Multilin Agile Feeder Management Series GEA35499

Multilin Agile is an advanced feeder management relay designed for utilities and industrial applications, offering versatile protection, control, and monitoring capabilities. It features a graphical color display, extensive data logging, and advanced communication options, making it suitable for renewable integration and enhancing service reliability. The device supports various protocols, has a compact design for easy retrofitting, and includes advanced cybersecurity measures.

Uploaded by

Mehdi Ounnar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
155 views11 pages

Multilin Agile Feeder Management Series GEA35499

Multilin Agile is an advanced feeder management relay designed for utilities and industrial applications, offering versatile protection, control, and monitoring capabilities. It features a graphical color display, extensive data logging, and advanced communication options, making it suitable for renewable integration and enhancing service reliability. The device supports various protocols, has a compact design for easy retrofitting, and includes advanced cybersecurity measures.

Uploaded by

Mehdi Ounnar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

GRID SOLUTIONS

MULTILIN AGILE
P14N, P14D, P94V
Feeder Management Series Advanced Protection
& Control
Multilin Agile offers versatile protection and control, making it suitable for utilities, industrial
• Fast protection execution, scan rate
plants, onshore and offshore renewable collectors, and more. This advanced feeder relay
8 times / cycle
supports text or integrated graphical color display option allowing direct device interaction.
• Advanced protection including rate of
The graphical color display option presents custom-drawn Single Line Diagrams (SLD) that
change, autoreclose, synchrocheck, high
enables bay monitoring and control.
impedance fault, load encroachment,
Applied as primary or backup feeder protection and equipped with advanced communication transient ground, and fault location
options along with extensive monitoring capabilities, it delivers advanced functionalities • Renewable integration features
including high-performance protection, flexible configuration, and comprehensive power (27Q, 27T)
quality monitoring.
This powerful device also provides extensive data-logging capabilities, oscillography, and Advanced Monitoring
event capture, empowering users to make informed power network decisions swiftly and
effectively, thereby enhancing service reliability and availability.
& Metering
• Harmonics and THD up to the 21st order
Key Benefits • Extensive recording – 2048 events, 25
• Smaller footprint for easy retrofitting of aging infrastructure fault records, up to 128 samples/cycle
oscillography
• Intuitive graphical display for effective monitoring, communications & troubleshooting
• Built-in supervision for equipment health
• Advanced functions addressing the challenges of renewable integration monitoring
• Advanced Cybersecurity to prevent unauthorized access and cyber attacks
• High impedance (HiZ) fault detection to protect people, property, livestock Advanced
• Draw-out design for simplified testing, commissioning & maintenance Communications
• Cost savings on engineering time & wiring due to traditional hardwired control • Supports IEC 61850 Ed. 2, IEC 62439
scheme replacement (PRP/ HSR), Modbus RTU/TCP, IEC
60870- 5-103, DNP 3.0 serial/ethernet
Applications protocols

• Applicable to distribution and industrial feeders • IEEE 1588 (PTP), IRIG-B and SNTP
time synchronization
• Distribution feeder protection for detection of downed conductors, faults on
• Ethernet and serial protocols capable
compensated networks and load encroachment on heavily loaded lines to operating concurrently
• Renewable integration requiring advanced protection, harmonic monitoring and
accurate recording
Ease of Use
• Fast load-shedding schemes using advanced frequency functions
• Compact and withdrawable design
• High reliability in coastal, industrial and polluted environments thanks to harsh with 4“ and 6” case size options
environmental coating of PCBs (printed circuit boards) as standard • Configurable single line diagram for
bay monitoring & control (30TE)
• Push buttons and direct function keys
for connected switchgear (30TE)
• Select-before-operate, breaker health
checks and interlocking capabilities
• Single Setting file for relay
configuration
Multilin Agile

Intuitive User Interface Environmental Responsibility


The 20TE (4”) front HMI hosts a multi-line text display which allows The relays are manufactured in a lead-free soldering process using
direct device interaction. Smart dependencies within the menu ensure lead-free components. Power dissipation is very low as it minimizes
that settings for unused elements are hidden. Four tricolor LED lamps the burden on station batteries Even the product weight (including
are available, freely configurable, in addition to four fixed-function packaging) is optimized to lessen the transit carbon footprint. Such
LEDs which provide a cost-effective solution for annunciation. actions boost the eco-responsibility demonstrated in the Product
Environment Profile (PEP). The product does not require any
Four tri-color resident battery.
Programmable
LEDs The PEP shows claims for raw material, energy and water depletion,
Fixed-function global warming potential, ozone depletion, photochemical ozone
LEDs Slot-in user creation, air acidification, and hazardous waste production.
labeling

LCD screen Quality Built-in


Quality Built-In methodology is applied throughout the development
Hotkeys
and manufacturing processes. The product is designed with an
IEC62443-4-1:2018 certified secure development lifecycle process.
Data reading Menu
& clear key Parts stress analysis in R&D, rigorous component supplier selection
navigation and a shipping carton compliant with ISTA protection requirements
are examples of the best practice to maximize long-life reliability. All
USB(B) port
circuit boards have harsh environmental coating to resist moisture,
salt, corrosive atmosphere and industrial ambient pollution as
Front panel interface 20TE (4”) standard. Circuit board production uses in-circuit tests, boundary
scanning, built-in self-test, automated optical inspection, and X-ray
scanning to achieve 100% test coverage.
The 30TE (6”) version front HMI hosts a fully graphical color screen
that supports open, close, local/remote and direct function key Manufacturing of the product is at an ISMS 27001 certified plant
access facilitating the control of connected switchgear. Sixteen
tricolor LED lamps are available, and freely configurable, in addition Retrofitting
to four fixed-function LEDs.
In addition to new-build, Multilin Agile can be used to refurbish
Programmable LEDs legacy protection schemes. Having lower depth than most 4U
relays or electromechanical disk relays in the installed base makes
retrofitting within the existing footprint and AC/DC schematic an
Fixed-function
LEDs easy task.

Multilin Agile with Graphical HMI Offers:


LCD screen • Space-saving 4U height (177 mm) and 20TE (4”) / 30TE (6”)
width case size
Programmable • Terminals with IP20 protection, safer within the panel
function keys Tab pushbuttons
with LEDs • A front USB port and rear RS485 and RJ45 ports
Read key
• Power-up diagnostics and continuous self-monitoring
Bay control and USB
Local/Remote • Freely programmable opto-isolated binary I/O relays
engineering
port • Watchdog health contact

Menu navigation Reset key • Field upgradeable via firmware upgrade to change relay
& data entry model avoiding costly hardware change

Front panel interface 30TE (6”) - ANSI version

Both 20TE & 30TE version support multiple languages with easy
switching between English and an additional language on the local
display without uploading new firmware. A USB front port offers
ready access by field personnel laptops.

2 GEGridSolutions.com
Multilin Agile

Feeder Protection Distributed Generation Protection


Phase and Ground Fault Overcurrent Undervoltage Reactive Power (27Q)
Six independent stages are available for each phase overcurrent More and more distributed energy resources (DER) are fitted in the
element. Additional to the definite time and predefined IDMT curve MV grid. National grid codes and regulations require these units
selection, programmable curves for customized operation and must support the mains voltage of a network failure. If a voltage
resetting are available. drops and an inductive, reactive power flows in the direction
towards the generating unit, the affected one will be switched off.
Standard ground fault elements are available, with four independent
The restoration function reconnects when grid is healthy.
stages. The sensitive ground fault (SEF) order option allows application
on systems whose ground fault currents are constrained.
Timed Undervoltage Protection (27T)
In certain scenarios, during a voltage drop, the power plants are
IEC/UK curves IEEE/US curves
sometimes required to continue supporting the grid and not to
be disconnected. The Multilin Agile relay provides one Timed
Phase Undervoltage (UV) protection element that can be used for
protection against transient voltage drops and low voltage ride
through applications.

Voltage Controlled and Voltage Restrained Overcurrent


Voltage-dependent protection boosts sensitivity, and reduces
tripping times for faults on weaker systems, such as those with a
high prevalence of distributed generation. The timing characteristics
can be set as either definitive time or IDMT inverse.

Power
Underpower and overpower elements are available that can
be configured to operate as forward or reverse directional and
active or reactive. This element can be used for reverse power
IEC and ANSI/IEEE inverse-time curve profiles and low forward power applications for synchronous machines or
interconnections involving co-generation.

Special Applications Under / Over voltage


Load encroachment (blinder), cold load pick-up, broken conductor Under/over voltage protection may be configured to operate
protection, wattmetric ground fault, fault location, auto reclose, from phase-phase or phase-neutral quantities. Four independent
switch on to fault, rate of change of frequency elements and check stages can be configured for definite time, inverse time or user
synchronizing are built-in depending on the selected model number. defined characteristics.

High Impedance & Transient Ground Fault Check Synchronizing


Detection (HIF & TGFD) The check synchronizing feature ensures that the CB contacts
touch at the instant of synchronism, minimizing the stress on plant
Innovative high impedance ground fault algorithms improve the
assets when paralleling.
detection of downed conductors which have fallen on surfaces
with high resistivity (e.g., sand, dry scrubland, trees). This helps the
utility to save human lives, protect nearby animals and lessen the Transformer Protection
risk of vegetation fires caused by prolonged arcing. Current protection with second harmonic blocking, thermal
Transient ground fault detection benefits from an advanced and overload, negative sequence overcurrent and an instantaneous
innovative algorithm to detect the direction of single-phase faults in restricted ground fault element (REF) with high or low impedance
compensated power systems. are supported. The Volts per Hertz protection prevents damage to
generators and transformers due to overexcitation.

Load Shedding
Nine stages each of frequency protection are available (except
P14N). Each may measure in over-, under-, rate of change, and
frequency supervised rate of change modes. Fast underfrequency
element is supported for performing fast load-shedding. The wide
range of setting options permits application of any frequency-based
load shedding or islanding scheme.

GEGridSolutions.com 3
Multilin Agile

Advanced Logic and Control Capabilities


Multilin Agile incorporates advanced automation capabilities that
reduce the need for additional programmable controllers or discrete
control relays by including programmable logic, communication,
and HV bay / MV cell monitoring, there by reducing equipment and
engineering cost. Advanced automation also enables seamless
integration into other protection or process systems (SCADA or DCS).

FlexElements™
FlexElement™ is a universal comparator that can be programmed
to respond either to a signal level or to a rate-of-change (delta)
over a pre-defined period. FlexElements™ can be used to generate
special protection or monitoring functions. The relay supports up to
8 FlexElements™.
Enhanced Bay visualization & control aided
Digital Counters by single line diagram display – 30TE (6”) version
Multilin Agile provides sixteen identical digital counters. A digital
counter counts the number of state transitions from logic 0 to logic
Breaker Health Monitoring
1. The counters are generally used to count operations such as
pickups of an element, changes of state of an external contact (e.g., The breaker is monitored by the relay not only for detection of breaker
breaker auxiliary switch), or pulses from a watt-hour meter. failure, but also for the overall “breaker health” which includes:
• Breaker close and breaker open times
FlexLogic™
• Trip circuit monitoring
FlexLogic™ is the powerful programming logic engine that provides
• Spring charging time
the ability to create customized protection and control schemes
logic for feeder control interlocking schemes with adjacent • Per-phase arcing current
protection and dynamic setting group changes, minimizing the need • Trip counters
for and the associated costs of auxiliary components and wiring.
DC Supply Monitoring
Switchgear Control and Configurable SLD
Multilin Agile measures the DC auxiliary supply infeed to the device,
Multilin Agile offers comprehensive switchgear control aided by a to determine whether the supply is within acceptable operational
configurable SLD & breaker control. A total of 8 switchgear elements limits. Three DC supply monitoring zones are available, for under and
can be controlled. Circuit Breaker control is available through dedicated overvoltage alarming. The DC auxiliary supply value can be displayed
Open/Close push buttons, graphical HMI interface, optically isolated on the front panel LCD. This measurement also assists in auto
inputs and remotely via the substation communication. configuration of binary input pickup thresholds to provide accurate
Up to six (6) pages of configurable SLD are supported which can be pickup and drop-off.
configured to show breakers, switches, metering, and status items.
The device allows double point status and control over the IEC 61850 Active Impedance Binary Inputs
protocols for various types of switches and disconnectors. Multilin Agile binary inputs comply to the ESI 48-4 EB2 standard and
are immune to inductive fields created in substations where wiring
Supervisory and Condition Monitoring Functions runs for hundreds of meters in the yard and neighboring wires,
Depending on the hardware base, two stage circuit breaker failure busbars and power conductors create strong fields. The inputs
protection, CT/VT supervision, circuit breaker condition monitoring support programmable pickup and drop-off and no spurious pickup
and trip circuit supervision are available. during battery ground faults or capacitive discharges, thereby making
them perfect for plant status monitoring.
The optically isolated inputs and programmable scheme logic
enable supervision of the trip circuit in both open and closed
states. Multilin Agile claims full compliance with the benchmark H7
supervision scheme.

Binary inputs immunity to inductive fields

4 GEGridSolutions.com
Multilin Agile

Measurement, Recording and Post-Fault Analysis Local and Remote Communication


Multilin Agile offers unmatched power system analytics through the Multilin Agile provides advanced communication technologies for
advanced features and monitoring and recording tools. remote data and engineering access, making it easy and flexible to
use and integrate into new and existing networks. Providing several
Up to 2048 time-tagged event records are stored in non-volatile
Ethernet and serial port formats and supporting a wide range of
memory and can be extracted using the communication ports or
industry standard protocols, the relay can be integrated directly into
viewed on the front panel display. Records of the last 25 faults are
DCS and SCADA systems.
stored, and fault data is also available via the IEC 61850 protocol.
The following protocols are supported:
The internal disturbance recorder has up to 16 analog oscillograph
channels and 64 digital channels, with a 30 second capacity. • Modbus (RS485 serial and Ethernet)

The relay offers comprehensive Power Quality metering by • IEC 61850 Ed. 2
measuring up to the 21st harmonic for both currents and voltages • IEC 60870-5-103 serial
including total harmonic distortion (THD).
• DNP3.0 (RS485 serial and Ethernet)
A voltage interruption monitoring element displays the number of • IEC62439 (PRP/HSR) redundancy protocol
voltage interruptions and the duration of voltage interruption for a
selected period. • IEEE 1588 (PTP) for time synchronization
Substation
Incomer Automation
HARMONICS Fundamental
Blocking high set
3rd Harmonic element & CB fail
5th Harmonic backtrip Modbus TCP
Amplitude

7th Harmonic
Resultant

RTU/Gateway Modbus TCP

1 3 5 7 9 Time
Meters
IEC 60870-5-103
Power Quality Monitoring & Custom Schemes
IEC 61850 GOOSE
Multilin Agile provides a comprehensive datalogging facility where the
Mixed Communication Protocols: Application Example
average values of analog metering can be recorded at a user selectable
interval. The datalogger can store information from up to 16 analog
channels, selected from any analog values calculated by the relay.
All serial protocols - Modbus, IEC 60870-5-103 and DNP 3.0 -
are switchable in settings and site- selectable for customer use.
Similarly, all the Ethernet protocols (Modbus TCP, IEC 61850 and
DNP 3.0) are available for selection once ordered.

The concurrent Ethernet protocol feature allows customers to


futureproof their investment for applications requiring support of
multiple Ethernet protocols in a single device. Similarly, ordering the
Ethernet option in a device initially connected with a serial protocol
can provision for a future communications upgrade to Ethernet.

Multilin Agile offers 128 virtual inputs, and superior GOOSE


performance.

Phasor view for effective monitoring, commissioning & troubleshooting

GEGridSolutions.com 5
Multilin Agile

Advanced Cybersecurity Security Server

Multilin Agile helps prevent unauthorized access and malware by


delivering host of cybersecurity features compliant with NIS and NERC
CIP guidelines, or other security regulations.
• Authentication/authorization/accounting server support Access Authentication Request:
Request: Role, User, Password
(AAA-Radius) Encrypted (SSH)
Role, User,
• Role Based Access Control (RBAC) Password

• Non-erasable cyber event recorder (Syslog for SEM)


• Product level security
• Achilles Level 1 certified for Cyber Security penetration tests

Testing and Simulation


Multilin Agile offers the capability for simulating current and voltage
inputs. Other test operations are also possible such as the LED lamp Authentication Request:
Role, User, Password
test for each color, contact input states and testing of output relays. Encrypted (SSH)
The simulation feature tests the response to programmed conditions,
without the need of external AC voltage and current inputs. First time
users will find this to be a valuable training tool. System parameters Cybersecurity with Radius Authentication
such as currents, voltages and phase angles are entered as setpoints.
When placed in simulation mode, the relay suspends reading actual AC
inputs, generates samples to represent the programmed phasors, and
loads these samples into the memory to be processed by the relay.
Normal (pre-fault), fault and post-fault conditions can be simulated to
exercise a variety of relay features.

Model Variants and Intended Application


MODEL HARDWARE BASE INTENDED APPLICATION CASE SIZE
P14NB P14N Non-directional feeder 20TE / 30TE
P14NL P14N Non-directional feeder with autoreclose 20TE / 30TE
P14NZ P14N Non-directional feeder with autoreclose and HIF** downed conductor 20TE / 30TE
P14DB P14D Directional feeder 20TE / 30TE
P14DL P14D Advanced directional feeder with autoreclose and check synchronizing 20TE / 30TE
P14DZ P14D Advanced directional feeder plus HIF** downed conductor or TGFD*** 20TE / 30TE
transient ground fault detection
P94VB P94V Voltage and frequency 20TE / 30TE
P94VP P94V Voltage and frequency with autoreclose and check synchronizing 20TE / 30TE
** HIF (with sensitive CT, TGFD not available)
** HIF support in 30TE (6”) version only
***TGFD (with standard CT, HIF not available)

Hardware Overview
VOLTAGE &
NON-DIRECTIONAL DIRECTIONAL
FREQUENCY
FUNCTION P14N P14D P94V
CT (AC current) inputs : 1 and 5 A software selectable 3Ph +N 3Ph +N
VT (AC voltage) inputs : 100/120 V 4 4
Digital inputs min./max. hardware option
20TE (4”) Case 5 to 14
30TE (6”) Case 11 to 30
Output relays min./max. hardware option
20TE (4”) Case 5 to 11
30TE (6”) Case 9 to 25
Rear communication port (software selectable to convert into
RS485
demodulated IRIG-B)
2nd Rear communication port options Additional RS485 serial (20TE only), 0 to 3 RJ45 Ethernet,
0 to 3 fiber Ethernet*
Communication Protocols IEC 103, Modbus, DNP3.0, Modbus TCP, DNP3 Ethernet, IEC 61850, IEC62439
(PRP/HSR) *
Trip circuit supervision (H7 scheme) Yes

*Refer to order code for possible combinations. Please refer to the wiring diagram

6 GEGridSolutions.com
Multilin Agile

Protection & Control Functions


VOLTAGE &
NON-DIRECTIONAL DIRECTIONAL
FREQUENCY
ANSI
FUNCTION P14NB P14NL P14NZ P14DB P14DL P14DZ P94VB P94VP
CODE
50 Definite time overcurrent protection 6 6 6 6 6 6
50N/G Neutral / Ground definite time overcurrent
4 4 4 4 4 4
protection (Derived and Measured)
51 IDMT overcurrent 3 3 3 3 3 3
51N/G Neutral / Ground IDMT overcurrent protection 2 2 2 2 2 2
50/51SEF Sensitive ground fault 4 4 4 4 4 4
68 Inrush blocking • • • • • •
Cold load pick up • • • • • •
YN Admittance protection • •
21BL Load encroachment supervision (Load blinders) • •
HIF High Impedance (HiZ) Ground Fault (downed 30TE 30TE
conductor)** only only
TGFD Transient Ground Fault Detection*** •
46 Negative sequence overcurrent 4 4 4 4 4 4
46BC Broken conductor 4 4 4 4 4 4
55 Power factor • •
Programmable curves 4 4 4 4 4 4
67 Directional phase overcurrent 6 6 6
67N/G Directional neutral/ground overcurrent 4 4 4
Sensitive directional ground fault 4 4 4
67_2 Directional negative sequence overcurrent • • •
32N Wattmetric ground fault • • •
Blocking scheme • • • • • •
37 Undercurrent detection (loss of load) • • • • • •
32 Phase directional power (forward/reverse/
4 4
under/over)
49 Thermal overload (current replica) • • • • • •
50BF CB failure • • • • • •
21FL Fault locator • •
24 Volts per Hertz • • • •
27Q Undervoltage reactive power • •
27T Timed undervoltage • • • • •
27/59 Undervoltage/overvoltage 4/4 4/4 4/4 4/4 4/4
27V/59V Positive sequence undervoltage/overvoltage 2/2 2/2 2/2 2/2 2/2
59N Residual overvoltage 4 4 4 4 4
47 Negative sequence overvoltage • • • • •
79 Autoreclose (number of shots) 4 4 4 4 4
25 Check synchronizing • • •
81O Overfrequency 9 9 9 9 9
81U Underfrequency 9 9 9 9 9
81V Undervoltage blocking of frequency protection • • • • •
81 df/dt Rate of change of frequency 9 9 9 9
Fast underfrequency • • • • •
Underfrequency restoration • • •
87G Restricted ground fault (REF) • • • •
FlexLogic • • • • • • • •
86 Latching output contacts (lockout) • • • • • • • •
Switch status control • • • • • • • •
VTS VT supervision • • •
CTS CT supervision • • •
DC supply supervision • • • • • • • •
CB condition monitoring • • • • • • • •
52PD Pole discrepancy • • • • • •
Setting groups 6 6 6 6 6 6 6 6

** HIF (with sensitive CT, TGFD not available)


** HIF support in 30TE (6”) version only
***TGFD (with standard CT, HIF not available)

GEGridSolutions.com 7
Multilin Agile

Wiring Diagram – 20TE (4”) Version

20 19 18 17 16 15 14 13 12 11
REVISION HISTORY
DIRECTION OF FORWARD CURRENT FLOW REV ITR ECO # DESCRIPTION DD/MM/YY APPROVED

A 0 T2019037684 FIRST ISSUE 14-03-19 J.A.

A
P2
S2 S1
P1
FIG. 1 1
2
T2019047761
T2019098259
FIRST REVISION
SECOND REVISION
08-04-19
01-10-19
J.A.
J.A.

B 52 3 T2019108337 THIRD REVISION 16-10-19 J.A.


A 2 T2019118511 FOURTH REVISION 21-11-19 A.Z.
C B C A 3 T2020048981 GENERAL REVISION 22-04-20 A.Z.
PHASE ROTATION
A.C./D.C. SUPPLY B 2 T2020048992 GENERAL REVISION 29-04-20 A.Z.

C 2 CID006806 GENERAL REVISION 11-03-21 N.M.


E C B A A B C -/N +/L
CASE EARTH CONNECTION T2021030001
CID006893
E
D 2 GENERAL REVISION 17-05-21 N.M.
T2021050041
B1 A2 A1 E 2 CID006893
T2021080002
GENERAL REVISION 03-08-21 A.Z.
CID008056
IA B2 F 2
T2023090022
GENERAL REVISION 15-11-23 I.M.
N N
B3 Table 3
n n IB B4 + IRIG-B +
COMMUNICATIONS

COM 1
EIA RS485 / IRIG-B -
B5 1
GND IRIG-B GND CORTEC
c b a a b c IC B6 COM 1 COM 2 ETH1 ETH 2 ETH3
GND
DIGIT 7

ETH 1, 2, 3 COM 2
B7 EIA RS485 - RJ45 ENG
3 2 EIA RS485/IRIG-B - PORT
- -
IN B8 +
5 EIA RS485/IRIG-B - RJ45 - -
10 Base-T / 100 Base TX RJ45
VA A3 6 EIA RS485/IRIG-B - Fiber - -
TX
100FX LC Fiber A EIA RS485/IRIG-B EIA RS485 RJ45 RJ45 RJ45
RX
VB A4
D 2 B EIA RS485/IRIG-B EIA RS485 RJ45 Fiber Fiber D
C EIA RS485/IRIG-B EIA RS485 Fiber Fiber Fiber

P14D
VC A5

A6
A7

V CHECK
SYNC Table 4
A8
INPUT/OUTPUT
Table 1 SLOT
DESCRIPTION
SENSITIVE EARTH (GROUND) FAULT CT D C
A BINARY INPUT / OUTPUT OPTIONS (ORDER CODE DIGIT 8)
DIRECTION OF FORWARD CURRENT FLOW 5 inputs (2 for Trip Circuit
B Supervision) + 7 outputs +1 I/O TYPE 1 N/A
P2 P1 I/O TYPE 1 I/O TYPE 2 I/O TYPE 4
A Watchdog
S2 S1 C B

ORDER CODE DIGIT (8)


B Opto I/P 1 Opto I/P 1 Opto I/P 1
(*)1 + (*)1 + (*)1 + 8 inputs (2 for Trip Circuit
OPTO ISOLATED

OPTO ISOLATED
BINARY INPUTS

BINARY INPUTS
PHASE ROTATION
C C
C Supervision) + 5 outputs +1 I/O TYPE 2 N/A C
(*)2 + Opto I/P 2 (*)2 + Opto I/P 2 (*)2 + Opto I/P 2
B1 Watchdog
IA B2
(*)3 + Opto I/P 3 (*)3 + Opto I/P 3 (*)3 + Opto I/P 3 11 inputs (2 for Trip Circuit

OPTO ISOLATED
BINARY INPUTS
B3
D Supervision) + 11 outputs +1 I/O TYPE 1 I/O TYPE 4
IB B4 (*)4 - Opto I/P 1,2,3 (*)4 - Opto I/P 1,2,3 (*)4 - Opto I/P 1,2,3 Watchdog
B5
(*)5 + (*)5 + (*)5 + Opto I/P 4 14 inputs (2 for Trip Circuit
OPTO ISOLATED

OPTO ISOLATED
IC B6 Opto I/P 4 Opto I/P 4 Supervision) + 9 outputs +1
TCS INPUTS

TCS INPUTS
E I/O TYPE 2 I/O TYPE 4
B7 (*)6 - (*)6 - (*)6 + Opto I/P 5 Watchdog
IN SENSITIVE B8
(*)7 + (*)7 + (*)7 + Opto I/P 6
Opto I/P 5 Opto I/P 5
(*)8 - (*)8 - (*)8 - Opto I/P 4,5,6

Table 2 (*)9 (*)9 (*)9


+ Opto I/P 6

RELAY OUTPUT CONTACTS


Relay O/P 1
OPTO ISOLATED
BINARY INPUTS

DELTA CONECTION Relay 1 - Trip / (*)10


DIRECTION OF FORWARD CURRENT FLOW (*)10 Relay O/P 1 (*)10 + Opto I/P 7
A (*)11
B B
(*)11 (*)11 Relay O/P 2
A + Opto I/P 8 (*)12
B Relay O/P 2 (*)13
C B (*)12 (*)12 -
C Opto I/P 6,7,8 Relay O/P 3
PHASE ROTATION (*)14
RELAY OUTPUT CONTACTS

Notes
(*)13 (*)13 1. Standard Earth (Ground) Fault CT typical connections (Order code digit ‘6’, option ‘1’). For
Relay O/P 3 Relay 1 - Trip / (*)15
(*)14 (*)14 Relay O/P 1 Relay O/P 4 Sensitive Earth (Ground) Fault CT connections (Order code digit ‘6’, option ‘2’), refer Table 1.
(*)16 2. Wye VT typical connections. For Delta connections, refer Table 2.
(*)15 (*)15
RELAY OUTPUT CONTACTS

3. For Communciation interface options, refer to Table 3.


Relay O/P 4 Relay O/P 2 4. For Input/Output options, refer to Table 4.
(*)16 (*)16
5. (*) To be replaced by Slot digit (e.g. C1 for using Slot C in first input).
(*)17 (*)17 6. Outputs working as "Relay 1 - Trip" and "Critical Fail" only in I/O when located in Slot D.
Relay O/P 5 Relay O/P 3 7. Maximum continuous current supported by outputs 1, 2 and 3 of I/O type 1 and 2 is 10A.
VA A3 (*)18 (*)18
For all other outputs of different I/O types, it is 5A.
(*)19 (*)19
VB A4 Relay O/P 6 Relay O/P 4
(*)20 (*)20
UNLESS OTHERWISE SPECIFIED NAME DD/MM/YY
VC A5 (*)21 (*)21 DIMENSIONS ARE (TBS) Grid Solutions
Relay O/P 7 Relay O/P 5 DRAWN N. M. 22-01-21 GE Power Management
A N A6 (*)22 (*)22 INTERPRET DIM TOLERANCE
PER ASME Y14.5/ISO BS8888 CHECKED
AV. PINOA 10, 48170 ZAMUDIO (SPAIN) A
(*)23 (*)23 TOLERANCE MM: TOLERANCE INCH: APPROVED TITLE: STATUS:
Critical Fail/Relay Critical Fail/Relay 1 PL +/- 1 PL +/- .X MATERIAL:
(*)24 O/P 8 (*)24 O/P 6 2 PL +/- 2 PL +/- .XX
P14D DIRECTIONAL PHASE
APPROVED
ANGLE +/- 3 PL +/- .XXX OVERCURRENT IED, 20TE CASE
ANGLE +/- 0.5 DEG FINISH:

THIRD ANGLE CTQ (Critical to Quality) SIZE: DWG.NO. REV. ITR.


PROJECTION
MAJOR INSPECTION NEXT STAGE: 2 C C154201 F 2
TBD TBD
SCALE: PART NUMBER: C1542P1 REV F2 SHEET 1

20 19 18 17 16 15 14 13 12 11

8 GEGridSolutions.com
Multilin Agile

Wiring Diagram – 30TE (6”) Version

20 19 18 17 16 15 14 13 12 11
REVISION HISTORY
DIRECTION OF FORWARD CURRENT FLOW REV ITR ECO # DESCRIPTION DD/MM/YY APPROVED

A A 1 T2023060050 FIRST ISSUE 16/06/23 I.V.

A
P2
S2 S1
P1
FIG. 6 B
C
2
2
T2023070064
T2024070010
GENERAL REVISION
GENERAL REVISION
19/07/23
04/07/24
I.M.
I.M.

B 52
C B C
PHASE ROTATION
A.C./D.C. SUPPLY
E C B A A B C -/N +/L
CASE EARTH CONNECTION E
Table 3
B1 A2 A1 COMMUNICATIONS
IA B2
N N ORDER CODE
COM 1 ETH1 ETH 2 ETH3
B3 DIGIT 7
n n IB B4 + IRIG-B +
RJ45 ENG

COM 1
EIA RS485 / IRIG-B -
2 EIA RS485
PORT
- -
B5 1
c b a a b c GND IRIG-B GND 5 EIA RS485 RJ45 - -
IC B6 3

ETH 1, 2, 3
10 Base-T / 100 Base TX RJ45 6 EIA RS485 Fiber - -
B7
IN B8 100FX LC Fiber
TX D EIA RS485 RJ45 RJ45 RJ45
RX
E EIA RS485 RJ45 Fiber Fiber

VA A3 F EIA RS485 Fiber Fiber Fiber

VB A4
D 2 D
Table 4

P14D
VC A5 INPUT/OUTPUT
A6 SLOT
DESCRIPTION
A7 F E D C

V CHECK 11 inputs (2 for Trip Circuit


SYNC D Supervision) + 11 outputs +1 I/O TYPE 1 I/O TYPE 3 NA NA
A8 Watchdog

Table 1 14 inputs (2 for Trip Circuit


SENSITIVE EARTH (GROUND) FAULT CT E Supervision) + 9 outputs +1 I/O TYPE 2 I/O TYPE 3 NA NA
A BINARY INPUT / OUTPUT OPTIONS (ORDER CODE DIGIT 8) Watchdog
DIRECTION OF FORWARD CURRENT FLOW
P2 P1 I/O TYPE 1 I/O TYPE 2 I/O TYPE 3 16 inputs (4 for Trip Circuit
A F Supervision) + 11 outputs +1 I/O TYPE 2 NA I/O TYPE 2 NA
S2 S1 C B
B
(*)1 + Opto I/P 1 (*)1 + Opto I/P 1 + Opto I/P 1 Watchdog
(*)1
OPTO ISOLATED

OPTO ISOLATED
BINARY INPUTS

BINARY INPUTS
PHASE ROTATION

ORDER CODE DIGIT (8)


C C C
Opto I/P 2 Opto I/P 2 22 inputs (4 for Trip Circuit
B1 (*)2 + (*)2 + (*)2 + Opto I/P 2
G Supervision) + 15 outputs +1 I/O TYPE 2 I/O TYPE 3 I/O TYPE 2 NA
IA B2 Watchdog
(*)3 + Opto I/P 3 (*)3 + Opto I/P 3 (*)3 + Opto I/P 3

OPTO ISOLATED
BINARY INPUTS
B3
(*)4 - Opto I/P 1,2,3 (*)4 - Opto I/P 1,2,3 (*)4 - Opto I/P 1,2,3 30 inputs (6 for Trip Circuit
IB B4
H Supervision) + 21 outputs +1 I/O TYPE 2 I/O TYPE 3 I/O TYPE 2 I/O TYPE 2
B5
Opto I/P 4 Watchdog
(*)5 + (*)5 + (*)5 +
OPTO ISOLATED

OPTO ISOLATED
IC B6 Opto I/P 4 Opto I/P 4
TCS INPUTS

TCS INPUTS
- - Opto I/P 5
24 inputs (6 for Trip Circuit
B7 (*)6 (*)6 (*)6 +
J Supervision) + 25 outputs +1 I/O TYPE 2 I/O TYPE 3 I/O TYPE 1 I/O TYPE 1
IN SENSITIVE B8 Watchdog
(*)7 + (*)7 + (*)7 + Opto I/P 6
Opto I/P 5 Opto I/P 5
16 inputs (4 for Trip Circuit
(*)8 - (*)8 - (*)8 - Opto I/P 4,5,6
P Supervision) + 11 outputs + 1 I/O TYPE 2 N/A N/A I/O TYPE 2
Table 2 (*)9 (*)9 (*)9 watchdog (Ring terminals)
+ Opto I/P 6

RELAY OUTPUT CONTACTS


Relay O/P 1
OPTO ISOLATED
BINARY INPUTS

DELTA CONECTION Relay 1 - Trip / (*)10 22 inputs (4 for Trip Circuit


DIRECTION OF FORWARD CURRENT FLOW (*)10 Relay O/P 1 (*)10 + Opto I/P 7 Supervision) + 15 outputs + 1
A (*)11
B R I/O TYPE 2 I/O TYPE 3 N/A I/O TYPE 2 B
Relay O/P 2 watchdog (Ring + Pin hybrid
(*)11 (*)11 + (*)12 terminals)
A Opto I/P 8
B Relay O/P 2 (*)13
C B (*)12 (*)12 -
C Opto I/P 6,7,8 Relay O/P 3
PHASE ROTATION (*)14
RELAY OUTPUT CONTACTS

Notes
(*)13 (*)13 1. Earth fault typical CT connections (Order Code Digit 6, option 1). For Sensitive Earth Fault CT
Relay O/P 3 Relay 1 - Trip / (*)15
(*)14 (*)14 Relay O/P 1 Relay O/P 4 option (Order Code Digit 6, option 2) see table 1.
(*)16 2. Wye VT typical connections. For Delta connections see table 2.
(*)15 (*)15
RELAY OUTPUT CONTACTS

3. For Order Code Communication options see table 3.


Relay O/P 4 Relay O/P 2 4. For Order Code input/output options see table 4. N/A (not available)
(*)16 (*)16
5. (*) To be replaced by Slot digit (e.g. C1 for using Slot C in first input).
(*)17 (*)17 6. Outputs working as "Relay 1 - Trip" and "Critical Fail" only in I/O when located in Slot F.
Relay O/P 5 Relay O/P 3 7. Maximum continuous current supported by outputs 1, 2 and 3 of I/O type 1 and 2 is 10A.
VA A3 (*)18 (*)18
For all other outputs of different I/O types, it is 5A.
(*)19 (*)19
VB A4 Relay O/P 6 Relay O/P 4
(*)20 (*)20
UNLESS OTHERWISE SPECIFIED NAME DD/MM/YY
VC A5 (*)21 (*)21 DIMENSIONS ARE (TBS) Grid Solutions
DRAWN
A (*)22 Relay O/P 7 (*)22 Relay O/P 5 INTERPRET DIM TOLERANCE
GE Power Management
A
N A6 PER ASME Y14.5/ISO BS8888 CHECKED
AV. PINOA 10, 48170 ZAMUDIO (SPAIN)

(*)23 (*)23 TOLERANCE MM: TOLERANCE INCH: APPROVED I.V. 16/06/23 TITLE: STATUS:
Critical Fail/Relay Critical Fail/Relay
(*)24 O/P 8 (*)24
1 PL +/- 1 PL +/- .X MATERIAL: P14D DIRECTIONAL
O/P 6 2 PL +/- 2 PL +/- .XX
ANGLE +/- 3 PL +/- .XXX PHASE OVERCURRENT
GE PROPRIETARY AND CONFIDENTIAL INFORMATION ANGLE +/- 0.5 DEG FINISH: IED, 30TE CASE
This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express condition that neither it nor the information contained therein THIRD ANGLE CTQ (Critical to Quality) SIZE: DWG.NO. REV. ITR.
shall be disclosed to others without the express written consent of GE, and that the information shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. PROJECTION
This document may be subject to certain restrictions under U.S. export control laws and regulations. © General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. MAJOR INSPECTION NEXT STAGE: 7 C C154206 C 2
TBD TBD
SCALE: PART NUMBER: C1542P6 REV C2 SHEET 6

20 19 18 17 16 15 14 13 12 11

GEGridSolutions.com 9
Multilin Agile

Order Code Information


VARIANTS ORDER NUMBER
1-4 5 6 7 8 9 10 11 12-13 14 15
Multilin Agile Application
Feeder Management Protection - Directional (with voltage and current inputs) P14D
Feeder Management Protection - Non Directional (current inputs only) P14N
Voltage/Frequency Protection - (voltage inputs only) P94V
Application Package Options
Base B
Base + 32/32N power, 79/25 reclose, df/dt frequency, 21FL fault locator P14D L
P14DL + HIF** downed conductor / TGFD*** transient ground fault P14D Z
Base + 79 reclose P14N L
Base + 79/25 reclose P94V P
Current / Voltage Inputs
Standard Earth (Ground) CT P14D/N 1
Voltage Only P94V 1
Sensitive Earth (Ground) Fault CT P14D/N 2
Hardware Options Case
EIA RS485 serial comms – with RJ45 Engineering Port (only) 20TE/30TE 2
EIA RS485 serial comms and station bus Ethernet - Single channel RJ45 copper 20TE/30TE 5
EIA RS485 serial comms and station bus Ethernet - Single channel fiber 20TE/30TE 6
2x EIA RS485 serial, 2x RJ45 Ethernet (configurable PRP/HSR/LLA) and 1x RJ45 20TE A
2x EIA RS485 serial, 2x fiber Ethernet (configurable PRP/HSR/LLA) and 1x RJ45 20TE B
2x EIA RS485 serial, 2x fiber Ethernet (configurable PRP/HSR/LLA) and 1x fiber 20TE C
1x EIA RS485 serial, 2x RJ45 Ethernet (configurable PRP/HSR/LLA) and 1x RJ45 30TE D
1x EIA RS485 serial, 2x fiber Ethernet (configurable PRP/HSR/LLA) and 1x RJ45 30TE E
1x EIA RS485 serial, 2x fiber Ethernet (configurable PRP/HSR/LLA) and 1x fiber 30TE F
Binary Input / Output Options Case
5 inputs (2 for Trip Circuit Supervision) + 7 outputs + 1 watchdog 20TE B
8 inputs (2 for Trip Circuit Supervision) + 5 outputs + 1 watchdog 20TE C
11 inputs (2 for Trip Circuit Supervision) + 11 outputs + 1 watchdog 20TE/30TE D
14 inputs (2 for Trip Circuit Supervision) + 9 outputs + 1 watchdog 20TE/30TE E
16 inputs (4 for Trip Circuit Supervision) + 11 outputs + 1 watchdog 30TE F
22 inputs (4 for Trip Circuit Supervision) + 15 outputs + 1 watchdog 30TE G
30 inputs (6 for Trip Circuit Supervision) + 21 outputs + 1 watchdog 30TE H
24 inputs (6 for Trip Circuit Supervision) + 25 outputs + 1 watchdog 30TE J
16 inputs (4 for Trip Circuit Supervision) + 11 outputs + 1 watchdog (Ring terminals) 30TE P
22 inputs (4 for Trip Circuit Supervision) + 15 outputs + 1 watchdog (Ring + Pin hybrid terminals) 30TE R
Communication protocols / Cybersecurity
DNP3.0 / Modbus / IEC 60870-5-103 2
IEC 61850 / DNP3.0 / Modbus / IEC 60870-5-103 3
IEC 61850 / DNP3.0 / Modbus / IEC 60870-5-103 + advanced cyber Level 2 4
Case
20TE Flush (4 inch width) with text display B
30TE Flush (6"), 6 function keys, 16 programmable LEDs and Color Graphical HMI (IEC version)* C
30TE Flush (6"), 6 function keys, 16 programmable LEDs and Color Graphical HMI (ANSI version)* E
30TE Flush (6"), 6 function keys, 16 programmable LEDs, Color Graphical HMI & Bay Control (IEC
G
version)
30TE Flush (6"), 6 function keys, 16 programmable LEDs, Color Graphical HMI & Bay Control
N
(ANSI version)
Software upgrade only (via After Sales) 0
Language
English (UK) / English (US) / French / Spanish / Russian / Turkish 0
Software Version
Unless specified the latest version will be delivered **
Customization / Regionalization
Regular (IEC standards and 50Hz/1 amp based default settings) 0
IEEE market default configuration - US English, 60Hz and 5 amp preconfiguration 6
Customer specific A
Hardware design suffix
Enhanced model E

Note
P40 Agile Enhanced (20TE) is now rebranded to Multilin Agile (20TE)
* Offers a single line diagram for control, but with a basic, fixed bay template only. G and N options are required for a configurable mimic diagram.
** Only with ground fault (SEF) CT option.
** HIF support in 30TE (6”) version only.
***TGFD (with standard CT, HIF not available).

10 GEGridSolutions.com
For more information
visit GEGridSolutions.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered
trademark of Schneider Automation. NERC is a registered trademark of North American Electric
Reliability Council. NIST is a registered trademark of the National Institute of Standards and
Technology. ABB Thomas & Bets is a registered trademark of ABB Installation Products Ltd.
Cooper Nova is a registered trademark of Eaton Corporation. All other trademarks, images and
graphics are property of their respective owners.

GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of
General Electric Company. GE Vernova reserves the right to make changes to specifications
of products described at any time without notice and without obligation to notify any person
of such changes.

© 2024 GE Vernova and/or its affiliates. All rights reserved. GEA35499


English