This document provides installation and operating instructions for the XW270L and XW271L microprocessor-based controllers used in refrigeration units. It includes safety precautions, descriptions of key functions, and detailed explanations of the control parameters, including temperature settings, defrost modes, and alarm configurations. Additionally, it outlines the use of the keyboard and LED indicators for monitoring and controlling the device's operations.

Uploaded by

Oscar Mota
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views4 pages

,qvwdoolqj DQG 2shudwlqj, Qvwuxfwlrqv: 1. General Warning

This document provides installation and operating instructions for the XW270L and XW271L microprocessor-based controllers used in refrigeration units. It includes safety precautions, descriptions of key functions, and detailed explanations of the control parameters, including temperature settings, defrost modes, and alarm configurations. Additionally, it outlines the use of the keyboard and LED indicators for monitoring and controlling the device's operations.

Uploaded by

Oscar Mota
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

 ,QVWDOOLQJ DQG 2SHUDWLQJ ,QVWUXFWLRQV UHO  FRG 

:,1* To see the max. stored temperature; in programming mode it browses the parameter codes or
increases the displayed value. By holding it pressed for 3s the fast freezing cycle is started.
;:/  ;:/ To see the min stored temperature; in programming mode it browses the parameter codes or
decreases the displayed value.

1. GENERAL WARNING
By holding it pressed for 3s the defrost is started.

1.1 PLEASE READ BEFORE USING THIS MANUAL Switch ON and OFF the cold room light.
• This manual is part of the product and should be kept near the instrument for easy and quick reference.
• The instrument shall not be used for purposes different from those described hereunder. It cannot be used By holding it pressed for 3s Energy Saving function is started or stopped.
as a safety device.
• Check the application limits before proceeding.
For XW270L model. Switch ON and OFF the auxiliary output.

1.2 SAFETY PRECAUTIONS For XW271L model. Switch ON and OFF the anti-condensing heater output.
• Check the supply voltage is correct before connecting the instrument.
• Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden Switch ON and OFF the instrument.
temperature changes with high atmospheric humidity to prevent formation of condensation
• Warning: disconnect all electrical connections before any kind of maintenance.
• Fit the probe where it is not accessible by the End User. The instrument must not be opened. KEY COMBINATIONS
• In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see
address) with a detailed description of the fault.


Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each other,
+ To lock and unlock the keyboard.

without crossing or intertwining.


• In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
+ To enter the programming mode.

2. GENERAL DESCRIPTION
Models XW270L and XW271L, 38x185 mm format, are microprocessor based controllers suitable for applications
+ To exit the programming mode.

on medium or low temperature refrigerating units. They are provided with six relay outputs to control compressor,
defrost - which can be either electrical or hot gas - the evaporator fans, the lights, the alarm and an auxiliary
output. In XW271L the auxiliary output is configured as anti-condensing heater.
4.1 USE OF LEDS
They are also provided with three NTC probe inputs, one for temperature control, one to control the defrost end Each LED function is described in the following table.
temperature of the evaporator and the third, optional, for the display. There are two digital inputs (free contact) for
the door switch and configurable by parameter. LED MODE Function
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS- ON The compressor is running
RTU compatible monitoring system and to programme the parameter list with the “Hot Key”.
An optional output for remote display “XW-REP” is available. FLASHING - Programming Phase (flashing with LED )
- Anti-short cycle delay enabled
3. CONTROLLING LOADS ON The fan is running
FLASHING
3.1 THE COMPRESSOR Programming Phase (flashing with LED )
The regulation is performed according to the temperature measured by the thermostat probe with a positive ON The defrost is enabled
differential from the set point: if the temperature increases and reaches set point plus differential the compressor is
started and then turned off when the temperature reaches the set point value again. FLASHING Drip time in progress
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “COn”
ON The Fast Freezing cycle is enabled
and “COF”.
ON - ALARM signal
3.2 FAST FREEZING - In “Pr2” indicates that the parameter is also present in “Pr1”
When defrost is not in progress, it can be activated the keypad by holding the 9
key pressed for about 3
ON (Present only in ’XW271L)
The Anti-condensing heater relay (Aux) is ON.
9
seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle
can be terminated before the end of the set time using the same activation key, for about 3 seconds.
Function of the LEDs placed on the left top side of buttons:
3.3 DEFROST
BUTTON MODE FUNCTION
Three defrost modes are available through the “tdF” parameter: defrost with electrical heater, hot gas or
SET FLASHING The Set point is displayed and it can be modified
thermostatic defrost. The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made
SET FAST FLASHING The Energy Saving is enabled
every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON and the evaporator temperature is bigger than “SdF” parameter). DEFROST ON The Manual Defrost is activated
At the end of defrost the drip time is controlled through the “Fdt” parameter. ENERGY SAVING ON The Energy Saving is enabled
LIGHT ON The Light is ON
AUX ON The Auxiliary output is ON (XW270L)
3.4 CONTROL OF EVAPORATOR FANS HEATER ON The Anti-condensing heater is ON (XW271L)
The fan control mode is selected by means of the “FnC” parameter: ON/OFF ON The instrument is OFF
FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:;
FnC=C-y fans will run continuously, but not during defrost 4.2 HOW TO SEE THE MIN TEMPERATURE
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter.
FnC=O-n fans will switch ON and OFF with the compressor and run during defrost; 1. 8
Press and release the key.
FnC=O-y fans will run continuously also during defrost 2. The “Lo” message will be displayed followed by the minimum temperature recorded.

An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above which
3. 8
By pressing the key or waiting for 5s the normal display will be restored.

the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower than set 4.3 HOW TO SEE THE MAX TEMPERATURE
in “FSt”.
1. 9
Press and release the key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3.5 AUXILIARY OUTPUT 3. 9
By pressing the key or waiting for 5s the normal display will be restored.
The auxiliary output is switch ON and OFF by means of the corresponding button on the keyboard.
The auxiliary output of the XW271L model controls the anti-condensing heater and it is automatically activated if 4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
the room temperature is lower than the “SAA” parameter.
To reset the stored temperature, when max or min temperature is displayed :
1. Press SET key until “rST” label starts blinking.
4. KEYBOARD
N.B. After the installation RESET the temperature stored .

)& HOW TO SEE AND MODIFY THE SET POINT


1. Push and immediately release the SET key: the display will show the Set point value;

9 8
2. The SET LED start blinking;
3. To change the Set value push the or arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.

To display and modify target set point; in programming mode it selects a parameter or confirm an
operation.
By holding it pressed for 3s when max or min temperature is displayed it will be erased.

1592009037 XW270-271L GB r1.0 15.12.2004.doc ;:/  ;:/ 1/4


Downloaded from www.Manualslib.com manuals search engine
 ,QVWDOOLQJ DQG 2SHUDWLQJ ,QVWUXFWLRQV UHO  FRG 

TO START A MANUAL DEFROST P2 = Evaporator probe


P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)
1. Push the DEF key for more than 2 seconds and a manual defrost will start.
DEFROST
tdF Defrost type:
TO ENTER IN PARAMETERS LIST “PR1” rE = electrical heater (Compressor OFF)
To enter the parameter list “Pr1” (user accessible parameters) operate as follows: rT = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on the
evaporator temperature and “dtE” value.
1. Enter the Programming mode by pressing the Set and DOWN key for few seconds in = hot gas (Compressor and defrost relays ON)
( and start blinking). EdF Defrost mode:
in = interval mode. The defrost starts when the time “Idf” is expired.
2. The instrument will show the first parameter present in “Pr1” Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor is
running (even non consecutively) and only if the evaporator temperature is less than the value in "SdF” (set
point for SMARTFROST).
TO ENTER IN PARAMETERS LIST “PR2” SdF Set point for SMARTFROST: (-30÷30 °C/ -22÷86 °F) evaporator temperature which allows the IdF
counting (interval between defrosts) in SMARTFROST mode.
To access parameters in “Pr2”: dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe
1. Enter the “Pr1” level. is present) sets the temperature measured by the evaporator probe which causes the end of defrost.
2. Select “Pr2” parameter and press the “SET” key. IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
9 8
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. cycles.
4. Use or to input the security code in the flashing digit; confirm the figure by pressing “SET”. The MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost
security code is “321“. duration, when P2P = y, defrost end based on temperature, it sets the maximum length for defrost.
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit. dFd Display during defrost:
rt = real temperature;
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys it = temperature reading at the defrost start;
within 30 seconds. Set = set point;
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + 8. When a dEF = “dEF” label;
dEG = “dEG” label;
parameter is present in “Pr1” LED is on. dAd Defrost display time out: (0÷255 min) Sets the maximum time between the end of defrost and the
restarting of the real room temperature display.
HOW TO CHANGE THE PARAMETER VALUE Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the
restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that
9 or 8.
1. Enter the Programming mode.
might have formed due to defrost.
2. Select the required parameter with
dPO First defrost after start-up:
3. Press the “SET” key to display its value ( and LED starts blinking). y = Immediately;
9 8
4. Use or to change its value. n = after the IdF time
dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first defrost will be
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key. delayed for this time.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
FANS
HOW TO LOCK THE KEYBOARD FnC Fan operating mode:
1. 9 8
Keep the and keys pressed together for more than 3 s the and keys. 9 8 C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
2. The “POF” message will be displayed and the keyboard is locked. At this point it is only
O-n = continuous mode, OFF during the defrost;
possible the viewing of the set point or the MAX o Min temperature stored and to switch ON O-y = continuous mode, ON during the defrost;
and OFF the light, the auxiliary output and the instrument. Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator fans start.
FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe,
TO UNLOCK THE KEYBOARD above which the fan is always OFF.
Keep the 9 and 8 keys pressed together for more than 3s. ALARMS
ALC Temperature alarm configuration
ON/OFF FUNCTION rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is ALU High temperature alarm setting:
switched ON. ALC= rE, 0 ÷ 50°C or 90°F
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a ALC= Ab, ALL ÷ 110°C or 230°F
monitoring system is connected, it does not record the instrument data and alarms. when this temperature is reached and after the ALd delay time the HA alarm is enabled.
N.B. During the OFF status the Light and AUX buttons are active.
ALL Low temperature alarm setting:
ALC = rE , 0 ÷ 50 °C or 90°F
TO SEE THE PROBE VALUES
ALC = Ab , - 50°C or -58°F ÷ ALU
1. Enter in “Pr2” level. when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
2. Select “Prd” parameter with or .9 8 AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature
alarm set point and fan regulation set point, always positive.
3. Press the “SET” key to display “Pb1” label alternate with Pb1 value.
4. Use 9 8 and keys to display the other probe values.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the
corresponding alarm signalling.
5. Press “SET” to move to the following parameter. dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the
temperature alarm condition after the instrument power on and the alarm signalling.
PARAMETER LIST EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the detection of the temperature
alarm condition at the end of defrost and the alarm signalling.
REGULATION dot Delay of temperature alarm after closing the door : (0÷255 min) Time delay to signal the temperature
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor Cut alarm condition after closing the door.
IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its alarm
LS Minimum set point limit: (-50,0°C÷SET; -58°F÷SET) Sets the minimum acceptable value for the set signalling: the flashing message “dA” is displayed.
point. tbA Buzzer and alarm relay silencing: by pushing one of the keypad buttons.
US Maximum set point limit: (SET÷110°C; SET÷230°F) Set the maximum acceptable value for set point. n= Only the Buzzer is silenced;
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the y= Buzzer and relay are silenced.
instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light can nPS Pressure switch number: (0 ÷15) Number of activation of the pressure switch, during the “did” interval,
work) before signalling the alarm event (I2F= PAL).
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart. PROBE INPUTS
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used, for
instance, when the room is filled with new products. Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case thermostat probe.
of faulty thermostat probe. With COn=0 compressor is always OFF. OE Evaporator probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of evaporator probe.
faulty thermostat probe. With COF=0 compressor is always active. O3 Auxiliary probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the evaporator
probe.
P2P Evaporator probe presence:
DISPLAY n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time.
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is changed P3P Auxiliary probe presence: n= not present; y= present.
the SET point and the values of the regulation parameters have to be modified HES Temperature increase during the Energy Saving cycle : (-30,0°C ÷ 30,0°C / -22÷86°F) sets the
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. increasing value of the set point during the Energy Saving cycle.
de = 0,1°C
in = 1 °C DIGITAL INPUTS
Lod Local display : select which probe is displayed by the instrument: odc Compressor and fan status when open door:
P1 = Thermostat probe no = normal;
P2 = Evaporator probe Fan = Fan OFF;
P3 = auxiliary probe CPr = Compressor OFF;
1r2 = difference between P1 and P2 (P1-P2) F_C = Compressor and fan OFF.
Red Remote display : select which probe is displayed by the remote display (XW-REP) I1P Door switch input polarity:
P1 = Thermostat probe CL : the digital input is activated by closing the contact;

1592009037 XW270-271L GB r1.0 15.12.2004.doc ;:/  ;:/ 2/4


Downloaded from www.Manualslib.com manuals search engine
 ,QVWDOOLQJ DQG 2SHUDWLQJ ,QVWUXFWLRQV UHO  FRG 
+1
OP : the digital input is activated by opening the contact. 165 -1

I2P Configurable digital input polarity: 150


+0.5
-0

CL : the digital input is activated by closing the contact;


OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:

+0.5
-031
EAL = generic alarm;
bAL = serious alarm mode;
PAL = Pressure switch;
dFr = Start defrost;
AUS = Relay AUX actuation; Ø3 x2

Es = Energy Saving;
onF = remote On/OFF.
did Time interval/delay for digital input alarm:(0÷255 min.) Time interval to calculate the number of the XW270L/XW271L MOUNTING
pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines the
time delay between the detection and the successive signalling of the alarm.
SAA Set Point for anti-condensing heater: (-50,0÷110,0°C; -58÷230°F) defines the room temperature
setpoint to switch on the anti-condensing heater.

OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
Rel Release software: (read only) Software version of the microprocessor. 1
Ptb Parameter table: (read only) it shows the original code of the  parameter map. 2
Prd Probes display: (read only) display the temperature values of the evaporator probe Pb2 and the auxiliary
probe Pb3.
Pr2 Access to the protected parameter list (read only).
4
3
DIGITAL INPUTS
The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the
second is programmable in seven different configurations by the “I2F” parameter.

DOOR SWITCH INPUT


It signals the door status and the corresponding relay output status through the “odc” parameter:
no = normal (any change);
Fan = Fan OFF;
CPr = Compressor OFF; 1
F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and the 3 2
display shows the message “dA”. The alarm stops as soon as the external digital input is disabled again. During R G -L X g a s ck e
this time and then for the delay “dot” after closing the door, the high and low temperature alarms are disabled. (o p tio n al)
4

CONFIGURABLE INPUT - GENERIC ALARM (EAL)


As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm
message. The outputs status don’t change. The alarm stops just after the digital input is de-activated. ELECTRICAL CONNECTIONS
The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm2 for
the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). Heat-resistant
CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s
When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm message. requirements. Separate the probe cables from the power supply cables, from the outputs and the power
The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable
external relay.
N.B. Maximum current allowed for all the loads is 20A.
CONFIGURABLE INPUT - PRESSURE SWITCH (PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of the PROBE CONNECTIONS
“nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the regulation are
stopped. When the digital input is ON the compressor is always OFF. The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is
recommended to place the thermostat probe away from air streams to correctly measure the average room
temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is
formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
CONFIGURABLE INPUT - START DEFROST (DFR)
It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart
only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired. TTL SERIAL LINE
The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line
ModBUS-RTU compatible as the  monitoring system XJ500 (Version 3.0).
CONFIGURABLE INPUT - RELAY AUX ACTUATION (AUS)
The same TTL connector is used to upload and download the parameter list of the “HOT KEY“.
This function allows to turn ON and OFF the auxiliary relay by using the digital input as external switch.
USE OF THE PROGRAMMING “HOT KEY “
CONFIGURABLE INPUT - ENERGY SAVING (ES) The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the “Hot
The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter) sum. Key” and vice-versa.
This function is enabled until the digital input is activated.
DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
CONFIGURABLE INPUT - REMOTE ON/OFF (ONF) 1. Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert the
This function allows to switch ON and OFF the instrument. “Hot Key” and then turn the Wing ON.
2. Automatically the parameter list of the “Hot Key” is downloaded into the Wing memory, the “DoL”
message is blinking. After 10 seconds the instrument will restart working with the new parameters.
DIGITAL INPUTS POLARITY 3. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
The digital inputs polarity depends on “I1P” and “I2P” parameters. “end “ for right programming. The instrument starts regularly with the new programming.
CL : the digital input is activated by closing the contact. “err” for failed programming. In this case turn the unit off and then on if you want to restart the download again or
OP : the digital input is activated by opening the contact remove the “Hot key” to abort the operation.

INSTALLATION AND MOUNTING UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
Instruments XW270L, XW271L shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 1. Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then

9
screws ∅ 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The turn it ON again.
temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive
gases, excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the cooling 2. When the Wing unit is ON, insert the “Hot key” and push key; the "uPL" message appears.
holes. 3. Push “SET” key to start the UPLOAD; the “uPL” message is blinking.
4. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
CUT OUT At the end of the data transfer phase the instrument displays the following messages:
“end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to restart the programming again or remove
the not programmed “Hot key”.

ALARM SIGNALS
Message Cause Outputs
“P1” Thermostat probe failure Alarm output ON; Compressor output according to
parameters “COn” and “COF”
“P2” Evaporator probe failure Alarm output ON; Other outputs unchanged

1592009037 XW270-271L GB r1.0 15.12.2004.doc ;:/  ;:/ 3/4


Downloaded from www.Manualslib.com manuals search engine
 ,QVWDOOLQJ DQG 2SHUDWLQJ ,QVWUXFWLRQV UHO  FRG 

“P3” Auxiliary probe failure Alarm output ON; Other outputs unchanged
“HA” Maximum temperature alarm Alarm output ON; Other outputs unchanged DEFAULT SETTING VALUES
“LA” Minimum temperature alarm Alarm output ON; Other outputs unchanged
“EE” Data or memory failure Alarm output ON; Other outputs unchanged Label Name Range Default Level
“dA” Defrost timeout alarm Alarm output ON; Other outputs unchanged REGULATION °C/°F XW270L XW271L
“dAL” Door switch alarm Alarm output ON; Other outputs unchanged Set Set point LS÷US -5 Pr1 Pr1
“EAL” External alarm Alarm output ON; Other outputs unchanged Hy Differential 0,1÷25,5 °C / 1÷45°F 2 Pr1 Pr1
“BAL” Serious external alarm Alarm output ON; Other outputs OFF LS Minimum set point -50,0°C÷SET / -58°F÷SET -30 Pr2 Pr2
“PAL” Pressure switch alarm Alarm output ON; Other outputs OFF US Maximum set point SET ÷ 110°C / SET ÷ 230°F 20 Pr2 Pr2
The alarm message is displayed until the alarm condition is recovery. OdS Outputs activation delay at start up 0÷255 min. 1 Pr2 Pr2
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. AC Anti-short cycle delay 0÷30 min. 1 Pr1 Pr1
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for about CCt Compressor ON time during fast freezing 0 ÷ 23h 50 min. 0 Pr2 Pr2
3s. COn Compressor ON time with faulty probe 0÷255 min. 15 Pr2 Pr2
COF Compressor OFF time with faulty probe 0÷255 min. 30 Pr2 Pr2
SILENCING BUZZER / ALARM RELAY OUTPUT DISPLAY
If “tbA = y”, once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key. CF Temperature measurement unit °C ÷ °F °C Pr2 Pr2
If “tbA = n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers. rES Resolution (integer/decimal point) in ÷ de de Pr1 Pr1
Lod Local display P1 ÷ 1r2 P1 Pr2 Pr2
“EE” ALARM Red Remote display P1 ÷ 1r2 P1 Pr2 Pr2
The  instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a DEFROST
failure in the memory data occurs. In such cases the alarm output is enabled. tdF Defrost type rE, rT, in rE Pr1 Pr1
EdF Defrost mode In, Sd In Pr2 Pr2
ALARM RECOVERY SdF Set point for SMART DEFROST -30 ÷ +30°C / -22÷+86°F 0 Pr2 Pr2
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal dtE Defrost termination temperature -50,0÷110°C/ -58÷230°F 8 Pr1 Pr1
operation. Check connections before replacing the probe. (1°Evaporator)
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal IdF Interval between defrost cycles 1÷120h 6 Pr1 Pr1
values or when the defrost starts. MdF (Maximum) length for 1° defrost 0÷255 min. 30 Pr1 Pr1
Door switch alarm “dA” stop as soon as the door is closed.
dFd Displaying during defrost rt, it, SEt, dEF, dEG it Pr2 Pr2
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled “PAL” alarm is recovered by
switching OFF the instrument. dAd MAX display delay after defrost 0÷255 min. 30 Pr2 Pr2
Fdt Draining time 0÷60 min. 0 Pr2 Pr2
TECHNICAL DATA dPO First defrost after start up n÷ y n Pr2 Pr2
dAF Defrost delay after fast freezing 0 ÷ 23h 50 min. 2 Pr2 Pr2
Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 76mm FANS
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws. ∅ 3 x 2mm. FnC Fans operating mode C-n, C-y, O-n, O-y O-n Pr2 Pr2
Distance between the holes 165mm Fnd Fans delay after defrost 0÷255 min. 10 Pr2 Pr2
Protection: IP20. FSt Fans stop temperature -50,0÷110°C/ -58÷230°F 2 Pr2 Pr2
Frontal protection: IP65 with frontal gasket mod RG-L. (optional) ALARMS
Connections: Screw terminal block ≤ 2,5 mm2 heat-resistant wiring and 6,3mm Faston ALC Temperature alarms configuration rE÷Ab rE Pr2 Pr2
Power supply: 230Vac or. 110Vac ± 10% ALU MAXIMUM temperature alarm -50,0÷110°C/ -58÷230°F 10 Pr1 Pr1
Power absorption: 7VA max. ALL minimum temperature alarm -50,0÷110°C/ -58÷230°F 10 Pr1 Pr1
Display: 3 digits, red LED, 14,2 mm high. AFH Temperature alarm and fan differential 0,1÷25,5 °C / 1÷45°F 2
Inputs: 3 NTC probes
ALd Temperature alarm delay 0÷255 min. 15 Pr2 Pr2
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A dAO Delay of temperature alarm at start up 0 ÷ 23h 50 min. 1,3 Pr2 Pr2
compressor: relay SPST 20(8) A, 250Vac EdA Alarm delay at the end of defrost 0÷255 min. 30 Pr2 Pr2
light: relay SPST 16(3) A, 250Vac dot Delay of temperature alarm after closing 0÷255 min. 15 Pr2 Pr2
fans: relay SPST 8(3) A, 250Vac the door
defrost: relay SPST 8(3) A, 250Vac dOA Open door alarm delay 0÷255 min. 15 Pr2 Pr2
alarm: SPST relay 8(3) A, 250Vac tBA Alarm relay silencing y÷ n y Pr2 Pr2
auxiliary: SPST relay 16(3) A, 250Vac nPS Pressure switch activation number 0÷15 0 Pr2 Pr2
Other output : alarm buzzer ANALOGUE INPUTS
Serial output : TTL standard Ot Thermostat probe calibration -12,0÷12,0°C / -21÷21°F 0 Pr1 Pr1
Communication protocol: Modbus - RTU OE Evaporator probe calibration -12,0÷12,0°C / -21÷21°F 0 Pr2 Pr2
Data storing: on the non-volatile memory (EEPROM).
O3 Auxiliary probe calibration -12,0÷12,0°C / -21÷21°F 0 Pr2 Pr2
Kind of action: 1B.
P2P Evaporator probe presence n÷ y y Pr2 Pr2
Pollution grade: normal
Software class: A. P3P Auxiliary probe presence n÷ y n Pr2 Pr2
Operating temperature: 0÷60 °C. HES Temperature increase during the Energy -30÷30°C / -22÷86°F 0 Pr2 Pr2
Storage temperature: -25÷60 °C. Saving cycle
Relative humidity: 20÷85% (no condensing) DIGITAL INPUTS
Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F) Odc Open door control no, Fan, CPr, F_C Fan Pr2 Pr2
Resolution: 0,1 °C or 1°C or 1 °F (selectable). I1P Door switch polarity CL÷OP CL Pr2 Pr2
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit I2P Configurable digital input polarity CL÷OP CL Pr2 Pr2
i2F Digital input configuration EAL, bAL, PAL, dFr, EAL Pr2 Pr2
CONNECTIONS AUS, ES, OnF
dId Digital input alarm delay 0÷255 min. 5 Pr2 Pr2
XW270L/XW271L SAA Set point for anti-condensing heater -50,0÷110°C/ -58÷230°F -20.0 --- Pr2
OTHER
(*) In XW271L, AUX is an anticondensing heater Adr Serial address 0÷247 1 Pr1 Pr1
rEL Software release --- 1.0 Pr2 Pr2
;:/;:/ Ptb Map code --- --- Pr2 Pr2
16A 8A 8A 8A 16A 20A Prd Probes display Pb1÷Pb3 --- Pr2 Pr2
250Vac 250Vac 250Vac 250Vac 250Vac 250Vac MA X Pr2 Access parameter list --- --- Pr2 Pr2
20A

                    
Digital inp.

Room
Common

Door switch

Display
N eutral

AUX ALARM
Line

Def.

Dixell S.p.A. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
(*)
Def. Fan Lig ht Comp tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 - (PDLOGL[HOO#GL[HOOFRP  KWWSZZZGL[HOOFRP

1592009037 XW270-271L GB r1.0 15.12.2004.doc ;:/  ;:/ 4/4