Infinity
ÈEclipse CX 9400 Central Processing Unit
The Infinity CX 9400 with flash EPROM is the Central Processing Unit (CPU) board for the ÈEclipse FEATURES
family of controllers. Through its flexible, modular design, the ÈEclipse system allows you to to meet • High-Powered CPU Board for
Monitoring and Control of
the high point-type and point-density needs of a specific site by mixing various combinations of user-
ÈEclipse High Density I/O
configurable I/O modules in a single compact 4-I/O-slot or 8-I/O-slot rack. Along with the CX 9400 CPU Modules
module and slots for four to eight I/O modules, each ÈEclipse system includes a plug-in power supply
• High-Speed Networking —
module. The CX 9400 board monitors and controls these I/O modules through the ÈEclipse parallel
Ethernet LAN and/or Echelon
backplane interface. An optional NEMA 1-style enclosure is available for wall mounting of either an LON™ Communications
ÈEclipse 4-I/O slot rack or a ÈEclipse zero-I/O slot rack (CPU and power supply only) .
• System Coordinator for Up to 316
Infinet Distributed Controllers
The CX 9400 also acts as the system coordinator for all distributed Infinity Infinet controllers,
• Four Programmable Comm. Ports
providing integrated global control, history logging, local and remote alarming, and a fully menu driven
for Flexible Interconnect
user interface. Each CX 9400 contains communication ports to the Infinet field bus, RS-232/RS-485
• Flash EPROM for Easy On-Line
communications to modems, printers, dumb terminals, and third-party devices, plus optional Ethernet
Software Updates
LAN and/or Echelon LON™ networks.
• Plain English ® Language
Simplifies Programming
The CX 9400 supports expansion for up to two Infinet networks. Each network can contain 127 Infinet
controllers and up to 31 ACX series access controllers or DCX 250 display controllers. • Real-Time Data Logging and
Trending Capabilities
PROGRAMMING
The CX 9400 can be configured to meet the exact requirements of your application, using the powerful Plain • Programmable Battery Backup
English® programming language. Programs are entered into a CX 9400 using a SX 8000 workstation, LSX 280 Lap- Provides Choice of Shutdown
Top Service Tool, or dumb terminal with full screen editor. The program is then stored in, and executed by, the CX Options
9400.
• Optional Auto Dial/Auto Answer
Modem for Remote Communications
Infinity ÈEclipse
Eclipse 9400 Central Processing Unit
SOFTWARECAPABILITIES
The dynamic memory of the CX 9400 can be allocated for any combination of Plain English programs,
scheduling, alarming, reporting and data logging. Our object-oriented language with intuitive keywords
provides easy operation and programming. In addition, Plain English’s pre-defined and customized functions
and powerful math capabilities reduce programming time for repetitive applications.
PROGRAMMABLECOMMUNICATIONSPORTS
The CX 9400 has the power to share information between third-party systems, using its programmable
communications port feature. Each of the four CX 9400 communications ports can be custom-programmed as
either a RS-232 or RS-485 interface, with user-selectable baud rates, data bits, parity, flow control, and
hardware handshaking. Andover Controls has developed an extensive library of third party software drivers,
including tie-ins to chiller control panels, fire alarm systems, emergency generator systems, bar code readers,
elevator controls, and videomatrix switchers.
FLASHMEMORY
The CX 9400’s 4 or 8 mb of flash EPROM allows you to download software revisions over Ethernet or standard
telephone lines using an Infinity SX 8000 workstation. This flash memory feature eliminates the need to
perform EPROM change-outs in the field.
OPTIONAL ETHERNET LAN INTERFACE
The CX 9400 offers optional Ethernet LAN support. With this option, the CX 9400 can communicate with your
other Andover network controllers and SX 8000 workstations over a high-speed 10 Mb Ethernet network (using
either NetBeui, TCP/IP or Novell protocols). Three different Ethernet modules are available, supporting three
different media: 10BASE-2 (thin coax) ,10BASE-T (twisted pair), or 10BASE-FL (fiber optic cable).
OPTIONAL ECHELON LON INTERFACE
The CX 9400’s optional Echelon control module provides an open communication interface to Andover or third-
party Echelon-compatible products. This Echelon port is in addition to the four communications ports
mentioned above. Contact Andover Controls for more details on the Echelon interface module.
OPTIONALAUTO-BAUDMODEMMODULE
The optional Andover Controls ÈEclipse modem allows the CX 9400 to communicate and exchange data over
standard voice grade telephone lines with speeds up to 14.4K baud. The modem has built-in data compression
and error-correction protocols, as well as auto-dial/auto-answer capabilities.
THE CX 9410
For control applications where extensive data logging and programming capabilities, higher CPU performance,
greater processing speeds, and more RAM memory is needed, the CX 9410 is the perfect upgrade. The CX
9410 offers 8 Mb of RAM, 8 Mb of Flash EPROM, and a floating point math co-processor.
14.17"
359.92mm
ÈEclipse CX9400 Dimensional Diagram
Infinity ÈEclipse
Eclipse 9400 Central Processing Unit
SPECIFICATIONS
ELECTRICAL
Power Consumption: 16 watts max., provided through ÈEclipse backplane. System’s total power
consumption not to exceed 100 watts.
Overload Protection: 2 amp slow-blow pico fuse
Real Time Clock: Battery-backed by UPS
MECHANICAL
Operating Environment: 32 to 120°F, (0 to 49°C), 10 to 95% (non-condensing)
Size: 1.58" W x 14.17" H x 5.67" D (40.1 W x 359.9 H x 144.0 D)mm
Weight: 1.3 lb. (.590kg)
BATTERY
Battery Backup: Two 12V 6.5AH sealed rechargeable batteries on ÈEclipse power supply
module programmable for 90 minutes full UPS/72 hours memory and real-
time clock. Expandable by use of greater amp hour batteries. Charge time
will vary. Contact Andover Controls for details.
COMMUNICATIONS
Serial Comm. Interface: Four programmable RS-232/485 ports, software configurable as user port,
printer, modem, third party system, or TankNet. Infinet can be configured on
Ports 1 and 2.
Optional Ethernet LAN
Interface Module: 10 BASE T, 10 BASE 2, 10 BASE FL
Optional Echelon LON
Interface Module: Free Topology (FT) Twisted Pair
Serial Comm. Speed: 300 to 19.2K baud selectable for Infinet, user terminal, and 14.4K baud for
modem
Comm. Error Checking: International Standard CRC 16
Bus Length and Media
Infinet: 4,000 ft. (1,220m) standard for Infinet using twisted, shielded pair approved,
low capacitance cable. InfiLink module allows extension to longer
distances.
S P E C I F I C A T I O N S (Cont'd)
Optional Ethernet: 606 ft. (185m) standard for 30 nodes using 10BASE-2 thin coaxial cable. EnergyLink
modules allow longer distances.
327 ft. (100m) standard for 2 nodes using 10BASE-T unshielded twisted pair cable.
EnergyLink modules allow longer distances.
6,562 ft. (2,000m) standard for 2 nodes using 10BASE-FL fiber optic cable.
EnergyLink modules allow longer distances.
Optional Echelon LON: 500m to 2700m depending on bus topology.
CONNECTIONS
Power: Powered through ÈEclipse backplane.
EnergyNet: Female BNC coax connector for Ethernet 10BASE-2
RJ-45 connector for Ethernet 10BASE-T
ST-style connector for Ethernet 10BASE-FL
Echelon: Three-position removable terminal block
Infinet, TankNet: Twelve-positon removable terminal block
User Terminal, Printer: RJ-45
Modem: RJ-11 connector
Service Port: RJ-11 connector
LED DISPLAYS
Status LEDs: 4 (POWER, CPU, SCAN, ERROR)
Comm. Activity LEDs: 12 (TD, RD, ONLINE on 4 comm ports)
Modem Activity LEDs: 2 (DCD, DTR)
Network Activity LEDs: 5 (TD, RD, PDL, COL, LINK)
MEMORY
DRAM Flash EPROM Serial EEPROM
CX 9400: 4 Mb 4 Mb 4K bit
CX 9410: 8Mb 8Mb 4K bit
S P E C I F I C A T I O N S (Cont'd)
MODELS
CX 9400 4 Mb RAM, 127 Infinet Nodes
CX 9410 8 Mb RAM, 127 Infinet Nodes, Math Coprocessor
CX 9410 8 Mb RAM, 254 Infinet Nodes, Math Coprocessor
AGENCY LISTINGS UL/CUL 916, 1092, FCC, CE
OPTIONS
• Ethernet Module, 10BASE-2 (Coax)
• Ethernet Module, 10BASE-T (Twisted Pair)
• Ethernet Module, 10BASE-FL (Fiber Optic)
• Echelon LON Module, Free Topology (FT) (Twisted
Pair)
• XDriver Support (up to 3 commports)
Andover Controls Corporation
• 14,4K Bps Telephone Modem (UPS Supported)
World Headquarters
• NetBeui, TCP/IP, Novell Support 300 Brickstone Square
Andover, Massachusetts 01810 USA
• Command Line Support Tel: 978 470 0555
Fax: 978 470 0946
• NEMA 1-Style Enclosure for 4-Slot or Zero-Slot Rack http://www.andovercontrols.com
Andover Controls Ltd.
Smisby Road
Ashby-de-la-Zouch
Leicestershire LE65 2UG England
Tel: 01530 417733
Fax: 01530 414225
Andover Controls GmbH
Am Seerhein 8
D-78467 Konstanz, Germany
Tel: 07531 99370
Fax: 07534 993710
Andover Controls Asia
707 Chinachem Golden Plaza
77 Mody Road
Kowloon, Hong Kong
Tel: 2739 5497
Fax: 2739 7350
Copyright 1997, Andover Controls
Corporation. Trademarks remain the
property of their respective owners.
Data subject to change without notice.
Consult ÈEclipse System Hardare
Installation Guide for exact installation
instructions and specifications.
#DS-9400-C