Mfl69150610 English
Mfl69150610 English
ҚАЗАҚ ТІЛІ
AIR
CONDITIONER
БЕЛАРУСКАЯ МОВА
O‘ZBEK TILI
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
www.lg.com
P/NO : MFL69150610
2 SAFETY PRECAUTIONS
ENGLISH
SAFETY PRECAUTIONS
• This product must be installed by an installation professional from an LG authorized service
center.
• Any issues stemming from an installation by an unauthorized person is the responsibility of
the user and will not be covered by warranty.
• The following safety precautions are to prevent any unforeseen dangers or damage.
• This product has been designed for business use, or for areas outside the home, and has
passed the Electromagnetic Interference Test.
! WARNING
It can result in serious injury or death when the directions are ignored.
! CAUTION
It can result in minor injury or product damage when the directions are ignored.
! WARNING
Installation
• To reinstall the product, please contact the dealer from where you purchased the product, or
a service center for reinstallation service.
- Installation of the product by an unauthorized person may result in fire, electric shock, explo-
sion, injury, or a malfunctioning of the product.
• Do not twist or damage the power cord.
- It may cause fire or electric shock.
• For electrical work, please contact the dealer from where you purchased the product, or a
service center.
- Disassembly or repair by an unauthorized person may result in fire or electric shock.
• Install the product in an area shielded from rain.
- If water gets into the product, it may malfunction.
• Do not install the product in a humid area.
- If the product is damp, it may malfunction.
• For installation of the product, please contact the dealer from where you purchased the prod-
uct, or a service center.
- Installation of the product by an unauthorized person may result in fire, electric shock, explo-
sion, injury, or a malfunctioning of the product.
• For electrical work, please have an electrician do the work based on the installation manual
and specified circuit diagram.
- Using an unsuitable cord, or having a non-professional work on the electricals may result in
fire or electrical shock.
• Do not place the product near a fire source.
- It may result in the product catching fire.
• If the product is installed in a hospital or a communication base station, provide sufficient pro-
tective equipment against electrical noise.
- The product may malfunction or other products may work abnormally.
• Securely install the product.
- If the product is not secured during installation, it may fall or malfunction.
• Read the manual thoroughly to correctly install the product.
- If not, an incorrect installation may cause fire or electric shock.
SAFETY PRECAUTIONS 3
ENGLISH
• When wiring the product, do not use a non-standard cable, nor extend the cable excessively.
- It may cause a fire or electric shock.
• Securely install the power cord and communication cable.
- An unsecure installation may result in a fire or electric shock.
• Do not connect the power cord to the communication terminal.
- It may cause a fire, electric shock, or a product malfunction.
• Do not install the product in an area near combustible gas.
- It may result in fire, electric shock, explosion, injury, or a malfunctioning of the product.
Use
• Do not place a heavy object on the power cord.
- It may cause a fire or electric shock.
• Do not change or extend the power cord arbitrarily.
- It may cause a fire or electric shock.
• Use the cord specific to the product.
- Using an unauthorized non-standard cord may result in a fire or electric shock.
• Do not use a heat device near the power cord.
- It may cause a fire or electric shock.
• Ensure that water never gets into the product.
- It can result in an electric shock, or the product may malfunction.
• Do not place any container with liquid on the product.
- The product may malfunction.
• Do not touch the product with wet hands.
- It may cause a fire or electric shock.
• Use standard components.
- Use of an unauthorized product may result in fire, electric shock, explosion, injury, or a malfunction-
ing of the product.
• If the product has been submerged in water, you should contact a service center.
- It may cause a fire or electric shock.
• Do not shock the product.
- The product may malfunction.
• Do not store or use any combustible gas or flammable substances near the product.
- It may cause a fire, or a product malfunction.
• Do not disassemble, repair, or revamp the product arbitrarily.
- It may cause a fire or electric shock.
• Children and the elderly should use the product under the supervision of a guardian.
- Carelessness may cause an accident, or the product to malfunction.
• The guardian should prevent children from accessing the product.
- The product may be damaged or it may fall, causing injury to children.
• Keep in mind the operating temperature range specified in the manual. If there is no operating tem-
perature range in the manual, use the product between 0 and 40 °C (32 and 104 °F).
- If the product is used outside this range, the product may be severely damaged.
• Do not press the switch or button with a sharp object.
- It can result in an electric shock, or the product may malfunction.
• Do not wire the product while it is turned on.
- It may cause a fire or electric shock.
• If the product sounds or smells different, stop using the product.
- It may cause a fire or electric shock.
4 SAFETY PRECAUTIONS
ENGLISH
! CAUTION
Installation
• Securely install the product in an area where the weight of the product can be supported.
- The product may fall and be destroyed.
• Do not use the product where there is oil, steam, or sulfuric gas.
- It may effect the product's performance, or damage it.
• Check the rated power capacity.
- It may cause a fire, or a product malfunction.
• Use the adapter provided with the product or power from a class 2 24 V~ transformer, depending
on model.
- If a non-standard adapter is used, the product may malfunction. The adaptor is not provided with
the ACP BACnet package sold in the U.S.
• Be careful not to drop or damage the product when moving it.
- The product may malfunction or the person may sustain an injury.
• Ensure that the cord is connected securely to prevent dew, water, or insects from getting into the
product.
- If a foreign substance gets inside, it may cause an electric shock or the product may malfunction.
Use
• Clean the product with a soft cloth, but not with a solvent-based detergent.
- The use of a solvent-based detergent may cause a fire or deform the product.
• Do not touch the panel using a pointy or sharp object.
- It can result in an electric shock, or the product may malfunction.
• Do not let the product come into contact with a metal substance.
- The product may malfunction.
• When sterilizing or disinfecting, stop using the product.
- The product may work abnormally.
• Do not touch inside the product.
- The product may malfunction.
• Check the condition of the product after using the product for an extended period of time.
- If the product is used for an extended period of time, the product's condition may be worsen, caus-
ing injury to the user.
• Do not leave the product near a flower base, water bottle, or any other liquids.
- It may cause a fire or electric shock.
• If the liquid crystal of the product is broken, please do not let your skin such as face or hands con-
tact with.
- Personal injury or property damage may occur.
SAFETY PRECAUTIONS 5
ENGLISH
• Transformer selection:
- Select an insulating product that complies with IEC61558-2-6 and NEC Class 2.
- In addition, consider the combined power consumption of the modules, accessories, and
field devices installed for the selection of an appropriate transformer.
Main module current: 24 V~, 850 mA
- Use the provided adaptor when using DC 12 V. The adaptor is not provided with the ACP
BACnet package sold in the U.S.
Class A device
! NOTE
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own
expense.
! CAUTION
Changes or modifications not expressly approved by the manufacturer responsible for com-
pliance could void the user’s authority to operate the equipment.
6 ACP BACnet FUNCTIONS AND SPECIFICATION
ENGLISH
ENGLISH
РУССКИЙ ЯЗЫК УКРАÏНСЬКА
INSTALL/OWNER’S MANUAL
ҚАЗАҚ ТІЛІ
AIR
CONDITIONER БЕЛАРУСКАЯ МОВА
OʻZBEK TILI
PQNFB17C0
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
www.lg.com
P/NO : MFL69150610
! NOTE
Components or options may differ from the actual product picture.
ACP BACnet FUNCTIONS AND SPECIFICATION 7
ENGLISH
Names of each part of ACP BACnet
ACP BACnet is composed as follows.
155.0 mm
¢
£ 270.0 mm
64.8 mm
¤ ¥ ¦ §
¨
© ª
« ¬
! CAUTION
• The ACP BACnet installation work needs the professional technique. Therefore, the instal-
lation described in this chapter should be performed by the certified installation profes-
sional.
• Consult the service center or the professional installation agency certified by us about any
question or request related to the installation.
INSTALLING ACP BACnet 9
ENGLISH
Check points during the ACP BACnet installation
• The number of PI485 connected to one RS-485 communication line
- ACP BACnet provides 4 RS-485 ports for indoor unit connection. (CH 1~4)
- Up to 16 PI485 for outdoor unit can be connected to one RS-485 port, and up to 31 PI485 for
- SINGLE/ERV can be connected.
• The number of the indoor units that can be connected to one ACP BACnet
- One ACP BACnet can be connected up to 256 indoor units. To one RS-485 port, all of 256
indoor units, which is the maximum number that can be connected to the ACP BACnet, may
be connected.But, to improve the communication performance of RS-485, it is recommended
to be divided and connected to 4 ports.
• RS-485 communication cable connection
- There is a polarity in RS-485 communication cable connection, so be careful not to reverse the
connection of the two cables.
- Do not let the length of RS-485 communication cable exceed total of 1 Km.
- RS-485 communication cable must be connected with BUS type.
• IP address of the ACP BACnet
- IP address of the ACP BACnet, address of Gateway, and Net mask must be requested to the
person in charge of the network of the corresponding site.
! CAUTION
RS-485 Connection of the ERV equipment
To connect ERV equipment, it is recommended to use the ports other than RS-485 commu-
nication ports which are connected to air conditioners.
10 INSTALLING ACP BACnet
ENGLISH
! NOTE
Assigning indoor and outdoor unit number
If the outdoor unit product is Multi V, it is recommended to
assign the address by setting the first digit of the address
as the number of the outdoor unit, and classifying the sec-
ond digit as the number or the indoor unit, for easy compo-
sition and classification of the system.
PQNFB17C0
PLNWKB000
ACP
BACnet
ERV
ERV
When the ACP BACnet is interconnected with the AC Manager, the ERV can be installed togeth-
er and controlled.
The above figure shows the example that sets the addresses of 30 and 31 to the ERV and con-
nects to the ACP BACnet.
! NOTE
How to set the central control address of the indoor unit
The central control address setting method may be different for each indoor unit product or
remote control type, so set the address by referring to the manual of the indoor unit prod-
uct or wired remote controller.
INSTALLING ACP BACnet 11
ENGLISH
Installing ACP BACnet and Installing the ACP BACnet in DIN
connecting cables RAIL
After setting PI485, the ACP BACnet shall be ACP BACnet can be installed in DIN RAIL with
installed in an adequate place, and RS-485 width 35mm and height 7.5mm.
cable shall be connected for the communica- Proceed as the follows to install the ACP
tion with PI485. BACnet in an adequate place.
And, Ethernet cable (LAN cable) shall be con- The installation method of the ACP BACnet is
nected for the connection with internet or AC explained here with the example of installing
Manager. To fix the ACP BACnet, the follow- the ACP BACnet in DIN RAIL.
ing 2 methods may be used.
Install in DIN RAIL or fix to the wall consider- • Decide the space to install the ACP BACnet.
ing the environment of the site.
• Before installing the ACP BACnet, check if it
is the adequate place to connect the ACP
BACnet with the power, RS-485, and LAN
cable.
• Install DIN RAIL.
• Hook the top part of the ACP BACnet on
DIN RAIL.
PQNFB17C0
• Push the main body of the ACP BACnet until
you hear the sound of installation.
Power
• Pull the ACP BACnet to check if it is fixed.
£ Hooking on
DIN RAIL
! CAUTION
¤Fixing to DIN RAIL
If four times the power con-
nector for the connection, as
shown by using the right
connection, but please note
that an electric shock. ! CAUTION
Use the designated parts
must be connected to a • After installing to DIN RAIL, do not fix to
power source. the wall using screws.
• Connector manufacturers: PHOENIX • ACP BACnet may be damaged.
CONTACTPartNo: MVSTBR 2,5 / 2-ST-5, • DIN Rail fixing Screw Spec: M3, screw
08 2P 5.00MM head height 2.0 ~ 1.75mm, screw head
diameter 7.0 ~ 5.5mm
12 INSTALLING ACP BACnet
ENGLISH
PQNFB17C0
ENGLISH
Connecting ACP BACnet and PC Setting the ACP BACnet net-
It is the case of installing AC Manager in a
work address
separate PC and connecting ACP BACnet and After connecting the ACP BACnet to various
PC directly. devices via the cable, the network environ-
In such case, Ethernet cable shall be connect- ment of the ACP BACnet should be set by
ed as a cross cable. driving the ACP BACnet. The following infor-
mation should be set for using the ACP
Use Ethernet cable (cross cable) to connect to BACnet.
LAN port of the ACP BACnet.
• IP address of the ACP BACnet
• Gateway address
• Net mask
! CAUTION
Setting the network environment informa-
tion
If the above information is not entered,
the communication error may be occurred
or it may be impossible to control by the
Connection
ACP BACnet. So, be careful to correctly
with hub input.
Direct cable
Direct connection
with PC
Cross cable
Before configuring the ACP BACnet
environment
The network environment of the ACP BACnet
! CAUTION can be set by the LCD and the buttons at the
front side of the ACP BACnet.
Ethernet cable types
The current ACP BACnet information and the
• You must distinguish if the Ethernet
menu are displayed on the LCD, and the
cable to connect is a direct cable or a
menu can be changed and selected by press-
cross cable.
ing and button and
• Also, connect after checking the exis-
Up/Down/Left/Right (▲, ▼, ◀, ▶) buttons.
tence of problem in the cable using LAN
tester.
PQNFB17C0
PQNFB17C0
14 INSTALLING ACP BACnet
ENGLISH
! NOTE
Software version
LG BACnet
The software version of the current ACP BACnet is displayed at the SW ver. 1.0.0
initial ACP BACnet screen. Also, the software version may be differ- IP 192.168.001.100
GW 192.168.001.001
ent according to the manufacturing date of the ACP BACnet.
! CAUTION DB back up
DB recover
Data Logging
• [Function] menu is used by the system air conditioner service 4
technician, so user shallnever use this function. [Register FD]
IP 000.000.000.000
• If this function is incorrectly used, it may cause disorder of PORT: 00000
TTL : 00000
the ACP BACnet. ON : 0
STARTING 15
ENGLISH
STARTING
Login and logout
The following explains how to log in and out of Central Controller.
Central Controller is, can be controlled not only equipment, but also Web. If you enter the IP
address of the Central Controller in the address bar of the Internet without the installation of
another program, the central control program Central Controller, Web server has is executed
automatically, to use the functionality of the various content I can.
The Manual, I will explain to Central Controller standard equipment.
! NOTE
• You will need the Adobe Flash Player be installed for the Web control.(Recommended
specification : Adobe Flash Player 11)
• The special character (^), (‘) and (,) are not available.
Login
You can login as follows.
1 Run Central Controller.
2 After entering your ID and password in the login window, click(touch) [Confirm].
- You should be logged in now.
Logout
You can logout as follows.
1 On the top right of the Central Controller home screen, click(touch) the [Logout] button.
- You should be logged out now.
16 HINT
ENGLISH
HINT
Pre-Tech Support Checklist
If the abnormality occurs in products, please first check the following points before requesting to
service center.
Symptom Measures
I would like to change the Log in as superuser → System Settings → After select the
name of the indoor unit. device you want to change, modify the name of or the device
→ Apply → Complete group settings
VER. 1.0.1