063 Funcd

The document describes the Analog Input List function code 63 for the BRC-100 and HAC controllers, which acquires data from eight analog points through a Controlway/module bus or peer-to-peer network. It details the configurable parameters for data transfer, including sample period and source module addresses, as well as the output data structure. Additionally, it specifies the requirements for point quality indicators and the configuration needed for the source node/module.

Uploaded by

fxv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views4 pages

063 Funcd

The document describes the Analog Input List function code 63 for the BRC-100 and HAC controllers, which acquires data from eight analog points through a Controlway/module bus or peer-to-peer network. It details the configurable parameters for data transfer, including sample period and source module addresses, as well as the output data structure. Additionally, it specifies the requirements for point quality indicators and the configuration needed for the source node/module.

Uploaded by

fxv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Analog Input List

(Periodic Sample) Function Code 63


A IL/B In the BRC-100 controller, the analog input list (periodic sam-
(6 3)
N
ple) function code acquires the data values of eight analog
points in a single Controlway/module bus message. The
N+1 source module and destination module must be located in the
same process control unit. Input data consists of analog sig-
N+2
nals and qualities. Data transfer between the source module
N+3 and destination module is via the module bus. The address
and block number of the source module and the update time
N+4 are configurable parameters.
N+5 The HAC controller uses function code 63 to acquire the data
values of eight analog points in a single peer-to-peer network
N+6
message. Input data consists of analog signals and qualities.
N+7 Data transfer between the source module and destination
module is via the peer-to-peer network. The address and block
number of the source node and the update time are config-
urable parameters.

Output data consists of real numbers corresponding to the


analog data received, and point quality indicators. To insure
that the signal is successfully transferred, the analog signal
generates a point quality flag. To test the quality of the signal,
include a function code 31 in the configuration. The quality of
the point cannot be used as an input to any other type of
block. The analog output value can be used as an input to any
analog processing block. Refer to Appendix G for a definition of
point quality.

NOTE: A block defined as an analog input reads a value for any existing ana-
log output from a function block configured in the source node/module. No
additional configuration in the source node/module is required.

Outputs

Blk Type Description


N R <S3>
N+1 R <S4>
N+2 R <S5>
N+3 R <S6>
N+4 R <S7>

WBPEEUI210504C0 63 - 1
Outputs (continued)

Blk Type Description


N+5 R <S8>
N+6 R <S9>
N+7 R <S10>

Specifications

Spec Tune Default Type Range Description


S1 N 1.0 R Full Sample period (in seconds)
S2 N 0 I Note 1 Source node/module address
S3 N Note 2 I Note 3 Source block address (N)
S4 N Note 2 I Note 3 Source block address (N+1)
S5 N Note 2 I Note 3 Source block address (N+2)
S6 N Note 2 I Note 3 Source block address (N+3)
S7 N Note 2 I Note 3 Source block address (N+4)
S8 N Note 2 I Note 3 Source block address (N+5)
S9 N Note 2 I Note 3 Source block address (N+6)
S10 N Note 2 I Note 3 Source block address (N+7)
NOTES:
1. Range values are: 0-31 for the BRC-100, IMMFP11/12
1-250 for the HAC
2. Default values are: 9,999 for the BRC-100, IMMFP11/12
2 for the HAC
3. Maximum values are: 9,998 for the BRC-100, IMMFP11/12
31,998 for the HAC

Explanation
Specifications
S1 – MBUPD (Sample period) Defines the update rate for the Controlway/
module bus or peer-to-peer network message inputs. Sample
period is specified in seconds. Specification S1 is tunable. The
system allows tuning the value shown for the sample period,
however, the original sample period will be retained. To change
it the module must be placed in configure mode.
S2 – SMAD (Source node/module address) In the BRC-100 controller, the
address of the node/module containing the eight values
desired. The address of the source module must be between
zero and 31 inclusive.

63 - 2 WBPEEUI210504C0
In the HAC controller, S2 is the Cnet address of the HAC con-
troller node that this function code is sampling data from via
the peer-to-peer network. This node address must be between
1-250.
S3 Block address for output block N.
S4 Block address for output block N+1.
S5 Block address for output block N+2.
S6 Block address for output block N+3.
S7 Block address for output block N+4.
S8 Block address for output block N+5.
S9 Block address for output block N+6.
S10 Block address for output block N+7.

WBPEEUI210504C0 63 - 3
WBPEEUI210504C0