easYgen-3200 Overview
Genset Control for Multiple Unit Operation
marked
CERTIFICATE of Design Assessment by ABS
American Bureau of Shipping & Affiliated Companies
ONE UNIT - INFINITE POSSIBILITIES: the easYgen- 3000
Introduction
The easYgen-3000 platform offers a new level of technology for power generation customers. New software and hardware capabilities enable users to customize this control to their exact requirements and adapt it to numerous genset applications. The functions needed to run applications from very basic to the advanced have been incorporated into a single part number and at an exceptionally competitive price. The easYgen-3000 is the result of Woodwards leading edge, global experience in the genset control business. Communications with our global market have enabled Woodward to optimize a control that meets technical and commercial aspects for the market today and in the future. The easYgen-3000 will permit our customers to differentiate themselves in their respective markets and will assist them in maintaining a competitive advantage in the coming years. This presentation is to introduce the easYgen-3200 as the first model available from the easYgen-3000 platform line.
3
Current and future Part Numbers
P2
easYgen-3000 Platform RP-3000 (Remote Panel) easYgen-3100 easYgen-3200 easYgen-3400 easYgen-3500 Terminal Blocks 2 80 80 80+ 80+ Comm. Ports 1 4 4 4+ 4+ 1A CT No 8440-1818 8440-1816 8440-xxxx 8440-xxxx 5A CT No 8440-1817 8440-1831 8440-xxxx 8440-xxxx 1A CT P2 No 8440-1844 8440-1842 8440-xxxx 8440-xxxx 5A CT P2 No 8440-1845 8440-1843 8440-xxxx 8440-xxxx
RP-3000
easYgen-3100
easYgen-3200
Market
Genset application
Diesel and gas engines. Synchronous Generators Single unit island/mains parallel operation Multiple unit island/mains parallel operation
Typical Field applications
Emergency mode - AMF (Automatic Mains Failure) Stand-by application Cogeneration CHP (Combined Heat and Power) Peak shaving Prime mover application Export/Import control Load or process dependend start/stop for single/multiple units
Application
Single Unit Mains Parallel
Engine start / stop Generator protection AMF (auto mains failure) Generator control Frequency / active power Voltage / power factor Parallel to mains Full Generator Breaker Control Full Mains Breaker Control
No external mains breaker control module required. Mains CT and PT will connected to all easYgen-3000. => Full redundant protection/control over the Mains Breaker.
Application
Multiple Unit Mains Parallel
Overview
FlexAppTM FlexRangeTM FlexInTM Multiple breaker operation application setups in one unit: No breaker, GCB o/, GCB o/c, GCB & MCB o/c* Allows for the control to operate on a wide range of PT voltage inputs and CT configurations The controller analog inputs are compatible with both resistive and mA signals permitting the use of a wide range of sending units Configurations, operating sequences, and operating modes can be modified through the use of logical operators, timers, internal and external status Analog signals can be monitored and sent to an output (metered values, bias signals for control purposes) Free running and programmable analog limit switches extend the quantity of trip levels or actuation triggers Allows for CANopen and J1939 protocols
* o/ = open; o/c = open/synch./close
LogicsManagerTM
Analog ManagerTM FlexLimitsTM FlexCANTM
8
Features Overview
Engine control
Diesel or gas engines Start/Stop management ECU interconnection
Protection
Engine protection
Generator protection Mains monitoring Breaker monitoring
Breaker control
GCB MCB No breaker application
Customization
High flexibility via LogicsManager Multiple languages Customized front foils/face panels
Power Management
kW-,kVAr-, f-, V-, [Link].-Control kW-, kvar-, Sharing
Features Engine Control
Stop, Manual, Automatic modes Start / stop by discrete inputs, interface, frontpanel, analog inputs ... ECU CAN J1939 connection for Monitoring Visualization Control Override mode for critical operation Speed sensing/monitoring by MPU Redundant relay outputs for safety considerations (breaker, gas valves,...) via LogicsManager
10
Crank control and protection Aux. excitation for alternator via D+ termimal Aux. services for preand postrun Counters for running hours , service requests,...
Features Engine Control
Start-Stop-Management
Load-Dependent Start/Stop (LDSS) up to 32 generator sets based on: Fuel efficiency System reserve power Service hours Different sized engines/generators Fault conditions on genset X in the network (Next genset starts) Process data; e.g. temperature, fuel level, or any other measured state Loss of mains detection for supplying emergency power
11
Features Breaker
Breaker
No breaker, GCB, MCB
Synchronization Modes
Phase matching
Slip frequency synch. Synch. check option
Breaker modes
Parallel Open transition Closed transition Interchange (Soft transfer) External (No breaker ops.)
Protection
Synch Time Out Close Time Out Open Time Out Field rotation monitoring
12
Features Controllers
Droop can be dynamically activated/deactivated via LogicsManager.
AVR and Governor Control Signals
Frequency
Load sharing Isochronous Droop
Two setpoints for each controller
Internal setpoints Interface Discrete Inputs (discrete raise/lower) Analog inputs (by mA, by potentiometer)
Voltage
Reactive (var) sharing Isochronous Droop
Bias outputs (for AVR & Governor)
Adjustable analog bias signal between +/-20 mA or +/-10 V PWM output Relay outputs raise/lower (3-step-Logic) Analog bias and raise/lower outputs are separately configurable for V, var, f and kW. (=> dual fuel capability)
Load control
Baseload Export/Import
Power Factor
13
Constant
Features - LogicsManagerTM
Configuration and modification of sequences and operation modes by using logical operators, timers, internal and external status conditions.
Digital Signals
Discrete inputs Relay status External discrete inputs External relays Control messages via CAN, Modbus,
Relay Outputs
Assignment
With timer ON-delay and OFF-delay 16 additional/internal flags or logical operations
- Operate free configurable outputs
Internal Conditions
Conditions - CB status - operating mode - engine status
Internal Conditions
- Start/stop engine - Change operation mode - Acknowledge of alarms - Inhibit emergency mode - Creating internal flags for cascading multiple dependencies
Alarms - warning alarm - shutdown alarm Time / Date
14
Discrete I/O
12 x Relay Outputs
Alarm and control
6 single-pole contacts 6 two-pole contacts Max 2A @ inductive load
Expansion with external DI/DO boards
Max. 16 DI/16 DO
Woodward IKD 1 Phoenix
12 x Discrete Inputs
Alarm and control (isolated) Configurables: Timers, alarm classes, text
15
Analog I/O
3 x Analog Inputs
0 to 500 Ohm or 0/4 to 20 mA
Change between different senders via parameter 1- and 2-wire senders supported 11 bit resolution Configurables: Timers, alarm classes, text
1 x Battery Voltage
Monitoring of power supply 8 to 40 Vdc
P2
Expansion with external analog boards
1 x Magnetic Pickup Unit (MPU)
Switching or inductive Configurable for number of teeth
16
Analog I/O
2 x Analog Outputs
Maximum +/- 20 mA or +/- 10 V or PWM (500 kHz)
Preconfigured for speed and voltage bias and configurable as scalable output for measured values (kW) (ext. analog meters) Change between voltage and current by using simple jumpers
11/12 bit resolution
1 x Auxiliary Excitation D+
Input: Sensing and monitoring of excitation voltage Output: Supplying excitation voltage (via internal shunt resistor)
17
Voltage and Current sensing Generator and Mains
3Ph4W (3phase, 4wire) 3Ph3W (3phase, 3wire)
1-, 2- and 3-phase CT arrangement possible & configurable for each phase
FlexRangeTM
1Ph3W (1phase, 3wire)
only 2-phase CT possible
1Ph2W (1phase, 2wire)
only 1-phase CT possible
18
AC Generator sensing
True RMS Voltage Sensing
4-phase (L1, L2, L3, Neutral)
100 and 400 V input Frequency measurement
True RMS Current Sensing
3-phase
Non-returning slave pointer Class 1 accuracy
Field rotation detection
Class 1 accuracy Phase-to-Phase meassurement
Power Sensing
Class 2 accuracy
Phase-to-Neutral meassurement
3ph3w, 3ph4w, 1ph2w, or 2ph3w
True RMS power measuring
Real and reactive power Power factor
True RMS Auxilliary Current Sensing
Configurable as mains CT or Generator ground fault CT
19
Energy counters Wh and varh
AC Mains sensing
True RMS Voltage Sensing
4-phase (L1, L2, L3, Neutral)
100 and 400 V input Frequency measurement
True RMS Current Sensing
Non-returning slave pointer
Class 1 accuracy
Field rotation detection
Class 1 accuracy Phase-to-Phase measurement
Phase-to-Neutral measurement
3ph3w, 3ph4w, 1ph2w, or 2ph3w
Power Sensing
Real, reactive and appearant power
20
AC Bus sensing
True RMS Voltage Sensing
2-phase sensing (phase-to-phase or phase-to-neutral)
Phase angle between mains / bus and generator / bus Dead bus detection
21
DynamicsLCDTM
Multiple languages 10 standard
- English - German - Italian - French - Spanish
- Turkish - Portuguese - Russian - Chinese - Japanese
22
DynamicsLCDTM
Italian French Spanish
Turkish
Portuguese
23
DynamicsLCDTM
Chinese
Russian
Japanese
24
DynamicsLCDTM
The 320x240 pixel graphic interactive LC display provides soft keys whose functionality changes depending on application (see FlexAppTM) and operation.
Delta / Wye Voltage Automatic Manual STOP
Alarm Screen Configure Parameter Additional measured values Acknowledge/ reset centralized alarm
Change operation modes
Engine start / stop
Breaker control
25
DynamicsLCDTM
The display sections:
Last alarm Current operation, i.e. cranking, loading, start pause, etc.
Single line diagram and operation mode
26
DynamicsLCDTM
Operating modes
Automatic mode
Manual mode
Stop mode
27
DynamicsLCDTM
Symbol meanings in the single line diagram
Voltage detected Rotation field clockwise (CW) Rotation field counter clockwise (CCW) Import/export mains power Delayed engine monitoring expired Engine speed detected
28
DynamicsLCDTM
Stop command issued
Start/run command issued
Unit is trying to close the breaker
Unit is trying to open the breaker
29
DynamicsLCDTM
Examples for measuring screens
30
DynamicsLCDTM
Alarm screen
Visible active state Date and time stamp With totally 16 entries
Event History
In-/ out coming events (+ / -)
Date and time stamp
300 entries (FIFO)
Alarms will stay active until acknowledged, even if power is cycled.
31
Alarm Classes
Alarm Classes are free configurable for most monitorings
Class Action Result
Display
Warning
Warning Cool down Cool down Immediate Stop Immediate Stop Shut down Shut down Shut down Shut down internal
Display and Horn
Display and Horn Unload Gen. and open GCB Display and Horn Open GCB immediate
Display and Horn Unload Gen. and open GCB Display and Horn Open GCB immediate
For control purposes via LogicsManager to change/modify sequencing or discrete outputs
32
Generator Protection
# of Trip Levels
Over-/undervoltage Voltage asymmetry Over-/underfrequency Overload (IOP/MOP) Reverse/reduced power Unbalanced load Definite time-overcurrent Inverse time-overcurrent Overspeed (MPU) Measured ground current Calculated ground current 2/2 1 2/2 2 2 2 3 1 2 2 2
ANSI Code
[59/27] [47] [81O/U] [32] [32R/F] [46 measured] [50/51] [IEC 255] [12] [50G]
33
Generator Protection
# of Trip Levels
Power factor (PF) lagging PF leading loss of excitation Phase rotation field CW/CCW Psetpoint Pactual mismatch Unload mismatch (time out monitoring) Operating range failed 2 2 1 1 1 1
ANSI Code
[40Q]
Controller* Controller* Controller*
* plausibility monitoring features
34
Engine Protection
Maintenance days exceeded
Maintenance hours exceeded
Over-/Underspeed (MPU) Unintended Stop
Engine Stop malfunction
Speed/frequency mismatch Start failure
Charge alternator low voltage
Red stop lamp (J1939) Amber warning lamp (J1939)
Battery over-/undervoltage
35
Mains Monitoring and decoupling
# of Trip Levels
Over-/undervoltage Over-/underfrequency Import/Export power Power factor leading Power factor lagging Phase shift Field rotation 2/2 2/2 2 2 2 1ph/3ph
ANSI Code
[59/27 ] [81O/U] [32]
[78 ]
36
Miscellaneous Monitoring
GCB / MCB fail to close GCB / MCB fail to open Synch. Time Out GCB / MCB Phase rotation mismatch generator / busbar / mains Mains decoupling CAN bus communications monitoring (J1939, CANopen) Parameter alignment (multiple units) Missing members (multiple units) EEPROM failure (internal CPU) Wire break analog inputs Discrete inputs FlexLimitsTM for analog values
37
Interfaces
Load share CANopen
ToolKit Modbus Serial 1
CAN 1
RS-232
CAN 2
Extension cards (IKD 1, Phoenix) J1939 ECU
Serial 2
RS-485
Modbus
All interfaces are galvanically isolated!
38
Interface Overview CAN bus
Guidance level
Load share CANopen
PLC
Total 32 units
CAN 1 CAN 2
Engine level J1939 (ECU) Extension cards
ECU GATEWAY GATEWAY ENGINE GENERATOR
Digital expansion modules
2x IKD 1
Phoenix
Analog expansion modules
ECU
P2
Phoenix J1939
Engine
39
Generator
Interface Overview Serial Ports
Serial RS-232 Modem
ToolKit Modbus Peer-to-peer
PC
Ethernet
Serial 1 Serial RS-232 Serial RS-485
RS-232
Serial 2
PLC
Profibus
RS-485
Modbus
Multiple units
PC
40
Configuration via ToolKit
RS-232 or CAN
Serial 1 RS-232
41
Miscellaneous
CE marked, UL listed, Marine Approval (LR) IP54 (NEMA 2) from front with clamp fasteners IP66 (NEMA 4) from front with screw kit IP20 from back Operating temperature range 20 to +70C Weight approx. 1,850 g UL CERTIFICATE of Design Assessment by ABS
marked
CERTIFICATE of Design Assessment by ABS
American Bureau of Shipping & Affiliated Companies
42
Complete Product Package
Control unit easYgen-3200-5 (5A CT model) 12 x Screws for IP66 front panel mounting 8923-1262 4 x clamp fasteners brackets and screws for IP56 front panel mounting 8923-1263 1 x CD with
PC Configuration ToolKit Version 2.0 ToolKit *.WTOOL files (English and German) ToolKit *.SID files (English and German) Manuals
43
Planned Remote Panel
Remote Panel RP-3000
CANopen connected panel to all easYgen-3000 controls Point-to-point connection Same look and feel as easYgen-3200 Target release: 2008
easYgen-3000 controls CANopen RP-3000
44
easYgen-3100
easYgen-3100 (1A CT and 5A CT model)
Metal housing: no display, HMI via interfaces and DI Same functionality as easYgen-3200
45
Planned Release easYgen-3500
easYgen-3200 I/O and functionality plus:
11 x Discrete Inputs (onboard, freely configurable) 11 x Discrete Outputs (onboard, freely configurable) 2 x Sinking Outputs (onboard, kWh metering) 9 x Analog Inputs (onboard, freely configurable ) 4 x Analog Outputs (onboard, scalable) 1x Ethernet port (load sharing, SCADA connection, Modbus TCP/IP) Release date: mid-2009
46
only P2
New Features Package P2
Extended I/O via external terminals graphical Overview
ECU
47
only P2
New Features Package P2
Extended I/O via external terminals
48 x Analog Inputs
- 32 x Inputs via predefined J1939 engine messages in 10 languages - 16 x Inputs via CANopen terminals
4 x Analog Outputs (CANopen, scalable, 0-20 mA or 0-1 0V)
16 x Discrete Inputs (CANopen terminals) additional 32 total 16 x Discrete Outputs (CANopen terminals) additional 32 total Some terminals I/O will be mapped to act like a central terminal (single point connection and message broadcast to every control e.g.: central room temperature, central fuel tank level, gas leakage detection, .) The J1939 terminals need to be configured by the PC tools of the terminal manufacturers. The CANopen terminals can be configured via ToolKit directly
48
only P2
New Features Package P2
Free running PID loops
3 x Independent freely programmable PID control loops
Configurable as Analog Outputs (0-20 mA) or 3-step-outputs (Relay Outputs) Proportional, Integral and Derivative adjustment Programmable for activation/deactivation via LogicsManager External and internal set points can be used
- Usable for water heat cycle control, dual-fuel control, room temperature control
49
only P2
3rd Party Accessories
Accessories easYgen-3000/P2
CANopen bus coupler
IL CAN BK-TC-PAC (#2718701) [max 3 possible]
Analog inputs
IB IL AI 2/SF-PAC (#2861302) 2x analog (0-20 mA, 4-20 mA, 20 mA, 0-10 V, 10 V) IB IL TEMP 2 UTH-PAC (#2861386) 2x thermocouples
IB IL TEMP 2 RTD-PAC (#2861328) 2x RTDs, resistive senders
Analog outputs
IB IL AO 2/SF-PAC (#2863083) 2x analog outputs (0-20 mA, 4-20 mA, 0-10 V)
Phoenix order # numbers in brackets
50
only P2
3rd Party Accessories
Accessories easYgen-3000/P2
J1939 Analog inputs
TC 4 (#AXTC4) 4x thermocouples
TC 20(#TC20) 20x thermocouples
Analog input 10 (#AX030100) free configurable, for advanced J1939 users only
Axiomatic order # numbers in brackets
51
Accessories
Accessories easYgen-3000 all types
IKD 1 Digital Expansion Card [P/N 8440-1041] Terminal Strip Kit Plug Set [P/N 8923-1314]
52
3rd Party Accessories
Accessories easYgen-3000 all types
CANopen bus coupler
IL CAN BK-TC-PAC (#2718701) [max 3 possible]
Discrete inputs / outputs
IB IL 24/230 DOR4/W (#2836421) 4x discrete output, PDT (5-253V, 3 A) IB IL 24 DO2-2A-PAC (#2861263) 2x discrete output, (24V, 2A)
Supports IB IL 24 DO 8; IB IL 24 DO 16 and IB IL 24 DO 32 types
IB IL24 DI 2-PAC (#2861221) 2x discrete input (24V) Supports IB IL24 DI 4; IB IL24 DI 8; IB IL24 DI 16 and IB IL24 DI 32 types
Phoenix order # numbers in brackets
53
Product Documentation
Product Specification
English [P/N 37258] / German [P/N GR37258] / Chinese [P/N CH37258] / Portuguese [P/N PT37258]
Product Presentation
[P/N 37397]
Manual
Installation Manual - [P/N 37223] Configuration Manual - [P/N 37224] Operation Manual - [P/N 37225] Interface Manual - [P/N 37383] Application Manual - [P/N 37226]
P2
Installation Manual - [P/N 37414] Configuration Manual - [P/N 37515] Operation Manual - [P/N 37416] Interface Manual - [P/N 37418] Application Manual - [P/N 37417]
54
[Link]/power/[Link]
Thank you for your attention
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and applications.