Adedamola Ojerinde MOBOLANLE Complete
Adedamola Ojerinde MOBOLANLE Complete
Dr Eshrar Latif
i
ii
Abstract
Shelter is a basic human need for comfort and safety; however, Nigeria has a housing
deficit of 17 million units. Modern construction materials are not affordable for most
earners and have a significant environmental impact.
This research investigates the suitability of substituting locally available rice husk ash
(RHA) for up to 50% cement stabiliser in compressed earth blocks (CEB) over three
different curing times. CEBs with up to 30% RHA substitution were produced with enough
compressive strength for load-bearing use in 2 and 3 storey buildings. They also met
initial hygrothermal requirements.
Data from the mechanical and hygrothermal investigation were utilised in hygrothermal
simulations for normal (eg bedroom, living room) and high relative humidity spaces (eg
kitchen, bathroom) to establish likely issues with condensation (interstitial or surface) or
mould growth on interior wall, which could affect occupant comfort and safety, or impair
structure durability. Simulation was based on the tropical Savannah climate in Nigeria for
full cavity and partially insulated cavity wall structures for CEB with up to 30% RHA
substitution. 20% was the highest RHA substitution CEBs achieving acceptable results.
In a full cavity wall structure, it was less likely to suffer condensation or mould (than in
partial insulated cavity) but would benefit from treatment with a moisture retarding material
if used in a high humidity space.
Thermal simulation of a free-running building indicated that thermal comfort with 20%
RHA substitution CEBs achieved similar hours at 90% satisfaction as a concrete wall, so
replacement would not lead to disadvantage for occupants.
iii
Acknowledgements
I would like to thank the following people who have supported me during the period of the
research:
My supervisor’s Dr Vicki Stevenson and Dr Eshrar Latif for their enthusiasm for the project,
for their support, encouragement, and patience.
I would like to thankful to Welsh school of Architecture and School of Chemistry, Cardiff
University, Covenant University and Federal Ilaro Polytechnic.
I would also like to thank Mr Odion, the sculptor that allowed me to use his furnace for
combusting Rice husk. Mr Gbadamosi Ibrahim Abiodun and Mr Mathew Oladele Bamidele
for building the thermal box required for the thermal test.
I would like to appreciate my parent, friends, Prof Dibu Ojerinde, Dr Raheem Oloyo and my
husband for the unconditional support throughout duration of the research.
iv
Table of Contents
Contents
Abstract ....................................................................................................................... iiiii
Acknowledgements .....................................................................................................iviii
Nomenclature ...........................................................................................................xxxix
1. Introduction ................................................................................................................ 1
2. Introduction ................................................................................................................ 5
2.1. Housing in Nigeria – Types, Demand Challenge and Supply Strategies ............. 5
2.2. Traditional and Modern Architecture and Types of Housing in Nigeria ................ 8
2.4.2. Blockwork....................................................................................................................................... 25
2.8.1. Possible walls system used for construction with compressed earth blocks. ... 64
3 Research Methodology............................................................................................. 71
vi
3.4.1 Modelling for interstitial condensation and assessing risk of mould growth
development on selected CEB compositions.....................................................................................107
5.2.1. Adaptive comfort for a tropical savanna climate (ASHRAE 55-2010) ................177
6. Discussion ..............................................................................................................179
viii
List of Tables
Page
Table 2.3 Number of housing unit/ net hectare provided by different types 16
of houses
Table 2.6 Types of presses used for Compressed earth blocks (CEBs) 35
Production
Table 2.8 Chemical and physical properties of sugar bagasse ash (SBA) 43
Table typical moisture generated in areas with normal and high relative 56
2.11 humidity in a typical Nigeria house generated from Table 2.10
ix
Table 3.5 Condition of CEBs in a laboratory 90
Table 4.1 Properties of Laterite sample used for making the experimental 113
CEB
Table 4.2 Description of the unified soil classification with laterite 114
classification highlighted
Table 4.3 Percentage amorphous silica contents of experimental rice husk 116
ash (RHA) samples at different combustion times
Table 4.4 Bulk density of solid CEBs produced with varying partial 117
replacement of OPC with RHA
Table 4.5 Bulk density of hollow CEBs produced with varying partial 118
replacement of OPC with RHA
Table 4.6 Effect of RHA inclusion and curing duration on the bulk density of 119
solid CEBs
Table 4.7 Effect of RHA inclusion and curing duration on the bulk density of 120
hollow CEBs
Table 4.8 Compressive strength of solid CEBs produced with varying 121
partial replacement of OPC with RHA
Table 4.9 Compressive strength of hollow CEBs produced with varying 122
partial replacement of OPC with RHA
Table Effect of RHA inclusion and curing duration on the compressive 123
4.10 strength of experimental solid CEBs
Table Effect of RHA inclusion and curing duration on the compressive 124
4.11 strength of experimental hollow CEBs
Table Water absorption capacity of solid CEBs produced with varying 126
4.12 partial replacement of OPC with RHA
Table Water absorption capacity of hollow CEBs produced with varying 127
4.13 partial replacement of OPC with RHA
Table Water absorption capacity of solid CEBs with varying RHA levels 128
4.14 cured for 14, 21 and 28 days
x
Table Water absorption capacity of hollow CEBs with varying RHA 129
4.15 levels cured for 14, 21 and 28 days
Table Thermal Conductivity of CEBs masonry wall with varying RHA 147
4.29 content
Table 5.2 Properties of experimental CEB used for simulation study 151
xi
Table 5.5 Distance of wall with varying Positions on wall 155
Table 5.7 Temperature of Wall section EP at areas with normal internal 156
relative humidity
Table 5.8 Temperature of Wall section EP at areas with high relative 157
internal humidity
Table 5.9 Temperature of Wall section NP at areas with normal internal 158
relative humidity
Table Relative humidity of Wall section EP at areas with normal internal 161
5.11 relative humidity
Table Relative humidity of Wall section EP at areas with high internal 161
5.12 relative humidity
Table Relative humidity of Wall section NP at areas with normal internal 162
5.13 relative humidity
Table Relative humidity of Wall section NP at areas with high internal 163
5.14 relative humidity
Table Moisture content of Wall section EP at areas with normal internal 165
5.15 relative humidity
Table Moisture content of Wall section EP at areas with high internal 166
5.16 relative humidity
Table Moisture content of Wall section NP at areas with normal internal 167
5.17 relative humidity
Table Moisture content of Wall section NP at areas with high internal 168
5.18 relative humidity
Table Building use, proportion of OPC replacement with RHA, mould 172
5.19 growth and WUFI code
xii
Table Adaptive comfort using natural ventilation 178
5.21
Table Time not achieving thermal comfort over 1 year - using Adaptive 178
5.22 comfort model at 90% and 80%
Table 6.1 Required CEB compressive strength for wall structures 184
Table 6.2 Correlation coeeficient (r) matrix for solid CEBs 186
Table 6.3 Correlation coeeficient (r) matrix for hollow CEBs 187
Table 6.4 Suitability of solid CEBs for application based on mechanical 191
properties
Table 6.5 Suitability of hollow CEBs for application based on mechanical 192
properties
Table 6.6 Suitability of solid CEBs for application based on hygrothermal 193
properties
Table 6.7 Suitability of solid CEBs for application based on results from 196
mould growth and interstitial condensation simulation
Table 7.1 %RHA compositions which meet required CEB compressive 201
strength for wall structures
xiii
List of Figures
Page
Figure 2.6 Nigeria max temperature for dry and rain season climate data 20
(Am, Aw, BWh, BSh) superimposed on bioclimatic template
Figure 2.13 Solid wall with external insulation with low resistance finish 65
Figure 2.14 Solid wall with external insulation with high vapour resistance 65
finish
Figure 2.17 Masonry wall with cavity- insulation partial filling the cavity 67
Figure 3.2 Green outline highlighting the location of Ogun state on the 75
map
xiv
Figure 3.3 Map of Ogun state and location of site, location and distance of 75
material to site
Figure 3.10 Change of mass per area vs square root of immersion time - 94
This represents a sample which did not develop water on the
top surface even after the longest immersion time
Figure 3.11 Change of mass per area vs square root of immersion time - 94
This represents a sample which developed water on the top
surface
Figure 3.15 Section of in-situ thermal test with CEB blocks exposed to 104
laboratory environment
Figure 3.16 Elevation of in-situ thermal test with CEB blocks exposed to 104
laboratory environment
Figure 4.3 Effects of RHA inclusion on bulk density of experimental solid 119
CEBs
xv
Figure 4.4 Effects of RHA inclusion on bulk density of experimental hollow 120
CEBs
Figure 4.9 Water content change over surface area and square root of 131
time in 24 hrs (control, S/0 RHA)
Figure 4.10 Water content change over surface area and square root of 132
time in 24 hrs (CEBs, S/0.2 RHA)
Figure 4.11 Water content change over surface area and square root of 133
time in 24 hrs (CEBs, S/0.4 RHA)
Figure 4.12 Water content change over surface area and square root of 134
time in 24 hrs (CEBs, S/0.6 RHA)
Figure 4.13 Water content change over surface area and square root of 135
time in 24 hrs (CEBs, S/0.8 RHA)
Figure 4.14 Water content change over surface area and square root of 136
time in 24 hrs (control, S/1 RHA)
Figure 4.15 Change in mositure content in CEBs at 10% RHA (S/0.2 RHA) 138
inclusion
Figure 4.16 Change in mositure content in CEBs at 20% RHA (S/0.4 RHA) 138
inclusion
Figure 4.17 Change in mositure content in CEBs at 30% RHA (S/0.6 RHA) 139
inclusion
Figure 4.18 Change in mositure content in CEBs at 40% RHA (S/0.8 RHA) 139
inclusion
Figure 4.19 Change in mositure content in CEBs at 50% RHA (S/1 RHA) 140
inclusion
xvi
Figure 4.20 Equilibrium moisture content curve for CEBs with 0% RHA (S/0 142
RHA)
Figure 4.21 Equilibrium moisture content curve for CEBs with 10% RHA 143
(S/0.2 RHA)
Figure 4.22 Equilibrium moisture content curve for CEBs with 20% RHA 143
(S/0.4 RHA)
Figure 4.23 Equilibrium moisture content curve for CEBs with 40% RHA 144
(S/0.8 RHA)
Figure 4.24 Compressed earth block stabilized with OPC (control) 146
Figure 4.25 10% RHA partially replaced OPC in compressed earth blocks 146
Figure 4.26 20% RHA partially replace OPC in compressed earth blocks 146
Figure 4.27 50% RHA partially replaced OPC in compressed earth blocks 147
Figure 4.28 Thermal condcutivity for masonry CEBs stabilized with RHA 147
Figure 5.6 Temperature of wall section EP for areas with normal internal 157
humidity
Figure 5.7 Temperature of wall section EP for areas with high internal 158
humidity
Figure 5.8 Temperature of wall section NP for areas with normal internal 159
humidity
Figure 5.9 Temperature of wall section NP for areas with high internal 160
humidity
Figure 5.10 Relative humidity of wall section EP for areas with normal 161
internal humidity
Figure 5.11 Relative humidity of wall section EP for areas with high internal 162
humidity
xvii
Figure 5.12 Relative humidity of wall section NP for areas with normal 163
internal humidity
Figure 5.13 Relative humidity of wall section NP for areas with high internal 164
humidity
Figure 5.14 Moisture content of wall section EP for areas with normal 165
internal humidity
Figure 5.15 Moisture content of wall section EP for areas with high internal 166
humidity
Figure 5.16 Moisture content of wall section NP for areas with normal 168
internal humidity
Figure 5.17 Moisture content of wall section NP for areas with high internal 169
humidity
Figure 5.18 Mould growth on interior wall surface EP for areas with normal 170
internal humidity
Figure 5.19 Mould growth on interior wall surface EP for areas with high 170
internal humidity
Figure 5.20 Mould growth on interior wall surface NP for areas with normal 171
internal humidity
Figure 5.21 Mould growth on interior wall surface NP for areas with high 171
internal humidity
Figure 5.22 Total water content in wall section EP in area with high relative 173
humidity for 1 year
Figure 5.23 Total water content in wall section NP in area with high relative 173
humidity for 1 year
Figure 5.24 Total water content in wall section EP in area with normal 174
relative humidity for 3 years
Figure 5.25 Total water content in wall section NP in area with normal 174
relative humidity for 3 years
Figure 5.26 Annual temperature and relative humidity of Lagos, Nigeria 175
Figure 5.27 Wind direction and wind speed using wind rose 177
xviii
Figure 6.1 Chat of unified soil classification 181
xix
Nomenclature
A area (m2)
EP External Plaster
L length (mm)
Lp plasticity index (numerical difference between liquid limit and plastic limit)
m mass (g)
xx
NBRRI Nigerian Building and Road Research Institute
NP No External Plaster
p vapour pressure
PR point of reference
RH Relative Humidity
S suitable
SD standard deviation
t time (s)
tp period (s)
T temperature (oC)
wl liquid limit (water content at which soil passes from the liquid to the plastic
state)
V volume (m3)
W water content
xxi
Z water vapour resistance, this is the reciprocal of the water vapour
permeance (m2.s.Pa/kg)
Greek Symbols
relative humidity
relative humidity
temperature (oC)
density (kg/m3)
xxii
1. Introduction
_______________________________________________________________________
1.1. Background
Shelter is a basic need for humans (Sekhar C & Nayak, 2018). Essentially, it provides
comfort and safety for the occupants. Quality housing enhances the health and wellbeing
of humans. Design and construction details and service life of the building determines the
house quality. Consequently, the construction industry has undergone changes in
response to changes in the environment, lifestyle of the people, increase in population, cost
of construction and other factors. The construction industry has contributed to the increased
greenhouse gas (GHGs) emissions which are associated with global climate change.
Globally, 24% of the raw materials are used in the construction industry; while the residential
and commercial buildings use 32% of total energy and account for over 30% of green gas
emissions worldwide (Tettey et al, 2017). In this context, it has been reported that cement
is the most widely used man-made material and is the source of about 8% of the world’s
CO2 emissions (Rogers, 2018).
However, the building industry has failed to reduce the housing deficit in Nigeria. The
need to provide low cost houses in Nigeria cannot be over emphasized. Indeed, it was
reported that the country’s housing deficit grew from 5 million units in 1991 to 17 million
units in 2017. Lagos alone, the country’s commercial nerve centre, has an estimated
housing shortage of 5 million units. Unfortunately, about 62% of Nigerians live below the
international poverty line (UNDP, 2015), which makes it difficult for them to afford
contemporary housing of the types prevalent in the developed countries. Over 90% of
low-income earners cannot afford decent accommodation even if they saved 100% of
their income for 10 years (Emmanuel, 2012). Doing that will be contravening the
recommendation that affordable house rental cost or mortgage repayment should not
exceed 30% of household income (including bills). In Nigeria the rental expenditure
annually in cities amount to $216 whereas the average income of 90% of Nigerians is
about $113 or $31 for more than 75% Nigerians (Olanrewaju et al, 2016). Also,
Government’s efforts at solving the problem of housing shortage proved futile because it
ended in providing unaffordable houses.
It is noticed that construction materials accounts for 60% of the total cost of building
construction, hence the use of cheaper and available suitable alternative materials could
contribute to housing sustainability in future. The Nigeria Building and Road Research
Institute (NBRRI) and Federal Housing Authority (FHA) in a collaborative investigation
noted that cost of building construction was reduced by at least 40% with the use of local
1
materials. In this regard, use of earth material in building construction may find useful
application in the context of Nigeria (Olotuah, 2002). While the use of earth material may
be of considerable value in low-rise building, it may be necessary to improve the strength
and durability of such construction materials if they will be used in the construction of multi
dwelling unit.
Several workers have confirmed that compressed earth block (CEB), an earth material,
can be stabilized to improve on its mechanical properties (Donkor & Obonyo, 2015;
Taallah & Guettala, 2016). The use of several agricultural waste products including rice
husk ash (Antiohos et al, 2014), waste sugarcane bagasse (Kazmi et al, 2016b), palm oil
fuel ash (Karim et al, 2013) sawdust or wood ash (Chowdhury et al, 2015), etc. as
stabilizing agents has been reported in other building materials.
The current study is interested in the use of rice husk ash (RHA) as a stabilizing agent in
CEB because of the huge investment of the Federal Government of Nigeria in rice
production in furtherance of the shift of the economy from being dependent on the crude
oil to agriculture. Consequently, the waste generation from rice processing industry
would increase; and it should therefore be reused to avoid environmental pollution it
would cause when not properly disposed.
Cost of cement has been of concern in the provision of sustainable housing. The material
is used as a binding agent in compressed earth block moulding. Sourcing an acceptable
alternative low-cost binding agent will significantly reduce cost of providing housing. RHA,
like other sustainable pozzolans could serve useful application here (Kumar & Gupta,
2016). (Kazmi et al, 2016b) suggested that addition of RHA in fired brick manufacturing
could lead towards sustainable and economical construction. A pozzolan is a siliceous or
a combination of siliceous and aluminous materials. Independently, it possesses little or
no cementing property, but in a finely divided form - and in the presence of moisture – it
will chemically react with calcium hydroxide to form compounds possessing cementitious
properties (Mehta et al, 1996). This suggests that the stabilizing strength of RHA in earth
blocks will depend on the geochemical composition of the earth material used. The
geochemical composition of the soil will vary according to the nature and mineral
composition originating rock.
Apart from reducing cost, RHA’s utilization in construction will displace the use of cement
in the construction industry thereby reducing environmental pollution. Also, it has lower
embodied energy compared to cement hence its use will save energy cost (Mithra, 2015).
RHA being a product of agricultural production will raise the farmers’ income. It will be
worthwhile to see the possibility of replacing cement with RHA in CEB.
1. Investigate the proportions of laterite, RHA, OPC and sharp sand needed to
produce RHA CEBs for walls in the tropical Nigeria.
2. Evaluate the mechanical and hygrothermal properties of the resulting CEBs and
analyse them against wall construction requirements; and
3. Simulate the hygrothermal and thermal properties to evaluate indoor air quality
and thermal comfort.
Chapter 2 (Literature Review) gives a critical evaluation of the research problem, current
materials used for masonry wall construction, and sustainable and affordable design
principles required for the Nigeria’s climate. It shows critical analysis of the available
pozzolans in the country, and most suitable mechanical and hygrothermal property for the
climate selected by studying suitable material characteristics to be used to address the
research problem in the form of review of literature.
Chapter 5 (Simulation Results) reports the results from simulation using WUFI PRO 5.3,
WUFI Bio and Design Builder 5.5. The simulation results were analysed to evaluate
indoor air quality and thermal comfort for the occupants of the residential house.
Chapter 6 (Discussion) presents the principles and relationships indicated by the results.
It points out exceptions or any lack of correlation and defines unsettled points. Finally, it
shows how the results and interpretations agree (or contrast) with the existing body of
knowledge. Discussion of the theoretical implication of the research results and possible
practical application is given in this section, also.
4
2. Introduction
_______________________________________________________________________
The large deficit of residential houses requires that the research concentrate on affordable
and sustainable building material for wall. The literature review explains a mean to achieve
wall material using local material with agricultural pozzolans to partially replace Ordinary
Portland cement by stabilizing earth material.
An investigation of the cause that led to the large deficit of residential house is reviewed in
this chapter. This process involves studying the urban population in each urban town, the
income of government worker at each level and to understand that the low-income earner
reason they cannot afford a safe house. The review aims to study a sustainable and
affordable wall material to reduce the cost of superstructure, as materials cost about 60%
of the whole building. The chapter investigates the traditional and modern means houses
to improve on the conditions of the people by studying the design strategy for the climate
to ensure comfort. The common wall material used in Nigeria was then studied, it was then
established to use local material to reduce cost and improve sustainability of the material.
The earth material was stabilized to ensure adequate mechanical and hygrothermal
property. The most frequently used stabilizing material is the ordinary Portland cement
(OPC), a review of some agricultural pozzolan was then studied to partially replace OPC.
The design approach to be used for masonry unit for wall was studied to ensure a means
to ensure indoor air quality and thermal comfort.
5
The rate of population migration from rural to urban areas in Nigeria has continued to
increase for some decades. For instance, in the early 1950s, there were 56 cities in the
country with 10.6% total population. By 1963 it increased to 19.1%, by 1985 increased to
24.5% of total population and in 2019 the city population increased to 48%.
The statistics shown in Table 2.1. illustrates the population densities in cities across
Nigeria. The cities with highest population density may need affordable housing unit to be
increased vertically (medium rise buildings) in direction rather than horizontal direction
(low rise buildings).
Port
1,148,065 158 7,266
Harcourt
The population of top 10 cities have been divided according to the climate in the country,
from the observation 6 of the cities are located at the tropical savanna climate. The
proposed affordable and sustainable design for wall material will be for the growing housing
deficits.
This rise in population in cities has also led to acute shortage of dwelling units which
resulted in overcrowding, high rent, poor urban living, low infrastructure services and high
6
crime rate. Public housing provision in the country has continued to lag behind the housing
demand (Ugochukwu & Chioma, 2015). The authors attributed the lag to the following
reasons:
The Nigeria’s housing deficit was estimated at 16-17 million units as at 2015. Also, it was
estimated that it would cost approximately $97,223,000,000 to fund 14 million units, an
average cost of $ 6944.50 per housing unit. Meanwhile, Salary Grade Level government
workers shown in Table 2.2 revealed that workers at the Director Level could comfortably
afford a 25-year mortgage to buy a property costing $13194.55, whereas a more typical
graduate post (Levels 8 to 9) would proportionately only be able to afford a mortgage on
$2368 – significantly lower than the projected cost (Ugochukwu & Chioma, 2015).
Government workers in the Director status on Salary Grade Level 17 are in the top workers
in the Public Service and are in the minority. Most of the workforce earn less, could not
afford to pay mortgage and thus needing affordable housing. Consequently, the current
research has focused on reducing cost building construction using cheaper and locally
available materials to provide affordable housing.
7
Table 2.2. Income of Government Workers in Nigeria
Level 02 514
Level 03 552.68
Level 05 693.22
©Federal civil service commission salary structure (Chizoba, 2019; Gberevbie, 2010)
In developing countries, it can be seen with modernization of the construction sector the
traditional knowledge that previously underpinned climate responsive vernacular design is
rapidly declining. Modern design pays little attention to local materials and traditional
method of construction. Vernacular architecture provides strong local content both in
traditions, materiality, building skills and methods. Traditional architecture buildings are
8
built with material within 360 m of their location due to the cost and difficulty of transporting
over long distance. Local materials selected are reflective on local climate and leads to
significant saving of embodied energy (Alabsi et al, 2016; Kırbaş & Hızlı, 2016).
The demand for sustainable construction at low cost is growing as a process of resolving
social, economic and environmental issues.
a. Culture: The Islamic faith encourages segregation of female and male (Figure 2.1).
They are also engaged in ornamentation and agriculture, which reflects on the façade
of the buildings (Figure 2.2).
b. Climate: Northern Nigeria has the vegetation of the equatorial desert characterised by
little rainfall and extreme temperature difference between the day and night-time; and
bright sunshine, hot and dry air during the daytime and during the night-time extremely
cold. The wind direction is mainly from the North–eastern (Sahara Desert) and some
from South-western (Atlantic Ocean) and average speed of 2-3m/s. The average
ground temperature is about 29-30oC annually, relative humidity has an average of 12-
29% from Oct-May and 45-59% from June-Sept (Meteonorm 7.2).
The house design has also undergone some changes because of colonialism;
movement to a more urban area; and separation of the extended family within a
compound. That is, making allowance for smaller unit living in the compound.
c. Social / economic: There has been a growing preference for a more modern style of
living over the traditional styles. However, there are still several Hausa that are
nomads.
Figure 2.1. Layout of Northern Living quarters showing separation of men and
women©(Moughtin, 2013)
10
Figure 2.2. Ornamentation of building Facade in Northern House ©Wikipedia,
Hausa people.
a. Climate: The region records average 26-28oC temperature and 75-90% relative
humidity annually, and predominant rainfalls. (Meteonorm and Climate consultant).
b. Design Approach: Architecture style of the Yoruba people is a courtyard, cuboid or
rectangular form of compound. The rooms are rectangular and arranged in a linear
pattern. The household leader has his room at the front of the house to provide a form
of security, boys rooms are at the corner. The wall surface is made of courses of mud
mixed with vegetative material such as straw and adhesives. The ceiling made of palm
fronds or split bamboo. Mud is then placed on the palm fronds to use as a decking
material. Construction takes place during dry season to accelerate curing. The
bedrooms and storage areas have small windows to allow light and air, providing a
comfortable living environment. The veranda is opened to allow light and air, while
shading openings. The cooking activity is performed outside (Adedokun, 2014).
There are two house types that characterise the southern region of Nigeria as depict below:
i. The first house type is built around one or more courtyards. The type of family system
within determines the form of the house. The compound has an open plan with a single
entrance, rooms facing the courtyard.
ii. The second house type is a new concept that became popular in 1930s when the
earning from coca, palm oil and other agricultural produce made people travel for work
purposes. The house has no compound and has a central corridor with series of
unconnected rooms (rooming house). The wall construction of this type of house was
compressed earth blocks, some of which were used without stabilization. The design
11
was to provide housing rental accommodation at reasonable cost for the immigrants
from rural to urban area (Okeyinka, 2015).
The second house type of Yoruba architecture (rooming style) is depicted in Figure 2.3.
The building has a raised ground level with a solid concrete foundation to prevent water
or moisture from penetrating into the interior of the building. Furthermore, it has a
veranda that the occupant uses as a sit out area. There is a long corridor with rooms
along the building.
12
Bungalow Duplex
African architecture has not been documented scientifically in terms of the design,
constructions approach but can be deduced to have good durability property based on the
long life of traditional existing buildings, which satisfies thermal comfort, aesthetic and
sustainability. African architecture technology has been regarded as primitive when
compared to western technology used for the construction of skyscrapers. However, there
are buildings in ancient towns of Kano and Zaria in Nigeria that have lasted over 100yrs.
Those buildings are affordable and comfortable with little carbon footprint. The introduction
13
of modern technology has relegated traditional component (Akadiri, 2015; Ugochukwu &
Chioma, 2015).
Affordable construction has been identified as requiring low embodied energy. Operation
Energy consumption has increased in the recent years as a result of fast urbanization,
continuous industrialization and improved living standards. Understanding the concept of
affordable construction is predicated on understanding of the terminologies: embodied
energy; life cycle energy; operating energy; affordable housing; and sustainability
(environmental and social). The terms are defined as follows:
a. Embodied energy: It has been defined as the sum of primary energy consumed in
constructing a building using construction materials, products and processes along with
related transportation, administration and services. Life cycle energy is the sum of
embodied energy, operational energy and decommission energy (Cabeza et al, 2013;
Dixit, 2017).
b. Operating energy: It is the energy expended in maintaining the inside environment
through process such as heating and cooling, lighting and operating appliances
(Cabeza et al, 2013).
c. Affordable housing: usually refers to housing for people whose income is not enough
to have access to appropriate houses at market value. It is important to include
economical sustainability factors in order for the low-income earner to afford the house
proposed. It therefore means considering the initial and future cost, transport cost and
energy bill (Gan et al, 2017).
Sustainability is generally elaborated as a development that satisfies the needs of the
current generation and not at the cost of compromising future generation (Aste et al,
2017; Gan et al, 2017).
d. Environmental sustainability considers energy efficiency, water efficiency, effective
utilization of resources, efficient water management, comfortable and healthy
environment, reduction of footprint to minimize the biodiversity loss, climate change
and mitigation of greenhouse gas emission. (Aste et al, 2017; Gan et al, 2017; Walsh
et al, 2017). Selection of a wall material that is environmentally sustainable and doesn’t
compromise the economic sustainability such as local earth material is best.
e. Social sustainability is another important factor in sustainability. It emphasizes the
equal distribution and consumption of housing resource with special attentions to
horizontal equity and vertical equity. Vertical equity refers to equal treatment of people
in unequal position, horizontal in equal treatment of people in equal positions (Aste et
al, 2017; Gan et al, 2017; Walsh et al, 2017).
Reduction of building energy consumption will require a radical change in building design
procedure. A well designed building can support the local based economy by using on site
material as well as local labour forces (Aste et al, 2017). Unfortunately, too, there is
14
infrastructure deficit in Nigeria. The infrastructure including energy is inadequate for the
growing population that live in the urban areas. Almost all Nigerian home has to provide
water (borehole unit), generate electricity and construct drainages around their compounds.
(Ugochukwu & Chioma, 2015) identified the following challenges encountered in the
delivery of affordable houses in Nigeria:
The Nigerian Government has gone through different phases since the independence of
the country in 1960. Although several of the administrations have committed to providing
housing for the general public, relatively small numbers of houses have been built
(Olayiwola et al, 2005) and are summarized below:
15
iv. Budget reduction and improper phasing of the infrastructure and housing
construction
v. A slow rate of construction
vi. Lack of material choice
vii. Inadequate building and construction technology
g. Democracy 1999 till 2005: The Government completed 500 housing units in Abuja.
In addition, partnered with private investor developers to provide 1,127 units in Abuja
and Port Harcourt. Furthermore, construction resumed at previously abandoned
sites in Lagos.
h. Current 2005-2019: the government established a mortgage payment that requires
30% of the cost as down payment for a 10-year load. The cost is not affordable for
most government workers (Wallace and Adeleke 2019).
Construction of high-rise building demand a huge capital, requires massive energy and
mechanical services, which increase the cost of running the building. Tall buildings
accommodate many people on a smaller area of land than low rise building for the same
number of units. High rise buildings create open land that can be used for communal
facilities such as libraries, sport areas and parks (Craighead, 2009).
There is shortfall in energy generation in Nigeria, hence the country is unable to meet the
energy needs of the urban cities. Although high rise buildings, could be the fastest route to
solving the housing deficit problem, they require more energy for mechanical services so
will not be of use here.
Table 2.3: Number of housing unit/ net hectare provided by different types of
houses.
16
Table 2.3 shows the number of houses in a single hectare depending on its vertical
measurement. Low rise can accommodate a smaller number of families which might not be
adequate for a dense urban city. The shortage of houses in Nigeria is about 16-17 million
units - providing low rise buildings will create a large urban spread, which would reduce the
natural vegetation and energy efficiency of the towns that is required for vertical
transportation in such buildings. Land is a scarce commodity in urban city, Arable land area
is constantly threatened by urban spread. Low rise housing does not ensure adequate
utilization of this resource for sustainable housing (Adabre et al, 2020).
From the foregoing, medium rise (3-6 storeys) buildings appear to solve the housing deficit
in the country as they accommodate more people, reduce the urban spread, and do not
require particularly high energy for vertical transport. The reason medium rise buildings up
to 4 floors are suitable to provide house in a dense city and to manage the scare land
available in the city.
The temperature and relative humidity of the space affects the level of comfort for the users.
To ensure the correct passive design strategy, weather data can be super imposed on a
bioclimatic chart showing passive strategy options (an example is shown in Figure 2.6).
The application of passive design strategies in finding solution to housing deficit and
provision of sustainable houses for the low-income mass of Nigeria population would
require knowledge of the geographical location, soil and climate of the country. Nigeria, a
17
West African country is on Latitude 4-13oN and Longitude 2-14oE. It covers 923000km2
land area. The topography is mostly flat in the south and some elevated areas and
mountains in the northern part of the country (World, 2020). The lowest elevation is 0m
near the Atlantic Ocean in the south and highest elevated area of 2419m at the north-
eastern part of the country.
The Köppen-Geiger classification system indicates four climates across Nigeria: tropical
savanna, monsoon, warm semi-arid and warm desert climate shown in Figure 2.5. The
map in Figure 2.5 shows about 75% of the country has Köppen-Geiger classification
tropical savannah climate (Aw).
The main group and corresponding subgroup in the country includes the tropical (Am and
Aw) and dry (BWh and BSh). The Köppen climate classification of Nigeria are explained
below.
a. Tropical climate:
18
▪ Monsoon climate (Am): This region has short dry season. The driest month has
less than 60mm rain, the average monthly maximum is 380mm and minimum is
20mm. The maximum temperature in this region is 28-33oC, minimum
temperature 18oC. The relative humidity of the area is 58-80%.
▪ Tropical savanna climate (Aw): the driest month experiences less than 60mm
rainfall, the rainy season starts around April to October. The mean temperature
28-32oC with its peak in February and March (Fasona et al, 2013). The relative
humidity is about 80-85%.
b. Dry climate:
▪ Warm desert climate (BWh): the climate experiences long hot summers, warm
transitional season and short , mild chilly winters with mean temperature of equal
or greater than 18oC (Wang et al, 2019), The relative humidity is about 15-65%.
▪ Warm semi- arid climate (BSh): most of the area experiences less than 500mm
rainfall annually(Engelbrecht & Engelbrecht, 2016), the maximum temperature
ranges from 30-36oC . The relative humidity is about 25-80% annually.
19
BWh
BS
h Am Aw
Figure 2.6. Nigeria max temperature for dry and rainy seasons climate data
(Am, Aw, BWh, BSh) superimposed on bioclimatic template (Givoni, 1992;
Roshan et al, 2019). NB: The comfort band is based on Givoni’s work which
applies to developed countries
The chart in Figure. 2.6 indicates the appropriate passive strategy for dry and rainy seasons
of each climate (based on mean data):
i. Monsoon climate (Am): the position of monsoon climate on figure 2.6 shows that the
passive design strategy required for this area is natural ventilation.
ii. Tropical savannah climate (Aw): the position on figure 2.6 shows that it requires
natural ventilation for its user to achieve thermal comfort wet season. The use of air
conditioning and conventional dehumidification is indicated for the other season, but
20
it should be noted that the comfort band on figure 2.6 is not based on an acclimatized
population. The comfort band is higher in this region.
iii. Warm desert climate (BWh): the design for thermal comfort to be achieve is shading,
thermal mass with night ventilation and evaporative cooling.
iv. Warm semi- arid climate (BSh): the design for thermal comfort to be achieved is
buildings with high thermal mass and evaporative cooling.
Most of the country falls in the tropical savannah climate (Aw) and monsoon climate (Am)
which require shading and natural ventilation. Natural ventilation is adequate when
maximum temperature is approximately 34 oC, average 32 oC, wind speed 1.5 m/s and
relative humidity between 30-90% (Khambadkone & Jain, 2017). Natural ventilation can be
accomplished by façade openings, solar chimney, wind catcher and atrium.
The northern part of the country warm desert climate (BWh) and warm semi-arid climate
(BSh) require shading and high thermal mass (in combination with night ventilation for the
warm desert climate area. Earth blocks can be used as a thermal mass material.
The comfort band based on the mean temperature for Nigeria with 80% comfort is
approximately 23-30 oC and for 90% 24-29 oC (Toe et al, 2010). Adaptable comfort level of
approximately 80% can be achieve at air speed 0.1-0.2 m/s. Air speed of about 1 m/s for
temperature above comfort limit of 30 oC can provide adaptable comfort level. ASHRAE
Standard 55-2013, comfort level can be expanded by 2-3 oC when air movement is 1-1.5
m/s for air temperature and relative humidity boundary is 90% (Khambadkone & Jain, 2017).
Clay is a widely available raw material, which can be used to produce bricks.
Characteristically, it is suitable for brick because it could be moulded and shaped, it has
21
enough tensile strength to keep its shape and it fuses together when exposed to adequate
temperature. Clay occurs in the forms of surface clay, shales and fireclays. Surface clay
are found close to the surface of the earth, shales are clays that have been subjected to
high pressure and have become hard and fireclays are found at deeper levels. The most
important characteristic is its ability to withstand high temperatures. Clay is a complex
material but mainly composes of silica and alumina with varying quantity of metallic oxides
and other ingredients. Clay can be divided into two main types. That is, calcareous clay
(has 15% calcium carbonate and burns to yellowish colour), and Non-Calcareous clay
(contains silicate of alumina, with feldspar and iron oxide 2-10%, with burning colour of red,
buff or salmon)(Lyons, 2014).
- Common bricks have acceptable strength, water absorption durability, thermal and
moisture movement. They are cheap to produce but have poor appearance.
- Facing bricks are more expensive, have better appearance and are better to use in
exposed area. They have similar performance to common bricks.
- Engineering bricks are stronger than common or facing brick. They have low moisture
absorption but are more expensive than common bricks. They are used where
enhanced strength and low porosity is needed (Lyons, 2014).
The manufacture of clay brick can be done through three stages: excavation and
preparation of the raw material; forming the shape required; and drying and firing. The
process is illustrated in Figure 2.7 and explained below:
i. Excavation of clay: Mined material is checked for impurities before use to determine
the active soluble salts content of masonry (Lyons, 2014). It quarried crushed,
screened to remove stone and other debris, mixed with water and then passed through
a pug mill to produce uniform clay of high plasticity (Charlett, 2013).
ii. Forming the shape: Shaping is made manually or by using machine. If done
manually, the lump of clay is put into wooden mould that have been lined with sand or
sawdust which have relatively irregular shaped and dimension. The machine or
alternative clay is formed through a die and cut and shape into dimensions needed by
stretched wires. Clay needed to be moderately stiff (Lyons, 2014).
iii. Drying and firing bricks: Firing temperature is usually around 900oC. The bricks are
dried prior firing otherwise they will crack when exposed to high temperature within the
kiln. Finally, bricks are cooled by incoming air needed for combustion. (Charlett, 2013;
Lyons, 2014).
iv. Manufacture of calcium silicate: It is manufactured with sand, flint mixed with quick
lime or hydrated lime and water in protein to proportion of 10 parts sand or flint to 1-
part quick lime or hydrated lime mixed with pressed steel in mould and then autoclaved
22
for 12h in steam oven mould at 170o C temperature and 10 atmospheric pressure. It
forms CO2 when exposed to air forming calcium carbonate which provides strength and
hardness. (Charlett, 2013; Lyons, 2014).
v. Manufacture concrete brick: It is manufactured from concrete having dense
aggregate to BS EN771-3:2011. Mixture is placed in steel mould and autoclave with
high pressure like calcium silicate bricks. (Charlett, 2013; Lyons, 2014).
The properties studied includes compressive strength, water absorption, durability, thermal
and moisture movement, thermal conductivity, sound insulation, fire resistance, density,
appearance and sustainability. These properties are factors that ensures adequate
structural safety, thermal comfort and, indoor air quality
Compressive strength.: ranges from 5-100 N/mm2 at firing temperature of 1100 oC for fired
clay bricks and calcium silicate bricks 5-75 N/2 (Bodian et al, 2018; Dai et al, 2019; Lyons,
2014; Phonphuak et al, 2019).
Water absorption is dependent on the type of brick and method of manufacture. Most
common fired clay bricks have absorption 7-26%, calcium silicate have 8-15% depending
on the size and distribution of the pore while water absorption for engineering bricks is 4.5%
and class b is 7% maximum (Baden-Powell, 2011; Charlett, 2013; Dai et al, 2019).
23
Durability is affected by the water absorption of the brick, but clay is mainly affected by
soluble salt, which could cause staining or efflorescent. Unburnt brick is less durable than
fired brick. Engineering clay bricks have the best durability. Calcium silicate and concrete
bricks are not affected by soluble salt like clay brick (Charlett, 2013).
Thermal and moisture movement: moisture movement is negligible in burnt bricks, but
thermal movement is 0.3mm/m. It is advisable therefore to incorporate 10mm expansion
joint protected by plastic sealant for every 12m wall not broken by door or window. Moisture
movement is higher in calcium silicate and concrete bricks, so it is recommended to have
10 mm expansion joint at every unbroken 7m wall.
Thermal conductivity of fired clay bricks depend on the density and position, but typically
ranges from 0.43 to 1.4 W/m.K and calcium silicate (0.6-1.3 W/m.K) with thickness of 100-
102.5 mm (Charlett, 2013; Engineering, 2002; Lyons, 2014).
Sound insulation: Most bricks have good sound reduction values ranging from 44 to 57dB
(Binici et al, 2009; Charlett, 2013; Hegger, 2006).
Fire resistance: The resistance of clay bricks has fired resistance up to 1-4 hrs. Calcium
silicate provides resistance up to 3 hrs. Concrete bricks have high resistance also (Charlett,
2013).
Density: The density of bricks varies from 1600 to 2100 kg/m3 (Ashby, 2013).
Appearance: Clay is usually faced with sand or colouring of natural pigment of clay.
Calcium silicate is usually off white or pale pink in colour, smooth finish but textured can be
available. Concrete has slightly rougher surface and can be available in smooth rustic or
weathered finish (Charlett, 2013; Hegger, 2006).
Sustainability: The recycle fraction in current supply 15-20% (Ashby, 2013). During the
production of clay bricks, the emission of carbon dioxide and other pollutant like sulphur
dioxide is emitted to the environment and embodied energy for bricks is approximately 200-
220 KgCO2/ tonne(SFGB, 2011; Torgal & Said, 2011). Well-constructed clay bricks have
long life span (50+ years) (Maia de Souza et al, 2016; Thomas & Ding, 2018; Udawattha &
Halwatura, 2017) and low maintenance. The use of Portland cement requires high level of
technology and skill for production.
In summary, brickwork has the advantage of being: locally sourced; able to withstand high
temperature in case of fire outbreaks; amenable to different product sizes and finishes, and
can be made for different uses (i.e. Engineering, decorative and regular use). However, it
has drawbacks because it requires more energy, high technology would require this
material high cost for production of low-cost housing with the material.
24
2.4.2. Blockwork
Blocks are made from either clay or concrete. Clay blocks are available in three width
variation of 62.5, 75 or 150 mm wide. The 62.5mm and 75mm thick blocks are used for
non-load bearing application (Charlett, 2013).
Concrete blocks are made from dense, lightweight or aerated concrete. Lightweight or
aerated concrete is used for internal leaves of cavity walls or internal partitions; it has good
thermal expansion, sound insulation as a result of the air voids within (Kalpana & Mohith,
2020). The size ranges from 370 to 590mm length, 140 to 290mm height and 60 to 250mm
thick. Concrete blocks are made from a mixture of Portland cement and aggregates. It can
be designed to be hollow, cellular, sound absorbing, insulating or solid blocks.
Manufacture of concrete block has mixture of cement, appropriate aggregate and water.
The mixture is put into a steel mould compacted by pressure or vibration, demoulded
immediately and left to cure either naturally or artificially. Aerated blocks are made from
sand, pulverised fuel ash, cement and aluminium powder. Like most concrete products,
concrete blocks shrink as they cure.
Compressive strength: The minimum compressive strength for clay block is 1.4 N/mm2
for non-load bearing and 2.8 N/mm2 for load bearing. The compressive strength for dense
concrete blocks over 75 mm thickness ranges from 2.8 to 35.0 N/mm 2 and light weight or
aerated 5.5-45N/mm2. (Charlett, 2013; Gyurkó et al, 2019)
Water absorption: Due to the pores, blocks have higher water absorption than bricks.
Dense concrete is better for below ground level since it has lower porosity than light-weight
blocks. Aerated concrete is more porous, and this should be considered when designing to
minimize the absorption rate (Charlett, 2013).
Durability: it has good resistance to freeze/ thaw condition beyond DPC level but
compressive strength lower than 7 N/mm2 should not beyond DPC( damp proof course )
level(Lyons, 2014).
25
Thermal and moisture movement: They are like brick but can be bad for aerated concrete
blocks if exposed to damping prior to laying which leads to cracking from drying shrinkage
(Charlett, 2013).
Fire resistance: Block is slightly less resistant to fire than clay brick. A 100mm block has
2 h resistance to its load bearing and 4h if it is non-load bearing (Charlett, 2013; Stowell,
2020).
Density: aerated blocks have density of 400-1500 kg/m3 and dense blocks are closer to
2050-2300 kg/m3 (Charlett, 2013; Lyons, 2014; Goodhew, 2016).
Appearance: Clay blocks have grooved surfaces to provide a surface for rendering. Dense
and high strength concrete tend to be slightly rough textured which makes it good for
application of finishes. Aerated blocks have smooth finish (Charlett, 2013).
Sustainability: the major environmental impacts of concrete blocks relates to the carbon
emissions of cement which is attributed with 5-7% of the total CO2 emitted worldwide and
embodied energy of the material is approximately 143-375 Kg CO2/ tonne (Alsubari et al,
2016; Liu et al, 2017; SFGB, 2011; Torgal & Said, 2011). However, the blocks often make
use of recycled aggregates such a fly ash and foamed granulated blast furnace slag. The
lightweight and aerated concrete blocks have reduced transportation energy in comparison
with dense blocks (Charlett, 2013).
26
i.)Cracking in concrete (Holland, ii) spalling in concrete
2011),
2.4.3. Earth
Earth is a widely available material; however, its composition varies depending on location.
About a third to a half of the world live in earth buildings. Most of such buildings are in
developing countries, but some are in France, Germany, and United Kingdom.
Earth construction is often assumed to be best suited to dry climates. However, long lasting
examples can be found in wet climates (e.g. cob houses in United Kingdom) as well as
West Africa where it has been used since 1500BC (Hall et al, 2012). Stone or concrete
foundations can prevent capillary rise of water, while good siting (not in a dip) and over-
hanging roofs can prevent the rain from touching the wall directly.
There are several methods of utilising earth as a building material. These include:
27
Wattle and Daub: Straw and earth are pressed in a relatively light woven lattice of wooden
strips, sometimes simple boughs, the lattice is connected to a stronger vertical or incline
wooden frame (Van Damme & Houben, 2017). The image shown in Fig 2.9 (I).
Cob: uses the same straw mix as for wattle and daub but without any support for formwork,
which allows a free shaped wall. The moist earth (cob) mixture is lightly tamped into place
to form monolithic walls (Hall et al, 2012). The image shown in Fig 2.9(ii).
Adobe brick: can be made from earth with a clay content between 10-30% and earth
containing 5-40% and no particles larger than 15mm. Straw is added to reduce shrinkage
with a small amount of water to make the earth workable. The blocks are pressed in a
mould, then removed and placed to dry for two weeks in a place protected from rain
(McHenry, 1984). Adobe is commonly used for single and two storey houses, but it has
been used for construction of 10-storey building (Pacheco-Torgal, 2015). Example in Fig
2.9 (iii).
Rammed earth: requires a formwork for the wall. Damp earth is poured into the form and
tamped to compact the earth (McHenry, 1984). Rammed earth is better for lower clay
levels than adobe blocks (higher clay levels increase likelihood of cracking during drying)
and coarse particles can be included (Van Damme & Houben, 2017). Stabilizing agents
such as Portland cement may be added to provide moisture proofing or additional strengths
quality (McHenry, 1984). The formwork can be removed before the wall has fully dried (Hall
et al, 2012). Rammed earth is more appropriate for humid climates than adobe (McHenry,
1984). Example in Fig 2.9 (iv).
Earth loaves: freshly hand formed earth loaves are laid like the brick construction, but only
four courses are completed in a day. Stick reinforcements are introduced at every third
course. After it is dried for 6 weeks the earth is strong enough to support the roof. This
technique can be used for internal and external walls with load and non-loadbearing function
(Berge, 2000). This technique was further developed in Germany to become the Earth
Strand which was more suitable to the locally available earth. A brick extruding machine
was used to compress and extrude a tube of 8-16cm in diameter (Berge, 2000).
Earth filled hoses are suitable for clay free earth – even for pure sand with no binding
properties. The filled sacks are piled up within a light timber framework (Berge, 2000).
Compressed Earth Blocks (CEBs): The use of compacted stabilized blocks was seen
after the 1940s. Paul Ramirez developed the CINVA-RAM press in 1952. Social houses
were built with stabilized blocks of up to 3 storeys (Hall et al, 2012). Further details will be
presented in Section 2.3.
28
-
iii) Adobe- Santa Fe - Adobe Building is iv) Rammed Earth- Materials: Rammed
a photograph by Frank Romeo Earth, Paul Downton 2013
Figure 2.9. Traditional earth building techniques
Thermal and moisture movement: the movement of rain on wall surface doesn’t have
erosive effect above 25mm/m (Torgal & Said, 2011).
Thermal conductivity: dry earth has a thermal conductivity of 1.5 W /m. K, like dense brick
and dense concrete. The thermal performance of earth can be improved by adding fibres
(Berge, 2000; Engineering Toolbox, 2002).
Sound insulation: the sound insulation of earth structure is 51 to 53dB (Binici et al, 2009).
Fire resistance: earth structures are considered fireproof (Hall et al, 2012)
Density: dry density ranges from 1450-2400 (Steve, 2016; Torgal & Said, 2011)
29
Appearance: the appearance varies from rough surface to smooth clean surface based on
the images in Figure 2.9
Sustainability: earth is a low pollution material. When the building is no longer required, it
can be reverted to earth (unless it has been stabilised). The replacement of concrete
blocks by 5% with earth blocks will reduce the CO2 emission by approximately 10000
tonnes. The embodied energy for this material is about 22 Kg CO2/ tonne (Torgal & Said,
2011).
There is little documentation of methods for formal earth building construction and structural
performance in construction codes is scanty. The use of earth for construction depends on
constraints of mining, resource delivery and processing, access to labour force, quality
control and approve building plans. However, it helps with local job creation and economic
growth as well as low production and maintenance costs (Krosnowski, 2011). The material
required for earth construction is locally available but the skills for construction have not
been passed to the new generation as the material has been ignored for modern material
as a result of social stigma attached to earth buildings as it is often used by the poorest in
the community.
2.4.4. Stonework
Stone is one of the oldest building materials known to man, it was a dominant building
material until the 20th century and is preferred for construction of permanent buildings.
The extraction of stone is more labour intensive, which could not compete with the growing
industrialization of construction despite having a lower energy consumption compared to
bricks and concrete.
The process of removing stone from earth is known as quarrying; drilling and splitting the
stone can remove it. The method varies depending on the thickness of the stone. Holes
can be drilled on the face at right angles, wedges are driving to the holes in order to divide
the rock, the rocks are large and can be divided into pieces and shape required, the stone
can be finished with planar finish, carbon finish, rubbed finish and different machine finishes.
The building industry today uses stone to face building with exterior made of steel or
concrete frames (Hegger, 2006; Lyons, 2014).
Rock can be classified into igneous (e.g. granite) sedimentary (e.g. limestone / travertine,
sandstone) or metamorphic (e.g. marble, slate, serpentine). Stones used for construction
can be classified into commercial forms, which are rubble (fieldstone), dimension (cut
stone), flagstone (flat slabs), and crushed stone. Rubble stone are used the way it is found
in the field, dimension stones are cut to suitable sizes, flag stones are cut to 12.7mm and
up and crushed stone are cut in sizes varying from 9.5 to 152mm. Crushed stone is
30
commonly used for aggregate in concrete or levelling for loose foundation(Richardson,
2001).
Compressive strength: varies depending on stone type. E.g. Sandstone and limestone
2.1 N/ mm2, slate 3.5 N /mm2, granite 4.8 N /mm2 (Engineering Toolbox, 2008)
Thermal and moisture movement: the thermal expansion oranges from 0.0032-0.044%
(Hackman & Kessler, 1950)
Appearance: colour, grain, porosity and texture are important to the appearance and vary
between stone types
Sustainability: The recycling fraction in the current supply is 1-2% (Ashby, 2013). The
embodied energy for stonework is 64-84 Kg CO2 /tonne (SFGB, 2011). Stonework material
is available in Nigeria but requires high energy for extraction and processing for construction
use; these factors increases the cost of houses and reduces the potential for the purpose
of affordable houses in the country.
2.4.5. Summary
The review on conventional material used for wall construction in Nigeria on requirement all
of the materials described above can be considered (assuming earth materials are
stabilized). With this basic requirement met, the decision on material choice is based on
appearance, material availability and cost implications for the resulting building
construction. The summary of the materials characteristics of wall material characteristics
is shown in Table 2.4
The use of stonework, brickwork, blockwork require significant energy for production, the
amount available in the country is inadequate. For these reasons, stabilised CEBs have
been chosen as the most suitable wall material for affordable and sustainable residential
building.
31
Table 2.4: Comparing compressed earth blocks with other masonry
Reversible thermal
dilation % 0.02-0.2 0-0.02 - 0.02-0.05
Density
Kg/m3 1700-2200 1400-2400 1200-1700 1700-
Durability 2200
- Low to very Low- Poor
good excellent Low-very
good
Use in masonry Load Load bearing Load bearing Good infill
bearing without render with render with
without render
render
©(Rigassi & CRATerre-EAG., 1985; Vincent Rigassi & CRATerre-EAG., 1985)
32
furnace slag or other pozzolans are used either alone or in association with other elements
(Van Damme & Houben, 2017).
Curing is an important aspect of stabilization process. Clay soil are less reactive at elevated
temperature and the kinetics of their pozzolanic reaction is slow which is the reason it is
cured under a plastic cover or by sprinkling with water regularly before drying and using in
construction (Van Damme & Houben, 2017). There is no restriction as to the season when
CEB can be produced if measures are taken during wet and hot seasons to protect the
blocks when stored.
Materials used for stabilizing CEB are used to reduce the rate of shrinkage when exposed
to water or atmospheric moisture and loss of strength. Over time the development of
Cement and Lime industry had caused replacement of the use of local stabilizers with
cement and lime (Van Damme & Houben, 2017). However, the new method had led to
other problems in the environment in terms of the cost, reuse of the material and the
pollution caused by the cement industry. The challenges have led to a development of
alternative materials that can combat the problems caused by the cement industry without
compromising the integrity of the CEB materials. The cost of CEB is about 32% less than
Sandcrete block that are commonly used in Nigeria; and that satisfactory results were
obtained with CEB having 5-10% cement or lime for stabilization (Egenti et al, 2014).
The use of cheap natural pozzolans has been considered for the stabilization of building
materials in order to reduce construction cost. In that regard, waste materials from the glass
industry, rubber industry, and agricultural industry have been used. Also, chemicals such
as geopolymer was used to develop the calcium silicate hydrate (C-S-H) to provide the
binding properties that cement has over other binding agents.
Typically, CEBs requires about 5-10% dry weight- based binder added to the mix,
compressive strength of 3-4 N/mm2 (Mostafa & Uddin, 2016a). It can be used for walls up
to 3 floors and higher potential to 5 floors (Hjort & Widén, 2015). Furthermore, CEB has
the following advantages:
▪ The mechanical presses used to produce CEBs ensures it has an improved property
over other earth blocks (adobe) which ensures its social acceptance.
▪ Its quality meets the requirement of other building products standards used in urban
society
▪ In places where construction industry relies on small masonry (fired clay bricks,
concrete blocks). CEBs is a good alternative serves as a socio-economic
development of the building sector
▪ Policy makers find the use of CEBs acceptable in the rural and urban context
33
▪ Builders appreciate using the presses to ensure regular shape and sharp edges
which ensures high density when compacted and improves the compressive
strength as well as resistance to erosion
▪ It is flexible for use for different size of project
▪ It has similar property (water absorption, compressive strength, sound insulation,
fire insulation and thermal insulation) with fired clay bricks
▪ It can be locally produced
The stages of producing CEBs are listed in Table 2.5.
It has been reported that the best results for CEB production was obtained with sandy soil.
Meanwhile, the presence of iron oxides in lateritic soil allowed for efficient stabilization.
34
Also, soil must be free of organic matter before use for CEB production. Water with salt
and in particular sulphate should be avoided to achieve the best CEB (Rigassi & CRATerre-
EAG., 1985)
Table 2.6 shows the different presses that are available to produce CEB. It also highlights
the average blocks that can be produced and the cost of production.
Table 2.6: Types of presses used for Compressed earth blocks (CEBs)
production
2.6. Stabilizers
Stabilization has been defined as the controlled modification of texture, structure and/or
physio-mechanical properties of the soil. It can be in the form of physical, mechanical or
chemical modification, and its main objectives are listed below:
- Mechanical stabilization: its inexpensive, it involves the mixture of two or more soil
types to get the required grade (sand and gravel). Adding sand or gravel to the mixture
can improve soil with high content of clay. Densification of soil through compaction
(Hall et al, 2012; Pacheco-Torgal, 2015)
- Stabilization by compaction: loose soil is compacted to be denser. It imposes
strength, reduces porosity, etc. - modifies physical soil texture by firing, freezing or
electro-osmosis (Hall et al, 2012; Pacheco-Torgal, 2015).
- Stabilization by additives: Modifies soil through mixing with chemical additives such
as lime, cement (4-10%) (Hall et al, 2012; Pacheco-Torgal, 2015). It helps control
excessive shrinkage that causes cracks in blocks. Ordinary Portland cement is the
most used stabilizer. Its content ranges from 5-10%. The formation of CSH gel in the
mixture of soil, cement and water establishes insoluble bonds and binds the sand and
the silt particles.
However, demerits of stabilizers are listed below:
Generally amorphous silica reacts with calcium hydroxide much more rapidly than silica in
crystalized form. Also, fine pozzolanic particles with higher surface areas reacts much more
rapidly than larger particles.
36
Natural pozzolans may be classified into two principal classes. First, those derived from
volcanic rocks in which the amorphous content is produced by glass fusion and second,
those derived from rocks or earth from which the silica constituents contain opal, either from
precipitation of silica or from the remains of organisms.
Some agricultural wastes have pozzolanic properties, i.e. they have little or no cementitious
value but react with calcium hydroxide in presence of moisture to form compounds with
cementitious properties. Such materials can be substituted for a proportion of Portland
cement.
Pozzolans are a variety of materials or classes of materials, which may differ from one
another in both their chemical and physical composition and their effect on the properties
of mortars and concrete. There are three classification of pozzolans ASTM C618-19
includes class N, F and C. Class N is naturally occurring from diatomaceous earth, volcanic
ashes, class F is the fly ash gotten from burning bituminous coal and class C is fly ash that
is produced from burning lignite coal. The minimum percentage of SiO2, AL2O3 and Fe2O3
for class N. F AND C is 70,70 and 50 respectively. Agricultural pozzolan falls under the
classification N.
Fineness and grain size of materials are determined using Automatic Blaine Machine and
Malvern Matersizer, respectively. The amorphous or crystalize phase of material are
determined with X- RAY diffraction. Chemical composition is determined by X RAY
Fluorescence (XRF) test. The morphological view and shape of the particles of the material
are examined using Scanning Electron Microscopy (SEM) analysis (Bahurudeen &
Santhanam, 2015; Cordeiro et al, 2009a; Sore et al, 2016; Sturm et al, 2016).
The loss of ignition is also another important test used in inorganic analytical chemistry,
particularly in the analysis of materials. It involves heating a material, allowing the volatile
substance to escape until its mass stops to change. This is helpful because the
replacement of pozzolans is specified or calculated with the volume of the material to
replace Portland cement in the mix.
The fineness modulus is an empirical factor obtained by adding the cumulative percentage
of aggregate retained on each of the standard sieves. It is generally used to determine how
coarse or fine the aggregate is, and it affects the water- cement ratio, workability, shrinkage
and creep of concrete (Aprianti et al, 2015). Creep and shrinkage occur in concrete when
concrete is loaded, the structure undergoes elastic and inelastic deformation. Aggregate
play an important role. The water demand and workability are affected by the particle size
distribution, particle packing effect and voids present in the solid system.
Rice husk ash, Sugar Bagasse Ash, and Palm Oil Fuel Ash; like other sustainable
pozzolans could serve useful application here. The binding and stabilizing strengths of the
37
three agricultural waste materials in the production of concrete, building blocks, and mortar
will depend on the geo-chemical composition of the aggregates used. The geo-chemical
composition of the aggregates will vary per the nature and mineral composition of the
originating rock.
Furthermore, successful replacement of cement with RHA, SBA, and POFA will provide a
solution to management of agricultural waste, environmental pollution and financial
sustainability (Aprianti et al, 2015; Chong et al, 2015).
The pozzolanic properties of Rice Husk Ash (RHA), Sugar Bagasse Ash (SBA), and Palm
Oil Fuel Ash (POFA) are studied in detail in sections 2.6.2 – 2.6.4. The information will
facilitate more understanding of the binding qualities and their use in the construction
industry.
Rice husk ash, sugar bagasse ash and palm oil fuel ash have high silica content in
amorphous form, which makes it useful as pozzolans. The following agricultural wastes are
studied because they are common crops grown in Nigeria.
The cost and environmental hazards of cement production have been described earlier.
Sourcing acceptable alternative low cost and environmentally friendly binding agent will
significantly reduce cost of providing housing and the cost environmental pollution
management.
The chemical activity of amorphous silica in RHA to produce the required filling effect in
structures to increase compressive strength and reduce water permeability is dependent
on the surface area of RHA (Givi et al, 2010). Also the fineness of the RHA influences the
rate of reaction, increase in concrete strength, water-cement ratio, workability, shrinkage
and creep of concrete (Aprianti et al, 2015). The RHA particle ranges from 5 to 10μm with
a very high surface area of more than 250 m2/g due to the porous nature of RHA (Aprianti
et al, 2015; Van Tuan et al, 2011). RHA has 2.11 specific gravity, and a modulus of rupture
ranging from 0.67-1.49 MPa (Kazmi et al, 2016a). Its colour ranges from whitish grey to
black depending on the source of the raw material, method of incineration, and time and
burning temperature (Aprianti et al, 2015). The amount of silicon dioxide (SiO2), iron oxide
(Fe2 O3), aluminium oxide (Al 2O3) in the ash should be greater than 70%, and the Loss of
Ignition (LOI) should not be less than 12%, as mentioned in ASTM C618 requirement
(Aprianti et al, 2015). Variations in the chemical composition of RHA in different countries
are shown in Table 2.7.
39
2.6.2.3. Rice Husk Ash as Pozzolan
Cook (1986) reported that highly reactive pozzolans such as rice husk ash can reduce the
size of voids in hydrated cement paste, thus making them almost impenetrable to water and
chloride ions even at early days of curing (Cook, 1986).
The silica in RHA reacts with Ca (OH)2 produced from cement in the presence of water as
shown below to produce Calcium-Silicate-Hydrate (C-S-H) gel
2.6.2.4 Effect of RHA on mechanical properties of concrete and fired clay bricks
There is a little of literature reporting the effect of RHA on OPC replacement of CEBs. The
literature documenting the effect of RHA on OPC replacement in concrete and fired bricks
was analysed as an indicator of potential effects.
The standard compressive strength of concrete combined with or without RHA, is within
range for conventional concrete (15-45 MPa) with a density of about 2400 kg/m3. (Aprianti
et al, 2015) showed the possibility of increasing compressive strength after curing concrete
for 7days and 28 days to approximately 55MPa and 72MPa, respectively.
The presence of 30%RHA in concrete mix has been noticed to improve concrete’s
mechanical and durability properties by producing C-S-H gel that filled the large and
continuous pores within the concrete. It increased compression strength, improved the
microstructure of the paste making it more homogenous and denser, and finally enhanced
its resistance to water and chloride penetration to prevent the possibility of corrosion
(Ganesan et al, 2008; Givi et al, 2010).
By replacing OPC by 10% with RHA, the compressive strength increased from the control,
but it starts to decrease at 20% and 30% by 7.89% and 26.32%. The concrete was grade
range of M25 and M35 ((Takhelmayan et al, 2014; Rama et al, 2015). Another group of
researchers observed that at 15% replacement the compressive strength was maximum
(Ganesan et al, 2008; Salas et al, 2009). (Tsado et al, 2014) produced concrete of grade
M25-M35 by replacing OPC with RHA, the compressive strength decreased from control at
33.62MPa to 30.58, 26.51, and 17.68MPa when replaced with RHA at 10, 20 and 30%,
respectively. Rao et al. (2014) achieved grade M30 by replacing OPC with RHA at 5-12.5%.
(Rama et al, 2015; Ramezanianpour et al, 2009) replaced 5-20% and 7-15% OPC,
respectively with RHA to make concrete grade of M45 and M40. Keertana and Gobhiga
40
(2016) replaced OPC with RHA at 5-10% to make concrete of grade M35-M40. Givi et al
(2010) carried out similar test and noticed an increase in compressive strength. 10%
replacement of volume of OPC for 95μm and 5μm particle sizes of RHA to retain and
improve its properties (Givi et al, 2010). (Raut et al, 2013) produced nearly 50% higher
compressive strength in bricks of about 11-15 MPa, which is 3 times greater than the normal
3MPa. In another study, replacement of OPC in mortar cubes production up to 15% with
RHA resulted in optimal compressive strength. Replacement between 30 and 35% caused
a sharp drop in cubes’ strength (Ganesan et al, 2008). The tensile strength of concrete was
optimum when 30% volume of OPC was replaced with RHA (Ganesan et al, 2008). The
bulk density and compressive strength of brick is maximum at 1.68 g/cm3 and 6.20MPa,
respectively when RHA replaced 2% of the volume of OPC in brick production and when
RHA replacement was 15.20% of the volume of OPC, water absorption reduction was at
the maximum (Kaewkhao et al, 2012). Similarly when 0-20% volume of OPC was gradually
replaced with RHA and water treatment sludge (WTS) there was a decreased in the bulk
density from 2.4 to 1.6g/cm3 with relatively high compressive strength (Chiang et al, 2009).
Finally, Mehta et al (2013) replaced 7.5-22.5% volume of OPC gradually with RHA and Fly
Ash in concrete mix and observed that, the maximum split tensile strength was taken at
28% was less than the control concrete, the maximum flexural strength was achieve, the
workability of concrete was found to decrease with increase in RHA in concrete (Givi et al,
2010; Mehta et al, 2013).
In summary, up to 10% replacement of OPC with RHA was generally found to be acceptable
for concrete, although larger replacements of OPC with RHA were found to adversely affect
compressive strength.
The presence of chloride ions in concrete results in corrosion; however, the inclusion of 7-
25% RHA to replace OPC reduced the permeability of the blocks significantly ( (Givi et al,
2010; Ramezanianpour et al, 2009; Saraswathy & and Ha-Won, 2007). Also, 10-15% RHA
replacement reduced sulphate attack on the concrete (Rama et al, 2015; Takhelmayan et
al, 2014).
41
Freeze and thaw resistance, water inside solid state expands by approximately 9% during
this period (ASTM C67), specimen can be considered unacceptable if it cracks during freeze
and thaw cycles or weight loss increases by 3%, by incorperating RHA the weight loss
during the process was less than 3% which helps improves aesthetic appearance (Kazmi
et al, 2016b).
RHA replacement of OPC at all levels was considered to reduce porosity and thereby
permeability and water absorption.
Table 2.8: Chemical and physical properties of sugar bagasse ash (SBA)
Chemical Composition (% by
mass):
Physical Properties:
SBA is considered as non-plastic (not clay like) and non-cohesive material. The weight per
unit area when replacing clay with SBA and RHA in the manufacture of bricks is 15% and
4% lighter, respectively. These phenomena affected the weight of bricks produced with SBA
and RHA such that their densities 258.6kg/m3 and 550.54 kg/m3, respectively and were
43
lighter compared to clay with 1120kg /m3. Therefore, inclusions of SBA and RHA resulted
in the reduction of transportation and labour costs (transportation are priced by the weight
of the material and labour is reduced by allowing the workers to move a larger volume of
material faster) while at the same time reduction in structural load and flexibility to
architectural design (Kazmi et al, 2016b).
Initial rate of absorption can be defined as the absorbed water over the brick bed area of
19354.8 30 sq.mm for one minute. It has been noted that the initial rate of absorption for
bricks with RHA and SBA are higher compared to that of controlled bricks (bricks with no
substitution with pozzolan). The rate of absorption was 0.78g/cm2/min when 15% SBA was
incorporated while clay absorbed at the rate of 0.46g/cm2 /min. The limit should lie between
0.025 and 0.15g/cm2/min; which means bricks should be wetted before laying to ensure
efficient bond between bricks and mortar (Bahurudeen et al, 2014).
The compressive strength of brick dropped from 8.38 to 5.10 MPa with the incorporation of
SBA and RHA. Although there was increase in porosity, strength (5MPa) met the minimum
standard. Modulus of rupture is the maximum bending strength before failure of a structural
element. The modulus of rupture reduced from 1.49 to 0.72 but still within the minimum
standard (0.65 MPa) stipulated in the ASTM C67 guidelines. The water absorption of bricks
with SBA was 21% which is according to ASTM C62 for bricks in moderate weather (Kazmi
et al, 2016a).
44
The reduction in particle size with increase in grinding time is accompanied by an increase
in pozzolanic activity index with lime and is also responsible for microdefects and
electrostatic charges on the particles increasing their surface energy. Increase in
compressive strength can also be as a result of the packing density with is linked to the filler
effects of the ultrafine particles of SBA (Cordeiro et al, 2008).
SBA was successfully used as SCM in the production of concrete and bricks by
(Bahurudeen et al, 2014). Concrete with SBA replacement show equal or marginally better
strength performance even as early as 3 days and the replacement up to 25% replacement
can be used (Bahurudeen et al, 2015).
2.6.3.3 Effect of SBA on mechanical properties of concrete and fired clay bricks
As with RHA, there is a lack of literature reporting the effect of SBA on OPC replacement
of CEBs. The literature documenting the effect of SBA on OPC replacement in concrete
and fired bricks was analysed as an indicator of potential effects. The compressive strength
of concrete increased with the partial replacement of OPC with 10-30%SBA where 20%
replacement produced concrete of grade M25-M30. Also, some researchers (Malhotra &
Mehta, 1996)produced grade M25-M30 concrete and noticed higher compressive strength
with 5-15% but observed a decline with further increase in replacement of OPC. They
recorded the lowest strength at 30% replacement. In making M40 concrete, (Amin, 2011)
observed that replacement of OPC with 5-20%SBA resulted in compressive strength higher
than the control but the highest strength was attained at 10% and the least at 30%. The
compressive strength of concrete with 5% each of SBA and RHA replacement showed 7.18
and 6.62 MPa, respectively. The concrete still attained the minimum strength for building
brick of 3.5 MPa. 5% replacement of clay by SBA led to approximately 14% decrease in
compressive strength. The reduction of compressive strength is approximately 50% in 10%
and 15% replacement of aggregate (clay) (Kazmi et al, 2016a).
The split tensile strength was higher than the control concrete when partially replaced with
10-30% SBA, while the highest strength was at 20%, (Subramaniyan & and Sivaraja, 2016).
Similarly, (Ganesan et al, 2007) noted that 15% produced the highest strength while the
split strength at 5-15% was approximately 4.5-5 MPa. The splitting tensile strength values
at 28 days containing SBA up to 20% increased to 4.81 MPa and at 25-30% of SBA the
value decreased to 3MPa (Aprianti et al, 2015).
According to ASTM C67, the minimum permissible limit of rupture is 0.67 MPa, brick with
SBA inclusion had a modulus of rupture ranging from 0.67 to 1.49 MPa. It therefore implied
that the usage would help produce efficiently mass scale production, leading to economical
gain and sustainable construction.
45
2.6.3.4 Effect of SBA on hygrothermal properties of concrete and fired clay bricks
SBA inclusion remarkably affected water absorption coefficient where 5-20% caused
reduction while it was the reverse at 30% replacement (Ganesan et al, 2007). Permeability
of chloride ion reduced as OPC was replaced with 10-40%SBA, it was lowest at 20%-25%
after curing for 28 days (Amin, 2011; Ganesan et al, 2007; Subramaniyan & and Sivaraja,
2016). The sorptivity of concrete was tested when OPC was partially replace with SBA at
10-40%, it was lower than that of control and lowest at 10% and 15% (Ganesan et al, 2007;
Subramaniyan & and Sivaraja, 2016).
(Almeida et al, 2015) suggested that the substitution of natural sand with SBA up to 30%
could lead to improvement of maintenance properties, micropore clogging and durability of
the mortar in comparison with control mix. The workers added the increased chloride
penetration resistance could be as a result of the physical and chemical effects of SBA.
The durability and porosity of bricks, which can affect the mechanical property, was
improved with inclusion of SBA (Almeida et al, 2015; Fairbairn et al, 2010). It can therefore
be best utilized in places where insulation and heat transfer resistance are required.
Water absorption also affects the durability of bricks, in corperating SBA showed that the
rate of absorption was less than 21%, according to ASTM C62, water absorption should
not be more than 17% for severe weather resistance and 22% for moderate weather
resistance which means it can be used in places with moderate weather condition i.e.
Nigeria. (Kazmi et al, 2016b). It was also observed by increasing temperature of firing of
fired clay bricks from 900 to 1000 o C, absorption reduces from 40% to 2%.
Sulphate attacks reduces the compressive strength, incorperating SBA improves resistance
against sulphate attack by 5% (Kazmi et al, 2016b).
46
the residue would lead to 5% ash by weight of solid waste. The availability of palm oil fuel
ash is located 6 states that are in tropical savannah climate, and monsoon climate. There
are three state that have palm oil in the tropical savannah climate which includes Enugu,
Ogun and Oyo. The monsoon climate state includes Imo, Cross-river and Rivers state.
Tangchrapat et al. (2009) defined palm oil fuel ash (POFA) as an agricultural waste formed
when palm oil residue is burnt at 800-1000oC to produce steam for electricity in biomass
thermal power (Alsubari et al, 2016; Tangchirapat et al, 2009).
The specific gravity of ordinary POFA ranges from 1.89 -2.43 and that of ground POFA
ranges from 2.05 to 2.78 (Antiohos et al, 2014). Sata et al 2004 and Tangchirapat et al
2009 found that by grinding process, the pozzolanic reactivity of POFA increased in
response to the increased fineness of POFA. Based on ASTM C618 the strength activity
index which is an indirect method of measuring pozzolanic activity specifies the minimum
strength index for fly ash as 75% (Khankhaje et al, 2016). Unground POFA have shown to
have larger size, which makes its highly porous compared to ground POFA. Fly ash
concrete requires less water compared to POFA concrete to achieve the required slump
because of its spherical shaped particles and the solid texture of fly ash. Increasing water
in the mix lowers the pH value of concrete and increases the distance between cement
hydration products resulting in delay or decrease in the hydration activities of the cement
particle. It also decreases the setting time as the fineness increased (Khankhaje et al,
2016).
Fire resistance is an important issue in buildings; in concrete, it must preserve its structural
actions for prescribed timespan. The mass loss of concrete containing 20% POFA was
lower than control concrete under fire test conditions (Khankhaje et al, 2016).
47
shows that POFA is slow at the early stage and increased at a later stage. The reaction
also confirmed that faster reaction of finer particles. The median size particles (10μm)
utilized in high strength concrete had compressive strength ranging 60-66 MPa with 20%
replacement of OPC at 28 days with total binder 550-560 kg/m3. The increase in fineness
will reduce the expansion and loss in the compressive strength of concrete(Jaturapitakkul
et al, 2011).
POFA chemical and physical properties are similar to fly ash, which attracted its use as
cement substitute in concrete (Khankhaje et al, 2016).
Particles containing 10μm POFA showed a reduced expansion compared to control mix
and mortar containing 45μm POFA, this is because 10μm hasten the pozzolanic reactivity
forms secondary C-S-H gel in a short time. It can also serve as a favourable pozzolan
replacing part of Portland cement in producing mortar that exhibits a low carbonation depth
and a high strength (Khankhaje et al, 2016).
Replacing up to 30% of OPC with POFA performed adequately but higher proportions
caused significant reduction of compressive strength (Aprianti et al, 2015).
(Khankhaje et al, 2016) observed that compressive strength of concrete that contains 20%
ground POFA was like OPC concrete. However, increasing the ground POFA content
lowered compressive strength because of high water demand. Sumadi and Hussin (1995)
reported that inclusion of 20% ground POFA produced durable concrete that was like OPC
concrete.
Abdullah et al (2006) suggested that replacing 10-35% of cement with POFA is likely
producing aerated concrete. Hussin and Abdullah (2009) demonstrated that 30% of OPC
replacement with POFA was able to produce an aerated concrete panel exhibiting strength
equivalent to that of an aerated concrete with 100% cement (Khankhaje et al, 2016).
(Jaturapitakkul et al, 2011) investigated the use of POFA to replace 10-40% cement and
noted the compressive strength of mortar varied from 0.1MPa to 4.5 MPa at 7 days and 2.5
MPa to 22.5 MPa at 90 days. Also, concrete samples with 20% and 30% POFA showed
compressive strength of 59 and 60 MPa, respectively. (Jaturapitakkul et al, 2011).
48
2.6.3.4 Effect of POFA on hygrothermal properties of concrete and fired clay bricks
The incorporation of POFA improves mortar’s resistance to chloride penetration. This is
because of pozzolanic reactivity, the reduced Ca(OH)2 and the improved permeability of the
mortar. These researches (Khalid et al, 2016) observed that the higher the fineness levels
of POFA, the faster the pozzolanic reaction for formation of extra C-S-H gel thus creating
denser concrete and enabling it to exhibit better resistance to chloride attack and the longer
the curing days (Khankhaje et al, 2016).
It could also be another way to make use of RHA, SBA and POFA because the alkali silicate
geo-polymer manufacture could be made from the agricultural wastes (Ariffin et al. 2011).
The mixture of pulverised fuel ash (PFA) and POFA completely replaced the combination
of sodium silicate and sodium hydroxide solution in the manufacture of geo-polymer
concrete. A ratio of 70:30 PFA: POFA achieved the highest compressive strength of
25MPa. The compressive strength also increased with the longer the curing time
(Khankhaje et al, 2016)
Karim et al (2013) made a non-cement composite binder (NCB) using slag from cement
manufacture, POFA, and RHA with NAOH as the activator. The combination of 42% slag,
28% POFA and 30% RHA with 5% NaOH at 28days achieved the highest compressive
strength of 40.68 MPa and flexural strength of 6.57 MPa. (Khankhaje et al, 2016)
Geo-polymer concrete showed better structural stability than OPC concrete after exposure
to 800oC. Surface cracks appeared at temperature between 600 and 800oC for geo-
49
polymer concrete whereas it was noticed in OPC concrete at a temperature of 200 oC
(Khankhaje et al, 2016).
Tensile strength
The selected pozzolan is RHA as it’s the most widely available in the location the material
is required and has good properties based on the pozzolans available in the country.
In the tropical climate, building materials used for external purpose are subjected to
extremely high temperature, high relative humidity and heavy rainfall. Materials used under
such conditions will change in mass if they allow moisture into their membranes. The
phenomenon had been the reason for testing the water absorption coefficient of
compressed earth blocks. Additionally, it helps to understand how the blocks will perform.
51
Water absorption coefficient required for CEBs unit is discussed in section 6.2.2.1 and
moisture absorption is discussed in section 6.2.2.3
Water vapor transmission required masonry unit such as CEBs in section 6.2.2.2
Moisture buffering performance is the ability of the space to regulate relative humidity level
daily or seasonally. The moisture buffering value is the amount of water that is transported
in and out of a material per open space during a certain period when it’s subjected to
variation in R.H of the surrounding air. The effect of moisture buffering on the compressed
52
earth blocks stabilized with ordinary Portland cement and rice husk ash was explored by
subjecting the samples in a cyclic variation of low (33%) and high (75%) relative humidity
variation (Adam & Jones, 1995). The objective was to determine the moisture buffering
value of both fully and partially stabilized with ordinary Portland cement compressed earth
blocks according to NORDTEST method (BYG DTU R-126, 2005). Before the test was
initiated the samples were conditioned at 23±5oC and R.H pf 50±5% for a period of 2 weeks
till constant mass was reached. Samples were exposed to R.H of 75% and 33% for a period
pf 8hr/16hr interval. Temperature was controlled at 23±5oC throughout the cycle. Five
humidity cycles were then performed which was enough to attain steady state conditions.
Steady state is reached when mass change of three consecutive cycle at moisture uptake
at 75% and moisture released at 33% R.H must not vary more than 5% (BYG DTU R-126,
2005). Moisture buffering value for construction material can be classified as negligible,
limited, moderate, good or excellent as indicated in Figure 2.11. Moisture buffering
requirement based on literature review in discussed in section 6.2.2.4
53
sustainable thermal comfort building the thermal performance criteria has increased from
the norm where high heating and cooling services are required to achieve comfort for users
(Ashour et al. 2015).
Thermal conductivity required for masonry unit such as CEBs is discussed in section
6.2.2.5.
There is a high risk of mould growth on the external fabric of a building when the relative
humidity is above 70% for a long period of time, the risk can be reduced by increasing
temperature, or decreasing vapour pressure or a combination of the two factors. Moisture
can also be introduced into the building structure from sources such as follows.
a. Water used in construction: masonry structure, concrete, plastering of the walls etc.
b. Ground water seeping in from walls and floors in contact with the ground.
c. Flooding:
d. Precipitation: Rain fall been a major factor in the southern part of Nigeria.
e. Spillage or leaks
54
f. Airborne moisture, continuous high relative humidity
g. Building use: areas such as kitchen and bathrooms has more moisture in the internal
spaces than areas used for living rooms or sleeping areas (WHO 2009). Data related
to this is presented in Tables 2.10 and 2.11.
The two parameters considered most relevant to the interior moisture level of the building’s
life are building use and external climate. The moisture attributed to these parameters is
now discussed in more detail.
A. Building use
Table 2.4: Moisture generated by different household activities in
residential buildings.
Household Activities Moisture generation rage Moisture rate typical person
in a day
People:
Cooking:
(BS 5250:2011+A1:2016)
In a typical house in Nigeria with 4 people living in the space, cooking is primary
done using gas as a source of fuel in the house. The calculation of moisture that
can be done by the people using the space on a washing day.
From the table 2.11, its observed that some part of the house generate more
moisture in the spaces depending on the type of activities that is carried out in the
space. The moisture content in a typical Nigerian house generate in living room,
55
bedroom and dining room combine is less or about the same as a place like kitchen
alone in one day.
Table 2.5: Typical moisture generated in areas with normal and high
relative humidity in a typical house generated from table 2.10
Bedroom 1280g/day
Kitchen:
Cooking 3000g/day
Bathroom:
Bathing 800g/day
Rain fall is natural climatic factor that occurs in the Southern part of Nigeria regular
with high driving force. The driving rain direction intensity on the building structure
can be influenced by factors such as mentioned below:
Mould can reduce the quality of a building fabric. Mould in building also causes negative
effect on the physiological, visual hazard and health risk to the users of the space
(Marincioni and Altamirano-Medina 2017). Mould may release volatile organic compounds
(VOCs) which can lead to sick building syndrome (Sadovský and Koronthályová 2017).
57
People often spend 90% of their time indoor so it is important to ensure that mould growth
is eliminated. The tropics (latitudes from 23.4367o North to 23.4367o South) is the worst
climate condition for building materials as its exposed high amount of rainfall, high sun
radiation, high humid wind etc (Udawattha et al. 2018).
Large mould spores are present in the atmosphere at relative humidity of 80% which also
provides oxygen and moisture resulting in easy germination. Mould spores can germinate
at relative humidity lower than 80% and survive in dry environment although it would not
germinate during such conditions. Mould growth can occur in the winter because of greater
duration of relative humidity remaining at 70% or more during this season. Problem of indoor
air quality is an important risk factor for health of both the developing and developed
countries. A rule of thumb states that relative humidity higher than 80% presents a risk of
mould growth, the risk is dependent on the surface temperature and the number of days of
exposure.
These findings are supported by the work of Gradeci et al (2017) carried out an investigation
which found that relative humidity was the most important parameter in relation to mould
growth. Mould growth would likely occur at relative humidity of 75-95% and temperature of
-20oC to 60oC (Gradeci et al. 2017). Germination of mould will occur in interior spaces when
high relative humidity for longer than a day and if the dry period or low humidity is
experienced long the germination possibility is low or negligible. Mould growth is likely to
occur during desorption period than during the absorption period as growth is not just the
function of water activity but also moisture ration. It is affected by how fast the building
material is likely dry or lose its moisture (Gradeci et al. 2017). An increase in relative
humidity by 1% is more likely to cause a change in the germination process than an increase
in temperature by 8oC for relative humidity higher than 85% (Gradeci et al. 2017).An
investigation of mould growth analysed the following materials: engineering bricks, cement
blocks, cabook, cement stabilized earth blocks, mud concrete block, fly ash stabilized earth
blocks Engineering brick was found to be the most susceptible to mould growth and cement
stabilized earth block was the least susceptible to mould growth(Udawattha et al. 2018).
Mould risk can be predetermined or assessed using one of the following principles
mentioned when simulations are run on the building materials.
1. Mould can be assumed to occur when the conditions for “mould risk” in Figure 2.12 are
met in the internal space. When the relative humidity is greater than the critical relative
humidity at certain temperature mould is likely to germinate (Sadovský and
Koronthályová 2017)(Fedorik & Illikainen, 2013).
58
Figure 2.11: Range of temperature and relative humidity for mould
germination.(Fedorik & Illikainen, 2013)
- The critical relative humidity varies for temperature from ≥ 0oC < 20oC. the
relative humidity at each point needs to be mathematically calculated using the
formula below
RHcrit=−0.00267T3+0.161T3+3.13T+100
59
Table 2.6: Substrate class for mould growth
Sensitivity class Examples of Min relative Substrate Description of
building materials humidity materials
The mould growth simulation is based on data representing total water content, temperature
and the relative humidity the wall is exposed to. After the simulation has been complete the
mould growth on the surface of the material can then be classed using the index described
in Table 2.13.
0 0 0% No growth
Figure 2.12: Limiting growth curves for mould growth categories (Clarke et al, 1999)
Xerophilic organism can grow with low moisture content and hydrophilic organisms
needs high moisture content to germinate. The figure shows that the increase in
relative humidity which means increase in moisture content agrees with the
hydrophilic and xerophilic characteristics of mould organism.
2.7.3.2. Condensation
Condensation can occur in building in two forms – condensation on the surface of the
building material and interstitial condensation. Both are described below.
Temperature of the surface of building material can be affected by; time rate of heating in
the building, ventilation rate, thermal property of the surface finish of the building fabric,
61
external temperature. The building material in Nigeria climate is to be exposed to external
climatic factors which cannot be change, thermal property of building material is gotten from
the thermal conductivity rate. The ventilation rate is the factor that can be adjusted to meet
the need of the people and the building. It can be through natural or HVAC system. To
achieve affordable and sustainable building, the natural means of ventilation is the most
adequate.
Vapour pressure of the building can be influence by, water vapour production within the
building space, ventilation rates, moisture content of the outdoor air, ability of building to
absorb or desorb water content (moisture buffering effect) (BS, 5250:2011+A1:2016). The
different spaces in the building have different vapour pressure. The moisture production in
the building spaces differ based on the use of the space which is discussed in Table 2.10
and 2.11.
2. Interstitial condensation
Interstitial condensation occurs within the building material when water vapour moving
through it meets material that is at a temperature and relative humidity below the dew point
of the vapour. In the winter, interior of building is warmer, and air contains more moisture
than the external side of the building. In spring, autumn as well as summer, surface
temperature might be lower in the external side, the external surface of south facing walls
may be wet by driving rain and can be heated by sun causing when the moisture can dry.
Interstitial condensation can lead to staining, odours, deterioration of fabric and loss of
thermal performance.
Relative humidity of interior air, air tightness of the vapour barrier and the temperature are
all import factors to study in order to prevent interstitial condensation in building structure.
The indoor environment can be improved by controlling the external climate that is allowed
into the space. It can be controlled by altering the building form and adjusting the orientation
of the building in relation to the topography, prevailing winds, sun light, and shadows caused
from surrounding buildings or obstructions (BS 5250:2011+A1:2016).
The interior space can be improved by improving the air tightness in wall cavities to reduce
hygrothermal risk. Relative humidity of interior air can also be reduced by providing
adequate source of ventilation. Increasing the ventilation alone cannot reduce hygrothermal
risk but in tandem with an increase in temperature and or increasing air tightness can also
improve the risk in buildings.
Interstitial condensation can occur easily in areas of the house such as;
62
▪ Internal part of the building facing the driving the driving rain direction (BS
5250:2011+A1:2016).
a. Coldest month should not have internal relative humidity above 80%
b. Any interstitial condensation that occurs during the winter should be evaporated during
the summer period.
c. The risk of degradation of material should be assessed in terms of the level of
condensation which might occur.
The external climate allows the building structure such as wall component to be exposed to
solar gain, night sky radiation and exposed position.
- Exposure to solar gain: the building structure increases temperature which promotes
rapid drying of any condensation that nay have occurred.
- Night sky radiation: the external surface of the building cools easily at night which
means interstitial condensation can occur on the internal surface easily and can then
be easily evaporated during the daytime to reduce condensation on the building fabric.
(BS 5250:2011+A1:2016).
- Exposed position: (BS 5250:2011+A1:2016). In an urban city, some areas of the
building are exposed to external climate and the other part of the building can be
sheltered. The exposed area has high wind speed and driving wind that cools the
external surface of the building and cools the internal areas closest. (BS
5250:2011+A1:2016).
63
1. Ventilation: constant flow of air allows internal relative humidity (moisture in the air) to
remain between 40-70% to ensure comfort and reduce mould risk. Ventilation is also
used to remove unwanted smells and pollutants from a space (BS
5250:2011+A1:2016). This is usually achieved by natural ventilation. The rate of
ventilation depends on the size of the openings/vents, driving force of air which can
create wind pressure and buoyancy from temperature difference can also cause stack
effects. Wind pressure is dependent on the wind speed and direction. Natural ventilation
in a house can be achieved through different means such as single sided ventilation,
cross ventilation, wind tower, stack system, atrium ventilation. The southern climate of
Nigeria commonly uses cross ventilation and places that can’t be cross ventilated use
single sided ventilation. The northern climate of Nigeria commonly uses the wind tower
system
2. Insulation: building insulation can raise the surface temperature of the building (BS
5250:2011+A1:2016).
3. Places with high relative humidity such as kitchen and bathroom can control the
moisture content by doing one or a combination of the following:
a. keeps the internal doors for kitchen closed and leave the windows opened while
cooking.
b. keeps the doors closed while bathing and open the windows after bathing or
showering.
c. uses an electric fan till the mist in the air clears in the space.
The current research concentrates on using compressed earth blocks for the construction
of affordable and sustainable walls. The different wall system is to be studied to under the
most suitable for Nigerian climate. Solid walls include stonework, brickwork, blockwork,
earthwork or concrete. The thermal mass property allows change in temperature to respond
to change in air temperature slowly and of moisture change to some degree.
2.8.1. Possible walls system used for construction with compressed earth blocks.
There are different wall types that be used in construction earth walls in Nigeria. Each is
described below in relation to their risk of interstitial condensation and mould risk. The wall
design is studied to understand the best principle that should be applied in a place with
tropical savanna climate, with high relative humidity and high temperature to prevent
moisture build up in the building structure.
1. Solid masonry wall- external insulation with low pressure resistance finish is illustrated
in Figure 2.13 (internal finish on right). Insulation can be applied to new and old
64
buildings. External insulation when applied reduces the risk of thermal bridges and risk
of water penetration. There is no calculation needed for mould growth and interstitial
condensation (BS, 5250:2011+A1:2016).
Figure 2.13: Solid wall with external insulation with low resistance finish, (BS,
5250:2011+A1:2016)
2. Solid masonry wall- external insulation with high vapour resistance finish is illustrated
in Figure 2.14 (internal finish on right) A ventilated cavity is present between the
insulation and the finish. The risk of mould growth should be calculated following the
principles of BS EN ISO 13788(BS, 5250:2011+A1:2016).
Figure 2.8: Solid wall with external insulation with high vapour resistance
finish, (BS, 5250:2011+A1:2016)
65
3. Solid wall- internal insulation is illustrated in Figure 2.15 (internal finish on right). the
risk of moisture risk on the wall is calculated using BS EN 15026: 2007(BS,
5250:2011+A1:2016; BS EN, 15026:2007)
4. Masonry wall with cavity- External insulation is illustrated in Figure 2.16 (internal finish
on right). The use of external insulation might be necessary for improving thermal
performance. There is a risk of interstitial condensation when the building is heated;
however, a Nigerian building does not get heated as it has warm climate all through the
year, therefore no calculation is needed for mould growth and interstitial condensation.
(BS, 5250:2011+A1:2016)
66
Cavity is to prevent rainwater to the interior of the house. Rainwater may penetrate the
external skin of the structure if it’s not adequately constructed but the cavity will reduce
the chances of it going through the inner skin and entering the interior space. The use
of these wall system seems to be a very good for the climate in Nigeria that is
considered. (BS, 5250:2011+A1:2016)
5. Masonry wall with cavity- internal insulation: The insulation could fully or partially fill the
cavity. The introduction of insulation in the cavity might reduce the primary purpose of
the cavity of reducing rainwater. The risk of interstitial condensation depends on the
heating regime of the interior space and the type of thermal mass material used in the
inner leaf. There is a higher risk of interstitial condensation when a higher density is
combined with a heating regime. Nigeria house doesn’t have any heating regime
throughout the year. The use of fully insulated cavity will not be advisable to use in the
country as the external wall is required to keep the large driving rain fall from coming
into the internal space (BS, 5250:2011+A1:2016). The risk of moisture is calculated
using BS EN 13788, (BS EN, 13788:2012)
Figure 2.11:Masonry wall with cavity- insulation partial filling the cavity(BS,
5250:2011+A1:2016)
Medium rise housing appear to be the optimum compromise between low rise housing
(significant land use) and high rise housing (significant energy use particularly for vertical
transport) (Craighead, 2009). Medium multi-story (3-5 storeys) houses were found to have
the best compromise between minimising land use and minimising energy consumption –
67
particularly for vertical transport. The quality of the building design strategy for passive
environment is to be analysed used simulation too design builder to ensure maximum
adaptable comfortable interior environment.
(Olotuah, 2002) found that using local materials could reduce the overall cost by 50%.
Traditional architecture responds to local culture, climate, and materials (Alabsi et al, 2016;
Kırbaş & Hızlı, 2016). The traditional architecture tends to use local material and passive
design strategies that are important to the climate such as shading ventilations and thermal
mass in the north and in the south roof with wide slope, raised building and cross
ventilations. Whereas the modern residential building uses materials that focuses on the
aesthetic and international designs strategies not suitable for the climate. This modern
design raises the building materials and increases the energy required for the operation and
construction of the building. The need to provide affordable houses should be reconciled
consideration to the environment - this research aims to solve the problem of
accommodation while minimising problems to the environment.
The building material was the focus to reduce the cost of building material and energy use
of building. The requirement of the building material required needs to be affordable,
minimise environmental impact, structurally appropriate, conducive to thermal comfort and
good indoor air quality and avoid social stigmatisation.
The present research concentrates on materials used for wall construction for residential
building. The materials most used are blockworks, fired clay bricks, stonework and earth
blocks. Blocks and fired bricks– not affordable and have significant environmental impact.
Stone has fewer environmental impacts than bricks and blocks, but there is not a sufficient
local resource, which requires importing and expense. (Ashby, 2013) (Charlett, 2013).
Earth is labour intensive and has many environmental benefits in construction and in use
(Abd Rashid & Yusoff, 2015; Darko et al, 2017; Van Damme & Houben, 2017). However,
in some forms (particularly adobe blocks) it is associated with poor quality construction and
social stigmatisation. This can be addressed using CEBs which have a different
appearance, but more importantly have appropriate strength and durability if incorporated
in a sympathetic design which protects the blocks from driving rains common in Nigeria.
However, using the lateritic earth available in Nigeria it requires stabilisation. Cement is
currently used, but this has associated costs and environmental impacts. Ashes from
agricultural waste (rice husk, sugar bagasse and palm oil fuel) have been researched as
cement substitutes in blocks, bricks and mortar applications. These sources have
particularly been chosen for their availability in Nigeria. The impact on mechanical
properties of a range of cement substitute proportions have been analysed for these three
materials (Almeida et al, 2015; Ganesan et al, 2008; Givi et al, 2010) (Khankhaje et al,
2016). The waste product considered were rice husk ash, sugar bagasse ash, and palm oil
68
fuel ash. Rice husk ash is deemed to be the most suitable agricultural waste as it’s widely
available in the country, particularly in the Tropical savannah climate which dominates
Nigeria.
The reason for abandonment includes factors such as strength, durability, social
stigmatization. The current research would aim to improve factors mentioned.
Hygrothermal properties are important to ensure the CEBs will have the expected durability
and will not have adverse impacts on indoor air quality (eg mould formation)
(Mukhopadhyaya et al 2002) (Nguyen et al. 2017). Equally the impact of CEBs on thermal
comfort (RH, temperature and surface condensation) (Fantucci et al. 2017) (BS
5250:2011+A1:2016) are important considerations for occupant acceptance, particularly
given previous stigmatisation of earth-based housing.
The quality of residential material using local soil as the main constituent of construction,
while utilizing agricultural waste ash for partial stabilization in the country for sustainable
and comfortable environment can be determined by two criteria. The quality of the material
for the type of building required and the potential design strategies required.
The quality of material can be analysed by checking the mechanical and hygrothermal
property of the material in a laboratory. The mechanical strength is to ensure that material
can carry the load it will be exposed to from dead load, live load of users, external load etc.
the mechanical strength for compressed earth blocks to be analysed includes compressive
strength and bulk density of the material.
The hygrothermal properties relate to indoor air quality and are also required to ensure the
comfort of the users in the space. The tests required includes water absorption coefficient,
moisture absorption test, water vapour transmission, moisture buffering test and thermal
conductivity test. Improvement of the property of the material would also mean the reduction
of energy required to keep the user of the space comfortable. To analyse the hygrothermal
property of the material in depth, hygrothermal simulation based on the laboratory results
is required.
The parameters affecting hygrothermal and thermal performance were identified such as
building location in relation to climate and surrounding buildings, orientation, shelter from
rain (ie roof), moisture from indoor activities. The assessment criteria for mould growth risk
were defined (Sadovský and Koronthályová 2017) (Fedorik & Illikainen, 2013), (ISO
13788:2012 (Gradeci et al. 2018)
Potential wall structures which can incorporate CEBs are considered in relation to potential
interstitial condensation and mould growth. The most suitable wall design for tropical
savanna climate (Aw) in Nigeria is the option of masonry wall with cavity to prevent driving
69
rain from going into the inner skin of the wall. The wall could be having full cavity or partially
filled cavity with insulation.
This literature review has revealed a lack of research on CEBs with RHA as a cement
substitute and its effect on the resulting hygrothermal properties and impact on indoor air
quality and thermal comfort of the resulting building. It has also revealed little data on the
mechanical properties of CEBs with RHA as a cement substitute.
70
3 Research Methodology
_______________________________________________________________________
This chapter describes the activities carried out at various stages of the research project in
order to achieve the objectives of the study. Section 3.1 describes the relevant research
strategies used from the inception to the conclusion of the research. Section 3.2 describes
the processes adopted in this research for production and testing of materials used for
manufacturing CEBs, and the production of the experimental CEBs. Section 3.3 describes
the tests carried out on the CEBs to ascertain their mechanical, physical and durability
properties. Section 3.4 describes the simulation to test the hygrothermal performance of
the wall material. Section 3.5 describes the method applied to develop the building design
optimised for CEBs in the local climate and to compare the thermal comfort arising from
using CEBs versus concrete blocks.
72
1. PROVISION OF AFFORDALE AND SUSTAINABLE RESIDENTIAL
HOUSES
3. RAW MATERIAL
4. PRODUCTION OF CEBS
Figure 3.1, Theoretical framework for providing affordable and sustainable residential
houses
73
f. fine soil could include silt and clay soil
a. Soil Type: Combinations of clay soil, silt, sand or gravel are commonly used to produce
CEBs. To improve binding due to poor soil type, stabilizers are used to enhance the
property of soil type available (Mostafa, 2016). Laterite (clay) soil is rich in iron oxide,
silica, alumina which can be gotten from weathering of rocks with colour generally red,
yellow and brown. It is the predominant soil in Nigeria (Adam & Agib, 2001; Mostafa &
Uddin, 2016b) and was extracted in Ogun state as shown in Figures 3.2 and 3.3.
Laterite has poor workability, low shear strength, high compressibility and poor bearing
capacity as a result of the property of clay. Stabilization will reduce soil compressibility,
improve workability and soil drainage characteristic. Production usually requires
stabilizer such as lime, cement, straw, bitumen and pozzolans. Attempts are being
made to avoid cement due to its environmental impact. The large proportion of clay
causes excessive shrinkage; and therefore, requires an addition of sand to make it
suitable for CEB. A small test sample of laterite soil and stabiliser was first test without
the addition of sand, the compressive strength was poor so further test was not
conducted for this batch. For this study, laterite was therefore combined with sharp
sand to achieve soil with an appropriate ratio of components to form bricks.
The laterite was taken from an excavation site close to CEB production site (Ilaro) along
the Oja-Odan road, Ilaro, Ogun State, Nigeria. Sharp sand was collected from a local
stream along the Oja-Odan road, Illaro, Ogun State, Nigeria. Samples of the laterite
and sharp sand were collected to carry out standard procedure test to determine
Atterberg limits, and porosity.
b. Cement: The 42.5 grade Dangote Ordinary Portland Cement (OPC) brand
manufacture in Ogun state (location shown in Figure 3.3) is popularly used for building
construction in Nigeria and was purchase from a retailer along Oja-Odan Road, Ilaro
Ogun State, Nigeria for the stabilisation of laterite in this research.
c. Rice Husk: The rice husk was obtained from a rice milling factory along Lagos -
Abeokuta Expressway, Ogun State (location shown in Figure 3.3). This was used to
make rice husk ash for the stabilisation of laterite in this research.
d. Water: Potable water from a borehole at the production site was used to mix the
material after batching.
74
Figure 3.2: green outline highlighting the location of Ogun state on the map. (d-maps.com,
2020)
Figure 3.3: Map of Ogun state and location of site, location and distance of materials to site.
75
3.2.1.2 Raw material preparation
Each material required preparation before being used to produce CEBs. The preparation
process for each material is described in this section.
a. Soil Type: The excavated soil was air dried on a flat surface, pulverised and passed
through sieve. Laterite was sieved with a minimum and maximum sieve mesh size of
0.063mm and 63mm respectively to ensure the appropriate grain were attained
(Akinwunmi et al 2019). Similarly, the sharp sand was subjected to sieving through
mesh size between 2mm and 0.425mm to attain the appropriate grain sizes (Mostafa,
2016). The sieved soil was spread across a large surface area where they were air
dried for a week.
b. Rice Husk Ash (RHA): The rice husk was charred before subjected to combustion for
a period of 3 – 4hrs at temperatures of 550-700oC in a furnace to obtain Rice Husk Ash
(RHA). The treatment was to ensure the RHA retains its high amorphous silica content
(Alsubari et al, 2016; Chiang et al, 2009; Ganesan et al, 2008; Sore et al, 2016). The
process of carrying out the burning of the rice husk ash was challenging, as a large
combusting device to burn the rice husk at the required temperature wasn’t available.
i. At Covenant University the combustion furnace was damaged and the part that was
to be fixed wasn’t available in the country, so it was to be ship into the school from
the buyer. The only combustion furnace available was too small to burn the amount
that would be required for the partially replacement needed in the soil mix.
ii. There was also an enquiry of the device at Nigeria Building and Road Research
Institute Nigeria (NBRRI) but the furnace available to burn at controlled temperature
was damaged and the other furnaORDIce did not have enough temperature control.
iii. There was an enquiry of the furnace at National Agency for Food and Drug
Administration (NAFDAC), the furnace available was small and can only burn 50 g
of rice husk at a time per day as the furnace would take a few hours to cool down
before another batch can be put in to burn.
Finally, the burning process of rice husk ash had to be done with a private sculptor that had
a large furnace. The burning process took about three weeks to be completed as the
furnace had to be cooled for 36 hours after each batch before it could be removed from the
furnace.
76
density and other test. For soil to be deemed adequate for engineering purpose, soil needs
certain particle distribution, plasticity index, moisture content and bulk density. A range of
tests was carried out to analyse the raw materials and ensure that they are suitable for
making CEBs.
Atterberg limit test: The soil composition used for engineering purpose are describe in soil
fraction. The soil fraction for the purpose of CEBs is composed of primary and secondary
fraction. Primary fraction of the soil determines the engineering properties of the soil which
can be given as basic of plasticity. The secondary fraction helps to modify the engineering
properties of the soil. The test carried out ensure the soil can be categorized appropriated
(i.e. sandy Gravel, sandy is the secondary fraction and gravel is the primary fraction of the
soil). Silt and clay react differently in the presence of water. The Atterberg limit test defines
the plastic and liquid limits and includes a linear shrinkage test. These tests are described
below and were conducted according to (BS, EN ISO 17892-12:2018).
Description of device
▪ Specimen cup: the cup has to be made of brass or stainless steel. The surface
has to be smooth and replaced when there is damage on the surface
▪ Carriage: the carriage is secured and adjusted to 10mm height of the cup drop.
▪ Cam or crank: the crank shall be able to raise the cup easily continuously to its
maximum height by rotating it at least 180o.
▪ Grooving tool: a flat curved non-corroding metal tool.
77
KEY
1. Specimen cup
2. Hanger
3. Carriage with
pin
4. Cam or crank
5. Base
6. Rubber feet
7. Point of contact
Preparation of specimen
▪ Measure fine soil sample: 200g of fine soil to an accuracy of 0.1% of the mass, or 0.01g
(whichever is greater). The soil must be less than 0.4mm particle size (soil particles
larger than 0.4mm are removed). Soil used in these tests does not need to be oven
dried;
Where it is not possible to remove large particles by sieving, the wet separation method is
used:
▪ Put soil in a jar and add distilled water to cover the soil sample and then stir until it
becomes a slurry;
▪ Pour slurry soil sample through a 0.4mm or nearest size sieve (a large aperture guard
sieve may be used to protect the sieve);
▪ Dry the sample that is retained in the sieve 110±5oC. Weigh the dried material to an
accuracy of 0.1g or 0.1% (whichever is greater). This is the reference mass (mr.);
▪ Allow the sample that passed through the sieve to settle and pour off the clear water;
▪ The sample is allowed to dry in a oven of not more than 50oC until it becomes a firm
paste (stirring occasionally to prevent premature edge/surface drying);
78
v. The crank was turned for about 2 revolutions per second without holding the base. The
number of blows required for the groove cut to occur were recorded. NB - the closure
of the gap on the soil should be by soil flow not by soil slide across the face of the cup.
vi. Crank rotation was stopped as soon as the groove has closed over a length of 10mm.
The number of crank rotations (blows) were recorded, if it did not meet the requirements
stated in Table 3.1, the test result was repeated with minor adjustments to water
content as required.
vii. A sample (15g) was taken from the soil in the cup to determine its moisture content.
This was done by finding the difference between the mass of wet soil sample from the
cup and the mass of the soil sample after drying in the oven for 18 – 24 hours at
110±5oC;
viii. The procedure (i-vii) was repeated four more times.
ix. The percentage of water content was calculated using Equation 3.1 and the liquid limit
was calculated from Equation 3.2.
Equations
i. water content (W) of liquid limit test (BS EN ISO 17892-12 2018):
… Equation 3.1
79
B. Plastic limit: It is the moisture content in the soil between the plastic and semi-solid
state of the soil. It is measured by rolling a 3mm stick soil sample on glass surface until
it begins to crumble,
Apparatus
▪ Mixing plate: it’s a smooth, flat, clean surface used to roll the threads. It’s usually
made of glass of about 100mm thick with square dimension of 300mm.
▪ Rod or gauge: it’s a rod of 3mm to 3.5mm or a gauge with opening equal to be
used to check the size of thread made.
i. the remainder of the sample from the liquid limit test machine was
retrieved.
ii. take 15g to 20g of the retrieved soil sample and plate on the mixing
plate.
iii. allow the paste to dry partially until it has reached plastic state.
iv. mould the sample into a ball and roll into an ellipsoidal shape.
v. divide the portion into three.
vi. each portion should be rolled into ellipsoidal shape of 6mm first.
vii. the ellipsoidal shape was rolled into a uniform thread of 3mm diameter
through the length.
viii. the thread was broken into 6 pieces and squeezed back together into a
uniform rod.
ix. place the pieces into a suitable container and place a lid on it.
x. repeat step 4-9 until the thread crumbles and the soil can no longer be
rolled into a thread.
xi. the moisture content of the crumbled soil was determined by finding the
difference between the mass of the wet crumbled soil sample from the
cup and the mass of the crumbled soil sample after drying in the oven
for 18 – 24 hours at 110±5oC and calculate using Equation 3.3;
xii. the percentage plastic limit was calculated using Equation 3.4.
Equations
𝑚𝑎𝑠𝑠 𝑜𝑓 𝑤𝑎𝑡𝑒𝑟
𝑚𝑜𝑖𝑠𝑡𝑢𝑟𝑒 𝑐𝑜𝑛𝑡𝑒𝑛𝑡(𝑊𝑃 ) = 𝑥100(GTM-7, 2015) Equation 3.3
𝑤𝑒𝑖𝑔ℎ𝑡 𝑜𝑓 𝑑𝑟𝑦 𝑠𝑜𝑖𝑙
80
▪ Plasticity index (Lp) (BS EN ISO 17892-12 2018)
Lp = wL – wP … Equation 3.4
Where:
C. Linear shrinkage: In soil with moisture content equivalent to the liquid limit, linear
shrinkage is the decrease in length of the soil when it has been exposed to drying,
(Adam & Agib, 2001; ASTM, Standard D 4318 2005). The procedure is described
below:
Equation
𝐿𝑆
𝑙𝑖𝑛𝑒𝑎𝑟 𝑠ℎ𝑟𝑖𝑛𝑘𝑎𝑔𝑒 = × 100 (ASTM, Standard D 4318 2005)
𝐿
… Equation 3.5
Where:
The RHA sample was exposed to monochromatic radiation over a varying incident angle
range in an x-ray diffraction device. This caused an interaction with the RHA atoms. The
spectra are characterised by the chemical composition and the phases of RHA developed.
This technique provided phase identification (i.e. amorphous or crystalline), along with
81
phase quantification, percentage crystallinity, crystallite size and unit cell. The x-ray
diffraction device at Cardiff University can collect high resolution data at low temperature to
systems that can probe structures up to 9000C under 10 different atmospheres of reactive
gases.
The RHA samples were obtained using two different methods in order to establish which
was the most suitable for high amorphous silica content
Method 1
The rice husk ash used for the test was gotten form Abeokuta, Ogun state. The rice husk
was first charred to remove the moisture and organisms from the waste using a local
burning method in a local mud pot. The colour of the husk changed from cream to black
and the husk reduced to about half its size in mass. The charred husk was then combusted
in a furnace for about 2-3 hrs at temperature ranging from 550-780oC. The furnace was left
to cool for about 24 hrs before the RHA was brought out of the furnace. The colour of the
resulting rice husk ash was whitish grey colour.
Method 2
The rice husk was combusted directly in the furnace for 21/2 hrs- 4hrs. The colour of the rice
husk changed from cream to whitish grey. The furnace was fed with the same quantity of
husk used in ‘method 1’, the burning of the hush took a long time and cost more because
the mass of the husk has not been reduced from the charring step which removes moisture
and organisms. The second method was introduced to reduce the time of production
process.
82
Six different mix ratios were used to produce 162 solid and 108 hollow CEBs to test the
best mixture ratio. The solid CEBs are to be used for exterior and load bearing walls, as
these walls will be exposed to environmental climate and structural loads. The production
of hollow blocks was used to reduce the raw material needed to make interior walls as these
are not exposed to environmental climate and are not load bearing. The mix ratio variables
included Laterite, Sharp Sand, OPC, RHA and Water. Each mix ratio was grouped and
labelled accordingly. The control mixes for solid CEBs adopted ratio 11:7:2 for Laterite,
Sharp Sand and OPC. While the hollow CEBs adopted ratio 13:5:2 for Laterite, Sharp Sand
and OPC. The mix ratio for hollow CEBs differed from the solid because the formation of
the hollow block required more laterite.
The experimental CEBs were intended to explore the replacement of OPC with RHA. For
this reason, the proportions of laterite and sharp sand were identical to the control mix. The
OPC component was replaced with 10%, 20%, 30%, 40% and 50% of RHA respectively for
both block shapes – this is detailed in Table 3.3.
The manual production method was used for this study because the equipment is light,
sturdy, low cost, simple to manufacture and repair and could be easily purchased in Nigeria
for about $500- $800. A more detailed description of the process follows:
a. Measuring and mixing of required proportions materials (i.e. laterite, sand, OPC, RHA
and water). Wetting with water was done to ensure workability and binding of the
materials.
b. The mix was poured into the mould of the mechanical pressing machine in Figure 3.5.
manual Pressure was applied manually for a few seconds for uniform compaction; and
83
Materials before molding CEBs pressing machine
Production of blocks was carried out in Nigeria; the blocks were manufactured by some
laboratory technologists at Covenant University and Illaro Polytechnic.
3.2.2.3 Curing
The blocks were manufactured in Nigeria, which experiences high temperature, high
relative humidity and (at some time of the year) high rainfall. The blocks produced for
affordable building are made externally which means the blocks need to be protected when
produced and when curing process occurs. The blocks were laid as shown in Figures 3.6
and 3.7 after compaction. The blocks were kept in a controlled environment (23±5 oC and
84
90%RH) during curing. Extreme shrinking and cracking were prevented by covering the
blocks with a 1mm thick tarpaulin sheet to control the rate of moisture desorption. Watering
of blocks was done with a spray bucket at least twice daily to ensure adequate occurrence
of hydration reactions (Adam & Agib, 2001). Sets of blocks were cured for 14, 21 and 28
days. After curing, the blocks were then stored in a dry room in preparation for the
subsequent tests. The production and curing incorporated the procedure for clay masonry
units according to British standard (BS, EN 771-1:2011+A1:2015).
0% RHA 21
28
10% RHA 21
28
20% RHA 21
28
30% RHA 21
28
40% RHA 21
28
50% RHA 21
28
* Control sample
85
Table 3.3b, Composition of mix for CEBs – Hollow
Hollow % RHA 13 5 2* - 14
21
28
10% RHA 21
28
20% RHA 21
28
30% RHA 21
28
40% RHA 21
28
H/1 RHA 13 5 1 1 14
50% RHA 21
28
* Control sample
Samples of the experimental hollow and solid compressed earth blocks produced in this
study are shown in Figures 3.6 and 3.7, respectively.
86
Figure 3.6. Samples of experimental solid CEBs produced in this study
87
For each block shape, mix ratio and curing option:
a. three blocks were selected randomly from the solid block samples cured for 14 days
for each mix ratio.
b. the blocks were weighed separately with a digital weighing balance and recorded to an
accuracy of 0.1% of their mass.
f. Steps a-e were repeated for each curing condition and for hollow blocks
Equations
2:2014)
The blocks were tested based on the standards for fired clay bricks in British standard (BS,
EN 772-1:2011+A1:2015) for each block shape, mix ratio and curing option:
88
Apparatus
The machine will have adequate strength to crush the entire test specimen and conform to
Table 3.4 and Figure 3.8. The machine shall have two steel bearing platens. The deflection
of the platen surface shall be less than 0.1mm measure over 250mm. the surface of the
platen shall be hardened, or the face-case hardened. The platen shall align freely with the
surface of the specimen and shall be held by friction or tilting during loading. The bearing
of the platen shall be larger than the surface of the specimen.
a. Cure specimen under sack kept damp throughout the curing period at relative humidity
greater than 90%
b. Weigh the samples to an accuracy of 0.1% of their mass
c. Conditioning before testing:
Air dry conditioning involves:
▪ Storing in the laboratory (conditions defined in Table 3.5) until constant mass is
reached when the consecutive mass weight of the sample 24 hours apart is less
than 0.2% of the total mass.
89
Alternatively, dry the specimen in an oven at 105°C ±5°C for at least 24 hours and
cool at room temperature for 4 hours.
a. three blocks were selected randomly from the solid block samples cured for 14 days
from the controlled mix ratio.
b. The gross area (mm2) of the surface of the sample shall be calculated by multiplying
the length and the width of the specimen. Equation 3.9 was used for solid CEBs and
Equation 3.10 was used for hollow blocks.
c. Wipe the surface of the machine clean to remove loose grits from the bed of the
specimen. Alig the specimen to the centre of the platen so uniform load can be applied
across the surface.
d. Application of force perpendicular to the CEBs was gradually increased until failure or
a visible crack occurs.
e. The Force at the point of failure for each block was recorded.
f. The compressive strength of the blocks was calculated using Equation (3.9).
g. The mean compressive strength of the blocks was calculated from Equation (3.10).
h. steps a – g was repeated for the block samples cured for each combination of curing
and mix ratio; and
i. steps a – h was repeated for hollow block samples.
Equations
90
C1 +C2 +C3 +Cn
number of compressive strength
…………. Equation 3.12
Water absorption is the quantity of water in kg absorbed by a unit of block when fully
immersed in water for duration of 24 hours. Water absorption rate is expressed as a
percentage of the weight of the dry unit. The water absorption rate of the block samples
was determined in accordance with British standard (BS, EN 772-21:2011) highlighted in
the procedure below for each block shape, mix ratio and curing option:
Apparatus
• Water tank large enough to soak the samples, with base slightly raised, so that water
encounters all the surfaces of the samples
• Ventilated oven to maintain temperature of 105±5°C
• Weighing device to accuracy of 0.1% of dry mass
Procedure
a. Three blocks were selected randomly from the solid block samples cured for 14 days
from the controlled mix ratio.
b. The sample was dried in the oven at temperature of 105±5oC until constant mass is
reached. Constant mass is reached when two consecutive mass measures taken
24hrs apart are within 0.2% of the total mass. Allow to cool to room temperature
before weighing.
c. The blocks were weighed separately with a digital weighing balance and their
weights were recorded.
d. The blocks were fully submerged in water for 24±0.5 hours.
e. The blocks were removed from the water and the surface of the blocks were dried
with damp cloth.
f. The damp blocks were weighed with a digital weighing balance separately and their
weighs were recorded.
g. The water absorption rate was calculated from Equation 3.13 to the nearest 1%.
h. The mean water absorption rate was calculated from Equation 3.14.
i. Steps a – h was repeated for the block samples cured for 21 and 28 days for each
mix ratio: and
j. Steps a – i was repeated for hollow block samples
91
Equations
Ms -Md
Water absorption rate WS = Md
x 100…….. Equation 3.13
a. Three blocks were selected randomly from the solid block samples cured for 28 days
from the controlled mix ratio.
b. The blocks were weighed separately with a digital weighing balance and their
weights were recorded.
c. The area of the horizontal surface to be partially immersed in water was calculated
by the expression in Equation 3.9.
d. The blocks were placed in separate PVC containers over small PVC studs to ensure
the blocks did not touch the surface of container.
e. The water level was maintained during the test at 5±2mm above the base of the test
block samples as shown in Figure 3.9.
f. The block samples were removed after 20 minutes and blotted with dry cloth to
remove excess water on their surfaces.
g. The block samples were weighed, and the new masses were recorded.
h. Steps d – g were repeated several times allowing immersion in water to continue for
1 hour, 2 hours, 4 hours, 8 hours, 12 hours, 18 hours and 24 hours;
92
i. The change in mass per area was calculated as expressed in Equation 3.15,
j. The water absorption coefficient was calculated as expressed in Equation 3.16, and
3.17.
k. Steps a – j was repeated for the block samples cured 28 days for each mix ratio.
Equations
The change in mass shall be plotted against √t. The graph plotted could either be straight
or curved. The water absorption coefficient is dependent on the shape of the graph.
▪ Straight graph equation represents a sample with no water on top of surface after
longest immersion time (illustrated in Figure 3.10) (BS, EN ISO
15148:2002+A1:2016):
Where:
∆m0 is the mass at time zero on the graph that cuts the vertical axis when the line
is extended,
93
Figure 3.9 Section of Water Absorption Coefficient test set up
Figure 3.10, Change of mass per area vs square root of immersion time - This represents
a sample which did not develop water on the top surface even after the longest immersion
time
Figure 3.11 Change of mass per area vs square root of immersion time - This represents a
sample which developed water on the top surface
94
3.3.5 Water vapour transmission
The British Standard (BS, EN ISO 12572:2016) describes the procedure for the
determination of water vapour transmission. The block samples were subjected to different
conditions in order to determine the density of water flow rate, water vapour resistance,
water vapour permeability, and water vapour resistance factor. The procedures described
below were followed for a selected solid block mix ratio cured for 28 days:
Procedure
a. Three block samples were selected randomly from the solid block samples cured for
28 days from a mix ratio.
c. The block samples were sealed with waterproof tapes at all sides to leave the top and
bottom exposed.
e. The area of the exposed surfaces was calculated from equation (3.9)
f. The block sample was placed over a dry cup 0% (calcium chloride) in such a way that
the bottom surface of the block was exposed and sealed from exposure to the external
conditions, the overhanging part of the block was sealed with waterproof tape.
g. The sample in step f was placed in an airtight PVC container containing aqueous salt
solution (Magnesium nitrate) to control the relative humidity to 50% as shown in Figure
3.12. The temperature was maintained at 23±1oC;
h. The block sample was weighed every 24 hours until the difference in masses of five
consecutive readings was within ±5% of the running mean value of the block sample
weight.
j. The mass change rate was determined by the expression in Equation 3.18.
k. The density of water vapour flow rate was calculated from Equation 3.19.
o. The water vapour resistance factor was determined by from Equation 3.23.
p. The water vapour permeability of air was calculated from Equation 3.24; and
95
q. Steps a – p will be repeated for the block samples cured 28 days for other mix ratio.
Equations
• Change of mass rate for water vapour transmission (BS, EN ISO 12572:2016):
… Equation 3.18
Where:
Δm12 is the mass per time for a single determination, given as kg/s
• Water vapour flow rate through specimen (G) is the mean of five consecutive Δm12
• Density of water vapour flow rate for water vapour transmission (g) (BS, EN ISO
12572:2016):
… Equation 3.19
Where:
A is area from Equation 3.9
G is water vapour flow rate
▪ Water vapour permeance for water vapour transmission (WP) (BS, EN ISO
12572:2016):
𝐺
𝑊𝑃 = … Equation 3.20
𝐴∆𝑝
The value of ∆pV (water vapour pressure difference across specimen) shall be
calculated from the mean of the measure temperature and relative humidity over the
course of the test.
Note: for temperature greater than 0oC, vapour pressure on either side of the specimen
can be calculated as (BS, EN ISO 12572:2016):
96
17,269.θ
𝑝 = ϕ. 610,5. 𝑒 237+θ …Equation 3.20a
Where:
is relative humidity
is temperature (oC)
▪ Water vapour resistance (Z) for water vapour transmission (BS, EN ISO 12572:2016):
Z = 1/w … Equation 3.21
Where:
w is water vapour transmission
▪ Water vapour permeability () for water vapour transmission (BS, EN ISO 12572:2016):
= w.d … Equation 3.22
Where:
w is water vapour transmission
d is mean thickness of specimen (m)
▪ Water vapour resistance factor () for water vapour transmission (BS, EN ISO
12572:2016):
… Equation 3.23
Where:
… Equation 3.23a
RD is the gas constant of water vapour = 462 x 10-6 Nm/mg.K
∆𝒑. 𝛿𝒂𝒊𝒓
𝑔𝒂𝒊𝒓 =
µ. 𝒅
… Equation 3.24
97
Figure 3.12: Section of Water vapor transmission setup
a. Three block samples were selected randomly from the solid block samples cured for
28 days from a mix ratio.
c. All sides of the block samples excepting the bottom side were sealed with waterproof
tape.
d. The blocks were weighed separately, and their weights were recorded.
e. The area of the exposed side (i.e. bottom) was calculated from equation 3.9.
f. A cup was conditioned with an aqueous salt solution (magnesium chloride) to keep it
at a relative humidity of 33%.
g. The block sample was placed over the conditioned cup in such a way that the entire
bottom surface of the block covers the cup from exposure to the external conditions
and the overhanging part of the block is sealed with water proof tape as shown in Figure
3.13;
98
h. The mass of the block sample was taken at 24 hours interval until the constant mass
was attained (i.e. when the difference in masses of three consecutive readings were
within less 0.1% of the total mass of the block sample).
i. Step f was repeated to attain a relative humidity of 55%, 75% and 85% respectively.
j. Step g – h was repeated for the same sample with condition cup of relative humidity of
55% (magnesium nitrate), 75% (sodium chloride) and 85% (potassium chloride)
respectively.
k. The moisture content of the block sample was determined by the expression from
equation (3.25).
l. Steps a – k was repeated for the block samples cured 28 days for other mix ratio.
Equations
… Equation 3.25
Where:
99
3.3.7 Moisture buffering
The moisture buffering test was done according to the NORDTEST work group process
(McGregor et al, 2014; Rode et al, 2005; Zhang et al, 2017). The block samples were tested
at varying relative humidity level to determine the moisture buffering. The procedures used
are as follows for a selected solid block mix ratio cured for 28 days:
a. Three block samples were selected randomly from the solid block samples cured for
28 days from a mix ratio.
c. The block samples were sealed at all sides with a waterproof tape except the bottom
that was left exposed.
d. The blocks were weighed separately, and their weights were recorded.
e. The area of the exposed side is calculated with the expression from the equation (3.26).
f. A cup was conditioned with an aqueous salt solution (magnesium chloride) to keep it
at a relative humidity of 33%.
g. The block sample was placed over the conditioned cup in such a way that the entire
bottom surface of the block covers the cup from exposure to the external conditions
and the overhanging part of the block is sealed with water proof tape as shown in Figure
3.14;
h. The mass of the block sample was taken after 8 hours of exposure.
j. Step g was repeated for the same sample with condition cup kept at a relative humidity
of 75%.
k. The mass of the block sample was taken after 16 hours of exposure.
l. The mass of the block sample was taken at 8 hours interval until the constant mass
was attained (i.e. when the difference in masses of three consecutive readings was
within less 0.1% of the total mass of the block sample.
m. The moisture buffering of the block sample was calculated from equation (3.27).
n. Steps a – l was repeated for the block samples cured 28 days for other mix ratio
Equations
i. Moisture effusivity for moisture buffering test (bm) (Rode et al. 2005, (Rode et al,
2007)):
100
…Equation 3.26
Where:
du = moisture content change = mean of mass change of last 3 cycles= mean (mass
release +mass intake + mass release) OR mean (mass intake +mass release +mass
intake)
𝐺(𝑡)
𝑀𝐵𝑉𝑖𝑑𝑒𝑎𝑙 ≈ = 0.00568. 𝑝𝑠 . 𝑏𝑚 . √𝑡𝑝 …..Equation 3.27
∆𝑅𝐻
ΔRH= change in relative humidity between the low humidity (33%) and high humidity
(75%) exposed to the samples
Gt= accumulated moisture uptake
… Equation 3.27a
tp= time (between the last three cycles)
ps= saturation vapour pressure of air
17,269.θ
𝑝𝑠 = ϕ. 610,5. 𝑒 237+θ … Equation 3.20a
101
Figure 3.14: Section of Moisture buffering setup
Principle:
The principle for thermal performance of CEBs was achieve by construction of masonry
wall, the wall was surrounded with hot box using heat flux meter. The heat flow meter is
used to create two environmental condition for steady state of the materials. The masonry
wall is exposed to hot and cold environmental temperature for a selected solid block mix
ratio cured for 28 days:
a. hollow block samples were selected randomly from the solid block samples cured for
28 days from each mix ratio.
b. the block samples were used to construct a wall using a cement- sand mortar mix with
a thickness of 12-15mm in a hot box as shown in Figures 3.15 - 3.18.
c. heat was generated using an electric heater inside the hot box on one side of the wall
for two weeks. A controller was used to keep the internal temperature to 33+-2oC
102
d. heat flux plate and a thermistor were fixed on the side of the wall receiving the heat
generated from the heater while external sensors were placed on the other side of the
wall.
e. the heat flux plate, and thermistor were connected to a data logger that recorded the
temperature, relative humidity and heat flow every 15minutes while the external
sensors measured the temperature and relative humidity at the same frequency.
f. after the test, experimental data was collected by connecting the data logger and
external sensor to the computer.
g. the heat flux and thermal conductivity values of the block samples were determined by
the expression in equation (27) and (28).
h. In order to calculate the U-value, the construction of a hot-box using the samples of
CEB RHA mix sample to make a wall in the hot box was required in Figures 3.15 and
3.16. Heat flux plate were to be fixed to the wall. The wall and the heat flux plates are
protected in a guarded hot box (BRE 2014)
Equations
qxd
𝑘 = T1−T2
(BS, EN ISO 22007-1:2017)
…………………………………………………………………… Equation 3.28
Where:
Q
𝑞=A (BS, EN ISO 22007-1:2017)
Where:
Q is the quantity of heat passing through the base area of the sample (W)
The value q is gotten directly from the data logger in the case of this test
103
Figure 3.15: section of in-situ thermal test with CEB blocks exposed to laboratory
environment
Figure 3.16: Elevation of in-situ thermal test with CEB blocks exposed to laboratory
environment.
Equipment:
The in-situ thermal test was constructed using sheet plywood and insulated using expanded
polystyrene (EPS) see Figures 3.17 and 3.18. The In-situ box was constructed by Mr
Gbadamosi Ibrahim Abiodun and Mr Mathew Oladele Bamidele. It was able to carry out
testing of two different mix sample simultaneously. The size of the box was designed with
a length of 120cm, a width of 125 cm and a height of 120 cm. the cavity of the wall
104
constructed had a width of 0.15cm. The in- situ box was heated electrically. The thermal
conductivity test was performed with the inner temperature at 36±5oC while the external
temperature of the room remained at 26±2oC.
The specimen is located in-between the box and room, so is exposed to two different
environmental conditions. The box is hot inside and the heat flows to the cool outside of the
105
building envelop. The thermal property can then be measured by measuring the heat flux
(W/m2) on both sides of the wall (using the circular plates shown in Figure 3.19). The
temperature and relative humidity were measured every second using a sensor attached to
the heat flux in Figure 3.19. The average per minute was recorded by the data logger (Eltek
851L datalogger in Figure 3.20). The running mean values were then calculated using
equations 3.28 and 3.29 to calculate the thermal conductivity (W/m.K) and quantity of heat
passing through a unit area of the material (W/m2).
106
3.4 Simulation of Wall System
3.4.1 Modelling for interstitial condensation and assessing risk of mould growth
development on selected CEB compositions
After analysing the tests described in Section 3.3 to eliminate any curing/RHA composition
combinations which are not suitable for use, a selection of usable CEBs compositions were
selected. WUFI Pro 5.3 was used for the dynamic simulation of hygrothermal analysis.
Mould formation was further studied by exporting the result from WUFI pro 5.3 to WUFI bio
to study the amount of mould growth in mm in a year.
There are three stages in setting up the simulation. These involve the component, the
controls, and the climate and are described below.
i. Component
a. Assembly: the wall size and wall system are designed for each material in the
wall. The material property can also be adjusted accordingly. The wall design is
shown in section 2.8.1
b. Orientation, inclination, and height of the wall: orientation was chosen based
on the most prevalent wind direction. Inclination is vertical for a wall. The wall
height was based on a medium rise building (4 storeys).
107
c. Surface coefficient: heat resistant of different types of building structure was
given in the tool, so selection of external wall was chosen. The selection of short-
wave radiation absorptivity was brick, clay, cream and glazed was chosen as the
most similar from the options for the simulation of Compressed earth blocks walls.
The other parameters were left at the default values.
ii. Controls:
a. Calculation period and profiles: the start date and the end date are selected.
The simulation process was investigated for 1 year, and in some cases 3 years
b. Numerics: it allows the selection of the mode of calculation which typically
includes heat transport, moisture transport and temperature.
iii. Climate:
a. Outdoor (external side): selection of weather file for simulation of WUFI/ WAC
format from Meteonorm. This format is necessary to analyse the driving rain
direction in the location selected. The rain factor was calculated according to the
ASHRAE standard 160, with the wall exposed by a medium level and the wall
below a steep slope room for southern climate (Aw) of Nigeria. The data from
Lagos was used (as detailed in Section 3.4).
b. Indoor (internal side): two internal condition were selected. The first one
represented the indoor climate for areas like kitchen and bathroom with moisture
content resulting from the high relative humidity of about 85% by selecting the
sine curves. The other for areas with “normal” climate condition like living room,
dining rooms, bedrooms, by selecting EN 15026. The indoor climate in EN 15026
was calculate from the external climate.
WUFI bio is an add-on tool that can be used in connection with results from WUFI Pro to
analyse mould growth in the building. It is important to study different boundary conditions
that may potentially be experienced within the interior space of the building. The tool studies
the boundary conditions compared with growth conditions that are typical for mould growth
to thrive. It compares the critical water content and the water content that would support
the germination of spores. The analysis tells if the material used for wall is wet enough to
grow mould. The internal temperature, the relative humidity and substrate quality are
required for analysis. The mould spores that are close to the wall surface change water
content as the temperature and the relative humidity change. Biological activity begins and
the spores germinate at the point at which water content reaches the critical.
108
Limitations to the tools are highlighted below:
A variety of available substrates for mould growth in building simulation include the
following:
0: No growth
The results of the analysis are shown as traffic light colours and implications are highlighted
in Table 3.6.
109
Table 3.6 WUFI Bio traffic light indicators
i. Weather data was obtained from Meteonorm 7v7.3.3 for Lagos located at 6.50N/3.50E
– tropical savannah climate (Aw) which covers the largest area of Nigeria (compared
to the other three climates present). The data was based on the 1991-2010 period for
radiation, while temperature was from 2000-2009.
110
ii. The Adaptive Comfort Model in ASHRAE Standard 55-2010 was chosen as the most
suitable from the options available. This was considered appropriate due to the focus
on eliminating mechanical service systems to reduce the amount of energy required to
service the building over its lifetime. This fits well with the expected living conditions of
the occupants. This model considers that the occupants of the space can make
adaptations (e.g., adjust their clothing and open or close the windows) in response to
the external climate conditions.
iii. The weather file was visualised using Climate Consultant to obtain the following and
represented in Table 5.17:
1. Monthly diurnal averages: this indicates daily temperature variations in relation to solar
radiation.
3. Psychrometric chart: bioclimatic chart with simplified weather data was presented in
Section 2.3.1. Climate consultant helps visualize more detailed climate data. This
enables comparison of the periods of comfort created by the relevant passive
strategies.
As this investigation was testing the thermal response to the wall materials, a simplified
structure was used:
• double glazed windows (U-value of 3.0 W.m2.K-1) were positioned on north and
south facades to minimise solar gains and roof overhang of 0.9m for additional
shading,
• natural ventilation,
The area of the building tested was 360m2. The rectangular shape building is the most
suitable to ensure easy penetration of air into the building space. The two different shapes
are to understand the change of comfort level when the building is less compact to a larger
difference between the length and breadth.
a. 24x15m (area to volume ratio of 0.50238) oriented with long dimensions facing
North/South.
b. 36x10m (area to volume ratio of 0.54127) oriented with long dimensions facing
North/South.
These material options were analysed for occupant thermal comfort by checking the number
of hours of comfort in the house for a year. The intention of this analysis is to determine
whether occupant comfort is being adversely affected using CEBs in comparison with
typical modern materials.
112
4. Laboratory Test Results
_______________________________________________________________________
This chapter presents the results of laboratory testing on raw materials (laterite and rice
husk ash) in Section 4.1
In section 4.2 the results of laboratory testing of mechanical (4.2.1 bulk density, 4.2.2
compressive strength) and hygrothermal (4.2.3 water absorption, 4.2.4 water absorption
coefficient, 4.2.5 water vapour transmission, 4.2.6 moisture absorption, 4.2.7 moisture
buffering, 4.2.8 thermal conductivity) properties are presented for:
• CEBS with OPC partially replaced with RHA at 0%, 10%, 20%, 30%, 40%, and
50%
Table 4.1 Properties of laterite sample used for making the experimental CEB
Property Mean ± SD
Plotting the results of laterite properties (Table 4.1) in the unified soil classification chart
(Figure 4.1) showed that the laterite sample corresponds to soil classification CL.
Description of soil classes highlighted in Table 4.2 indicated the laterite sample is classified
113
in the category of clays. The Soil CL is inorganic clay of low to medium plasticity, gravelly,
sandy and silty clays. The results of liquid limit as shown in Figure 4.1 suggest that the soil
has low plasticity.
Table 4.2 Description of the unified soil classification with laterite classification
highlighted
silts
The findings about the laterite soil are discussed further in Section 6.1.1.(Hind K.J, 2007)
Two methods of processing rice husk in order to achieve ash with an appropriate silica
content were trialled. The method used for production of the rice husk ash was shown in
section 3.2.1.3
114
X-ray diffraction (XRD) was used to calculate the percentage of amorphous silica within the
RHA. The XRD analysis was carried out by the School of Chemistry, Cardiff University.
The X-ray diffraction trace for RHA prepared using Method 1 (pre-charred) is shown in
Figure 4.1. While the trace for RHA prepared using Method 2 (furnace only) is shown in
Figure 4.2. The percentage of amorphous silica indicated by the X-ray diffraction traces
are presented in Table 4.3.
115
Table 4.3 Percentage amorphous silica contents of experimental Rice Husk Ash
(RHA) samples at different combustion times
Both methods produced ashes containing amorphous silica contents adequate for
pozzolan chemical reaction when used for stabilization. Combusting the rice husk for a
longer period at the applied temperature (i.e. 550 to 780oC) as in Method 2, resulted in
ash that contained higher amount of silica, but incurred an energy penalty for using the
furnace for a longer period.
The different types (solid vs hollow), curing periods and RHA compositions were expected
to influence the mechanical and hygrothermal properties of the CEBs. These properties
were tested and are reported in the following sections of Chapter 4. As hollow blocks were
only intended for internal use, these were not tested for hygrothermal properties.
The mean bulk density values of the solid CEBs and duration of curing are shown in Table
4.4 and Figure 4.3 (abbreviated y-axis to illustrate this point).
116
Table 4.4. Bulk density of solid CEBs produced with varying partial replacement
of OPC with RHA
Code Duration of curing RHA (%) OPC (%) Bulk density
(days) (kg/m3)
Mean ± SD
S/0 RHA 14 0 100 1891.8 ± 14
0% RHA 21 0 100 1790.7 ± 57
28 0 100 1768.2 ± 40
S/0.2 RHA 14 10 90 1885.7 ± 12
10% RHA 21 10 90 1816.6 ± 16
28 10 90 1855.5 ± 19
S/0.4 RHA 14 20 80 1916.0 ± 28
20% RHA 21 20 80 1738.0 ± 34
28 20 80 1783.8 ± 26
S/0.6 RHA 14 30 70 1860.7 ± 41
30% RHA 21 30 70 1782.0 ± 28
28 30 70 1777.7 ± 27
S/0.8 RHA 14 40 60 1935.9 ± 51
40% RHA 21 40 60 1782.0 ± 31
28 50 60 1756.1 ± 29
S/1 RHA 14 50 50 1800.2 ± 43
50% RHA 21 50 50 1791.5 ± 39
28 50 50 1824.4 ± 49
117
Table 4.5. Bulk density of hollow CEBs produced with varying partial
replacement of OPC with RHA
Results presented in Table 4.6 (below) depict the effect of RHA and duration of curing on
the bulk density of CEB for solid blocks. Considering the influence of curing - the mean
bulk density values were highest in blocks cured for 14 days (1881.7 ±47.57 kg/m3), lowest
in blocks cured for 21 days (1775.4 ±32.80 kg/m3), while values for blocks cured for 28 days
curing were 1793.3 to ±39.15 kg/m3. Considering the influence of RHA content – the lowest
(1790.7± 64.53 kg/m3) mean bulk density value was recorded at S/0.6 RHA (30%) inclusion,
while the highest (1852.6 ± 34.64 kg/m3) was found at S/0.2 RHA (10%) inclusion.
118
Table 4.6. Effect of RHA inclusion and curing duration on the bulk density of solid
CEBs
1860
1850
Bulk desnity (Kg/3)
1840
1830
1820
1810
1800
1790
1780
0 10 20 30 40 50 60
% RHA
Figure 4.3 Effect of RHA inclusion on bulk
density of experimental Solid CEBs
The results for hollow CEBs are shown in Table 4.7 and Figure 4.4. Considering the
influence of curing – the mean bulk density values ranged from (low) 1808.37±24.4 kg/m3
in block cured for 21 days to (high) 1851.5±88.21 kg/m3 in block cured for 28 days.
Considering the influence of RHA content - the lowest was recorded for H/0.8 RHA (40%
RHA) with values 1791.7±27.38 while the highest was recorded for H/0 RHA (0% RHA -
control block) with 1867.3±68.55.
119
Table 4.7. Effect of RHA inclusion and curing duration on the bulk density of
hollow CEBs
1880
1870
Bulk density (Kg/m3)
1860
1850
1840
1830
1820
1810
1800
1790
1780
0 10 20 30 40 50 60
% RHA
Figure 4.4 Effect of RHA inclusion on bulk
density of experimental Hollow CEBs
For solid blocks, the bulk mean density of blocks cured for 14 days was found to be higher
than those cured for longer periods; however, this finding did not hold for hollow blocks.
There was no clear difference relating to RHA content for solid or hollow blocks. Nor was
there a clear difference in the bulk mean density between solid and hollow blocks.
The findings related to bulk density are discussed further in Section 6.2.1.1.
4.2.2 Compressive strength of experimental CEBs
The methodology used to determine compressive strength of the CEBs was described in
section 3.3.2. The results of compressive strength of the experimental solid and hollow
CEB with varying levels of RHA at different curing duration are presented in Tables 4.8 and
4.9, respectively. Mean values of compressive strength ranged from 2.39 ± 0.3 N/mm2
120
being the lowest and 6.39 ± 0.5 N/mm2 being the highest in the solid CEB. In case of hollow
CEB 0.61 ± 0.1 N/mm2 and 2.68 ±0.1 N/mm2 were least and highest values, respectively.
The results indicate that the solid CEBs were stronger than the hollow type.
Table 4.8. Compressive strength of solid CEBs produced with varying partial
replacement of OPC with RHA
Code Duration of curing RHA (%) OPC Compressive strength
(days) (%) (N/mm2)
Mean ± SD
S/0 RHA 14 0 100 4.86 ± 0.4
21 0 100 4.21± 0.3
28 0 100 5.34 ± 0.6
S/0.2 RHA 14 10 90 4.61± 0.2
21 10 90 5.83± 0.2
28 10 90 6.39 ± 0.5
S/0.4 RHA 14 20 80 3.92 ± 0.2
21 20 80 4.26 ± 0.3
28 20 80 4.08 ± 0.3
S/0.6 RHA 14 30 70 4.08 ± 0.4
21 30 70 3.89 ± 0.5
28 30 70 3.12 ± 0.4
S/0.8 RHA 14 40 60 3.63 ± 0.1
21 40 60 3.58 ± 0.3
28 50 60 2.99 ± 0.2
S/1 RHA 14 50 50 2.39 ± 0.3
21 50 50 3.84 ± 0.1
28 50 50 3.22 ± 0.4
121
Table 4.9. Compressive strength of hollow CEBs produced with varying partial
replacement of OPC with RHA
Code Duration of RHA OPC (%) Compressive strength
curing (days) (%) (N/mm2)
Mean ± SD
H/0 RHA 14 0 100 2.22 ± 0.4
21 0 100 2.30 ± 0.4
28 0 100 2.68 ±0.1
H/0.2 RHA 14 10 90 2.61 ±0.6
21 10 90 2.45 ± 0.2
28 10 90 2.45 ±0.2
H/0.4 RHA 14 20 80 1.46 ± 0.1
21 20 80 1.53 ± 0.1
28 20 80 1.92 ± 0.1
H/0.6 RHA 14 30 70 1.38 ± 0
21 30 70 1.46 ±0.1
28 30 70 1.46 ± 0.1
H/0.8 RHA 14 40 60 1.30 ± 0.3
21 40 60 1.38 ± 0
28 50 60 1.30 ± 0.1
H/1 RHA 14 50 50 0.61 ± 0.2
21 50 50 0.61 ± 0.1
28 50 50 0.84± 0.3
Mean values of compressive strength of experimental CEBs cured from 14 to 28 days for
solid blocks are shown in Table 4.10. Considering the influence of curing – the mean
compressive strength ranged from (low) 3.92±0.873 N/mm2 in blocks cured for 14 days to
(high) 4.27 ±0.803 N/mm2 in blocks cured for 21 days. However, the difference in the
compressive strength between different curing periods was not clear.
Considering the influence of RHA content - the results show that the values varied from
(low) 3.15±0.732 N/mm2 for the group with 50% RHA inclusion to (high) 5.61±0.910 N/mm2
for the group with 10%RHA inclusion. The group having 10% RHA inclusion has a higher
compression strength than the groups with higher RHA inclusions and were comparable to
CEBs stabilised using OPC only.
122
Table 4.10. Effect of RHA inclusion and curing duration on the compressive
strength of experimental solid CEBs
RHA (%) Compressive Strength (N/mm2)
Day 14 Day 21 Day 28 Mean ± SD
0 4.86 4.21 5.34 4.80±0.567
10 4.61 5.83 6.39 5.61±0.910
20 3.97 4.26 4.08 4.10±0.146
30 4.08 3.90 3.12 3.70±0.510
40 3.63 3.58 2.99 3.40±0.356
50 2.39 3.85 3.22 3.15±0.732
Mean ± SD 3.92±0.873 4.27 ±0.803 4.19 ±1.393
Figure 4.5 illustrates the trend in the compressive strength of the solid CEBs as affected by
the RHA inclusion. The picture depicted suggests that inclusion of RHA in the mix caused
the reduction of strength by almost half.
6
Compressive strength (N/mm 2)
0
0 10 20 30 40 50 60
% RHA
Figure 4.5 Effect of RHA inclusion on compressive
strength of experimental solid CEBs
Mean values of compressive strength of experimental CEBs cured from 14 to 28 days for
hollow blocks are shown in Table 4.11. Considering the influence of curing - the mean
compressive strength was least (1.6±0.65 N/mm2) after 14 days curing and highest (1.78
±1.393 N/mm2) after 28 days of curing. However, the difference in the compressive
strength between different curing periods was not clear.
123
The results show that the values varied with varying levels of RHA inclusion in the mix.
The group having 10% RHA inclusion recorded the highest value (2.40 ± 0.17 N/mm2)
while the group with 50%RHA inclusion had the least value (0.69±0.09 N/mm2). The
group having 10% RHA inclusion has a higher compressive strength than the groups with
higher RHA inclusions and was comparable to CEBs stabilised using OPC only. The
group with 50% RHA had a compressive strength which was lower than all other groups
tested. The group with 40% RHA had a compressive strength which was lower than all
other groups tested apart from those containing 50% RHA. Although there was an
overlap in the compressive strength results from groups containing 20 and 30% RHA, the
overall trend that increased RHA proportion reduces the compressive strength appears to
hold true for hollow blocks.
Table 4.11. Effect of RHA inclusion and curing duration on the compressive
strength of experimental hollow CEBs
Figure 4.6 illustrates the trend in the compressive strength of the hollow CEBs as affected
by the RHA inclusion.
124
6
Compressive strength
5
(N/mm2)
4
0
0 10 20 30 40 50 60
% RHA
Figure 4.6 Effect of RHA inclusion on
compressive strength of experimental hollow
CEBs
For curing periods of 14 and 21 days, the solid blocks show a higher compressive
strength than hollow blocks. There is not a difference in compressive strength for blocks
cured for 28 days for solid and hollow blocks. Considering RHA content, the “solid”
version of each RHA content has a higher compressive strength than the “hollow” version
with the same RHA content.
The findings for compressive strength are further discussed in Section 6.2.1.2.
125
Table 4.12. Water absorption capacity of solid CEBs produced with varying partial
replacement of OPC with RHA
Code Duration of curing RHA (%) OPC Water absorption
(days) (%) capacity
(%)
Mean ± SD
S/0 RHA 14 0 100 5.25 ± 0.16
21 0 100 7.43 ± 0.45
28 0 100 8.75 ± 0.47
S/0.2 RHA 14 10 90 5.40 ± 0.54
21 10 90 8.89 ± 0.24
28 10 90 5.88 ± 1.07
S/0.4 RHA 14 20 80 5.60 ± 0.65
21 20 80 9.66 ± 2.29
28 20 80 5.95 ± 0.82
S/0.6 RHA 14 30 70 6.88 ± 0.48
21 30 70 9.67 ± 1.23
28 30 70 7.90 ± 1.82
S/0.8 RHA 14 40 60 4.31 ± 0.87
21 40 60 8.51 ± 1.99
28 40 60 9.17 ± 2.29
S/1 RHA 14 50 50 7.68 ± 0.65
21 50 50 9.43 ± 1.03
28 50 50 7.43 ± 0.83
126
Table 4.13. Water absorption capacity of hollow CEBs produced with varying
partial replacement of OPC with RHA
Code Duration of curing RHA (%) OPC Water absorption
(days) (%) capacity
(%)
Mean ± SD
H/0 RHA 14 0 100 6.07 ± 1.46
21 0 100 7.38 ± 0.47
28 0 100 5.84 ± 1.66
H/0.2 RHA 14 10 90 5.34 ± 1.60
21 10 90 5.24 ± 0.77
28 10 90 6.16 ± 0.35
H/0.4 RHA 14 20 80 4.26 ± 0.93
21 20 80 6.70 ± 1.17
28 20 80 6.59 ± 0.42
H/0.6 RHA 14 30 70 6.61 ± 1.39
21 30 70 8.03 ± 0.25
28 30 70 6.99 ± 1.13
H/0.8 RHA 14 40 60 6.83 ± 0.89
21 40 60 7.40 ± 1.00
28 50 60 8.47 ± 1.53
H/1 RHA 14 50 50 7.96 ± 1.48
21 50 50 6.71 ± 1.14
28 50 50 7.15 ± 0.23
The mean water absorption capacity of the test solid CEB samples presented in Table 4.14
revealed that the lowest (4.31 ± 0.87%) and the highest (9.66 ± 2.29%) values were
obtained at 14 and 21 days of curing, respectively. Also, the least value (6.76±1.59%) and
the highest value (8.20±0.91%) were recorded in blocks that had 10% and 50%,
respectively.
127
Table 4.14 Water absorption capacity of solid CEBs with varying RHA levels
cured for 14, 21 and 28 days
Figure 4.7 illustrates the trends in the water absorption capacity of the solid CEBs as
affected by RHA inclusion. However, none of the RHA compositions performed differently
from the control sample (0% RHA). Similarly, there was no clear difference in water
absorption capacity between different curing periods.
9
Water absoprtion capacity
8
7
6
5
(%)
4
3
2
1
0
0 10 20 30 40 50 60
% RHA
The mean water absorption capacity of the test hollow CEB samples presented in Table
4.15 revealed that the lowest (5.85±1.11%) and the highest (9.01±0.85%) values were
obtained at 14 and 21 days of curing, respectively. Also, the least value (6.76±1.59) and
the highest value 8.20±0.91%) were recorded in blocks that had 10% and 50% RHA,
respectively
128
Table 4.15 Water absorption capacity of hollow CEBs with varying RHA levels
cured for 14, 21 and 28 days
Figure 4.8 illustrates the trends in the water absorption of the hollow CEBs as affected by
RHA inclusion. The group having 10% RHA inclusion has a lower water absorption capacity
than the groups with 40% or higher RHA inclusions. However, there was no clear difference
in water absorption capacity between different curing periods.
9
8
7
6
Water absorption capacity
5
4
3
(%)
2
1
0
0 10 20 30 40 50 60
% RHA
Figure 4.8 Effect of RHA inclusion on water
absorption capacity on experimental hollow
CEBs
The findings for water absorption capacity are further discussed in Section 6.2.1.3.
Time
Mass change ∆mt /A
√t (secs) ∆mt (kg)
mean ± SD (kg/m2)
(hr) (secs)
130
40
35
30
∆mt /A (kg/m2) 25
20
15
10
0
0 50 100 150 200 250 300 350
√t (secs)
Fig 4.9 Water content change over surface area and
square root of time in 24 hrs (control, S/0 RHA)
Using equation 3.17, Water coefficient for S/0 RHA (Control)= 0.09 kg/m2 s1/2
Time
Mass change ∆mt /A
√t (secs) ∆mt (kg)
mean ± SD (kg/m2)
(hr) (secs)
131
40
35
30
∆mt /A (kg/m2)
25
20
15
10
0
0 50 100 150 200 250 300 350
√t (secs)
Fig 4.10 Water content change over surface area and
square root of time in 24 hrs (S/0.2 RHA)
Using equation 3.17, Water coefficient for S/0.2 RHA (Control)= 0.10 kg/m2 s1/2
Time
Mass change ∆mt /A
√t (secs) ∆mt (kg)
mean ± SD (kg/m2)
(hr) (secs)
132
40
35
30
∆mt /A (kg/m2)
25
20
15
10
0
0 50 100 150 200 250 300 350
√t (secs)
Figure 4.11 Water content change over surface area
and square root of time in 24 hrs (S/0.4 RHA)
Using equation 3.17 Water coefficient for S/0.4 RHA (Control)= 0.10 kg/m2 s1/2
Time
Mass change
√t (secs) ∆mt (kg) ∆mt /A (kg/m2)
mean ± SD
(hr) (secs)
133
40
35
30
∆mt /A (kg/m2)
25
20
15
10
0
0 50 100 150 200 250 300 350
√t (secs)
Figure 4.12 Water content change over surface area and
square root of time in 24 hrs (S/0.6 RHA)
Using equation 3.17 Water coefficient for S/0.6 RHA (Control)= 0.10 kg/m2 s1/2
Time
Mass change ∆mt /A
√t (secs) ∆mt (kg)
mean ± SD (kg/m2)
(hr) (secs)
134
40
35
30
∆mt /A (kg/m2)
25
20
15
10
5
0
0 50 100 150 200 250 300 350
√t (secs)
Using equation 3.17 Water coefficient for S/0.8 RHA (Control)= 0.12 kg/m2 s1/2
Time
Mass change
√t (secs) ∆mt (kg) ∆mt /A (kg/m2)
mean ± SD
(hr) (secs)
135
40
35
30
∆mt /A (kg/m2)
25
20
15
10
0
0 50 100 150 200 250 300 350
√t (secs)
Figure 4.14 Water content change over surface area and
square root time in 24 hrs (S/1 RHA)
Using equation 3.17, Water coefficient for S/0.8 RHA (Control)= 0.089 kg/m2 s1/2.
The water absorption coefficient of experimental CEB at different RHA inclusion levels are
shown in Table 4.24. The results indicated that water absorption coefficient ranged from
0.089 (kg/m2 s1/2) at 50%RHA inclusion to 0.12 (kg/m2 s1/2) at 40%RHA inclusion. All the
plots of change in mass per area against square root of time exhibited curvilinear graphs.
Table 4.22 Water absorption coefficient of experimental solid CEB at different RHA
inclusion level
%RHA Water absorption
Type of Graph
coefficient
(kg/m2 s1/2)
0 0.090 Curvilinear
10 0.100 Curvilinear
20 0.100 Curvilinear
30 0.100 Curvilinear
40 0.120 Curvilinear
50 0.089 Curvilinear
*Experiment was conducted within the laboratory temperature conditions of 25±5oC
The findings for water absorption coefficient are further discussed in Section 6.2.2.1.
136
4.2.5 Water Vapour Transmission of Compressed Earth Blocks
The methodology used to determine the water vapour transmission was described in
Section 3.3.5. Solid blocks which had been cured for 28 days were tested and control
blocks were not tested, the result are to be extrapolated from literature. This test was not
applied to hollow blocks which are intended for internal use.
The results of mass changes due to moisture content until equilibrium is reached for
experimental CEBs with varying RHA are presented in Table 4.25. This data is then
illustrated graphically in Figures 4.15– 4.19. The hygroscopic properties are then presented
in Table 4.23.
0 - 0 0 0 0 0
137
0.25
R² = 0.5832
0.15
0.1
0.05
0
0 50000 100000 150000 200000 250000 300000 350000 400000
Time (s)
Figure 4.15 Changes in moisture contents in CEBs at
10%RHA (S/0.2 RHA) inclusion
The figure 4.15 plotted was plotted to get the slope of the moisture change until equilibrium
is achieved. The slope of the figure is 4E-07
0.25
Moisture change (Kg)
0.2
0.15
0.05
0
0 100000 200000 300000 400000
Time (s)
The figure 4.16 plotted was plotted to get the slope of the moisture change until equilibrium
is achieved. The slope of the figure is 2E-07
138
0.25
0.2
0.1
y = 1E-07x + 0.006
0.05 R² = 0.933
0
0 100000 200000 300000 400000
Time (s)
Figure 4.17 Changes in moisture contents in CEBs at
30%RHA (0.6 RHA) inclusion
The figure 4.17 plotted was plotted to get the slope of the moisture change until equilibrium
is achieved. The slope of the figure is 1E-07
0.25
0.2
Moisture change (Kg)
0.15
y = 3E-07x - 0.018
0.1 R² = 0.6777
0.05
0
0 50000 100000 150000 200000 250000 300000 350000 400000
Time (s)
-0.05
Figure 4.18 Changes in moisture contents in CEBs at
40%RHA (S/0.8 RHA) inclusion
The figure 4.18 plotted was plotted to get the slope of the moisture change until
equilibrium is achieved. The slope of the figure is 3E-07
139
0.25
Moisture change (Kg)
0.2
0.15
0.1
y = 1E-07x + 0.002
0.05 R² = 0.9875
0
0 100000 200000 300000 400000
Time (s)
Figure 4.19 Changes in moisture contents in CEBs at
50%RHA (S/1 RHA) inclusion
The figure 4.19 plotted was plotted to get the slope of the moisture change until equilibrium
is achieved. The slope of the figure is 1E-07
Density of water vapour rate, water vapour permeance, water vapour resistance, water
vapour permeability of the CEB and of the air, and water vapour resistance factor were all
computed, and the results are shown in Table 4.26. The results showed consistently that
excepting water vapour resistance factor and water vapour permeability of air, other
parameters were higher in CEB in which 10%RHA was included. Water vapour permeability
of air remained constant in all the treatment groups.
140
Table 4.24 Hygroscopic properties of CEB at various RHA inclusion
0 10 20 30 40 50
The findings for water absorption coefficient are further discussed in Section 6.2.2.2.
141
Table 4.25 Changes in moisture contents in CEB at varying levels of RHA
inclusion (moisture absorption)
10
Moisture content (%)
0
0 20 40 60 80 100
% Relative humidity
142
10
Moisture content(%)
8
0
0 20 40 60 80 100
% Relative humidity
Figure 4.21:Equilibrium Moisture
content curve of CEBs with 10% RHA (S/0.2 RHA)
10
8
Moisture content (%)
0
0 20 40 60 80 100
% Relative humidity
Figure 4.22: Equilibrim Moisture
content curve with 20% RHA (S/0.4 RHA)
143
10
Moisture content (%)
8
0
0 20 40 60 80 100
% Relative humidity
The findings for moisture absorption are further discussed in Section 6.2.2.3.
144
Table 4.26. Influence of stabilization on moisture buffering value of CEBs
Tests with 30% RHA (S/0.6 RHA) and 40% RHA (S/0.8 RHA) were not carried out.
However, this was not considered to be a problem as all other samples (including a sample
with 50% RHA) had been classified as “Good” or better.
The findings for moisture absorption are further discussed in Section 6.2.2.4.
The test was carried from August –September 2018. Test of four samples with different
RHA content (S/0 RHA, S/0.2 RHA, S/0.4 RHA and S/1 RHA) were taken during this period.
The pair tested together consisted of 0% and 50% for the first round and the 10% and 20%
for the second round. Each pair were tested for two weeks.
The result shown in Figure 4.24- 4.27 are clean library result for the duration for determining
thermal conductivity value for each of the different CEBs with varying RHA. The result had
to be clean because during the duration of the test, there was interrupted power supply
which created a low temperature different of the internal side of the box to the external side
of the box.
145
Figure 4.24 :Compressed Earth Block stabilized
with OPC(control)
2
1.5
1
0.5
0
36
71
1121
1016
1051
1086
1
911
106
141
176
211
246
281
316
351
386
421
456
491
526
561
596
631
666
701
736
771
806
841
876
946
981
Series1 Series2
1161
1001
1041
1081
1121
1201
1241
1281
1
681
121
161
201
241
281
321
361
401
441
481
521
561
601
641
721
761
801
841
881
921
961
Series1 Series2
1033
1076
1119
1162
1205
1248
1291
1
474
990
130
173
216
259
302
345
388
431
517
560
603
646
689
732
775
818
861
904
947
Series1 Series2
Key
Series1: actual running mean of the thermal conductivity test
Series 2: the average of the running mean of the thermal conductivity test
x- axis: the time
y-axis: the value of thermal conductivity (W/m.K)
146
Figure 4.27: 50% RHA partially replace OPC in
Compressed Earth Blocks
2
1.5
1
0.5
0
36
71
1016
1051
1086
1121
1
351
561
106
141
176
211
246
281
316
386
421
456
491
526
596
631
666
701
736
771
806
841
876
911
946
981
Series1 Series2
Key
Series1: actual running mean of the thermal conductivity test
Series 2: the average of the running mean of the thermal conductivity test
x- axis: the time
y-axis: the value of thermal conductivity (W/m.K)
The results of mean thermal conductivity are presented in Table 4.29 and Figure 4.28 of
the tested CEBs with varying RHA
Table 4.29: Thermal Conductivity of CEBs masonry wall with varying RHA content
Thermal conductivity (W/m.K) Bulk density (kg/m3)
% RHA
0.87 1816.9
0%
0.55 1852.6
10%
0.61 1812.6
20%
0.57 1805.4
50%
1
Thermal conductivty (W/m.K)
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0% 10% 20% 30% 40% 50% 60%
% RHA
Figure 4.28: Thermal conductivity for masonry CEBs
stabilized with RHA
The findings for thermal conductivity are further discussed in Section 6.2.2.5.
147
5. Simulation Results
_______________________________________________________________________
This chapter reports the findings from two simulation investigations. Firstly, the simulation
of mould growth and interstitial condensation is reported in Section 5.1. Then the
simulation for thermal comfort performance is reported in Section 5.2.
148
5.1.1.2 Wall system
A range of wall systems were considered in the literature review (Section 2.8.1). The design
for the compressed earth block wall (intended to be used for affordable and sustainable
design) could use two different types of wall systems. The wall system was designed
bearing in the mind the following factors:
a. A cavity is required to prevent ingress of driving rain. The options for this were:
i. masonry (CEB) external wall with plaster (EP)
ii. masonry (CEB) external wall partially filled with insulation (NP)
Both options (EP and NP) were chosen for further investigation because the masonry
wall with cavity prevent driving rain from the inner skin of the wall.
b. The CEB thickness was determined by the typical dimensions and placement of CEBs
during construction, the thickness of a typical CEBs and cavity gives a typical U-value
of wall requirement in Nigeria.
c. The Option EP with external plaster is to increase the hygrothermal property of the
outer skin layer. The external plaster is commonly used as the external wall finish in
Nigeria. This option is illustrated in Figure 5.1.
d. The Option NP has partially filled cavity to increase the hygrothermal property of the
wall. It designed to creates an extra layer of thermal insulation from external condition
and the cavity to prevent driving rain form penetrating the internal skin layer. The
addition MDF as insulation material was in order to use a typical insulating material and
one that the cost of the material compared to Option EP is similar. This option is
illustrated in Figure 5.2.
The masonry wall options were input to WUFI Pro 5.3 and are illustrated in Figures 5.1
and 5.2. These illustrations also show the assumed monitor positions on the internal and
external surfaces
Both wall conditions will be simulated for the CEB materials selected in Section 5.1.1.
The walls are simulated to use for external purpose. The wall properties are described in
Table 5.2.
150
5.1.1.2. External boundary condition
The boundary condition relates to the external situation and as such relates to the climate
in Lagos, Nigeria as described below. As a wall is being tested, the inclination is specified
as 90o (vertical).
The image in Figure 5.3 shows the direction and annual sum of the driving rain. As South
West is one of the orientations experiencing the most driving rain, this orientation is selected
for testing. The minimum mean and maximum relative humidity and temperature are
presented in Table 5.3 along with mean wind speed and normal annual rain sum.
Simulation of the South West wall was carried out in WUFI as it’s the most challenging
option.
151
Table 5.4 External boundary condition of wall
Name Description Unit Value
Heat resistance includes longwave External wall (m2K/W) 0.0588
radiation
Shortwave radiation absorptivity Brick, clay, cream, 0.36
glazed
Longwave radiation emissivity Brick, clay, cream, 0.9
glazed
Adhering fraction of rain 0.7
The study aimed to compare the two wall design options (i.e. wall sections EP- and NP-)
used for each of the compressed earth blocks proposed for affordable and sustainable
building in Lagos, Nigeria (Southern Nigeria [Aw]). The wall section in Figures 5.4 and 5.5
would be used to further explain the different temperature, relative humidity, and moisture
content at the different sections of the wall. The point of reference would be used to
describe the mean condition of the eternal wall exposed to the internal and external
conditions annually. The position in mm is described in Table 5.4.
152
Figure 5.4: Point of reference (PR) through Wall section EP
153
Table 5.5 Distance of wall with varying Positions on wall
A-A 0 E-E 0
CONSTANTS Values
VARIABLES
154
5.1.2. Temperature Simulation results
The temperature gradient from external to interior surface of the wall structures in normal
and high internal relative humidity (more wet areas) conditions are presented in Sections
5.1.2.1-5.1.2.4. This is discussed further in Section 6.3.
Wall section 30%RHA (S/0.6 RHA) had the lowest temperature value (25.1oC) at PR D-D,
while 10%RHA (S/0.2 RHA) had the highest temperature value (25.7oC) at the same
reference point. The temperature of wall section EP showed a steady decrease from the
outer surface layer to the inner surface layer as illustrated in Figure 5.6.
Figure 5.6 also shows the temperature at different positions of the wall (mm from external
surface).
155
Figure 5.6: Temperature of wall section EP for areas
with normal internal relative humidity
30
29
Temperqature (oC)
28
27
26
25
24
23
11
17
26
38
55
79
0
6
160
106
125
139
148
155
165
173
183
199
220
248
270
286
296
304
Wall section (mm)
0% (S/0 RHA) 10% (S/0.2 RHA) 20% (S/0.4 RHA) 30% (S/0.6 RHA)
156
Figure 5.7: Temperature of wall section EP for areas
with high relative humidity
30
29
Temperature (oC)
28
27
26
25
24
23
18
34
56
84
0
8
160
174
105
121
131
138
144
149
155
166
184
200
221
249
271
287
297
305
Wall section (mm)
0% (S/0 RHA) 10% (S/0.2 RHA) 20% (S/0.4 RHA) 30% (S/0.6 RHA)
157
Figure 5.8 Temperature of wall section NP for
areas with normal relative humidity
30
29
Temperature (OC)
28
27
26
25
24
23
18
34
56
84
0
8
149
105
121
131
138
144
155
160
166
174
184
200
221
249
271
287
297
305
Wall section (mm)
158
Figure 5.9: Temperature of wall section NP for
areas with high relative humidity
30
29
Temperature (oC)
28
27
26
25
24
23
18
34
56
84
0
8
249
105
121
131
138
144
149
155
160
166
174
184
200
221
271
287
297
305
Wall section (mm)
The temperature of the internal surface of the wall for the two option EP and NP
in areas with high internal relative humidity and normal internal relative humidity
fall within the range of 25-26oC for all the varying CEBs wall with varying RHA.
159
Table 5.11, Relative humidity of Wall section EP at areas with normal
internal relative humidity
95
90
85
80
75
70
65
60
11
55
17
26
38
79
0
6
139
106
125
148
155
160
165
173
183
199
220
248
270
286
296
304
Wall section (mm)
0% (S/0 RHA) 10% (S/0.2 RHA)
20% (S/0.4 RHA) 30% (S/0.6 RHA)
5.1.3.2. Relative humidity simulation of Wall Section EP – with high internal relative
humidity
The RH results are presented in Table 5.12 in relation to EP Wall points of reference
(identified in Figure 5.1), PR A-A (exterior) had RH values which were 3.5-12.5% higher
than the values at PR D-D (the inner CEB). The relative humidity of the wall at the PR D-D
records the highest value at 30% RHA (S/0.6 RHA) and lowest value at 0% RHA (S/0RHA)
with value of 72.9% and 68.6% respectively.
95
90
85
80
75
70
65
60
18
34
56
84
0
8
105
121
131
138
144
149
155
160
166
174
184
200
221
249
271
287
297
305
Wall section (mm)
161
Figure 5.12: Relative humdity of wall section NP for
areas with normal relative humdity
100
Relative humidity (%)
95
90
85
80
75
70
65
60
18
34
56
84
0
8
105
305
121
131
138
144
149
155
160
166
174
184
200
221
249
271
287
297
Wall section (mm)
0% (S/0 RHA) 10% (S/0.2 RHA) 20% (S/0.4 RHA) 30% (S/0.6 RHA)
5.1.3.4. Relative humidity simulation of Wall Section NP – with high internal relative
humidity
The RH results are presented in Table 5.14 in relation to the EP Wall points of reference
(identified in figure 5.2). PR E-E (exterior) had RH values which were 7.7-17.1% higher than
the values at PR H-H at the inner CEB. Also, at the PR H-H, the wall section 30%RHA
(S/0.6 RHA) had the highest (68.7%) relative humidity value whereas the wall sections
0%RHA (S/0 RHA) and 20%RHA (S/0.4 RHA) had the lowest (64.0-64.1%). The trend
pattern of RH shown in Figure 5.13 was like those observed earlier. The RH of the wall
section NP regardless of the %RHA increased from PR E-E (External surface of outer
CEBs) towards F-F (surface of MDF facing air cavity), and thereafter decreased towards
PR G-G (Joints between air cavity and Internal CEBs); and finally dropped to the lowest
level at the PR H-H (Inner CEBs wall section).
162
Figure 5.13: Relative humidity of wall section NP
for areas with high relative humidity
100
174
105
121
131
138
144
149
155
160
166
184
200
221
249
271
287
297
305
Wall section (mm)
0% (S/0 RHA) 10% (S/0.2 RHA) 20% (S/0.4 RHA) 30% (S/0.6 RHA)
All the wall relative humidity for wall type EP and NP for CEBS with RHA of 0-20% have
relative humidity between 68-69%. The CEBs with RHA of 30% records relative humidity
70-75% except for wall NP for areas with high relative humidity.
Based on the figure 2.13 using the relative humidity and temperature of the material, there
is no mould growth likely to germinate on the internal wall surface on all walls type EP and
NP used in areas with high and normal internal relative humidity for all the varying RHA.
There is likely to be mould growth germination with category highly xerophilic organism for
wall type EP in areas with normal and high relative humidity and wall type NP for areas with
normal internal relative humidity.
The relative humidity and temperature alone are not enough to adequately predict mould
germination, the moisture content generated need to analyse to come to a certain
conclusion. The moisture buffering property of the material can also change the effect of
mould germination in the wall.
163
content increases from PR A-A (external plaster) to PR B-B (external CEBs), the moisture
in the air cavity reduces and continues to reduce to PR D-D (internal CEBs). The moisture
content for wall section 20% (S/0.4 RHA) has lowest value of 4.8 kg/m3 at PR B-B and
continues to reduce to PR D-D to have a value of 0.6 kg/m3, this wall type is the best in
areas with normal relative humidity environment. The next most suitable is wall section 30%
(S/0.6 RHA), the moisture content from the external surface of the wall at PR A-A to PR D-
D also reduces as it gets closer to the interior wall.
Figure 5.14 shows moisture content at each point within the wall section. The wall section
EP shows reduction of moisture content at the air cavity and reduces to the internal CEBs
at PR D-D. The highest moisture content through all the wall type for wall section EP at
areas with normal relative humidity is less than 60 kg/m3.
80
60
40
20
0
11
17
26
38
55
79
0
6
106
125
139
148
155
160
165
173
183
199
220
248
270
286
296
304
Figure 5.15 shows moisture content at each point within the wall section. The wall section
EP shows reduction of moisture content at the air cavity and reduces to the internal CEBs
at PR D-D. The highest moisture content through all the wall type for wall section EP at
areas with normal relative humidity is less than 60 kg/m3.
80
60
40
20
0
11
17
26
28
55
79
0
6
106
125
139
148
155
160
165
173
183
199
220
248
270
286
296
304
165
5.1.4.3. Moisture content at different positions in Wall Section NP – with normal
internal relative humidity
Table 5.17 shows the wall section 0% (0/ RHA) and 10% (0.2/RHA) show similar moisture
content at each point of reference (PR) E-E, value of 44.3 kg/m3 and 42.9 kg/m3. The PR
F-F (external CEBs) increase to value of 92.4 kg/m3 and 89.5 kg/m3. The moisture in the
blocks starts to decrease towards the partially filled cavity, PR G-G has value of 19.5 kg/m3
and 19.4 kg/m3. The point of PR H-H (Internal CEBs) reduces to 5.0 kg/m3 and 5.1 kg/m3
respectively.
The moisture content for wall section 20% (S/0.4 RHA) recorded its lowest values at each
point of reference (PR). The peak occurs at the PR F-F (point between air cavity and MDF)
has value of 62.9 kg/m3 and continue to reduce until PR H-H (Internal CEBs, though the
values are lowest the cavity of the wall shows high moisture absorption increase which
makes its unsuitable.
The next most suitable is wall section 30% (S/0.6 RHA), the moisture content for this type
is like wall type 20% (S/0.4 RHA) with slightly higher moisture content.
Figure 5.16 shows moisture content at each point of reference within the wall section. The
wall section NP shows the external CEBs wall in the wall section reduction of moisture
content within and reduces within the air cavity and rises at the MDF. The highest moisture
content through all the wall type for wall section NP at areas with normal relative humidity
is less than 100 kg/m3.
166
Figure 5.16: Moisture content in Wall section
NP for areas with normal relative humidity
areas
100
18
34
56
84
0
8
105
121
131
138
144
149
155
160
166
174
184
200
221
249
271
287
297
305
Wall section(mm)
0% (S/0 RHA) 10% (S/0.2 RHA)
20% (S/0.4 RHA) 30% (S/0.6 RHA)
The moisture content for wall section 20% (S/0.4 RHA) has lowest value at each point of
reference (PR). The peak occurs at the PR F-F (point between air cavity and MDF) has
value of 70.1 Kg/m3 and continue to reduce until PR H-H (Internal CEBs). Although the
internal moisture content is lowest in the internal layer of the wall, the moisture level in the
cavity is high which makes it unsuitable.
The next most suitable is wall section 30% (S/0.6 RHA), the moisture content for this type
is like wall type 20% (S/0.4 RHA) but is slightly higher.
167
Figure 5.17 shows moisture content at each point within the wall section. The wall section
NP shows moisture content reduce in the external CEBs and reduces further within the air
cavity and rises at the MDF. The highest moisture content through all the wall type for wall
section NP at areas with normal relative humidity is less than 100 kg/m3.
80
60
40
20
0
18
34
56
84
0
8
105
121
131
138
144
149
155
160
166
174
184
200
221
249
271
287
297
305
Wall section(mm)
5.1.5.1. Mould Growth on interior wall surface after 1 year: Section EP – with
normal internal relative humidity
Mould growth results are presented in Figure 5.18 for wall section EP with normal internal
relative humidity.
168
Figure 5.18: Mould growth on interior wall
surface EP in areas with normal relative
humidity
300
No Mould growth occurred on interior wall surface for CEBs wall section 0%, 10%, 20% for
1 year. The mould growth on wall CEBs 30% for 1 year was zero until, third quarter of the
year, and was less than 50mm at the end of the year.
5.1.5.2. Mould Growth on interior wall surface after 1 year: Section EP – with high
internal relative humidity
Mould growth results are presented in Figure 5.19 for wall section EP with high internal
relative humidity.
250
200
150
100
50
0
0 2000 4000 6000 8000 10000
Time (hours)
There was mould growth in all the EP wall sections in areas with high relative humidity. The
mould growth for CEB with 30% RHA was two times more than for CEBs with 0%, 10%,
and 20%. The mould growth for CEBs with 30% RHA is 258mm and that of 0%-20% CEBs
RHA wall is approximately 116mm.
169
5.1.5.3. Mould Growth on interior wall surface after 1 year: Section NP – with
normal internal relative humidity
Mould growth results are presented in Figure 5.20 for wall section NP with normal internal
relative humidity.
250
200
150
100
50
0
0 2000 4000 6000 8000 10000
Time (hours)
All the wall section with various degree of partial stabilization of RHA for wall section NP
had no mould growth on the interior wall surface after 1 year.
5.1.5.4. Mould Growth on interior wall surface after 1 year: Section NP – with high
internal relative humidity
Mould growth results are presented in Figure 5.21 for wall section NP with high internal
relative humidity.
250
200
150
100
50
0
0 2000 4000 6000 8000 10000
Time (hours)
All the wall section NP in areas with high relative humidity had mould growth of 107mm at
the end of the year.
170
5.1.5.5. Mould Growth – Summary
The wall sections with normal relative humidity showed little to no mould growth after a
year on all wall sections. These do not need further investigation. However, the wall
sections under high relative humidity showed mould growth which warrants further
investigation – these results are presented in section 5.1.6.
Table 5.19 Building use, proportion of OPC replacement with RHA, mould
growth and WUFI code
Building Proportion of OPC replaced Mould growth WUFI Bio
use with RHA depth (mm) code
0% 112.5
Option EP
High 10% 114.8
relative 20% 116.3
humidity 30% 257.9
0% 116
Option NP
High 10% 118
relative 20% 111
humidity 30% 105
0% 0
Option EP
Normal 10% 0
relative 20% 0
humidity 30% 25.2
0% 0
Option NP
Normal 10% 0
relative 20% 0
humidity 30% 0
5.1.6.1. Total water content after 1 year: Section EP – with high internal relative
humidity
Total water content results after 1 year are presented in Figure 5.22 for wall section EP with
high internal relative humidity.
171
Figure 5.22: Total water content in wall section
EP in areas with high relative humidity for 1
year
40
Total water content (kg/m2)
35
30
25
20
15
10
5
0
08/19 10/19 12/19 01/20 03/20 04/20 06/20 08/20 09/20 11/20
Date (mm/yy)
Total water content for all wall types at end of 1 year shows that water content doubles at
the third quarter of the year in wall section EP. The total water content is always less than
20 kg/m2.
5.1.6.2. Total water content after 1 year: Section NP – with high internal relative
humidity
Total water content results after 1 year are presented in Figure 5.23 for wall section NP with
high internal relative humidity.
35
30
25
20
15
10
5
0
08/19 10/19 12/19 01/20 03/20 04/20 06/20 08/20 09/20 11/20
Date (mm/yy)
Total water content for wall types at end of 1 year shows that the water content raises to
15-30 kg/m2 in the third quarter of the year for RHA contents of 0%, 10%, and 20%. The
total water content for wall type 30% RHA is stable throughout the year at less than 10
kg/m2.
172
5.1.6.3. Total water content after 3 years: Section EP – with high internal relative
humidity
Total water content results after 3 years are presented in Figure 5.24 for wall section EP
with high internal relative humidity.
40
35
30
25
20
15
10
5
0
05/19 12/19 06/20 01/21 07/21 02/22 08/22 03/23
Date (mm/yy)
Total water content for the wall section EP rises and drops as the total water content is
studied for 3 years. This shows that the wall absorbs and desorbs over time.
5.1.6.4. Total water content after 3 years: Section NP – with high internal relative
humidity
Total water content results after 3 years are presented in Figure 5.25 for wall section NP
with high internal relative humidity.
40
35
30
25
20
15
10
5
0
05/19 12/19 06/20 01/21 07/21 02/22 08/22 03/23
Date (mm/yy)
173
Total water content for wall type 0%, 10%, and 20% for wall section absorbs and desorbs
from less than 5 to 40 kg/m2. The total water content for wall type 30% RHA is stable for 3
years at a value of less than 10kg/m2.
30 88
Temperature (oC)
25 86
20 84
15 82
10 80
5 78
0 76
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
months
174
Table 5.20: Average Climatic data of Lagos, Nigeria (2000-2009)
(m/s) (dominant)
175
Figure 5.27: Wind direction and wind speed using wind rose.
300
250
rainfall(mm)
200
150
100
50
0
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
months
80%
Acceptable RH limits (80-90%)
25.1 Comfort low- min operative temperature in this climate (oC)
31.4 Comfort high- max operative temperature in this climate (oC)
Table 5.22: Time not achieving thermal comfort over 1 year - using Adaptive
comfort model at 90% and 80%
hrs % Hrs %
177
In relation to achieving 90% thermal satisfaction, there was little difference between CEB
(20% RHA) and concrete wall materials. In relation to achieving 80% thermal satisfaction,
the results were more variable. The two wall materials had similar performance for
24x15m shape structure. CEB (20% RHA) had a better performance for 36x10m shape
structure with 60% WWR, while the opposite result held true for 40% WWR.
178
6. Discussion
_______________________________________________________________________
A preliminary test was conducted on using the laterite soil and ordinary Portland cement to
make some samples of compressed earth block and cured for between 14 and 28 days.
The blocks during the curing period developed visible cracks and when lifted began to
crumble. Consequently, sand particles were introduced in the mix to reduce the proportion
of clay in the mix and to neutralize the effect of shrinkage and cracking.
179
Figure 6.1 Chart for the unified soil classification showing data points for laterite soil
used for this research (blue star) and soil analysed by Bodian et al (2018) (orange cross).
Acceptable properties for use in CEBs (Uzoegbo, 2020) indicated with rectangle. (Bodian
et al, 2018; Hind K.J, 2007; Uzoegbo, 2020)
The plastic index, plastic limit and liquid limit for laterite are similar with other findings from
literature (Anifowose, 2000; Bodian et al, 2018; Uzoegbo, 2020). These sources state that
it responds to stabilisation to improve compressive strength. Laterite soil (even when
adequately stabilized) may disintegrate over time when it’s not properly protected. The soil
property improves when compaction pressure increases to reduce the water absorption rate
in the soil.
180
Optimisation of the amorphous silica in the RHA was necessary for the economics of
production, and this could be ensured through the control of the combustion process. The
production process had a controlled time and temperature for combustion to ensure the
phase change of the ash does not reach crystalline state when burnt for too long and higher
temperature than required.
In the current research two methods of producing ash from the rice husk were tried. In the
first method, the rice husk was subjected to charring before igniting in the furnace for 2 –
3h. The charring process could be done by the indigent users who would use the rice husk
first as source of fuel for their local cooking, then the charred rice husk would be sent to the
furnace. The disadvantage of using this method is that the process to seek out the waste
might take a longer process before it goes to the furnace.
The second method for producing high amorphous silica rice husk ash can be achieved
ensuring a standard procedure for collecting the rice husk and combusting by the waste
management body converting the agricultural waste to rice husk ash. The waste from the
agricultural rice farm can be sourced directly by commercial industry and taken to the
furnace for combustion process and be bagged into to standard sizes for the end user
(construction industry).
To ensure that there is a form of standardization the second method that allows the
commercial industry to process or produce the rice husk ash is the most suitable method.
The combustion furnace is not easily available as mentioned is section 3.2.1.4 by a layman.
The management of RHA waste helps provide another income revenue to the farmers and
ensures that every part of the rice is made useful. The use of agricultural waste means there
can be a positive improvement of the urban metabolism of the country.
The volumes of solid and hollow blocks were 0.00386m3 and 0.00371m3, respectively. The
production of the hollow blocks required 3.9% less of materials than the solid blocks and
181
resulted in 0.39% of OPC less in hollow blocks than solid. This implied that hollow CEB
would save production cost and may be particularly economical in construction areas
requiring less compressive strength and hygrothermal property as in the internal partition
walls.
The curing process in an open environment is a common and affordable practice in the
Nigerian construction industry. The blocks were laid (as shown in Figures 3.6 and 3.7) in
an open environment where they remained covered with water-proof plastic film as covering
the blocks with waterproof plastic film to allow for curing. The blocks were prevented from
direct exposure to high solar radiation and rainfall but were sprayed with water intermittently.
Curing reduced the rate of moisture loss, thus preventing cracking of the blocks (Serbah et
al, 2018). Curing periods were 14, 21 and 28 days. The production and construction of the
compressed earth blocks in this research was intended for sustainable and affordable wall
material in Nigeria. Also, it was to incorporate simple and current method used by the semi-
skilled workers (laborers). Apart from combusting the RHA in the furnace and transporting
it and the laterite were transported to site, the remaining processes of block production and
curing were manual, so CEB production required low energy.
In the current research, ordinary Portland cement was replaced gradually with RHA at the
rates of 0% to 50% in the mix used to produce experimental compressed earth blocks. The
blocks were tested for mechanical and hygrothermal properties to ascertain the effects of
RHA on the properties of the blocks and or whether RHA replacing a proportion of the
cement would be acceptable as a stabilizing agent in CEB.
182
2019; Nshimiyimana et al, 2020) reported a range of between 0.4 and 12 N/mm2
(compressive strength) for CEB. (Nshimiyimana et al, 2020) recommended compressive
strength requirements for CEB use in the construction of wall structure for affordable and
sustainable building in the tropical climate including Nigeria – these are indicated in Table
6.1.
Table 6.1 Required CEB compressive strength for wall structures ((Nshimiyimana et al,
2020)
CEB use (Structure type) Required Compressive Strength (N/mm2)
Non-load bearing 2
Load bearing – 2 storeys 2-4
Load bearing – 3 storeys 3-6
In the present study, compressive stength for solid CEB ranged from 2.39 ± 0.3 to 6.39 ±
0.5 N/mm2 (Table 4.8). While compressive strength for hollow CEB ranged from 0.61 ± 0.1
to 2.68 ±0.1 N/mm2 (Tables 4.9). The results indicate that the solid CEBs were significantly
stronger than the hollow type. This may be due to the perforations in the hollow blocks, or
to the higher laterite mix composition.
Mansour et al. (2016) noted that the variation in the compressive strength values reported
for the CEB was due to the differences in the bulk densities (1800-2100 kg/m3) of the blocks.
The ranges of bulk density values obtained in the present study (1738.0 ± 34 to 1935.9 ±
51 kg/m3 in solid CEBs, and from 1753.9 ± 66 to 1977.9 ± 29 kg/m3 in hollow CEBs) as
presented in Tables 4.6 and 4.7 were lower than the range reported by Mansour et al.
(2016). The difference might be attributed to the differences in mixes used for the various
CEB in the earlier and current studies. However, positive correlation between compressive
strength and bulk density of the CEB was observed (Table 4.16), and the correlation
coefficient, r being 0.740422. The results, therefore, affirmed earlier findings reported by
Mansour et al. (2016).
Results shown in Table 4.10 indicated that compressive strength for solid blocks increased
with increased duration of curing up to 21 days but declined thereafter. The highest
compressive strength (4.27 ± 0.803 N/mm2) was attained at 21 days of curing. Also,
inclusion of RHA in the mix affected the compressive strength of the CEB where the group
having 10%RHA inclusion recorded the highest value (5.61±0.910 N/mm2) whereas the
group with 50%RHA inclusion had the least value (3.15±0.732 N/mm2). The results suggest
that inclusion of RHA in the mix beyond 10% resulted in the lowering of the compressive
strength. Indeed, the results of correlation analysis presented in Table 4.16 showed that
183
the correlation coefficient, r of the relationship between RHA inclusion in the aggregate mix
and compressive strength of CEB was -0.87885.
In both types of CEBs, substitution of OPC with 10% RHA raised the compressive strength
by about 4.2% and 16.9% beyond control CEBs which OPC alone.
All the solid CEBs would be considered acceptable for non-load bearing or load bearing
use in 2 storey buildings. All solid CEBs (excepting those with 40% RHA cured for 28 days
and 50% RHA cured for 14 days) would be considered acceptable for load bearing use in
3 storey buildings. Hollow CEBs with 10% RHA would be considered acceptable for non-
load bearing or load bearing use in 2 storey buildings according to (Nshimiyimana et al,
2020).
It was observed also that duration of curing affected water absorption capacity of the CEB.
The lowest (5.85±1.11%) and the highest (9.01±0.85%) values were obtained at 14 and 21
days of curing, respectively (Table 4.14). Water absorption capacity declined slightly
beyond 21 days of curing. The group having 10% RHA inclusion has a lower water
absorption capacity than the groups with 20% or higher RHA inclusions. However, there
was no clear difference in water absorption capacity between different curing periods. Both
the water absorption capacity and RHA inclusion were positively correlated. The correlation
coefficient, r was 0.67619. Also, the least value (6.76±1.59%) and the highest value
(8.20±0.91%) were recorded in blocks that had 10% and 50%, respectively. All the blocks
have acceptable water absorption capacity.
6.2.1.4. Relationship among the mechanical properties of CEB and the effect of
RHA inclusion
In order to examine any possible correlation among the RHA inclusion in the compressed
earth solid and hollow blocks and the mechanical properties of the latter, data obtained in
the study were subjected to correlation analysis. Results of the analysis are presented for
solid blocks in Table 6.2.
Bulk density is a function of the weight of material in a unit volume of space, whereas water
absorption capacity is a function of voids in the block. Therefore, an inverse relationship is
expected to exist between bulk density and water absorption capacity. Indeed, the results
184
of correlation analysis presented in Table 4.16 for solid blocks shows the negative
correlation between the two parameters (r = -0.86766). Also, water absorption capacity
was negatively correlated with compressive strength (r = -0.84013). On the other hand,
bulk density was positively correlated with the compressive strength (r = 0.740422). These
results indicate that greater force should be applied in the block-pressing machine in order
to increase the bulk density and compressive strength of the CEBs. All of the correlational
relationships as obtained in the current study agree with the relationships between these
properties reported in literature (Kolawole et al, 2020; Mansour et al, 2016).
The results (Table 4.16) indicated also that %RHA was negatively bulk density (r = -
0.43637) has a weak relationship and compressive strength (r = -0.87885) but was
positively correlated with water absorption capacity (r = 0.67619) of the CEB.
Results of the analysis are presented for solid blocks in Table 4.17 and it revealed that
whereas %RHA inclusion was negatively correlated with bulk density (r = -0.8048) and
compressive strength (r = -0.95452), it was positively correlated with water absorption
coefficient (r = 0.67619). Also, compressive strength was positively correlated with bulk
density (r = 0.775174) but negatively correlated with water absorption capacity (r = -
0.46535). Bulk density and water absorption capacity were negatively correlated (r = -
0.66708).
185
Table 6.3 Correlation coefficient (r) matrix for Hollow CEBs
%RHA Bulk density Compressive Water
3
(Kg/m ) strength absorption
(N/mm) capacity (%)
%RHA 1
Bulk density
-0.8048 1
(kg/m3)
Compressive
strength -0.95452 0.775174 1
(N/mm)
Water
absorption 0.678098 -0.46535 -0.66708 1
capacity (%)
In the current research, compressed earth blocks with varying RHA content had values
ranging from 0.089 - 0.12 kg/m2 s1/2 (Table 4.24). Water absorption coefficients of building
materials based on the tangent method of calculation reported include traditional handmade
clay brick, typical clay brick, and quarry stones, was recorded as 0.205 kg/m2 s1/2, 0.27
kg/m2 s1/2 and 0.085-0.10 kg/m2 s1/2 respectively (Karagiannis et al, 2016). Also,
(Mukhopadhyaya, 2002) reported water absorption coefficients to be temperature
dependent and had average for red clay brick 0.084 kg/m2 s1/2 and 0.065 kg/m2 s1/2 when
temperature was 21oC and 35oC respectively. The water absorption coefficient value for
light earth building material ranged from 0.027-0.135 kg/m2 s1/2 (Colinart et al, 2020). CEBs
analysed by (Lavie Arsène et al, 2020) had water absorption coefficients ranging from 0.09-
0.3 kg/m2 s1/2. The CEBs in this research have similar water absorption coefficients to those
reported for red clay bricks and earth materials.
186
6.2.2.2. Water vapour transmission
Water vapour test is about movement of moisture from a point of higher relative humidity to
a point of lower relative humidity. While conducting water vapour test, Liuzzi et al. (2017)
noted that water resistance factor was dependent on the bulk density of materials. Also,
BS EN 12524-2000 affirmed that materials varied in their water vapour resistance factor
according to their bulk densities. That is, fired clay bricks with bulk density 1000-2400 kg/m3
has water vapour resistance factor of 16 and 10 (dry and wet respectively), calcium silicate
brick with bulk density of 900-1200 kg/m3 had a resistance of 20 and 5 (dry and wet
respectively), concrete masonry with bulk density of 500-1300 kg/m3 had a water vapour
resistance of 50 and 40 (dry and wet conditions respectively) (BS, EN 12524:2000). The
implication is that the higher the water resistance factor is the more resistant the building
material is to water vapour passing through its structure. Therefore, a larger water vapour
resistant factor is more beneficial in a material to use in places that have high moisture or
high relative humidity such as Nigeria.
Similarly, documentation in the WUFI library on some building materials revealed that the
water vapour resistance factors were: concrete blocks with pumice aggregate has a vapour
resistance factor of 4 (664 kg/m3 bulk density); fired clay blocks has a vapour resistance
factor of 15 (800 kg/m3 bulk density), solid brick extruded has a vapour resistance factor of
9.5 (1650 kg/m3 bulk density); solid brick hand formed has a vapour resistance factor of 17
(1725 kg/m3 bulk density) and solid bricks historically has a vapour resistance factor of 15
(1800 kg/m3 bulk density).
In the current research, compressed earth blocks with varying RHA content had water
vapour resistance factor values ranging from 11.65-44.91 (Table 4.26), the highest values
relating to RHA content of 20% and 50%, which had comparable water vapour resistance
factor values to concrete masonry
Moisture absorption of test material is a function of the quantity of water vapour absorbed
from the climatically controlled environment. Consequently, the relative humidity and
temperature of the environment affect the moisture absorption of the test material. The
experimental CEB were subjected to the test and the moisture absorption equilibrium
curves were plotted (Figures 4.21 – 4.25). The water absorption patterns shown by the
various CEB indicated that regardless of the level of inclusion of RHA (and its non-inclusion)
water absorption increased progressively, though at different rates, as the relative humidity
increased. The results thus suggested that inclusion of RHA in the CEB affected water
absorption properties of the latter (Table 4.27). Indeed, moisture absorption rate increase
when relative humidity increases from 33%- 85%; For the inclusion of RHA, CEBs material
0% RHA,10% RHA, 20% RHA and 40% RHA has an increase of 3.6%,4.8%, 2.2% and
187
3.5% respectively. The result obtained in this study agrees with the findings of Wang et al.
(2020) who reported that the addition of fibre increased moisture absorption in geopolymer
concrete reinforced by polypropylene fibres but the results obtained in this study agree with
the findings of Ouedraogo et al. (2020), who reported that stabilization of earth with 4-8%
cement reduces moisture adsorption rate by 20%. Replacement of ordinary Portland
cement by up to 40% with RHA in the CEB aggregate mix resulted in 33.985% reduction in
the moisture absorption (Table 4.28). However, 10% replacement caused an increase of
19.535% in moisture absorption. The results tended to suggest that up to 10% replacement
of ordinary Portland cement with RHA was not enough to serve as a stabilizing agent in the
CEB and hence could not cause a reduction in the moisture absorption in the earth block.
For practical application, Hola et al (2017) classified masonry wall into five categories
according to the moisture absorption or content as: I, permissible moisture content (0.3%);
II, masonry with elevated moisture content (>3-5%); III, medium damp masonry (>5-8); IV,
very damp masonry (>8-12%); and V, wet masonry wall (>12%). Nigeria’s climate being
tropical – hot and humid, surface walls are exposed to a range of relative humidity would
remain medium damp unless the wall has adequate buffering property. The continuous
exposure to moisture could cause chipping of wall and mortar, and crystallization of salts
on the wall material. This would lead to continuous degradation of the material’s strength,
cross section area and load bearing capacity of the wall. Furthermore, it would affect the
wall surface finishing – mould growth, deterioration and peeling of the paint, etc. The CEBs
with 20% RHA is the most suitable material for external use (Hola, 2017).
The incidence of mould and indeed biological growth on the wall surface is a function of the
wall material’s ability to absorb or release moisture from its structure. Also, the ability of the
material to mitigate the effect of wetness or high moisture absorption of the masonry wall is
dependent on the moisture buffering characteristic of the material (Hola et al., 2017). The
moisture buffering values (MBV) of the experimental CEB in the current research are shown
in Table 4.28. The range of MBV obtained in this study (i.e. 1.2 – 2.1 g/m2 %RH) agrees
with literature values of 1.2-3.9 g/m2 %RH (Rode et al. 2005; Zhang et al. 2017; Bruno et al
2017). In addition, application of the NORDTEST classification (Rode et al. 2005; Zhang
et al. 2017) indicated that RHA inclusion in the CEB’s aggregate mix remarkably affected
the moisture buffering value of the CEB where RHA inclusion of 0%,10%, 20%, 40%
boosted the moisture buffering characteristic. Indeed, the CEB with RHA up to 40% made
them good. The excellent moisture buffering characteristic of the CEB would be of pactical
importance in the provision of affordable low-cost housing in Nigeria. The excellent
moisture buffering ability of the CEB to which RHA has been included would ameliorate the
188
effect of high moisture absorption encountered in the humid and hot tropical climate of
Nigeria in areas where earth compressed blocks are used for building construction.
The thermal conductivity of compressed earth bricks/blocks has been studied by several
workers, and values reported include 0.52 – 0.72 W/m.K (Doubi et al, 2017) and 0.79 – 1.10
W/m.K (Saidi, 2018). The results of thermal conductivity of the experimental blocks in the
current study are shown in Table 4.29. The thermal conductivity values ranged from 0.55
to 0.87 W/m. K and they were within the ranges reported in the literature. The results record
that thermal conductivity of the CEB was affected remarkably by the inclusion of RHA in the
aggregate mix. There was a decrease in thermal conductivity when RHA was included in
the mix from 0.87 W/m. K for blocks with no RHA to 0.55-0.61 W/m.K.
Doubi et al. (2017) observed that in cement-stabilized compressed earth bricks addition of
shea butter wastes improved porosity that explained the improvement of the thermal
insulation properties of the bricks. Furthermore, addition of the agricultural wastes caused
reduction of the bulk density of the bricks. Finally, the authors were able to establish a
positive correlation between bulk density and thermal conductivity. The results indicate that
RHA has improved the thermal insulating property of the CEBs.
Thermal conductivity is a key parameter in the calculation of the U-value which is commonly
used to compare the thermal performance of wall systems. The U-value of wall section EP
without inclusion of RHA was 1.299 W/m2K. More RHA inclusion further reduced the U-
value to 1.136 W/m2K and 1.146 W/m2K at 10% and 30% RHA inclusions, respectively.
The U-value of wall section NP was 1.22 W/m2K for CEBs without RHA inclusion. Similarly,
the U-value reduced with inclusion of RHA to 1.076 and 1.086 for 10%RHA and 30% RHA,
respectively. In earlier study, (Olaniyan, 2012) noted that the U-value of external walls in
building construction using hollow sandcrete blocks in Nigeria was 1.035 W/m2K.
Therefore, the findings of the current research indicated that without and with inclusion of
the RHA up to 30% in the aggregate mix of the experimental CEB the latter was suitable for
the construction of external wall of buildings in Nigeria.
A summary of the mechanical properties of the CEBs is presented in Table 6.4 and 6.5.
This focuses on the suitability of the CEBs for application, where prime considerations were
given to ensuring that the material would be safe and structurally sound for the intended
use. From the mechanical properties, it is found that hollow blocks are generally not
suitable for load-bearing applications and are eliminated from the hygrothermal analysis.
The common practice of curing masonry unit in Nigeria is a maximum of 28 days, the CEBs
cured for 28 days were therefore ideal for simulation of hygrothermal properties.
189
Table 6.4 Suitability of solid CEBs for application based on mechanical properties
RHA (%) Curing time (Day) Compressive strength for wall Water
structures ((Nshimiyimana et al, absorption
2020) capacity
0 14 3 storey No issue
21 3 storey No issue
28 3 storey No issue
10 14 3 storey No issue
21 3 storey No issue
28 3 storey No issue
20 14 3 storey No issue
21 3 storey No issue
28 3 storey No issue
30 14 3 storey No issue
21 3 storey No issue
28 3 storey No issue
40 14 3 storey No issue
21 3 storey No issue
28 2 storey No issue
50 14 2 storey No issue
21 3 storey No issue
28 3 storey No issue
190
Table 6.5 Suitability of hollow CEBs for application based on mechanical
properties
RHA (%) Curing time (Day) Compressive strength for wall Water
structures ((Nshimiyimana et al, absorption
2020) capacity
0 14 3 storey No issue
21 3 storey No issue
28 3 storey No issue
10 14 3 storey No issue
21 3 storey No issue
28 3 storey No issue
21 N/A No issue
28 N/A No issue
30 14 N/A No issue
21 N/A No issue
28 N/A No issue
40 14 N/A No issue
21 N/A No issue
28 N/A No issue
50 14 N/A No issue
21 N/A No issue
28 N/A No issue
191
Table 6.6 Suitability of solid CEBs for application based on hygrothermal
properties
From a combination of mechanical and hygrothermal properties (Tables 6.2 and 6.4), it was
decided to eliminate CEBs with 40% or 50% RHA from the simulation studies. Although
these had similar hygrothermal performance to the CEBs with lower RHA content, their
compressive strength performance was poorer.
The results in the current research showed that the temperature of the wall sections in areas
with normal and high relative humidity values shows that temperature reduced
progressively from the external to the internal space (Figure 5.6-5.9). The results inferred
that heat transfer into the internal wall was retarded. This could be considered a good
property to have in this climate.
The results of relative humidity of all the wall sections are shown in Figures 5.10 – 5.13.
Throughout the year, the relative humidity of the wall surfaces was less than 100%, a
condition required for condensation to occur. So, there was no occurrence of condensation
on the external or inner wall surfaces.
The highest relative humidity on internal surface of the wall section EP were 76.2% and
72.9% for areas with normal and high relative humidity. The highest RH values were
obtained in wall having 30% RHA inclusion. The wall section NP relative humidity also
reduces at the internal surface to 74.5 and 68.7%, again for 30% RHA inclusion. The
moisture value for areas with high and normal relative in the interior surface reduces in wall
section NP compared to EP.
The wall should be studied to understand the moisture content on the whole wall section.
The areas where normal and high relative humidity prevails, the wall section EP had
moisture content of less than 30 kg/m3. The wall section also showed that the cavity in the
wall retarded movement of moisture from the external layer to the internal layer. In the
cases of all wall types in NP, moisture movement reduced from external to the cavity but
increased towards internal surface. This phenomenon might promote mould growth inside
the wall section where the MDF insulation is placed where normal and high relative humidity
are prevalent.
A key consideration in this investigation is mould growth. Figures 5.18-5.21 show the
simulated mould growth on each wall type and humidity condition over a period of a year.
In regions where normal relative humidity is prevalent, the inclusion of RHA beyond 20%
might result in potential mould growth in the wall section EP. Inclusion of 30% RHA resulted
in the wall section having less than 50mm mould growth. Testing on WUF bio, resulted in
a green traffic signal indicated that it is acceptable. However, in the case of regions where
high relative humidity is common, the highest mould growth on the wall section EP occurred
at 30% RHA inclusion and reached approximately 200mm. Testing on WUF bio showed a
193
red traffic signal, indicating that the material is not suitable in the region. The wall types
having 0%, 10% and 20% RHA inclusion had mould growth of less than 200mm, showed
yellow signal on the WUFI bio, suggesting further investigation was required.
The results of the present study showed further that no mould growth occurred on the
interior surface of wall section NP that had been partially stabilized with varying percentages
of RHA in regions where normal relative humidity is prevalent. On the other hand, under
the condition of high relative humidity, mould growth on the interior wall surface was more
than 50mm but less than 200mm. In addition, yellow traffic signal was observed.
Consequent upon the results of total water contents and mould growth on all the wall types
in the regions where high relative humidity is prevalent, further investigation was required.
This was carried out as a study on the changes in total water content for wall section types
EP and NP in high humidity and is illustrated over 1 year in Figures 5.22-5.23 and over 3
years in Figures 5.24-5.25. The water content in wall section absorbs for a quarter of the
year and desorbs for the three quarter of the year for wall type EP. This pattern shows that
the wall structure can desorb satisfactorily after absorbing. The study revealed that wall
type NP absorbed water for a quarter of the year, and it desorbed for three quarter of the
year. The wall type NP showed a higher water content than the wall section EP as shown
in Figures 5.24 and 5.25.
194
Table 6.7 Suitability of solid CEBs for application based on results from mould
growth and interstitial condensation simulation
NP Normal 5 0 Green -
10 EP Normal 5 0 Green -
From the findings so far, CEB with 20%RHA inclusion was considered the most suitable
material using the wall type EP. This was because it combined the highest possible RHA
content (displacing expensive OPC) with suitable properties for use in the region where
normal and high relative humidity conditions are prevalent. This material and wall type were
analysed further for thermal comfort performance (Section 6.4).
195
6.4. Thermal comfort simulation
Prior to undertaking thermal comfort simulation, key passive design strategies for cooling
were considered in relation to the building. Key factors to be included in the design of the
simplified structure are:
• appropriate building orientation and form to minimise solar gains and facilitate
natural ventilation for cooling (long axis running North South) with large openings
to receive cooling breezes.
• Thermal mass to reduce heat absorption and to use in conjunction with night cooling
in appropriate climates.
• Cross ventilation to allow easy natural flow of air into the building to improve thermal
comfort.
• Pitch insulated roof to allow the flow of rainwater easily and reduce the solar heat
gain from the roof.
• Shading of the windows and walls using the roof overhang (Ogunsote et al, 2010).
Consequent upon the above, the performance of the simplified structure incorporating 20%
RHA CEBs in the wall section was compared to the wall section with concrete.
According to ASHRAE 55-2010 Adaptive comfort standard, the 80% and 90% thermal
comfort satisfaction temperature and relative humidity for tropical savanna climate where
natural ventilation only is prevalent are 25.1 - 31.4oC and 80 - 90% and 23.1 - 29.4oC and
80 - 90%, respectively (Table 5.18). Banerjee et al. (2020) noted 19.5 - 31oC as the thermal
comfort temperature of people inhabiting in the tropical climate, which shows a reasonable
agreement with the 90% thermal comfort satisfaction conditions. The relative humidity
ranged from 70% to 100%.
The climate data presented in Table 5.17, indicated that the outside air temperatures were
higher than acceptable comfort levels in February to May. Also, for Lagos, Nigeria the wind
was from the south western direction. The wind brings moist air with high relative humidity
from the Atlantic Ocean.
For 90% satisfaction in the base building design (24x15m) there was little difference in the
number of hours where thermal comfort was achieved (Table 5.19). The use of CEB
provided thermal comfort for the user for 74% of the hours at a 90% thermal satisfaction
level. At an 80% thermal satisfaction level, this increased to 80% of hours. These results
were like those using concrete with same U value in the Aw climate in Nigeria.
An initial investigation was able to increase the hours in comfort by elongating the building
(keeping the same floor area) and reducing the window wall ratio. A more detailed
investigation could potentially further increase the hours in comfort.
196
7 Conclusion and contribution to knowledge
_______________________________________________________________________
7.1 Introduction
The concept of this research was based on the need to provide a possible solution for
deficit of residential houses for the low-income earner in Nigeria. The deficit of residential
houses in Nigeria is because of growing urbanisation and inadequate planning to meet
expansion. Nigeria is a developing country that has a large population of people living
below the poverty level as discussed in Section 2.1, there is a need for low-cost building
that minimises harm to the present and future environment. The present generation of
low-income earners have created an organic response to the income inequality faced to
provide housing for themselves through slums, dilapidated houses, squatter housing,
unauthorised land development, room, or flats in uncompleted or dilapidated houses. One
in 7 people live in informal settlement (Gan et al. 2017). The people are then faced with
problems such as overcrowding, inadequate waste management, poor health, poor
sanitary systems, insecure residential status, and poor structural buildings. The
government have tried to create more houses from the period when the country gained
her independence. The reason for the deficit was because of the high cost for providing
residential buildings, inadequate policies, poor planning, and mismanagement as
indicated in Section 2.2.4. Based on this research, the government needs inclusion of the
people that require the houses, agricultural industry, and construction industry to work as
a team to ensure the system works. The methods for construction of the buildings for the
low-income earners require minimum energy as the country experiences interrupted
power supply daily. It also requires simple method of construction, so the people can build
their houses themselves and reduce the cost of the construction by eliminating expensive
devices and reducing labour. The construction of medium rise building to reduce the land
use caused by low rise building is the most suitable. The construction industry can have
positive impact by improving by encouraging low energy and low emission products,
introducing low carbon material and technology (i.e earth) and embracing circular
economy (IEA, 2019). The construction industry uses about 36% of related emission
globally (Cao et al, 2016) and 70 of energy consumption in residential buildings in 2018.
By aiming to a more sustainable material, design, and principles; the cost of building can
also be reduced as indicated in Section 2.1.
197
7.1.1 Aim and objectives
The aim of this research was to investigate the provision of a possible low cost,
sustainable building material for wall construction in Nigeria. To provide this solution the
research concentrated on using locally sourced material (earth) partially stabilized with
pozzolanic agricultural waste to reduce the amount of ordinary Portland cement (OPC)
that was used in the construction of houses. The reduction of OPC means an
improvement on the environment caused by reducing the pollution caused by the cement
industry in the country over time and the preservation of the raw material for the future
generation. The use of local material (laterite soil) and reduction of OPC for wall material
has significant potential to reduce the cost of the material (Section 2.1).
1. To investigate the raw materials, particularly proportions of laterite, RHA, OPC and
sharp sand needed to produce RHA CEBs for walls in the tropical savanna climate
of Nigeria.
2. Evaluate the mechanical and hygrothermal properties of the resulting CEBs and
analyse them against wall construction requirements.
3. Simulate the hygrothermal and thermal performance to evaluate indoor air quality
and thermal comfort.
7.2 Conclusions
The first objective was to investigate the raw materials, particularly the proportions
required to produce RHA stabilised CEBs for walls. The selection of RHA as the most
suitable pozzolanic material for this research, was based on the following factors.
i.) the availability of RHA: the selection of rice husk ash (RHA) as the most suitable
pozzolan to be used for the tropical savanna climate is because of the proximity of the
raw rice husk and the amount of waste produced from the agricultural industry to
meet the needs of the users. Laterite and sand are also readily available to the
potential site of construction. This means there would be reduction in the cost of
transportation, emission of greenhouse gas (GHG) to the environment from the trucks
commonly used in the country. It also means a potential reduction on the damage to
the roads infrastructure which uses a large amount of the country’s available funds for
maintenance. It is the most accessible pozzolan compare to SBA, POFA to tropical
savanna climate urban areas in the country.
ii.) the ease of processing RHA to get high silica content required for the
pozzolanic reaction to occur processing the rice husk ash (RHA) will be a
challenging initially, as experienced during the research. Furnaces are required
which burn at a controlled temperature (550-700oC). Such a furnace was found at a
198
private sculptor. To provide energy for the combustion of the furnace the purchase of
hydrocarbon gas from a fuelling station is needed regularly. The device is not
connected to the electrical grid of the country. The reason for not connecting the grid
was the large amount of power the furnace required and the electricity supply in the
country is unstable and inadequate. The controlled combustion of rice husk to rice
husk ash ensures that there is high amorphous silica content of about 80-96%.
Amorphous silica ensures that there is pozzolanic reaction in the particles when water
is added to the mix. Although there are challenges involved for production of RHA;
OPC required higher combustion temperature of 14500C and expensive equipment to
manufacture.
The most appropriate proportions of laterite, RHA, OPC and sharp sand required to
produce RHA stabilised CEBs was based on the results of mechanical and hygrothermal
properties (objective 2). The conclusions based on mechanical properties are presented
in section 7.2.1, while the conclusions based on hygrothermal properties are presented in
section 7.2.2.
The final objective was to simulate the hygrothermal and thermal performance to evaluate
indoor air quality and thermal comfort. The conclusions based on indoor air quality are
presented in Section 7.2.3, while the conclusions based on thermal comfort are presented
in Section 7.2.4.
199
Table 7.1 %RHA compositions which meet required CEB compressive strength for
wall structures
Structure type Required compressive strength Appropriate CEB type and RHA
(N/mm2) composition
The curing process of the blocks is very important to achieve the required strength of the
masonry unit. The blocks need to be cured for a minimum of 21 days to get optimum
strength.
Hollow CEBs with RHA of 30% or greater lack enough compressive strength to be used in
wall construction. Further hygrothermal testing of hollow blocks was not carried out, as
the material did not meet the required mechanical property for load-bearing wall material.
The water absorption coefficient of samples tested in the laboratory (Table 4.12) shows
that RHA stabilised samples have similar characteristics to fired clay bricks
(Mukhopadhyaya, 2002) and earth material (Colinart et al, 2020). The water absorption
coefficient for sample with RHA inclusion 10%, 20%, 30%, and 50% have lower values
compared to control sample with only OPC stabilisation.
The water vapour transmission reflects the change in mass of a wall sample due to
relative humidity changes (related to seasonal and diurnal changes). The water vapour
resistance factor for samples with 10% RHA (11.65) has similar resistance compared to
fired clay bricks (16) and concrete with expanded clay as main aggregate with (8) (BS, EN
ISO 10456:2007) which are common masonry materials used in Nigeria. The inclusion of
20-50% increase the water resistance factor compared to other masonry materials.
200
The moisture absorption for in CEB samples with 20% RHA was lower than the control
sample (0% RHA). All other RHA inclusions caused an increase in moisture absorption
compared to the control sample.
The moisture buffering value property of the building materials has a significant effect on
the amount of energy required to cool building in Nigeria. The higher the buffering value of
building material the lower the energy required to cool the building. All the tested
compressed earth blocks show values that can be categorised as good or excellent. The
CEBs with RHA inclusion of 10% had better performance than control CEBs which were
only stabilised with OPC.
The thermal conductivity property of CEBs with inclusion of RHA were all significantly
lower than the control (0% RHA). CEBs with 10% RHA had the lowest thermal
conductivity. The CEBs exhibited favourable thermal conductivity performance to common
building bricks (0.6-1.0 W/m. K) and was comparable with concrete (0.4-0.7 W/m. K)
(Engineering Toolbox A, No Date).
Based on the mechanical and hygrothermal property analysis of the CEBs, inclusion of
RHA from 10-30% have properties which are similar or better than conventional wall
materials in Nigeria.
Full year simulation of two wall types (full cavity and partial cavity) in high relative humidity
spaces (e.g., bathroom or kitchen) and normal relative humidity spaces, utilising solid
CEBs with 0%, 10%, 20% and 30% RHA assessed temperature, relative humidity,
moisture content, mould growth and total water content for a full year. From this, the most
suitable wall design for Nigeria could be identified.
The masonry wall design with cavity partially filled with thermal insulation material (MDF)
(NP) does not have mould growth on internal side of the wall in spaces with high and
normal internal relative humidity. However, this wall design wasn’t chosen because of
201
high relative humidity within the internal cavity which could cause mould growth in the wall
cavity. This would adversely affect the wall durability.
For a full cavity masonry wall (EP) RHA inclusions up to 20% were suitable for both high
and normal relative humidity spaces. The inclusion of RHA beyond 20% was found to
have potential to allow mould growth on the wall.
This wall construction was compared to a “typical” concrete wall structure for a 360m2
dwelling. The comparison was based on the hours “not comfortable” at 90% satisfaction
levels. The number of hours “not comfortable” achieved for CEBs partial stabilised with
20% RHA were like concrete walls using the same design strategy and building area.
202
b. solid CEBs have approximately double the compressive strength of hollow
CEBs.
4) Data from a comprehensive study of hygrothermal properties for solid CEBs with
OPC replaced by 0%, 10%, 20%, 30%, 40%, 50% RHA. This meets a research
gap identified after the literature review and concludes that up to 30% of OPC can
be replaced with RHA in solid CEBs while meeting the required mechanical and
hygrothermal properties for load-bearing walls up to 3 storeys.
5) Data from hygrothermal simulation of full cavity and partially insulated cavity wall
structures over a full year for the tropical savannah climate of Nigeria. This
considered the impact of high humidity internal spaces (eg kitchen, bathroom) as
well as normal humidity internal spaces on the hygrothermal performance of the
wall structures utilising solid CEBs with 0%, 10%, 20% and 30% for temperature,
relative humidity, moisture content, mould growth and total water content (also
evaluated over 3 years). This data indicates structures which could cause
potential indoor air quality issues with mould growth which could affect occupant
health and comfort as well as potential impact on the durability of the structure.
This meets a research gap identified after the literature review and concludes that
the full cavity wall type is less liable to excessive humidity in the cavity which could
reduce the wall durability. This is achieved while minimising the environmental /
economic impact.
6) Data from thermal simulation over a full year for the tropical savannah climate of
Nigeria. This considered a dwelling with 360m2 floor area. 90% satisfaction “not
comfortable” hours are very similar for the CEB and concrete structures, which is
considered acceptable, particularly since CEB is a more cost-effective structure
material. “Not comfortable” hours at 80% satisfaction could be reduced to 16.2%
of the year using CEB full cavity wall with 20% RHA CEBs without introducing any
mechanical ventilation or cooling. This is an important finding as Nigeria’s
electricity supply is not stable and some houses only receive supply for 3 hours a
day, energy supply in Nigeria is costly when available.
7) As the use of local materials has been found to reduce the total cost of housing to
approximately 50% (Olotuah, 2002), proving the capability of CEBs for use in wall
construction, gives an opportunity for residential dwellings to be made more
affordable to Nigeria’s low-income earners.
8) As a typical concrete mixture (1 part cement, 2 parts sand, 4 parts aggregate)
contains 14% cement (discounting water and entrained air), while CEB stabilised
with 20% RHA contains 8% cement, a structure has been proposed which
significantly reduces the amount of OPC required with corresponding drop in
environmental impacts. Particularly since the remaining CEB production is labour
intensive with little fossil fuel requirement.
203
7.3.1 Limitation of research
Simulations were only analysed for the tropic savannah climate in Nigeria. This climate
was chosen because it covers a larger area and population than each of the other three
climates. It cannot be assumed that simulation findings for tropic savannah climate apply
to the other climates, particularly the arid climates. Besides, simulation cannot include
every situation and that the computer software are unable to create real-life
situations. However, computer simulation offers the advantage of providing guidance
towards a possible solution or model creation. Furthermore, it serves as a stopgap where
it is impossible to have real-life experience. Because of limitations of time and resources,
therefore, the application of computer simulation for the tropical climate was chosen to
understand the model of mould growth and thermal comfort of the CEB/RHA wall.
i.) The condensation and interstitial condensation of the building material to ensure
that adequate indoor air quality is meant needs to be analysed on the material.
ii.) The full environmental impact of RHA stabilised CEBs. This would include
greenhouse gas (GHG) emissions, embodied energy, operating energy (assuming
uninterrupted power supply available for mechanical services), treatment at end of
life.
iii.) The financial cost of raw materials, labour required for construction of the CEBs.
iv.) To obtain the hygrothermal property (mould growth) and thermal performance of
CEBs partially stabilized with RHA in this research, the numerical simulation was
applied. Further test to achieve a more realistic result could apply the in-situ
measurement research approach in future studies.
7.4 Summary
The stated aim of this research was to investigate the provision of a possible low cost,
sustainable building material for wall construction in Nigeria. This has been achieved.
Solid CEB with RHA at 20% replacement of OPC has been selected as having the best
combination of maximum OPC replacement while attaining appropriate mechanical and
hygrothermal properties. In some cases, properties such as moisture buffering, water
absorption coefficient, water absorption capacity, water vapor transmission, the inclusion
of RHA provides improved characteristics of the CEB masonry unit.
The 20% RHA CEB has also been found suitable in relation to the impact on occupant’s
health and thermal comfort. Hygrothermal simulation under the local climate conditions
204
indicates there is unlikely to be a risk of internal condensation and mould generation.
Thermal simulation was undertaken for a free-running building as the local electricity
supply is expensive and erratic. The thermal simulation showed similar thermal comfort
hours for CEB with 20% RHA and for concrete walls. Although there was no improved
comfort for CEB with 20% RHA, this replacement does not cause a detrimental effect on
the user.
The major environmental impacts from concrete arise from cement, which is
approximately 14% of concrete (excluding water and entrained air). CEBs with 20% of
the cement substituted from RHA reduces the cement content to 8%. The remaining
material was sourced locally and utilised waste material as a pozzolan. The use of local
materials has been indicated as delivering a 50% saving in the construction cost (Olotuah,
2002) while the labour-intensive nature of CEB production also minimises energy used in
the process.
The introduction of the proposed compressed earth blocks partially stabilized with 20% RHA
would affect the economy, environment, and social aspect of the country. The lack of
adequate funds to reduce the housing deficit can be combated by using locally available
material, cheaper labour, and low-cost equipment to provide wall material which will also
improve the economy of the country. The constant build-up of the slums and informal
settlement in the urban city can be reduced when the CEBs masonry is used which will
improve the environment over time.
205
8 Reference
_______________________________________________________________________
Abd Rashid, A. F. & Yusoff, S. (2015) A review of life cycle assessment method for
building industry. Renewable and Sustainable Energy Reviews, 45(Supplement C), 244-
248.
Adabre, M. A., Chan, A. P. C., Darko, A., Osei-Kyei, R., Abidoye, R. & Adjei-Kumi, T.
(2020) Critical barriers to sustainability attainment in affordable housing: International
construction professionals’ perspective. Journal of Cleaner Production, 253, 119995.
Adam, E. A. & Agib, A. R. A. (2001) Compressed Stabilised Earth Block Manufacture in
Sudan. Improvement of Educational Facilities in the Least Developed Countries of the
Arab
States, 522.
Ade Bilau, A., Witt, E. & Lill, I. (2018) Research methodology for the development of a
framework for managing post-disaster housing reconstruction. Procedia Engineering, 212,
598-605.
Adedokun, A. (2014) Incorporating Traditional Architecture into Modern Architecture:
Case Study of Yoruba Traditonal Architecture. British Journal of Humanities and Social
Sciences, 11(1), 39-45.
Akadiri, P. O. (2015) Understanding barriers affecting the selection of sustainable
materials in building projects. Journal of Building Engineering, 4, 86-93.
Al-Saadi, H. (2014) Demystifying Ontology and Epistemology in Research Methods.
Alabsi, A. A. N., Song, D. X. & Garfield, W. H. (2016) Sustainable Adaptation Climate of
Traditional Buildings Technologies in the Hot Dry Regions. Procedia Engineering,
169(Supplement C), 150-157.
Almeida, F. C. R., Sales, A., Moretti, J. P. & Mendes, P. C. D. (2015) Sugarcane bagasse
ash sand (SBAS): Brazilian agroindustrial by-product for use in mortar. Construction and
Building Materials, 82, 31-38.
Alsubari, B., Shafigh, P. & Jumaat, M. Z. (2016) Utilization of high-volume treated palm oil
fuel ash to produce sustainable self-compacting concrete. Journal of Cleaner Production,
137, 982-996.
Amin, N. (2011) Use of bagasse ash in concrete and its impact on the strength and
chloride resistivity. ASCE J Mater Civ Eng, 23(5), 717–20.
Anifowose, A. Y. B. (2000) Stabilisation of lateritic soils as a raw material for building
blocks. Bulletin of Engineering Geology and the Environment, 58(2), 151-157.
206
Antiohos, S. K., Papadakis, V. G. & Tsimas, S. (2014) Rice husk ash (RHA) effectiveness
in cement and concrete as a function of reactive silica and fineness. Cement and
Concrete Research, 61–62, 20-27.
Aprianti, E., Shafigh, P., Bahri, S. & Farahani, J. N. (2015) Supplementary cementitious
materials origin from agricultural wastes – A review. Construction and Building Materials,
74, 176-187.
Arthur, H. & Kessler, D. W. (1950) Thermal and Moisture Expansion studies of some
domestic granites. Journal of research of the national bureau of standards.
Ashby, M. F. (2013) Materials and the environment : eco-informed material choice, 2nd
ed. edition. Oxford : Butterworth-Heinemann.
Ashour, T., Korjenic, A., Korjenic, S. & Wu, W. (2015) Thermal conductivity of unfired
earth bricks reinforced by agricultural wastes with cement and gypsum. Energy and
Buildings, 104, 139-146.
Aste, N., Adhikari, R. S., Del Pero, C., Leonforte, F. & Timis, I. (2017) Sustainable
Building Design in Kenya. Energy Procedia, 105(Supplement C), 2803-2810.
ASTM (Standard D 4318 2005) Standard Test Methods for Liquid Limit, Plastic Limit,and
Plasticity Index of Soils. ASTM International, West Conshohocken, PA.
Baden-Powell, C. (2011) Architect's Pocket bookRoutledge Ltd-M.U.A.
Bahurudeen, A., Kanraj, D., Gokul Dev, V. & Santhanam, M. (2015) Performance
evaluation of sugarcane bagasse ash blended cement in concrete. Cement and Concrete
Composites, 59, 77-88.
Bahurudeen, A., Marckson, A. V., Kishore, A. & Santhanam, M. (2014) Development of
sugarcane bagasse ash based Portland pozzolana cement and evaluation of compatibility
with superplasticizers. Construction and Building Materials, 68, 465-475.
Bahurudeen, A. & Santhanam, M. (2015) Influence of different processing methods on the
pozzolanic performance of sugarcane bagasse ash. Cement and Concrete Composites,
56, 32-45.
Beck, H. E., Zimmermann, N. E., McVicar, T. R., Vergopolan, N., Berg, A. & Wood, E. F.
(2018) Present and future Köppen-Geiger climate classification maps at 1-km resolution.
Scientific Data, 5(1), 180214.
Berge, B. (2000) The ecology of building materialsOxford : Butterworth-Heinemann.
Berto. L, Saetta. A, Scotta. R & Vitaliani. R (2005) Failure mechanism of masonry prism
loaded in axial compression: computational aspects. Materials and structures, 38(2), 249-
256.
Binici, H., Aksogan, O., Bakbak, D., Kaplan, H. & Isik, B. (2009) Sound insulation of fibre
reinforced mud brick walls. Construction and Building Materials, 23(2), 1035-1041.
Bodian, S., Faye, M., Sene, N. A., Sambou, V., Limam, O. & Thiam, A. (2018) Thermo-
mechanical behavior of unfired bricks and fired bricks made from a mixture of clay soil and
laterite. Journal of Building Engineering, 18, 172-179.
207
BRE (Report 2014) In-situ measurements of wall U-values in English housing. Department
of Energy and Climate Change.
Britain, S. F. o. G. (2011) Natural stone, the oldest sustainable material. Stone Federation
of Great Britain.
BS (5250:2011+A1:2016) Code of practice for condesation in building.
BS (EN 771-1:2011+A1:2015) EN 771-1:2011+A1:2015: Specification for masonry units.
Clay masonry units.
BS (EN 772-1:2011+A1:2015) EN 772-1:2011+A1:2015: Methods of test for masonry
units. Determination of compressive strength.
BS (EN 772-4: 1998) EN 772-4: 1998: Methods of test for masonry units. Determination of
real and bulk density and of total and open porosity for natural stone masonry units.
BS (EN 772-21:2011) EN 772-21:2011: Method of test for masonry units. Determination of
water absorption of clay and calcium silicate masonry units by cold water absorption.
BS (EN 1934:1998) EN 1934:1998: Thermal performance of buildings. Determination of
thermal resistance by hot box method using heat flow meter. Masonry.
BS (EN 12524:2000) EN 12524:2000: Building materials and products- hygrothermal
proerties- Tabulated design values.
BS (EN ISO 10456:2007) EN ISO 10456:2007: Building materials and products-
Hygrothermal properties- Tabulated design values and procedure for determining
declared and design thermal values.
BS (EN ISO 12571:2013) EN ISO 12571:2013: Hygrothermal performance of building
materials and products — Determination of hygroscopic sorption properties.
BS (EN ISO 12572:2016) EN ISO 12572:2016: Hygrothermal performance of building
materials and products. Determination of water vapour transmission properties. Cup
method.
BS EN. (13788:2012) 13788:2012: Hygrothermal performance of building components
and building elements. Internal surface temperature to avoid critical surface humidity and
interstitial condensation. Calculation methods.
BS (EN ISO 14688-1:2018) EN ISO 14688-1:2018: Geotechnical investigation and
testing. Identification and classification of soil. Identification and description.
BS (EN ISO 14688-2:2018) EN ISO 14688-2:2018: Geotechnical investigation and
testing. identification and classification of soil. Principles for a classification.
BS (EN ISO 15148:2002+A1:2016) EN ISO 15148:2002+A1:2016: Hygrothermal
performance of building materials and products. Determination of water absorption
coefficient by partial immersion.
208
Engelbrecht, C. J. & Engelbrecht, F. A. (2016) Shifts in Köppen-Geiger climate zones over
southern Africa in relation to key global temperature goals. Theoretical and applied
climatology, 123, 247-261.
211
Ganesan, K., Rajagopal, K. & Thangavel, K. (2008) Rice husk ash blended cement:
Assessment of optimal level of replacement for strength and permeability properties of
concrete. Construction and Building Materials, 22(8), 1675-1683.
Gberevbie, D. (2010) Strategies for employee recruitment, retention and performance:
Dimension of the Federal civil service of Nigeria. African Journal of Business
Management, 4, 1447-1456.
Givi, A. N., Rashid, S. A., Aziz, F. N. A. & Salleh, M. A. M. (2010) Assessment of the
effects of rice husk ash particle size on strength, water permeability and workability of
binary blended concrete. Construction and Building Materials, 24(11), 2145-2150.
Givoni, B. (1992) Comfort, climate analysis and building design guidelines. Energy and
Buildings, 18(1), 11-23.
González-Jorge, H., Puente, I., Riveiro, B., Martínez-Sánchez, J. & Arias, P. (2013)
Automatic segmentation of road overpasses and detection of mortar efflorescence using
mobile LiDAR data. Optics & Laser Technology, 54(Supplement C), 353-361.
GTM-7 (2015) Geotechnical test method: Test method for liquid limit, plastic limit, and
plasticity indest.
Gradeci, K., Labonnote, N., Time, B. & Köhler, J. (2017) Mould growth criteria and design
avoidance approaches in wood-based materials – A systematic review. Construction and
Building Materials, 150, 77-88.
Gradeci, K., Labonnote, N., Time, B. & Köhler, J. (2018) A probabilistic-based
methodology for predicting mould growth in façade constructions. Building and
Environment, 128, 33-45.
Sadovský, Z. & Koronthályová, O. (2017) Exploration of probabilistic mould growth
assessment. Applied Mathematical Modelling, 42, 566-575.
Gumaste, K. S., Rao, K. S. N., Reddy, B. V. V. & Jagadish, K. S. (2007) Strength and
Elasticity of brick masonry prims and wallettes under compression. Materials and
structures, 40(2).
Gyurkó, Z., Jankus, B., Fenyvesi, O. & Nemes, R. (2019) Sustainable applications for
utilization the construction waste of aerated concrete. Journal of Cleaner Production, 230,
430-444.
Habeeb, G. A. & and Fayyadh, M. M. (2009) Rice Husk Ash Concrete: the Effect of RHA
Average Particle Size on Mechanical Properties and Drying Shrinkage. Australian Journal
of Basic and Applied Sciences, 3(3), 1616-1622.
Hall, M. R., Lindsay, R. & Krayenhoff, M. (2012) Modern Earth Building, in Hall, M. R.,
Lindsay, R. & Krayenhoff, M. (eds), Modern Earth BuildingsWoodhead Publishing, 3-16.
Hegger, M. (2006) Construction materials manualBerlin : Birkhäuser.
Heung Fai, L. A. M., Kishore, R., Bhikshma, V. & Prakash, P. J. (2011) The Proceedings
of the Twelfth East Asia-Pacific Conference on Structural Engineering and
212
ConstructionStudy on Strength Characteristics of High Strength Rice Husk Ash Concrete.
Procedia Engineering, 14, 2666-2672.
Hind K.J (2007) The Casagrande plasticity chart – does it help or hinder the NZGS soil
213
Khalid, N. H. A., Hussin, M. W., Mirza, J., Ariffin, N. F., Ismail, M. A., Lee, H.-S.,
Mohamed, A. & Jaya, R. P. (2016) Palm oil fuel ash as potential green micro-filler in
polymer concrete. Construction and Building Materials, 102, Part 1, 950-960.
Khambadkone, N. K. & Jain, R. (2017) A bioclimatic analysis tool for investigation of the
potential of passive cooling and heating strategies in a composite Indian climate. Building
and Environment, 123, 469-493.
Khankhaje, E., Hussin, M. W., Mirza, J., Rafieizonooz, M., Salim, M. R., Siong, H. C. &
Warid, M. N. M. (2016) On blended cement and geopolymer concretes containing palm oil
fuel ash. Materials & Design, 89, 385-398.
Kırbaş, B. & Hızlı, N. (2016) Learning from Vernacular Architecture: Ecological Solutions
in Traditional Erzurum Houses. Procedia - Social and Behavioral Sciences,
216(Supplement C), 788-799.
Knoema (2020) Production, supply and distribuiton of agricultural commodies by market
year, 2020. Available online: https://knoema.com/USDAPSD2020Feb/production-supply-
and-distribution-of-agricultural-commodities-by-market-year-feb-2020 [Accessed.
Kočí, J., Žumár, J., Pavlík, Z. & Černý, R. (2011) Application of genetic algorithm for
determination of water vapor diffusion parameters of building materials. Journal of
Building Physics, 35(3), 238-250.
Kolawole, J. T., Olalusi, O. B. & Orimogunje, A. J. (2020) Adhesive bond potential of
compressed stabilised earth brick. Structures, 23, 812-820.
Krosnowski, A. D. (2011) A Proposed Best Practice Method of Defining a Standard of
Care for Stabilized Compressed Earthen Block Production.
Kumar, A. & Gupta, D. (2016) Behavior of cement-stabilized fiber-reinforced pond ash,
rice husk ash–soil mixtures. Geotextiles and Geomembranes, 44(3), 466-474.
Laskar, A. I. & and Talukdar, S. (2007) Rheological behavior of high performance
concrete with mineral admixtures and their blending. Construction and Building Materials,
22(12), 2345-2354.
Lavie Arsène, M.-I., Frédéric, C. & Nathalie, F. (2020) Improvement of lifetime of
compressed earth blocks by adding limestone, sandstone and porphyry aggregates.
Journal of Building Engineering, 29, 101155.
Liu, X., Fan, Y. & Wang, C. (2017) An estimation of the effect of carbon pricing for CO2
mitigation in China’s cement industry. Applied Energy, 185, Part 1, 671-686.
Lyons, A. (2014) Materials for architects and builders, Fifth edition. edition. London :
Routledge.
Maia de Souza, D., Lafontaine, M., Charron-Doucet, F., Chappert, B., Kicak, K., Duarte, F.
& Lima, L. (2016) Comparative life cycle assessment of ceramic brick, concrete brick and
cast-in-place reinforced concrete exterior walls. Journal of Cleaner Production, 137, 70-
82.
214
Maillard, P. & Aubert, J. E. (2014) Effects of the anisotropy of extruded earth bricks on
their hygrothermal properties. Construction and Building Materials, 63, 56-61.
Malalgoda, C., Amaratunga, D. & Haigh, R. (2018) Empowering local governments in
making cities resilient to disasters: research methodological perspectives. Procedia
Engineering, 212, 902-909.
Malhotra, V. M. & Mehta, P. K. (1996) Pozzolanic and cementitious materials, 1Gordon
and Breach.
Mansour, M. B., Jelidi, A., Cherif, A. S. & Jabrallah, S. B. (2016) Optimizing thermal and
mechanical performance of compressed earth blocks (CEB). Construction and Building
Materials, 104, 44-51.
Maxwell, J. & Loomis, D. (2003) Mixed method design: An alternative approach.
Handbook of Mixed Methods in Social and Behavioral Research, 241-272.
McGregor, F., Heath, A., Fodde, E. & Shea, A. (2014) Conditions affecting the moisture
buffering measurement performed on compressed earth blocks. Building and
Environment, 75, 11-18.
McHenry, P. G. (1984) Adobe and rammed earth buildings : design and constructionNew
York Chichester : Wiley.
Mehta, B. R., Sahay, M. K., Malhotra, L. K., Avasthi, D. K. & Soni, R. K. (1996) High
energy heavy ion induced changes in the photoluminescence and chemical composition
of porous silicon. Thin Solid Films, 289(1–2), 95-98.
Mehta, D. U., Sathawane, S. H., Vairagade, V. S. & Kene, K. S. (2013) Chemical, Civil
and Mechanical Engineering Tracks of 3rd Nirma University International Conference on
Engineering (NUiCONE2012)Combine Effect of Rice Husk Ash and Fly Ash on Concrete
by 30% Cement Replacement. Procedia Engineering, 51, 35-44.
Mkaouar, S., Maherzi, W., Pizette, P., Zaitan, H. & Benzina, M. (2019) A comparative
study of natural Tunisian clay types in the formulation of compacted earth blocks. Journal
of African Earth Sciences, 160, 103620.
Mostafa, M. & Uddin, N. (2016a) Experimental analysis of Compressed Earth Block (CEB)
with banana fibers resisting flexural and compression forces. Case Studies in
Construction Materials, 5, 53-63.
Mostafa, M. & Uddin, N. (2016b) Experimental analysis of Compressed Earth Block (CEB)
with banana fibers resisting flexural and compression forces. Case Studies in
Construction Materials, 5(Supplement C), 53-63.
Moughtin, J. C. (2013) The Traditional Settlement of Hausa People. The Town Planning
Review, Vol. 35, No. 1 (Apr., 1964), pp. 21-34.
Mukhopadhyaya, P. K., K.; Normandin, N.; Goudreau, P (2002) Effect of surface
temperature on water absorption coeffcient of building materials. Thermal Envelop and
Building Science, 26, 179-195.
215
Nagrale, S. D., Hajare, H. & and Modak, P. R. (2012) Utilization of Rice Husk Ash.
.International Journal of Engineering Research and Applications, 2(4), 001-005.
Narayanaswamy, A. H., Walker, P., Venkatarama Reddy, B. V., Heath, A. & Maskell, D.
(2020) Mechanical and thermal properties, and comparative life-cycle impacts, of
stabilised earth building products. Construction and Building Materials, 243, 118096.
Nehdi, M., Duquette, J. & El Damatty, A. (2003) Performance of rice husk ash produced
using a new technology as a mineral admixture in concrete. Cement and Concrete
Research, 33(8), 1203-1210.
Norsuraya, S., Fazlena, H. & Norhasyimi, R. (2016) Sugarcane Bagasse as a Renewable
Source of Silica to Synthesize Santa Barbara Amorphous-15 (SBA-15). Procedia
Engineering, 148, 839-846.
Nshimiyimana, P., Fagel, N., Messan, A., Wetshondo, D. O. & Courard, L. (2020)
Physico-chemical and mineralogical characterization of clay materials suitable for
production of stabilized compressed earth blocks. Construction and Building Materials,
241, 118097.
Ogunsote, O. O., Ogunsote, B. P. & Morisade, A. (2010) Optimizing passive cooling
systems in residential buildings: A case study of Akure, Nigeria.
Okeyinka, Y. R. a. O., S.A (2015) Houseform Characteristics of the Yoruba Culture.
Journal of Culture, Society and Development, 10.
Olaniyan, S. A. (2012) Optimizing thermal comfort for tropical residential designs in
Nigeria: How significant are the walling fabrics?, People and Buildings. London
Metropolitan University, London, UK, 18th September 2012.
Olanrewaju, A., Anavhe, P. & Hai, T. K. (2016) A Framework for Affordable Housing
Governance for the Nigerian Property Market. Procedia Engineering, 164, 307-314.
Olayiwola, L. M., Adeleye, O. & Ogunsakin, L. (2005) Urban Housing Crisis and
Responses in Nigeria: The planners' view point. World Congress on Housing
216
Phonphuak, N., Saengthong, C. & Srisuwan, A. (2019) Physical and mechanical
properties of fired clay bricks with rice husk waste addition as construction materials.
Materials Today: Proceedings, 17, 1668-1674.
Rama, K. B., Ratnam, M. K. M. V. & and Raju, U. R. (2015) Experimental Studies on
Concrete with Rice Husk Ash as a Partial Replacement of Cement Using Magnesium
Sulphate Solution. International Journal for Innovative Research in Science & Technology,
1(7), 333 - 340.
Ramezanianpour, A. A., Mahdi khani, M. & and Ahmadibeni, G. (2009) The effect of rice
husk ash on mechanical properties and durability of sustainable concretes. International
Journal of Civil Engineerng., 7(2), 83–91.
Raut, S., Ralegaonkar, R. & Mandavgane, S. (2013) Utilization of recycle paper mill
residue and rice husk ash in production of light weight bricks. Archives of Civil and
Mechanical Engineering, 13(2), 269-275.
Richardson, B. A. (2001) Defects and deterioration in buildings, 2nd ed. edition. London:
London : Spon.
Rigassi, V. & CRATerre-EAG. (1985) Compressed Earth Blocks: Manual of Production, 1.
Rode, C., Peuhkuri, R., Time, B., Svennberg, K. & Ojanen, T. (2007) Moisture buffer value
of building materials. ASTM Special Technical Publication, 1495, 33-44.
Rode, C., R, P., L.H, M., K.K, H., B, T., A, G., T, O., J, A., K, S. & L.E, H. (2005) Moisture
Buffering of Building Materials. Department of Civil Engineering Technical University of
Denmark.
Rodrigues, C. S., Ghavami, K. & and Stroeven, P. ((2006)) Porosity and water
permeability of rice husk ash-blended cement composites reinforced with bamboo pulp.
Journal of Materials Science, 41(21), 6925-6937.
Roshan, G., Oji, R. & Attia, S. (2019) Projecting the impact of climate change on design
recommendations for residential buildings in Iran. Building and Environment, 155, 283-
297.
Salas, A., Delvasto, S., R.M., D. G. & D., a. L. (2009) Comparison of two processes for
treating rice husk ash for use in high performance concrete. Cement and Concrete
Research,, 39, 773–8.
Saraswathy, V. & and Ha-Won, S. (2007) Corrosion performance of rice husk ash blended
concrete. Construction and Building Materials., 21(8), 1779–1784.
Sekhar C, D. & Nayak, S. (2018) Utilization of granulated blast furnace slag and cement in
the manufacture of compressed stabilized earth blocks. Construction and Building
Materials, 166, 531-536.
Serbah, B., Abou-Bekr, N., Bouchemella, S., Eid, J. & Taibi, S. (2018) Dredged sediments
valorisation in compressed earth blocks: Suction and water content effect on their
mechanical properties. Construction and Building Materials, 158, 503-515.
217
SFGB (2011) Natural stone, the oldest sustainable material. Stone Federation of Great
Britain.
Solutions, M. N. (2017) BlockFlash™* | The Complete Flashing Solution for Single Wythe
Concrete Masonry Unit Walls. Moisture Management for Masonry.
Sore, S. O., Messan, A., Prud’homme, E., Escadeillas, G. & Tsobnang, F. (2016)
Synthesis and characterization of geopolymer binders based on local materials from
Burkina Faso – Metakaolin and rice husk ash. Construction and Building Materials, 124,
301-311.
Steve, G. (2016) Sustainable Construction processesWiley- Blackwell.
Stowell (2020) Dense concrete blocks/bricks, 2020. Available online:
https://stowellconcrete.co.uk/dense-concrete-blocksbricks-10-4nmm2/ [Accessed.
Sturm, P., Gluth, G. J. G., Brouwers, H. J. H. & Kühne, H. C. (2016) Synthesizing one-part
geopolymers from rice husk ash. Construction and Building Materials, 124, 961-966.
Subramaniyan, K. S. & and Sivaraja, M. (2016) Assessment of sugarcane bagasse ash
concrete on mechanical and durability properties. Middle-East Journal of Scientific
Research, 24(S1), 257-267.
Taallah, B. & Guettala, A. (2016) The mechanical and physical properties of compressed
earth block stabilized with lime and filled with untreated and alkali-treated date palm
fibers. Construction and Building Materials, 104, 52-62.
Takhelmayan, G., Prasad, R. & and Savithal, A. L. (2014) Experimental Study on
Properties of Cement Using Riced Husk Ash. International Journal of Engineering Science
and Innovative Technology (IJESIT), 3(6), 101-107.
Tangchirapat, W., Jaturapitakkul, C. & Chindaprasirt, P. (2009) Use of palm oil fuel ash as
a supplementary cementitious material for producing high-strength concrete. Construction
and Building Materials, 23(7), 2641-2646.
Tay, J. H. (1990) Ash from oil-palm waste as a conrete material. Journal of materials in
civil engineering, 2(2), 94-105.
Taylor, P., Fuller, R. J. & Luther, M. B. (2008) Energy use and thermal comfort in a
rammed earth office building. Energy and Buildings, 40(5), 793-800.
Tettey, U. Y. A., Dodoo, A. & Gustavsson, L. (2017) Energy use implications of different
design strategies for multi-storey residential buildings under future climates. Energy, 138,
846-860.
Thomas, D. & Ding, G. (2018) Comparing the performance of brick and timber in
residential buildings – The case of Australia. Energy and Buildings, 159(Supplement C),
136-147.
Tian, H. & Zhang, Y. X. (2016) The influence of bagasse fibre and fly ash on the long-term
properties of green cementitious composites. Construction and Building Materials, 111,
237-250.
218
Toe, D., Toe, C. & Kubota, T. (2010) A Review of Adaptive Model of Thermal Comfort for
Naturally Ventilated Buildings in Hot-Humid Climate.
Torgal, F. P. & Said, J. (2011) Eco-efficient construction and building materialsSpringer.
Tsado, T. Y., Yewa, M., Yaman, S. & and Yewa, F. (2014) Comparative Analysis of
Properties of Some Artificial Pozzolana in Concrete Production. International Journal of
Engineering and Technology, 4(5), 251 - 255.
Udawattha, C. & Halwatura, R. (2017) Life cycle cost of different Walling material used for
affordable housing in tropics. Case Studies in Construction Materials, 7, 15-29.
Ugochukwu, I. B. & Chioma, M. I. B. (2015) Local Building Materials: Affordable Strategy
for Housing the Urban Poor in Nigeria. Procedia Engineering, 118, 42-49.
UN-Habitat (2011) Annual Report.
UN, D. o. e. a. s. A. (2018) 68% of World Population projected to live in urban areas by
2050, 2018. Available online:
https://www.un.org/development/desa/en/news/population/2018-revision-of-world-
urbanization-prospects.html [Accessed.
Uzoegbo, H. C. (2020) 12 - Dry-stack and compressed stabilized earth-block construction,
in Harries, K. A. & Sharma, B. (eds), Nonconventional and Vernacular Construction
Materials (Second Edition)Woodhead Publishing, 305-350.
Van Damme, H. & Houben, H. (2017) Earth concrete. Stabilization revisited. Cement and
Concrete Research.
Van Tuan, N., Ye, G., van Breugel, K., Fraaij, A. L. A. & Bui, D. D. (2011) The study of
using rice husk ash to produce ultra high performance concrete. Construction and
Building Materials, 25(4), 2030-2035.
Vincent Rigassi & CRATerre-EAG. (1985) COMPRESSED EARTH BLOCKS: MANUAL
OF PRODUCTION, 1.
Walsh, A., Cóstola, D. & Labaki, L. C. (2017) Review of methods for climatic zoning for
building energy efficiency programs. Building and Environment, 112(Supplement C), 337-
350.
Wang, C., Li, Y., Myint, S. W., Zhao, Q. & Wentz, E. A. (2019) Impacts of spatial
clustering of urban land cover on land surface temperature across Köppen climate zones
in the contiguous United States. Landscape and Urban Planning, 192, 103668.
Wang, Y., Zheng, T., Zheng, X., Liu, Y., Darkwa, J. & Zhou, G. (2020) Thermo-mechanical
and moisture absorption properties of fly ash-based lightweight geopolymer concrete
reinforced by polypropylene fibers. Construction and Building Materials, 251, 118960.
World, M. o. (2020) Nigeria Latitude and Longitude Map, 2020. Available online:
https://www.mapsofworld.com/lat_long/nigeria-lat-long.html [Accessed.
219
Worldometer (2019) Current world population, Main cities by population in Nigeria, 2019.
Available online: https://www.worldometers.info/world-population/nigeria-population/
[Accessed.
Xiao, X., Guan, B., Ihamouten, A., Villain, G., Dérobert, X. & Tian, G. (2018) Monitoring
water transfers in limestone building materials with water retention curve and Ground
Penetrating Radar: A comparative study. NDT & E International, 100, 31-39.
Xu, W., Lo, T. Y. & Memon, S. A. (2012) Microstructure and reactivity of rich husk ash.
Construction and Building Materials, 29, 541-547.
Zak, P., Ashour, T., Korjenic, A., Korjenic, S. & Wu, W. (2016) The influence of natural
reinforcement fibers, gypsum and cement on compressive strength of earth bricks
materials. Construction and Building Materials, 106, 179-188.
Zhang, M., Qin, M., Rode, C. & Chen, Z. (2017) Moisture buffering phenomenon and its
impact on building energy consumption. Applied Thermal Engineering, 124, 337-345.
Zhao, J. & Plagge, R. (2015) Characterization of hygrothermal properties of sandstones—
Impact of anisotropy on their thermal and moisture behaviors. Energy and Buildings, 107,
479-494.
220
SOFTWARE TOOLS
Meteonorm 7v7.3.3
221
Publication
Ojerinde,A., Adekunle,A., Fatai, O., Stevenson, V. & Latif, E. The partial replacement of
Ordinary Portland Cement with Rice Husk Ash to stabilize Compressed Earth Blocks for
Affordable Building materials. PLEA 2018: Smart and healthy within the two-degree limit,
Hong Kong, China, 10-12 Dec 2018. PLEA 2018-34th International Conference on Passive
and Low Energy Architecture. The Chinese University of Hong Kong, pp. 321-325.
222