BMG PV Bess SLD V2 18102023
BMG PV Bess SLD V2 18102023
LEGEND:
FOUR POLE CIRCUIT BREAKER
Alu SWA
Alu SWA
Alu SWA
Alu SWA
Alu SWA
Alu SWA
Alu SWA
Alu SWA
Note 4*
Note 4*
PILOT LIGHTS
ATESS Feeder
AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable AC Cable Earth Cable
1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2 LV MAINS MCCB 800A LV Sub MAINS MCCB 1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2 1 x 120mm² AC 1 x 35mm2
EMERGENCY STOP
Kiosk
Kiosk
36kA 3P 800A 36kA 3P
Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m) Alu SWA (14m) Bare Copper (14m)
800A/5A
CL 1 Splitcore C.T.
Notes:
200A 200A 200A 125A 125A 125A 125A 125A
6A 3P Fuse 25kA 400V 25kA 400V 25kA 400V 400 25kA 400V 25kA 400V 25kA 400V 400 25kA 400V 25kA 400V 25kA 400V
M MCCB MCCB MCCB VAC MCCB MCCB MCCB VAC MCCB MCCB MCCB
4 x 25mm² AC H07V-K 4 x 25mm² AC H07V-K
Main DB Room
6A 3P + N 40kA 100A Fuse 100A Fuse
Voltage Reference
Feeder 1 Feeder 2
1000A Isolator Isolator
SPD Type II (AC) MCCB 800A 630A SPD Type II (AC)
LOCAL MAIN 36kA 3P 36kA 3P 36kA 3P
BREAKER
1 x 16mm² H07V-K Janitza
M MCCB 1250A 1 x 16mm² H07V-K
SOLAR PV SUB DB 2
*Note 1
SOLAR PV SUB DB 1
10A 3P+N 25kA Fuse
6A 2P 6kA MCB Voltage Reference
Grid Relay Power Supply
ABB ABB
CM-UFD.M31 C3-AC CM-UFD.M31
CDD C1-AC C4-AC
CDD
6A 3P 6kA MCB 6A 3P 6kA MCB
630A CDD 1 Voltage reference 800A CDD 1 Voltage reference
3P 36kA 3P 36kA
MCCB C2-AC MCCB
UFD reference
UFD reference
Motorised Note 1* 16A 2P 6kA MCB
Feeding Comms Motorised Note 1* 16A 2P 6kA MCB
Feeding Comms
DB DB
1000A/5A 1000A/5A
CL 0.5 CL 0.5
Split core CT Split core CT
PCS630 FRONT PCS630 REAR ISOLATION TX630kVA BYPASS CABINETT 630
CAN B
Neutral Bar
630A CDD 2
CAN A
CAN A
a b
Output
32A 3P + N 40kA 32A 3P + N 40kA
4P 36kA Voltage Reference CONTACTOR
n
c
GRID
CONTACTOR
GEN
CONTACTOR Voltage Reference
Notes:
C B A
RS485
RS485
k1-AC
Motorised B
1250A
Auto Transfer
BATTERY INPUT/OUTPUT X Y Z INVERTER PCS LOAD BYPASS GRID GEN Switch
BREAKER BREAKER BREAKER BREAKER BREAKER BREAKER BREAKER BREAKER
FAULT LEVEL = 36 kA 1600A
36kA 4P
1250A
36kA 3P INDUCTOR
A C
PE 1250A
36kA 3P
1250A
36kA 3P
1250A
36kA 3P
1250A
36kA 3P
1250A
36kA 3P
1250A
36kA 3P
FAULT LEVEL = 36 kA
BESS + PV FACILITY
Primary side
Deep Sea DSE
1250A 3P 335
42kA
MCCB
C6-AC
C5-AC
C2-DC
CDD 2
BATTERY
MCCB DC
1600A 4P
25kA
Generator 1
350kVA G G Generator 2
350kVA
630A
4P 36kA
MCCB
32A 3P + N 40kA
Voltage Reference
Motorised
LOCAL MAIN
RS485
RS485
RS485
RS485
RS485
1x24V 4Ah
C1 - DC H07RN-F 1C x 2 120mm2 1 4 Freedom won Battery output to DC combiner 16mm2 1
V1 First Draft
SPD
SPD
SPD
SPD
SPD
SPD
STATUS: ####
CLIENT:
BMG Head OLce
1
SITE:
BESS + PV Phase 2
DRAWING TITLE:
AC & Comms SLD Tie-in 1
Checked by:
Drawn by:
CR
CR
N