(name of the bidding company ) (MANDATORY)
(what energy label(s) the
Gas boiler must be in accordance with the technical specification, and the
BoQ. The Bidder shall demonstrate that boilers to be supplied comply with
the basic requirements of the applicable directives are CE marked and
meet the most recent energy certification, national or regional ecolabels for
energy performance and/or Energy Star criteria
LOT 2 SVR Kumanovo
(model, type and manufactuer
of the offered product with
exact data of capacity, dT,
dP....as demanded on the BoQ
)
BoQ Container gas boiler station for outdoor installation with cascade rigs of
4 wall-hung natural gas condensing boilers with total heating capacity of
4x93.3 kW= 373.2kW in-line fitted. Made according to the EN 303 and
Viessmann Vitomodul KGB A4
EN677, CE marked. Each boiler unit consist of modulate cilindric gas
480
burner, made of stainless steel , with low emission and quite operation
according to the DVGW G260; heat exchanger made of high quality steel
1.4571
Maximum allowable pressure drop on the heat exchanger / hydraulic
switch on the secondary side dP<10kPa
Automation and control system depending on the outdoor temperature YES
Chimney Ø300 made of INOX, insulated, with a length of approx. 10m
with: YES
(technical specifications of the
offered product for the need of
TECHNICAL SPECIFICATIONS comparision to demanded
1 Number and capacity of built-in condensing gas boilers in the module: 4x120kW
2 Heat capacity of the gas heat generator at temperature regime 80/60° C
443,6kW
according to EN 15417, for natural gas or LPG operation:
3 Range of heat capacity of the device, ie. ratio of minimum and maximum
YES
power of the device: min. 1:5
4 Type of device: Condensing YES
5 Material of flue gasses/water exchanger: completely stainless steel (INOX) YES
6 The gas heat generator should be primarily prepared for the use of natural
YES
gas and factory pre-prepared for the use of LPG
7 Maximum temperature of supply line: min. 85°C YES
8 NOx gas emission: min. class 6 YES
9 Place and location of installation: Device for outdoor installation, facade or
YES
roof of the building
10 Degree of protection ie. water resistance of the device according to IP
YES
standard min. IPX4D (the device is resistant to splashing water from all
11 Control unit of cascade operation , modulating regulation of water YES
temperature dependin of outside ambient temperature. Delivery of digital
unit (1pcs) plus cascade module (3 pcs), outside temperature sensor
(1pcs) , water temperature sensors (1 in retur pipe and 4 in supply pipes).
Modulate gas burner regulation, LON-BUS connection, boiler protection
Therm-Control, daily and weekly programming options, dia system,
consumption information
Scope of delivery of Container gas boiler station
12 Metal container (housing) with dimensions 4000х2700х1200 mm,
including doors , supply weather-resistant louvre 225х125mm and return
weather-resistant louvre 225х75mm YES
13 Plate heat exchanger with 480kW capacity, sized for the gas boiler
cascade. Flanged connections DN80, thermal insulated , including glycol
for primary heating circuit. YES
14 Pump group, includes high efficiency pump and insulation, flow 3740 lit/h
by ∆т=23К and available pressure 0,38 bar
YES
15 Valve set consist of two ball valves (water supply and return) including
insukation, 1 set per boiler unit
YES
16 Stright gas valve 1”, Potv=4bar with thermal protection, one per unit YES
17 Check valve 11/4”, for horisontal , one per boiler unit
YES
18 Safety valve 1”, Potv=4bar , one per boiler unit YES
19 Stell support for cascade of 4 boiler unit in line YES
20 Condensate neutraliser including eutralisation medium. YES
21 Condensate siphon made of condensate discharge hose, one per boiler YES
unit
22 Condensate discharge set for 4 boiler units made fom PVC pipe and
fittings including discharge hose (1 set) YES
23 Supply and return manifold pipe DN100 with necessary connections for 4
boiler units cascade, prefabricated thermalinsulation box YES
24 Installation set made of Cu pipes including all fittings for connection of
each unit to the manifolds YES
25 Gas pipe collector DN80 for gas suply od 4 boiler units cascade, including
all fittings YES
26 Flue gas pipe system scope of delivery YES
27 PP flue gas pipe cacade system YES
28 Air/flue concentric façade system - stainless steel air