Structural Steel


HAT: 80x40x25x7x0.9 In-Process EPC CONTRACTOR:
6350.0 IS 1852 Cutting ARDRA POWER
SLOT-18x9 IS 7215 Punching SUIT #202,NISHAN-E-IQBAL
857.5 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 808.5

51.5
As per Specifications Bending ROAD NO.11,BANJARA HILLS
Hot Dip Galvanizing HYDERABAD-500034,TELANGANA
5 IS 4759, IS 2629 Defects & Surface Finish
IS 6745 Mass of Zinc Coating
103

103
Designed: Drawn:
IS 2633 Uniformity in thickness
IS 4759 Coating thickness
SLOT-24x12 SLOT-24x12 SLOT-24x12 5 IS 875 Wind Speed loading, dead, live,
snow & wind loads
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 IS 1893 Part -1
Criteria of Earthquake Resistant
3050.0
Design of Structures
Ordinary Port Land Cement,
D.V.S 11.10.2021 GHSV 11.10.2021
IS 12269 53 Grade - Specification
IS 10262 Concrete Mix Proportioning - Guidelines Reviewed: Approved:
PART-8 -PURLIN- 5
HAT: 80x40x25x7x0.9
A.V 11.10.2021 D.V.S 11.10.2021
4065.5
SLOT-18x9 Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
SLOT-24x12 527.5 68.0 7 NOS. 1086.0 68.0 1086.0 68.0 1086.0 76.0
6 NOS.
PHOTOVOLTAIC PROJECT
5 AT BHENDALA ,MAHARASHTRA.
Drawing Title: MODULES MOUNTING STRUCTURE 2Px28 ECCENTRIC
103

103

PART DETAILS & FABRICATION DRAWINGS


51.5

50 75 75 3865.5
5
Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
3050.0 SLOT-24x12
2 NOS. Date: 11.10.2021 02 of 08 R5
PART-9 - PURLIN- 6 Scale: AS SHOWN
HAT: 80x40x25x7x0.9 Graphic Scale: Original Size: A1
0 - -
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
be used or reproduced (in whole or in part) for purposes other than the project
named below without the express written consent of TEPSOL Projects Pvt.
16240.0 (PURLINS) -This drawing is not to be used for construction until sealed by the engineer for
2197 2197 that express purpose.
16136.0 (MODULES ARRGT. LG.)
-The Contractor is responsible for checking the drawing and verifying all levels
6777.5-P1
3612.5-P3 587 E N

and dimensions at the project site. The Contractor shall report any

N
E
N
20 6350.0-P2 4
1134 RAFTER C-LIP: 10 *113 W E discrepancies to the engineer and shall obtain written clarification from the
GAP(TYP) 3 250 250 2274
90x40x15x1.6 T O.L O.L 1100 SW engineer to resolve all discrepancies prior to commencing any shop fabrication

SE
B or site work.
20
H 587
SOUT
2P*14

HARDWARE S
587 12 KEY PLAN:
3600
MODULE-JINKO 4
10 *113 75
2274x1134x30H 2274 HARDWARE
11

1182
(535Wp) 1100 280
CLEARANCE

20
BRACINGS PURLIN- HAT:
GROUND
1000

80x40x25x7x0.9
2

200
CONNECTING MEMBER
7 587 11
RAFTER C-LIP:
200

C-90x40x2 THK.
3600

15°
105 90x40x15x1.6 T

20
30
COLUMN POST-1 E 3

G)

2182
1

BR R1)
C-LIP 200x75x20x2T 11

IN
1200

C-LIP 200x75x20x2 THK.

B
AC
EXTENDED COLMN

EA 4 4 (
NOTES:

1410
2 COLUMN POST-1
C-90x40x2 THK. 1:10

19
GROUND CLEARANCE
PURLIN- HAT:

R
B 80x40x25x7x0.9 264 40 GENERAL INFORMATION

(R
EARTHING
443 3050 3050 3050 3050 3050 443 1
4 to 6 BRACING-BR2 FR 865 ( HOLE BRACING-BR1
LATITUDE LONGITUDE 19.413, 76.073
C-LIP 60x40x10x1.6T ONT BR2 450

1000

58
DIA. 300 MM, C-LIP 60x40x10x1.6T
1 13 2 3 4 5 6 BR )

°
26°
M25 GRADE FDN. A SITE AREA 37.77 Acres
VIEW A-A 9 C ING 8

2
1200mm DEEP PILE
MODULE RATING Wp 535, 540
1:50 CONNECTING MEMBER
ELEVATION OF 2Px14 MODULES ASSEMBLY STRUCTURE 10

90
300
C-90x40x2 THK. NO OF 535Wp MODULES 2520

200
F.G.L
NO OF 540Wp MODULES 22512

6777.5 (PURLIN-1) 4 11 NO OF MODULES 25032


2024 1453
1134 20 6350.0 (PURLIN-2) 5 TOTAL CAPACITY WITH 535Wp (MWp) 1.3482
3612.5 (PURLIN-3) 6
1086 GAP(TYP) RAFTER C-LIP: PURLIN- HAT: EXTENDED COLUMN &

850
3 250 250 TOTAL CAPACITY WITH 540Wp (MWp) 12.15648
90x40x15x1.6 T 80x40x25x7x0.9 COLUMN POST-1
C/C OVERLAP OVERLAP C-LIP 200x75x20x2T 1 CONNECTING MEMBER 13.50468

1200
TOTAL CAPACITY (MWp)
2460.4 LG. C-90x40x2 THK.
MODULES TILT 15°
11 1:2.5
PITCH(Mtr's) 8.0
2274x1134

EXTENDED COLMN

400
40
2

15
100
C-90x40x2 THK. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
4412 (15° TILTED PLAN)

DIA. 300 MM,

50
M25 GRADE FDN.
13 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08
COULUMNS
L CENTER 1200mm DEEP PILE
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
VIEW B-B 1.6

90
COLUMN POST-1 1:20 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40
1
C-LIP 200x75x20x2T
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423
2274x1134

COLUMN POST-1

57.5
C-LIP 200x75x20x2T 1 250 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48
OVERLAP

15
TOTAL NO OF SMB 44
℄ OF OVERLAP 50 7575 50 MODULE FIXING RAFTER
PURLIN-A PURLIN-B HOLE
RAFTER C-LIP:
3 40 C-LIP 90x40x15x1.6 THK. TOTAL NO OF LA 8
90x40x15x1.6 T
1:2.5
SECTION D-D TOTAL NO OF CONVERTION STATIONS(5MVA) 2
1:20
443 3050 3050 3050 3050 3050 443 40

10
A A
RAFTER C-LIP:
1 2 3 4 5 6 3 0.9

80
90x40x15x1.6 T

20 20 DETAIL-A
PLAN OF 2Px14 MODULES ASSEMBLY STRUCTURE (15° TILTED) 1:20 1.6

60
45°

7
1:50 EXTENDED COLMN
C-90x40x2 THK. 2

Ø300
103

75
COLUMN POST-1 RAFTER FIXING 25 25
C-LIP 200x75x20x2T 1 HOLES

10
16240 (PURLINS) 200
PURLIN SECTION BRACING (BR1 & BR2)
16136 (MODULES ARRGT. LG.) SECTION C-C
1:20
HAT 80x40x25x7x0.9 C-LIP 60x40x10x1.6 THK.
6777.5 (PURLIN-1) 1:2.5 1:2.5
1134 6350.0 (PURLIN-2)
3612.5 (PURLIN-3) R4 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED
1086 RAFTER C-LIP: PURLIN- HAT:
90x40x15x1.6 T
3 250 250 DOCUMENT NUMBER CHANGED
C/C 80x40x25x7x0.9 RAFTER
HARDWARE
12 R3 03.11.2021 D.V.S GHSV A.V D.V.S
OVERLAP OVERLAP 3 AS PER NEW MDL
HARDWARE R2 25.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
11 PURLIN-B
R1 22.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
587

R0 18.10.2021 D.V.S GHSV A.V D.V.S -----------------------------


BRACING
Rev. Date Designed Drawn Review Approval Description
2274x1134

A
1100
C/C

PURLIN-A 250 AP OFFTAKER:


L
O VER
MAHARASHTRA STATE POWER
4568 (TRUE PLAN)

PURLINS OVERLAP ARRANGEMENT IN 3D


GENERATION COMPANY LTD.
587

1:20
20
587

DEVELOPER:
KARNATAKA RESCO
2274x1134

COLUMN POST-1
1100
C/C

C-LIP 200x75x20x2T
1
NOTES: ROOFTOP SOLAR PVT. LTD.
1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S
2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED.
CLIENT:
587

3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350).


4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE
SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF
TEPSOL
443 3050 3050 3050 3050 3050 443 5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759.
6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED PROJECTS PVT. LTD.
1 2 3 4 5 6 TO MINIMUM 80 MICRON.
7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.
VIEW E-E 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED PMC:
1:50
PLAN OF 2Px14 MODULES ASSEMBLY STRUCTURE
BY '"TORQUE WRENCH METHOD".
9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE
BUREAU VERITAS INDUSTRIAL
WITH IS:800 AND IS:802.
10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE
SERVICES (INDIA) PVT. LTD.
BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL.
11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS. EPC CONTRACTOR:
ARDRA POWER
IS CODES: SUIT #202,NISHAN-E-IQBAL
IS 12834-2013 Solar Photovoltaic energy systems ROAD NO.11,BANJARA HILLS
MS Structural Steel / Sheet (Hot Rolled) HYDERABAD-500034,TELANGANA
Mechanical Properties
IS 2062
Chemical Properties Designed: Drawn:
MS Structural Steel / Sheet (Cold Rolled)
Mechanical Properties
IS 1079
Chemical Properties
D.V.S 18.10.2021 GHSV 18.10.2021
Cold Reduced Low Carbon Steel
IS 513 (2008) Reviewed: Approved:
Sheet & Strip
Cold Formed Light Gauge Steel
IS 801 (1975)
Structural members
Zinc
IS 209 Chemical Properties A.V 18.10.2021 D.V.S 18.10.2021
IS 4759 HDG Structural Steel
In-Process
Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
IS 1852 Cutting
PHOTOVOLTAIC PROJECT
IS 7215 Punching
AT BHENDALA ,MAHARASHTRA.
As per Specifications Bending Drawing Title: MODULES MOUNTING STRUCTURE
Hot Dip Galvanizing
2Px14 ECCENTRIC GA DRAWING
IS 4759, IS 2629 Defects & Surface Finish
IS 6745 Mass of Zinc Coating
IS 2633 Uniformity in thickness
Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
IS 4759 Coating thickness Date: 18.10.2021 03 of 08 R4
IS 875 Wind Speed loading, dead, live,
snow & wind loads
Scale: AS SHOWN
Criteria of Earthquake Resistant
IS 1893 Part -1 Design of Structures
Ordinary Port Land Cement,
Graphic Scale: 0
Original Size: A1
IS 12269 - -
53 Grade - Specification
IS 10262 Concrete Mix Proportioning - Guidelines
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
be used or reproduced (in whole or in part) for purposes other than the project
40 90 SLOT-24x12 SLOT-24x12 named below without the express written consent of TEPSOL Projects Pvt.

30
263.6 30.3 48.3 1155.9 29.5 4 NOS.
1792.2 2 NOS. 200 -This drawing is not to be used for construction until sealed by the engineer for
SLOT-24x12 280.2
SLOT-24x12 75 50 75 that express purpose.
SLOT-24x12 PURLINS 4 NOS.
2 NOS.

15
-The Contractor is responsible for checking the drawing and verifying all levels

40
2 NOS. FIXING SLOTS

49.4
TOP FLANGE and dimensions at the project site. The Contractor shall report any
4

35
1.6 discrepancies to the engineer and shall obtain written clarification from the

90

90
4

400
engineer to resolve all discrepancies prior to commencing any shop fabrication
BOT FLANGE or site work.
48

30.7

28.7

15.7

57.3
30.2
56.8

62.5

49.5
2 2

15
294.0 1783.2 1165.1 309.6 KEY PLAN:
3600
VIEW 4-4
PART-3 - RAFTER 1:2.5 PART-2
C-LIP: 90x40x15x1.6 T EXTENDED COLMN
3600.0 C-90x40x2 THK.
1:10

1208.4
104.7 1100 1194 1100

20.0
2
SLOT-24x12 SLOT-24x12 SLOT-24x12 SLOT-24x12
2 NOS. 2 NOS. 2 NOS. 2 NOS. NOTES:

40
GENERAL INFORMATION
90

40.0
53.2 103 103 103 103 19.413, 76.073
LATITUDE LONGITUDE
== == == ==
RAFTER TOP FLANGE 49.8 SECTION 2-2 SITE AREA 37.77 Acres
PURLINS FIXING SLOTS
1:5 SLOT-24x12 MODULE RATING Wp
40 535, 540

10
30 SLOT-24x12 SLOT-24x12 30 1 NO. FOR
EARTHING NO OF 535Wp MODULES 2520
2 NOS. 2 NOS.

2460.4
40 1804.2 40

35
32.1 36.0 130.9 21.5 NO OF 540Wp MODULES 22512

85
40
1.6
3

60
SLOT-24x12 NO OF MODULES 25032
60

131.9 50
3 8 NOS. 2 TOTAL CAPACITY WITH 535Wp (MWp) 1.3482
75 50 75
1944.2 (BR1)

90.0
SLOT-24x12

90
TOTAL CAPACITY WITH 540Wp (MWp) 12.15648

2
4 NOS.
PART-11

10
2 TOTAL CAPACITY (MWp) 13.50468
BRACING-BR1 (REAR)

64.0
46.7

30.9
64.6
27.5
62.5
==
SECTION 3-3 MODULES TILT 15°
C-LIP 60x40x10x1.6T 1:5 450.0 SECTION 2-2 PITCH(Mtr's) 8.0
1:10 1:5 20 20
SLOT-24x12 SLOT-24x12 30
30
2 NOS. 2 NOS. PART-10 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
40 1725.3 40
CONNECTING MEMBER NOTES:

1062.5

2
3 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08

75
C-90x40x2 THK. 1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S
60

2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
3 1:10 3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350).
1865.3 (BR2) 4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE 200
SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF
1 1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40

PART-12 24.0 SLOT-24x12


5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759. SECTION 1-1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423
6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED
BRACING-BR2 (FRONT) 6 NOS. 1:5 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48
TO MINIMUM 80 MICRON.
7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.

12.0
C-LIP 60x40x10x1.6T 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED SLOT-24x12 TOTAL NO OF SMB 44

51.5
1:10 BY '"TORQUE WRENCH METHOD". 2 NOS.

103.0
9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE TOTAL NO OF LA 8
WITH IS:800 AND IS:802.

40
TOTAL NO OF CONVERTION STATIONS(5MVA) 2
10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE

30
18 BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL.
75.0 75.0 50.0 PART-1
11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS.
9

ENLARGED DETAIL-A COLUMN POST-1


SLOT-18x9 (TYP)
TYPICAL DETAIL C-LIP 200x75x20x2T
1:10
MODULES FIXING
6777.5
76.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 931.5
SLOT-18x9 75.0 75.0 50.0
11 NOS. A 5

103

103
R4 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED

R3 03.11.2021 D.V.S GHSV A.V D.V.S CHANGED THE PURLIN MODULE


552.5 3050.0 3050.0 5 FIXING SLOTS ORIENTATION

51.5
R2 25.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
SLOT-24x12 SLOT-24x12
2 NOS. 6 NOS. R1 22.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
PART-4 - PURLIN-1
R0 18.10.2021 D.V.S GHSV A.V D.V.S -----------------------------
HAT: 80x40x25x7x0.9
Rev. Date Designed Drawn Review Approval Description

6350.0 OFFTAKER:

404.5 68.0
SLOT-18x9
10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 107.5
MAHARASHTRA STATE POWER

51.5
5 GENERATION COMPANY LTD.
103

103
DEVELOPER:

50.0 75.0 75.0


SLOT-24x12
6 NOS.
SLOT-24x12
2 NOS. 5950.0
SLOT-24x12
6 NOS. 75.0 75.0 50.0
5 KARNATAKA RESCO
3050.0 3050.0 ROOFTOP SOLAR PVT. LTD.
PART-5 - PURLIN- 2 CLIENT:
HAT: 80x40x25x7x0.9 40
3612.5
TEPSOL
74.5 68
SLOT-24x12
6 NOS. 1086.0 68.0 1086.0 68.0 1086.0 76.0 PROJECTS PVT. LTD.
51.5

5 0.9

80
PMC:
BUREAU VERITAS INDUSTRIAL
103

103

45°

7
SLOT-24x12 5 103 SERVICES (INDIA) PVT. LTD.
50.0 75.0 75.0 3412.5 2 NOS. 25 25
3050.0
VIEW 5-5 EPC CONTRACTOR:
PART-9 - PURLIN- 6 1:2.5 ARDRA POWER
SUIT #202,NISHAN-E-IQBAL
HAT: 80x40x25x7x0.9 ROAD NO.11,BANJARA HILLS
IS CODES: HYDERABAD-500034,TELANGANA
IS 12834-2013 Solar Photovoltaic energy systems
MS Structural Steel / Sheet (Hot Rolled)
Mechanical Properties
Designed: Drawn:
IS 2062
Chemical Properties
MS Structural Steel / Sheet (Cold Rolled)
Mechanical Properties
IS 1079 D.V.S 18.10.2021 GHSV 18.10.2021
Chemical Properties

IS 513 (2008)
Cold Reduced Low Carbon Steel Reviewed: Approved:
Sheet & Strip
Cold Formed Light Gauge Steel
IS 801 (1975)
Structural members
Zinc
IS 209 Chemical Properties
A.V 18.10.2021 D.V.S 18.10.2021
IS 4759 HDG Structural Steel
In-Process
Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
IS 1852 Cutting PHOTOVOLTAIC PROJECT
IS 7215 Punching AT BHENDALA ,MAHARASHTRA.
As per Specifications Bending
Hot Dip Galvanizing Drawing Title: MODULES MOUNTING STRUCTURE 2Px14 ECCENTRIC
IS 4759, IS 2629 Defects & Surface Finish PART DETAILS & FABRICATION DRAWINGS
IS 6745 Mass of Zinc Coating
IS 2633 Uniformity in thickness
IS 4759 Coating thickness
Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
IS 875 Wind Speed loading, dead, live,
snow & wind loads
Date: 18.10.2021 04 of 08 R4
Criteria of Earthquake Resistant
IS 1893 Part -1 Design of Structures
Ordinary Port Land Cement,
Scale: AS SHOWN
IS 12269 53 Grade - Specification
IS 10262 Concrete Mix Proportioning - Guidelines Graphic Scale: 0
Original Size: A1
- -
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
32396 (PURLINS) be used or reproduced (in whole or in part) for purposes other than the project
named below without the express written consent of TEPSOL Projects Pvt.
32292 (MODULES ARRGT. LG.)
-This drawing is not to be used for construction until sealed by the engineer for
1134 20
GAP(TYP)
that express purpose.
RAFTER C-LIP: N -The Contractor is responsible for checking the drawing and verifying all levels
3 and dimensions at the project site. The Contractor shall report any

N
90x40x15x1.6 T

E
N
W E discrepancies to the engineer and shall obtain written clarification from the
B SW engineer to resolve all discrepancies prior to commencing any shop fabrication

SE
2P*28

or site work.

65 S
KEY PLAN:
CLEARANCE
GROUND

BRACINGS PURLIN- HAT:

20
8 4 80x40x25x7x0.9
1000

CONNECTING MEMBER 2
7

120
200

C-90x40x2 THK.

COLUMN POST-1

20
1
C-LIP 120x65x20x2T
1200

EXTENDED COLMN
C-90x40x2 THK.
2 C-LIP 120x65x20x2 THK.
B COLUMN POST-1 NOTES:
901 3050 3050 3050 3050 3050 3050 3050 3050 3050 3050 891 1:5
40 GENERAL INFORMATION
1 DIA. 300 MM, 2 3 4 5 6 7 8 9 10 11
M25 GRADE FDN.
16
LATITUDE LONGITUDE 19.413, 76.073
1200mm DEEP PILE VIEW A-A
1:50 SITE AREA 37.77 Acres
ELEVATION OF 2Px28 MODULES ASSEMBLY STRUCTURE

2
4180.5 (PURLIN-1) 4 MODULE RATING Wp 535, 540
1134 PURLIN- HAT: 6350 (PURLIN-2) 5 6350 (PURLIN-4) 7 4065.5 (PURLIN-6) 9
6350 (PURLIN-3) 6 2520

90
80x40x25x7x0.9 6350 (PURLIN-5) 8 NO OF 535Wp MODULES
1086 PURLIN- HAT:
20 250 80x40x25x7x0.9 250 250 250 250 NO OF 540Wp MODULES 22512
C/C OVERLAP OVERLAP OVERLAP OVERLAP OVERLAP
GAP(TYP)
NO OF MODULES 25032

TOTAL CAPACITY WITH 535Wp (MWp) 1.3482

EXTENDED COLUMN & 12.15648


2274x1134

TOTAL CAPACITY WITH 540Wp (MWp)


CONNECTING MEMBER TOTAL CAPACITY (MWp) 13.50468
4412 (15° TILTED PLAN)

C-90x40x2 THK. 15°


MODULES TILT
1:2.5
COULUMNS
L CENTER PITCH(Mtr's) 8.0
40

15
COLUMN POST-1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
1
C-LIP 200x75x20x2T
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08
2274x1134

1.6 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382

90
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40

TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423

TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48

901 3050 3050 3050 3050 3050 3050 3050 3050 3050 3050 891 TOTAL NO OF SMB 44

15
A A RAFTER
1 2 3 4 5 6 7 8 9 10 11 TOTAL NO OF LA 8
C-LIP 90x40x15x1.6 THK.
1:2.5
PLAN OF 2Px28 MODULES ASSEMBLY STRUCTURE (15° TILTED) TOTAL NO OF CONVERTION STATIONS(5MVA) 2
1:50
40

10
32396 (PURLINS)
32292 (MODULES ARRGT. LG.)
4180.5 (PURLIN-1) 1.6

60
1134 6350 (PURLIN-2) 6350 (PURLIN-4) 4065.5 (PURLIN-6)
6350 (PURLIN-3) 6350 (PURLIN-5)
1086 PURLIN- HAT:
80x40x25x7x0.9 250 250 250 250 250
C/C OVERLAP OVERLAP OVERLAP OVERLAP OVERLAP

10
BRACING (BR1 & BR2)
587

C-LIP 60x40x10x1.6 THK.


1:2.5
2274x1134

IS CODES:
IS 12834-2013 Solar Photovoltaic energy systems R4 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED
1100
C/C

MS Structural Steel / Sheet (Hot Rolled) DOCUMENT NUMBER CHANGED


R3 03.11.2021 D.V.S GHSV A.V D.V.S AS PER NEW MDL
Mechanical Properties
IS 2062
4568 (TRUE PLAN)

Chemical Properties R2 26.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS


MS Structural Steel / Sheet (Cold Rolled)
587

R1 18.10.2021 D.V.S GHSV A.V D.V.S ADDED IS CODES


Mechanical Properties
IS 1079
20

Chemical Properties R0 11.10.2021 D.V.S GHSV A.V D.V.S -----------------------------


587

Cold Reduced Low Carbon Steel


IS 513 (2008)
Sheet & Strip
Rev. Date Designed Drawn Review Approval Description
Cold Formed Light Gauge Steel
IS 801 (1975)
Structural members OFFTAKER:
2274x1134

COLUMN POST-1 Zinc


MAHARASHTRA STATE POWER
1100
C/C

C-LIP 200x75x20x2T IS 209 Chemical Properties

1 IS 4759 HDG Structural Steel


In-Process GENERATION COMPANY LTD.
IS 1852 Cutting
587

IS 7215 Punching
As per Specifications Bending DEVELOPER:
901 3050 3050 3050 3050 3050 3050 3050 3050 3050 3050 891
IS 4759, IS 2629
Hot Dip Galvanizing
Defects & Surface Finish
KARNATAKA RESCO
1 2 3 4 5 6 7 8 9 10 11 IS 6745 Mass of Zinc Coating
ROOFTOP SOLAR PVT. LTD.
IS 2633 Uniformity in thickness

2197 2197 VIEW E-E IS 4759 Coating thickness


1:50 IS 875 Wind Speed loading, dead, live,
snow & wind loads CLIENT:
587 E PLAN OF 2Px28 MODULES ASSEMBLY STRUCTURE MODULE FIXING IS 1893 Part -1
Criteria of Earthquake Resistant
Design of Structures

13 2274
*113
4 HOLE 40 IS 12269
IS 10262
Ordinary Port Land Cement,
53 Grade - Specification
Concrete Mix Proportioning - Guidelines
TEPSOL
1100 NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S PROJECTS PVT. LTD.
20 250 2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED.
H 587
SOUT HARDWARE OVERLAP 3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350).
HARDWARE RAFTER 14 0.9 PMC:

80
15 3 50 7575 50 4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE
587 3600
13
MODULE-JINKO
*113
4 14
HARDWARE
PURLIN-B
PURLIN-A PURLIN-B SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF BUREAU VERITAS INDUSTRIAL
2274x1134x30H 2 274 HARDWARE
14
5 5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759.
1182

45°

7
1100 280
(535Wp) 6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED
TO MINIMUM 80 MICRON.
SERVICES (INDIA) PVT. LTD.
BRACING 103
7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.
587 14 RAFTER FIXING 25 25 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED
RAFTER C-LIP: RAFTER C-LIP:
3600 3 HOLES BY '"TORQUE WRENCH METHOD". EPC CONTRACTOR:
15°

105 90x40x15x1.6 T 90x40x15x1.6 T


30

250 AP ARDRA POWER


PURLIN-A 9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE
E 3 4 DETAIL-A PURLIN SECTION
G)

2182

L
ER WITH IS:800 AND IS:802.
BR R1)

14 1:20
IN

O V HAT 80x40x25x7x0.9 SUIT #202,NISHAN-E-IQBAL


10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE
AC
B

ROAD NO.11,BANJARA HILLS


EA 44 (

PURLINS OVERLAP ARRANGEMENT IN 3D 1:2.5


1410

BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
1:20 HYDERABAD-500034,TELANGANA
19

DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL.
GROUND CLEARANCE

PURLIN- HAT:
R

80x40x25x7x0.9 264 11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS.
(R

EARTHING Designed: Drawn:


4 to 9 BRACING-BR2 186 HOLE BRACING-BR1
FR 5
C-LIP 60x30x10x1.6T ONT (BR2 450
1000

58

C-LIP 60x30x10x1.6T
BR )
°
26°

12 A CIN
G 11
D.V.S 11.10.2021 GHSV 11.10.2021
CONNECTING MEMBER Reviewed: Approved:
10
300

C-90x40x2 THK.
200

F.G.L

COLUMN POST-1
52.5

14 120 1
C-LIP 120x65x20x2T A.V 11.10.2021 D.V.S 11.10.2021
2024 1453
℄ OF OVERLAP Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
850

COLUMN POST-1 RAFTER C-LIP: PHOTOVOLTAIC PROJECT


1 3
C-LIP 120x65x20x2T 90x40x15x1.6 T AT BHENDALA ,MAHARASHTRA.
1200

SECTION D-D
2460.4 LG. 1:20
Drawing Title: MODULES MOUNTING STRUCTURE
14 20 20 2Px28 UDL GA DRAWING
400

EXTENDED COLMN EXTENDED COLMN


2 2
100

C-90x40x2 THK. C-90x40x2 THK.


Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
Ø300
65

DIA. 300 MM, Date: 11.10.2021 05 of 08 R4


50

COLUMN POST-1
M25 GRADE FDN. 16 C-LIP 200x75x20x2T 1
1200mm DEEP PILE Scale: AS SHOWN
120
VIEW B-B Graphic Scale: 0
Original Size: A1
SECTION C-C - -
1:20 1:20
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
48.3 1155.9 29.5
40 be used or reproduced (in whole or in part) for purposes other than the project
263.6 30.3 90 SLOT-24x12
1792.2 SLOT-24x12 280.2 SLOT-24x12 named below without the express written consent of TEPSOL Projects Pvt.

30
SLOT-24x12 2 NOS. 4 NOS. 120 -This drawing is not to be used for construction until sealed by the engineer for
SLOT-24x12 PURLINS 4 NOS.
2 NOS.

15
2 NOS. FIXING SLOTS 35 50 35 that express purpose.
TOP FLANGE -The Contractor is responsible for checking the drawing and verifying all levels

40

49.4
4 1.6 and dimensions at the project site. The Contractor shall report any

90

35
90
4 discrepancies to the engineer and shall obtain written clarification from the
BOT FLANGE

400
48 engineer to resolve all discrepancies prior to commencing any shop fabrication

30.2
56.8

30.7

28.7

15.7

57.3
62.5

49.5
or site work.

15
294.0 1783.2 1165.1 309.6 2 2
3600 KEY PLAN:
VIEW 4-4
PART-3 - RAFTER 1:2.5
C-LIP: 90x40x15x1.6 T PART-2
3600.0
EXTENDED COLMN
104.7 1100 1194 1100
C-90x40x2 THK.
1:10

20.0

1208.4
SLOT-24x12 SLOT-24x12 SLOT-24x12 SLOT-24x12
2 NOS. 2 NOS. 2 NOS. 2 NOS. 2
NOTES:

40
GENERAL INFORMATION

40.0
53.2 103 103 103 103
== == == == 90
RAFTER TOP FLANGE 49.8 LATITUDE LONGITUDE 19.413, 76.073
PURLINS FIXING SLOTS
30
SECTION 2-2 SITE AREA 37.77 Acres

10
30 SLOT-24x12 SLOT-24x12 30 1:5 SLOT-24x12 MODULE RATING Wp 535, 540
2 NOS. 2 NOS. 1 NO. FOR
40 1804.2 40 EARTHING NO OF 535Wp MODULES 2520

2460.4
35
1.6
3 NO OF 540Wp MODULES 22512

85
60
32.1 36.0 130.9 21.5 NOTES:
60

40
3 SLOT-24x12 NO OF MODULES 25032
131.9 50 1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S
1944.2 (BR1) 8 NOS. 2 2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED.
TOTAL CAPACITY WITH 535Wp (MWp) 1.3482
35 50 35
3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350). SLOT-24x12
PART-11

90.0
TOTAL CAPACITY WITH 540Wp (MWp) 12.15648

10

90
4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE 4 NOS.

2
BRACING-BR1 (REAR) SECTION 3-3 2 SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF TOTAL CAPACITY (MWp) 13.50468
5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759.
C-LIP 60x40x10x1.6T

64.0
46.7

27.5
62.5

30.9
64.6
1:5

==
6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED MODULES TILT 15°
1:10 TO MINIMUM 80 MICRON.
30 SLOT-24x12 SLOT-24x12 30 450.0 SECTION 2-2 7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.
PITCH(Mtr's) 8.0
2 NOS. 2 NOS.
40 1725.3 40 1:5 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED 20 20
PART-10 BY '"TORQUE WRENCH METHOD". TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
3 CONNECTING MEMBER 9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE

1062.5
60

WITH IS:800 AND IS:802. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08

65
3 C-90x40x2 THK. 10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
1865.3 (BR2) BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
1:10 DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL. 120
PART-12 11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS. 1 1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40

BRACING-BR2 (FRONT) SECTION 1-1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423
1:5
C-LIP 60x40x10x1.6T TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48

1:10 24.0 SLOT-24x12


SLOT-24x12 TOTAL NO OF SMB 44
4180.5 6 NOS.
2 NOS.
TOTAL NO OF LA 8

12.0
76 1086 68 1086 68 1086 68 642.5

51.5
51.5

40
SLOT-18x9 75 75 50 TOTAL NO OF CONVERTION STATIONS(5MVA) 2

103.0
18

30
7 NOS.
5
PART-1

9
103

103
COLUMN POST-1
75.0 75.0 50.0
1006 3050 5 SLOT-18x9 (TYP) C-LIP 120x65x20x2T
SLOT-24x12 SLOT-24x12
2 NOS. PART-4 - PURLIN-1 6 NOS.
ENLARGED DETAIL-A MODULES FIXING 1:10
TYPICAL DETAIL 40
HAT: 80x40x25x7x0.9
6350.0
SLOT-18x9
693.5 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 972.5

51.5
A 5 0.9

80
103
R4 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED

7
45°
R3 03.11.2021 D.V.S GHSV A.V D.V.S CHANGED THE PURLIN MODULE
SLOT-24x12 SLOT-24x12 SLOT-24x12 5 103
FIXING SLOTS ORIENTATION
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 R2 26.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
25 25
3050.0 3050.0 R1 18.10.2021 D.V.S GHSV A.V D.V.S ADDED IS CODES
PART-5 - PURLIN- 2 VIEW 5-5 R0 11.10.2021 D.V.S GHSV A.V D.V.S -----------------------------
1:2.5
HAT: 80x40x25x7x0.9 Rev. Date Designed Drawn Review Approval Description
6350.0
SLOT-18x9 OFFTAKER:
363.5 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 148.5
MAHARASHTRA STATE POWER

51.5
5
GENERATION COMPANY LTD.
103

103
DEVELOPER:
SLOT-24x12 SLOT-24x12 SLOT-24x12 5
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 KARNATAKA RESCO
3050.0
PART-6 - PURLIN- 3 ROOFTOP SOLAR PVT. LTD.
HAT: 80x40x25x7x0.9
IS CODES:
6350.0 CLIENT:
IS 12834-2013 Solar Photovoltaic energy systems
SLOT-18x9
33.5 68.0 1086.0 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 478.5
MS Structural Steel / Sheet (Hot Rolled)
TEPSOL

51.5
Mechanical Properties
IS 2062
5 Chemical Properties
MS Structural Steel / Sheet (Cold Rolled)
PROJECTS PVT. LTD.
103

103
Mechanical Properties
IS 1079
Chemical Properties
PMC:
SLOT-24x12 SLOT-24x12 SLOT-24x12 5 IS 513 (2008)
Cold Reduced Low Carbon Steel
Sheet & Strip BUREAU VERITAS INDUSTRIAL
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 Cold Formed Light Gauge Steel
IS 801 (1975)
3050.0 3050.0 Structural members
Zinc
SERVICES (INDIA) PVT. LTD.
PART-7 -PURLIN- 4 IS 209 Chemical Properties

IS 4759 HDG Structural Steel


HAT: 80x40x25x7x0.9 In-Process EPC CONTRACTOR:
6350.0 IS 1852 Cutting ARDRA POWER
SLOT-18x9 IS 7215 Punching SUIT #202,NISHAN-E-IQBAL
857.5 68.0 10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 808.5

51.5
As per Specifications Bending ROAD NO.11,BANJARA HILLS
Hot Dip Galvanizing HYDERABAD-500034,TELANGANA
5 IS 4759, IS 2629 Defects & Surface Finish
IS 6745 Mass of Zinc Coating
103

103
Designed: Drawn:
IS 2633 Uniformity in thickness
IS 4759 Coating thickness
SLOT-24x12 SLOT-24x12 SLOT-24x12 5 IS 875 Wind Speed loading, dead, live,
snow & wind loads
50 75 75 6 NOS. 2 NOS. 5950.0 6 NOS. 75 75 50 IS 1893 Part -1
Criteria of Earthquake Resistant
3050.0
Design of Structures
Ordinary Port Land Cement,
D.V.S 11.10.2021 GHSV 11.10.2021
IS 12269 53 Grade - Specification
IS 10262 Concrete Mix Proportioning - Guidelines Reviewed: Approved:
PART-8 -PURLIN- 5
HAT: 80x40x25x7x0.9
A.V 11.10.2021 D.V.S 11.10.2021
4065.5
SLOT-18x9 Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
SLOT-24x12 527.5 68.0 7 NOS. 1086.0 68.0 1086.0 68.0 1086.0 88.5
6 NOS.
PHOTOVOLTAIC PROJECT
5 AT BHENDALA ,MAHARASHTRA.
Drawing Title: MODULES MOUNTING STRUCTURE 2Px28 UDL
103

103

PART DETAILS & FABRICATION DRAWINGS


51.5

50 75 75 3865.5
5
Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
3050.0 SLOT-24x12
2 NOS. Date: 11.10.2021 06 of 08 R4
PART-9 - PURLIN- 6 Scale: AS SHOWN
HAT: 80x40x25x7x0.9 Graphic Scale: Original Size: A1
0 - -
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
be used or reproduced (in whole or in part) for purposes other than the project
named below without the express written consent of TEPSOL Projects Pvt.
16240.0 (PURLINS) -This drawing is not to be used for construction until sealed by the engineer for
2197 2197 that express purpose.
16136.0 (MODULES ARRGT. LG.)
-The Contractor is responsible for checking the drawing and verifying all levels
6777.5-P1 587 E N

and dimensions at the project site. The Contractor shall report any

N
3612.5-P3

E
N
6350.0-P2 4
1134 20 10 *113 W E discrepancies to the engineer and shall obtain written clarification from the
GAP(TYP)
RAFTER C-LIP:
3 250 250 2274
90x40x15x1.6 T O.L O.L 1100 SW engineer to resolve all discrepancies prior to commencing any shop fabrication

SE
or site work.
B H
20
SOUT 587
2P*14

HARDWARE 65 S
587 12 KEY PLAN:
3600
MODULE-JINKO 4
10 *113

20
2274x1134x30H 2274 HARDWARE
11

1182
(535Wp) 1100 280
CLEARANCE

BRACINGS PURLIN- HAT: 2

120
GROUND
1000

80x40x25x7x0.9
CONNECTING MEMBER 587 11
7 RAFTER C-LIP:

20
3600
200

C-90x40x2 THK.

15°
105 90x40x15x1.6 T

30
COLUMN POST-1 E 3

G)

2182
1

BR R1)
11 C-LIP 120x65x20x2 THK.

IN
C-LIP 120x65x20x2T
1200

B
AC
COLUMN POST-1

EA 4 4 (
EXTENDED COLMN NOTES:

1410
C-90x40x2 THK.
2
1:5

19
GROUND CLEARANCE
PURLIN- HAT:

R
B 80x40x25x7x0.9 264 GENERAL INFORMATION
40

(R
EARTHING
458 3050 3050 3050 3050 3050 428 4 to 6 1
BRACING-BR2 FR 865 ( HOLE BRACING-BR1
LATITUDE LONGITUDE 19.413, 76.073
C-LIP 60x30x10x1.6T ONT BR2 450

1000

58
DIA. 300 MM, C-LIP 60x30x10x1.6T
1 2 3 4 5 6 BR )

°
13

26°
A SITE AREA 37.77 Acres
M25 GRADE FDN. 9 C ING 8
VIEW A-A

2
1200mm DEEP PILE
MODULE RATING Wp 535, 540
1:50 CONNECTING MEMBER
ELEVATION OF 2Px14 MODULES ASSEMBLY STRUCTURE 10

90
300
C-90x40x2 THK. NO OF 535Wp MODULES 2520

200
F.G.L
NO OF 540Wp MODULES 22512

4
11 NO OF MODULES 25032
6777.5 (PURLIN-1)
2024 1453
1134 20 6350.0 (PURLIN-2) 5 TOTAL CAPACITY WITH 535Wp (MWp) 1.3482
3612.5 (PURLIN-3) 6
GAP(TYP) RAFTER C-LIP: PURLIN- HAT: EXTENDED COLUMN &

850
1086 TOTAL CAPACITY WITH 540Wp (MWp) 12.15648
90x40x15x1.6 T 3 80x40x25x7x0.9 250 250 COLUMN POST-1
C/C OVERLAP OVERLAP C-LIP 120x65x20x2T 1 CONNECTING MEMBER 13.50468

1200
TOTAL CAPACITY (MWp)
2460.4 LG. C-90x40x2 THK.
MODULES TILT 15°
11 1:2.5
PITCH(Mtr's) 8.0
2274x1134

EXTENDED COLMN

400
2 40

100
C-90x40x2 THK. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
4412 (15° TILTED PLAN)

DIA. 300 MM,

50
13

15
M25 GRADE FDN. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08
COULUMNS
L CENTER 1200mm DEEP PILE
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
VIEW B-B 1.6

90
COLUMN POST-1 1:20 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40
1
C-LIP 200x75x20x2T
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423
2274x1134

15
120 COLUMN POST-1

52.5
C-LIP 120x65x20x2T 1 250 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48
OVERLAP
TOTAL NO OF SMB 44
℄ OF OVERLAP 50 7575 50 MODULE FIXING RAFTER
PURLIN-A PURLIN-B HOLE
RAFTER C-LIP:
3 40 C-LIP 90x40x15x1.6 THK. TOTAL NO OF LA 8
90x40x15x1.6 T
1:2.5
SECTION D-D TOTAL NO OF CONVERTION STATIONS(5MVA) 2
1:20
458 3050 3050 3050 3050 3050 428 30
A A
RAFTER C-LIP:
1 2 3 4 5 6 3 0.9

80

10
90x40x15x1.6 T

20 20 DETAIL-A
PLAN OF 2Px14 MODULES ASSEMBLY STRUCTURE (15° TILTED) 1:20 1.6

60
45°

7
1:50 EXTENDED COLMN
C-90x40x2 THK. 2

Ø300
103

10
65
COLUMN POST-1 RAFTER FIXING 25 25
C-LIP 200x75x20x2T 1 HOLES
16240 (PURLINS) 120
PURLIN SECTION
16136 (MODULES ARRGT. LG.) SECTION C-C
BRACING (BR1 & BR2)
1:20
HAT 80x40x25x7x0.9 C-LIP 60x35x10x1.6 THK.
6777.5 (PURLIN-1) 1:2.5
1:2.5
1134 6350.0 (PURLIN-2)
3612.5 (PURLIN-3)
1086 RAFTER C-LIP: PURLIN- HAT:
90x40x15x1.6 T
3 250 250 HARDWARE
C/C 80x40x25x7x0.9 RAFTER 12 R3 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED
OVERLAP OVERLAP 3
HARDWARE DOCUMENT NUMBER CHANGED
R2 03.11.2021 D.V.S GHSV A.V D.V.S
11 PURLIN-B
AS PER NEW MDL
R1 26.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
587

R0 18.10.2021 D.V.S GHSV A.V D.V.S -----------------------------


BRACING
Rev. Date Designed Drawn Review Approval Description
2274x1134

A
1100
C/C

PURLIN-A 250 AP OFFTAKER:


L
O VER
MAHARASHTRA STATE POWER
4568 (TRUE PLAN)

PURLINS OVERLAP ARRANGEMENT IN 3D


GENERATION COMPANY LTD.
587

1:20
20
587

DEVELOPER:
KARNATAKA RESCO
2274x1134

COLUMN POST-1
1100
C/C

C-LIP 200x75x20x2T
1
NOTES: ROOFTOP SOLAR PVT. LTD.
1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S
2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED.
CLIENT:
587

3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350).


4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE
SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF
TEPSOL
458 3050 3050 3050 3050 3050 428 5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759.
6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED PROJECTS PVT. LTD.
1 2 3 4 5 6 TO MINIMUM 80 MICRON.
7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.
VIEW E-E 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED PMC:
1:50
PLAN OF 2Px14 MODULES ASSEMBLY STRUCTURE
BY '"TORQUE WRENCH METHOD".
9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE
BUREAU VERITAS INDUSTRIAL
WITH IS:800 AND IS:802.
10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE
SERVICES (INDIA) PVT. LTD.
BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL.
11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS. EPC CONTRACTOR:
ARDRA POWER
IS CODES: SUIT #202,NISHAN-E-IQBAL
IS 12834-2013 Solar Photovoltaic energy systems ROAD NO.11,BANJARA HILLS
MS Structural Steel / Sheet (Hot Rolled) HYDERABAD-500034,TELANGANA
Mechanical Properties
IS 2062
Chemical Properties Designed: Drawn:
MS Structural Steel / Sheet (Cold Rolled)
Mechanical Properties
IS 1079
Chemical Properties
D.V.S 18.10.2021 GHSV 18.10.2021
Cold Reduced Low Carbon Steel
IS 513 (2008) Reviewed: Approved:
Sheet & Strip
Cold Formed Light Gauge Steel
IS 801 (1975)
Structural members
Zinc
IS 209 Chemical Properties A.V 18.10.2021 D.V.S 18.10.2021
IS 4759 HDG Structural Steel
In-Process
Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
IS 1852 Cutting
PHOTOVOLTAIC PROJECT
IS 7215 Punching
AT BHENDALA ,MAHARASHTRA.
As per Specifications Bending Drawing Title: MODULES MOUNTING STRUCTURE
Hot Dip Galvanizing
2Px14 UDL GA DRAWING
IS 4759, IS 2629 Defects & Surface Finish
IS 6745 Mass of Zinc Coating
IS 2633 Uniformity in thickness
Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
IS 4759 Coating thickness Date: 18.10.2021 07 of 08 R3
IS 875 Wind Speed loading, dead, live,
snow & wind loads
Scale: AS SHOWN
Criteria of Earthquake Resistant
IS 1893 Part -1 Design of Structures
Ordinary Port Land Cement,
Graphic Scale: 0
Original Size: A1
IS 12269 - -
53 Grade - Specification
IS 10262 Concrete Mix Proportioning - Guidelines
-This drawing is the copyright property of TEPSOL Projects Pvt. Ltd. it may not
be used or reproduced (in whole or in part) for purposes other than the project
40 90 SLOT-24x12 SLOT-24x12 named below without the express written consent of TEPSOL Projects Pvt.

30
263.6 30.3 48.3 1155.9 29.5 4 NOS.
1792.2 2 NOS. 120 -This drawing is not to be used for construction until sealed by the engineer for
SLOT-24x12 280.2
SLOT-24x12 35 50 35 that express purpose.
SLOT-24x12 PURLINS 4 NOS.
2 NOS.

15
-The Contractor is responsible for checking the drawing and verifying all levels

40
2 NOS. FIXING SLOTS

49.4
TOP FLANGE and dimensions at the project site. The Contractor shall report any
4

35
1.6 discrepancies to the engineer and shall obtain written clarification from the

90

90
4

400
engineer to resolve all discrepancies prior to commencing any shop fabrication
BOT FLANGE or site work.
48

30.7

28.7

15.7

57.3
30.2
56.8

62.5

49.5
2 2

15
294.0 1783.2 1165.1 309.6 KEY PLAN:
3600
VIEW 4-4
PART-3 - RAFTER 1:2.5 PART-2
C-LIP: 90x40x15x1.6 T EXTENDED COLMN
3600.0 C-90x40x2 THK.
1:10

1208.4
104.7 1100 1194 1100

20.0
2
SLOT-24x12 SLOT-24x12 SLOT-24x12 SLOT-24x12
2 NOS. 2 NOS. 2 NOS. 2 NOS. NOTES:

40
GENERAL INFORMATION
90

40.0
53.2 103 103 103 103 19.413, 76.073
LATITUDE LONGITUDE
== == == ==
RAFTER TOP FLANGE 49.8 SECTION 2-2 SITE AREA 37.77 Acres
PURLINS FIXING SLOTS
1:5 SLOT-24x12 MODULE RATING Wp
30 535, 540

10
30 SLOT-24x12 SLOT-24x12 30 1 NO. FOR
EARTHING NO OF 535Wp MODULES 2520
2 NOS. 2 NOS.

2460.4
40 1804.2 40

35
32.1 36.0 130.9 21.5 NO OF 540Wp MODULES 22512

85
40
1.6
3

60
SLOT-24x12 NO OF MODULES 25032
60

131.9 50
3 8 NOS. 2 TOTAL CAPACITY WITH 535Wp (MWp) 1.3482
35 50 35
1944.2 (BR1)

90.0
SLOT-24x12

90
TOTAL CAPACITY WITH 540Wp (MWp) 12.15648

2
4 NOS.
PART-11

10
2 TOTAL CAPACITY (MWp) 13.50468
BRACING-BR1 (REAR)

64.0
46.7

30.9
64.6
27.5
62.5
==
SECTION 3-3 MODULES TILT 15°
C-LIP 60x30x10x1.6T 1:5 450.0 SECTION 2-2 PITCH(Mtr's) 8.0
1:10 1:5 20 20
SLOT-24x12 SLOT-24x12 30
30
2 NOS. 2 NOS. PART-10 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 535Wp 41
40 1725.3 40
CONNECTING MEMBER NOTES:

1062.5

65
3 C-90x40x2 THK. 1. ALL DIMENSIONS ARE IN MILLIMETERS. AND ALL LEVELS ARE IN METERS U.O.S
TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 535Wp 08
60

2. FOR DETAIL MATERIAL DESCRIPTION/GRADE AND QTY REFER BOM SHEET ATTACHED. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 WITH 540Wp 382
3 1:10 3. ALL HDG MEMBER SHALL BE AS PER IS:2062 GRADE-A (E350). 120
1865.3 (BR2) 4. ALL THE PUNCHED LOCATION OF GALVALUME SHEET AFTER FABRICATION SHALL BE
1 1 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 WITH 540Wp 40
SPRAYED WITH RICH ZINC-ALUMINIMUM SPRAY AT FACTORY WORK ITSELF SECTION 1-1
PART-12 24.0 SLOT-24x12
5. STRUCTURAL MEMBERS SHALL BE GALVANIZED IN ACCORDANCE WITH IS:4759.
1:5 TOTAL NO OF MODULE MOUNTING STRUCTURES 2X28 423
6. ALL STEEL MEMBERS TO BE ELECTRO GALVANIZED / HOT DIP GALVANIZED
BRACING-BR2 (FRONT) 6 NOS. TO MINIMUM 80 MICRON. TOTAL NO OF MODULE MOUNTING STRUCTURES 2X14 48
7. GALVALUME MEMBERS SHOULD BE COATING OF 150GSM.

12.0
C-LIP 60x30x10x1.6T 8. ALL BOLTS SHALL BE SNUG TIGHTENED AND FULL TIGHTNESS TO BE INSURED SLOT-24x12 TOTAL NO OF SMB 44

51.5
1:10 BY '"TORQUE WRENCH METHOD". 2 NOS.

103.0
9. FABRICATION AND ERECTION SHALL BE CARRIED OUT IN ACCORDANCE TOTAL NO OF LA 8
WITH IS:800 AND IS:802.

40
TOTAL NO OF CONVERTION STATIONS(5MVA) 2
10. ALL MEMBER SIZES AND THICKNESS MENTIONED IN THE DRAWING AND B.O.M ARE

30
BMT (i.e Base Material Thickness) and TH. IS THE THICKNESS ON WHICH STRUCTURE IS
18 DESIGNED AND SHOULD BE USED WHILE ORDERING THE RAW MATERIAL STEEL.
75.0 75.0 50.0 PART-1
11. ALL HARDWARE SHOULD BE KUN80 OR 8. GRADE HDG WITH FLANGE WITH SERRATIONS.
9

ENLARGED DETAIL-A COLUMN POST-1


TYPICAL DETAIL C-LIP 120x65x20x2T
SLOT-18x9 (TYP) 1:10
MODULES FIXING
6777.5
76.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 931.5
SLOT-18x9 75.0 75.0 50.0
11 NOS. A 5

103

103
R3 23.12.2021 D.V.S GHSV A.V D.V.S COLUMN SLOT ORIENTATION CHANGED
552.5 3050.0 3050.0 5

51.5
R2 03.11.2021 D.V.S GHSV A.V D.V.S CHANGED THE PURLIN MODULE
SLOT-24x12 SLOT-24x12 FIXING SLOTS ORIENTATION
2 NOS. 6 NOS. R1 26.10.2021 D.V.S GHSV A.V D.V.S AS PER COMMENTS
PART-4 - PURLIN-1
R0 18.10.2021 D.V.S GHSV A.V D.V.S -----------------------------
HAT: 80x40x25x7x0.9
Rev. Date Designed Drawn Review Approval Description

6350.0 OFFTAKER:

404.5 68.0
SLOT-18x9
10 NOS. 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 1086.0 68.0 107.5
MAHARASHTRA STATE POWER

51.5
5 GENERATION COMPANY LTD.
103

103
DEVELOPER:

50.0 75.0 75.0


SLOT-24x12
6 NOS.
SLOT-24x12
2 NOS. 5950.0
SLOT-24x12
6 NOS. 75.0 75.0 50.0
5 KARNATAKA RESCO
3050.0 3050.0 ROOFTOP SOLAR PVT. LTD.
PART-5 - PURLIN- 2 CLIENT:
HAT: 80x40x25x7x0.9 40
3612.5
TEPSOL
74.5 68
SLOT-24x12
6 NOS. 1086.0 68.0 1086.0 68.0 1086.0 76.0 PROJECTS PVT. LTD.
51.5

5 0.9

80
PMC:
BUREAU VERITAS INDUSTRIAL
103

103

45°

7
SLOT-24x12 5 103 SERVICES (INDIA) PVT. LTD.
50.0 75.0 75.0 3412.5 2 NOS. 25 25
3050.0
VIEW 5-5 EPC CONTRACTOR:
PART-9 - PURLIN- 6 1:2.5 ARDRA POWER
SUIT #202,NISHAN-E-IQBAL
HAT: 80x40x25x7x0.9 ROAD NO.11,BANJARA HILLS
IS CODES: HYDERABAD-500034,TELANGANA
IS 12834-2013 Solar Photovoltaic energy systems
MS Structural Steel / Sheet (Hot Rolled)
Mechanical Properties
Designed: Drawn:
IS 2062
Chemical Properties
MS Structural Steel / Sheet (Cold Rolled)
Mechanical Properties
IS 1079 D.V.S 18.10.2021 GHSV 18.10.2021
Chemical Properties

IS 513 (2008)
Cold Reduced Low Carbon Steel Reviewed: Approved:
Sheet & Strip
Cold Formed Light Gauge Steel
IS 801 (1975)
Structural members
Zinc
IS 209 Chemical Properties
A.V 18.10.2021 D.V.S 18.10.2021
IS 4759 HDG Structural Steel
In-Process
Project: DEVELOPMENT OF 13.5MWp/10MW SOLAR
IS 1852 Cutting PHOTOVOLTAIC PROJECT
IS 7215 Punching AT BHENDALA ,MAHARASHTRA.
As per Specifications Bending
Hot Dip Galvanizing Drawing Title: MODULES MOUNTING STRUCTURE 2Px14 UDL
IS 4759, IS 2629 Defects & Surface Finish PART DETAILS & FABRICATION DRAWINGS
IS 6745 Mass of Zinc Coating
IS 2633 Uniformity in thickness
IS 4759 Coating thickness
Drawing Number: KRRS-MG-BDA-V-DOC-228 Sheet: Revision:
IS 875 Wind Speed loading, dead, live,
snow & wind loads
Date: 18.10.2021 08 of 08 R3
Criteria of Earthquake Resistant
IS 1893 Part -1 Design of Structures
Ordinary Port Land Cement,
Scale: AS SHOWN
IS 12269 53 Grade - Specification
IS 10262 Concrete Mix Proportioning - Guidelines Graphic Scale: 0
Original Size: A1
- -