Solar inverters
ABB string inverters
PVI-5000/6000-TL-OUTD
5 to 6 kW
Designed for residential and Suitable for low power installations Highlights
small commercial photovoltaic with reduced string size − − Single-phase output
installations, this inverter fills a The wide input voltage range makes − − Transformerless topology
specific niche in the product line the inverter suitable for low power − − Each inverter is set on specific grid
to cater for those installations installations with reduced string size. codes which can be selected in the
producing between 5kW and 20kW. Flat efficiency curves ensure high field
efficiency at all output levels ensuring − − Dual input section with independent
This inverter has a dual input section to consistent and stable performance MPPT, allows optimal energy
process two strings with independent across the entire input voltage and harvesting from two sub-arrays
Maximum Power Point Tracking (MPPT), output power range. oriented in different directions
high speed and precise MPPT algorithm
for real-time power tracking and energy This outdoor inverter has been designed
harvesting, as well as transformerless as a completely sealed unit to withstand
operation for high performance the harshest environmental conditions.
efficiencies of up to 97.0%.
Additional highlights
−− Wide input voltage range
− − Natural convection cooling for
maximum reliability
− − Outdoor enclosure for unrestricted
use under any environmental
conditions
− − RS-485 communication interface (for
connection to laptop or datalogger)
Technical data and types
Type code PVI-5000-TL-OUTD PVI-6000-TL-OUTD
Input side
Absolute maximum DC input voltage (Vmax,abs) 600 V
Start-up DC input voltage (Vstart) 200 V (adj. 120...350 V)
Operating DC input voltage range (Vdcmin...Vdcmax) 0.7 x Vstart...580 V (min 90 V)
Rated DC input voltage (Vdcr) 360 V
Rated DC input power (Pdcr) 5150 W 6200 W
Number of independent MPPT 2
Maximum DC input power for each MPPT (PMPPTmax) 4000 W
DC input voltage range with parallel configuration of MPPT
150...530 V 180...530 V
at Pacr
DC power limitation with parallel configuration of MPPT Linear derating from max to null [530 V≤VMPPT≤580 V]
DC power limitation for each MPPT with independent 4000 W [220 V≤VMPPT≤530 V] 4000 W [220 V≤VMPPT≤530 V]
configuration of MPPT at Pacr, max unbalance example the other channel: Pdcr-4000 W [90 V≤VMPPT≤530 V] the other channel: Pdcr-4000 W [120 V≤VMPPT≤530 V]
Maximum DC input current (Idcmax) / for each MPPT (IMPPTmax) 36.0 A / 18.0 A
Maximum input short circuit current for each MPPT 22.0 A
Number of DC inputs pairs for each MPPT 2
DC connection type PV quick fit connector 3)
Input protection
Reverse polarity protection Yes, from limited current source
Input over voltage protection for each MPPT - varistor Yes
Photovoltaic array isolation control According to local standard
DC switch rating for each MPPT (version with DC switch) 25 A / 600 V
Output side
AC grid connection type Single-phase
Rated AC power (Pacr @cosφ=1 ) 5000 W 4) 6000 W
Rated AC power (P acr @cosφ=±0.9) 5000 W 4) 6000 W
Maximum AC output power (P acmax @cosφ=1) 5000 W 4) 6000 W
Maximum apparent power (S max) 5560 VA 6670 VA
Rated AC grid voltage (Vac,r) 230 V
AC voltage range 180...264 V 1)
Maximum AC output current (Iac,max) 25.0 A 30.0 A
Contributory fault current 32.0 A 40.0 A
Rated output frequency (fr) 50 Hz / 60 Hz
Output frequency range (fmin...fmax) 47...53 Hz / 57…63 Hz 2)
Nominal power factor and adjustable range > 0.995, adj. 0.8 inductive to 0.8 capacitive
Total current harmonic distortion < 3.5%
AC connection type Terminal block, cable gland M32
2 ABB solar inverters | Product flyer for PVI-5000/6000-TL-OUTD
Block diagram of PVI-5000/6000-TL-OUTD
IN1.1(+) IN1.1(+) MPPT 1 Inverter
(DC/DC) Bulk caps (DC/AC)
+ + +
IN1.2(+) IN1.2(+)
IN1 IN1 IN1
Line Grid parallel
filter relay
IN1.1(-) IN1.1(-)
- - -
L
IN1.2(-) IN1.2(-)
IN2.1(+) IN2.1(+) MPPT 2 PE
(DC/DC)
+ + +
IN2.2(+) IN2.2(+)
IN2 IN2 IN2 Residual current
detection
IN2.1(-) IN2.1(-)
- - -
IN2.2(-) IN2.2(-)
RS485
+ T/R
Standard version -S version
- T/R
RTN
DC/DC DC/AC
DSP DSP Remote control
contr. contr.
+R
-R
µP Alarm
N.C
N.O
C
Control circuit
Technical data and types
Type code PVI-5000-TL-OUTD PVI-6000-TL-OUTD
Output protection
Anti-islanding protection According to local standard
Maximum external AC overcurrent protection 32.0 A 40.0 A
Output overvoltage protection - varistor 2 (L - N / L - PE)
Operating performance
Maximum efficiency (ηmax) 97.0%
Weighted efficiency (EURO/CEC) 96.4% / -
Feed in power threshold 10.0 W
Night consumption < 0.4 W
Communication
Wired local monitoring PVI-USB-RS232_485 (opt.)
Remote monitoring VSN300 Wifi Logger Card (opt.), VSN700 Data Logger (opt.)
Wireless local monitoring VSN300 Wifi Logger Card (opt.)
User interface 16 characters x 2 lines LCD display
Environmental
-25...+60°C (-13...+ 140°F)
Ambient temperature range -25...+60°C (-13...+ 140°F)
with derating above 50°C (122°F)
Relative humidity 0...100% condensing
Sound pressure level, typical 50 dBA @ 1 m
Maximum operating altitude without derating 2000 m / 6560 ft
Physical
Environmental protection rating IP65
Cooling Natural
Dimension (H x W x D) 810 mm x 325 mm x 222 mm / 31.9” x 12.8” x 8.7”
Weight < 26.0 kg / 57.3 lbs
Mounting system Wall bracket
Safety
Isolation level Transformerless
Marking CE (50 Hz only), RCM
EN 50178, IEC/EN 62109-1, IEC/EN 62109-2, AS/NZS 3100, EN 61000-6-1,
Safety and EMC standard
EN 61000-6-3, EN 61000-3-11, EN 61000-3-12
CEI 0-21, DIN V VDE V 0126-1-1, G59/3, EN 50438 (not for all national appendices),
Grid standard (check your sales channel for availability)
RD 1699, RD 413, ITC-BT-40, AS 4777, C10/11, IEC 61727, IEC 62116
Available products variants
Standard PVI-5000-TL-OUTD PVI-6000-TL-OUTD
With DC switch PVI-5000-TL-OUTD-S PVI-6000-TL-OUTD-S
1)
The AC voltage range may vary depending on specific country grid standard
2)
The Frequency range may vary depending on specific country grid standard
3)
Please refer to the document “String inverters – Product manual appendix” available at www.abb.com/solarinverters for information on the quick-fit connector brand and
model used in the inverter
4)
4600 W for Australia
Remark. Features not specifically listed in the present data sheet are not included in the product
Product flyer for PVI-5000/6000-TL-OUTD | ABB solar inverters 3
Efficiency curves of PVI-5000-TL-OUTD Efficiency curves of PVI-6000-TL-OUTD
100 100
99 99
98 98
97 97
96 96
Efficiency [%]
Efficiency [%]
95 95
94 94
93 93
250 Vdc 250 Vdc
92 92
360 Vdc 360 Vdc
BCD.00375 EN Rev. F 31.08.2016
91 480 Vdc 91 480 Vdc
90 90
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
% of Rated Output Power % of Rated Output Power
Support and service For more information please contact © Copyright 2016 ABB. All rights reserved.
ABB supports its customers with your local ABB representative or visit: Specifications subject to change without notice.
dedicated, global service organization
in more than 60 countries and strong www.abb.com/solarinverters
regional and national technical partner www.abb.com/solar
networks providing complete range of www.abb.com
life cycle services.