MM 248 DN 96 1 Fiberglass 1

The document outlines a preliminary drawing for a 2-inch duplex wastewater fiberglass pump station, emphasizing that it is not for construction and that various specifications may change. It includes disclaimers regarding compliance with standards, the need for contractor verification of dimensions, and proprietary rights of Jensen Precast. Additionally, it provides a bill of materials and specifications for the pump station components, including pumps and control panels.

Uploaded by

chris p
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views2 pages

MM 248 DN 96 1 Fiberglass 1

The document outlines a preliminary drawing for a 2-inch duplex wastewater fiberglass pump station, emphasizing that it is not for construction and that various specifications may change. It includes disclaimers regarding compliance with standards, the need for contractor verification of dimensions, and proprietary rights of Jensen Precast. Additionally, it provides a bill of materials and specifications for the pump station components, including pumps and control panels.

Uploaded by

chris p
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PRELIMINARY DRAWING

NOT FOR CONSTRUCTION


2IN DUPLEX WASTEWATER FIBERGLASS PUMP STATION
THICKNESSES, NUMBER OF PIECES, AND
MM-248-DN-96-1 Fiberglass
TYPES OF PIECES COULD CHANGE

MM-248-DN-96-1 Fiberglass.idw
PLAN VIEW
NOT TO SCALE

TOP LEFT ISOMETRIC VIEW w/ SECTION


NOT TO SCALE

PROFILE VIEW
NOT TO SCALE

DESCRIPTION: REV:
DISCLAIMERS, INCLUDING BUT NOT LIMITED TO: ©2018 Jensen Precast - All rights reserved.
1.) All precast concrete materials and manufacturing methods shall conform to all current and applicable ASTM, AASHTO and NPCA standards and specifications.
All materials appearing as Jensen Precast documents and the like are
2.)
3.)
All precast concrete components to be manufactured in an NPCA certified plant.
All elevations have been provided by others, and have not been verified by Jensen Precast. Contractor to verify all dimensions and elevations prior to installation.
proprietary work product and are protected under 2IN DUPLEX WASTEWATER FIBERGLASS PUMP STATION
U.S. copyright and other laws.
4.) These layout drawings are intended to show overall system design only. All concrete component thicknesses, dimensions, lengths and joint orientations may TITLE PAGE
Unless in conjunction with business conducted with Jensen Precast, any SHEET:
vary across Jensen Precast's manufacturing facilities and are subject to change pending final design. Contractor to confirm all information prior to installation. 521 DUNN CIRCLE, SPARKS, NV 89431 use of Jensen Precast work product without express, written consent is PART NUMBER: DRAWN BY:
5.) System design criteria has been provided to Jensen Precast. Others are responsible for verification that system meets the intended application.
www.jensenwaterresources.com
MM-248-DN-96-1 Fiberglass C. Purdie
6.) Foundation, subgrade and backfill to be designed by others. prohibited, and recipient is prohibited from distributing any and all work
product to non-approved third parties under penalty of civil action. CREATED: MODIFIED:
1 OF 2
7.) For complete design and product information, or custom design conditions, please conctact Jensen Precast. (855) 468-5600 9/15/2022
BILL OF MATERIALS
OPTIONAL Ø4" PVC VENT ITEM QTY DESCRIPTION
PRELIMINARY DRAWING PIPE UPON REQUEST 1 1 48" DIA. FIBERGLASS WET WELL
NOT FOR CONSTRUCTION 2 1 48" DIA. FIBERGLASS TOP SECTION W/ HINGED ACCESS COVER
n4'-0" WET WELL I.D.
OPTIONAL ANTI-FLOTATION COLLAR 3 2 PUMP BASE ELBOW FOR SLIDE RAIL SYSTEM
THICKNESSES, NUMBER OF PIECES, AND HINGED SINGLE DOOR
TYPES OF PIECES COULD CHANGE 4 2 STAINLESS STEEL UPPER GUIDE RAIL BRACKET
ACCESS HATCH
RATED FOR 300PSF 5 2 SUBMERSIBLE PUMP 2IN BARNES
6 40 FT PIPE 1IN SCH40 GUIDE RAIL 304SS
13
NOTES: 7 2 ADAPTER 2IN MA THRD X SLIP SCH 80 PVC
A A 8 1 FITTING PVC TEE 2IN SCH 80 SLIP
PUMP STATION IS SOLD AS A PARTIALLY 8 9 2 90 DEG ELBOW 2IN SCH 80 PVC SLIP
PRE-ASSEMBLED UNIT WITH PUMPS AND
10 2 BALL VALVE 2IN SCH 80 PVC SLIP TRUE UNION
CONTROL PANEL SHIPPED LOOSE. SOME FORCE MAIN DISCHARGE
SITE ASSEMBLY REQUIRED. CONNECTION 11 40 FT PIPE PVC SCH 80 2IN DIA
*DESIGN BY OTHERS

MM-248-DN-96-1 Fiberglass.idw
INLET PIPE CONNECTION 12 2 Y CHECK VALVE 2IN SCH80 PVC SOCKET CONNECT FOR HARSH CHEMICALS
*INLET PIPING BY OTHERS*
STANDARD LOAD RATING IS 300PSF 13 1 CONNECTOR PIPE SEAL BOOT 2IN 3IN 4IN TEAR OUT POLY I
UNLESS OTHERWISE INDICATED. 9 14 1 FLOAT BRACKET 3-HOOK FORMED SS
15 10 FT CHAIN 3/16IN 316SS
INLET PIPE PENETRATIONS AND SEALING
BY OTHERS. 16 1 DUPLEX CONTROL PANEL
17 4 FLOAT SWITCH 30FT
PLAN VIEW
NOT TO SCALE
PROJECT SPECIFIC INFORMATION
16 RIM ELEV. (Ft.)
INLET ELEV. (Ft.)
FORCE MAIN DISCHARGE ELEV. (Ft.)
CONTROL PANEL
INSTALLATION, MOUNTING HINGED SINGLE DOOR
DESIGN & HARDWARE ACCESS HATCH
BY OTHERS SYSTEM CHARACTERISTICS
RATED FOR 300PSF
APPLICATION SEWAGE [ ] STORM WATER [ ]
DUTY POINT UP TO 50 GPM @ 15' TDH

CONDUIT DESIGNED, PROVIDED PUMP MAKE & MODEL BARNES 2SEV


& INSTALLED BY OTHERS REQUIRED POWER SUPPLY 240V SINGLE PHASE
2
PUMP TYPE SUBMERSIBLE SOLIDS HANDLING PUMP
14 4
PUMP RATED HP & CURRENT 0.5 HP / 6.3A
RIM EL:
LOAD RATING PEDESTRIAN

Abbreviated Specifications:
Basis of Design: Provide AK Industries pre-assembled fiberglass wastewater pump station, including specified controls, pumps, valves, internal
piping, and fiberglass well to be furnished by Jensen Water Resources, (855) 468-5600, [email protected],
2'-6" www.Jensenwaterresources.com.
6
Fiberglass
• AK Industries fiberglass chop hoopwound process w/ commercial grade resin and commercial grade glass fiber reinforcing material
manufactured in accordance with ASTM D3753-99. The bottom of the basin shall be reinforced with a fiberglass plate extending beyond
the basin diameter for anchoring to a concrete pad. Pump mounting studs will be attached to this plate and installed in pump basin.
Pumps
10 • Furnish and install 2 (qty) Barnes 2SEV submersible pumps with a self-engaging lift out assembly, designed to handle pumping of
unscreened wastewater.
• The volute, seal plates and motor housing shall be constructed of high quality ASTM A-48 class 30 cast iron. The pump impeller shall be of
12 the non-clog/vortex design capable of passing 2" spherical solids. The unit shall utilize a tandem mechanical shaft seal arrangement and
shall operate in an oil atmosphere. Single phase motors shall be of the capacitor start, capacitor run design.
8'-0" 17 • The motor shaft shall be of 416 stainless steel. Protection against excessive temperature shall be provided by heat sensor thermostat
attached to the stator windings and connected in series with the contractor coil in the control panel. The single phase models shall provide
15
protection against excessive temperature through the use of an in-line heat/current sensor. The lower bearing shall be of the single ball
type to accept radial and thrust loads, and the upper bearing of the single ball design, for radial loads. Bearings shall operate in an oil bath
11 atmosphere.
HIGH LEVEL ALARM: 36" • The pump shall utilize a lift out system. The pump shall be equipped with 30 ft. of CSA/UL Approved 12/4 Type SOW power cord and
connected to the motor via quick disconnect pin terminals.
LAG PUMP ON EL: 30" 5 Control Panel
7
• Provide Alderon single phase duplex Check It series pump control panel. Check It panel is float switch operated and includes: NEMA 4X
LEAD PUMP ON EL: 24" enclosure, lockable hasp, beacon and alarm buzzer, test & silence switches, HOA switches, pump run indicators and float switch indicators.
• Control Sequence of Operation: Cycle each pump on and off automatically to maintain well wastewater level. Automatic control operates
1
both pumps in parallel if well level rises above starting point of low-level pump, until shutoff level is reached. Automatic alternator, with
manual disconnect switch, changes sequence of lead-lag sewage pumps at completion of each pumping cycle.
PUMP(S) OFF EL: 12" • Minimum 4 qty mechanical float control switches shall be provided with control panel.
3 Piping & Hardware
• All piping, fittings, and valves shall be Schedule 80 and conforming to ASTM Standard D 1784.
• All hardware provided and used within wet well shall be 316SS quality.
Commissioning
FLOOR EL: 0" • The pumps and station integration shall be tested and confirmed at start-up by a qualified Jensen Pump Stations representative. On-site
and remote commissioning options are available.
Disclaimer
• All materials appearing as Jensen Precast documents and the like are proprietary work product and are protected under U.S. copyright
and other laws.
SECTION A-A FOUNDATION, SUBGRADE AND
• Unless in conjunction with business conducted with Jensen Precast, any use of Jensen Precast work product without express, written
NOT TO SCALE BACKFILL DESIGNED BY OTHERS
consent is prohibited, and recipient is prohibited from distributing any and all work product to non-approved third parties under penalty of
civil action.
©2018 Jensen Precast - All rights reserved

DESCRIPTION: REV:
DISCLAIMERS, INCLUDING BUT NOT LIMITED TO: ©2018 Jensen Precast - All rights reserved.
1.) All precast concrete materials and manufacturing methods shall conform to all current and applicable ASTM, AASHTO and NPCA standards and specifications.
All materials appearing as Jensen Precast documents and the like are
2.)
3.)
All precast concrete components to be manufactured in an NPCA certified plant.
All elevations have been provided by others, and have not been verified by Jensen Precast. Contractor to verify all dimensions and elevations prior to installation.
proprietary work product and are protected under 2IN DUPLEX WASTEWATER FIBERGLASS PUMP STATION
U.S. copyright and other laws.
4.) These layout drawings are intended to show overall system design only. All concrete component thicknesses, dimensions, lengths and joint orientations may MECHANICAL DETAIL
Unless in conjunction with business conducted with Jensen Precast, any SHEET:
vary across Jensen Precast's manufacturing facilities and are subject to change pending final design. Contractor to confirm all information prior to installation. 521 DUNN CIRCLE, SPARKS, NV 89431 use of Jensen Precast work product without express, written consent is PART NUMBER: DRAWN BY:
5.) System design criteria has been provided to Jensen Precast. Others are responsible for verification that system meets the intended application.
www.jensenwaterresources.com
MM-248-DN-96-1 Fiberglass C. Purdie
6.) Foundation, subgrade and backfill to be designed by others. prohibited, and recipient is prohibited from distributing any and all work
product to non-approved third parties under penalty of civil action. CREATED: MODIFIED:
2 OF 2
7.) For complete design and product information, or custom design conditions, please conctact Jensen Precast. (855) 468-5600 9/15/2022